Sie sind auf Seite 1von 12

21, rue dArtois, F-75008 PARIS http : //www.cigre.

org

A2-205

CIGRE 2006

Special Considerations on the Selection of On-load Tap-changers for Phase-shifting Transformers

A. KRMER*, D. DOHNAL, B. HERRMANN Maschinenfabrik Reinhausen GmbH Germany

SUMMARY
The selection of on-load tap-changers (OLTCs) for application in phase-shifting transformers (PSTs) differs in some tasks from that for standard power transformers (PTs). These differences has to be taken into account seriously in the planning stage of the transformer. This paper will give helpful guidance in questions of the selection of the appropriate on-load tap-changer (OLTC) for application in phase-shifting transformers (PSTs). When the change-over selector operates, high recovery voltages across the change-over selector contacts can occur, because the tap winding is momentarily disconnected from the main winding. In the case of PSTs with single core design, where the regulation takes place at the line end, very high recovery voltages can occur. The use of tie-in resistors or two-way change-over selectors often covers the problem. However, sometimes it is necessary to change the winding design. Therefore the investigation of this phenomenon should take place very early in the design phase. Contrary to most of the standard PTs, in PSTs exist service positions where the load current does not flow through any part of the transformer winding. In these positions only a reduced or no short-circuit impedance is effective between the load and the source side of the PST. This fact may make high demands on the short-circuit capability of the OLTC, if no short-circuit limiting measures were taken. Usually the rated phase shift of the PST is defined under no-load conditions. Internal impedances of the PST create a voltage drop, which generates an additional phase shift. The phase shift can be of additive or subtractive nature to the rated phase shift. This internal voltage drop depends on the load (through-current) and may affect the step voltage of the OLTC. When paralleling transformers, especially in case of PSTs, problems can arise, because the effective short-circuit impedance of the tap windings can be near to zero, depending on the OLTC position. This situation will be amplified by usually high step voltages in PSTs, which result in high voltage differences between the paralleled PSTs. Therefore high circulating currents between the OLTCs can occur and can lead to a non permissible stress.

KEYWORDS
Phase-shifting Transformer, On-load Tap-changer, Paralleling, Short-circuit Impedance, Rated Conditions

* a.kraemer@reinhausen.com

INTRODUCTION

The growth of electric power consumption combined with environmental pressures and legal regulations causing delays and cancellations of new transmission lines, forces the demand to use the existing networks with high efficiency and high reliability. Therefore high-voltage power grids are interconnected to strengthen the reliability of the electrical power supply and allow the transmission of electrical power over large distances. Complications, attributed to several factors such as different impedances of parallel paths in the grid, the power factor and variations in the power generation output and/or power consumption, can arise and have to be dealt with to avoid potentially catastrophic system black outs. Due to the mainly inductive character of the existing power system, an addition or subtraction of a voltage in phase to the system voltage (variation of the magnitude) affects the reactive power flow only, whereas an addition or subtraction of a voltage perpendicular to the system voltage (variation of the lag between source and load) influences the real power flow. The first case is accomplished by means of variation of the voltage ratio between primary and secondary (regulating power transformers, PTs). The latter one by means of generating a phase shift between source and load terminals (phase-shifting transformers, PSTs). PSTs are nowadays in many cases established and well proven to control the real power flow in transmission lines and system interties to stabilize the grid.

TYPES OF PSTS

PSTs can be designed to provide a discrete phase angle shift, continuous variable phase angle shift, or a combination of both. Some designs allow for magnitude as well as phase control. Many different winding arrangements are possible depending on the rated voltage, the power output, the amount of phase shift, and whether or not linear voltage control is also required. Discrete phase angle shifters normally provide settings for a plus-or-minus fixed degree value and zero. A variable phase shift can be achieved in a very efficient way by using on-load tap-changers (OLTCs) for the variation of the phase shift in definite steps during operation. In most cases, the PSTs are designed to allow the inversion of the phase shift from advance to retard and vice versa. In practice, various solutions are possible to design a PST. The chosen design depends on the major factors [1], [2]: Throughput power and phase-shift angle requirements Rated voltage Short-circuit capability of the connected system Shipping limitations On-load tap-changer performance requirements In addition, preferences of a manufacturer as to the type of transformer (core or shell) or other design characteristics (symmetric or non-symmetric, quadrature or non-quadrature) may also play a role. With respect to the OLTC, the decision whether a single- or a dual-core design is chosen, is very important and may be determined by the performance characteristics of the OLTC. Dual-core designs must not necessarily require a dual tank construction.

SELECTION OF OLTCS

OLTCs are subjected to numerous limits. Depending on the PST design, the tap-changer can be located directly at the line end (high voltage) or in a separate exciting unit. The solution with the OLTC(s) at the line end is typical for the single core design. The arrangement of the OLTC(s) in the exciting winding is typical for dual core designs. The advantage of the single core design is the less complexity combined with its high economic efficiency. However, a number of disadvantages are existing connected with this design and the OLTC application. As mentioned above, the OLTCs are located at the line end and therefore exposed to all disturbances in the system (over voltages, short-circuit fault currents). The regulation requirements determine directly the step voltage and the through-current of the OLTC, but a variation of these values (and with this a possibly more economic choice of the OLTC) is not possible due to the customer spe-

cification. In most of the cases each phase is equipped with one (non-symmetric design) or two (symmetric design) OLTCs. The most common configuration of a dual core design consists of a series and an exciting unit. These units can be enclosed in one tank, but for large capacity transformers, they are designed with to separate tanks. When using this design the step voltage and the through-current of the regulating winding can be varied and optimized with respect to the rated step voltage and rated through-current of the available OLTCs. Up to a certain rating, three-phase OLTCs can be used, with higher ratings three single-pole OLTCs are necessary. The highest voltage for equipment of the OLTC (insulation level) is independent of the system voltage and can be kept low. The use of winding arrangements with coarse and tap winding is possible when larger regulating ranges or reduced step voltage by increasing the number of steps are wanted or necessary. This solution requires an additional switch (Advanced Retard Switch) which serves for the advanced/retard selection. The basic selection of the OLTC is carried out with the maximum through-current and the maximum step voltage. The determination of these values has to be considered well. For both designs is valid that the maximum phase shift is defined under no load conditions and is, usually, symmetrical. However, the phase shift varies under load due to load losses and leakage impedances, resulting in increase of the phase shift in the retard position, but a decrease in the advanced position of the PST. Additionally the overloading of a PST amplifies the above mentioned effects and influences the rated values of the transformer and the OLTC. In addition to the above mentioned consideration and deduced from the experience from many discussions regarding the application of OLTCs in PSTs, the following topics could be found as very important and should be considered very well in the designing stage of a PST: The recovery voltage at the change-over selector (potential connection of the tap winding) The short-circuit impedance The breaking capacity The paralleling of OLTCs and PSTs

3.1

RECOVERY VOLTAGE AT THE CHANGE-OVER SELECTOR

The operation of the change-over selector only takes place in a certain position of the OLTC. During this operation the load current is not flowing through the tap winding. The change-over selector temporarily disconnects the tap winding from the main winding and the potential of the tap winding floats. The floating potential during contact separation is determined by the capacitive coupling to the adjacent winding(s) and/or other adjacent parts of the transformer. Usually, the floating potential is different from the potential of the tap winding when connected to the main winding. After contact separation one contact of the change-over selector is still connected to the main winding, the other one is connected to the floating tap winding and discharges occur. The breaking stresses are determined by the current flowing before the contacts open (currents through the coupling capacitors) and the voltage which arises when the arc extinguishes (recovery voltage). It can be firstly taken from this interrelation that high values of the coupling capacitances lead to high currents to be switched off. Secondly, high differences between the floating potential of the tap winding and the fixed potential of the main winding lead to high recovery voltages. The basic principle of generating a phase shift is to add a perpendicular voltage to the voltages of the source and load side. In a three phase system this can be realized by connecting the tap winding of one phase to the main winding of another phase. During the change-over operation, when the tap winding is disconnected from the main winding, the tap winding will be electrically displaced in direction to that phase, where it is geometrically located and capacitively coupled. In case of single core designs, the potential difference between the two stages tap winding connected to the main winding and tap winding is floating can reach inadmissible high values, because the system voltage is part of the potential difference. In certain winding arrangements, the recovery voltage at the change-over selector can reach values higher than the system voltage divided by square root three, but the limit of the recovery voltage is in the range of 15 to 35 kV. Therefore, particular atten-

tion should be paid to the recovery voltage problem very early and the tap-changer manufacturer should be consulted. In some cases the solution of this phenomenon can dictate the OLTC and can have large impact on the design of the PST due to extensive special countermeasures (additional double-reversing devices, static shielding). More detailed information can be found in [3], [4] and [5]. The potential connection of the tap winding has to be checked in case of dual core designs also, but in most of the cases the recovery voltage at the change-over selector is controllable with conventional measures.

3.2

SHORT-CIRCUIT IMPEDANCE

When the PST is serving in an intertie between two networks, the short-circuit impedance of the PST should be well taken into account. In case of single core PSTs the short-circuit impedance varies between zero and its maximum, depending on the OLTC position respectively the actual phase shift, because the tap winding(s) is the sole impedance between source and load side. Therefore, the PST will not contribute to a short-circuit impedance and herewith the limitation of fault currents. Although the fault current is not flowing through the tap winding at zero phase shift (zero short-circuit impedance), the OLTC is still in the circuit and the fault current is flowing through the OLTC. But the OLTC has only a limited short-circuit current carrying capability and, therefore, additional fault current limiting devices such as current limiting reactors have to be considered very well. The short-circuit impedance of the dual core PST is the sum of the impedances of the series and the exciting unit. If the impedance of the exciting unit is small compared to that of the series unit, the short-circuit impedance of the PST is nearly constant and is not much affected by the OLTC position and herewith by the actual phase shift. Particular care should be taken in case of low-impedance and booster transformers. In some instances, the short-circuit current magnitude can dictate the OLTC selection.

3.3

BREAKING CAPACITY

3.3.1 DEPENDENCY OF STEP VOLTAGE ON OLTC-POSITION AND PST-LOAD


Beside the through-current the step voltage is the most important parameter for a correct OLTC-selection concerning the required switching capacity of an OLTC. The step voltage in a PST may vary in a wide range depending on the load of the PST and the OLTC-position. In the following these dependencies are compared for two basic PST-designs: a symmetrical single core design according to fig. 1a and a symmetrical dual core design according to fig. 1b. The two OLTCs in fig. 1a are always operating at the same time, i.e. at 0-position no tap winding is active.
IS S US U1 IL L UB2 + + UL S IS + N IE1 UE1 N US U1=UE1 IE1 IE2 IL UE2 UL IB2 UB1=USL L

UE2=USL

Fig. 1a: symmetrical single core design

Fig. 1b: symmetrical dual core design

For the following equations the series connection of the two separate tap windings in fig. 1a were considered as one tap winding. The definitions of the used abbreviations are:

OLTC-position with maximum number of steps in service: OLTC-position with N steps in service: Turns ratio of the exciter unit at OLTC-position Nmax: Turns ratio of the exciter unit at OLTC-position N: Turns ratio of the booster unit: Impedance of the tap winding at position Nmax: Impedance of the tap winding in service at position N: Impedance of the booster unit on the high voltage side UB1: Phase angle between US and UL at OLTC-position N: Phase angle at OLTC-position Nmax and at no-load:

Nmax N RE REN = RE*Nmax /N RB ZE ZEN ZE*(N/Nmax) ZB N 0

with N = 0.. Nmax 3.3_1a

3.3_1b

The basic equations for currents and voltages of a transformer under load with turns ratio R, short-circuit impedance Z2 of winding 2 and power flow from winding 1 to winding 2 are: U2 = I2 = U1/R - I2*Z2 I1*R 3.3_2a 3.3_2b

Using eq. 3.3_2a,b the relations of voltages and currents of the exciter unit and the booster unit become: Exciter unit: with with Booster unit: UE2 = UE1/REN + IE2*ZEN IE2 = (IS + IL)/2 for single core design (fig. 1a), IE2 = - j* 3 *IB2 = - j* 3 *RB*(IS + IL)/2 for dual core design (fig. 1b). with IB1 = (IS + IL)/2 (fig. 1b). UB1 = UB2*RB + IB1*ZB 3.3_3 3.3_4a 3.3_4b 3.3_5

The sign of term UE1/REN in eq. 3.3_3 depends on the position of the change-over selector. Sign (+) is retard phase shift, sign (-) is advanced phase shift. With 3.3_1a,b: UE2 = UE1*N/(RE *Nmax) + IE2*ZE*(N/Nmax) The OLTC-step voltage can be calculated with eq. 3.3_6: UStep = UE2/N = UE1/(RE *Nmax) + IE2*ZE*N/Nmax 3.3_7 3.3_6

As an approximation the exciter voltage UE1 in eq. 3.3_7 can be expressed as function of the phase angle N at OLTC-position N, see fig. 2a: UE1 = j* 3 *U1 = j* 3 *US*cos(N/2) UE1 = U1 = US*cos(N/2) for single core design (fig. 1a) for dual core design (fig. 1b) 3.3_8a 3.3_8b

USL in fig. 2a is the voltage between source side and load side of the PST. The phase angle between USL and U1 is not exactly 90 due to the voltage drop at ZE und ZB under load, but the approximation in eq.3.3_8a,b with the cos-function is sufficient to show the basic influence of angle N on UE1.
USL U1= US cos(N/2) US UL N N0 IS IL (IS + IL) / 2= IS * cos(N0/2)

Fig. 2a:Vector diagram of voltages

Fig. 2b: Vector diagram of currents

The current IE2 in eq. 3.3_7 is a function of the phase angle N0 between the currents of source and load side at OLTC-position N, see fig. 2b. Due to eq. 3.3_2b the angle N0 is depending only on the turns ratio, whereas the angle N between the voltages is influenced additionally by the voltage drop at the

transformer impedances, i.e. N0 = N is only true at no-load condition: from 3.3_4a: from 3.3_4b: IE2 = IS*cos(N0/2) IE2 = - j* 3 *RB*IS*cos(N0/2) for single core design (fig. 1a) for dual core design (fig. 1b). 3.3_9a 3.3_9b

The equations 3.3_7 to _9 show two contrary effects on the step voltage: 1) The exciter voltage UE1 as well as the OLTC current IE2 decrease with increasing angle N and therefore with rising OLTC-position N according to function cos(N/2). This is a characteristic of the symmetrical designs shown in fig. 1a,b and can be different for other PST designs, for example unsymmetrical dual core design with e.g. UE1 = US = constant. Due to the characteristic of the cosfunction the effect of decreasing UE1 and IE2 with rising OLTC-position N is significant only for PSTs with high values of phase angle 0. This has the effect of decreasing step voltage with rising OLTC-position N at low load conditions. 2) The load dependent part of the step voltage in eq. 3.3_7 IE2*ZE*N/Nmax increases with the number of steps in service (N). This is more effective in case of small angles 0, because IE2 will remain nearly constant as mentioned above. The comparison of PSTs with the same voltage, through-put power and impedance ZE but different phase angles 0 shows that the step voltage will be more affected by the load in PSTs with a small 0 than in PSTs with a great 0. The first term in eq. 3.3_7 UE1/(RE*Nmax) is mainly determined by the required angle 0 (0 defines turns ratio RE, see also cl. 3.4) and will be of low value for PSTs with small angles, while the load dependent part of the step voltage is determined by the impedance and power and is nearly independent of the phase angle 0. Figures 3 and 4 show the effects of PST-load and transformer impedances as function of the OLTCposition for application examples with a great and a small phase angle. Each example has been calculated with the two PST designs according to fig. 1a and fig. 1b. The used data are: No-load angle at position Nmax: Transformer impedances in both cases: Power factor US , IS for both cases: Case 1: 0 = 12 Case 2: 0 = 37 ZE = 5%, ZB = 5%, (with ratio X/R = 8) 0.9

The step voltage UStep is shown as the ratio UStep/UStep0 (with: UStep0 = step voltage at no-load in OLTCposition N = 0). The PST-load is shown in p.u. (with: 1 p.u. = rated current). The meaning of transformer impedance Z = 5% is that that part of the voltage USL in OLTC-position Nmax due to the voltage drop at Z with a rated load of the PST is 5% of US. The sign in front of the OLTC-position at the xaxis indicates the position of the change-over selector. The impedance of the booster transformer in case of dual core designs influences the phase angle and the step voltage in a different way. The voltage USL and in consequence the phase angle of the PST is influenced by the voltage drop at the impedance of the booster transformer in case of dual core designs: with 3.3_5: USL = j* 3 *UE2*RB + IB1*ZB for dual core design (fig. 1b) 3.3_10

Compared to PSTs with single core design, the phase angle for a PST with dual core design additionally will be increased (retard) or decreased (advanced) by the load (fig. 3a and 3b). The difference in for both designs does not depend on 0 or position N of the OLTC but only depends on the values of the load and the impedance ZB (in p.u.) (see also [1]). Different to the above mentioned effect on phase angle , in both designs the step voltage is almost independent from the voltage drop at ZB (fig. 4a and 4b). The step voltage is affected by the phase angle according to eq. 3.3_8b and eq. 3.3_7. Based on an impedance ZB = 5% the phase angle will differ about only 3 at rated load for both designs. The exciter voltage UE1 and in consequence the step voltage will be changed according to eq. 3.3_8b only by approximately 1% due to the difference in phase angle of 3.

40 30 20 10

40 30 20 10

[]
0 -10 -20 -30 -40 -50 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 OLTC-position

[]
0 -10 -20 -30 -40 -50 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 OLTC-position

0 = 37 load (p.u) = 0 0 = 37 load (p.u) = 1 0 = 37 load (p.u) = 1.5 0 = 12 load (p.u) = 0 0 = 12 load (p.u) = 1 0 = 12 load (p.u) = 1.5

0 = 37 load (p.u) = 0 0 = 37 load (p.u) = 1 0 = 37 load (p.u) = 1.5 0 = 12 load (p.u) = 0 0 = 12 load (p.u) = 1 0 = 12 load (p.u) = 1.5

Fig.3a: Angle for single core design.


1,5 0 = 37 load (p.u) = 0 1,4 1,3 1,2 0 = 37 load (p.u) = 1 0 = 37 load (p.u) = 1.5 0 = 12 load (p.u) = 0 0 = 12 load (p.u) = 1 0 = 12 load (p.u) = 1.5

Fig.3b: Angle for dual core design.


1,5 0 = 37 load (p.u) = 0 1,4 1,3 1,2 0 = 37 load (p.u) = 1 0 = 37 load (p.u) = 1.5 0 = 12 load (p.u) = 0 0 = 12 load (p.u) = 1 0 = 12 load (p.u) = 1.5

UStep/UStep0
1,0 0,9 0,8 0,7 0,6 0,5 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 OLTC-position

1,1

UStep/UStep0
1,0 0,9 0,8 0,7 0,6 0,5 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 OLTC-position

1,1

Fig.4a: Step voltage for single core design.

Fig.4b: Step voltage for dual core design.

3.3.2 OLTC-ADAPTION FOR PHASE-SHIFTING TRANSFORMERS


All specified switching conditions of an application, including overload, have to be concerned to identify the highest value of the step voltage, which is required for the OLTC selection as rated step voltage. Especially in PST-applications with small phase angles 0 the specified overload conditions should be checked concerning an increase of step voltages in the retard direction. This rated step voltage will define the required minimum value of the transition resistor of the OLTC to limit the circulating current in the mid-position of the diverter switch to a permissible value concerning the switching capacity of the transition contacts. The voltage drop at the transition resistor caused by the through-current forms the recovery voltage of the main switching contact. Therefore, the switching capacity of this contact limits the maximum permissible value of the transition resistor for a specified overload to be switched. For the selection of the transition resistor it is always necessary to find a balance between the effects of the step voltage and the through-current. Therefore and for switching capability reasons the rated through-current of an OLTC is assigned to a specified rated step voltage. Regarding the switching capability this is also true for the maximum rated through-current of an OLTC, but the maximum rated through-current additionally determines the current carrying limits and is, with respect to contact heating and short-circuit withstand capability, independent on the step voltage. A standard requirement for OLTCs in common PTs is the capability to break twice the rated throughcurrent at rated step voltage (overload condition). This breaking capacity of the OLTC is guaranteed, provided that the step voltage is independent on the (over)load current. In PST-applications, where a load and OLTC-position dependent range of step voltages has to be handled, sometimes it is not possible to find a transition resistor dimensioning, which is suitable for the rated step voltage (maximum value of step voltage appearing under any specified switching condition) as well as for twice the rated load current. If the overload requirements in those applications are not based on a breaking capacity

of twice but for example of only 1.5 times the rated load current, it should be proven, if an OLTC with reduced rated through-current can be used to enable a more economical OLTC solution.
Limit of the rated step voltage at the rated through-current of the OLTC Limit of the rated step voltage at twice the rated through-current of the OLTC

Max. step voltage at overload = rated step voltage of the application


1
step voltage

Step voltage at rated load current of the application

Required overload to be switched

Rated load current of the application

Maximum rated through-current of the OLTC

load current

Fig. 5: Step voltage limits at rated and twice the rated through-current of any OLTC Figure 5 shows the step voltage limits (switching diagram) as function of the rated through-current as represents the operating point well as of twice the rated through-current of any OLTC. Load point of any PST-application at 1 p.u.. Load point represents the operating point of this PST-application under overload condition (here 1.5 times the rated load current). As mentioned above, point represents that pair of variates, for which the OLTC transition resistors have to be dimensioned. It is obvious that this point is beyond the limits. With the abdication for an overload switching capability of twice the rated load current and with the knowledge that the dimensioning of the transition resistors is carried out considering mainly the overload, now it becomes possible to adjust the transition resistors to the operating point . This procedure is only possible, if 1. the rated load current of the application is less than the maximum rated through-current of the OLTC and 2. the load point under the required overload to be switched is inside the limit of the rated step voltage at twice the rated through-current of the OLTC.

3.4

PARALLELING OF PHASE-SHIFTING TRANSFORMERS

When connecting two (or more) regulating transformers equipped with OLTCs in parallel an out-ofstep condition temporarily occurs due to the non synchronous operation of the different OLTCs. Even if their motor drives are operated at the same time, the diverter switches do not operate synchronously due to the spring operated energy accumulator. The voltage difference of one tap in the parallel circuits during this out-of-step condition will lead to different loadings of the transformers and the OLTCs, which are no longer proportionally to the rated power of the transformers. The duration of this out-of-step condition is extremely short (less than 1 s) and therefore causes no problems regarding the heating of the windings or of the OLTC contacts. However, these special breaking conditions of OLTCs in paralleled transformers should be taken into consideration for the OLTC-selection. OLTCs in paralleled PSTs may be more affected by the out-of-step condition than those in PTs. In the following the current distribution at out-of-step condition is compared for two paralleled PSTs

and two paralleled PTs to show the basic differences. Each of the paralleled transformers A and B is represented by the no-load voltages U0A resp. U0B and the impedances ZA resp. ZB. Figures 6a and b show the equivalent networks for two paralleled PSTs respectively two paralleled PTs, loaded with IL and system voltages US and UL.
PST A U0A ZA IA IA ZA IL ZB US U0B PST B IB UL PT A PT B U0A IB IL USL ZB UL U0B

Fig. 6a: Paralleled phase shift transformers.

Fig. 6b: Paralleled power transformers.

With the approximation that the load current IL and the impedances of the transformers are nearly equal before and after the tap-change operation at one of the paralleled transformers, the current distribution on the two transformers acc. fig. 6a and 6b is: Before the tap-change operation the OLTCs in the paralleled transformers are on the same position: U0A = U0B IA = IL * ZB / (ZA + ZB) = ILA = IL * ZA / (ZA + ZB) = ILB IB After the tap-change operation at one of the transformers, the out-of-step condition occurs: IA = ILA + IC IB = ILB - IC with and U = (U0A U0B) IC = U / (ZA + ZB) (IC = circulating current at out-of-step condition) 3.4_1a 3.4_1b 3.4_1c 3.4_2a 3.4_2b 3.4_2c 3.4_2d

In case of paralleled PSTs the tap-change operation from position 0 or to position 0 (compare clause 3.3) will lead to the most unsymmetrical current splitting of all possible out-of-step conditions. In case of dual core designs the PST impedance in position 0 is only the impedance of the booster unit, because the exciter unit is not loaded in this position and with this the circulating current IC in eq. 3.4_2d has its maximum value. In consequence the paralleling of PSTs with single core design according to fig. 1a is not possible, because there is no PST-impedance in position 0 effective to ensure a defined current distribution to the paralleled transformers and a short-circuit occurs. The equivalent network of two paralleled PSTs of dual core design, one in position 0 and one in position 1, can be reduced to that shown in fig. 7:
U ZA IA

USL IL ZB US IB UL

Fig. 7: Paralleled PSTs with PST A in pos. 1 and PST B in pos. 0.

In case of paralleled PTs the voltage U in eq. 3.4_2d is equal to the step voltage at no-load, whereas in case of paralleled PSTs U becomes -USL at no-load in OLTC-position 1 (compare fig. 2a and eq. 3.3_10). The vector diagrams of voltages and currents resulting from figs. 6b and 7 at the out-of-step condition are shown in fig. 8a,b, where a power factor of the load (PF) is assumed in the range of 1. In fig. 9a,b the same vector diagrams are shown with a PF in the range of 0. For these examples it is assumed that ZA and ZB of the paralleled transformers are equal. Then eq. 3.4_1b and 1c can be reduced to: ILA = ILB = IL /2
U IA * ZA IC IB * ZB IB IA U0B IL/2 IA UL IB IL/2

(symmetrical current splitting before tap-change operation)


U IA * ZA

3.4_3

IC

IB * ZB US UL

Fig. 8a: Vectors for paralleled PSTs with PF 1


U IA * ZA IB * ZB US UL IL/2 IB IC

Fig. 8b: Vectors for paralleled PTs with PF 1


U IB * ZB IB U0B UL IL/2 IA IA * ZA IC

IA

Fig. 9a: Vectors for paralleled PSTs with PF 0

Fig. 9b: Vectors for paralleled PTs with PF 0

Due to the inductive transformer impedances the circulating current IC has a phase shift to U of approximately 90. In case of paralleled PSTs U has a phase shift to the system voltage US of 90, and therefore the circulating current IC is nearly in phase respectively in phase opposition with US. In case of paralleled PTs, IC has a phase shift of approximately 90 to the system voltage, because U (= step voltage) is in phase with the system voltage. As shown in figs. 8 and 9, the circulating current IC at the out-of-step condition will increase or decrease the magnitudes of the currents IA and IB, all the more as IC is in phase with the load current IL. This arises at paralleled PSTs, if the power factor PF becomes nearly 1 and at paralleled PTs if PF becomes nearly 0. As stated above, in case of paralleled PSTs the voltage USL between source and load side at no-load condition in position 1 of the OLTC has to be considered as U in eq. 3.4_2d for the worst current splitting condition. This U can be calculated as a function of the phase angle 0 and the number of steps Nmax. (definitions see clause 3.3). The following abbreviations for phase angle and voltage in position 1 are used: Phase angle of the PST in OLTC-position 1 at no-load: Voltage USL of the PST in OLTC-position 1 at no-load: 1 USL1

For the OLTC in position N at no-load and using the definitions in clause 3.3 the phase angle becomes: with 3.3_3 and 3.3_10, fig. 2a: with 3.3_1a and N= 1: with 3.3_1a and N= Nmax: tan(N/2) = (USL/2)/UE1 = j* 3 *RB/(2*REN) tan(1/2) = j* 3 *RB/(2*RE*Nmax) tan(0/2) = j* 3 *RB/(2*RE) 3.4_4a 3.4_4b 3.4_4c

Phase angle 0 and Nmax are specified for a PST in order stage. With these values 1 can be calculated: with fig. 2a: and with 3.4_5: and with cos(1/2) 1: tan(1/2) = tan(0/2) / Nmax USL1 = 2*US*sin(1/2) ( = U in fig.7 and 3.4_2d) USL1 = 2*US*cos(1/2)* tan(0/2) / Nmax USL1 = 2*US* tan(0/2) / Nmax USL1 = US*Step / 56 with Step = 0/Nmax 3.4_5 3.4_6a 3.4_6b 3.4_6c

For 0 between 10 and 40 eq. 3.4_6c can be approximated with a deviation of less than 2% with: 3.4_6d

As an example fig. 10 shows the current splitting on two paralleled transformers as a function of U. The calculation was done with two different power factors PF of 0.9 and 0.3 to demonstrate the different influences on PSTs and PTs in the range of common step voltages and transformer impedances.
1,40 1,35 1,30 1,25

PST PF = 0.9 Z = 5% PST PF = 0.9 Z = 10% PST PF = 0.3 Z = 5% PST PT PT PT PT PF = 0.3 PF = 0.9 PF = 0.9 PF = 0.3 Z = 10% Z = 5% Z = 10% Z = 5%

IA / ILA
1,20 1,15 1,10 1,05 1,00

PF = 0.3 Z = 10%

1,0%

1,5%

2,0%

2,5%

3,0%

3,5%

4,0%

U / US

Fig. 10: Increase of the current IA in paralleled transformers, both with the same impedances Z (ratio X/R = 8), due to out-of-step condition. Load before tap-change operation: ILA = rated current. The current IA (see eq. 3.4_2a) in one of the two transformers respectively one of the OLTCs during out-of-step condition will be increased at most by IA assuming the following ordinary values for power factor and transformer impedance: PST: IA = 31% of the rated current with: PT: IA = 7% of the rated current with: Z = 5% PF = 0.9 Z = 10% PF = 0.3 U = 3.6 % resp. Step = 2 U = 1.5 %.

Regarding the required switching capacity of the OLTC, in case of paralleled transformers the above mentioned increase IA of the OLTC through-current in the out-of-step condition should be covered by the required overload which the OLTC should be able to break.

CONCLUSION

As stated in IEEE Standard C57.135 [5] and IEC Publication 60214-2 [6] the selection of OLTCs for the use in PSTs has to be considered very well because of some specific duties. The recovery voltage at the open change-over selector depends mainly on the transformer design. Especially in case of PSTs some specific rules have to be paid attention to. The recovery voltage should be checked together with the OLTC manufacturer in the planning stage of the PST to proof the design with respect to these stresses. The recovery voltage limits at the change-over selector can dictate the OLTC selection and sometimes the transformer design. Because of the limited short-circuit current carrying capability of the OLTC, the short-circuit impedance of the PST should be taken into account.

10

Unlike in standard PTs, the overloading of a PST influences the rated values of the transformer. All possible switching conditions for the OLTCs in the PST-application have to be concerned to identify the highest value of the step voltage, which is required for the OLTC selection as rated step voltage. Especially in PST-applications with small phase angles 0 the specified overload conditions should be checked taking into account the increase of step voltages in the retard direction. When paralleling two (or more) transformers equipped with OLTCs, an out-of-step condition for a very short time period occurs due to non synchronous operation of the different OLTCs. In this case the momentary voltage difference of the two transformers will force a circulating current through the circuit, which is only limited by the reactances involved. OLTCs in paralleled PSTs may be more affected by the out-of-step condition than those in PTs. Under certain conditions the magnitude of this circulating current may reach the order of one third of the load current. This has to be checked in every case with respect to the switching capability of the OLTC. The paralleling of PSTs in single core design is not possible with respect to the OLTC, because in the 0-position there is no transformer impedance effective. Consequently, the OLTC switching secondly has to break, in addition to the load current, a circulating current which is in the range of a short-circuit current.

BIBLIOGRAPHY
[1] [2] [3] Gustav Preininger Phase-shiftig Transformers(in: James Harlow Electric Power Transformer Engineering, CRC Press, New York, 2004, pages 2-63 2-80) Walter Seitlinger Phase Shifting Transformers Discussion of Specific Characteristics (CIGR Session 1998, Paris, 30th August 5th September 1998, paper 12-306) A. Krmer, J. Ruff Transformers for Phase Angle Regulation Considering the Selection of Onload Tap-changers (IEEE Transactions on Power Delivery, Vol. 13, No.2, April 1998, pages 518-525) Axel Krmer On-load Tap-changers for Power Transformers Operation Principles, Applications and Selection (MR-Publication, Regensburg, 2000). IEEE Standard C57.135 IEEE Guide for the Application, Specification and Testing of PhaseShifting Transformers, First edition, 2001 IEC Publication 60214-2 Tap-changers Part 2: Application Guide, First edition, 2004

[4] [5] [6]

11

Das könnte Ihnen auch gefallen