173 Advances in Natural and Applied Sciences, 6(2): 173-184, 2012 ISSN 1995-0772

This is a refereed journal and all articles are professionally screened and reviewed

ORIGINAL ARTICLE

Premium Power Park: A Review of the Concepts, Definitions and Applications


Masoud Farhoodnea, Azah Mohamed, Hussain Shareef, Ramizi Mohamed
Department of Electrical, Electronic and Systems Engineering, University Kebangsaan Malaysia Masoud Farhoodnea, Azah Mohamed, Hussain Shareef, Ramizi Mohamed: Premium Power Park: A Review of the Concepts, Definitions and Applications ABSTRACT With the deregulation of the energy market, the quality of the delivered power becomes an important issue for utilities and customers. The delivered power must be within acceptable range for most residential and commercial customers. However, disturbances tend to occur in power systems in which for example, short duration disturbances can be quite destructive to sensitive customers especially for those with automated process lines. In addition to the quality of power, the lack of reliability and availability of electricity supply will also affect the sensitive customers. To overcome issues related to quality, reliability and availability of electric power, many electric utilities are offering premium power to customers who are sensitive to power fluctuations by implementing premium power parks. This concept requires the integration of utilitys systems with several custom power devices that have been previously used as stand-alone devices. This paper presents the concept of premium power park, the custom power devices applied in the park and the experimental premium power parks that have been implemented. Key words: premium power; premium power park; custom power; power quality. Introduction Electrical supply has been designed to operate under constant magnitude and frequency of sinusoidal voltage waveform and any deviation from these predesigned magnitude and frequency can cause power quality problems and resultantly failure of equipment on the customer side (Dugan et al. 2003). Among the power quality disturbances, voltage sag and harmonic distortion are the most important disturbances which affect many customers in the distribution systems. For example, voltage sags down to 80% of nominal voltage with a few tens of millisecond duration can cause interruption in processing plants, resulting in hours of downtime and lots of turnover losses (Bollen 1995; Arnold 2001; Madtharad et al. 2007; Farhoodnea et al. 2010). A study in UK has estimated that the average cost of financial loss for a 24 hour disruption for industrial customers during peak-time operation is approximately 16300 (Kariuki et al. 1996). Another study in South Africa estimates that 891 minutes of time lost in 1996 due to voltage sags cause around $2 million turnover loss for that year (Long et al. 1998). In 2001, Electric Power Research Institute claimed that short-duration power disturbances caused U$119 billion interruption costs per year for the United States (Lineweber et al. 2001). However, as the concern for power quality grows, other related concerns such as reliability and availability of power also increase due to the presence of short-duration power quality events, growing demand, uncertain markets, and changing environmental regulations. Hence, the best solution to protect sensitive loads from power quality events is to feed sensitive customers with a premium grade power (Edinger et al. 2000). The concept of premium power is based on the use of state-of-the-art power electronic based devices called custom power devices and multi utility feeders to provide improved power for sensitive loads (Nara et al. 1999; Nara et al. 2000). This power must have a higher level of quality, reliability and availability (QRA) than the normal power supplied by the utility. The required devices to offer premium power can be installed for a single sensitive customer or to an industrial or commercial park that need enhanced power quality levels than the standard ones (Domijan et al. 2003; Chiumeo et al. 2010). In 1992, the concept of the premium power parks (PPP), also known as custom power park (CPP) was introduced by Westinghouse in order to meet improved QRA to give solution to customer demands and also offering different levels of power quality, which is helpful for customers in selecting the most proper level of power quality for their needs (Lasseter et al. 2000). To improve the overall QRA to customers, utility usually provide two utility side approaches in which the first approach considers a more reliable distribution configuration while the second approach considers the installation of custom power
Corresponding Author: Masoud Farhoodnea, Department of Electrical, Electronic and Systems Engineering, University Kebangsaan Malaysia E-mail: masoud702001@yahoo.com

174
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

devices (Baggini 2008). The mitigation option should be determined based on the economic feasibility according to the required QRA (Arora et al. 1998). Offering premium power services requires establishing a baseline for power quality to clarify the expected level of system performance. The most accurate evaluation of quality of provided power to the customer can be attained through long-term monitoring at the point of common coupling, which is not usually economical and practical. Other alternative and most reasonable method to collect such information is to use statistically valid data from a system-wide benchmarking project or a national survey to determine the baseline for power quality (Mansoor et al. 2000; Higgins et al. 2001; Madtharad et al. 2007). The determined baseline has several advantages for both utility and customer. It can help customers to evaluate the influence of normal power on their production and it can also help them to estimate the benefits and costs of their investment in premium power options. The baseline also allows utilities to estimate the requirements of their customers and provides an economic justification for customers to invest in premium power options (Madtharad et al. 2007). In this paper, the concept of PPP and its related definitions, requirements and applications is presented. In addition, the various PPP configurations and custom power devices that are used to mitigate power quality problems are addressed. This work also presents some examples of experimental PPP implemented in the United States and Taiwan. In addition, the issues and challenges considered for the setting of PPP is discussed. Premium Power Park Configuration: Better quality of power can be obtained by installing custom power devices for a single customer or implementing PPP with different levels of QRA for a group of customers (Chiumeo et al. 2010; Chiumeo et al. 2010). Thus, PPP can be defined as a practical enhancement of existing power system using the state-of-the-art power electronic devices to meet customer requirements. PPP can be considered as a small part of a more global concept called FRIENDS (Flexible, Reliable and Intelligent Electrical eNergy Delivery system) (Nara et al. 1997). The basic components in a PPP are custom power devices that are used to mitigate or compensate specic power quality problems. A combination of these devices can be used in close electrical proximity to simultaneously compensate multiple QRA problems. To provide premium power, reliable distribution configuration and application of custom power devices are considered. More reliable configurations are suitable for reducing the long-duration interruptions as well as to protect the system from short-duration interruptions (Baggini 2008). These configurations include automated loop distribution system (Conti et al. 2000) as shown in Fig. 1, primary or secondary selective schemes as shown in Fig. 2 which implements switching between two utility sources (David et al. 2006; Behnke July 2005) and spot or grid network as shown in Fig. 3. All these system configurations are used to mitigate sustained interruptions but not momentary interruptions and voltage sags (Cutler-Hammer 1999). These system distribution configurations cannot mitigate all types of power quality disturbances and therefore, custom power devices are considered to achieve a complete improvement of QRA.

Fig. 1: A typical automated distribution feeder (Howe et al. 2002)

175
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012
NCB: Normally Closed Breaker NOB: Normally Open Breaker

(A)
BUS 1

BUS 1 Feeder 1 Interlock NCB NOB Feeder 2

Transformer Load

(B)
BUS 1 Feeder 1 Feeder 2 BUS 1

Transformer 1

Transformer 2

Interlock NCB 1 NCB 2

Tie NOB

Load 1

Load 1

Fig. 2: Typical primary and secondary selective distribution systems. (A): A primary selective system. (B): A secondary selective system (David et al. 2006)

Fig. 3: A typical spot network (Cutler-Hammer 1999) Implementation of a PPP requires close cooperation between utilities and customers. Effective strategies in a PPP implement the combined use of state-of-the-art PQ monitoring system, proactive customer support, backup substation, strong transmission network, and independent transmission feeder to provide the backbone for a PPP. A PPP of this type can transform an ordinary commercial and industrial park into an attractive hub for a variety of power sensitive industries (Howe et al. 2002; Blajszczak et al. 2010). Custom Power Devices In A Premium Power Park: Custom power devices are basically power electronic based static controllers used for power quality enhancement on distribution power systems rated between 1 to 38 kV (Domijan Jr et al. 2005; IEEE 2011). The

176
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

custom power devices may be classified as network reconfiguration type and compensating type of devices (Ghosh et al. 2002). 3.1 Network Reconfiguration Type Custom Power Devices: The network reconfiguring types of custom power devices include static current limiter, static circuit breaker, static transfer switches and electronic tap changers devices (Ghosh et al. 2002; Meral 2009). The static current limiter is a series connected device that reduces the fault current level by inserting a series inductance in the faulty path. It consists of a pair of anti-parallel gate turn off thyristor (GTO) switches with snubber circuits and a current limiting inductor as shown in Fig. 4. In the pre-fault state, the GTO switches are closed and when a fault is detected, the switching state is changed to open state within a few microseconds and the fault current flows through the current limiting inductor (Gmez et al. 2009).

L R1 Sw1 C1

Source
Sw2 R2 C2

Load

Fig. 4: Basic configuration of a static current limiter (Ghosh et al. 2002) A static circuit breaker is a GTO based series connected devices that breaks a faulted circuit much faster than a mechanical circuit breaker which is used for ultra-rapid static protection (Cali et al. 1998). The basic structure of a static circuit breaker as shown in Fig. 5 is almost similar to the static current limiter excluding the limiting inductor, L which is placed in series with the thyristor switches. In a normal condition, GTOs are in the on state and act as normal current carrying elements. Once a fault is detected, the GTO switches are switched off and the thyristor pair is switched on. These changes in switching states will force the fault current to pass through the limiting inductor to protect GTOs from the surge current (Pollard 1973; Flurscheim 1982; Ghosh et al. 2002).

Fig. 5: Basic configuration of a static circuit breaker (Ghosh et al. 2002) The static transfer switches (STS) are connected in the bus tie position and contain two pairs of anti-parallel thyristors as shown in Fig. 6 to allow fast transfer of power from the faulty feeder to an alternative healthy feeder within a time scale of milliseconds (Schwartzenberg et al. 1995; Sannino 2001). The STS are effective devices to protect sensitive loads against power quality disturbances especially for upstream voltage sags and swells (Anaya-Lara et al. 2002). To ensure a rapid transfer between a faulty feeder and an alternative healthy feeder , a make-before-break or break-before-make switching strategy is implemented in the STS controller circuit to reduce the negative switching impacts on the loads (Ghosh et al. 2004).

177
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Fig. 6: Basic configuration of static transfer switches (Bertuzzi et al. 2007) The basic diagram of an electronic tap changer (ETC) as shown in Fig. 7 contains a set of anti-parallel thyristor switches which are mounted on a particular transformer in order to rapidly change its turns ratio according to changes in the input voltage. The rating of an ETC essentially should be the same as the full rating of loads, because the ETC has to feed the entire load during power quality events (Larsson et al. 1997; Meyer et al. 1999). The ETC should be able to recover the output even for severe voltage sags with a time delay of a few milliseconds.

Fig. 7: Basic configuration of an electronic tap changer (Bongiorno 2007) 3.2 Compensating Type Custom Power Devices: The most common compensating type of custom power devices include the distribution static compensator (D-STATCOM), active power filter (APF), dynamic voltage restorer (DVR) and unified power quality conditioner (UPQC). These devices have the task of load compensation, power factor and unbalance correction and voltage quality improvement (Strzelecki et al. 2008). The D-STATCOM configuration as shown in Fig. 8 is a shunt connected device which consists of an IGBT based AC/DC converter and a DC voltage source that is connected to the system through a coupling transformer and is mostly used for compensating power quality problems related to current. A D-STATCOM can operate in current or voltage control modes (Ledwich et al. 2002). In the current control mode, D-STATCOM operates as a shunt active power filter and power factor corrector. This operating mode is called the load compensation mode. In the voltage control mode, the DSTATCOM acts as a bus voltage regulator against power quality events (Chacko et al. 2011). The DSTATCOM has several advantages including fast acting, continuous regulation, low harmonic content, damping power system oscillation and improve both static and transient stabilities in power systems (Haque 2001; Chiumeo et al. 2010; Guopeng et al. 2010). In the literature, there are many approaches in designing DSTATCOM controllers. These approaches are generally based on phase angle and modulation index (MI) as control variables. By considering phase angle as a standalone control variable (Moran et al. 1993), the controller cannot provide fast adjustment in the inverter output voltage. To overcome this problem, a new control technique based on xed DC voltage and variable MI was proposed by Schauder et al. (1993). However, the main drawback of this technique is that the harmonic level varies with the variable MI. Therefore, a novel controller scheme based on a steady state MI regulator has been developed to keep harmonics generated by the D-STATCOM as minimum as possible (Ben-Sheng et al. 2007).

178
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Fig. 8: Basic configuration of a D-STATCOM (Chiumeo et al. 2010) Active power filter (APF) is a custom power device that is connected to the power system either in series or shunt configurations. However, the shunt APF is more popular because it can perform both power factor correction and harmonic filtering. The shunt APF mitigate harmonics by generating a current waveform in opposite phase to the harmonic component in the load current, where the series APF is used as a line impedance modifier to increase the line impedance for selected harmonics so as to prevent the injection of selected harmonic currents into the system. The main advantage of the series APF is its ability to mitigate voltage harmonics and to balance three phase voltages, which are important for voltage sensitive devices (Salam et al. 2007; Yingjie et al. 2008; Turunen 2009). In comparison with passive power filter, APFs are also able to eliminate harmonics without posing any negative effects on the fundamental frequency reactive power (Kiran et al. 2011). A dynamic voltage restorer (DVR) is a series compensating device which injects voltage with required magnitude and frequency onto the faulted phase to regulate the bus voltage at the load and also to protect sensitive loads from voltage sag and swell (Bhaskar et al. 2010). It can also protect against voltage with depth up to 40% of nominal voltage within a few milliseconds (Wunderlin et al. 1998). A DVR consists a DC/AC power converter and a DC energy-storage device that is connected in series to a distribution line through a booster transformer (Haque 2001). The basic diagram of a DVR is shown in Fig. 9. To correct the voltage drop, active and/or reactive power injections are needed. A DVR can generate the required reactive power by itself, but to provide the active power, a DC energy storage is needed (Haque 2001). Usually, an optimization technique is applied to minimize the active power injection to increase the life of the energy storage device and duration of compensation (Haque 2001; Bhaskar et al. 2010). As mentioned earlier, both DVR and DSTATCOM are able to compensate voltage sag, but DVR is capable of mitigating voltage sag only on the downstream side, whereas the D-STATCOM can provide the same mitigation for voltage sag on both downstream and upstream sides (Haque 2001).

Fig. 9: Basic configuration of a dynamic voltage restorer (Bhaskar et al. 2010) A unified power quality conditioner (UPQC) consists of a series and a shunt unit with a common DC energy storage capacitor as shown in Fig. 10. The UPQC can provide voltage and current compensation by coordinating the DVR and D-STATCOM so that one level power quality can be supplied to end users (Brenna et al. 2009). Thus, UPQC can perform shunt and series compensation at the same time and mitigate almost all power quality problems (Fujita et al. 1998; Vilathgamuwa et al. 1998). Due to the long distance between the locations of DVR and D-STATCOM, a coordination system which needs costly signal processing and communication systems is required.

179
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Fig. 10: Basic configuration of a unified power quality conditioner (Hojo et al. 2008) Experimental Premium Power Park: The first PPP plan was designed and implemented to supply customers with high quality power in the Delaware Industrial Park in Delaware, Ohio in 1999 by the American Electric Power. The project was implemented in three phases; developing an application methodology, simulation and implementation, and monitoring and performance evaluation (Domijan et al. 2000; Domijan et al. 2005). As shown in Fig. 11, the Delaware PPP consists of a DVR to protect the system against voltage sags and swells, a STS to monitor and divert power from the main source to an alternative source if a power quality event occurs upstream, and a Static Var Compensator (SVC) to provide fast voltage regulation.

Fig. 11: Delaware PPP basic configuration (Domijan et al. 2005) In April 1999, the Taiwan Power Company started to organize a power quality management and improvement task force which lead to the design and development of the Taiwan Science-Based Power Quality Park in 2002. A lot of effort has been put on network infrastructures including network reconfiguration as well as replacing all overhead power lines with underground cables. To provide enhanced power quality, TPC installed two sets of DVR and several power quality monitoring devices at the park (Tzong-Yih et al. 2003). Other examples of the implemented PPP are such as the University Research Park in Irvine, California and the Domain Multi-Energy Park in Austin, Texas. The integrated solutions in theses PPPs include using the

180
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

combined custom power devices with distributed energy resources to improve QRA (McGranaghan 2007). Other possible configurations implemented in the PPP, are by using combined custom power devices comprising of backup generator, DVR and STS as shown in Fig. 12 (Meral 2009). This configuration can provide three different QRA level to feed conventional, sensitive, and critical loads shown in Fig. 12 as loads LA, L-AA and L-AAA, respectively. This PPP has two incoming feeders which can provide improved grounding and insulation for all load levels. The STS protects all loads against upstream voltage sags and interruptions, while loads L-AA and L-AAA can receive the benefit of a backup generator which can come up to about 5 to 10 seconds in the case of two feeder loss caused by downstream transmission line faults or fault in both the preferred and alternate feeders. Furthermore, load L-AAA which is a critical load can have the advantage of DVR for mitigating downstream voltage sags. However, this configuration has several drawbacks which include inability to provide reactive power injection for power factor improvement and incapability to compensate current harmonics. To further improve the overall performance of the system, an active power filter is installed as shown in Fig. 13 to provide current harmonic compensation and reactive power injection at all load levels (Meral et al. 2009).

Fig. 12: A Premium Power Park using combination of backup generator, DVR and STS (Meral 2009)

Fig. 13: System improvement by installing active power filter (Meral et al. 2009)

181
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Fig. 14 shows another configuration of the PPP using a combination of STS, D-STATCOM and DVR (Chiumeo et al. 2010). This scheme provides three load levels named level A, AA and AA-B. At level A, the STS mitigate upstream interruption and voltage sag. At level AA, the DVR mitigates the negative effects of downstream voltage sag and interruption. The ability of the DVR in voltage sag compensation strongly depends on the DVR design and its coordinated operation with the STS. The D-STATCOM ensures that the loads connected to the A and AA are not affected by the voltage variations caused by the disturbing loads at level AAB. In addition, the D-STATCOM can provide current harmonic compensation for all load levels.

Fig. 14: A Premium Power Park using combination of D-STATCOM, DVR and STS (Chiumeo et al. 2010) Issues And Challenges In Developing Premium Power Park: The issues and challenges in the implementation of PPP can are described as follows: i.For successful implementation of PPP, it is important to integrate and coordinate different custom power devices in close electrical proximity. Uncoordinated operation of custom power devices may inject inrush current caused by series connected devices and resultantly transformer saturation or reverse current flow in the system. In addition, uncoordinated operation may create phase shift that are harmful for thyristor-based power supplies such as DC drives (Middlekauff et al. 1998). ii.Using DG as a backup power supply can increase unexpected short circuit currents depending the on its capacity, penetration, technology, interface and connection point of DG (Zayandehroodi et al. 2010). In addition, DGs can negatively affect system protection coordination which leads to conflict and malfunction of protection devices in PPP at the time of fault occurrence (Zayandehroodi et al. 2009). In addition to DGs, custom power devices can also have a negative effect on the designed protection scheme. For example, for faults occurring downstream of DVR which result in voltage sag, the DVR may wrongly increase the short circuit current at the time of sag compensation(Gharedaghi et al. 2011). iii.The voltage source converter based devices such as DVR and D-STATCOM tend to inject voltage and current harmonics into the system. These produced harmonics are the main cause of resonance problems and overheating of transformers and conductors (Farhoodnea et al. 2011). Hence, it is vital to use a sophisticated modulation scheme and proper filter to mitigate harmonics to acceptable limits (Wunderlin et al. 1998). iv.Network reconfiguration as a power quality mitigation method is a complicated combinatorial, nondifferentiable and constrained optimization problem which is not practical in many cases and may pose a huge financial investment to the utility (Ching-Tzong et al. 2003). v.Selection of PPP location is an important factor that should be considered for its setup and implementation. Many factors have be taken into account such as commercial transportation, environmental quality and regulation, real estate availability and cost, utility costs and electric power QRA (Howe et al. 2002). Conclusion: The concept of premium power and the necessity of creating PPP to enhance the quality, reliability and availability of delivered power to end users are presented in this paper. A review of various PPP configurations and custom power devices such as DVR, STS, D-STATCOM and active power filters which are the main components in a PPP is also described. The experimental PPPs that have been implemented are then addressed. Finally, the issues and challenges related to the development and implementation of PPP are discussed.

182
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

References Anaya-Lara O. and E. Acha, 2002. Modeling and analysis of custom power systems by PSCAD/EMTDC. IEEE Transactions on Power Delivery, 17(1): 266-272. Arnold R., 2001. Solutions to the power quality problem. Power Engineering Journal., 15(2): 65-73. Arora A., K. Chan, T. Jauch, A. Kara and E. Wirth, 1998. Innovative system solutions for power quality enhancement. ABB REV.(3): 4-12. Baggini A.B., 2008. Handbook of power quality. Wiley Online Library. Behnke M., July 2005. Secondary Network Distribution Systems Background and Issues Related to the Interconnection of Distributed Resources. National Renewable Energy Laboratory Ben-Sheng C. and H. Yuan-Yih, 2007. An Analytical Approach to Harmonic Analysis and Controller Design of a STATCOM. IEEE Transactions on Power Delivery, 22(1): 423-432. Bertuzzi G., U.S. Cinti, E. Cevenini and A. Nalbone, 2007. Static transfer switch (STS): Application solutions. Correct use of the STS in systems providing maximum power reliability. 29th International Telecommunications Energy Conference (INTELEC '07), pp: 587-594. Bhaskar M.A., S. Dash, C. Subramani, M.J. Kumar, P. Giresh, et al., 2010. Voltage Quality Improvement Using DVR. International Conference on Recent Trends in Information, Telecommunication and Computing (ITC '10), pp: 378-380. Blajszczak G. and P. Antos, 2010. Power Quality Park - Idea and feasibility study. Electric Power Quality and Supply Reliability Conference (PQ), pp: 17-22. Bollen M.H.J., 1995. Fast assessment methods for voltage sags in distribution systems. IEEE Industry Applications Conference, pp: 2282-2289. Bongiorno M., 2007. On Control of Grid-connected Voltage Source Converters-Mitigation of Voltage Dips and Subsynchronous Resonances. PhD Thesis, Chalmers University of Technology. Brenna M., R. Faranda and E. Tironi, 2009. A New Proposal for Power Quality and Custom Power Improvement: OPEN UPQC. IEEE Transactions on Power Delivery, 24(4): 2107-2116. Cali A., S. Conti, C. Oriti and G. Tina, 1998. Utilisation of static circuit breakers in loop distribution systems for reliability improvement. 8th International Conference on Harmonics And Quality of Power, pp: 982-987. Chacko S. and N. Goel, 2011. Voltage Sag mitigation in Electric Arc Furnace with D-STATCOM. International Electrical Engineering Journal., 2(2): 536-542. Ching-Tzong S. and L. Chu-Sheng, 2003. Network reconfiguration of distribution systems using improved mixed-integer hybrid differential evolution. IEEE Transactions on Power Delivery, 18(3): 1022-1027. Chiumeo R. and C. Gandolfi, 2010. D-STATCOM control system and operation in a configuration of Premium Power Park. 14th International Conference on Harmonics and Quality of Power (ICHQP), pp: 1-7. Chiumeo R. and C. Gandolfi, 2010. Simulations of a possible configuration of Premium Power Park. International Conference on Renewable Energies and Power Quality, (ICREPQ10). Granada (Spain), pp: 1-6. Conti S., N. Messina, G. Tina and P. Nicotra, 2000. Automatic control for loop distribution system reconfiguration: reliability and efficiency improvement. Canadian Conference on Electrical and Computer Engineering, pp: 1152-1156. Cutler-Hammer, 1999. Spot Network Systems. www.eaton.bz. David D. and P.E. Roybal, 2006. Primary and Secondary Electrical Distribution Systems. Critical Facilities Round Table 12th Quarterly Membership Meeting. Eaton Electrical. Domijan A., Jr., A. Montenegro, A.J.F. Keri and K.E. Mattern, 2005. Simulation study of the world's first distributed premium power quality park. IEEE Transactions on Power Delivery, 20(2): 1483-1492. Domijan A., Jr., Z. Song, G.N. Baptista, A. Montenegro, X. Wang, et al., 2000. Power quality monitoring and analysis in a customized power industrial area using the FRIENDS concept. Ninth International Conference on Harmonics and Quality of Power, pp: 379-384. Domijan A., A. Montenegro, A. Keri, K. Mattern, C. Edwards, et al., 2003. Premium Power Park: the next step in Power Quality. Proceedings of the Caribbean Colloquium on Power Quality (CCPQ). Domijan Jr A., A. Montenegro, A.J.F. Keri and K.E. Mattern, 2005. Custom power devices: an interaction study. IEEE Transactions on Power Systems, 20(2): 1111-1118. Dugan R.C., M.F. McGranaghan, S. Santoso and H.W. Beaty, 2003. Electrical Power Systems Quality (2nd Edition). McGraw-Hill. Edinger R. and S. Kaul, 2000. Humankind's detour toward sustainability: past, present, and future of renewable energies and electric power generation. Renewable and Sustainable Energy Reviews, 4(3): 295-313. Farhoodnea M., A. Mohamed and H. Shareef, 2010. Identification of multiple harmonic sources in power systems using independent component analysis and mutual information. International Journal of Engineering Intelligent Systems for Electrical Engineering and Communications., 18(1): 51-63.

183
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Farhoodnea M., A. Mohamed and H. Shareef, 2011. Harmonic Source Localization in Power Systems: Single and Multiple Harmonic Sources, . LAP LAMBERT Academic Publishing. Flurscheim C.H., 1982. Power circuit breaker theory and design Peter Peregrinus Ltd., London. Fujita H. and H. Akagi, 1998. The unified power quality conditioner: the integration of series and shunt-active filters. IEEE Transactions on Power Electronics, 13(2): 315-322. Gharedaghi F., H. Jamali, M. Deysi and A. Khalili, 2011. Voltage Quality Enhancement and Fault Current Limiting with Z-Source based Series Active Filter. Research Journal of Applied Sciences, Engineering and Technology, 3(11): 1246-1252. Ghosh A. and A. Joshi, 2004. The concept and operating principles of a mini custom power park. IEEE Transactions on Power Delivery, 19(4): 1766-1774. Ghosh A. and G. Ledwich, 2002. Custom Power Devices: An Introduction. In: Power Quality Enhancement Using Custom Power Devices. Springer US, pp: 113-136. Ghosh A. and G. Ledwich, 2002. Power quality enhancement using custom power devices. Kluwer Academic Pub. Gmez M., M.. Cmara, E. Jimnez and E. Martnez-Cmara, 2009. Custom power equipment to facilitate the penetration of embedded generation in distribution networks. Electrical Engineering Electronic Journal., 1(1): 1-6. Guopeng Z. and L. Jinjun, 2010. An analysis on the influence of interface inductor to STATCOM system with Phase and Amplitude Control and corresponding design considerations. Twenty-Fifth Annual IEEE Applied Power Electronics Conference and Exposition (APEC), pp: 1633-1639. Haque M.H., 2001. Compensation of distribution system voltage sag by DVR and D-STATCOM. IEEE Porto Power Tech Proceedings, p. 5 pp. Haque M.H., 2001. Voltage Sag Correction by Dynamic Voltage Restorer with Minimum Power Injection. IEEE Power Engineering Review, 21(5): 56-58. Higgins M., A. Mansoor and A. Sundaram, 2001. Understanding premium power grades. Quality and Use of Electricity, 7(2): 19-25. Hojo M. and T. Funabashi, 2008. Unified Power Quality Conditioner for dynamic voltage restoration and fault current limitation. 13th International Conference on Harmonics and Quality of Power (ICHQP '08) pp: 1-5. Howe B., A. Mansoor and D. Dorr, 2002. Premium Power Industrial Park Design. EPRI. Palo Alto, CA. IEEE, 2011. Draft Guide for the Application of Power Electronics for Power Quality Improvement on Distribution Systems Rated 1 kV Through 38 kV. IEEE P1409/D14: 1-87. Kariuki K.K. and R.N. Allan, 1996. Evaluation of reliability worth and value of lost load. IEE ProceedingsGeneration, Transmission and Distribution., 143(2): 171-180. Kiran C.N., S.S. Dash and S.P. Latha, 2011. A Few Aspects of Power Quality Improvement Using Shunt Active Power Filter. International Journal of Scientific & Engineering Research, 2(5): 1-11. Larsson T., R. Innanen and G. Norstrom, 1997. Static electronic tap-changer for fast phase voltage control. IEEE International Electric Machines and Drives Conference Record pp: TC3/4.1-TC3/4.3. Lasseter R. and P. Piagi, 2000. Providing premium power through distributed resources. Proceedings of the 33rd Annual Hawaii International Conference on System Sciences, pp: 1-9. Ledwich G. and A. Ghosh, 2002. A flexible DSTATCOM operating in voltage or current control mode. IEE Proceedings-Generation, Transmission and Distribution, 149(2): 215-224. Lineweber D., S. McNulty and E.P.R. Institute, 2001. The cost of power disturbances to industrial & digital economy companies. EPRI. Long D., D.T. Grobler and J. Hosking, 1998. The Effects of Quality of Suppry on SAPPI's Southern African Mills. First Southern African Power Quality Conference, paper no. 1. Madtharad C., C. Sorndit, S. Premrudeepreechacharn and M. McGranaghan, 2007. PEA's premium power service: Baseline and risk assessment. 9th International Conference on Electrical Power Quality and Utilisation, (EPQU 2007), pp: 1-6. Mansoor A. and A. Sundaram, 2000. Offering premium power services. International Conference on Advances in Power System Control, Operation and Management (APSCOM-00), pp: 162-167. McGranaghan M., 2007. Developing a PQ Technology Park Concept for Poland. EPRI. http://www.pjcee.pl. Meral M.E., 2009. Voltage Quality Enhancement With Custom Power Park. PhD dissertation, University of ukurova Institute of Natural And Applied Science. Meral M.E., A. Teke, K.C. Bayindir and M. Tumay, 2009. Power quality improvement with an extended custom power park. Electric Power Systems Research, 79(11): 1553-1560. Meyer A.S. and J. Van Coller, 1999. Electronic tap changers for use with ultra-light rural distribution lines. IEEE Africon, pp: 909-912. Middlekauff S.W. and E.R. Collins, Jr., 1998. System and customer impact: considerations for series custom power devices. IEEE Transactions on Power Delivery, 13(1): 278-282.

184
Adv. in Nat. Appl. Sci., 6(2): 173-184, 2012

Moran L., P.D. Ziogas and G. Joos, 1993. A solid-state high-performance reactive-power compensator. IEEE Transactions on Industry Applications., 29(5): 969-978. Nara K. and J. Hasegawa, 1997. A new flexible, reliable, and intelligent electrical energy delivery system. Electrical Engineering in Japan., 121(1): 26-34. Nara K. and J. Hasegawa, 1999. Configuration of new power delivery system for reliable power supply. IEEE Power Engineering Society Summer Meeting, pp: 248-253. Nara K., Y. Mishima and J. Hasegawa, 2000. A new type power delivery system for reliable power supplyFRIENDS and its optimal network design. International Conference on Power System Technology (PowerCon), pp: 649-654. Pollard E.M., 1973. STATIC CIRCUIT BREAKER. U. S. patents. United States. General Electric Copmany, 3725742. Salam Z., T.P. Cheng and A. Jusoh, 2007. Review of Active Power Filter Technologies. Journal - The Institution of Engineers., 68(2): 47-53. Sannino A., 2001. Static transfer switch: analysis of switching conditions and actual transfer time. IEEE Power Engineering Society Winter Meeting, pp: 120-125. Schwartzenberg J.W. and R.W. De Doncker, 1995. 15 kV medium voltage static transfer switch. Thirtieth IAS IEEE Conference Record of the Industry Applications, pp: 2515-2520. Strzelecki R. and G. Benysek, 2008. Active Power Quality Controllers. In: Power Electronics in Smart Electrical Energy Networks. Springer London, pp: 229-267. Turunen J., 2009. Series Active Power Filter in Power Conditioning. PhD dissertation, Julkaisu-Tampere University of Technology. Tzong-Yih G., H. Chiung-Yi, L. Ching-Yun and L. Ching-Jung, 2003. Power quality task force of taipower: experiences & results on PQ monitoring and mitigation. Sixth International Conference on Advances in Power System Control, Operation and Management (ASDCOM '03), pp: 41-48. Vilathgamuwa M., Y.H. Zhang and S.S. Choi, 1998. Modelling, analysis and control of unified power quality conditioner. 8th International Conference on Harmonics And Quality of Power, pp: 1035-1040. Wunderlin T., O. Amhof, P. Dahler and H. Guning, 1998. Power supply quality improvement with a dynamic voltage restorer (DVR). International Conference on Energy Management and Power Delivery (EMPD '98), pp: 518-525. Yingjie H., L. Jinjun, T. Jian, W. Zhaoan and Z. Yunping, 2008. Research on control system of DC voltage for active power filters with three-level NPC inverter. Twenty-Third Annual IEEE Applied Power Electronics Conference and Exposition, (APEC '08), pp: 1173-1178. Zayandehroodi H., A. Mohamed, H. Shareef and M. Mohammadjafari, 2009. An Overview of Protection Coordination Methods in Distribution Network with DGs. International Conference, Electrical Energy and Industrial Electronic Systems (EEIES '09), pp: 1-6. Zayandehroodi H., A. Mohamed, H. Shareef and M. Mohammadjafari, 2010. A New Protection Scheme for Distribution Network with Distributed Generations Using Radial Basis Function Neural Network. International Journal of Emerging Electric Power Systems., 11(5): 3.