room supply
Volume flow: 1000 m/h 5% = 950 1050 m/h
no problem
room pressure
room supply
Volume flow: 1000 m/h 5% = 950 1050 m/h
room pressure
room supply
Volume room pressure 500 Pa! flow: (by leakage volume flow 75 m/h)
room pressure
Physical Background
According to Bernoulli:
p = * A* 2
If the area is nearly zero
room pressure 500 Pa!
Even a lowest volume flow difference will change the room pressure dramatically!
Regulation triangle
Pressure control
V p = * A* 2
tightness
V p = * A* 2
Reference Pressure
The reference must be stable / constant pressure - 15 Pa - 25 Pa
P
- 15 Pa
- 10 Pa
- 10 Pa
forbidden!!!
Attention
every pressure room must be regulated to a reference room No pressure variation in reference room No pressure variation in the ventilation system In air tight rooms regard the hysteresis of the VAV regulator the regulation quality dependents of all installed regulator in the room, even the non pressure regulator The pressure is every time a function of the leakage volume flow
Cheap solution
Damper will move to extreme positions (Open / Close) High pressure jumps after closing doors Door switches can not be used in laboratories (Not Controller allowed streamings are possible) No fast reaction times possible
Reference pressure
Defined control areas No extreme positions of the damper No door switches needed
Contr. Contr.
www.trox.de