Testing of Transformer Differential Relay T60(MAKE: GE)

1.0 Make Diagram no. Frequency Rated voltage No of logic Inputs: 2.0 Visual Inspection Item 1 2 3 4 5 6 7 8 9 10 Relay General Data
Transformer Differential Relay

Page 1 of 29 Date: 23/3/2010,Revision: 0

Function

Serial No. Model No. Aux. Voltage Firmware no. Rated current: No of outputs:

ABHC09000583
T60-G01-HCH-F8M-H6P-M8R-P6P-UXXWXX

GE 386A5686 50-60 120 8

125 VDC V3.01 1A&5A 8

Description

S/L. No. on Module, Cover and Case are identical Inspect for any physical damage or defects. Verify connections as per approved drawings. Check that serial no. of relay matching with serial no. of display. Relay case connected to local earth bar Tightness of contact of the relay and CT shorting terminal makes good contact when relay is withdrawn Connection on Relay terminals are good Ferrules are according to the drawings Test and settings switches operate properly CT shorting function checked.

Checked OK OK OK OK OK OK OK OK OK OK

3.0 Electrical Functional Test. Test switch / Test Block CT shorting contacts proved Relay CT shorting contacts proved 4.0 Secondary Injection test. 4.1. Relay Power Measurment at Rated Voltage(Burden Test) Terminal B5b-B6a Voltage (V) 110 Current (mA) Quiescent 178.5 Output Operated 184.4 Burden (W) Quiescent 19.635 Output Operated 20.284 Nominal Burden (W) Quiescent W < 20 Max W < 50

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 2 of 29 Date: 23/3/2010,Revision: 0

4.2. Testing Of LEDs First Column( Status) LED No. LED-1 LED-2 LED-3 LED-4 LED-5 LED-6 LED-7 LED-8 LED-9 LED-10 LED-11 LED-12 LED-13 LED-14 Assigned Function IN SERVICE TROUBLE TEST MODE TRIP ALARM PICKUP VOLTAGE CURRENT FREQUENCY OTHER PHASE A PHASE B PHASE C NUETRAL GROOUND Result s OK OK OK OK OK OK OK OK OK OK OK OK OK OK Second Column (Setting in use) Results LED No. Assigned Function LED-1 LED-2 LED-3 LED-4 LED-5 LED-6 LED-7 LED-8 LED-9 LED-10 LED-11 LED-12
XFMR INST DIFF OP XFMR PCNT DIFF OP GROUND TOC1 OP
VOLTS PER HERTZ 1 OP

off PHASE IOC1 OP PHASE TOC1 OP Spare Spare Spare Spare Spare

OK OK OK OK OK OK OK

4.3. Testing Of Out Put Relays Output Relay No. Critical H1 H2 H3 H4 H5 H6 P1 P2 P3 P4 P5 Output Contact No. B1b-B1a (N.O) / B2b-B1a(NC) H1c-H1b(NO) H2c-H2b(NO) H3c-H3b(NO) H4c-H4b(NO) H5c-H5b(NO) H6c-H6b(NO) P1c-P1b(NO) P2c-P2b(NO) P3c-P3b(NO) P4c-P4b(NO) P5c-P5b(NO) Subcontract/Tested by Name: Signature: Date: Output relay status
B1b-B1a (N.O) B2b-B1a (N.c )

Contact Operation check


B1b-B1a (c) B2b-B1a (o )

Actual Assignment of Relays


Power Supply on

Contact Resistan ce()


C = 0.3

Remarks

For Test Purpose FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE

N/O N/O N/O N/O N/O N/O N/O N/O N/O N/O N/O

CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE

ANY TRIP INPUT (H7C) INPUT (H8A) INPUT (H8C) TOC1-PH IOC1-PH INPUT (P7A) INPUT (P7C) INPUT (P8A) INPUT (P8C) TOC1-N

0.7 0.6 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 3 of 29 Date: 23/3/2010,Revision: 0

N/O CLOSE IOC1-N 0.6 FOR TEST PURPOSE P6 P6c-P6b(NO) 4.4. Testing Of Binary Inputs (Energize only one OPTO INPUT at a time with relay rated OPTO input voltage CAUTION!! -Check RATED OPTO INPUT VOLTAGE before apply voltage to OPTO Input terminal) OPTO Input No. H7 H7 H8 H8 P7 P7 P8 P8 V DC Applied Terminal No. H7a(+)-H7b(-) H7c(+)-H7b(-) H8a(+)-H7b(-) H8c(+)-H7b(-) P7a(+)-P7b(-) P7c(+)-P7b(-) P8a(+)-P7b(-) P8c(+)-P7b(-) Minimum Pickup Voltage(V) 83.7 83.9 84.5 84.6 83.9 84.0 84.4 84.6 Status of OPTO INPUT CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE Function assigned for OPTO INPUT OUTPUT (H1) OUTPUT (H2) OUTPUT (H3) OUTPUT (H4) OUTPUT (P1) OUTPUT (P2) OUTPUT (P3) OUTPUT (P4) Remarks
FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE FOR TEST PURPOSE

4.5. Metering Function(Meter Accuracy Test) 4.5.1. Phase Current Accuracy Test Relay Setting CT F1 (SRC 2 ) GSU L.V Phase CT primary: 6000A Phase CT secondary: 1A Test Result Injected Current Expected Current (A) (A) 0.2 0.25 0.3 0.5 0.75 1200 1500 1800 3000 4500

Measured Current (A) Phase A Phase B Phase C 1191 1492 1792 2992 4488 5996 1192 1492 1795 2992 4488 5988 1192 1494 1795 2992 4488 5988 4.5.2.Phas e

1 6000 Current Accuracy Test Relay Setting CT M5 (SRC 1) Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Phase CT primary: 600A Phase CT secondary: 1A Test Result Injected Current (A) 0.2 0.25 0.3 0.5 0.75 1 Accuracy Test Relay Setting CT M5 (SRC1 ) Phase CT primary: 600A Phase CT secondary: 1A Test Result Injected Current (A) 0.2 0.25 0.3 0.5 0.75 1 Accuracy Test Relay Setting VT F5 Phase VT Connection Phase VT Secondary Phase VT Ratio Test Results Test Values (V) Expected Current (A) 120 150 180 300 450 600

Page 4 of 29 Date: 23/3/2010,Revision: 0

Measured Current (A) Phase A Phase B Phase C 119.158 149.141 179.172 299.215 449.431 599.311 119.124 149.293 179.114 299.473 448.635 598.962 119.176 149.116 179.253 299.041 449.321 599.013 4.5.3.Ground Current

Expected Current (A) 120 150 180 300 450 600

Measured Current (A) 119.403 149.290 179.171 299.230 449.864 599.668 4.5.4.Phase Voltage

(SRC 1) Star 69.3 V 120: 1 Expected Voltage (KV) Arabian BEMCO Measured Voltage (kV) Vab Vbc Vca SEC-COA

Applied Voltage (V)

Subcontract/Tested by Name: Signature: Date:

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 5 of 29 Date: 23/3/2010,Revision: 0


11.718 12.418 13.798 15.170 15.878 11.717 12.416 13.795 15.171 15.878 11.711 12.414 13.794 15.168 15.875

66.4 15% 66.4 10% 66.4 66.4 + 10% 66.4 + 15%

56.4 59.76 66.4 73 76.4

11.723 12.421 13.8 15.17 15.88

4.6. Testing of Grouped Element 4.6.1. Transformer Differential Setting / Grouped Elements / Group 1 / Transformer/percent differential TRANSFORMER DATA: 110 MVA, 380/13.8 kV, CT (HV) = 600:1, CT (LV) = 6000:1, Yn/d1d1 OPERATING CRITERIA: The differential element operates if the differential current (Id) exceeds the characteristic defined by the relay settings for restraint current magnitude (Ir) The differential current Id is the vector sum of the compensated currents, and Ir is the largest compensated current. Compensation refers to vector and magnitude corrections applied to the currents from the HV and LV transformer sides. The tests verify the operation and no-operation response for points from all regions of the percentage differential characteristic. These tests are: Test for zero differential current Minimum Pickup Slope 1 The region between Slope 1 and Slope 2 Slope 2 RELAY CONFIGURATION: NOTE: WARNING: APPLICATION OF EXCESSIVE CURRENT (> 3 x In) FOR EXTENTED PERIODS WILL CAUSE DAMAGE TO THE RELAY!

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


CT M5 600 1 600 1 CT M1 X X X X

Page 6 of 29 Date: 23/3/2010,Revision: 0

AC INPUTS SETTING Phase CT Primary Phase CT Secondary Ground CT Primary Ground CT Secondary

CT F1 6000 1 X X

SOURCE SETTING Name Phase CT Ground CT Phase VT

SOURCE 1 SOURCE 2

SRC1 M5 M5 F5

SRC2 F1 X X

WINDING I SETTINGS VALUE Source Rated MVA Nom Ph-Ph Voltage Connection Grounding Angle WRT Resistance 3Ph Name: Signature: Date: SRC 1 110MVA 380 kV WYE within zone

WINDING 2 SETTINGS VALUE Source Rated MVA Nom Ph-Ph Voltage Connection Grounding SRC2 110MVA 13.8 kV DELTA Not Within zone 0 Arabian BEMCO 10.000 ohms Test setting

-30 Angle WRT Subcontract/Tested by 10.000 ohms Resistance 3Ph

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


PERCENT DIFF VALUE Minimum PKP Slope 1 Breakpoint 1 Breakpoint 2 Slope 2 0.2 pu 25% 2 pu 6 pu 80%

Page 7 of 29 Date: 23/3/2010,Revision: 0

DIFFERENTIAL CHARACTERISTIC TEST BETWEEN W1, W2 Test For Zero Differential Current (Balanced Condition ) Phase A B C Injected Current (A) I(w1) I(w2) 0.126 <180 0.2 <0 0 <0 0 <0 0 <0 0.2 <180 Displayed Current (A) Id Ir 0 0.199 0 0 0 0.199

Phase A B C Phase A B C

Injected Current (A) I(w1) I(w2) 0.943 <180 1.5 <0 0 <0 0 <0 0 <0 1.5 <180 Injected Current (A) I(w1) I(w2) 4.402 <180 7 <0 0 <0 0 <0 0 <0 7 <180

Displayed Current (A) Id Ir 0 1.497 0 0 0 1.497 Displayed Current (A) Id Ir 6.991 0 0 0 0 6.991

4.6.1.1.

Minimum Pickup Test Arabian BEMCO SEC-COA

Subcontract/Tested by Name: Signature: Date:

Testing of Transformer Differential Relay T60(MAKE: GE)


Stable Phase A B C Operate Phase A B C 4.6.1.2. Stable Phase A B C Operate Phase A B C 4.6.1.3. Stable Phase A B C Operate Phase A B C Injected Current (A) I(w1) I(w2) 0.709 <180 1.5 <0 0 <0 0 <0 0 <0 1.5 <180 Injected Current (A) I(w1) I(w2) 0.708 <180 1.5 <0 0 <0 0 <0 0 <0 1.5 <180 Slop 2 Test Injected Current (A) I(w1) I(w2) 0.884 <180 7 <0 0 <0 0 <0 0 <0 7 <180 Injected Current (A) I(w1) I(w2) 0.883 <0 7 <0 0 <0 0 <0 0 <0 7 <180 Injected Current (A) I(w1) I(w2) 0.252 <180 0.2 <0 0 <0 0 <0 0 <0 0.2 <180 Slop 1 Test Injected Current (A) I(w1) I(w2) 0.251<180 0.2 <0 0 <0 0 <0 0 <0 0.2 <180

Page 8 of 29 Date: 23/3/2010,Revision: 0

Displayed Current (A) Id Ir 0.199 0.397 0 0 0.199 0.397 Displayed Current (A) Id Ir 0.2 0.399 0 0 0.2 0.399

Displayed Current (A) Id Ir 0.371 1.496 0 0 0.371 1.496 Displayed Current (A) Id Ir 0.373 1.495 0 0 0.373 1.497

Displayed Current (A) Id Ir 5.584 6.987 0 0 5.589 6.991 Displayed Current (A) Id Ir 5.586 6.987 0 0 5.590 6.991

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


4.6.1.4. Instantaneous Differential Setting: Pickup 3.5 pu Injected Current (A) Phase I(w1) I(w2) A 2.518 <180 0.5 <0 B 0 <0 0<0 C 0 <0 0.5 <180 4.6.1.5. Harmonic Testing 4.6.1.5.1. 2nd Harmonic Setting = 20% Phase Injection W1 Current 1 1 1 B 1 1 C 1 W1 Harm.% 18 20 18 20 18 20 W2 Current 0 0 0 0 0 0

Page 9 of 29 Date: 23/3/2010,Revision: 0

Displayed Current (A) Id Ir 3.497 3.995 0 0 3.496 3.995

Time 11.7 ms

Block/ Op. Operate Block Operate Block Operate Block

4.6.1.5.2. 5th Harmonic Testing 5th Harmonic Setting = 10% 1. Connect the relay test set to inject current into the Winding 1 Phase A CT input. 2. Inject currents into the relay as shown in the table below until the biased differential element picks up. 3. Confirm that only the percent differential element has operated. 4. Increase the harmonic content until the element drops out. Record this value as the Inrush Inhibit Level Pickup. 5. Gradually decrease the harmonic content level until the element picks up. Record this value as the Inrush Inhibit Level Dropout. 6. Switch off the current. 7. Repeat steps 1 through 6 for phases B and C. 8. Repeat steps 1 through 7 for Winding 2 and Windings 3.

phase

Injection

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 10 of 29 Date: 23/3/2010,Revision: 0


Block/ Op. Operate Block Operate Block Operate Block

W1 Current A 1 1 1 B 1 1 C 1

W1 Harm.% 9.7 9.8 9.6 9.8 9.6 9.7

W2 Current 0 0 0 0 0 0

4.6.2. Phase Current ( Winding -1 SRC-1) Setting / Inputs Outputs / Contact Outputs PARAMETER H1 Contact Output 1 Name Con Op 1 Operate PHASE TOC1 OP (Timing test) 4.6.2.1. Phase Time Over Current Test TOC 1 4.6.2.1.1. Pick up drop out test Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 1pu Current (A) Pick- up value Drop out value Calculated pick-up R 1.002 0.970 1 Y 1.003 0.973 1 B 1.002 0.972 1 4.6.2.1.2. Time Characteristic test IEC Curve A Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC ` PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 1pu Curve IEC Curve A TD Multiplier 0.40 Phase Subcontract/Tested by Name: Signature: Date: Arabian BEMCO

% Error 0.2 0.3 0.2

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Results 1.5 In=1.5A Phase Expected Time(s) 6.878 6.878 6.878 Measured Time(s) 6.95 6.97 6.95 2 In=2 A Expected Time(s) 4.012 4.012 4.012 Measured Time(s) 4.05 4.05 4.05

Page 11 of 29 Date: 23/3/2010,Revision: 0

3 In=3 A Expected Time(s) 2.521 2.521 2.521 Measured Time(s) 2.55 2.55 2.55

R Y B

4.6.2.1.3. Time Characteristic test IEC Curve B Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 1pu Curve IEC Curve B TD Multiplier 0.4 Results 1.5 In=1.5A Phase R Y B Expected Time(s) 10.8 10.8 10.8 Measured Time(s) 10.90 10.94 10.92 2 In=2 A Expected Time(s) 5.4 5.4 5.4 Measured Time(s) 5.44 5.44 5.45 3 In=3 A Expected Time(s) 2.7 2.7 2.7 Measured Time(s) 2.73 2.73 2.74

4.6.2.1.4. Characteristic test IEC Curve C Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 1pu Curve IEC Curve C TD Multiplier 0.40

Results 1.5 In=1.5A Subcontract/Tested by Name: Signature: Date: 2 In=2 A Arabian BEMCO 3 In=3 A SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


PHASE R Y B Expected Time(s) 25.6 25.6 25.6 Measured Time(s) 25.85 25.96 25.88 Expected Time(s) 10.667 10.667 10.667 Measured Time(s) 10.73 10.75 10.73

Page 12 of 29 Date: 23/3/2010,Revision: 0


Expected Time(s) 4 4 4 Measured Time(s) 4.04 4.05 4.04

4.6.2.1.5. Time Characteristic test IEC short time Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable 1.5 In=1.5A 2 In=2 A Signal Source SRC 1 (SRC 1) PHASE Pickup 1pu Expected Measured Expected Measured Curve IEC short time Time(s) Time(s) Time(s) Time(s) TD Multiplier 0.40 R 1.223 1.26 0.711 0.736 Y B 1.223 1.223 1.25 1.26 0.711 0.711 0.733 0.740

Results 3 In=3 A Expected Time(s) 0.445 0.445 0.445 Measured Time(s) 0.469 0.467 0.468

4.6.2.2. Phase Instantaneous Over Current Test IOC 1 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase IOC PARAMETER PHASE IOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 5 pu Delay 0.0sec Results Phase R Y B 4.6.3. Pick-up Current (A) 5.008 5.010 5.009 Time setting Inst. Inst. Inst. Measured time(ms) 40.8 35.3 35.3

Phase Current ( SRC-2) 4.6.3.1. Phase Time Over Current Test TOC 1 4.6.3.1.1. Pick up drop out test Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Function Signal Source Pickup Results Phase Enable SRC2 (SRC 2) 1pu

Page 13 of 29 Date: 23/3/2010,Revision: 0

Current (A) Pick- up value Drop out value Calculated pick-up R 1.003 0.972 1 Y 1.003 0.972 1 B 1.002 0.972 1 4.6.3.1.2. Time Characteristic test IEC Curve A Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC ` PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 1pu Curve IEC Curve A TD Multiplier 0.40 Results 1.5 In=1.5A Phase R Y B Expected Time(s) 6.878 6.878 6.878 Measured Time(s) 6.96 6.91 6.96 2 In=2 A Expected Time(s) 4.04 4.04 4.04 Measured Time(s) 4.05 4.05 4.05

% Error 0.3 0.3 0.2

3 In=3 A Expected Time(s) 2.521 2.521 2.521 Measured Time(s) 2.55 2.56 2.55

4.6.3.1.3. Time Characteristic test IEC Curve B Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 1pu Curve IEC Curve B TD Multiplier 0.4 Results 1.5 In=1.5A Phase Expected Time(s) Measured Time(s) 2 In=2 A Expected Time(s) Measured Time(s) 3 In=3 A Expected Time(s) Measured Time(s) SEC-COA

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 14 of 29 Date: 23/3/2010,Revision: 0


2.7 2.7 2.7 2.74 2.73 2.73

R Y B

10.8 10.8 10.8

10.94 10.84 10.94

5.4 5.4 5.4

5.45 5.45 5.43

4.6.3.1.4. Time Characteristic test IEC Curve C Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 1pu Curve IEC Curve C TD Multiplier 0.40 Results PHASE R Y B 1.5 In=1.5A Expected Measured Time(s) Time(s) 25.6 25.6 25.6 25.94 25.95 25.96 2 In=2 A Expected Measured Time(s) Time(s) 10.667 10.667 10.667 10.73 10.75 10.73 3 In=3 A Expected Measured Time(s) Time(s) 4 4 4 4.06 4.05 4.05

4.6.3.1.5. Time Characteristic test IEC short time Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase TOC PARAMETER PHASE TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 1pu Curve IEC short time TD Multiplier 0.40

Results 1.5 In=1.5A PHASE R Expected Time(s) 1.223 Measured Time(s) 1.27 2 In=2 A Expected Time(s) 0.711 Measured Time(s) 0.733 3 In=3 A Expected Time(s) 0.445 Measured Time(s) 0.470 SEC-COA

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 15 of 29 Date: 23/3/2010,Revision: 0


0.445 0.445 0.467 0.465

Y B

1.223 1.223

1.24 1.26

0.711 0.711

0.734 0.739

4.6.3.2. Phase Instantaneous Over Current Test IOC 1 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Phase Current / Phase IOC 1 PARAMETER PHASE IOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 5 pu Delay 0.0sec Results Phase R Y B Pick-up Current (A) 5.013 5.012 5.011 Time setting Inst. Inst. Inst. Measured time(ms) 39.1 37.3 38.4

4.6.4. Neutral Current Setting / Inputs Outputs / Contact Outputs PARAMETER H1 Contact Output 1 Name Con Op 1 Operate Neutral TOC1 OP 4.6.5.

(Timing test)

Neutral Time Over Current Test TOC 1SRC-1

4.6.5.1. Pick up drop out test Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Phase B-N Pick- up value 0.101 Current (A) Drop out value 0.098 Calculated pick-up 0.1 % Error 1

4.6.5.1.1. Time Characteristic test IEC Curve A Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 `PARAMETER NEUTRAL TOC 1 Function Enable Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Signal Source Pickup Curve TD Multiplier Results 1.5 In=0.15A Phase Expected Time(s) 6.878 Measured Time(s) 6.89 SRC 1 (SRC 1) 0.1pu IEC Curve A 0.40 2 In=0.2 A Expected Time(s) 4.012 Measured Time(s) 4.03

Page 16 of 29 Date: 23/3/2010,Revision: 0

3 In=0.3 A Expected Time(s) 2.521 Measured Time(s) 2.55

B-N

4.6.5.1.2. Time Characteristic test IEC Curve B Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Curve IEC Curve B TD Multiplier 0.4 Results 1.5 In=0.15A Phase Expected Time(s) 10.8 Measured Time(s) 10.79 2 In=0.2 A Expected Time(s) 5.4 Measured Time(s) 5.41 3 In=0.3 A Expected Time(s) 2.7 Measured Time(s) 2.72

B-N

4.6.5.1.3. Time Characteristic test IEC Curve C Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Curve IEC Curve C TD Multiplier 0.40 Results 1.5 In=0.15A PHASE Expected Time(s) Measured Time(s) 2 In=0.2 A Expected Time(s) Measured Time(s) 3 In=0.3 A Expected Time(s) Measured Time(s) SEC-COA

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 17 of 29 Date: 23/3/2010,Revision: 0


4 4.00

B-N

25.6

25.51

10.667

10.63

4.6.5.1.4. Time Characteristic test IEC short time Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Curve IEC short time TD Multiplier 0.40 Results 1.5 In=0.15A PHASE B-Neutral Expected Time(s) 1.223 Measured Time(s) 1.26 2 In=0.2 A Expected Time(s) 0.711 Measured Time(s) 0.745 3 In=0.3 A Expected Time(s) 0.445 Measured Time(s) 0.474

4.6.5.2. Neutral Instantaneous Over Current Test IOC 1 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL IOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.5 pu Delay 0.0sec Results Phase Pick-up Current (A) Time setting B-Neutral 0.501 Inst.

Measured time(ms) 37.3

Neutral Time Over Current Test TOC 1SRC-2 4.6.5.2.1. Pick up drop out test Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Function Signal Source Pickup Results Phase BNeutral Pick- up value 0.101 Current (A) Drop out value 0.098 Enable SRC 2 (SRC 2) 0.1pu

Page 18 of 29 Date: 23/3/2010,Revision: 0

Calculated pick-up 0.1

% Error 1

4.6.5.2.2. Time Characteristic test IEC Curve A Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Results Signal Source SRC 2 (SRC 2) 1.5 In=0.15A 2 In=0.2 A Pickup 0.1pu 3 In=0.3 A Phase Curve IEC Curve A TD Multiplier Expected Measured Expected 0.40 Measured Expected Measured Time(s) Time(s) Time(s) Time(s) Time(s) Time(s) B6.878 6.86 4.012 4.03 2.521 2.54 Neutral 4.6.5.2.3. Time Characteristic test IEC Curve B Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 0.1pu Curve IEC Curve B TD Multiplier 0.4 Results 1.5 In=0.15A Phase BNeutral Expected Time(s) 10.8 Measured Time(s) 10.76 2 In=0.2 A Expected Time(s) 5.4 Measured Time(s) 5.39 3 In=0.3 A Expected Time(s) 2.7 Measured Time(s) 2.74

4.6.5.2.4. Time Characteristic test IEC Curve C Setting (Pickup and Time) Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 19 of 29 Date: 23/3/2010,Revision: 0

Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 0.1pu Curve IEC Curve C TD Multiplier 0.40 Results 1.5 In=0.15A PHASE B-Neutral Expected Time(s) 25.6 Measured Time(s) 25.41 2 In=0.2 A Expected Time(s) 10.667 Measured Time(s) 10.61 3 In=0.3 A Expected Time(s) 4 Measured Time(s) 3.99

4.6.5.2.5. Time Characteristic test IEC short time Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL TOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 0.1pu Curve IEC short time TD Multiplier 0.40 Results 1.5 In=0.15A PHASE B-Neutral Expected Time(s) 1.223 Measured Time(s) 1.25 2 In=0.2 A Expected Time(s) 0.711 Measured Time(s) 0.737 3 In=0.3 A Expected Time(s) 0.445 Measured Time(s) 0.475

4.6.5.2.6. Neutral Instantaneous Over Current Test IOC 1 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Neutral Current / Neutral TOC1 PARAMETER NEUTRAL IOC 1 Function Enable Signal Source SRC 2 (SRC 2) Pickup 0.5 pu Delay 0.0sec Results Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Phase B-Neutral Pick-up Current (A) 0.501 Time setting Inst.

Page 20 of 29 Date: 23/3/2010,Revision: 0


Measured time(ms) 37.1

4.6.6. Ground Current Setting / Inputs Outputs / Contact Outputs PARAMETER H1 Contact Output 1 Name Con Op 1 Operate Ground TOC1 OP

(Timing test)

4.6.6.1. Ground Time Over Current Test TOC 1SRC-1 4.6.6.1.1. Pick up drop out test Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground TOC1 PARAMETER Ground TOC 1 Function Enable Signal Source SRC1(SRC1) Pickup 0.1pu Phase G Pick- up value 0.101 Current (A) Drop out value 0.098 Calculated pick-up 0.1 % Error 1

4.6.6.1.2. Time Characteristic test IEC Curve A Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground TOC1 PARAMETER GROUND TOC 1 Function Enable Signal Source SRC2 (SRC2) Pickup 0.1pu Curve IEC Curve A TD Multiplier 0.40 Results Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 21 of 29 Date: 23/3/2010,Revision: 0

1.5 In=0.15A Phase Expected Time(s) 6.878 Measured Time(s) 7.05

2 In=0.2 A Expected Time(s) 4.012 Measured Time(s) 4.08

3 In=0.3 A Expected Time(s) 2.521 Measured Time(s) 2.56

4.6.6.1.3. Time Characteristic test IEC Curve B Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground TOC1 PARAMETER Ground TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Curve IEC Curve B TD Multiplier 0.4 Results 1.5 In=0.15A Phase Expected Time(s) 10.8 Measured Time(s) 11.09 2 In=0.2 A Expected Time(s) 5.4 Measured Time(s) 5.50 3 In=0.3 A Expected Time(s) 2.7 Measured Time(s) 2.75

4.6.6.1.4. Time Characteristic test IEC Curve C Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground TOC1 PARAMETER GROUND TOC 1 Function Enable Signal Source SRC2 (SRC 2) Pickup 0.1pu Curve IEC Curve C TD Multiplier 0.40 Results Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 22 of 29 Date: 23/3/2010,Revision: 0


3 In=0.3 A Expected Time(s) 4 Measured Time(s) 4.07

1.5 In=0.15A PHASE G Expected Time(s) 25.6 Measured Time(s) 26.38

2 In=0.2 A Expected Time(s) 10.667 Measured Time(s) 10.88

4.6.6.1.5. Time Characteristic test IEC short time Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground TOC1 PARAMETER GROUND TOC 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.1pu Curve IEC short time TD Multiplier 0.40 Results 1.5 In=0.15A PHASE G Expected Time(s) 1.223 Measured Time(s) 1.28 2 In=0.2 A Expected Time(s) 0.711 Measured Time(s) 0.755 3 In=0.3 A Expected Time(s) 0.445 Measured Time(s) 0.480

4.6.6.1.6. Ground Instantaneous Over Current Test IOC 1 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Ground Current / Ground IOC1 PARAMETER GROUND IOC 1 Function Enable Signal Source SRC 1 (SRC1) Pickup 0.5 pu Delay 0.0sec Results Phase G Pick-up Current (A) 0.501 Time setting Inst. Arabian BEMCO Measured time(ms) 26.0 SEC-COA

Subcontract/Tested by Name: Signature: Date:

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 23 of 29 Date: 23/3/2010,Revision: 0

4.6.6.1.7

Restricted Ground Fault1

Setting / Grouped Elements / Group 1 / Ground Current / Restricted Ground Fault1 PARAMETER Function Signal Source Pickup Delay a-Pick up Test Phase Pickup Current (A) Operating Time(ms) 23.0 23.1 22.8 22.5 Expected operation No operation Actual operation No operation Restricted Ground Fault1 Enable SRC 1 (SRC 1) 0.1 pu 0.0sec

R 0.101 Y 0.101 B 0.101 G 0.102 a. Stability Test by secondary injection Phase R Y B

Injected Current (A) Phase CT side Ground CT side 0.5 0.5 0.5 0.5

i.

b. Slope Test Slope-0 Operation Phase R R Y Y B B Injected Current (A) Phase CT side Ground CT side 0.05 0.05 0.150 0.05 0.05 0.05 0.150 0.05 0.05 0.05 0.150 0.05 Expected operation No operation Operate No operation Operate No operation Operate Actual operation No operation Operate No operation Operate No operation Operate SEC-COA

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

Testing of Transformer Differential Relay T60(MAKE: GE)


ii. Slope- 40% Operation Phase R R Y Y B B 4.6.7. Injected Current (A) Phase CT side Ground CT side 0.461 0.2 0.462 0.2 0.461 0.2 0.462 0.2 0.461 0.2 0.462 0.2

Page 24 of 29 Date: 23/3/2010,Revision: 0

Expected operation No operation Operate No operation Operate No operation Operate

Actual operation No operation Operate No operation Operate No operation Operate

Voltage elements 4.6.7.1. Phase Under Voltage Test UV1 Setting (Pickup, Dropout and Time) Setting / Grouped Elements / Group 1 / Voltage Elements / Phase UV PARAMETER PHASE UV 1 Function Enable Signal Source SRC 1 (SRC 1) Mode Phase to Ground Pickup 0.8 pu Curve Definite Time Delay 1.00 s Minimum Voltage 0.1 pu Test Results Pick Up (V) Drop Off (V) PHASE Calculated Measured Measured R Y B 55.44 55.44 55.44 55.43 55.45 55.45 56.53 56.55 56.55

Measured Time(s) At 55 V 1.02 1.02 1.03

4.6.7.2. Phase Under Voltage Test UV2 Setting (Pickup, Dropout and Time) Setting / Grouped Elements / Group 1 / Voltage Elements / Phase UV PARAMETER PHASE UV 2 Function Enable Signal Source SRC 1 (SRC 1) Mode Phase to Ground Pickup 0.85 pu Curve Definite Time Delay 1.00 s Minimum Voltage 0.1 pu Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Test Results Pick Up (V) PHASE R Y B Calculated 58.9 58.9 58.9 Measured 58.9 58.91 58.91 Drop Off (V) Measured 60.06 60.10 60.07

Page 25 of 29 Date: 23/3/2010,Revision: 0

Measured Time(s) At 58 V 1.02 1.02 1.02

4.6.7.3. Phase Over Voltage Test OV1 Setting (Pickup, Dropout and Time) Setting / Grouped Elements / Group 1 / Voltage Elements / Phase OV PARAMETER PHASE OV 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.9 pu Curve Definite Time Delay 1.00 s Minimum Voltage 0.1 pu Test Results PHASE R-Y Y-B B-R Pick Up Calculated 108 108 108 Measured 108.0 108.0 108.0 Drop Off Measured 105.6 105.6 105.7 Measured Time At 63*3 V 1.05 1.04 1.04

4.6.7.4.

Neutral Over Voltage Test OV1 Setting (Pickup, Dropout and Time) Setting / Grouped Elements / Group 1 / Voltage Elements / Neutral OV1 PARAMETER Neutral OV 1 Function Enable Signal Source SRC 1 (SRC 1) Mode Phase to Ground Pickup 0.3 pu Curve Definite Time Delay 1.00 s Minimum Voltage 0.1 pu Subcontract/Tested by Arabian BEMCO SEC-COA

Name: Signature: Date:

Testing of Transformer Differential Relay T60(MAKE: GE)


Test Results PHASE R Y B Pick Up Calculated 20.7 20.7 20.7 Measured 20.80 20.82 20.81 Drop Off Measured 20.15 20.17 20.17

Page 26 of 29 Date: 23/3/2010,Revision: 0

Measured Time At 21 V 1.06 1.06 1.06

4.6.7.5. Volts per Hertz 4.6.7.5.1. Inverse Curve A: Ref equation page # 5-167 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Voltage element / Volts per Hertz PARAMETER Volts per Hertz Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.8pu Curve Inverse Curve A TD Multiplier 1 Results PHASE R-N Y-N B-N 1.5 Vp=83.16 Expected Measured Time(s) Time(s) 0.8 0.883 0.8 0.932 0.8 0.905 2 Vp= 110.88 Expected Measured Time(s) Time(s) 0.333 0.447 0.333 0.443 0.333 0.412

4.6.7.5.2. Inverse Curve B: Ref equation page # 5-167 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Voltage element / Volts per Hertz PARAMETER Volts per Hertz Function Enable Signal Source SRC 1 (SRC1) Pickup 0.8pu Curve Inverse Curve B TD Multiplier 1 Test Results 1.5 Vp=83.16 Subcontract/Tested by Name: Signature: Date: Arabian BEMCO 2 Vp= 110.88 SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


PHASE R-N Y-N B-N Expected Time(s) 2 2 2 Measured Time(s) 2.11 2.09 2.08

Page 27 of 29 Date: 23/3/2010,Revision: 0


Expected Time(s) 1 1 1 Measured Time(s) 1.11 1.08 1.08

4.6.7.5.3. Inverse Curve C: Ref equation page # 5-167 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Voltage element / Volts per Hertz PARAMETER Volts per Hertz Function Enable Results Signal Source SRC 1 (SRC 1) 1.5 Pickup 0.8pu Vp=83.16 2 Vp= 110.88 CurvePHASE Inverse Curve C Measured Expected Expected Measured TD Multiplier 1 Time(s) Time(s) Time(s) Time(s) R-N 4.45 4.56 2.414 2.52 Y-N B-N 4.45 4.45 4.54 4.55 2.414 2.414 2.51 2.47

4.6.7.5.4. Definite Time: Ref equation page # 5-167 Setting (Pickup and Time) Setting / Grouped Elements / Group 1 / Voltage element / Volts per Hertz PARAMETER Volts per Hertz Function Enable Signal Source SRC 1 (SRC 1) Pickup 0.8pu Curve Definite time TD Multiplier 1 Results : 1.5 Vp=83.16 PHASE R-N Y-N Subcontract/Tested by Name: Signature: Date: Expected Time(s) 1 1 Measured Time(s) 1.12 1.09 Arabian BEMCO 2 Vp= 110.88 Expected Time(s) 1 1 Measured Time(s) 1.10 1.09 SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 28 of 29 Date: 23/3/2010,Revision: 0


1 1.08

B-N

1.09

4.7. Testing of Controlled Element 4.7.1. Under Frequency Setting (Pickup, Dropout and Time) Setting / Control elements / under frequency PARAMETER Under Frequency 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 59 Hz Pickup Delay 0.00 s Minimum Voltage/Amp 0.10 pu Test Results Setting 59 Hz Timing Test: F Setting 59 Hz

F Pick Up 59 F Applied 55 Hz

F Drop Off 59.04 Measured Time 110 ms

4.7.2. Over Frequency Setting (Pickup, Dropout and Time) Setting / Control elements /Over frequency PARAMETER Over Frequency 1 Function Enable Signal Source SRC 1 (SRC 1) Pickup 61 Hz Pickup Delay 0.00 s Test Results Setting 61 Hz Timing Test: F Setting 61 Hz F Pick Up 61 Hz F Applied 63 Hz F Drop Off 60.96Hz Measured Time 88.4 ms

Subcontract/Tested by Name: Signature: Date:

Arabian BEMCO

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 29 of 29 Date: 23/3/2010,Revision: 0

Test Equipment

Model

Cal due date

Serial Number

Freja 300 FLUKE

Programma 187

30-8-2010 1-9-2010

7501806 1099

4.7.3.

Final Setting test: 4.7.3.1. Final Setting 4.7.3.1.1. OSCILLOGRAPHY FUNCTION SETTINGS Number Of records 6 Trigger Mode Automatic Overwrite Trigger Position 25% Trigger Source TRIG OSC On (VO5) AC Input Waveforms 64 samples/cycle Digital Channel 2 EXT TRIG On(P7a) Digital Channel 4 GSU PRESS On (H7a) Digital Channel 5 TRIP 86U IOn (H1) Digital Channel 6 XFMR INST DIFF OP A Subcontract/Tested by Arabian BEMCO

UNITS

REMARKS

SEC-COA

Name: Signature: Date:

Testing of Transformer Differential Relay T60(MAKE: GE)


Digital Channel 7 Digital Channel 8 Digital Channel 9 Digital Channel 10 Digital Channel 11 Digital Channel 12 Digital Channel 13 Digital Channel 14 Digital Channel 15 Digital Channel 16 Digital Channel 17 Digital Channel 18 Digital Channel 19 Digital Channel 20 Digital Channel 21 Digital Channel 22 Digital Channel 23 Digital Channel 24 Digital Channel 25 Digital Channel 26 Digital Channel 27 Digital Channel 28 Digital Channel 29 Digital Channel 30 Digital Channel 31 Digital Channel 32 Digital Channel 33 Digital Channel 34 Digital Channel 36 Digital Channel 37 Digital Channel 38 Digital Channel 39 Analog Channel 1 Analog Channel 2 Analog Channel 3 Analog Channel 4 Analog Channel 5 Analog Channel 6 Analog Channel 7 Analog Channel 8 Analog Channel 9 Analog Channel 10 Analog Channel 11 Subcontract/Tested by Name: Signature: Date: XFMR INST DIFF OP B XFMR INST DIFF OP C XFMR PCNT DIFF OP A XFMR PCNT DIFF OP B XFMR PCNT DIFF OP C XFMR PCNT DIFF PKP A XFMR PCNT DIFF PKP B XFMR PCNT DIFF PKP C RESTD GND FT1 OP REST GND FT1 PKP PHASE IOC1 OP A PHASE IOC1 OP B PHASE IOC1 OP C PHASE TOC1 OP A PHASE TOC1 OP B PHASE TOC1 OP C PHASE TOC1 PKP A PHASE TOC1 PKP B PHASE TOC1 PKP C VOLT PER HERTZ 1 OP VOLT PER HERTZ 1 PKP VOLT PER HERTZ 2 OP VOLT PER HERTZ 2 PKP GSU GND OC 1 IOn (H2) GSU GND OC 2 IOn (H3) GSU GND OC IOn (H4) GROUND TOC1 OP GROUND TOC 1 PKP T60 TRIP IOn (P1) TRIG G60A IOn (P5) TRIG G60 IOn (P6) ANY TRIP On (VO4) SRC1 La Mag SRC2 la Mag SRC3 la Mag SRC1 lb Mag SRC2 lb Mag SRC3 lb Mag SRC1 lc Mag SRC2 lc Mag SRC3 lc Mag Xfmr lad Mag Xfmr lad Angle Arabian BEMCO

Page 30 of 29 Date: 23/3/2010,Revision: 0

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


Analog Channel 12 Xfmr lar Mag Analog Channel 13 Xfmr lar Angle Analog Channel 14 Volts Per Hertz 1 Analog Channel 15 SRC2 LG Mag 4.7.3.1.2. DEMAND Current Method CUSTOMER Power Method CUSTOMER Interval CUSTOMER Trigger CUSTOMER 4.7.3.1.3. USER-PROGRAMMBLE LEDS:LED TEST Function Disabled Control OFF 4.7.3.1.4. TRIP AND ALARMS LEDS Trip LED Input ANY TRIP On (VO4) Alarms LED Input ANY SELF TESTS 4.7.3.1.5. USER PROGRAMMABLE LEDS LED 4: OPERAND GSU PRESS On (H7a) LED 4: TYPE Self Reset LED 6: OPERAND EXT TRIP On (P7a) LED 6: TYPE Self Reset LED 7: OPERAND TRIP 86U IOn (H1) LED 7: TYPE Latched LED 8: OPERAND XFMR INST DIFF OP A LED 8: TYPE Latched LED 9: OPERAND XFMR INST DIFF OP B LED 9: TYPE Latched LED 10: OPERAND XFMR PCNT DIFF OP C LED 10:TYPE Latched LED 11: OPERAND XFMR PCNT DIFF OP A LED 11: TYPE Latched LED 12: OPERAND XFMR PCNT DIFF OP B LED 12: TYPE Latched LED 13: OPERAND XFMR PCNT DIFF OP C LED 13: TYPE Latched LED 14: OPERAND RESTD GND FT1 OP LED 14: TYPE Latched LED 15: OPERAND PHASE IOC1 OP LED 15: TYPE Latched LED 16: OPERAND PHASE TOC1 OP LED 16: TYPE Latched LED 17: OPERAND VOLTS PER HERTZ 1 OP LED 17: TYPE Latched LED 18: OPERAND VOLTS PER HERTZ 1 OP Subcontract/Tested by Name: Signature: Date: Arabian BEMCO

Page 31 of 29 Date: 23/3/2010,Revision: 0

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


LED 18: TYPE Latched LED 19: OPERAND GSU GND OC 1 IOn (H2) LED 19: TYPE Lathed LED 20: OPERAND GSU GND OC 2 IOn (H3) LED 20: TYPE Latched LED 21: OPERAND GSU GND OC IOn (H4) LED 21: TYPE Latched LED 22: OPERAND GROUND TOC1 OP LED 22: TYPE Latched LED 23: OPERAND T60 TRIP IOn (P1) LED 23: TYPE Self reset LED 24: OPERAND TRGI G60 IOn (P5) LED 24: TYPE Self Reset LED 25: OPERAND TRIG G60B IOn (P6) LED 25: TYPE Self Reset 4.7.3.1.6. USER-PROGRAMMABLE SELF TESTS Remote Device Off Function CUSTOMER Pri-ethernet Fail Function CUSTOMER Battery Fail Function CUSTOMER SNTP Fail Function CUSTOMER IRIG B Fail Function CUSTOMER 4.7.3.1.7. INSTALLATION Relay Settings Not Programmable Relay Name CUSTOMER 4.7.3.1.8. SYSTEM SETUP: AC INPUTS: CURRENT CT F1:Phase CT Primary 6000 A CT F1:Phase CT Secondary 1A CT F1 :Ground CT Primary 1A CT F1 : Ground CT Secondary 1A CT M1:Phase CT Primary 6000 A CT M1:Phase CT Secondary 1A CT M1 :Ground CT Primary 1A CT M1: Ground CT Secondary 1A CT M5 :Phase CT Primary CUSTOMER CT M5 :Phase CT Secondary CUSTOMER CT M5 :Ground CT Primary CUSTOMER CT M5 : Ground CT Secondary CUSTOMER 4.7.3.1.9. VOLTAGE VT F5: Phase VT Connection Wye VT F5 : Phase VT Secondary 66.4 V VT F5 :Phase VT Ratio 120:1 VT F5 : Auxiliary VT None Connection Subcontract/Tested by Name: Signature: Date: Arabian BEMCO

Page 32 of 29 Date: 23/3/2010,Revision: 0

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


VT F5 : Auxiliary VT None Secondary VT F5 :Auxiliary VT Ratio None 4.7.3.1.10. SIGNAL SOURCES SOURCE 1:Name GEN SOURCE 1: Phase CT F1 SOURCE 1: Ground CT None SOURCE 1: Phase VT F5 SOURCE 1: Auxiliary VT None SOURCE 2: Name AUX SOURCE 2: Phase CT M1 SOURCE 2: Ground CT None SOURCE 2: Phase VT None SOURCE 2: Auxiliary VT None SOURCE 3: Name GSU SOURCE 3: Phase CT M5 SOURCE 3: Ground CT M5 SOURCE 3: Phase VT None SOURCE 3: Auxiliary VT None 4.7.3.1.11. TRANSFORMER: GENERAL Number Of Windings CUSTOMER Phase Compensation Internal (software) Load Loss At rated load CUSTOMER Rated Windings Temperature CUSTOMER Rise No Load Loss CUSTOMER Type Of Cooling CUSTOMER Top-Oil Rise Over Ambient CUSTOMER Thermal Capacity CUSTOMER Winding Thermal Time CUSTOMER Constant 4.7.3.1.12. WINDINGS WINDING 1: Source CUSTOMER WINDING 1: Rated MVA CUSTOMER WINDING 1: Nominal Phs-phs CUSTOMER Voltage WINDING 1: Connection CUSTOMER WINDING 1: Grounding CUSTOMER WINDING 1: Angle Wrt CUSTOMER Winding WINDING 1: Resistance CUSTOMER WINDING 2: Source CUSTOMER WINDING 2: Rated MVA CUSTOMER Subcontract/Tested by Name: Signature: Date: Arabian BEMCO

Page 33 of 29 Date: 23/3/2010,Revision: 0

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 34 of 29 Date: 23/3/2010,Revision: 0

WINDING 2: Nominal Phs-phs CUSTOMER Voltage WINDING 2: Connection CUSTOMER WINDING 2: Grounding CUSTOMER WINDING 2: Angle Wrt CUSTOMER Winding WINDING 2: Resistance CUSTOMER WINDING 3: Source CUSTOMER WINDING 3: Rated MVA CUSTOMER WINDING 3: Nominal Phs-phs CUSTOMER Voltage WINDING 3: Connection CUSTOMER WINDING 3: Grounding CUSTOMER WINDING 3: Angle Wrt CUSTOMER Winding WINDING 3 : Resistance CUSTOMER 4.7.3.1.13. FLEXLOGIC: FLEXLOGIC EQUATION EDITOR FlexLogic Entry 1 XFMR INST DIFF OP FlexLogic Entry 2 XFMR PCNT DIFF OP FlexLogic Entry 3 REST GND FT1 OP FlexLogic Entry 4 PHASE IOC1 OP FlexLogic Entry 5 PHASE TOC1 OP FlexLogic Entry 6 VOLTS PER HERTZ 1 OP FlexLogic Entry 7 VOLTS PER HERTZ 2 OP FlexLogic Entry 8 OR(7) FlexLogic Entry 9 =TRIP 86U (VO1) FlexLogic Entry 10 TRIP 86U On (VO1) FlexLogic Entry 11 GROUND TOC1 OP FlexLogic Entry 12 OR(2) FlexLogic Entry 13 =ANY TRIP (VO4) FlexLogic Entry 14 EXT TRIG On (P7a) FlexLogic Entry 15 TMER 1 FlexLogic Entry 16 ANY TRIP On (VO4) FlexLogic Entry 17 OR (2) FlexLogic Entry 18 =TRIG OSC (V05) FlexLogic Entry 19 END 4.7.3.1.14. FLEXLOGIC TIMERS TIMER 1 Type Millisecond TIMER 1 Pick up Delay 1 TIMER 1 Dropout Delay 0 4.7.3.1.15. GROUP ELEMENTS GROUP 1: TRANSFORMER: PERCENT DIFFERENTIAL [GROUP 1] Function Enabled Pickup CUSTOMER Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 35 of 29 Date: 23/3/2010,Revision: 0

Slope1 CUSTOMER Break 1 CUSTOMER Break 2 CUSTOMER Slope 2 CUSTOMER Inrush Inhibit Function CUSTOMER Inrush Inhibit Mode CUSTOMER Inrush Inhibit Level CUSTOMER Overexcitation Inhibit Function CUSTOMER Overexcitition Inhibit Level CUSTOMER Block OFF Target Latched Events Enabled 4.7.3.1.16. INSTANTENEOUS DIFFENTIAL [GOURP 1] Function Enabled Pick up CUSTOMER Block OFF Target Latched Events Enabled 4.7.3.1.17. GROUP CURRENT: Restricted Ground Fault [GROUP 1] Function Enabled Source Customer Pickup Customer Slope Customer Pick up Delay Customer Reset Delay Customer Block OFF Target Latched Events Enabled 4.7.3.1.18. PHASE CURRENT: PHASE IOC [GROUP 1] PHASE TOC1: Function Enabled PHASE TOC1: Signal Source SCR3 PHASE TOC1: Input CUSTOMER PHASE TOC1: Pick up CUSTOMER PHASE TOC1: Curve CUSTOMER PHASE TOC1: TD Multiplier CUSTOMER PHASE TOC1: Reset CUSTOMER PHASE TOC1: Voltage CUSTOMER Restraint PHASE TOC1: Block A OFF PHASE TOC1: Block B OFF PHASE TOC1: Block C OFF PHASE TOC1: Target Latched PHASE TOC1: Events Enabled Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


4.7.3.1.19. PHASE CURRENT: PHASE IOC [GROUP 1] PHASE IOC 1: Function Enabled PHASE IOC 1: Source SRC3 PHASE IOC 1: Pickup CUSTOMER PHASE IOC 1:Delay CUSTOMER PHASE IOC 1: Reset Delay CUSTOMER PHASE IOC 1:Block A OFF PHASE IOC 1:Block B OFF PHASE IOC 1: Block C OFF PHASE IOC 1:Target Self Reset PHASE IOC 1: Events Enabled 4.7.3.1.20. VOLTS PER HERTZ [GROUP 1] VOLTS PER HERTZ Enabled 1:Function VOLTS PER HERTZ 1: Source SRC 1 VOLTS PER HERTZ 1: Pickup CUSTOMER VOLTS PER HERTZ 1: Curves CUSTOMER VOLTS PER HERTZ 1:TD CUSTOMER Multiplier VOLTS PER HERTZ 1: T Reset CUSTOMER VOLTS PER HERTZ 1: Block OFF VOLTS PER HERTZ 1: Target Latched VOLTS PER HERTZ 2: Events Enabled VOLTS PER HERTZ 2: Enabled Function VOLTS PER HERTZ 2: Source SRC 1 VOLTS PER HERTZ 2: Pickup CUSTOMER VOLTS PER HERTZ 2: Curves CUSTOMER VOLTS PER HERTZ 2: TD CUSTOMER Multiplier VOLTS PER HERTZ 2: T reset CUSTOMER VOLTS PER HERTZ 2: Block OFF VOLTS PER HERTZ 2: Target Latched VOLTS PER HERTZ 2: Events Enabled 4.7.3.1.21. GROUND CURRENT: GROUND TOC [GROUP 1] GROUND TOC1: Function Enabled GROUND TOC1: Source SRC 3 GROUND TOC1: Input CUSTOMER GROUND TOC1: Pickup CUSTOMER GROUND TOC1: Curve CUSTOMER GROUND TOC1: TD CUSTOMER Multiplier GROUND TOC1: Reset CUSTOMER Subcontract/Tested by Name: Signature: Date: Arabian BEMCO

Page 36 of 29 Date: 23/3/2010,Revision: 0

SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


GROUND TOC1: Block GROUND TOC1: Target GROUND TOC1: Events OFF Latched Enabled

Page 37 of 29 Date: 23/3/2010,Revision: 0

4.7.3.1.22. INPUTS/OUPUTS: 4.7.3.1.22.1. CONTACT INPUTS H7A : ID Cont lp 1 H7A :Debounce Time 2.0 ms H7A :Events Enabled H7C: ID Cont lp 2 H7C :Debounce Time 2.0 ms H7C :Events Disabled H8A : : ID Cont lp 3 H8A :Debounce Time 2.0 ms H8A :Events Disabled H8C : ID Cont lp 4 H8C :Debounce Time 2.0 ms H8C :Events Disabled P7A : ID EXT TRIG P7A :Debounce Time 2.0 ms P7A :Events Enabled P7C : ID Cont lp 6 P7C : Debounce Time 2.0 ms P7C :Events Disabled P8 A : ID Cont lp 7 P8A :Debounce Time 2.0 ms P8A :Events Disabled P8C : : ID Cont lp 8 P8C :Debounce Time 2.0 ms P8C :Events Disabled 4.7.3.1.22.2. CONTACT OUTPUTS Cont lp 1: Cont lp 2: Cont lp 3: 84 Vdc Cont lp 4:(H7a:H7c:H8a:H8c) EXT TRIG :Cont lp 6:Cont lp 84 Vdc 7 : Cont lp 8(P7a:P7c:P8a:P8c) 4.7.3.1.22.3. CONTACT OUTPUTS H1: ID TRIP 86U1 H1 :Operate TRIP 86U1 On (VO1) H1 :Seal in OFF H1 :Events Enabled H2: ID TRIP 86U2 H2 :Operate TRIP 86U2 On (VO1) H2 :Seal in OFF Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)


H2 :Events H3: ID H3 :Operate H3 :Seal in H3 :Events P1: ID P1 :Operate P1 :Seal in P1 :Events P5: ID P5 :Operate P5 :Seal in P5 :Events P6: ID P6 :Operate P6 :Seal in P6 :Events Enabled GSU GND OC GROUND TOC1 OP OFF Enabled T60 TRIP ANY TRIP On(VO4) OFF Enabled TRIG OSC G60A ANY TRIP On(VO4) OFF Enabled TRIG OSC G60B ANY TRIP On (VO4) OFF Enabled

Page 38 of 29 Date: 23/3/2010,Revision: 0

4.7.3.1.22.4. VIRTUAL OUTPUTS VIRTUAL OUTPUTS 1: ID TRIP 86U VIRTUAL OUTPUTS 1:Events Enabled VIRTUAL OUTPUTS 4: ID ANY TRIP VIRTUAL OUTPUTS 4:Events Enabled VIRTUAL OUTPUTS 5:ID TRIG OSC VIRTUAL OUTPUTS 5:Events Enabled 4.7.3.1.23. REMOTE DEVICES Remote Device 1 ID Remote Device 1 4.7.3.2. . 4.7.3.3. 4.7.3.4. Voltage sensitivity test: Timing Test: Current sensitivity test:

4.7.4. Fault Record: Fault record verification done. 4.7.5. Waveform Record: Waveform record verification 4.8. Relay Setting: Final relay setting retrieved through UR software and printout attached. Subcontract/Tested by Name: Signature: Date: Arabian BEMCO SEC-COA

Testing of Transformer Differential Relay T60(MAKE: GE)

Page 39 of 29 Date: 23/3/2010,Revision: 0

Test Equipment

Model

Cal due date

Test Equipment

Model

Cal due date

Subcontract/Tested by Name: Signature: Date: