Beruflich Dokumente
Kultur Dokumente
HF-Select TL-D
Definition Slim and lightweight high frequency (HF) electronic driver for fluorescent TL-D lamps. Product features Up to 25% reduction in energy consumption compared to an electromagnetic ballast. Programmed start: flicker-free warm start < 2 sec., preheating the lamp electrodes which enables the lamps to be switched on and off without reducing useful life. 50% longer lamp life compared to electromagnetic systems. Unit is protected against excessive mains voltages and incorrect connections. Automatic stop circuit is activated within five seconds in case of lamp failure (Safety stop); once the lamp has been replaced, the driver resets automatically. Application areas Typical areas of application include: Department stores, shops, supermarkets Suitable for use with infrared remote control systems Airports, railway stations Outdoor lighting Office buildings, for example, insurance companies, banks, government ministries Hospitals Hotels Industrial premises
Philips quality This assures optimum quality regarding: European standards Philips HF electronic regulating drivers comply with all relevant European rules and regulations. System supplier As manufacturer of lamps, electronic drivers and lighting control equipment, Philips ensures that, from the earliest development stage, optimum lamp/driver performance is maintained.
B
Dimensions in mm A 265 265 265 265 265 265 265 B 280 280 280 280 280 280 280 C 30 30 39 30 30 30 30 D 28 28 28 28 28 28 28 E 4.2 4.2 4.2 4.2 4.2 4.2 4.2
118 TLD* 218 TLD* 3/418 TLD 136 TLD 236 TLD 158 TLD 258 TLD
HF-Select TL-D
Performance IEC 60929 Vibration & bump tests EN 60068-2-6-FC EN 60068-2-29-Eb Quality standard ISO 9001 Environmental standard ISO 14001 RoHS compliant Approval marks ENEC, EMV-VDE Temp. declared thermally protected EN 61347-1 110 CE marking
Technical data in relation to energy saving (all typical values at Vmains =230V)
Lamp Qty. of Lamps Driver System Power W Lamp Power W
16 16 16 16 33 64 32 51 100
Driver Losses W
3 4 5 6 4 8 12 5 10
CELMA EEI
A2 A2 A2 A2 A2 A2 A2 A2 A2
TL-D 18W 1 HF-S 118 TLD 19 TL-D 18W 2 HF-S 218 TLD 40 TL-D 18W 3 HF-S 3/418 TLD 53 TL-D 18W 4 HF-S 3/418 TLD 70 TL-D 36W 1 HF-S 136 TLD 37 TL-D 36W 2 HF-S 236 TLD 72 TL-D 36W 3 HF-S 336 TLD 108 TL-D 58W 1 HF-S 158 TLD 56 TL-D 58W 2 HF-S 258 TLD 110 * Typical values for /830 and /840 colours at 25C lamp ambient temperature
Technical data for installation Mains operation Rated mains voltage With tolerances for performance -8% +6% With tolerances for safety: +/- 10%
(3)
(3)
Ignition and operation possible between Mains frequency Operating frequency (typical) Power factor
Suitable for de-centralized emergency lighting installations Technical data for installation Earth leakage current Total Harmonic Distortion (THD) Ignition time Constant light operation
< 0.5 mA per driver < 10% <2s In case of AC mains voltage fluctuations, within 202-254 V, the luminous flux Changes by a maximum of 5 % 48 hrs at 320 V AC
Dual fixture: master-slave Automatic restart after lamp replacement or voltage dip Insulation resistance test
Max 120pF between lamp wires lp-lp Max 200pF between lamp wires and earth lp-gnd EMI precautions have to be taken (7) Possible, in general a maximum of 2m lamp wires between driver and lamp is allowed yes: tested with a dip down to 30% with a duration of 10 mains cycles 500 V DC from Line/Neutral to Earth (not between Line and Neutral) Note: Ensure that the neutral is reconnected again after above mentioned test is carried out and before the installation is put in operation
HF-Select TL-D
Input current A
0.08 0.15 0.31 0.16 0.32 0.46 0.23 0.48
13 12 11
HF DRIVER
1 2 3 4
L N
Inrush current
Balast Max. quantity of driver per Miniature Circuit Breaker Type B16 A
(1x18W TL-D) (2x18W TL-D) (4x18W TL-D) (1x36W TL-D) (3x36W TL-D) (2x36W TL-D) (1x58W TL-D) (2x58W TL-D) 28 28 12 28 12 28 28 12
118 TLD 218 TLD 3/418 TLD 136 TLD 336 TLD 236 TLD 158 TLD 258 TLD
13 12 11
HF DRIVER
1 2 3
4 5 6
L N
Conversion table for max. quatities of drivers on other types of Miniature Circuit Breaker
MCB Type
B B C C L, I L, I G, U, II G, U, II K, III K, III
1 2
13 12 11
HF DRIVER
4 5 6 7 8 9 10
L N
Notes 1. Data is based on a mains supply with an impedance of 400 m (equal to 15 m cable of 2.5mm2 and another 20m to the middle of the power distribution), under worst case conditions. With an impedance of 800 mW the number of drivers can be increased Lamp current crest by 10%. 2. Measurements will be verified in real installations; therefore data are subject to change. 3. In some cases the maximum number of drivers is not determined by the MCB but by the maximum electrical load of the lighting installation. 4. Note that the maximum number of drivers is given when these are all switched on the same moment, i.e. by a wall switch. 5. Measurements were carried out on single-pole MCBs. For multi-pole MCBs it is advisable to reduce the number of drivers by 20%. 6. The maximum number of drivers which can be connected to one Residual Current Detector of 30mA is 30. 7. The average cable capacity Lp-Gnd is 100pF per meter for standard installation wire Diameter 1.0 mm (bundled lamp wiring situation). For more information regarding this. subject consult the Philips Application guide to fluorescent lamp control gear (3222 635 59771 *May 2006)
1 2 3
13 12 11
HF DRIVER
4 5 6 7 8 9 10
L N
Wiring diagrams
HF-Select TL-D
Connector type: Connection wiring is greatly simplified through use of insert contacts. Earth connection can be made via housing. Wire lengths: For optimal performance, note that following wires need to be kept short: For one lamp circuits keep wires to terminals 1 and 2 short For two lamp circuits keep wires to terminals 1,2,5 and 6 short For triple and quad lamp circuits keep wires to terminals 1,2,9 and 10 short Wire cross-section: Mains Lamp(s) connector Strip length 0.5mm 1.5mm2 0.5mm 1.5mm2 10 11mm
Lifetime of a driver depends on the temperature of the driver.This means there is a relation between the Tc point on the driver and its lifetime. For more information regarding this subject consult the Philips Application guide to fluorescent lamp control gear (3222 635 59771 *May 2006) Hum and noise level Outdoor use inaudible (< 30 dBa at 1 meter) Driver IP=23, in outdoor applications the Luminaire has to besufficient IP rated. Permitted humidity is tested according to IEC 61347-1 par 11 Note that no moisture or condensation may Enter the driver. Earthing of the driver in a luminaire is necessary for EMC (Electromagnetic Compatibility)
Earthing
The drivers that are thermally protected use a protective method of another type providing equivalent thermal protection.
Weight Gross kg
EAN code
EOC
118 TL-D* 218 TL-D* 3/418 TL-D 136 TL-D 236 TL-D 336 TL-D 158 TL-D 258 TL-D
12 12 10 12 12 10 12 12
3222 635 47431 09/2007 Printed in the Netherlands Data subject to change