Beruflich Dokumente
Kultur Dokumente
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.....................................................................25
Introduction to the technical reference manual.................................25
About the complete set of manuals for an IED............................25
About the technical reference manual.........................................26
This manual.................................................................................27
Introduction.............................................................................27
Principle of operation..............................................................27
Input and output signals.........................................................30
Function block........................................................................30
Setting parameters.................................................................30
Technical data........................................................................31
Intended audience.......................................................................31
Related documents......................................................................31
Revision notes.............................................................................32
1
Technical reference manual
Table of contents
2
Technical reference manual
Table of contents
Introduction..................................................................................83
Principle of operation...................................................................84
Function block.............................................................................85
Input and output signals..............................................................86
Setting parameters......................................................................86
IED identifiers...................................................................................86
Introduction..................................................................................86
Setting parameters......................................................................87
Product information..........................................................................87
Introduction..................................................................................87
Setting parameters......................................................................87
Factory defined settings..............................................................87
Signal matrix for binary inputs SMBI................................................88
Introduction..................................................................................88
Principle of operation...................................................................88
Function block.............................................................................89
Input and output signals..............................................................89
Signal matrix for binary outputs SMBO ...........................................90
Introduction..................................................................................90
Principle of operation...................................................................90
Function block.............................................................................90
Input and output signals..............................................................91
Signal matrix for mA inputs SMMI....................................................91
Introduction..................................................................................91
Principle of operation...................................................................91
Function block.............................................................................92
Input and output signals..............................................................92
Signal matrix for analog inputs SMAI...............................................92
Introduction..................................................................................92
Principle of operation...................................................................93
Frequency values........................................................................93
Function block.............................................................................94
Input and output signals..............................................................94
Setting parameters......................................................................96
Summation block 3 phase 3PHSUM................................................97
Introduction..................................................................................97
Principle of operation...................................................................97
Function block.............................................................................98
Input and output signals..............................................................98
Setting parameters......................................................................98
Authority status ATHSTAT...............................................................99
Introduction..................................................................................99
Principle of operation...................................................................99
3
Technical reference manual
Table of contents
Function block.............................................................................99
Output signals..............................................................................99
Setting parameters....................................................................100
Denial of service DOS....................................................................100
Introduction................................................................................100
Principle of operation.................................................................100
Function blocks..........................................................................100
Signals.......................................................................................101
Settings......................................................................................101
4
Technical reference manual
Table of contents
Setting parameters....................................................................170
Technical data...........................................................................171
1Ph High impedance differential protection HZPDIF .....................171
Identification..............................................................................171
Introduction................................................................................171
Principle of operation.................................................................172
Logic diagram.......................................................................172
Function block...........................................................................172
Input and output signals............................................................173
Setting parameters....................................................................173
Technical data...........................................................................173
5
Technical reference manual
Table of contents
Principle of operation.................................................................205
Function block...........................................................................210
Input and output signals............................................................210
Setting parameters....................................................................211
Technical data...........................................................................212
Sensitive rotor earth fault protection, injection based
ROTIPHIZ ......................................................................................212
Introduction................................................................................212
Principle of operation.................................................................212
The injection unit REX060....................................................214
Rotor Earth Fault Protection function...................................215
General measurement of earth fault impedance..................216
Simplified logic diagram.......................................................218
Commissioning tool ICT.......................................................220
Description of input signals........................................................223
Description of output signals.....................................................223
Function block...........................................................................225
Input and output signals............................................................225
Setting parameters....................................................................226
Technical data...........................................................................227
100% stator earth fault protection, injection based STTIPHIZ .......227
Introduction................................................................................228
Principle of operation.................................................................228
Configuration principle..........................................................229
Generator system earthing methods....................................231
100% Stator earth fault protection function..........................235
General measurement of earth fault impedance..................239
Measuring reference impedance..........................................241
Simplified logic diagram.......................................................246
The commissioning tool ICT.................................................247
Description of input signals........................................................249
Description of output signals.....................................................250
Function block...........................................................................251
Input and Output signals............................................................252
Setting parameters....................................................................252
Technical data...........................................................................254
6
Technical reference manual
Table of contents
Technical data...........................................................................257
Four step phase overcurrent protection OC4PTOC ......................257
Introduction................................................................................257
Principle of operation.................................................................257
Function block...........................................................................262
Input and output signals............................................................262
Setting parameters....................................................................264
Technical data...........................................................................269
Instantaneous residual overcurrent protection EFPIOC ................270
Introduction................................................................................270
Principle of operation.................................................................270
Function block...........................................................................271
Input and output signals............................................................271
Setting parameters....................................................................271
Technical data...........................................................................272
Four step residual overcurrent protection EF4PTOC ....................272
Introduction................................................................................272
Principle of operation.................................................................273
Operating quantity within the function..................................273
Internal polarizing.................................................................274
External polarizing for earth-fault function............................276
Base quantities within the protection....................................276
Internal earth-fault protection structure................................276
Four residual overcurrent steps............................................277
Directional supervision element with integrated
directional comparison function............................................278
Second harmonic blocking element.....................................280
Switch on to fault feature......................................................282
Function block...........................................................................284
Input and output signals............................................................285
Setting parameters....................................................................286
Technical data...........................................................................291
Four step directional negative phase sequence overcurrent
protection NS4PTOC .....................................................................291
Introduction................................................................................292
Principle of operation.................................................................292
Operating quantity within the function..................................292
Internal polarizing facility of the function..............................293
External polarizing for negative sequence function..............294
Base quantities within the function.......................................294
Internal negative sequence protection structure..................295
Four negative sequence overcurrent stages........................295
Directional supervision element with integrated
directional comparison function............................................296
7
Technical reference manual
Table of contents
Function block...........................................................................299
Input and output signals............................................................299
Setting parameters....................................................................300
Technical data...........................................................................305
Sensitive directional residual overcurrent and power protection
SDEPSDE .....................................................................................305
Introduction................................................................................305
Principle of operation.................................................................307
Function inputs.....................................................................307
Function block...........................................................................313
Input and output signals............................................................314
Setting parameters....................................................................315
Technical data...........................................................................317
Thermal overload protection, two time constants TRPTTR ...........318
Introduction................................................................................318
Principle of operation.................................................................318
Function block...........................................................................322
Input and output signals............................................................322
Setting parameters....................................................................322
Technical data...........................................................................324
Breaker failure protection CCRBRF ..............................................324
Introduction................................................................................324
Principle of operation.................................................................325
Function block...........................................................................327
Input and output signals............................................................328
Setting parameters....................................................................328
Technical data...........................................................................329
Pole discordance protection CCRPLD ..........................................330
Introduction................................................................................330
Principle of operation.................................................................330
Pole discordance signaling from circuit breaker...................333
Unsymmetrical current detection..........................................333
Function block...........................................................................333
Input and output signals............................................................334
Setting parameters....................................................................334
Technical data...........................................................................335
Directional underpower protection GUPPDUP...............................335
Introduction................................................................................335
Principle of operation.................................................................336
Low pass filtering..................................................................338
Calibration of analog inputs..................................................338
Function block...........................................................................339
Input and output signals............................................................340
8
Technical reference manual
Table of contents
Setting parameters....................................................................340
Technical data...........................................................................341
Directional overpower protection GOPPDOP ................................342
Introduction................................................................................342
Principle of operation.................................................................343
Low pass filtering..................................................................345
Calibration of analog inputs..................................................345
Function block...........................................................................346
Input and output signals............................................................347
Setting parameters....................................................................347
Technical data...........................................................................349
Negativ sequence time overcurrent protection for machines
NS2PTOC ......................................................................................349
Introduction................................................................................349
Principle of operation.................................................................350
Start sensitivity.....................................................................352
Alarm function......................................................................352
Logic diagram.......................................................................352
Function block...........................................................................353
Input and output signals............................................................353
Setting parameters....................................................................354
Technical data...........................................................................355
Accidental energizing protection for synchronous generator
AEGGAPC......................................................................................355
Introduction ...............................................................................355
Principle of operation.................................................................356
Function block...........................................................................357
Input and output signals............................................................357
Setting parameters....................................................................357
Technical data...........................................................................358
9
Technical reference manual
Table of contents
Introduction................................................................................372
Principle of operation.................................................................372
Measurement principle.........................................................373
Time delay............................................................................373
Blocking................................................................................379
Design..................................................................................379
Function block...........................................................................381
Input and output signals............................................................381
Setting parameters....................................................................382
Technical data...........................................................................384
Two step residual overvoltage protection ROV2PTOV .................384
Introduction................................................................................384
Principle of operation.................................................................385
Measurement principle.........................................................385
Time delay............................................................................385
Blocking................................................................................390
Design..................................................................................390
Function block...........................................................................391
Input and output signals............................................................392
Setting parameters....................................................................392
Technical data...........................................................................394
Overexcitation protection OEXPVPH ............................................394
Introduction................................................................................394
Principle of operation.................................................................395
Measured voltage.................................................................397
Operate time of the overexcitation protection.......................398
Cooling.................................................................................402
Overexcitation protection function measurands...................402
Overexcitation alarm............................................................403
Logic diagram.......................................................................403
Function block...........................................................................404
Input and output signals............................................................404
Setting parameters....................................................................404
Technical data...........................................................................406
Voltage differential protection VDCPTOV ......................................406
Introduction................................................................................406
Principle of operation.................................................................406
Function block...........................................................................408
Input and output signals............................................................408
Setting parameters....................................................................408
Technical data...........................................................................409
100% Stator earth fault protection, 3rd harmonic based
STEFPHIZ......................................................................................409
10
Technical reference manual
Table of contents
Introduction................................................................................410
Principle of operation.................................................................411
Function block...........................................................................416
Input and output signals............................................................417
Setting parameters....................................................................418
Technical data...........................................................................418
11
Technical reference manual
Table of contents
Section 12 Control..........................................................................485
12
Technical reference manual
Table of contents
13
Technical reference manual
Table of contents
Introduction...........................................................................526
Principle of operation............................................................526
Function block......................................................................528
Input and output signals.......................................................529
Setting parameters...............................................................530
Reservation input RESIN...........................................................530
Introduction...........................................................................530
Principle of operation............................................................530
Function block......................................................................532
Input and output signals.......................................................533
Setting parameters...............................................................534
Interlocking ....................................................................................534
Introduction................................................................................534
Principle of operation.................................................................534
Logical node for interlocking SCILO .........................................537
Introduction...........................................................................537
Logic diagram.......................................................................537
Function block......................................................................538
Input and output signals.......................................................538
Interlocking for busbar earthing switch BB_ES .........................538
Introduction...........................................................................539
Function block......................................................................539
Logic diagram.......................................................................539
Input and output signals.......................................................539
Interlocking for bus-section breaker A1A2_BS..........................540
Introduction...........................................................................540
Function block......................................................................541
Logic diagram.......................................................................542
Input and output signals.......................................................543
Interlocking for bus-section disconnector A1A2_DC ................544
Introduction...........................................................................545
Function block......................................................................545
Logic diagram.......................................................................546
Input and output signals.......................................................546
Interlocking for bus-coupler bay ABC_BC ................................547
Introduction...........................................................................547
Function block......................................................................548
Logic diagram.......................................................................549
Input and output signals.......................................................551
Interlocking for 1 1/2 CB BH .....................................................554
Introduction...........................................................................554
Function blocks....................................................................555
Logic diagrams.....................................................................557
14
Technical reference manual
Table of contents
15
Technical reference manual
Table of contents
Introduction................................................................................600
Principle of operation.................................................................601
Function block...........................................................................601
Input and output signals............................................................601
Setting parameters....................................................................602
AutomationBits, command function for DNP3.0 AUTOBITS..........602
Introduction................................................................................603
Principle of operation.................................................................603
Function block...........................................................................604
Input and output signals............................................................604
Setting parameters....................................................................605
Single command, 16 signals SINGLECMD....................................619
Introduction................................................................................619
Principle of operation.................................................................619
Function block...........................................................................620
Input and output signals............................................................620
Setting parameters....................................................................621
Section 13 Logic.............................................................................623
Tripping logic SMPPTRC ...............................................................623
Introduction................................................................................623
Principle of operation.................................................................623
Logic diagram.......................................................................625
Function block...........................................................................628
Input and output signals............................................................628
Setting parameters....................................................................629
Technical data...........................................................................630
Trip matrix logic TMAGGIO............................................................630
Introduction................................................................................630
Principle of operation.................................................................630
Function block...........................................................................632
Input and output signals............................................................632
Setting parameters....................................................................633
Configurable logic blocks................................................................634
Introduction................................................................................634
Inverter function block INV........................................................634
OR function block OR................................................................635
AND function block AND...........................................................636
Timer function block TIMER......................................................636
Pulse timer function block PULSETIMER..................................637
Exclusive OR function block XOR.............................................637
Loop delay function block LOOPDELAY...................................638
Set-reset with memory function block SRMEMORY.................638
Reset-set with memory function block RSMEMORY.................639
16
Technical reference manual
Table of contents
Section 14 Monitoring.....................................................................653
Measurements................................................................................653
Introduction................................................................................654
Principle of operation.................................................................655
Measurement supervision....................................................655
Measurements CVMMXN.....................................................659
Phase current measurement CMMXU.................................664
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU..............................................................665
17
Technical reference manual
Table of contents
18
Technical reference manual
Table of contents
Function block...........................................................................717
Input signals..............................................................................717
Technical data...........................................................................717
Indications......................................................................................717
Introduction................................................................................717
Principle of operation.................................................................718
Function block...........................................................................719
Input signals..............................................................................719
Technical data...........................................................................719
Event recorder ...............................................................................719
Introduction................................................................................719
Principle of operation.................................................................719
Function block...........................................................................720
Input signals..............................................................................720
Technical data...........................................................................720
Trip value recorder.........................................................................720
Introduction................................................................................720
Principle of operation.................................................................721
Function block...........................................................................721
Input signals..............................................................................721
Technical data...........................................................................722
Disturbance recorder......................................................................722
Introduction................................................................................722
Principle of operation.................................................................722
Memory and storage............................................................723
IEC 60870-5-103..................................................................724
Function block...........................................................................725
Input and output signals............................................................725
Setting parameters....................................................................725
Technical data...........................................................................725
Section 15 Metering.......................................................................727
Pulse-counter logic PCGGIO..........................................................727
Introduction................................................................................727
Principle of operation.................................................................727
Function block...........................................................................729
Input and output signals............................................................730
Setting parameters....................................................................730
Technical data...........................................................................731
Function for energy calculation and demand handling
ETPMMTR......................................................................................731
Introduction................................................................................731
Principle of operation.................................................................731
Function block...........................................................................732
19
Technical reference manual
Table of contents
20
Technical reference manual
Table of contents
21
Technical reference manual
Table of contents
Design..................................................................................816
Numeric processing module (NUM)..........................................818
Introduction...........................................................................818
Functionality.........................................................................818
Block diagram.......................................................................819
Power supply module (PSM).....................................................820
Introduction...........................................................................820
Design..................................................................................820
Technical data......................................................................820
Local human-machine interface (Local HMI).............................821
Transformer input module (TRM)..............................................821
Introduction...........................................................................821
Design..................................................................................821
Technical data......................................................................822
Analog digital conversion module, with time
synchronization (ADM) .............................................................823
Introduction...........................................................................823
Design..................................................................................823
Binary input module (BIM).........................................................825
Introduction...........................................................................825
Design..................................................................................825
Technical data......................................................................829
Binary output modules (BOM)...................................................829
Introduction...........................................................................829
Design..................................................................................829
Technical data......................................................................831
Binary input/output module (IOM)..............................................832
Introduction...........................................................................832
Design..................................................................................832
Technical data......................................................................834
mA input module (MIM).............................................................835
Introduction...........................................................................835
Design..................................................................................835
Technical data......................................................................837
Serial and LON communication module (SLM) ........................837
Introduction...........................................................................837
Design..................................................................................837
Technical data......................................................................839
Optical ethernet module (OEM).................................................839
Introduction...........................................................................839
Functionality.........................................................................839
Design..................................................................................840
Technical data......................................................................840
22
Technical reference manual
Table of contents
23
Technical reference manual
Table of contents
Section 20 Labels...........................................................................885
Labels on IED.................................................................................885
Labels on injection equipment........................................................888
Section 23 Glossary.......................................................................969
24
Technical reference manual
1MRK 502 027-UEN A Section 1
Introduction
Section 1 Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineeringmanual
Installation and
Commissioning manual
Operator’s manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN
25
Technical reference manual
Section 1 1MRK 502 027-UEN A
Introduction
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.
• Local HMI describes the control panel on the IED and explains display
characteristics, control keys and various local HMI features.
• Basic IED functions presents functions for all protection types that are
included in all IEDs, for example, time synchronization, self supervision with
event list, test mode and other general functions.
• Current protection describes functions, for example, over current protection,
breaker failure protection and pole discordance.
• Voltage protection describes functions for under voltage and over voltage
protection and residual over voltage protection.
• Frequency protection describes functions for over frequency, under frequency
and rate of change of frequency protection.
• Multipurpose protection describes the general protection function for current
and voltage.
• Secondary system supervision describes current based functions for current
circuit supervision and fuse failure supervision.
• Control describes control functions, for example, synchronization and
energizing check and other product specific functions.
• Logic describes trip logic and related functions.
• Monitoring describes measurement related functions that are used to provide
data regarding relevant quantities, events and faults, for example.
• Station communication describes Ethernet based communication in general,
including the use of IEC 61850 and horizontal communication via GOOSE.
• Remote communication describes binary and analog signal transfer, and the
associated hardware.
26
Technical reference manual
1MRK 502 027-UEN A Section 1
Introduction
1.1.3.1 Introduction
Logic diagrams
Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.
Signal names
Input and output logic signals consist of two groups of letters separated by two
dashes. The first group consists of up to four letters and presents the abbreviated
name for the corresponding function. The second group presents the functionality
of the particular signal. According to this explanation, the meaning of the signal
BLKTR in figure 4 is as follows:
• BLKTR informs the user that the signal will BLOCK the TRIP command from
the under-voltage function, when its value is a logical one (1).
Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed.
Input and output signals can be configured using the ACT tool. They can be
connected to the inputs and outputs of other functions and to binary inputs and
outputs. Examples of input signals are BLKTR, BLOCK and VTSU. Examples
output signals are TRIP, START, STL1, STL2, STL3.
27
Technical reference manual
Section 1 1MRK 502 027-UEN A
Introduction
Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their
values are high (1) only when the corresponding setting parameter is set to the
symbolic value specified within the frame. Example is the signal Block TUV=Yes.
Their logical values correspond automatically to the selected setting value.
Internal signals
Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts and
continues, see figure 1.
BLKTR
TEST
TEST
&
Block TUV=Yes BLOCK-int.
>1
BLOCK
VTSU
BLOCK-int.
&
STUL1N
BLOCK-int.
& >1 & TRIP
t
STUL2N
BLOCK-int.
START
&
STUL3N
STL1
STL2
STL3
xx04000375.vsd
IEC04000375 V1 EN
External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix “-cont.”, see figure 2 and figure 3.
28
Technical reference manual
1MRK 502 027-UEN A Section 1
Introduction
STZMPP-cont.
>1
STCND
& STNDL1L2-cont.
1L1L2
STNDL2L3-cont.
&
1L2L3
& STNDL3L1-cont.
1L3L1
& STNDL1N-cont.
1L1N
& STNDL2N-cont.
1L2N
STNDL3N-cont.
&
1L3N
>1 STNDPE-cont.
>1
1--VTSZ 1--STND
>1 &
1--BLOCK
BLK-cont.
xx04000376.vsd
IEC04000376 V1 EN
STNDL1N-cont.
>1
STNDL2N-cont. 15 ms
& t STL1
STNDL3N-cont.
STNDL1L2-cont. >1 15 ms
& t STL2
STNDL2L3-cont.
15 ms
STNDL3L1-cont. & t STL3
>1
15 ms
& t START
>1
BLK-cont.
xx04000377.vsd
IEC04000377 V1 EN
29
Technical reference manual
Section 1 1MRK 502 027-UEN A
Introduction
Input and output signals are presented in two separate tables. Each table consists of
two columns. The first column contains the name of the signal and the second
column contains the description of the signal.
Input signals are always on the left hand side and output signals on the right hand
side. Settings are not displayed. Special kinds of settings are sometimes available.
These are supposed to be connected to constants in the configuration scheme and
are therefore depicted as inputs. Such signals will be found in the signal list but
described in the settings table.
• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set a signal name of
their own in PCM600.
• The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
IEC 61850 - 8 -1
Logical Node Mandatory
signal (*)
Inputs Outputs
PCGGIO
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
^SCAL_VAL
en05000511-1-en.vsd
User defined
name (^)
Diagram
Number
IEC05000511 V2 EN
These are presented in tables and include all parameters associated with the
function in question.
30
Technical reference manual
1MRK 502 027-UEN A Section 1
Introduction
The technical data section provides specific technical information about the
function or hardware described.
Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in
the protective devices. The installation and commissioning personnel must have a
basic knowledge in the handling electronic equipment.
31
Technical reference manual
Section 1 1MRK 502 027-UEN A
Introduction
32
Technical reference manual
1MRK 502 027-UEN A Section 2
Analog inputs
2.1 Introduction
Analog input channels must be configured and set properly to get correct
measurement results and correct protection operations. For power measuring and
all directional and differential functions the directions of the input currents must be
defined properly. Measuring and protection algorithms in the IED use primary
system quantities. Set values are done in primary quantities as well and it is
important to set the data about the connected current and voltage transformers
properly.
The direction of a current to the IED depends on the connection of the CT. The
main CTs are typically star connected and can be connected with the star point to
the object or from the object. This information must be set to the IED.
• Positive value of current or power means quantity direction into the object.
• Negative value of current or power means quantity direction out from the object.
33
Technical reference manual
Section 2 1MRK 502 027-UEN A
Analog inputs
en05000456.vsd
IEC05000456 V1 EN
The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.
The CT and VT ratio and the name on respective channel is done under Main
menu/Hardware/Analog modules in the Parameter Settings tool.
34
Technical reference manual
1MRK 502 027-UEN A Section 2
Analog inputs
35
Technical reference manual
Section 2 1MRK 502 027-UEN A
Analog inputs
36
Technical reference manual
1MRK 502 027-UEN A Section 2
Analog inputs
37
Technical reference manual
Section 2 1MRK 502 027-UEN A
Analog inputs
38
Technical reference manual
1MRK 502 027-UEN A Section 2
Analog inputs
39
Technical reference manual
Section 2 1MRK 502 027-UEN A
Analog inputs
40
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
The local human machine interface is available in a small and a medium sized
model. The difference between the two models is the size of the LCD. The small
size LCD can display seven lines of text and the medium size LCD can display the
single line diagram with up to 15 objects on each page. Up to 12 single line
diagram pages can be defined, depending on the product capability.
41
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
IEC05000055-LITEN V1 EN
IEC05000056-LITEN V1 EN
42
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
3.2.1 Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and
time. The remaining 5 lines are dynamic. This LCD has no graphic display potential.
3.2.2 Design
The local HMI is identical for both the 1/2, 3/4 and 1/1 cases. The different parts of
the small local HMI are shown in figure 8
43
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
1 2 3
en05000055.eps
8 7
IEC05000055-CALLOUT V1 EN
44
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
3.3.1 Medium
The following case sizes can be equipped with the medium size LCD:
• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD
is required.
3.3.2 Design
The different parts of the medium size local HMI are shown in figure 9. The local
HMI exists in an IEC version and in an ANSI version. The difference is on the
keypad operation buttons and the yellow LED designation.
45
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
1 2 3
en05000056.eps
8 7
IEC05000056-CALLOUT V1 EN
46
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
3.4 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.
IEC05000153 V1 EN
Table 7 describes the HMI keys that are used to operate the IED.
Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN
Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN
Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN
47
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
Key Function
Press to navigate forward between screens and move right in editing mode.
IEC05000109 V1 EN
Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN
Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN
Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN
3.5 LED
3.5.1 Introduction
The LED module is a unidirectional means of communicating. This means that
events may occur that activate a LED in order to draw the operators attention to
something that has occurred and needs some sort of action.
48
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
Alarm indication LEDs and hardware associated LEDs are located on the right
hand side of the front panel. Alarm LEDs are located on the right of the LCD
screen and show steady or flashing light.
Alarm LEDs can be configured in PCM600 and depend on the binary logic.
Therefore they can not be configured on the local HMI.
The RJ45 port has a yellow LED indicating that communication has been
established between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
3.6.1 Introduction
The local HMI can be adapted to the application configuration and to user preferences.
49
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
3.6.3.1 Design
The function block LocalHMI controls and supplies information about the status of
the status indication LEDs. The input and output signals of local HMI are
configured with PCM600.
The function block can be used if any of the signals are required in a configuration
logic.
See section "Status indication LEDs" for information about the LEDs.
IEC05000773-2-en.vsd
IEC05000773 V2 EN
50
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
3.6.4.1 Introduction
The function block LEDGEN controls and supplies information about the status of
the indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.
Each indication LED on the local HMI can be set individually to operate in six
different sequences
The light from the LEDs can be steady (-S) or flashing (-F). See the technical
reference manual for more information.
3.6.4.2 Design
The information on the LEDs is stored at loss of the auxiliary power to the IED in
some of the modes of LEDGEN. The latest LED picture appears immediately after
the IED is successfully restarted.
Operating modes
• Collecting mode
51
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
• Re-starting mode
• In the re-starting mode of operation each new start resets all previous
active LEDs and activates only those which appear during one
disturbance. Only LEDs defined for re-starting mode with the latched
sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a
new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has
elapsed.
Acknowledgment/reset
• From local HMI
• Active indications can be acknowledged or reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function
is positive edge triggered, not level triggered. The acknowledged or reset
is performed via the reset button and menus on the local HMI. See the
operator's manual for more information.
• Automatic reset
• Automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When
automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.
Operating sequences
The operating sequences can be of type Follow or Latched.
• For the Follow type the LED follows the input signal completely.
• For the Latched type each LED latches to the corresponding input signal until
it is reset.
52
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
Figure 12 show the function of available sequences that are selectable for each
LED separately.
The letters S and F in the sequence names have the meaning S = Steady and F =
Flashing.
At the activation of the input signal, the indication operates according to the
selected sequence diagrams.
In the sequence diagrams the LEDs have the characteristics as shown in figure 12.
en05000506.vsd
IEC05000506 V1 EN
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN
Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing
instead of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if
53
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing
light have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the
activation of the input signal, the indication will light up with a steady light. The
difference to sequence 3 and 4 is that indications that are still activated will not be
affected by the reset that is, immediately after the positive edge of the reset has
been executed a new reading and storing of active signals is performed. Every LED
is independent of the other LEDs in its operation.
Activating
signal
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN
Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the
positive edge of that the manual reset has been executed a new reading and storing
54
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
of active signals is performed. LEDs set for sequence 6 are completely independent
in its operation of LEDs set for other sequences.
Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is
activated until a settable time, tRestart, has elapsed after that all activating signals
for the LEDs set as LatchedReset-S have reset. However if all activating signals
have reset and some signal again becomes active before tRestart has elapsed, the
tRestart timer does not restart the timing sequence. A new disturbance start will be
issued first when all signals have reset after tRestart has elapsed. A diagram of this
functionality is shown in figure 16.
From
disturbance
length control ³1 New
per LED ³1 disturbance
set to
sequence 6
tRestart
& t
&
³1
³1
&
en01000237.vsd
IEC01000237 V1 EN
In order not to have a lock-up of the indications in the case of a persisting signal
each LED is provided with a timer, tMax, after which time the influence on the
definition of a disturbance of that specific LED is inhibited. This functionality is
shown i diagram in figure 17.
Activating signal
To LED
To disturbance
AND
tMax length control
t
en05000507.vsd
IEC05000507 V1 EN
55
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN
Figure 19 shows the timing diagram for a new indication after tRestart time has
elapsed.
Disturbance Disturbance
tRestart tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN
56
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
Figure 20 shows the timing diagram when a new indication appears after the first
one has reset but before tRestart has elapsed.
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN
57
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
IEC05000508_2_en.vsd
IEC05000508 V2 EN
58
Technical reference manual
1MRK 502 027-UEN A Section 3
Local HMI
59
Technical reference manual
Section 3 1MRK 502 027-UEN A
Local HMI
60
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.1 Authorization
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:
Be sure that the user logged on to the IED has the access required
when writing particular data to the IED from PCM600.
61
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the User Management Tool.
62
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: “No
user defined!”
If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
60 minutes at delivery.
If there are one or more users created with the User Management Tool and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.
The cursor is focused on the User identity field, so upon pressing the “E” key, the
user can change the user name, by browsing the list of users, with the “up” and
“down” arrows. After choosing the right user name, the user must press the “E”
key again. When it comes to password, upon pressing the “E” key, the following
character will show up: “$”. The user must scroll for every letter in the password.
After all the letters are introduced (passwords are case sensitive) choose OK and
press the “E” key again.
If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses “Cancel”.
4.2.1 Introduction
Self supervision with internal event list function listens and reacts to internal
system events, generated by the different built-in self-supervision elements. The
internal events are saved in an internal event list.
63
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.
IEC04000520 V1 EN
64
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
IO fail
OR Set e.g. BIM 1 Error
IO stopped
Reset
IO started
e.g. IOM2 Error OR
e.g. IO (n) Error Internal
OR FAIL
LON ERROR
TIMESYNCHERROR
OR TIMESYNCHERROR
Time reset Set
SYNCH OK Reset
SETCHGD
Settings changed
1 second pulse
en04000519-1.vsd
IEC04000519 V2 EN
Some signals are available from the INTERRSIG function block. The signals from
this function block are sent as events to the station level of the control system. The
signals from the INTERRSIG function block can also be connected to binary
outputs for signalization via output relays or they can be used as conditions for
other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix tool. Error signals from time synchronization can be obtained
from the time synchronization block TIME.
Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal status of the IED, they are also
called internal signals. The internal signals can be divided into two groups.
• Standard signals are always presented in the IED, see Table 15.
• Hardware dependent internal signals are collected depending on the hardware
configuration, see Table 16.
65
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
66
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see Figure
25.
ADx
Adx_Low
x1
u1
x2
Adx
Adx_High Controller
x1
u1
x2
en05000296-2-en.vsd
IEC05000296 V2 EN
67
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The technique to split the analog input signal into two A/D converters with
different amplification makes it possible to supervise the incoming signals under
normal conditions where the signals from the two converters should be identical.
An alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.
When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given.
IEC09000787 V1 EN
68
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.3.1 Introduction
The time synchronization source selector is used to select a common source of
absolute time for the IED when it is a part of a protection system. This makes it
possible to compare event- and disturbance data between all IEDs in a station
automation system possible.
Time definitions
The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called
the clock accuracy and means how much the error increases, that is how much the
clock gains or loses time. A disciplined (trained) clock knows its own faults and
tries to compensate for them.
69
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
External
Synchronization
sources Time tagging and general synchronisation
Off
Comm- Protection
LON Events
Time- unication and control
SPA Regulator functions
Min. pulse
(Setting,
GPS see
SW-time
technical
SNTP
reference
DNP manual) Connected when GPS-time is
IRIG-B used for differential protection
PPS
*IEC 61850-9-2
IEC08000287-2-en.vsd
IEC08000287 V2 EN
All time tagging is performed by the software clock. When for example a status
signal is changed in the protection system with the function based on free running
hardware clock, the event is time tagged by the software clock when it reaches the
event recorder. Thus the hardware clock can run independently.
The echo mode for the differential protection is based on the hardware clock. Thus,
there is no need to synchronize the hardware clock and the software clock.
The synchronization of the hardware clock and the software clock is necessary only
when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential
protection. The two clock systems are synchronized by a special clock
synchronization unit with two modes, fast and slow. A special feature, an
automatic fast clock time regulator is used. The automatic fast mode makes the
synchronization time as short as possible during start-up or at interruptions/
disturbances in the GPS timing. The setting fast or slow is also available on the
local HMI.
If a GPS clock is used for other 670 series IEDs than line differential RED670, the
hardware and software clocks are not synchronized
70
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
When the time difference is >16us, the differential function is blocked and the time
regulator for the hardware clock is automatically using a fast mode to synchronize
the clock systems. The time adjustment is made with an exponential function, i.e.
big time adjustment steps in the beginning, then smaller steps until a time deviation
between the GPS time and the differential time system of >16us has been reached.
Then the differential function is enabled and the synchronization remains in fast
mode or switches to slow mode, depending on the setting.
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical
structure. A function is synchronized from a higher level and provides
synchronization to lower levels.
Synchronization from
a higher level
Function
Optional synchronization of
modules at a lower level
IEC09000342-1-en.vsd
IEC09000342 V1 EN
71
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The IED has a built-in real-time clock (RTC) with a resolution of one second. The
clock has a built-in calendar that handles leap years through 2038.
Synchronization messages configured as coarse are only used for initial setting of
the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds resets the time.
Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized
for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. Normally, it takes 20 minutes to reach full accuracy.
72
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
Three main alternatives of external time synchronization are available. Either the
synchronization message is applied via any of the communication ports of the IED
as a telegram message including date and time or as a minute pulse, connected to a
binary input, or via GPS. The minute pulse is used to fine tune already existing
time in the IEDs.
• Coarse message is sent every minute and comprises complete date and time,
that is, year, month, day, hours, minutes, seconds and milliseconds.
• Fine message is sent every second and comprises only seconds and milliseconds.
IEC60870-5-103 is not used to synchronize the IED, but instead the offset between
the local time in the IED and the time received from 103 is added to all times (in
events and so on) sent via 103. In this way the IED acts as it is synchronized from
various 103 sessions at the same time. Actually, there is a “local” time for each 103
session.
73
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The minute pulse is connected to any channel on any Binary Input Module in the
IED. The electrical characteristic is thereby the same as for any other binary input.
The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute
after the last flank.
Pulse data:
en05000251.vsd
IEC05000251 V1 EN
The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.
74
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
If contact bounces occurs, only the first pulse will be detected as a minute pulse.
The next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, for example, it is exactly 60 seconds between the
pulses, contact bounces might occur 49 ms after the actual minute pulse without
effecting the system. If contact bounces occurs more than 50 ms, for example, it is
less than 59950 ms between the two most adjacent positive (or negative) flanks, the
minute pulse will not be accepted.
To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic
BNC connector and one optical ST connector. IRIG-B 12x messages can be
supplied via the galvanic interface, and IRIG-B 00x messages can be supplied via
either the galvanic interface or the optical interface, where x (in 00x or 12x) means
a number in the range of 1-7.
“00” means that a base band is used, and the information can be fed into the IRIG-
B module via the BNC contact or an optical fiber. “12” means that a 1 kHz
modulation is used. In this case the information must go into the module via the
BNC connector.
The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
75
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
compatible with IRIG-B and contains year information and information of the time-
zone.
It is recommended to use IEEE 1344 for supplying time information to the IRIG-B
module. In this case, send also the local time in the messages, as this local time
plus the TZ Offset supplied in the message equals UTC at all times.
IEC05000425-2-en.vsd
IEC05000425 V2 EN
76
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
77
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
78
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.4.1 Introduction
Use the six sets of settings to optimize the IED operation for different system
conditions. Creating and switching between fine-tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can
cope with a variety of system scenarios.
79
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between.
ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
+RL2 ACTIVATE GROUP 1
IOx-Bly1 ActiveGroup
Æ ACTGRP1 GRP1
IOx-Bly2
Æ ACTGRP2 GRP2
IOx-Bly3
Æ ACTGRP3 GRP3
IOx-Bly4
Æ ACTGRP4 GRP4
IOx-Bly5
Æ ACTGRP5 GRP5
IOx-Bly6 ACTGRP6
Æ GRP6
SETCHGD
en05000119.vsd
IEC05000119 V2 EN
The above example also includes seven output signals, for confirmation of which
group that is active.
SETGRPS function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used
will be shown on the Parameter Setting Tool.
80
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
IEC05000433_2_en.vsd
IEC05000433 V2 EN
SETGRPS
MAXSETGR
IEC05000716_2_en.vsd
IEC05000716 V2 EN
81
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
4.5.1 Introduction
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.
The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:
• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group
82
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input Function
1 Activated
0 Deactivated
IEC09000946-1-en.vsd
IEC09000946 V1 EN
4.6.1 Introduction
When the Test mode functionality TESTMODE function is activated, protection
functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
83
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.
While the IED is in test mode, the ACTIVE output of the function block
TESTMODE is activated. The other outputs of the function block TESTMODE
shows the generator of the “Test mode: On” state — input from configuration
(OUTPUT output is activated) or setting from local HMI (SETTING output is
activated).
While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be unblocked individually regarding functionality
and event signalling.
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode
(output ACTIVE is activated), see example in figure 35. When leaving the test
mode, that is entering normal mode, these blockings are disabled and everything is
set to normal operation. All testing will be done with actually set and configured
values within the IED. No settings will be changed, thus no mistakes are possible.
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.
When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the
IED will re-enter test mode and all functions will be blocked, also
functions that were unblocked before the change. During the re-
entering to test mode, all functions will be temporarily unblocked
for a short time, which might lead to unwanted operations. This is
only valid if the IED is put in TEST mode by a binary input, not by
local HMI.
84
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
Each of the protection functions includes the blocking from the TESTMODE
function block. A typical example from the undervoltage function is shown in
figure 35.
The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a maintenance test.
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN
IEC09000219-1.vsd
IEC09000219 V1 EN
85
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
4.7.1 Introduction
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
86
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.8.1 Introduction
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:
• IEDProdType
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
87
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
• IEDProdType
• Describes the type of the IED (like REL, REC or RET). Example: REL670
• ProductDef
• Describes the release number, from the production. Example: 1.2.2.0
• FirmwareVer
• Describes the firmware version. Example: 1.4.51
• Firmware versions numbers are “running” independently from the
release production numbers. For every release numbers (like 1.5.0.17)
there can be one or more firmware versions, depending on the small
issues corrected in between releases.
• IEDMainFunType
• Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).
• SerialNo
• OrderingNo
• ProductionDate
4.9.1 Introduction
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how binary inputs are brought
in for one IED configuration.
88
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
IEC05000434-2-en.vsd
IEC05000434 V2 EN
89
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
4.10.1 Introduction
The Signal matrix for binary outputs (SMBO) function is used within the
Application Configuration Tool (ACT) in direct relation with the Signal Matrix
Tool (SMT), see the application manual to get information about how binary inputs
are sent from one IED configuration.
IEC05000439-2-en.vsd
IEC05000439 V2 EN
90
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.11.1 Introduction
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how milliamp (mA) inputs are
brought in for one IED configuration.
91
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
IEC05000440-2-en.vsd
IEC05000440 V2 EN
4.12.1 Introduction
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.
92
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. AIN is always the neutral
current, calculated residual sum or the signal connected to GRPxN. Note that
function block will always calculate the residual sum of current/voltage if the input
is not connected in SMT. Applications with a few exceptions shall always be
connected to AI3P.
IEC10000060-1-en.vsd
IEC10000060 V1 EN
93
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.
The same phase-phase voltage connection principle shall be used for frequency
tracking master SMAI block in pump-storage power plant applications when
swapping of positive and negative sequence voltages happens during generator/
motor mode of operation.
IEC05000705-2-en.vsd
IEC05000705 V2 EN
SMAI2
BLOCK AI3P
^GRP2L1 AI1
^GRP2L2 AI2
^GRP2L3 AI3
^GRP2N AI4
TYPE AIN
IEC07000130-2-en.vsd
IEC07000130 V2 EN
94
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
95
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
96
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.13.1 Introduction
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.
97
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
IEC05000441-2-en.vsd
IEC05000441 V2 EN
98
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
4.14.1 Introduction
Authority status (ATHSTAT) function is an indication function block for user log-
on activity.
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC
61850 station bus.
IEC06000503-2-en.vsd
IEC06000503 V2 EN
99
Technical reference manual
Section 4 1MRK 502 027-UEN A
Basic IED functions
4.15.1 Introduction
The Denial of service functions (DOSFRNT, DOSOEMAB and DOSOEMCD) are
designed to limit overload on the IED produced by heavy Ethernet network traffic.
The communication facilities must not be allowed to compromise the primary
functionality of the device. All inbound network traffic will be quota controlled so
that too heavy network loads can be controlled. Heavy network load might for
instance be the result of malfunctioning equipment connected to the network.
IEC09000749-1-en.vsd
IEC09000749 V1 EN
DOSOEMAB
LINKUP
WARNING
ALARM
IEC09000750-1-en.vsd
IEC09000750 V1 EN
100
Technical reference manual
1MRK 502 027-UEN A Section 4
Basic IED functions
DOSOEMCD
LINKUP
WARNING
ALARM
IEC09000751-1-en.vsd
IEC09000751 V1 EN
4.15.4 Signals
Table 57: DOSFRNT Output signals
Name Type Description
LINKUP BOOLEAN Ethernet link status
WARNING BOOLEAN Frame rate is higher than normal state
ALARM BOOLEAN Frame rate is higher than throttle state
4.15.5 Settings
The function does not have any parameters available in the local HMI or PCM600.
101
Technical reference manual
102
1MRK 502 027-UEN A Section 5
Differential protection
5.1.1 Introduction
Short circuit between the phases of the stator windings causes normally very large
fault currents. The short circuit gives risk of damages on insulation, windings and
stator iron core. The large short circuit currents cause large forces, which can cause
damage even to other components in the power plant, such as turbine and generator-
turbine shaft.
To limit the damage due to stator winding short circuits, the fault clearance must be
as fast as possible (instantaneous). If the generator block is connected to the power
system close to other generating blocks, the fast fault clearance is essential to
maintain the transient stability of the non-faulted generators.
Normally, the short circuit fault current is very large, that is, significantly larger
than the generator rated current. There is a risk that a short circuit can occur
between phases close to the neutral point of the generator, thus causing a relatively
small fault current. The fault current can also be limited due to low excitation of
the generator. Therefore, it is desired that the detection of generator phase-to-phase
short circuits shall be relatively sensitive, detecting small fault currents.
It is also of great importance that the generator differential protection does not trip
for external faults, with large fault currents flowing from the generator.
To combine fast fault clearance, as well as sensitivity and selectivity, the generator
differential protection is normally the best choice for phase-to-phase generator
short circuits.
103
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IEC06000430-2-en.vsd
IEC06000430 V2 EN
If the fault is internal, the faulty generator must be quickly tripped, that is,
disconnected from the network, the field breaker tripped and the power to the
prime mover interrupted.
GENPDIF function always uses reference (default) directions of CTs towards the
protected generator as shown in figure 48. Thus, it always measures the currents on
the two sides of the generator with the same reference direction towards the
generator windings. With the orientation of CTs as in figure 48, the difference of
currents flowing in, and out, of a separate stator winding phase is simply obtained
by summation of the two currents fed to the differential protection function.
Numerical IEDs have brought a large number of advantages and new functionality
to the protective relaying. One of the benefits is the simplicity and accuracy of
calculating symmetrical components from individual phase quantities. Within the
firmware of a numerical IED, it is no more difficult to calculate negative-sequence
components than it is to calculate zero-sequence components. Diversity of
operation principles integrated in the same protection function enhances the overall
performance without a significant increase in cost.
104
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
and the 2nd and 5th harmonic components of the instantaneous differential currents.
The instantaneous differential currents are calculated from the input samples of the
instantaneous values of the currents measured at both ends of the stator winding.
The DC and the 2nd and 5th harmonic components of each separate instantaneous
differential current are extracted inside the differential protection.
The fundamental frequency phasors of the phase currents from both sides of the
generator (the neutral side and the terminal side) are delivered to the differential
protection function by the pre-processing module of the IED.
The fundamental frequency RMS differential current is a vectorial sum (that is,
sum of fundamental frequency phasors) of the individual phase currents from the
two sides of the protected generator. The magnitude of the fundamental frequency
RMS differential current, in phase L1, is as calculated in equation 1:
One common fundamental frequency bias current is used. The bias current is the
magnitude of the highest measured current in the protected circuit. The bias current
is not allowed to drop instantaneously, instead, it decays exponentially with a
predefined time constant. These principles make the differential IED more secure,
with less risk to operate for external faults. The “maximum” principle brings as
well more meaning to the breakpoint settings of the operate-restrain characteristic.
105
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IL1n IL1t
IL1t Idiff
IL1n
IEC07000018_3_en.vsd
IEC07000018 V3 EN
IL1n IL1t
IL1t IL1n
Idiff = 0 en07000019-2.vsd
IEC07000019 V2 EN
106
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
The stabilized differential protection applies a differential (operate) current, and the
common bias (restrain) current, on the operate-restrain characteristic, as shown in
figure 52. Here, the actual limit, where the protection can operate, is dependent on
the bias (restrain) current. The operate value, is stabilized by the bias current. This
operate – restrain characteristic is represented by a double-slope, double-breakpoint
characteristic. The restrained characteristic is determined by the following 5 settings:
Note that both slopes are calculated from the characteristics break
points.
107
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
Note that both slopes are calculated from the characteristics break
points.
AddTripDelay: If the input DESENSIT is activated also the operation time of the
protection function can be increased by using the setting AddTripDelay.
operate current
[ times IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1 Section 2 Section 3
SlopeSection3
1
TempIdMin
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en06000637.vsd
IEC06000637 V2 EN
108
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
taken as a kind of bias in the sense that the highest sensitivity of the differential
protection is inversely proportional to the ratio of this DC component to the
maximum fundamental frequency differential current. Similar to the
‘desensitization’ described above, a separate (temporary) additional limit is
activated. The value of this limit is limited to either the generator rated current, or 3
times IdMin, whichever is smaller. This temporary extra limit decays exponentially
from its maximum value with a time constant equal to T = 1 second. This feature
must be used when unmatched CTs are used on the generator or shut reactor,
especially where a long DC time constant can be expected. The new limit is
superposed the otherwise unchanged operate-bias characteristic, and temporarily
determines the highest sensitivity of the differential protection. This temporary
sensitivity must be lower than the sensitivity in section 1 of the operate-bias
characteristic.
If a fault is classified as internal, then any eventual block signals by the harmonic
criterion are ignored, and the differential protection can operate very quickly
without any further delay.
If all the differential currents which caused their respective start signals to be set,
are free of harmonic pollution, that is, if no harmonic block signal has been set,
then a (minor) internal fault, simultaneous with a predominant external fault, can
be suspected. This conclusion can be drawn because at external faults, major false
109
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
differential currents can only exist when one or more current transformers saturate
transiently. In this case, the false instantaneous differential currents are highly
polluted by higher harmonic components, the 2nd, and the 5th.
The internal or external fault discriminator responds to the relative phase angles of
the negative sequence fault currents at both ends of the stator winding. Observe
that the source of the negative sequence currents at unsymmetrical faults is at the
fault point.
• If the two negative sequence currents, as seen by the differential relay, flow in
the same direction (that is with the CTs oriented as in figure 48), the fault is
internal. If the two negative sequence currents flow in opposite directions, the
fault is external.
• Under external fault condition, the relative angle is theoretically equal to 180°.
Under internal fault condition, the angle is ideally 0°, but due to possible
different negative-sequence impedance angles on both sides of the internal
fault, it may differ somewhat from 0°.
The setting NegSeqROA, as shown in figure 53, represents the so called Relay
Operate Angle, which determines the boundary between the internal and external
fault regions. It can be selected in the range ±30° to ±90°, with a step of 1°. The
default value is ±60°. The default setting, ±60°, favors somewhat security in
comparison to dependability.
110
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
this value persists, then this is an indication that no directional comparison has
been made. Neither internal, nor external fault (disturbance) is declared in this case.
90 deg
120 deg
NegSeqROA
Angle could not be (Relay Operate Angle)
measured. One or both
currents too small
Internal fault
region
IminNegSeq
External fault
region
Internal /
external fault
boundary.
Default ± 60 deg
The characteristic is defined by the
settings:
IMinNegSeq and NegSeqROA
270 deg
en06000433-2.vsd
IEC06000433 V2 EN
Figure 53: NegSeqROA determines the boundary between the internal and
external fault regions
111
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
Harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal there was to prevent an unwanted trip
command due to magnetizing inrush currents at switching operations, due to
magnetizing currents at over-voltages, or external faults. Harmonic restrain is just
as useful with Generator differential protection GENPDIF. The harmonic analysis
is only executed in those phases, where start signals have been set.
At external faults dangerous false differential currents can arise for different
reasons, mainly due to saturation of one or more current transformers. The false
differential currents display in this case a considerable amount of higher
harmonics, which can, therefore, be used to prevent an unwanted trip of a healthy
generator or shunt reactor.
The cross-block logic says that in order to issue a common trip command, the
harmonic contents in all phases with a start signal set (start = TRUE) must be
below the limit defined with the setting HarmDistLimit. In the opposite case, no
trip command will be issued.
The cross-block logic is active if the setting OpCrossBlock = Yes. By always using
the cross-block logic, the false trips can be prevented for external faults in cases
where the internal or external fault discriminator should for some reason fail to
declare an external fault. For internal faults, the higher frequency components of an
instantaneous differential current are most often relatively low, compared to the
fundamental frequency component. While for an external (heavy) fault, they can be
relatively high. For external faults with moderate fault currents, there can be little
or no current transformer saturation and only small false differential currents.
112
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
TRIP
Signals
Start
Phasors IL1N, IL2N,IL3N Magnitude phase
Calculation Idiff and Ibias Diff.prot. selective
Idiff and Ibias characteristic
Phasors IL1T, IL2T,IL3T
START
Signals
BLOCK
Signals
en06000434-2.vsd
IEC06000434 V3 EN
Figure 54: Simplified principle design of the Generator differential protection GENPDIF
Simplified logic diagrams of the function are shown in figures 55, 56, 57 and 58.
113
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
BLKUNRES
IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG
IBIAS STL1
AND
BLOCK
BLKRES
INTFAULT TRIPRESL1
AND
OR 1
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
AND
OpCrossBlock=On
en07000020.vsd
IEC07000020 V2 EN
Internal/ EXTFAULT
Neg.Seq. Diff External INTFAULT
Current Fault
Contributions discrimin
ator TRNSSENS
AND
OpNegSeqDiff=On
IBIAS
a
b>a
b
Constant
BLKNSSEN
BLKNSUNR
BLOCK
TRNSUNR
STL1 AND
STL2
OR
STL3
en07000021.vsd
IEC07000021 V2 EN
114
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
STL1
STL2 START
OR
STL3
BLKHL1
BLKHL2 BLKH
OR
BLKHL3
en07000022.vsd
IEC07000022 V1 EN
TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3
TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3
TRIP
TRNSSENS OR
TRNSUNR
en07000023.vsd
IEC07000023 V1 EN
115
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IEC11000212-1-en.vsd
IEC11000212 V1 EN
116
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
117
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
118
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
SYMBOL-BB V1 EN
SYMBOL-BB V1 EN
5.2.1 Introduction
The Transformer differential protection, two-winding (T2WPDIF) and Transformer
differential protection, three-winding (T3WPDIF) are provided with internal CT
ratio matching and vector group compensation and settable zero sequence current
elimination.
The function can be provided with up to three-phase sets of current inputs. All
current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer in multi-breaker station arrangements.
119
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN
two-winding power
transformer with
unconnected delta
xx05000049.vsd tertiary winding
IEC05000049 V1 EN
two-winding power
transformer with two
circuit breakers on
xx05000050.vsd one side
IEC05000050 V1 EN
two-winding power
transformer with two
circuit breakers and
two CT-sets on both
sides
xx05000051.vsd
IEC05000051 V1 EN
Three-winding applications
three-winding power
transformer with all
three windings
connected
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with two
circuit breakers and
two CT-sets on one
side
xx05000053.vsd
IEC05000053 V1 EN
Autotransformer with
two circuit breakers
and two CT-sets on
two out of three sides
xx05000057.vsd
IEC05000057 V1 EN
120
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
The setting facilities cover the applications of the differential protection to all types
of power transformers and auto-transformers with or without load tap changer as
well as for shunt reactors or and local feeders within the station. An adaptive
stabilizing feature is included for heavy through-faults.By introducing the load tap
changer position, the differential protection pick-up can be set to optimum
sensitivity thus covering internal faults with low fault level.
The main CTs are normally supposed to be star connected. The main CTs can be
earthed in anyway (that is, either "ToObject" or "FromObject"). However
internally the differential function will always use reference directions towards the
protected transformer as shown in figure 61. Thus the IED will always internally
measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in figure 61.For more
information see the Application manual
IW1 IW2
Z1S1 Z1S2
E1S1 E1S2
IW1 IW2
IED
en05000186.vsd
IEC05000186 V1 EN
Even in a healthy power transformer, the currents are generally not equal when
they flow through the power transformer, due to the ratio of the number of turns of
the windings and the connection group of the protected transformer. Therefore the
121
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
differential protection must first correlate all currents to each other before any
calculation can be performed.
Numerical IEDs have brought a large number of well-known advantages and new
functionality to the protective relaying. One of the benefits is the simplicity and
accuracy of calculating symmetrical components from individual phase quantities.
Within the firmware of a numerical IED, it is no more difficult to calculate negative-
sequence components than it is to calculate zero-sequence components. Diversity
of operation principles integrated in the same protection function enhances the
overall performance without a significant increase in cost.
122
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
Before any differential current can be calculated, the power transformer phase
shift, and its transformation ratio, must be allowed for. Conversion of all currents
to a common reference is performed in two steps:
• all current phasors are phase-shifted to (referred to) the phase-reference side,
(whenever possible a first winding with star connection)
• all currents magnitudes are always referred to the first winding of the power
transformer (typically transformer high-voltage side)
The two steps of conversion are made simultaneously on-line by the pre-
programmed coefficient matrices, as shown in equation 5 for a two-winding power
transformer, and in equation 6 for a three-winding power transformer.
1 2 3
EQUATION1880 V1 EN (Equation 5)
where:
1. is Differential Currents
2. is Differential current contribution from W1 side
3. is Differential current contribution from W2 side
123
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
1 2 3 4
EQUATION1556 V2 EN (Equation 6)
where:
1. is Differential Currents
2. is Differential current contribution from W1 side
3. is Differential current contribution from W2 side
4. is Differential current contribution from W3 side
1. Power transformer winding connection type, such as star (Y/y) or delta (D/d)
2. Transformer vector group such as Yd1, Dy11, YNautod5, Yy0d5 and so on,
which introduce phase displacement between individual windings currents in
multiples of 30°.
3. Settings for elimination of zero sequence currents for individual windings.
124
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
When the end user enters all these parameters, transformer differential function
automatically calculates off-line the matrix coefficients. During this calculations
the following rules are used:
For the phase reference, the first winding with set star (Y) connection is always
used. For example, if the power transformer is a Yd1 power transformer, the HV
winding (Y) is taken as the phase reference winding. If the power transformer is a
Dy1, then the LV winding (y) is taken for the phase reference. If there is no star
connected winding, such as in Dd0 type of power transformers, then the HV delta
winding (D) is automatically chosen as the phase reference winding.
As it can be seen from equation 5 and equation 6 the first entered winding (W1) is
always taken for ampere level reference (current magnitudes from all other sides
are always transferred to W1 side). In other words, within the differential
protection function, all differential currents and bias current are always expressed
in HV side primary Amperes.
It can be shown that the values of the matrix A, B & C coefficients (see equation 5
and equation 6) can be in advanced pre-calculated depending on the relative phase
shift between the reference winding and other power transformer windings.
Table 66 summarizes the values of the matrices for all standard phase shifts
between windings.
125
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
126
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
With help of table 66, the following matrix equation can be written for this power
transformer:
where:
IDL1 is the fundamental frequency differential current in phase L1 (in W1 side primary amperes)
IDL2 is the fundamental frequency differential current in phase L2 (in W1 side primary amperes)
IDL3 is the fundamental frequency differential current in phase L3 (in W1 side primary amperes)
IL1_W1 is the fundamental frequency phase current in phase L1 on W1 side
Table continues on next page
127
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
As marked in equation 5 and equation 6, the first term on the right hand side of the
equation, represents the total contribution from the individual phase currents from
W1 side to the fundamental frequency differential currents compensated for
eventual power transformer phase shift. The second term on the right hand side of
the equation, represents the total contribution from the individual phase currents
from W2 side to the fundamental frequency differential currents compensated for
eventual power transformer phase shift and transferred to the power transformer
W1 side. The third term on the right hand side of the equation, represents the total
contribution from the individual phase currents from W3 side to the fundamental
frequency differential currents compensated for eventual power transformer phase
shift and transferred to the power transformer W1 side. These current contributions
are important, because they are used for calculation of common bias current.
128
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
position corresponding value for Ur_W1 will be calculated and used in above-
mentioned equations. By doing this complete on-line compensation for load tap
changer movement is achieved. Differential protection will be ideally balanced for
every load tap changer position and no false differential current will appear
irrespective on actual load tap changer position.
Typically the minimum differential protection pickup for power transformer with
load tap changer is set between 30% to 40%. However with this load tap changer
compensation feature it is possible to set differential protection in the IED more
sensitive pickup value of 15% to 20%.
Load tap changer position is measured within the IED by Tap changer control and
supervision, (TCLYLTC). Within this function block the load tap changer position
value is continuously monitored to insure its integrity.
When any error with load tap changer position is detected the alarm is given which
shall be connected to the OLTCxAL input into the differential function block.
While OLTCxAL input has logical value one the differential protection minimum
pickup, originally defined by setting parameter IdMin, will be increased by the set
range of the load tap changer. Alternatively the differential current alarm feature
can be used to alarm for any problems in the whole load tap changer compensation
chain.
• two-winding differential protection in the IED can on-line compensate for one
load tap changer within protected power transformer
• three-winding differential protection in the IED can on-line compensate for up
to two load tap changers within protected power transformer
Bias current
The bias current is calculated as the highest current amongst individual winding
current contributions to the total fundamental frequency differential currents, as
shown in equation 5 and equation 6. All individual winding current contributions
are already referred to the power transformer winding one side (power transformer
HV winding) and therefore they can be compared regarding their magnitudes.
There are six (or nine in case of three-winding transformer) contributions to the
total fundamental differential currents, which are the candidates for the common
129
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
bias current. The highest individual current contribution is taken as a common bias
(restrain) current for all three phases. This "maximum principle" makes the
differential protection more secure, with less risk to operate for external faults and
in the same time brings more meaning to the breakpoint settings of the operate -
restrain characteristic.
It shall be noted that if the zero-sequence currents are subtracted from the separate
contributions to the total differential current, then the zero-sequence component is
automatically eliminated from the bias current as well. This ensures that for
secondary injection from just one power transformer side the bias current is always
equal to the highest differential current regardless of the fault type. During normal
through-load operation of the power transformer, the bias current is equal to the
maximum load current from two (three) -power transformer windings.
The magnitudes of the common bias (restrain) current expressed in the HV side
Amperes can be read as service values from the function. At the same time it is
available as outputs IBIAS from the differential protection function block. Thus, it
can be connected to the disturbance recorder and automatically recorded during
any external or internal fault condition.
For application with so called "T" configuration, that is, two restraint CT inputs
from one side of the protected power transformer, such as in the case of breaker-and-
a-half scheme the primary CT ratings can be much higher then the rating of the
protected power transformer. In order to determine the bias current for such T
configuration, the two separate currents flowing on the T-side are scaled down to
the protected power transform level by means of additional setting. This is done in
order to prevent unwanted de-sensitizing of the overall differential protection. In
addition to that, the resultant currents (the sum of two currents) into the protected
power transformer winding, which is not directly measured is calculated, and
included as well in the common bias calculation. The rest of the bias calculation
procedure is the same as in protection schemes without breaker-and-a-half scheme.
The zero sequence currents can be explicitly eliminated from the differential
currents and common bias current calculation by special, dedicated parameter
settings, which are available for every individual winding.
• the protected power transformer cannot transform the zero sequence currents
to the other side, for any reason.
• the zero sequence currents can only flow on one side of the protected power
transformer.
In most cases, power transformers do not properly transform the zero sequence
current to the other side. A typical example is a power transformer of the star-delta
130
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
type, for example YNd1. Transformers of this type do not transform the zero
sequence quantities, but zero sequence currents can flow in the earthed star-
connected winding. In such cases, an external earth-fault on the star-side causes the
zero sequence currents to flow on the star-side of the power transformer, but not on
the other side. This results in false differential currents - consisting exclusively of
the zero sequence currents. If high enough, these false differential currents can
cause an unwanted disconnection of the healthy power transformer. They must
therefore be subtracted from the fundamental frequency differential currents if an
unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if an earthing transformer
exist within differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to
some extent sensitivity of the differential protection for internal earth-faults. In
order to counteract this effect to some degree, the zero sequence currents are
subtracted not only from the three fundamental frequency differential currents, but
automatically from the bias current as well.
The restrained (that is, stabilized) part of the differential protection compares the
calculated fundamental differential (that is, operating) currents, and the bias (that
is, restrain) current, by applying them to the operate - restrain characteristic.
Practically, the magnitudes of the individual fundamental frequency differential
currents are compared with an adaptive limit. This limit is adaptive because it is
dependent on the bias (that is, restrain) current magnitude. This limit is called the
operate - restrain characteristic. It is represented by a double-slope, double-
breakpoint characteristic, as shown in figure 62. The restrained characteristic is
determined by the following 5 settings:
131
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
operate current
[ times IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1 Section 2 Section 3
SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en05000187-2.vsd
IEC05000187 V2 EN
where:
132
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
value to the bias (restrain) current. The reset ratio is in all parts of the characteristic
is equal to 0.95.
Section 1: This is the most sensitive part on the characteristic. In section 1, normal
currents flow through the protected circuit and its current transformers, and risk for
higher false differential currents is relatively low. Un-compensated on-load tap-
changer is a typical reason for existence of the false differential currents in this
section. Slope in section 1 is always zero percent.
The operate - restrain characteristic should be designed so that it can be expected that:
• for internal faults, the operate (differential) currents are always safely, that is,
with a good margin, above the operate - restrain characteristic
• for external faults, the false (spurious) operate currents are safely, that is, with
a good margin, below the operate - restrain characteristic
133
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
1 2 3
where:
1. is Negative Sequence Differential Currents
2. is Negative Sequence current contribution from W1 side
3. is Negative Sequence current contribution from W2 side
and where:
IDL1_NS is the negative sequence differential current in phase L1 (in
W1 side primary amperes)
IDL2_NS is the negative sequence differential current in phase L2 (in
W1 side primary amperes)
IDL3_NS is the negative sequence differential current in phase L3 (in
W1 side primary amperes)
INS_W1 is negative sequence current on W1 side in primary
amperes (phase L1 reference)
INS_W2 is negative sequence current on W1 side in primary
amperes (phase L1 reference)
Ur_W1 is transformer rated phase-to-phase voltage on W1 side
(setting parameter)
Ur_W2 is transformer rated phase-to-phase voltage on W2 side
(setting parameter)
j ×120
o 1 3
a=e =- + j×
2 2
EQUATION1248 V1 EN (Equation 28)
Because the negative sequence currents always form the symmetrical three phase
current system on each transformer side (that is, negative sequence currents in
every phase will always have the same magnitude and be phase displaced for 120
electrical degrees from each other), it is only necessary to calculate the first
negative sequence differential current that is, IDL1_NS.
As marked in equation 27, the first term on the right hand side of the equation,
represents the total contribution of the negative sequence current from W1 side
compensated for eventual power transformer phase shift. The second term on the
right hand side of the equation, represents the total contribution of the negative
sequence current from W2 side compensated for eventual power transformer phase
134
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
shift and transferred to the power transformer W1 side. These negative sequence
current contributions are phasors, which are further used in directional
comparisons, made in order to characterize a fault as internal or external. See
section "Internal/external fault discriminator" for more information.
135
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
1. IMinNegSeq
2. NegSeqROA
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement
NegSeqROA
is done, and (Relay
120 degrees
Operate
is mapped Angle)
IMinNegSeq
External Internal
fault fault
region region
270 deg
en05000188-2-en.vsd
IEC05000188 V2 EN
136
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
For example, for any unsymmetrical external fault, ideally the respective negative
sequence current contributions from the W1 and W2 power transformer sides will
be exactly 180 degrees apart and equal in magnitude, regardless the power
transformer turns ratio and phase displacement. One such example is shown in
figure 64, which shows trajectories of the two separate phasors representing the
negative sequence current contributions from HV and LV sides of an Yd5 power
transformer (for example, after the compensation of the transformer turns ratio and
phase displacement by using equation 27) for an unsymmetrical external fault.
Observe that the relative phase angle between these two phasors is 180 electrical
degrees at any point in time. No current transformer saturation was assumed for
this case.
137
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
"steady state"
for HV side 90
neg. seq. phasor
60
150 30
10
ms
180 0
0.1 kA
0.2 kA
0.3 kA
10 0.4 kA
ms
210 330
"steady state"
240 for LV side
270 neg. seq. phasor
en05000189.vsd
IEC05000189 V1 EN
Therefore, under all external fault condition, the relative angle is theoretically
equal to 180 degrees. During internal fault, the angle shall ideally be 0 degrees, but
due to possible different negative sequence source impedance angles on W1 and
W2 sides of the protected power transformer, it may differ somewhat from the
ideal zero value. However, during heavy faults, CT saturation might cause the
measured phase angle to differ from 180 degrees for external, and from about 0
degrees for internal fault. See figure 65 for an example of a heavy internal fault
with transient CT saturation.
138
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
Dire ctiona l Compa ris on Crite rion: Inte rna l fa ult a s s e e n from the HV s ide
90
e xcurs ion
120 60
from 0 de gre e s
35 ms due to CT
s a tura tion
150 30
de finite ly
a n inte rna l
fa ult
180 0
trip c o mmand
in 12 ms
e xte rna l
fa ult Inte rna l fa ult
0.5 kA de cla re d 7 ms
re gion
210 330 a fte r inte rna l
fa ult occure d
1.0 kA
240 300
1.5 kA
270
HV s ide contribution to the tota l ne ga tive s e que nce diffe re ntia l curre nt in kA
Dire ctiona l limit (within the re gion de limite d by ± 60 de gre e s is inte rna l fa ult)
en05000190.vsd
IEC05000190 V1 EN
However, it shall be noted that additional security measures are implemented in the
internal/external fault discriminator algorithm in order to guaranty proper operation
with heavily saturated current transformers. The trustworthy information on
whether a fault is internal or external is typically obtained in about 10ms after the
fault inception, depending on the setting IminNegSeq, and the magnitudes of the
fault currents. At heavy faults, approximately 5ms time to full saturation of the
main CT is sufficient in order to produce a correct discrimination between internal
and external faults.
139
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
If the same fault has been positively recognized as internal, then the unrestrained
negative sequence differential protection places its own trip request.
Any block signals by the harmonic and/or waveform criteria, which can block the
traditional differential protection are overridden, and the differential protection
operates quickly without any further delay.
This logic guarantees a fast disconnection of a faulty power transformer for any
heavier internal faults.
If the same fault has been classified as external, then generally, but not
unconditionally, a trip command is prevented. If a fault is classified as external, the
further analysis of the fault conditions is initiated. If all the instantaneous
differential currents in phases where start signals have been issued are free of
harmonic pollution, then a (minor) internal fault, simultaneous with a predominant
external fault can be suspected. This conclusion can be drawn because at external
faults, major false differential currents can only exist when one or more current
transformers saturate. In this case, the false instantaneous differential currents are
polluted by higher harmonic components, the 2nd, the 5th etc.
The instantaneous differential currents are calculated using the same matrix
expression as shown in equation 5 and equation 6. The same matrices A, B and C
are used for these calculations as well. The only difference is that the matrix
algorithm is fed by instantaneous values of currents, that is, samples.
140
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
Harmonic restrain
The harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal is to prevent an unwanted trip
command due to magnetizing inrush currents at switching operations, or due to
magnetizing currents at over-voltages.
The magnetizing currents of a power transformer flow only on one side of the
power transformer (one or the other) and are therefore always the cause of false
differential currents. The harmonic analysis (the 2nd and the 5th harmonic) is
applied to instantaneous differential currents. Typically instantaneous differential
currents during power transformer energizing are shown in figure 66. The
harmonic analysis is only applied in those phases, where start signals have been
set. For example, if the content of the 2nd harmonic in the instantaneous differential
current of phase L1 is above the setting I2/I1Ratio, then a block signal is set for
that phase, which can be read as BLK2HL1 output of the differential protection.
Waveform restrain
The waveform restrain criterion is a good complement to the harmonic analysis.
The waveform restrain is a pattern recognition algorithm, which looks for intervals
within each fundamental power system cycle with low instantaneous differential
current. This interval is often called current gap in protection literature. However,
within differential function this criterion actually searches for long-lasting intervals
with low rate-of-change in instantaneous differential current, which are typical for
the power transformer inrush currents. Block signals BLKWAVLx are set in those
phases where such behavior is detected. The algorithm do not requires any end user
settings. The waveform algorithm is automatically adapted dependent only on the
power transformer rated data.
141
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IEC05000343 V1 EN
142
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
quickly. A quick reset of the waveblock criterion will temporarily disable the
second harmonic blocking feature within the differential function. This
consequently ensures fast operation of the transformer differential function for a
switch onto a fault condition. It shall be noted that this feature is only active during
initial power transformer energizing, more exactly, under the first 50 ms. When the
switch onto fault feature is disabled by the setting parameter SOTFMode, the
waveblock and second harmonic blocking features work in parallel and are
completely independent from each other.
143
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except of the unrestrained (instantaneous) differential. An
alarm signal is also produced after a settable delay (tOCTAlarmDelay) to report to
operational personal for quick remedy actions once the open CT is detected. When
the open CT condition is removed (that is, the previously open CT reconnected),
the functions remain blocked for a specified interval of time, which is also a setting
(tOCTResetDelay). The task of this measure is to prevent an eventual mal-
operation after the reconnection of the previously open CT secondary circuit.
The open CT feature works only during normal loading condition. Thus, the open
CT feature must be automatically disabled for all external faults, big overloads and
inrush conditions.
The open CT algorithm provides detailed information about the location of the
defective CT secondary circuit. The algorithm clearly indicates IED side, CT input
and phase in which open CT condition has been detected. These indications are
provided via the following outputs from Line differential protection function:
Once the open CT condition is declared, the algorithm stops to search for further
open CT circuits. It waits until the first open CT circuit has been corrected. Note
that once the open CT condition has been detected, it can be automatically reset
within the differential function. It is not possible to externally reset open CT
condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:
After the reset, the open CT detection algorithm starts again to search for any other
open CT circuit within the protected zone.
The simplified internal logics, for transformer differential protection are shown in
the following figures.
144
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
IDL2
individual windings
Open CT logic on W2 side
phase current
IDL1MAG
Fundamental frequency (phasor
based) Diff current, phase L1 &
ratio
IDL2MAG
Fundamental frequency (phasor
based) Diff current, phase L2 &
phase current contributions from
individual windings
IDL3MAG
Fundamental frequency (phasor
based) Diff current, phase L3 &
phase current contributions from
individual windings
MAX IBIAS
en06000554-3-en.vsd
IEC06000544 V3 EN
Figure 67: Treatment of measured currents within IED for transformer differential function
Figure 67 shows how internal treatment of measured currents is done in case of two-
winding transformer.
The following currents are inputs to the power transformer differential protection
function. They must all be expressed in true power system (primary) A, that is, as
measured.
145
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
1. Instantaneous values of currents (samples) from HV, and LV sides for two-
winding power transformers, and from the HV, the first LV, and the second
LV sides for three-winding power transformers.
2. Currents from all power transformer sides expressed as fundamental frequency
phasors, with their real, and imaginary parts. These currents are calculated
within the protection function by the fundamental frequency Fourier filters.
3. Negative sequence currents from all power transformer sides expressed as
phasors. These currents are calculated within the protection function by the
symmetrical components module.
BLKUNRES
IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG
IBIAS STL1
AND
BLOCK
BLKRES
TRIPRESL1
AND
OR 1
IDL1
to fault logic
2nd BLK2HL1
Switch on
Harmonic
Wave BLKWAVL1
block
5th BLK5HL1
Harmonic
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
OR
AND
OpCrossBlock=On
en06000545.vsd
IEC06000545 V1 EN
146
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
IEC05000167-TIFF V1 EN
TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3
TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3
TRIP
TRNSSENS OR
TRNSUNR
en05000278.vsd
IEC05000278 V1 EN
147
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IEC05000279-TIFF V1 EN
148
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
of that phase (see signal IDL1) is analyzed for the 2nd and the 5th harmonic
contents (see the blocks with the text inside: 2nd Harmonic; Wave block and
5th Harmonic). If there is less harmonic pollution, than allowed by the settings
I2/I1Ratio, and I5/I1Ratio, (then the outputs from the blocks 2nd harmonic and
5th harmonic is 0) then it is assumed that a minor simultaneous internal fault
must have occurred. Only under these conditions a trip command is allowed
(the signal TRIPRESL1 is = 1). The cross-block logic scheme is automatically
applied under such circumstances. (This means that the cross block signals
from the other two phases L2 and L3 is not activated to obtain a trip on the
TRIPRESL1 output signal in figure 68)
6. All start and blocking conditions are available as phase segregated as well as
common (that is three-phase) signals.
IDL1 MAG
a
a>b
I Diff Alarm b
IDL3 MAG
a
a>b
I Diff Alarm b
en06000546.vsd
IEC06000546 V1 EN
149
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
IEC06000249_2_en.vsd
IEC06000249 V2 EN
150
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
T3WPDIF
I3PW1CT1* TRIP
I3PW1CT2* TRIPRES
I3PW2CT1* TRIPUNRE
I3PW2CT2* TRNSUNR
I3PW3CT1* TRNSSENS
I3PW3CT2* START
TAPOLTC1 STL1
TAPOLTC2 STL2
OLTC1AL STL3
OLTC2AL BLK2H
BLOCK BLK2HL1
BLKRES BLK2HL2
BLKUNRES BLK2HL3
BLKNSUNR BLK5H
BLKNSSEN BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000250_2_en.vsd
IEC06000250 V2 EN
151
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
152
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
153
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
154
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
155
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
156
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
157
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
158
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
159
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
SYMBOL-AA V1 EN
5.3.1 Introduction
Restricted earth-fault protection, low-impedance function (REFPDIF) can be used
on all directly or low-impedance earthed windings. The REFPDIF function
provides high sensitivity (down to 5%) and high speed tripping as it measures each
winding individually and thus does not need inrush stabilization.
160
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
REFPDIF is of “low impedance” type. All three phase power transformer terminal
currents, and the power transformer neutral point current, must be fed separately to
REFPDIF . These input currents are then conditioned within REFPDIF by
mathematical tools.
Fundamental frequency components of all currents are extracted from all input
currents, while other eventual zero sequence components (for example, the 3rd
harmonic currents) are fully suppressed. Then the residual current phasor is
constructed from the three line current phasors. This zero sequence current phasor
is then vectorially added to the neutral current, in order to obtain differential current.
The following facts may be observed from the figure 75 and the figure 76 (where
the three-phase line CTs are lumped into a single 3Io current, for the sake of
simplicity).
161
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
zone of protection
s Izs1 Ia = 0
o L1 L1
u Izs1 Ib = 0
L2 L2
r
c Izs1 Ic = 0
L3 L3
e
Uzs Current in the neutral (IN)
3Io=3I zs1 IN = -3Izs1 IN serves as a directional
reference because it has
the same direction for both
internal and external faults.
IEC09000107-1-en.vsd
IEC09000107 V1 EN
162
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
power system
contribution to
fault current zone of protection
s Izs2 Izs1 Ia = 0
o L1 L1
u Izs2 Izs1
L2 Ib = 0 L2
r
c Izs2 Izs1 Ic = 0
e L3 L3
MTA
IN
Reference is
ROA
neutral current
1. For an external earth fault, (figure 75) the residual current 3Io and the neutral
conductor current IN have equal magnitude, but they are 180 degree out-of-
phase due to internal CT reference directions used in the IED. This is easy to
understand, as both CTs ideally measure exactly the same component of the
earth fault current.
2. For an internal fault, the total earth-fault current is composed generally of two
zero sequence components. One zero sequence component (that is, 3IZS1)
flows towards the power transformer neutral point and into the earth, while the
other zero sequence component (that is, 3IZS2) flows out into the connected
power system. These two primary currents can be expected to be of
approximately opposite directions (about the same zero sequence impedance
angle is assumed on both sides of the earth-fault). However, on the secondary
CT sides they will be approximately in phase due to internal CT reference
directions used in the IED. The magnitudes of the two components may be
different, dependent on the magnitudes of zero sequence impedances of both
sides. No current can flow towards the power system, if the only point where
the system is earthed, is at the protected power transformer. Likewise, no
current can flow into the power system, if the winding is not connected to the
163
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
power system (circuit breaker open and power transformer energized from the
other side).
3. For both internal and external earth faults, the current in the neutral connection
IN has always the same direction, that is, towards the earth.
4. The two measured zero sequence current are 3Io and IN. The vectorial sum
between them is the REFPDIF differential current, which is equal to Idiff = IN
+3Io.
Since REFPDIF is a differential protection where the line zero sequence (residual)
current is constructed from 3 line (terminal) currents, a bias quantity must give
stability against false operations due to high through fault currents. An operate -
bias characteristic (only one) has been devised to the purpose.
It is not only external earth faults that REFPDIF should be stable against, but also
heavy phase-to-phase faults, not including earth. These faults may also give rise to
false zero sequence currents due to saturated line CTs. Such faults, however,
produce no neutral current, and can thus be eliminated as a source of danger, at
least during the fault.
REFPDIF has only one operate-bias characteristic, which is described in the table
78, and shown in the figure 77.
164
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
operate current in pu
4 operate
1
minimum base sensitivity 50 %
default base sensitivity 30 % first slope block
maximum base sensitivity 5 %
0 1 2 3 4 5 6
IEC98000017-2-en.vsd
IEC98000017 V3 EN
Idiff = IN + 3 Io
EQUATION1533 V1 EN (Equation 30)
where:
IN current in the power transformer neutral as a fundamental frequency phasor,
3Io residual current of the power transformer line (terminal) currents as a phasor.
165
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
If there are two three-phase CT inputs on the HV winding side for REFPDIF (such
as in breaker-and-a-half configurations), then their respective residual currents are
added within REFPDIF function so that:
where the signals are defined in the input and output signal tables for REFPDIF.
As the bias current the highest current of all separate input currents to REFPDIF,
that is, of current in phase L1, phase L2, phase L3, and the current in the neutral
point (designated as IN in the figure 75 and in the figure 76).
If there are 2 feeders included in the zone of protection of REFPDIF, then the
respective bias current is found as the relatively highest of the following currents:
1
current[1] = max (I3PW1CT1) ×
CTFactorPri1
EQUATION1526 V1 EN (Equation 31)
1
current[2] = max (I3PW1CT2) ×
CTFactorPri2
EQUATION1527 V1 EN (Equation 32)
1
current[3] = max (I3PW2CT1) ×
CTFactorSec1
EQUATION1528 V1 EN (Equation 33)
1
current[4] = max (I3PW2CT2) ×
CTFactorSec2
EQUATION1529 V1 EN (Equation 34)
current[5] = IN
EQUATION1530 V1 EN (Equation 35)
The bias current is thus generally equal to none of the input currents. If all primary
ratings of the CTs were equal to IBase, then the bias current would be equal to the
highest current in Amperes. IBase shall be set equal to the rated current of the
protected winding where REFPDIF function is applied.
166
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
External faults are more common than internal earth faults for which the restricted
earth fault protection should operate. It is important that the restricted earth fault
protection remains stable during heavy external earth and phase-to-phase faults,
and also when such a heavy external fault is cleared by some other protection such
as overcurrent, or earth-fault protection, and so on. The conditions during a heavy
external fault, and particularly immediately after the clearing of such a fault may be
complex. The circuit breaker’s poles may not open exactly at the same moment,
some of the CTs may still be highly saturated, and so on.
The detection of external earth faults is based on the fact that for such a fault a high
neutral current appears first, while a false differential current only appears if and
when one, or more, current transformers saturate.
An external earth fault is thus assumed to have occurred when a high neutral
current suddenly appears, while at the same time the differential current Idiff
remains low, at least for a while. This condition must be detected before a trip
request is placed within REFPDIF. Any search for external fault is aborted if a trip
request has been placed. A condition for a successful detection is that it takes not
less than 4ms for the first CT to saturate.
For an internal earth fault, a true differential current develops immediately, while
for an external fault it only develops if a CT saturates. If a trip request comes first,
before an external fault could be positively established, then it must be an internal
fault.
If an external earth fault has been detected, then the REFPDIF is temporarily
desensitized.
Directional criterion
The directional criterion is applied in order to positively distinguish between
internal- and external earth faults. This check is an additional criterion, which
should prevent malfunctions at heavy external earth faults, and during the
disconnection of such faults by other protections. Earth faults on lines connecting
the power transformer occur much more often than earth faults on a power
transformer winding. It is important therefore that the Restricted earth faults
protection, low impedance (REFPDIF,) must remain secure during an external
fault, and immediately after the fault has been cleared by some other protection.
For an external earth faults with no CT saturation, the residual current in the lines
(3Io) and the neutral current (IN in the figure 75) are theoretically equal in
magnitude and are 180 degree out-of-phase. It is the current in the neutral (IN)
which serves as a directional reference because it flows for all earth faults, and it
has the same direction for all earth faults, both external and internal. The
directional criterion in REFPDIF protection makes it a current-polarized IED.
If one or more CTs saturate, then the measured currents 3Io and IN may no more be
equal, nor will their positions in the complex plane be exactly 180 degree apart.
There is a risk that the resulting false differential current Idiff enters the operate
167
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
area when clearing the external fault. If this happens, a directional test may prevent
a malfunction.
1. a trip request signal has been issued, REFPDIF function START signal set to 1)
2. if the residual current in lines (3Io) is at least 3% of the IBase current.
If a directional check is either unreliable or not possible to do, due to too small
currents, then the direction is cancelled as a condition for an eventual trip.
RCA = 0 degrees = constant; where RCA stands for Relay Characteristic Angle
ROA = 60 to 90 degrees; where ROA stands for Relay Operate Angle.
RCA determines a direction MTA (“Maximum Torque Angle”) where the line
residual current 3Io must lie for an internal earth fault, while ROA sets a tolerance
margin.
1. Check if current in the neutral Ineutral (IN) is less than 50% of the base
sensitivity Idmin. If yes, only service values are calculated, then REFPDIF
algorithm is exited.
2. If current in the Ineutral (IN) is more than 50% of Idmin, then determine the
bias current Ibias.
3. Determine the differential (operate) current Idiff as a phasor, and calculate its
magnitude.
4. Check if the point P(Ibias, Idiff) is above the operate - bias characteristic. If
yes, increment the trip request counter by 1. If the point P(Ibias, Idiff) is found
to be below the operate - bias characteristic, then the trip request counter is
reset to 0.
168
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
5. If the trip request counter is still 0, search for an eventual heavy external earth
fault. The search is only made if the neutral current is at least 50% of the IBase
current. If an external earth fault has been detected, a flag is set which remains
set until the external fault has been cleared. The external fault flag is reset to 0
when Ineutral falls below 50% of the base sensitivity Idmin. Any search for
external fault is aborted if trip request counter is more than 0.
6. For as long as the external fault persists an additional temporary trip condition
is introduced. That means that REFPDIF is temporarily desensitized.
7. If point P(Ibias, Idiff) is found to be above the operate - bias characteristic), so
that trip request counter is becomes more than 0, a directional check can be
made. The directional check is made only if Iresidual (3Io) is more than 3% of
the IBase current. If the result of the check means “external fault”, then the
internal trip request is reset. If the directional check cannot be executed, then
direction is no longer a condition for a trip.
8. When neutral current, residual current and bias current are within some
windows and some timing criteria are fulfilled, the ratio of 2nd to fundamental
tone is calculated. If it is found to be above 60% the trip request counter is
reset and TRIP remains zero.
9. Finally, a check is made if the trip request counter is equal to, or higher than 2.
If it is, and that at the same instance of time tREFtrip, the actual bias current at
this instance of time tREFtrip is at least 50% of the highest bias current Ibiasmax
(Ibiasmax is the highest recording of any of the three phase currents measured
during the disturbance) then REFPDIF sets output TRIP to 1. If the counter is
less than 2, TRIP signal remains 0.
IEC06000251_2_en.vsd
IEC06000251 V2 EN
169
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
170
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
5.4.1 Identification
IEC 61850 IEC 60617 ANSI/IEEE C37.2
Function description
identification identification device number
SYMBOL-CC V2 EN
5.4.2 Introduction
The 1Ph High impedance differential protection (HZPDIF) function can be used
when the involved CT cores have the same turns ratio and similar magnetizing
characteristics. It utilizes an external CT current summation by wiring, a series
resistor, and a voltage dependent resistor which are mounted externally connected
to the IED.
171
Technical reference manual
Section 5 1MRK 502 027-UEN A
Differential protection
See the application manual for operating voltage and sensitivity calculation.
The logic diagram shows the operation principles for the 1Ph High impedance
differential protection function HZPDIF, see figure 79. It is a simple one step IED
function with an additional lower alarm level. By activating inputs, the HZPDIF
function can either be blocked completely, or only the trip output.
IEC05000301 V1 EN
Figure 79: Logic diagram for 1Ph High impedance differential protection
HZPDIF
IEC05000363-2-en.vsd
IEC05000363 V2 EN
172
Technical reference manual
1MRK 502 027-UEN A Section 5
Differential protection
173
Technical reference manual
174
1MRK 502 027-UEN A Section 6
Impedance protection
S00346 V1 EN
6.1.1 Introduction
The numerical mho line distance protection is a, up to four zone full scheme
protection for back-up detection of short circuit and earth faults. The four zones
have fully independent measuring and settings, which gives high flexibility for all
types of lines.
The function can be used as under impedance back-up protection for transformers
and generators.
The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
are executed in parallel.
175
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.
The distance function consists of four instances. Each instance can be selected to
be either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The
operating characteristic is in accordance to figure 81.
jx
Mho, zone4
Mho, zone3
Zs=0
Mho, zone2
R
Mho, zone1
Zs=Z1
R Zs=2Z1
IEC11000223-1-en.vsd
IEC11000223 V1 EN
Figure 81: Mho characteristic and the source impedance influence on the mho characteristic
The mho characteristic has a dynamic expansion due to the source impedance.
Instead of crossing the origin as for the mho to the left of figure 81, which is only
valid where the source impedance is zero, the crossing point is moved to the
coordinates of the negative source impedance given an expansion of the circle
shown to the right of figure 81.
The polarization quantities used for the mho circle are 100% memorized positive
sequence voltages. This will give a somewhat less dynamic expansion of the mho
circle during faults. However, if the source impedance is high, the dynamic
expansion of the mho circle might lower the security of the function too much with
high loading and mild power swing conditions.
The mho distance element has a load encroachment function which cuts off a
section of the characteristic when enabled. The function is enabled by setting the
176
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Each impedance zone can be switched On and Off by the setting parameter
Operation.
Each zone can also be set to Non-directional, Forward or Reverse by setting the
parameter DirMode.
For critical applications such as for lines with high SIRs as well as CVTs, it is
possible to improve the security by setting the parameter ReachMode to
Underreach. In this mode the reach for faults close to the zone reach is reduced by
20% and the filtering is also introduced to increase the accuracy in the measuring.
If the ReachMode is set to Overreach no reduction of the reach is introduced and
no extra filtering introduced. The latter setting is recommended for overreaching
pilot zone, zone 2 or zone 3 elements and reverse zone where overreaching on
transients is not a major issue either because of less likelihood of overreach with
higher settings or the fact that these elements do not initiate tripping unconditionally.
The zone reach for phase-to-earth fault and phase-to-phase fault is set individually
in polar coordinates.
The impedance is set by the parameters ZPE and ZPP and the corresponding
arguments by the parameters ZAngPE and ZAngPP.
Compensation for earth-return path for faults involving earth is done by setting the
parameter KNMag and KNAng where KNMag is the magnitude of the earth-return
path and KNAng is the difference of angles between KNMag and ZPE.
Z0-Z1
KNMag =
3 × Z1
EQUATION1579 V1 EN (Equation 36)
177
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
KNAng = arg
( Z 0 - Z1
3 × Z1
)
EQUATION1580 V1 EN (Equation 37)
where
Z0 is the complex zero sequence impedance of the line in Ω/phase
Z1 is the complex positive sequence impedance of the line in Ω/phase
The activation of input signal BLKZ can be made by external fuse failure function
or from the loss of voltage check in the Mho supervision logic (ZSMGAPC). In
both cases the output BLKZ in the Mho supervision logic shall be connected to the
input BLKZ in the Mho distance function block (ZMHPDIS)
The input signal BLKZMTD is activated during some ms after fault has been
detected by ZSMGAPC to avoid unwanted operations due to transients. It shall be
connected to the BLKZMTD output signal of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the built-
in resonance circuit in the CVT, which reduce the secondary voltage for a while.
The input BLKHSIR shall be connected to the output signal HSIR on ZSMGAPC
for increasing of the filtering and high SIR values. This is valid only when
permissive underreach scheme is selected by setting ReachMode=Underreach.
The mho algorithm is based on the phase comparison of a operating phasor and a
polarizing phasor. When the operating phasor leads the reference polarizing phasor
by more than 90 degrees, the function operates and gives a trip output.
178
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Phase-to-phase fault
Mho
The plain mho circle has the characteristic as in figure 82. The condition for
deriving the angle β is according to equation 38.
where
179
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
IL1L2·X
Ucomp = UL1L2 - IL1L2 • ZPP
IL1L2 • ZPP
ß
Upol
UL1L2
IL1L2·R
en07000109.vsd
IEC07000109 V1 EN
Figure 82: Simplified mho characteristic and vector diagram for phase L1-to-
L2 fault
Offset Mho
The characteristic for offset mho is a circle where two points on the circle are the
setting parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has
the settable angle AngZPP and the angle for ZRevPP is AngZPP+180°.
The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater than or equal to 90°
(figure 83). The angle will be 90° for fault location on the boundary of the circle.
The angle β for L1-to-L2 fault can be defined according to equation 39.
æ U -IL1L2 × ZPP ö
b = arg ç ÷
è U-(-IL1L2 × ZRevPP) ø
EQUATION1792 V1 EN (Equation 39)
where
ZRevPP is the positive sequence impedance setting for phase-to-phase fault in reverse direction
180
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
IL1L2jX
U
Ucomp2 = U = IF•ZF=UL1L2
IL1L2R
- IL1L2 • Z RevPP
en07000110.vsd
IEC07000110 V1 EN
Figure 83: Simplified offset mho characteristic and voltage vectors for phase
L1-to-L2 fault.
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 39
The directional information is brought to the mho distance measurement from the
mho directional element as binary coded information to the input DIRCND. See
Directional impedance element for mho characteristic (ZDMRDIR) for information
about the mho directional element.
181
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
IL1L2jX
ZPP
UL1L2
ArgNegRes f
IL1L2
ArgDir
en07000111.vsd
IEC07000111 V1 EN
Figure 84: Simplified offset mho characteristic in forward direction for phase
L1-to-L2 fault
The β is derived according to equation 39 for the mho circle and φ is the angle
between the voltage and current.
182
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
ZPP
ArgNegRes
ϕ
IL1L2
ArgDir R
UL1L2
ZRevPP
en06000469.eps
IEC06000469 V1 EN
Phase-to-earth fault
Mho
The measuring of earth faults uses earth-return compensation applied in a
conventional way. The compensation voltage is derived by considering the
influence from the earth-return path.
For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as
shown in figure 86.
where
Upol is the polarizing voltage (memorized UL1 for Phase L1-to- earth fault)
Z1+ZN = Z 1 × 1 + KN ( )
EQUATION1799 V1 EN (Equation 41)
Table continues on next page
183
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
where
Z1 is the positive sequence impedance of the line (Ohm/phase)
The angle β between the Ucomp and the polarize voltage Upol for a L1-to-earth
fault is
where
UL1 is the phase voltage in faulty phase L1
KN Z0-Z1
EQUATION1593 V1 EN
3 × Z1
EQUATION1594 V1 EN
the setting parameter for the zero sequence compensation consisting of the
magnitude KN and the angle KNAng.
Upol is the 100% of positive sequence memorized voltage UL1
IL1·X
IL1·ZN
Ucomp
IL1 • Zloop
IL1·ZPE
Upol
f
IL1 (Ref) IL1·R
en06000472_2.vsd
IEC06000472 V2 EN
Figure 86: Simplified offset mho characteristic and vector diagram for phase
L1-to-earth fault
184
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Offset mho
The characteristic for offset mho at earth fault is a circle containing the two vectors
from the origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for
the positive sequence impedance in forward respective reverse direction. The
vector ZPE in the impedance plane has the settable angle AngZPE and the angle for
ZRevPP is AngZPE+180°.
The condition for operation at phase-to-earth fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater or equal to 90° see
figure 87. The angle will be 90° for fault location on the boundary of the circle.
IL1L 2 • jX
UL1
U comp2 = UL1 - (-IL1 • ZRevPE)
IL1L2 • R
- I L1 • Z Re vPe
en 06000465.vsd
IEC06000465 V1 EN
Figure 87: Simplified offset mho characteristic and voltage vector for phase L1-
to-L2 fault
185
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 45
IL1 jX
UL1
ArgNegRes f
IL1 IL1·R
ArgDir
en 06000466.vsd
IEC06000466 V1 EN
Figure 88: Simplified characteristic for offset mho in forward direction for L1-to-
earth fault
The conditions for operation of offset mho in reverse direction for L1-to-earth fault
is 90≤β≤270 and 180°-Argdir≤φ≤ArgNegRes+180°.
186
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
The β is derived according to equation 45 for the offset mho circle and φ is the
angle between the voltage and current.
ZPE
ArgNegRes
ϕ
IL
1
ArgDir R
UL1
ZRevPE
en06000470.eps
IEC06000470 V1 EN
Figure 89: Simplified characteristic for offset mho in reverse direction for L1-to-
earth fault
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-
phase signals are designated by L1L2, L2L3, and L3L1.
One type of function block, ZMHPDIS are used in the IED for zone 1 - 5.
187
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FMPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FMPSPDIS function output signal
STCNDPHS.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filters out the
relevant signals depending on the setting of the parameter DirMode. Input signal
DIRCND must be configured to the STDIRCND output signal on ZDMRDIR
function.
OffsetMhoDir=
Non-directional
AND AND
DirMode=Offset
STCND T
AND F
AND
LoadEnchMode=
On/Off
LDCND
T
True F
AND Release
DIRCND
OffsetMhoDir=
Forward/Reverse
AND
DirMode=
Forward/Reverse
BLKZ
BLOCK OR
IEC11000216-1-en.vsd
IEC11000216 V1 EN
Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 90.
188
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Release STPE
OR
AND
STL1N STL1
OR
AND
STL2N
AND
STL3N
STL2
OR
AND
STL1L2
AND
STL2L3
STL3
OR
AND
STL3L1
START
OR
STPP
OR
IEC11000217-1-en.vsd
IEC11000217 V1 EN
Tripping conditions for the distance protection zone one are symbolically presented
in figure 92.
189
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
15ms
AND TRIP
BLKTRIP t
AND TRL2
STL2
IEC11000218-1-en.vsd
IEC11000218 V1 EN
IEC06000423_2_en.vsd
IEC06000423 V2 EN
190
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
191
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
192
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
S00346 V1 EN
193
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
6.2.1 Introduction
The phase-to-earth impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.
Where:
ArgDir Setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees)
ArgNegRes Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 94 for mho characteristics.
U1L1 Positive sequence phase voltage in phase L1
U1L1L2M Memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees
respectively (see figure 94) and they should not be changed unless system studies
show the necessity.
194
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
X
Zset reach point
ArgNegRes
-ArgDir R
-Zs
en06000416.vsd
IEC06000416 V1 EN
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100ms or until the positive sequence voltage is
restored. After 100ms, the following occurs:
195
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
• If the current is still above the set value of the minimum operating current the
condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, no directional
indications will be given until the positive sequence voltage exceeds 10% of
its rated value.
The STDIRCND output provides an integer signal that depends on the evaluation
and is derived from a binary coded signal as follows:
Values for the following parameters are calculated, and may be viewed as service
values:
• resistance phase L1
• reactance phase L1
• resistance phase L2
• reactance phase L2
• resistance phase L3
• reactance phase L3
• direction phase L1
• direction phase L2
• direction phase L3
196
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
IEC06000422_2_en.vsd
IEC06000422 V2 EN
197
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
6.3.1 Introduction
The phenomenon pole slip, also named out of step conditions, occurs when there is
phase opposition between different parts of a power system. This is often shown in
a simplified way as two equivalent generators connected to each other via an
equivalent transmission line and the phase difference between the equivalent
generators is 180°.
The centre of the pole slip can occur in the generator itself or somewhere in the
power system. When a pole slip occurs within the generator it is essential to trip the
generator. If the centre of pole slip occurs outside any generator the power system
198
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
should be split into two different parts that could have the ability to get stable
operating conditions.
Pole slip protection (PSPPPAM) function in the IED can be used both for generator
protection application as well as, line protection applications.
The situation with pole slip of a generator can be caused by different reasons.
A short circuit may occur in the external power grid, close to the generator. If the
fault clearing time is too long, the generator will accelerate so much, that the
synchronism cannot be maintained.
The operation of a generator having pole slip will give risk of damages to the
generator, shaft and turbine.
• At each pole slip there will be significant torque impact on the generator-
turbine shaft.
• In asynchronous operation there will be induction of currents in parts of the
generator normally not carrying current, thus resulting in increased heating.
The consequence can be damages on insulation and stator/rotor iron.
The Pole slip protection (PSPPPAM) function shall detect pole slip conditions and
trip the generator as fast as possible if the locus of the measured impedance is
inside the generator-transformer block. If the centre of pole slip is outside in the
power grid, the first action should be to split the network into two parts, after line
protection action. If this fails there should be operation of the generator PSPPPAM
in zone 2, to prevent further damages to the generator, shaft and turbine.
The movements in the impedance plain can be seen in figure 97. The transient
behaviour is described by the transient EMF's EA and EB, and by X'd, XT and the
transient system impedance ZS.
199
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Zone 1 Zone 2
EB X’d XT XS EA
IED
B A
jX
XS
Pole slip
impedance XT
d Apparent generator
movement impedance R
X’d
IEC06000437_2_en.vsd
IEC06000437 V2 EN
where:
X'd = transient reactance of the generator
• the minimum current exceeds 0.10 IN (IN is IBase parameter set under general
setting).
• the maximum voltage falls below 0.92 UBase
• the voltage Ucosφ (the voltage in phase with the generator current) has an
angular velocity of 0.2...8 Hz and
• the corresponding direction is not blocked.
200
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
en07000004.vsd
IEC07000004 V1 EN
Figure 98: Different generator quantities as function of the angle between the
equivalent generators
An alarm is given when movement of the rotor is detected and the rotor angle
exceeds the angle set for 'WarnAngle'.
When the impedance crosses the slip line between ZB and ZC it counts as being in
zone 1 and between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone
1 when signal EXTZONE1 is high (external device detects the direction of the
centre of slipping).
After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction
of slip - either GEN or MOTOR are issued.
Every time pole slipping is detected, the impedance of the point where the slip line
is crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of
rotor movement has reduced in relation to the preceding slip or the slip line is
crossed in the opposite direction outside ZA-ZB. A further slip in the opposite
direction within ZA-ZB resets all the signals and is then signalled itself as a first slip.
201
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than TripAngle. The TRIP2 signal is generated
after N2 slips in zone 2, providing the rotor angle is less than TripAngle.
START
AND
0.2 £ Slip.Freq. £ 8 Hz
d ³ startAngle
ZONE1
AND
Z cross line ZA - ZC
ZONE2
AND
Z cross line ZC - ZB
Counter
a
a³b
N1Limit b TRIP1
AND
d £ tripAngle TRIP
OR
Counter
a
N2Limit b a³b TRIP2
AND
en07000005.vsd
IEC07000005 V1 EN
Figure 99: Simplified logic diagram for pole slip protection PSPPPAM
202
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
IEC10000045-1-en.vsd
IEC10000045 V1 EN
203
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
204
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
<
SYMBOL-MM V1 EN
6.4.1 Introduction
There are limits for the under-excited operation of a synchronous machine. A
reduction of the excitation current weakens the coupling between the rotor and the
stator. The machine may lose the synchronism and start to operate like an induction
machine. Then, the reactive power consumption will increase. Even if the machine
does not loose synchronism it may not be acceptable to operate in this state for a
long time. Reduction of excitation increases the generation of heat in the end
region of the synchronous machine. The local heating may damage the insulation
of the stator winding and the iron core.
205
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Zposseq U posseq
=
I posseq
EQUATION1771 V1 EN (Equation 48)
ZL1L2 U L1 - U L 2
=
I L1 - I L 2
EQUATION1772 V1 EN (Equation 49)
ZL2L3 U L 2 - U L3
=
I L 2 - I L3
EQUATION1773 V1 EN (Equation 50)
ZL3L1 U L 3 - U L1
=
I L 3 - I L1
EQUATION1774 V1 EN (Equation 51)
Naimly:
• Offset mho circle for Z1
• Offset mho circle for Z2
• Directional blinder
206
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
UnderexitationProtection
Underexcitation protection
Restrainarea
Restrain area
R
Directional
blinder
IEC06000455-2-en.vsd
IEC06000455 V2 EN
When the apparent impedance reaches the zone Z1 this zone will operate, normally
with a short delay. The zone is related to the dynamic stability of the generator.
When the apparent impedance reaches the zone Z2 this zone will operate, normally
with a longer delay. The zone is related to the static stability of the generator.
LEXPDIS protection also has a directional blinder (supervision). See figure 101.
207
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Offset
R
XoffsetZ1
Z (apparent impedance)
Z1 = Z - (XoffsetZ1 +
Z1diameter Z1diameter/2)
Z1 or Z2
en06000456-2.vsd
IEC06000456 V2 EN
The impedance Z1 is constructed out from the measured apparent impedance Z and
the impedance corresponding to the centre point of the impedance characteristic
(Z1 or Z2). If the amplitude of this impedance is less than the radius (diameter/2)
of the characteristic, this part of the protection will operate.
If the directional restrain is set off the impedance zone operation will start the
appropriate timer and LEXPDIS will trip after the set delay (tZ1 or tZ2).
If the directional restrain is set On the directional release function must also
operate to enable operation. A new impedance is constructed as XoffsetDirLine. If
the phase angle of this impedance is less than the set DirAngle LEXPDIS function
will be released, see figure 103.
208
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Underexcitation Protection
Restrain area
R
XoffsetDirLine
DirAngle
Z (apparent impedance)
en06000457.vsd
IEC06000457 V1 EN
Positive tZ1
sequence Z in startZ1 t TripZ1
&
current Z1 char.
phasor
Dir.
Restrain
Dir.Restrain ON ³1
en06000458-2.vsd
IEC06000458 V3 EN
209
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
IEC07000031_2_en.vsd
IEC07000031 V2 EN
210
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
211
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
6.5.1 Introduction
The sensitive rotor earth fault protection (ROTIPHIZ) is used to detect earth faults
in the rotor windings of generators. ROTIPHIZ is applicable for all types of
synchronous generators.
To implement the above concept, a separate injection box is required. The injection
box generates a square wave voltage signal at a certain preset frequency which is
fed into the rotor winding.
The magnitude of the injected voltage signal and the resulting injected current is
measured through a resistive shunt located within the injection box. These two
measured values are fed to the IED. Based on these two measured quantities, the
protection IED determines the rotor winding resistance to ground. The resistance
value is then compared with the preset fault resistance alarm and trip levels.
The protection function can detect earth faults in the entire rotor winding and
associated connections.
Requires injection unit REX060 and a coupling capacitor unit REX061 for correct
operation.
212
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
4 Step-up
Transformer
U> 3
Uinj 1
Rshunt
7 R C
~ Generator
5
6
REX061 2
ROTOR EF
I
RN
REX060/RIM module
REG670
IEC11000014-4-en.vsd
Generator Protection Panel
IEC11000014 V1 EN
The injection signals are generated in a separate unit, REX060. The signals have
square wave form and are injected to the generator via the coupling capacitor unit
REX061 to the excitation circuit.
In the REX060 unit the injection voltage and current signals are amplified to a
level adapted to the analogue voltage inputs of IED. In IED the measured signals
evaluated to detect rotor earth faults.
213
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
IED and
Injection Top view Power Back view Front view
connectors connector Keylock
LED
Injection Stator
Injection Rotor
18 18
X62 X82
PSM
1 1
5 5
Power
Stator
Rotor
Backplane
IEC11000015-1-en.vsd
IEC11000015 V1 EN
The REX060 unit is a common unit that can be configured for either rotor or stator
earth fault protection, or for both. The REX060 have separate modules for rotor
and stator protection. The REX060 generate square wave signals, where one is
used for injection to the stator neutral point and the other to the field winding
circuit (rotor circuit), if configured for both stator and rotor protection. The injected
voltage and currents are measured by the unit and amplified, resulting in voltage
signals both for the injected voltage and current, and adapted to the analogue inputs
of IED. The injection unit REX060 shall be located close to the IED, preferably in
the same cubicle.
For the Sensitive rotor earth fault protection, there are some settings necessary for
REX060:
REX060 will also continuously check the measured signal for detection of
saturation which could cause error in the evaluation in IED. If saturation level is
reached a binary signal, connected to IED, is activated. Also other errors in the
injection circuit will initiate a binary signal to IED for blocking of the function.
Rotor injection output is protected against high voltages by a relay blocking the
injection circuit. This blocking remains blocked by stored status in non-volatile
memory.
The output is also protected by a fuse. If this fuse is blown, it is caused by external
voltage source, since the injection unit cannot provide enough energy to blow this
fuse.
214
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Refer to the Hardware section in this manual for a detailed description of REX060.
Iinj
+
DC
Crot
Rf Crot Uinj
AC
REX061 -
Rf Iinj
+
Rotor Reference
U inj
Im pedance
-
IEC11000065-1-en.vsd
IEC11000065 V1 EN
Figure 108: Equivalent diagram for Sensitive rotor earth fault protection principle
The impedance ZMeasured is equal to the capacitive reactance between the rotor
winding and earth (1/ωCrot) and the earth fault resistance (Rf). The series resistance
in the injection circuit is eliminated. Rf is very large in the non-faulted case and the
measured impedance, called the rotor reference impedance and can be calculated as :
1
Z ref = - j
wCrot
EQUATION2510 V1 EN
alternative
1
= jwCrot
Z ref
EQUATION2511 V1 EN
Where
w = 2p × finj
EQUATION2512 V1 EN
The injected frequency finj of the square wave, is a set value, deviating from the
fundamental frequency (50 or 60 Hz). The injected frequency can be set within the
range 75 – 250 Hz with the recommended value 113 Hz in 50 Hz systems and 137
Hz in 60 Hz systems.
215
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Rseries is a resistance in the REX061 unit used to protect against overvoltage to the
injection unit. Such overvoltages can occur if the unit is fed from static excitation
system.
The injection unit REX060 is connected to the generator and to IED as shown in
figure 106.
From the REX060 the injected voltage and current are delivered as AC voltages to
IED. The injected voltage and current is measured and analyzed in the protection
function software within IED. The measured injected voltage and current are first
processed by means of special filtering so that the signals are referred to the
injected frequency only.
U Inj
Z bare =
I Inj
EQUATION2500 V1 EN
ZMeasured ZBare
Z series Iinj
Rf Z shunt Uinj
IEC11000003-2-en.vsd
IEC11000003 V1 EN
Z Measured = k1 × Z bare + k 2
EQUATION2501 V1 EN
216
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
The factors k1 and k2 [Ω] are derived from measurements during commissioning,
where calibration to known fault resistance will be used to convert the
measurement to true primary impedance. The factor k1 will compensate for
transformer ratio and other factors to achieve impedance values related to the
primary system. The factor k2 [Ω] will compensate for the series impedance Zseries
The measured values are transferred to the primary impedance values by taking the
actual impedance value through the complex transformation given by the equation.
Ztrue = k1 × Z measured + k2
GUID-20ADF3F6-6A89-4B5F-B0DA-9740C4FD5482 V1 EN
The factors k1 and k2 [Ω] are derived during the calibration measurements under
commissioning. As support for the calibration, the Injection Commissioning tool
must be used. This tool is an integrated part of the PCM600 tool.
1 1 1
= +
Z Z ref Z f
=
1 1 1
= -
Zf Z Z ref
EQUATION2405 V1 EN
1 æ1 1 ö
= Re ç - ÷
Rf ç ÷
è Z Z ref ø
EQUATION2421 V1 EN
RAlarm and RTrip are the two resistance levels given in the settings. The values of
RAlarm and RTrip are given in Ω.
An alarm signal ALARM is given after a set delay tAlarm if Rf < RAlarm
217
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
ROTIPHIZ
Uinj
Rshunt
2
1
3
4
6 5
I Inj u_i_ref
Z Measured
Z Bare
¸ I
Rf X
Compare & S U Inj u_u_ref
Evaluate
7
K2
K1
U
ZRef1
ZRef2 REX060
REG670
IEC10000327-2-en.vsd
IEC10000327 V1 EN
Figure 110: Simplified logic diagram for sensitive rotor earth fault protection,
injection based ROTIPHIZ
1 The sensitive rotor earth fault protection function receives amplified injected voltage and
current via the REX060 unit as two voltages signals. (Voltage inputs in the IED)
2 The phasor of injected voltage UInj and phasor of injected current IInj is calculated by using
special filter from raw samples. Observe that phasors are calculated for the injected
frequency.
3 The complex bare impedance is calculated from Uinj / Iinj.
6 The fault resistance (Rf) is calculated from the complex measured impedance and a
selected complex reference.
7 Selection of one (out of maximum 2) ZRef.
218
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Rf tAlarm
a
a<b t ALARM
b OR
RAlarm
a TRIP
a<b
b
RTrip
IEC10000326-2-en.vsd
IEC10000326 V1 EN
If the fault resistance Rf is smaller than RAlarm and longer than alarm delay (using
delay-on), output ALARM is set. If the fault resistance Rf is smaller than RTrip,
using internal trip time characteristic, output signal TRIP is set after the calculated
time. For trip time delay, see fig 112
When 1s filter length is used and the fault resistance is equal to the set value RTrip,
the trip time is about 10 s. If the fault resistance is estimated to be 0 Ω, the trip
delay is 2 s. For values in between, the delay follows the linear interpolation
describing the fault resistance time characteristic.
219
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Trip time
10 × FilterLength
2 × FilterLength
Fault resistance
RTrip RAlarm
IEC11000002-1-en.vsd
IEC11000002 V1 EN
A third high level step for the detection of excitation system earth faults on the AC
side of the excitation rectifier is available. This step uses the network frequency (50
or 60 Hz) for the evaluation. If an earth fault occurs at the AC side of the excitation
system rectifier, there is a fundamental frequency component at the measured
voltage and current injection points.
The third high level step is not applicable if mixed signals are used, that is when
the REX060 is used for both rotor and stator earth fault protection and only two,
instead of four, analog inputs on the IED are used.
The sensitive rotor earth fault protection function in IED require a number of
settings. The settings k1, k2 and the reference impedance require measurements on
the generator performed by the ICT (injection commissioning tool). The factors are
derived in connection to the calibration measurements during commissioning. ICT
is an integrated part of the PCM600 tool.
220
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
There are five different parts of the ICT tool to be performed at commissioning and
operation:
1. Installing
2. Calibrating
3. Commissioning
4. Monitoring
5. Auditing
Before proceeding make sure that all necessary connections are in place.
Installing
When the injection is started, check that the injected voltage and current are within
the permissible limits. If not, adjust the settings in the injection unit REX060. The
ICT tool will check automatically for slight differences between actual injected and
set injection frequency (for example, due to accuracy of the REX060 hardware).
Set manually the actual frequency value measured by ICT in the IED via PST.
The high accuracy of this frequency is essential for proper operation of the
protection under different operating conditions.
Calibrating
The calibration is based on three measurement steps:
1. The injection is made to the faultless generator and the measured complex
impedance is stored.
2. A known resistance is connected between one rotor pole (see Figure 113) and
earth. The injection is made to the generator and the measured complex
impedance is stored.
3. The one rotor pole (see Figure 113) is directly short-circuited to the earth. The
injection is made to the generator and the measured complex impedance is stored.
DC DC DC
Crot C rot Crot
AC AC AC
IEC11000205-1-en.vsd
IEC11000205 V1 EN
221
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
The sequence of the calibration session follows a scheme shown in the tool.
• Calibration sequence 1: The injection must be activated and the rotor must be
left with no impedance connected. The ICT now makes consecutive
measurements until the statistical error reaches an acceptable value. This is
graphically shown in a diagram. The user stops the sequence by acceptance of
the measurement. The result is stored for later calculations.
• Calibration sequence 2: A known resistor is connected between the rotor
winding and earth. The value of the resistance is the input to ICT. The ICT
now makes consecutive measurements until the statistical error reaches an
acceptable value. This is graphically shown in a diagram. The user stops the
sequence by acceptance of the measurement. The result is stored for later
calculations.
• Calibration sequence 3: The generator rotor winding is now directly connected
to earth. The ICT now makes consecutive measurements until the statistical
error reaches an acceptable value. This is graphically shown in a diagram. The
user stops the sequence by acceptance of the measurement. The result is stored
for later calculations.
After the three measurements ICT calculates the complex factors k1 and k2. The
reference impedance RefR1 + jRefX1 is also calculated. After this the values are
downloaded to the parameter setting in PCM600. From PCM600 the settings are
downloaded to IED.
During the three measurements described above a check is made that there are
sufficient changes in the measured impedance in order to guarantee that there is no
primary fault from the beginning or other problems due to the installation or
calibration procedure.
Now the reference impedance is derived for one operational state. It might be
necessary to make measurements to derive reference impedance for other
operational cases. For information on this, see Commissioning below.
Commissioning
There is a possibility to have two different reference impedances. The need to
change the reference impedance is due to different operating conditions of the
machine.
In the commissioning part of ICT this can be done. For each operation state of
interest a measurement is performed. If the reference impedance differs from the
first one, calculated under the calibration session, the new reference impedance is
stored by the command; Submit toParameter Setting.
If more than one reference impedance are to be used, there must be a logic
configured to detect such changes in the operation states that requires a change of
reference impedance.
222
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Monitoring
In the monitoring part the calibration can be checked by applying the known fault
resistance and compare it with the actual function measurement. It is also possible
to identify operational states where change of reference impedance is required.
Auditing
In the auditing part calibration and commissioning reports are made.
223
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Convert the integer output signal to binary and see table below for interpretation of
individual bits:
The priority of the signals is set that the group priority 1 overrides the group
priority 2 and 3, and priority 2 overrides priority 3. Note that the ERRSTAT signal
can enable several error cases at the same time.
224
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
• Prio1 = B0, B1
• Prio2 = B3, B4, B5, B6
• Prio3 = B2, B7
IEC10000297-2-en.vsd
IEC10000297 V1 EN
225
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
226
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
227
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
6.6.1 Introduction
The 100% stator earth-fault protection STTIPHIZ is used to detect earth faults in
the stator windings of generators and motors. STTIPHIZ is applicable for
generators connected to the power system through a unit transformer in a block
connection. An independent signal with a certain frequency different from the
generator rated frequency is injected into the stator circuit. The responce of this
injected signal is used to detect stator earth faults.
To implement the above concept, a separate injection box is required. The injection
box generates a square wave voltage signal which for example can be fed into the
secondary winding of the generator neutral point voltage transformer or grounding
transformer. This signal propagates through this transformer into the stator circuit.
The magnitude of the injected voltage signal is measured on the secondary side of
the neutral point voltage transformer or grounding transformer. In addition, the
resulting injected current is measured through a resistive shunt located within the
injection box. These two measured values are fed to the IED. Based on these two
measured quantities, the IED determines the stator winding resistance to ground.
The resistance value is then compared with the preset fault resistance alarm and
trip levels.
The protection function can not only detect the earth fault at the generator star
point, but also along the stator windings and at the generator terminals, including
the connected components such as voltage transformers, circuit breakers, excitation
transformer and so on. The measuring principle used is not influenced by the
generator operating mode and is fully functional even with the generator at
standstill. It is still required to have a standard 95% stator earth-fault protection,
based on the neutral point fundamental frequency displacement voltage, operating
in parallel with the 100% stator earth-fault protection function.
Requires injection unit REX060 and optional shunt resistor unit REX062 for
correct operation.
228
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
In the REX060 unit the injection voltage and current signals are amplified to a
level adapted to the analogue voltage inputs of IED. In IED the measured signals
are processed and evaluation will give detection of stator faults.
10
4 Step-up
Transformer
U>
Uinj 1
Rshunt
7 5
~ Generator
6
100% SEF
I
RN
U
2
9 REX060/SIM module 8
95 % SEF
REG670 IEC11000067-2-en.vsd
Generator Protection Panel
IEC11000067 V1 EN
229
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Injection Stator
Injection Rotor
18 18
X62 X82
PSM
1 1
5 5
Power
Stator
Rotor
Backplane
IEC11000015-1-en.vsd
IEC11000015 V1 EN
The REX060 unit is a common unit that can be equipped for either rotor or stator
earth fault protection, or for both. The REX060 has specific injection modules for
rotor and stator protection. The REX060 generates square wave signals, where one
is used for injection to the stator neutral point and the other to the field winding
circuit (rotor circuit), if configured for both stator and rotor protection. The injected
voltages and currents are measured by the unit and amplified, giving voltage
signals both for the injected voltage and current, and adapted to the analogue inputs
of IED. The injection unit REX060 shall be located close to the IED.
For the stator earth fault protection, there are some settings necessary for REX060:
REX060 will also continuously check the measured signal for detection of
saturation which could cause error in the evaluation in IED. If saturation level is
reached, a binary output contact is activated, which is connected to IED. Also other
errors in injection will activate another output contact to IED for blocking the
function.
The output is also protected by a fuse. If this fuse is blown, it is caused by external
voltage source, since the injection unit cannot provide enough energy to blow this
fuse.
230
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Refer to the Hardware section in this manual for a detailed description of REX060.
There are several principles for system earthing of synchronous generators. The
choice of earthing method depends on different factors:
Normally the generator system has some kind of high resistance earthing, giving
earth fault current within the range 5 – 20 A, thus preventing serious damages in
case of stator earth faults. Direct earthing will give too high earth fault current
level. Isolated generator system will give risk of transient overvoltages.
A B C
IEC110000066-1-en.vsd
IEC11000066 V1 EN
231
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
This earthing method utilizes a high resistance in the primary circuit by inserting
resistor RN between the generator neutral and the ground. The actual resistance
value of RN is generally in order of kΩ. Such high resistance is required in order to
limit the primary earth fault current to a quite small value (i.e. always < 20A and
quite often < 10A primary). Actual primary earth fault current can be calculated as
follows:
U G _ Ph - Ph
I =
3 × RN
EF_Max
EQUATION2515 V1 EN
where:
RN is the ohmic value of the primary resistor
U G _ Ph - Ph U2
U EF_Max = ×
3 U1
EQUATION2516 V1 EN
where:
U2/U1 is the turn (i.e. rated voltage) ratio of the VT
UG_Ph-Ph is the protected generator rated phase to phase voltage
232
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
2
æ U1 ö
REq = ç ÷ × RN
èU2 ø
EQUATION2517 V1 EN
where:
U1/U2 is the turn (i.e. rated voltage) ratio of the distribution transformer
RN is the ohmic value of the resistor connected to the secondary winding
The distribution transformer typically has rating of several kVA (e.g. 33kVA) and
rated secondary winding voltage of up to 240V. Note that maximum voltage on the
secondary side of the distribution transformer for an earth fault at generator
terminals can be calculated as follows:
U G _ Ph - Ph U2
U EF_Max = ×
3 U1
EQUATION2516 V1 EN
where:
U2/U1 is the turn (i.e. rated voltage) ratio of the distribution transformer
UG_Ph-Ph is the protected generator rated phase to phase voltage
Note that in case of an earth fault in the stator, the secondary current through the
RN resistor will be often in order of couple of hundred amperes. This maximum
secondary current can be calculated as follows:
U EF _ Max
I EF _ Sec =
RN
EQUATION2518 V1 EN
233
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
2
æ U1 ö
REq = ç ÷ × RN
è 3 ×U 2 ø
EQUATION2519 V1 EN
where:
U1/U2 is the turn (i.e. rated voltage) ratio of one phase of the power transformer, e.g.
8 kV
3
500V
3
EQUATION2521 V1 EN
The three-phase power transformer typically has rating of several tens of kVA (e.g.
129kVA) and rated secondary winding voltage of up to 550V. Note that maximum
voltage across secondary resistor RN for an earth fault at generator terminals can
be calculated as follows:
U2
U EF_Max = 3 ×U G _ Ph - Ph ×
U1
EQUATION2520 V1 EN
where:
U2/U1 is the turn (i.e. rated voltage) ratio of one phase of the power transformer, e.g.
500V
3
8 kV
3
EQUATION2522 V1 EN
Note that in case of an earth fault in the stator, the secondary current through the
RN resistor will be often in order of couple of hundred amperes. This maximum
secondary current can be calculated as follows:
U EF _ Max
I EF _ Sec =
RN
EQUATION2518 V1 EN
For all the alternatives the 100% stator earth fault protection can be applied.
234
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Z Bare
Z Measured
Z series Iinj
Cstat
a +
R fault
Û UN
Rf Cstat RN ZmT Uinj
-
b
Iinj
Stator Reference
+ a Impedance ZRef
RN Uinj
- b
IEC11000008-4-en.vsd
IEC11000008 V1 EN
There are some alternatives for connection of the neutral point resistor as shown in
figure 119 (low voltage neutral point resistor connected via a DT).
235
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Cstat
Iinj
a
+
RN Uinj
-
b
IEC11000009-2-en.vsd
IEC11000009 V1 EN
236
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
I inj
a
+
RN
C stat U inj
-
b
IEC11000010-3-en.vsd
IEC11000010 V1 EN
It is also possible to make the injection via VT open delta connection, as shown in
figure 121.
237
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
U1 / U2
Y
Y
Y
I inj
a
+
Rd U inj
-
C stat b
2
æU ö
R d >>çç 1 ÷÷ × R N
èU2 ø
RN
IEC11000011-3-en.vsd
IEC11000011 V1 EN
238
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
recommended to make the injection via the open delta VT on the terminal side in
most applications.
Note that it is possible to connect two REG670 in parallel to the REX060 injection
unit in order to obtain redundant measurement in two separate IEDs. However, at
commissioning both REG670 IEDs must be connected during calibration procedure.
From the REX060 the injected voltage and current are delivered as AC voltages to
IED. The injected voltage and current is measured and analyzed in the protection
function software within IED. The measured injected voltage and current are first
processed by means of special filtering so that the signals are referred to the
injected frequency only.
U Inj
Z bare =
I Inj
EQUATION2500 V1 EN
239
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
ZMeasured ZBare
Z series Iinj
Rf Z shunt Uinj
IEC11000003-2-en.vsd
IEC11000003 V1 EN
Z Measured = k1 × Z bare + k 2
EQUATION2501 V1 EN
The factors k1 and k2 [Ω] are derived from measurements during commissioning,
where calibration to known fault resistance will be used to convert the
measurement to true primary impedance. The factor k1 will compensate for
transformer ratio and other factors to achieve impedance values related to the
primary system. The factor k2 [Ω] will compensate for the series impedance Zseries
If the measured impedance is larger than the setting openCircuitLimit, the output
OPCIRC is set TRUE. If OPCIRC is set, it means there is a strong likelihood that
the generator neutral resistor is not anymore connected to ground, since only the
capacitive part in the circuit is left. The open circuit is only applied on the stator
winding protection. To make the open circuit limit more stable a hysteresis is
added. If OPCIRC is TRUE, the measured fault impedance must drop below open
circuit limit * (1 - OpenCircLim) to reset. The hysteresis is hidden and set to a
default value of 10% of open Circuit limit for the stator.
240
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Open- circuit
characteristics
no open- circuit open- circuit
Open Circuit
Hysteresis
{Z } re
0 Measured
openCircuitLimit
IEC11000073-1-en.vsd
IEC11000073 V1 EN
Blocking: The output OPCIRC is blocked during an error occurring and during
initialization of function.
Detailed Set: If the total measured real part of the impedance is greater than the
setting OpenCircLim the output OPCIRC is TRUE, see figure 109.
The healthy impedance is equal to the parallel connection of the neutral point
resistor (RN), the capacitive reactance between the stator windings and earth (1/
ωCstat), the transformer magnetization impedance (ZmT) and the earth fault
resistance (Rf). The series resistance in the injection circuit is eliminated by k2. Rf
is very large in the non-faulted case and the measured impedance is equal to the
stator reference impedance:
1 1 1
= + jw C stat +
Z ref RN Z mT
EQUATION2502 V1 EN
Where
w = 2p × finj
EQUATION2503 V1 EN
The injected frequency finj of the square wave, is a set value, deviating from the
fundamental frequency (50 or 60 Hz). The injected frequency can be set within the
range 50 – 250 Hz with recommend value 87 Hz in 50 Hz systems and 103 Hz in
60 Hz systems.
The reference impedance can vary depending on the operational state. The reason
for this can be the following:
241
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
• The influence from the impedance ZmT will be different when the generator is
stand-still and when it is in operation
• The capacitance to earth will vary if the generator breaker is open or closed
• The capacitance will vary if the generator is energized or not depending on
stator end winding corona protection
• Non-linearity of used injection transformer, different properties at low and
high total voltage and temperature changes
• Impedance to ground is affected by auxiliary loads connected between
generator and unit transformer. If these loads vary, the estimated earth fault
resistance will be affected.
RMS voltage (rmsVolt) value at the injection point can be used for detecting when
a reference needs to be changed and logical outputs can be set to reflect whether
the RMS voltage is higher or lower than a prescribed value. There is one such
output for the voltage signal and one for the current signal. It is advantageous to
use RMS to determine a change of machine condition because the RMS makes a
distinction between the measured values and the total amplitude of the signal. The
standstill condition only contains the injected frequency, while the full load
condition and full speed condition contains other frequencies, which amplitudes
may change under varying machine conditions.
In case of a stator earth fault with fault impedance Zf the measured admittance will
be:
1 1 1
= +
Z Z ref Zf
EQUATION2513 V1 EN
242
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
1 1 1
= -
Zf Z Z ref
EQUATION2514 V1 EN
1 æ1 1 ö
= Re ç - ÷
Rf ç ÷
è Z Z ref ø
EQUATION2421 V1 EN
• RAlarm given in Ω. If
R f < RAlarm
EQUATION2524 V1 EN
R f < RTrip
EQUATION2523 V1 EN
If the fault resistance is slightly below the set value RTrip the trip time will be
about 10 s with default filter length of 1 s. If the fault resistance is estimated to 0 Ω
the trip delay will be 2 s with default filter length of 1 s. For values in between the
delay will follow linear interpolation describing the fault resistance time relation,
as shown in figure 124.
Note that actual tripping time is dependent on the set parameter FilterLength which
has default value of 1s.
243
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Trip time
10 × FilterLength
2 × FilterLength
Fault resistance
RTrip RAlarm
IEC11000002-1-en.vsd
IEC11000002 V1 EN
During run-up and shut down of the generator, i.e. when the rotational speed of the
generator changes, there will occur harmonic voltages with varying frequency at
the injection equipment connection point (for example see voltage generator Un in
Figure 118). If such frequencies interfere with the injected frequency this might
create an error in the fault resistance estimation. Such situations are identified in
the function and the function is automatically stabilized to prevent unwanted
operation of the protection.
The following automatic choice for the actual reference impedance can for
example be made:
244
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
• Generator voltage < set value and generator circuit breaker open: Reference
impedance 1
• Generator voltage > set value and generator circuit breaker open: Reference
impedance 2
• Generator voltage > set value and generator circuit breaker closed: Reference
impedance 3
From the measured impedance the stator earth fault resistance can be estimated
since the reference impedance is known. An alarm level (Ω) is set at a higher value
and the ALARM signal is activated after a set alarm delay time. A trip level (Ω) is
also set at a lower value. When the trip level is reached a TRIP signal is activated
as shown in figure 124.
245
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
STTIPHIZ
Uinj
Rshunt
2
1
3
4
6 5
I Inj u_i_sef
Rf Z Measured
Z Bare I
X
Compare & S U Inj u_u_sef
Evaluate
K2 K1
U
ZRef1
7 ZRef2
ZRef3 REX060
ZRef4
SELECT REFERENCE
ZRef5
tON=0.5s UN un
95% Trip a U
t a>b
b
UN> = 5% 8
9
95% Stator earth fault protection
REG670
IEC10000325-2-en.vsd
IEC10000325 V1 EN
Figure 125: Simplified logic diagram for 100% stator earth fault protection
STTIPHIZ
1 The 100% stator earth fault protection function receives amplified injected voltage and
current via the REX060 unit as two voltage signals. (Voltage inputs in the REG670).
2 The phasor of injected voltage UInj and phasor of injected current IInj is calculated by using
special filter from raw samples. Observe that phasors are calculated for the injected
frequency.
3 The complex bare impedance is calculated from Uinj / Iinj.
6 The fault resistance (RFault) is calculated from the complex measured impedance and a
selected complex reference.
7 Selection of one (out of maximum 5) ZRef.
8 Fourier filter to derive the phasor of zero sequence voltage at fundamental frequency
9 The 95% stator earth fault zero sequence over voltage function must operate in parallel
with STTIPHIZ.
246
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Rf tAlarm
a
a<b t ALARM
b OR
RAlarm
a TRIP
a<b
b
RTrip
IEC10000326-2-en.vsd
IEC10000326 V1 EN
If the fault impedance Rf is smaller than RAlarm and last longer than set alarm delay
(using delay-on), output ALARM is set. If the fault impedance Rf is smaller than
RTrip, output signal TRIP is set after the calculated time. For trip time delay, see fig
124
The 100% earth fault protection function in REG670 require a number of settings.
The settings k1, k2 and the reference impedance require measurements made on the
generator and protection set-up. This has to be done during commissioning of the
protection. The factors are derived in connection to calibration measurements
during commissioning. In connection with this calibration also the reference
impedance is derived. To do this the ICT tool (Injection Commissioning Tool) has
to be used. This tool is an integrated part of the PCM600 tool.
Further more, ICT also helps the commissioning engineer to perform successful
installation trough its validating capabilities. Underneath the shell, during
installation, commissioning and calibration, ICT performs various tests using
signal analysis, to verify that the installation itself is acceptable and calibration has
been performed in the right manner. Besides carrying out the actual tests, ICT also
gives the commissioning engineer tips if possible issues may occur during the
commissioning stage.
When ICT is started, 100% stator earth fault protection is chosen for the
commissioning of this function.
247
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
There are five different parts that needs to be performed using the ICT tool:
1. Installing
2. Calibrating
3. Commissioning
4. Monitoring
5. Auditing
Installing
The injection is started and level of injected voltage and current is checked if they
are within the permissible range. If not the settings of the injection unit REX060
must be adjusted. Also the injection frequency is checked and stored for use in ICT
and in IED.
Calibration
Step 1: Injection is made to the non-faulted generator and the measured complex impedance is
stored.
Step 2: A resistor with known resistance is connected between the primary object (stator circuit).
Injection is made to the generator and the measured complex impedance is stored.
Step 3: The primary object (stator circuit) is directly short circuited to earth. Injection is made to
the generator and the measured complex impedance is stored.
The sequence of the calibration session follows a scheme shown in the tool.
After the three measurements ICT calculates the complex factors k1 and k2. The
first reference impedance RefR1 + jRefX1 is also calculated. After this the values
are downloaded to the parameter setting part of the PCM600 tool. From PCM600
the setting can be downloaded to IED.
It is important to save the settings after download to IED, otherwise the ICT cannot
perform the correct calculations. ICT compares settings in PCM600 and IED each
time a measurement is started, if these are not equal, no measurement should be made.
During the three measurements described above a check is made that there are
sufficient changes in the measured impedance in order to guarantee that the
function is capable of detecting a fault in the actual installation.
Now the reference impedance is derived for one operational state. It might be
reasonable to make measurements to derive reference impedance for other
operational cases. This is done under the point Commissioning described below.
Commissioning
248
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
Comment: The capacitance will change when switching in breaker between step-up
transformer and generator.
Neutral point RMS voltage (rmsVolt) can be used for detecting when a reference
needs to be changed and logical outputs can be set to reflect whether the RMS
voltage is higher or lower than a prescribed value. There is one such output for the
voltage signal and one for the current signal
If more than one reference impedance is to be used there must be logics configured
to detect changes in operation states where the reference impedance shall be
changed. Further, the monitoring part should be consulted if the sensitivity to earth
faults is to be set at the highest possible value as this depends on the properties of
the individual site.
Monitoring
In the monitoring part the calibration can be checked. It is also possible to identify
operational states where change of reference impedances is required.
Auditing
In the auditing part reports from calibration and commissioning are made.
249
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
Convert the integer output signal to binary and see table below for interpretation of
individual bits:
250
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
The priority of the signals is set that the group priority 1 overrides the group
priority 2 and 3, and priority 2 overrides priority 3. Note that the ERRSTAT signal
can enable several error cases at the same time.
• Prio1 = B0, B1
• Prio2 = B3, B4, B5, B6
• Prio3 = B2, B7
IEC10000298-2-en.vsd
IEC10000298 V1 EN
251
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
252
Technical reference manual
1MRK 502 027-UEN A Section 6
Impedance protection
253
Technical reference manual
Section 6 1MRK 502 027-UEN A
Impedance protection
254
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
SYMBOL-Z V1 EN
7.1.1 Introduction
The instantaneous three phase overcurrent function has a low transient overreach
and short tripping time to allow use as a high set short-circuit protection function.
There is also a possibility to activate a preset change of the set operation current
(StValMult) via a binary input (ENMULT). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.
255
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEC04000391-2-en.vsd
IEC04000391 V2 EN
256
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
7.2.1 Introduction
The four step phase overcurrent protection function OC4PTOC has an inverse or
definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always
definite time delayed.
All IEC and ANSI inverse time characteristics are available together with an
optional user defined time characteristic.
The directional function is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.
257
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
U3P
TRIP
Harmonic harmRestrBlock
I3P Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
en05000740.vsd
IEC05000740 V1 EN
A common setting for all steps, StartPhSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out
of 3 or 3 out of 3.
258
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component
and higher harmonic current components are almost completely suppressed. If
RMS option is selected then the true RMS values is used. The true RMS value in
addition to the fundamental frequency component includes the contribution from
the current DC component as well as from higher current harmonic. The selected
current values are fed to OC4PTOC.
In a comparator, for each phase current, the DFT or RMS values are compared to
the set operation current value of the function (I1>, I2>, I3> or I4>). If a phase
current is larger than the set operation current, outputs START, STx, STL1, STL2
and STL3 are, without delay, activated. Output signals STL1, STL2 and STL3 are
common for all steps. This means that the lowest set step will initiate the
activation. The START signal is common for all three phases and all steps. It shall
be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.
Service value for individually measured phase currents are also available on the
local HMI for OC4PTOC function, which simplifies testing, commissioning and in
service operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and the relation is compared to a set
restrain current level.
The function can be directional. The direction of the fault current is given as
current angle in relation to the voltage angle. The fault current and fault voltage for
the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
voltage is a combination of the apparent voltage (85%) and a memory voltage
(15%). The following combinations are used.
U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN (Equation 52)
U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN (Equation 53)
U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN (Equation 54)
Table continues on next page
259
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN (Equation 55)
U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN (Equation 56)
U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN (Equation 57)
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition
seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle AngleRCA for the function
and an angle window AngleROA.
260
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Reverse
Uref
RCA
ROA
ROA Forward
Idir
en05000745.vsd
IEC05000745 V1 EN
The default value of AngleRCA is –65°. The parameters AngleROA gives the angle
sector from AngleRCA for directional borders.
A minimum current for directional phase start current signal can be set:
IminOpPhSel.
If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is
available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in section "Inverse
characteristics".
All four steps in OC4PTOC can be blocked from the binary input BLOCK. The
binary input BLKSTx (x=1, 2, 3 or 4) blocks the operation of respective step.
261
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEC06000187-2-en.vsd
IEC06000187 V2 EN
262
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
263
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
264
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
265
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
266
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
267
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
268
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
269
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEF V1 EN
7.3.1 Introduction
The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than the typical eighty percent of the line
at minimum source impedance. EFPIOC can be configured to measure the residual
current from the three-phase current inputs or the current from a separate current
input. EFPIOC can be blocked by activating the input BLOCK.
There is also a possibility to activate a preset change of the set operation current
via a binary input (enable multiplier MULTEN). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.
270
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
EFPIOC function can be blocked from the binary input BLOCK. The trip signals
from the function can be blocked from the binary input BLKAR, that can be
activated during single pole trip and autoreclosing sequences.
IEC06000269-2-en.vsd
IEC06000269 V2 EN
271
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
7.4.1 Introduction
The four step residual overcurrent protection EF4PTOC has an inverse or definite
time delay independent for each step separately.
All IEC and ANSI time-delayed characteristics are available together with an
optional user defined characteristic.
272
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
EF4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.
EF4PTOC can be configured to measure the residual current from the three-phase
current inputs or the current from a separate current input.
These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.
The function always uses Residual Current (3I0) for its operating quantity. The
residual current can be:
273
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of
the fundamental frequency component of the residual current is derived. The
phasor magnitude is used within the EF4PTOC protection to compare it with the
set operation current value of the four steps (IN1>, IN2>, IN3> or IN4>). If the
residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This
signal will, without delay, activate the output signal STINx (x=step 1-4) for this
step and a common START signal.
The function can be set to use voltage polarizing, current polarizing or dual polarizing.
Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage
-3U0 as polarizing quantity U3P. This voltage can be:
where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
Note! In order to use this all three phase-to-earth voltages must be connected to three IED VT inputs.
274
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor
of the fundamental frequency component of the residual voltage is derived. This
phasor is used together with the phasor of the operating current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a
minimum level defined by setting parameter UpolMin.
It shall be noted that –3U0 is used to determine the location of the earth fault. This
insures the required inversion of the polarizing voltage within the earth-fault function.
Current polarizing
When current polarizing is selected the function will use the residual current (3I0)
as polarizing quantity IPol. This current can be:
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
275
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
which will be then used, together with the phasor of the operating current, in order
to determine the direction to the earth fault (Forward/Reverse). In order to enable
current polarizing the magnitude of polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.
Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the
voltage based and current based polarizing in accordance with the following formula:
Then the phasor of the total polarizing voltage UTotPol will be used, together with
the phasor of the operating current, to determine the direction of the earth fault
(Forward/Reverse).
The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx to provide
external directional control (that is, torque control) by for example using one of the
following functions if available in the IED:
The base quantities shall be entered as setting parameters for every earth-fault
function. Base current (IBase) shall be entered as rated phase current of the
protected object in primary amperes. Base voltage (UBase) shall be entered as
rated phase-to-phase voltage of the protected object in primary kV.
276
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:
Simplified logic diagram for one residual overcurrent step is shown in figure 133.
277
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
BLKTR
IMinx Characteristx=DefTime
X T b
a>b
F a
TRINx
tx AND
|IOP|
a OR
a>b
b
STINx
INxMult AND
X T
INx> F tMin
AND Inverse
BLKSTx
BLOCK Characteristx=Inverse
2ndHarm_BLOCK_Int
OR
HarmRestrainx=Off
DirModex=Off OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC10000008-1-en.vsd
IEC10000008 V1 EN
Figure 133: Simplified logic diagram for residual overcurrent step x, where x =
step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, STINx and TRINx, can be blocked from the binary
input BLKSTx. The trip signals from the function can be blocked from the binary
input BLKTR.
The protection has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the parameter setting
polMethod. The polarizing quantity will be selected by the function in one of the
following three ways:
The operating and polarizing quantity are then used inside the directional element,
as shown in figure 134, in order to determine the direction of the earth fault.
278
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Operating area
STRV
0.6 * IN>DIR
Characteristic for reverse
release of measuring steps
-RCA -85 deg
Characteristic
for STRV 40% of
IN>DIR RCA +85 deg
RCA
65° Upol = -3U 0
STFW
I op = 3I0
Operating area
Characteristic
for STFW IEC11000243-1-en.ai
IEC11000243 V1 EN
279
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
|Iop|
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b
AND STFW
IN>Dir b
FORWARD_Int
X
0.4
FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin
Characteristic
Directional
polMethod=Dual UPol IPolMin
T
Iop
polMethod=Current 0.0 F
OR
UTotPol
IPol AND REVERSE_Int
T RVS
0.0 F
UIPol STAGE1_DIR_Int
RNPol Complex X T STAGE2_DIR_Int
XNPol Number 0.0 F STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND
IEC07000067-4-en.vsd
IEC07000067 V4 EN
Figure 135: Simplified logic diagram for directional supervision element with integrated directional
comparison step
In addition to the basic functionality explained above the 2nd harmonic blocking
can be set in such way to seal-in until residual current disappears. This feature
280
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-
in feature will be activated when all of the following three conditions are
simultaneously fulfilled:
Once Block for Parallel Transformers is activated the basic 2nd harmonic blocking
signal will be sealed-in until the residual current magnitude falls below a value
defined by parameter setting UseStartValue (see condition 3 above).
Simplified logic diagram for 2nd harmonic blocking feature is shown in figure 136.
281
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
BLOCK
Extract second
IOP 2NDHARMD
harmonic current a
a>b
OR
component 2ndHarmStab b
X
Extract
fundamental
q-1
current component
t=70ms OR
t AN OR 2ndH_BLOCK_Int
D
BlkParTransf=On
|IOP|
a
a>b
b
UseStartValue
IN1>
IN2>
IN3>
IN4>
en07000068-2.vsd
IEC07000068 V2 EN
Figure 136: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature
Integrated in the four step residual overcurrent protection are Switch on to fault
logic (SOTF) and Under-Time logic. The setting parameter SOTF is set to activate
either SOTF or Under-Time logic or both. When the circuit breaker is closing there
is a risk to close it onto a permanent fault, for example during an autoreclosing
sequence. The SOTF logic will enable fast fault clearance during such situations.
The time during which SOTF and Under-Time logics will be active after activation
is defined by the setting parameter t4U.
The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected
by setting parameter StepForSOTF. The SOTF logic can be activated either from
change in circuit breaker position or from circuit breaker close command pulse.
The setting parameter ActivationSOTF can be set for activation of CB position
open change, CB position closed change or CB close command. In case of a
residual current start from step 2 or 3 (dependent on setting) the function will give
a trip after a set delay tSOTF. This delay is normally set to a short time (default 200
ms).
The Under-Time logic always uses the start signal from the step 4. The Under-
Time logic will normally be set to operate for a lower current level than the SOTF
282
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
function. The Under-Time logic can also be blocked by the 2nd harmonic restraint
feature. This enables high sensitivity even if power transformer inrush currents can
occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The Under-Time logic is
activated either from change in circuit breaker position or from circuit breaker
close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set
delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms). Practically the Under-Time logic acts as circuit breaker pole-discordance
protection, but it is only active immediately after breaker switching. The Under-
Time logic can only be used in solidly or low impedance grounded systems.
SOTF
Open
tPulse
Closed
ActivationSOTF
Close command
tSOTF
AND
AND t
STIN2
StepForSOTF
STIN3
OperationMode
BLOCK
OFF
SOTF
UNDERTIME TRIP
UnderTime
tUnderTime
SOTF or
2nd Harmonic AND
HarmResSOFT t UnderTime
OR
Open
Close OR
tPulse
Close command
ActUnderTime
AND
STIN4
IEC06000643-2-en.vsd
IEC06000643 V2 EN
Figure 137: Simplified logic diagram for SOTF and Under-Time features
EF4PTOC Logic Diagram Simplified logic diagram for the complete EF4PTOC
function is shown in figure 138:
283
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
signal to
communication
scheme
Directional Check
Element
DirMode
enableDir
harmRestrBlock
3I0 Harmonic
Restraint ³1
Element
CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4
DirectionalMode1-4
en06000376.vsd
IEC06000376 V1 EN
IEC06000424-2-en.vsd
IEC06000424 V2 EN
284
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
285
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
286
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
287
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
288
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
289
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
290
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
291
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEC10000053 V1 EN
7.5.1 Introduction
Four step negative sequence overcurrent protection (NS4PTOC) has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an
optional user defined characteristic.
NS4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.
These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.
292
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
sequence current is calculated from three-phase current input within the IED. The
pre-processing block calculates I2 from the first three inputs into the pre-
processing block by using the following formula:
1
I op = I 2 =
3
(
× IL1 + a × IL 2 + a × IL3
2
)
EQUATION2266 V1 EN (Equation 63)
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
a is so called operator which gives a phase shift of 120 deg, that is, a = 1∠120 deg
a2 similarly gives a phase shift of 240 deg, that is, a2 = 1∠240 deg
A polarizing quantity is used within the protection to determine the direction to the
fault (Forward/Reverse).
Four step negative sequence overcurrent protection NS4PTOC function can be set
to use voltage polarizing or dual polarizing.
Voltage polarizing
When voltage polarizing is selected, NS4PTOC uses the negative sequence voltage
-U2 as polarizing quantity U3P. This voltage is calculated from three phase voltage
input within the IED. The pre-processing block calculates -U2 from the first three
inputs into the pre-processing block by using the following formula:
1
UPol = -U 2 = - × (UL1 + a × UL 2 + a 2 × UL3)
3
EQUATION2267 V1 EN (Equation 64)
293
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
To use this all three phase-to-earth voltages must be connected to three IED VT inputs.
Note that –U2 is used to determine the location of the fault. This ensures the
required inversion of the polarizing voltage within the function.
Dual polarizing
When dual polarizing is selected, the function uses the vectorial sum of the voltage
based and current based polarizing in accordance with the following formula:
Then the phasor of the total polarizing voltage UTotPol is used, together with the
phasor of the operating current, to determine the direction to the fault (Forward/
Reverse).
The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx (where x
indicates the relevant step within the protection) to provide external directional
control (that is, torque control) by for example using one of the following functions
if available in the IED:
The base quantities must be entered as setting parameters for every function. Base
current (IBase) must be entered as rated phase current of the protected object in
primary amperes. In line protections the primary rated current of the CT is chosen.
294
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Simplified logic diagram for one negative sequence overcurrent stage is shown in
the following figure:
295
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
BLKTR
Characteristx=DefTime tx TRx
|IOP| AND
a OR
a>b
ENMULTx b
STx
IxMult AND
X T
Ix> F
Inverse
BLKSTx
BLOCK Characteristx=Inverse
DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC09000683-2-en.vsd
IEC09000683 V1 EN
Figure 140: Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4
NS4PTOC can be completely blocked from the binary input BLOCK. The start
signals from NS4PTOC for each stage can be blocked from the binary input
BLKSTx. The trip signals from NS4PTOC can be blocked from the binary input
BLKTR.
NS4PTOC has integrated directional feature. As the operating quantity current Iop
is always used. The polarizing method is determined by the setting polMethod. The
polarizing quantity can be selected by NS4PTOC in one of the following two ways:
The operating and polarizing quantity are then used inside the directional element,
as shown in figure 134, to determine the direction of the fault.
296
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Reverse
Area
AngleRCA Upol=-U2
Forward
Area
Iop = I2
IEC10000031-1-en.vsd
IEC10000031 V1 EN
297
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
|Iop|
a a>
STRV
b b AND
REVERSE_Int
0.6
X
a a>
STFW
I>Dir b b FORWARD_Int
AND
X
0.4
FWD
AND FORWARD_Int
AngleRCA
C h a r a c e ri s ti c
polMethod=Voltage
OR
D i r e c ti o n a l
UPolMin
polMethod=Dual UPol IPolMin
t
T
Iop
0.0 F
IPol UTotPol
AND REVERSE_Int
RVS
UIPol
RNPol Complex X T
XNPol Number 0.0 F STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND
IEC07000067-4-en.vsd
IEC07000067-4 V1 EN
Figure 142: Simplified logic diagram for directional supervision element with integrated directional
comparison step
298
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
IEC10000054-1-en.vsd
IEC10000054 V1 EN
299
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
300
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
301
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
302
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
303
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
304
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
7.6.1 Introduction
In networks with high impedance earthing, the phase-to-earth fault current is
significantly smaller than the short circuit currents. Another difficulty for earth-
305
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
fault protection is that the magnitude of the phase-to-earth fault current is almost
independent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-
earth faults in high impedance earthed networks. The protection uses the residual
current component 3I0 · cos φ, where φ is the angle between the residual current
and the residual voltage (-3U0), compensated with a characteristic angle.
Alternatively, the function can be set to strict 3I0 level with an check of angle 3I0
and cos φ.
Directional residual power can also be used to detect and give selective trip of phase-
to-earth faults in high impedance earthed networks. The protection uses the
residual power component 3I0 · 3U0 · cos φ, where φ is the angle between the
residual current and the reference residual voltage, compensated with a
characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
In an isolated network, that is, the network is only coupled to earth via the
capacitances between the phase conductors and earth, the residual current always
has -90º phase shift compared to the reference residual voltage. The characteristic
angle is chosen to -90º in such a network.
As the amplitude of the residual current is independent of the fault location the
selectivity of the earth-fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used and
when should the sensitive directional residual power protection be used? Consider
the following facts:
306
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from pre-
processor blocks.
The sensitive directional earth fault protection has the following sub-functions
included:
RCADir = 0 , ROADir = 0
3I0
ϕ = ang(3I0 ) − ang(3Uref )
−3U0 = Uref
3I0 ⋅ cosϕ
IEC06000648-3-en.vsd
IEC06000648 V3 EN
307
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
Uref
RCADir = −90 , ROADir = 90
3I0
3I0 ⋅ cos ϕ
−3U0
IEC06000649_3_en.vsd
IEC06000649 V3 EN
For trip, both the residual current 3I0·cos φ and the release voltage 3U0, must be
larger than the set levels: INCosPhi> and UNRel>.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated. The trip from this sub-function has definite time
delay.
There is a possibility to increase the operate level for currents where the angle φ is
larger than a set value as shown in figure 146. This is equivalent to blocking of the
function if φ > ROADir. This option is used to handle angle error for the instrument
transformers.
308
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
RCADir = 0o
3I0
Operate area
j
-3U0 = Uref
3I0 × cos j
ROADir
IEC06000650_2_en.vsd
IEC06000650 V2 EN
309
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
RCADir = 0º
Operate area
-3U0 =Uref
Instrument
transformer a
RCAcomp
angle error
Characteristic after
angle compensation
en06000651.vsd
IEC06000651 V2 EN
For trip, both the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the
release voltage 3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN are activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction
is defined as 3I0 · 3U0·cos (φ + 180°) ³ the set value.
This variant has the possibility of choice between definite time delay and inverse
time delay.
310
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
RCADir = 0º
ROADir = 80º
Operate area
3I0
80 -3U0
en06000652.vsd
IEC06000652 V2 EN
For trip, both the residual current 3I0 and the release voltage 3U0, shall be larger
than the set levels INDir> and UNREL> and the angle φ shall be in the set sector
ROADir and RCADir.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated.
311
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
Directional functions
For all the directional functions there are directional start signals STFW: fault in
the forward direction, and STRV: start in the reverse direction. Even if the
directional function is set to operate for faults in the forward direction a fault in the
reverse direction will give the start signal STRV. Also if the directional function is
set to operate for faults in the reverse direction a fault in the forward direction will
give the start signal STFW.
This variant shall have the possibility of choice between definite time delay and
inverse time delay. The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set levels (INNonDir>).
Trip from this function can be blocked from the binary input BLKNDN.
When the function is activated binary output signal STNDIN is activated. If the
activation is active after the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN are activated.
There shall also be a separate trip, with its own definite time delay, from this set
voltage level.
For trip, the residual voltage 3U0 shall be larger than the set levels (UN>).
Trip from this function can be blocked from the binary input BLKUN.
When the function is activated binary output signal STUN is activated. If the
activation is active after the set delay tUNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 149.
312
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
INNonDir> STNDIN
t TRNDIN
UN> STUN
t TRUN
OpMODE=3I0cosfi
IN>
&
INcosPhi>
OpMODE=3I03U0cosfi
INUNcosPhi> t
SN
& TRDIRIN
Phi in RCA +- ROA
TimeChar = InvTime
&
OpMODE=3I0 and fi
&
TimeChar = DefTime
DirMode = Reverse
&
Reverse STRV
en06000653.vsd
IEC06000653 V2 EN
Figure 149: Simplified logical diagram of the sensitive earth-fault current protection
IEC07000032-2-en.vsd
IEC07000032 V2 EN
313
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
314
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
315
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
316
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
317
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
SYMBOL-A V1 EN
7.7.1 Introduction
If a power transformer or generator reaches very high temperatures the equipment
might be damaged. The insulation within the transformer/generator will have
forced ageing. As a consequence of this the risk of internal phase-to-phase or phase-
to-earth faults will increase. High temperature will degrade the quality of the
transformer/generator insulation.
The thermal overload protection estimates the internal heat content of the transformer/
generator (temperature) continuously. This estimation is made by using a thermal
model of the transformer/generator with two time constants, which is based on
current measurement.
Two warning levels are available. This enables actions in the power system to be
done before dangerous temperatures are reached. If the temperature continues to
increase to the trip value, the protection initiates a trip of the protected transformer/
generator.
From the largest of the three phase currents a relative final temperature (heat
content) is calculated according to the expression:
318
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
2
æ I ö
Q final =ç ÷÷
ç I ref
è ø
EQUATION1171 V1 EN (Equation 67)
where:
I is the largest phase current
Iref is a given reference current
If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current a start output signal START is activated.
If Q final > Q n
EQUATION1172 V1 EN (Equation 68)
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø
EQUATION1173 V1 EN (Equation 69)
If Q final < Qn
EQUATION1174 V1 EN (Equation 70)
Dt
Qn = Q final - ( Q final - Q n -1 ) × e
-
t
where:
Qn is the calculated present temperature
319
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
When the transformer temperature reaches any of the set alarm levels Alarm1 or
Alarm2 the corresponding output signals ALARM1 or ALARM2 are activated.
When the temperature of the object reaches the set trip level which corresponds to
continuous current equal to ITrip the output signal TRIP is activated.
There is also a calculation of the present time to operation with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1176 V1 EN (Equation 72)
The calculated time to trip can be monitored as it is exported from the function as a
real figure TTRIP.
After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the temperature of the object is above the set lockout release temperature
setting ResLo.
The time to lockout release is calculated, That is, a calculation of the cooling time
to a set value.
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1177 V1 EN (Equation 73)
In the above equation, the final temperature is calculated according to equation 67.
Since the transformer normally is disconnected, the current I is zero and thereby
the Θfinal is also zero. The calculated component temperature can be monitored as it
is exported from the function as a real figure, TRESLO.
When the current is so high that it has given a start signal START, the estimated
time to trip is continuously calculated and given as analogue output TTRIP. If this
calculated time get less than the setting time Warning, set in minutes, the output
WARNING is activated.
320
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
I3P
Calculation
of final
temperature
ALARM1
Actual Temp >
Alarm1,Alarm2
ALARM2
Temp
S LOCKOUT
Binary input:
Forced cooling Management of R
On/Off setting
parameters: Tau,
Actual Temp
IBase Tau used
< Recl
Temp
time to trip
Calculation
of time to
warning if time to trip < set value
trip
Calculation
of time to time to reset of lockout
reset of
lockout
en05000833.vsd
IEC05000833 V1 EN
321
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEC06000272_2_en.vsd
IEC06000272 V2 EN
322
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
323
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
Operate time: Ip = load current before overload IEC 60255–8, class 5 + 200
occurs ms
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 74)
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
3I>BF
SYMBOL-U V1 EN
7.8.1 Introduction
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case the own breaker fails to open. CCRBRF can be current based,
contact based, or an adaptive combination of these two conditions.
Current check with extremely short reset time is used as check criterion to achieve
high security against unnecessary operation.
Contact check criteria can be used where the fault current through the breaker is small.
CCRBRF can be single- or three-phase initiated to allow use with single phase
tripping applications. For the three-phase version of CCRBRF the current criteria
can be set to operate only if two out of four for example, two phases or one phase
plus the residual current start. This gives a higher security to the back-up trip
command.
324
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
The start signal can be phase selective or general (for all three phases). Phase
selective start signals enable single pole re-trip function. This means that a second
attempt to open the breaker is done. The re-trip attempt can be made after a set
time delay. For transmission lines single pole trip and autoreclosing is often used.
The re-trip function can be phase selective if it is initiated from phase selective line
protection. The re-trip function can be done with or without current check. With
the current check the re-trip is only performed if the current through the circuit
breaker is larger than the operate current level.
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, by detection of either low current through RMS
evaluation and a special adapted current algorithm or by open contact indication.
The special algorithm enables a very fast detection of successful breaker opening,
that is, fast resetting of the current measurement. If the current and/or contact
detection has not detected breaker opening before the back-up timer has run its
time a back-up trip is initiated.
• The minimum length of the re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 will however sustain as long as there is an indication of closed
breaker.
• In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out
of 4 where it is sufficient to detect failure to open (high current) in one pole or
high residual current and 2 out of 4 where at least two current (phase current and/
or residual current) shall be high for breaker failure detection.
• The current detection level for the residual current can be set different from the
setting of phase current detection.
• It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
• The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
• It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is insufficient to clear faults, for example at low gas pressure.
325
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
START 30 ms
IEC09000976-1-en.vsd
IEC09000976 V1 EN
IP>
a
a>b
b
FunctionMode Current
OR AND Reset L1
OR
Contact
1 Time out L1
Current and Contact OR
AND
Current High L1
IL1 CB Closed L1
AND
OR
BFP Started L1
a AND AND
a>b OR AND
I>BlkCont b
IEC09000977-1-en.vsd
IEC09000977 V1 EN
t1 TRRETL3
BFP Started L1 From other
t Retrip Time Out L1
phases TRRETL2 OR
TRRET
tPulse
RetripMode No CBPos Check AND
OR TRRETL1
OR
1
OR AND
CB Pos Check
AND
CB Closed L1
CBFLT
IEC09000978-1-en.vsd
IEC09000978 V1 EN
326
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
IN
a
a>b AND
IN> b
CBFLT
AND
t2
BFP Started L1 Backup Trip L1
t AND
OR
t2MPh
AND t
AND
OR OR
tPulse
From other Backup Trip L2 OR TRBU
OR
phases Backup Trip L3
From other BFP Started L2 2 of 3
phases BFP Started L3 tPulse
t3
OR
TRBU2
S Q t
R SR
AND
IEC09000979-1-en.vsd
IEC09000979 V1 EN
Figure 156: Simplified logic scheme of the back-up trip logic function
Internal logical signals Current High L1, Current High L2, Current High L3 have
logical value 1 when current in respective phase has magnitude larger than setting
parameter IP>.
IEC06000188-2-en.vsd
IEC06000188 V2 EN
327
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
328
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
329
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
PD
SYMBOL-S V1 EN
7.9.1 Introduction
An open phase can cause negative and zero sequence currents which cause thermal
stress on rotating machines and can cause unwanted operation of zero sequence or
negative sequence current functions.
Normally the own breaker is tripped to correct such a situation. If the situation
persists the surrounding breakers should be tripped to clear the unsymmetrical load
situation.
en05000287.vsd
IEC05000287 V2 EN
This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.
330
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
There is also a possibility to connect all phase selective auxiliary contacts (phase
contact open and phase contact closed) to binary inputs of the IED, see figure 159.
C.B.
+
poleOneOpened from C.B.
en05000288.vsd
IEC05000288 V1 EN
In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set
delay.
The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discordance function can be blocked during sequences
with a single pole open if single pole autoreclosing is used.
The simplified block diagram of the current and contact based Pole discordance
protection function CCRPLD is shown in figure 160.
331
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
BLOCK
OR
BLKDBYAR
PolPosAuxCont
AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR
PD Signal from CB
AND
EXTPDIND
CLOSECMD t+200 ms
OR
OPENCMD
AND
Unsymmetry current
detection
en05000747.vsd
IEC05000747 V1 EN
• The IED is in TEST mode and CCRPLD has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high
The BLOCK signal is a general purpose blocking signal of the pole discordance
protection. It can be connected to a binary input in the IED in order to receive a
block command from external devices or can be software connected to other
internal functions in the IED itself in order to receive a block command from
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The BLKDBYAR signal blocks the pole discordance operation when a single
phase autoreclosing cycle is in progress. It can be connected to the output signal
1PT1 on SMBRRECfunction block. If the autoreclosing function is an external
device, then BLKDBYAR has to be connected to a binary input in the IED and this
binary input is connected to a signalization “1phase autoreclosing in progress”
from the external autoreclosing device.
If the pole discordance protection is enabled, then two different criteria can
generate a trip signal TRIP:
332
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
If one or two poles of the circuit breaker have failed to open or to close the pole
discordance status, then the function input EXTPDIND is activated from the pole
discordance signal derived from the circuit breaker auxiliary contacts (one NO
contact for each phase connected in parallel, and in series with one NC contact for
each phase connected in parallel) and, after a settable time interval tTrip (0-60 s), a
150 ms trip pulse command TRIP is generated by the Polediscordance function.
• any phase current is lower than CurrUnsymLevel of the highest current in the
three phases.
• the highest phase current is greater than CurrRelLevel of IBase.
If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set
time delay tTrip if the detection occurs in the next 200 ms after the circuit breaker
has received a command to open trip or close and if the unbalance persists. The 200
ms limitation is for avoiding unwanted operation during unsymmetrical load
conditions.
The pole discordance protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs
can be connected to terminal binary inputs if the information are generated from
the field (that is from auxiliary contacts of the close and open push buttons) or may
be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).
IEC06000275-2-en.vsd
IEC06000275 V2 EN
333
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
334
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
SYMBOL-LL V1 EN
7.10.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 162 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a
higher margin and should provide better dependability. On the other hand, the risk
for unwanted operation immediately after synchronization may be higher. One
should set the underpower IED to trip if the active power from the generator is less
than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1% depending on the type of turbine.
When IED with a metering class input CTs is used pickup can be set to more
sensitive value (e.g.0,5% or even to 0,2%).
335
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC09000018-2-en.vsd
IEC09000018 V2 EN
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 173.
336
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
337
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
low, normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) +
Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value, the function will
reset after a set time DropDelay1(2). The reset means that the start signal will drop
out and that the timer of the stage will reset.
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 84)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
TD
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92 in case of slow operating functions.
Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
164.
338
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values
or in the disturbance report. The active power is provided as MW value: P, or in
percent of base power: PPERCENT. The reactive power is provided as Mvar value:
Q, or in percent of base power: QPERCENT.
IEC07000027-2-en.vsd
IEC07000027 V2 EN
339
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
340
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
341
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
DOCUMENT172362-IMG158942
V1 EN
7.11.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 166 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a
higher margin and should provide better dependability. On the other hand, the risk
for unwanted operation immediately after synchronization may be higher. One
should set the underpower IED to trip if the active power from the generator is less
than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more
sensitive value (e.g.0,5% or even to 0,2%).
342
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Figure 166: Reverse power protection with underpower IED and overpower IED
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC06000567-2-en.vsd
IEC06000567 V2 EN
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 180.
343
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
344
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the start signal will drop out
ant that the timer of the stage will reset.
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 94)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k =
0.92 in case of slow operating functions.
Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
168.
345
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of
base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.
IEC07000028-2-en.vsd
IEC07000028 V2 EN
346
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
347
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
348
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
7.12.1 Introduction
Negative-sequence time overcurrent protection for machines NS2PTOC is intended
primarily for the protection of generators against possible overheating of the rotor
caused by negative sequence component in the stator current.
The negative sequence currents in a generator may, among others, be caused by:
• Unbalanced loads
• Line to line faults
• Line to earth faults
• Broken conductors
• Malfunction of one or more poles of a circuit breaker or a disconnector
NS2PTOC can also be used as a backup protection, that is, to protect the generator
in case line protections or circuit breakers fail to clear unbalanced system faults.
where:
349
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
NS2PTOC has a wide range of K settings and the sensitivity and capability of
detecting and tripping for negative sequence currents down to the continuous
capability of a generator.
To avoid oscillation in the output signals, a certain hysteresis has been included.
For both steps, the reset ratio is 0.97.
Step 1 of NS2PTOC can operate in the Definite Time (DT) or Inverse Time
(IDMT) mode depending on the selected value for the CurveType1 parameter. If
CurveType1= Definite, NS2PTOC operates with a Definite Time Delay
characteristic and if CurveType1 = Inverse, NS2PTOC operates with an Inverse
Time Delay characteristic. Step 2 can only operate in the Definite Time (DT)
mode. The characteristic defines the time period between the moment when
measured negative sequence current exceeds the set start levels in parameter I2-1>
or I2-2> until the trip signal is initiated.
350
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
time is depending on the setting of parameter K1, which must be set according to
the generators negative sequence current capacity.
K = I 2 2t
EQUATION2112 V1 EN
Where:
I2 is negative sequence current expressed in per unit of the rated generator current
Operate
time
t1Max
(Default= 1000 s)
t1Min
(Default= 5 s)
K1
Current I2-1>
IEC09000691-2-en.vsd
IEC09000691 V2 EN
ResetMultip
ResetTime [ s ] = ⋅ K1
I 2
NS − 1
I Start
EQUATION2111 V2 EN (Equation 95)
Where
351
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
ResetMultip is multiplier of the generator capability constant K equal to setting K1 and thus
defines reset time of inverse time characteristic
The trip start levels Current I2-1> and I2-2> of NS2PTOC are freely settable over
a range of 3 to 500 % of rated generator current IBase. The wide range of start
setting is required in order to be able to protect generators of different types and sizes.
After start, a certain hysteresis is used before resetting NS2PTOC. For both steps
the reset ratio is 0.97.
The alarm function is operated by START signal and used to warn the operator for
an abnormal situation, for example, when generator continuous negative sequence
current capability is exceeded, thereby allowing corrective action to be taken
before removing the generator from service. A settable time delay tAlarm is
provided for the alarm function to avoid false alarms during short-time unbalanced
conditions.
DT time
selected t1
TR1
Negative sequence current OR
a
a>b
b
I2-1> ST1
AND
Inverse
Operation=ON
Inverse time
BLKST1 selected
BLOCK
IEC08000466-2-en.vsd
IEC08000466-1-EN V2 EN
Figure 171: Simplified logic diagram for step 1 of Negative sequence time
overcurrent protection for machines (NS2PTOC)
352
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
ST1
START
ST2 OR
tAlarm ALARM
TR1
TRIP
TR2 OR
IEC09000690-2-en.vsd
IEC09000690 V2 EN
Figure 172: Simplified logic diagram for the START, ALARM and TRIP signals
for NS2PTOC
IEC08000359-2-en.vsd
IEC08000359-1-EN V2 EN
353
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
354
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
I 22t = K
I 22t = K
7.13.1 Introduction
Inadvertent or accidental energizing of off-line generators has occurred often
enough due to operating errors, breaker head flashovers, control circuit
malfunctions, or a combination of these causes. Inadvertently energized generator
operates as induction motor drawing a large current from the system. The voltage
supervised overcurrent protection is used to protect the inadvertently energized
generator.
355
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
When the maximum phase-to-phase voltage is less than the ArmU< for the period
tArm, it is ensured that the generator is off-line. The ARMED signal will initiate
the overcurrent function. If the calculated maximum current of the three phases is
larger than I> for the period tOC then the TRIP signal becomes activated. Also
START signal becomes activated when overcurrent is detected.
When the maximum phase-to-phase voltage is larger than DisarmU> for the period
tDisarm, it is ensured generator is on line. During this state, undervoltage operation
is disarmed, blocking the overcurrent operation and thus the function becomes
inoperative.
BLOCK input can be used to block AEGGAPC . In addition, the BLKTR input that
blocks the TRIP signal is also present. The input BLKTR can be used if
AEGGAPC is to be used only for monitoring purposes.
Imax_DFT
a
a>b
I> b
tOC
AND TRIP
Operation = ON t
BLOCK
START
ARMED
Uph-ph_max_DFT tArm
a
a<b t
ArmU< b AND
S OUT
ON - Delay
R NOUT
tDisarm
a
t OR
a>b
DisarmU> b
ON - Delay
IEC09000784-2-en.vsd
IEC09000784 V2 EN
356
Technical reference manual
1MRK 502 027-UEN A Section 7
Current protection
IEC09000783-1-en.vsd
IEC09000783 V1 EN
357
Technical reference manual
Section 7 1MRK 502 027-UEN A
Current protection
358
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
2U<
SYMBOL-R-2U-GREATER THAN
V1 EN
8.1.1 Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed
back-up to primary protection.
UV2PTUV has two voltage steps, each with inverse or definite time delay.
359
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay three different modes are available:
• inverse curve A
• inverse curve B
• customer programmable inverse curve
k
t=
æ U < -U ö
ç ÷
è U< ø
EQUATION1431 V1 EN (Equation 98)
360
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
k × 480
t= 2.0
+ 0.055
æ U < -U ö
ç 32 × - 0.5 ÷
è U< ø
EQUATION1432 V1 EN (Equation 99)
é ù
ê ú
ê k×A ú+D
t=
êæ U < -U ö ú
p
êç B × -C÷ ú
ëè U< ø û
EQUATION1433 V1 EN (Equation 100)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U<
down to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 101)
The lowest voltage is always used for the inverse time delay integration. The
details of the different inverse time characteristics are shown in section 22.3
"Inverse characteristics".
Trip signal issuing requires that the undervoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by some special voltage level dependent time curves for the
inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2pickup for the inverse time) the corresponding start output is reset. Here it
should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Note that for the undervoltage function the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 176 and figure 177.
361
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
tReset1
Voltage tReset1
Measured
START Voltage
Hysteresis
TRIP
U1<
Time
START t1
TRIP
Time
Integrator Frozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset IEC05000010-3-en.vsd
IEC05000010 V3 EN
Figure 176: Voltage profile not causing a reset of the start signal for step 1, and inverse time delay
362
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
tReset1
Voltage
tReset1
START
START
Hysteresis Measured Voltage
TRIP
U1<
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset IEC05000011-en-2.vsd
IEC05000011 V2 EN
Figure 177: Voltage profile causing a reset of the start signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
178. Detailed information about individual stage reset/operation behavior is shown
in figure 179 and figure 180 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured.
363
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
ST1
U tReset1 t1
a
b>a t t
TR1
U1<
b AND
OFF ON
Delay Delay
IEC09000785-1-en.vsd
IEC09000785 V1 EN
Un<
START
TRIP
tResetn
tn
IEC10000039-1-en.vsd
IEC10000039 V1 EN
364
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
Un<
START
TRIP
tResetn
tn
IEC10000040-1-en.vsd
IEC10000040 V1 EN
8.1.2.3 Blocking
If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Off resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure 181. The delay of the blocking function must
be set less than the time delay of under voltage function.
365
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN
8.1.2.4 Design
366
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
Step 1
Time integrator TR1L2
MinVoltSelect t1 TRIP
or tReset1
ResetTypeCrv1 TR1L3
TR1
OR
Comparator ST2L1
UL1 < U2< Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 < U2< 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
Comparator 3 out of 3
&
UL3 < U2< Trip ST2
Output OR
Step 2
Time integrator TR2L2
MinVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
OR START
TRIP
OR
en05000012.vsd
IEC05000834 V1 EN
367
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
IEC06000276-2-en.vsd
IEC06000276 V2 EN
368
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
369
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
370
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
371
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
2U>
8.2.1 Introduction
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines etc.
Two step overvoltage protection (OV2PTOV) function can be used to detect open
line ends, normally then combined with a directional reactive over-power function
to supervise the system voltage. When triggered, the function will cause an alarm,
switch in reactors, or switch out capacitor banks.
OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV has an extremely high reset ratio to allow settings close to system
service voltage.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the global set base voltage
UBase, which is set in kV, phase-to-phase.
The setting of the analog inputs are given as primary phase-to-earth or phase-to-
phase voltage. OV2PTOV will operate if the voltage gets higher than the set
372
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
percentage of the set base voltage UBase. This means operation for phase-to-earth
voltage over:
All the three voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of
3 measured voltages have to be higher than the corresponding set point to issue the
corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 104)
373
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 105)
k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 106)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 107)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U< down
to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/100). If
the programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 108)
The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure 184. The details of the different inverse time
characteristics are shown in section "Inverse characteristics"
374
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
Voltage
IDMT Voltage
UL1
UL2
UL3
Time
en05000016.vsd
IEC05000016 V1 EN
Figure 184: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by selected voltage level dependent time curves for the
inverse time mode (IDMT). If the START condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for
the inverse time) the corresponding START output is reset, after that the defined
reset time has elapsed. Here it should be noted that after leaving the hysteresis area,
the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area. The hysteresis value for each step is settable
(HystAbs2) to allow an high and accurate reset of the function. It should be noted
that for Two step overvoltage protection OV2PTOV the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time..
375
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
tReset
1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured
Voltage
Time
START t1
TRIP
Time
Integrator Linear Decrease
Frozen Timer
t1
Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN
Figure 185: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay
376
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
tReset1
Voltage tReset1
START TRIP
START
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset
IEC05000020 V2 EN
Figure 186: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
187. Detailed information about individual stage reset/operation behavior is shown
in figure 179 and figure 180 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured
377
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
ST1
U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-1-en.vsd
IEC10000100 V1 EN
Un>
START
TRIP
tResetn
tn
IEC10000037-1-en.vsd
IEC10000037 V1 EN
378
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
Un>
START
TRIP
tResetn
tn
IEC10000038-1-en.vsd
IEC10000038 V1 EN
8.2.2.3 Blocking
8.2.2.4 Design
379
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
OR TR1
Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
2 outof 3 ST2L3
3 out of 3 Phase 3 Start
Comparator &
UL3 > U2> Trip ST2
OR
Output
START Logic TR2L1
Step 2
Time integrator TR2L2
MaxVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
START
OR
TRIP
OR
en05000013.vsd
IEC05000013-WMF V1 EN
380
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
IEC06000277-2-en.vsd
IEC06000277 V2 EN
381
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
382
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
383
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
8.3.1 Introduction
Residual voltages may occur in the power system during earth faults.
384
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
ROV2PTOV has two voltage steps, each with inverse or definite time delay.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.
The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
385
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 109)
k × 480
t= 2.0
- 0.035
æ 32 × ö
U -U >
ç - 0.5 ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 110)
k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 111)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 112)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U> up to
U> · (1.0 + CrvSatn/100) the used voltage will be: U> · (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN (Equation 113)
The details of the different inverse time characteristics are shown in section
"Inverse characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves
for the inverse time mode (IDMT).
386
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
If the START condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and
tReset2 for the definite time and tIReset1 and tIReset2 for the inverse time) the
corresponding START output is reset, after that the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to
the hysteresis area. Also notice that for the overvoltage function IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 185 and figure 186.
tReset
1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured
Voltage
Time
START t1
TRIP
Time
Integrator Linear Decrease
Frozen Timer
t1
Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN
Figure 192: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay
387
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
tReset1
Voltage tReset1
START TRIP
START
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset
IEC05000020 V2 EN
Figure 193: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
194. Detailed information about individual stage reset/operation behavior is shown
in figure 179 and figure 180 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured
388
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
ST1
U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-1-en.vsd
IEC10000100 V1 EN
Un<
START
TRIP
tResetn
tn
IEC10000039-1-en.vsd
IEC10000039 V1 EN
389
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
Un<
START
TRIP
tResetn
tn
IEC10000040-1-en.vsd
IEC10000040 V1 EN
8.3.2.3 Blocking
8.3.2.4 Design
390
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
ST2
Comparator Phase 1
UN > U2> TR2
Start
START &
Trip START
Output OR
Time integrator
Logic
t2 TRIP
tReset2
Step 2
ResetTypeCrv2 TRIP
OR
en05000748.vsd
IEC05000748 V1 EN
IEC06000278-2-en.vsd
IEC06000278 V2 EN
391
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
392
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
393
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
U/f >
SYMBOL-Q V1 EN
8.4.1 Introduction
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into non-
laminated components not designed to carry flux and cause eddy currents to flow.
394
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
The eddy currents can cause excessive heating and severe damage to insulation and
adjacent parts in a relatively short time. The function has settable inverse operating
curves and independent alarm stages.
Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
emergency that includes overexcitation does occur, transformers may be damaged
unless corrective action is promptly taken. Transformer manufacturers recommend
an overexcitation protection as a part of the transformer protection system.
E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN (Equation 114)
E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN (Equation 115)
395
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
The IEC 60076 - 1 standard requires that transformers operate continuously at 10%
above rated voltage at no load, and rated frequency. At no load, the ratio of the
actual generator terminal voltage to the actual frequency should not exceed 1.1
times the ratio of transformer rated voltage to the rated frequency on a sustained
basis, see equation 116.
---- £ 1.1 × Ur
E ------
f fr
EQUATION900 V1 EN (Equation 116)
E V Hz >
£
f fr
IECEQUATION2297 V2 EN (Equation 117)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does
not know exactly what to set, then the default value for V/Hz> = 110 % for the
standard IEC 60076-1 shall be used.
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 118)
It is clear from the above formula that, for an unloaded power transformer, M = 1
for any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M ≤ V/Hz>, V/Hz> expressed in %
of Ur/fr.
396
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
As an example, at a transformer with a 15% short circuit impedance Xsc, the full
load, 0.8 power factor, 105% voltage on the load side, the actual flux level in the
transformer core, will not be significantly different from that at the 110% voltage,
no load, rated frequency, provided that the short circuit impedance X can be
equally divided between the primary and the secondary winding: Xleak = Xleak1 =
Xleak2 = Xsc / 2 = 0.075 pu.
OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage
reactance of the winding where OEXPVPH is connected) is known to the user. The
assumption taken for two-winding power transformers that Xleak = Xsc / 2 is
unfortunately most often not true. For a two-winding power transformer the
leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers
the situation is still more complex. If a user has the knowledge on the leakage
reactance, then it should applied. If a user has no idea about it, Xleak can be set to
Xc/2. OEXPVPH protection will then take the given measured voltage U, as the
induced voltage E.
If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2
must be applied. From these two input currents, current IL1L2 = IL1 - IL2 is
397
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
If three phase-to-earth voltages are available from the side where overexcitation is
connected, then OEXPVPH shall be set to measure positive sequence voltage and
current. In this case the positive sequence voltage and the positive sequence current
are used by OEXPVPH. A check is made if the positive sequence voltage is higher
than 70% of rated phase-to-earth voltage, when below this value, OEXPVPH exits
immediately, and no excitation is calculated. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.
The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 Hz
and 60 Hz respectively.
Basically there are two different delay laws available to choose between:
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match the transformer core capability well.
0.18 × k 0.18 × k
top = 2
= 2
æ M ö overexcitation
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V2 EN (Equation 119)
where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 200.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.
398
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
æ Umeasured ö
ç ÷ Umeasured frated
=è
fmeasured ø
M = ×
æ UBase ö UBase fmeasured
ç ÷
è frated ø
IECEQUATION2404 V1 EN
top
A digital, numerical relay will instead look for the lowest j (that is, j = n) where it
becomes true that:
n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN (Equation 121)
where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is
given as Ur/fr.
As long as M > V/Hz> (that is, overexcitation condition), the above sum can only
be larger with time, and if the overexcitation persists, the protected transformer will
be tripped at j = n.
Inverse delays as per figure 200, can be modified (limited) by two special definite
delay settings, namely tMax and tMin, see figure 199.
399
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
delay in s
tMax
overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>
99001067.vsd
IEC99001067 V1 EN
A definite maximum time, tMax, can be used to limit the operate time at low
degrees of overexcitation. Inverse delays longer than tMax will not be allowed. In
case the inverse delay is longer than tMax, OEXPVPH trips after tMax seconds.
A definite minimum time, tMin, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than tMin,
OEXPVPH function trips after tMin seconds. The inverse delay law is not valid for
values exceeding Mmax. The delay will be tMin, irrespective of the overexcitation
level, when values exceed Mmax (that is, M>V/Hz>).
400
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
1000
100
k = 60
k = 20
k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3
k=2
k=1
1
1 2 3 4 5 10 20 30 40
OVEREXCITATION IN % (M-Emaxcont)*100)
en01000373.vsd
IEC01000373 V1 EN
(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN (Equation 122)
401
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
delay in s
tMax
under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M
Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN
Delays between two consecutive points, for example t3 and t4, are obtained by
linear interpolation.
Should it happen that tMax be lower than, for example, delays t1, and t2, the actual
delay would be tMax. Above Mmax, the delay can only be tMin.
8.4.2.3 Cooling
If the overexcitation is so low that the valid delay is tMax, then the estimation of
the remaining time to trip is done against tMax.
The relative excitation M, shown on the local HMI and in PCM600 has a
monitored data value VPERHZ, is calculated from the expression:
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 123)
402
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
If VPERHZ value is less than setting V/Hz> (in %), the power transformer is
underexcited. If VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal
to the power transformer continuous capability. If VPERHZ is higher than V/Hz>,
the protected power transformer is overexcited. For example, if VPERHZ = 1.100,
while V/Hz> = 110 %, then the power transformer is exactly on its maximum
continuous excitation limit.
Monitored data value THERMSTA shows the thermal status of the protected
power transformer iron core. THERMSTA gives the thermal status in % of the trip
value which corresponds to 100%. THERMSTA should reach 100% at the same
time, as TMTOTRIP reaches 0 seconds. If the protected power transformer is then
for some reason not switched off, THERMSTA shall go over 100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin,
then the Thermal status will generally not reach 100% at the same time, when
tTRIP reaches 0 seconds. For example, if, at low degrees of overexcitation, the
very long delay is limited by tMax, then the OEXPVPH TRIP output signal will be
set to 1 before the Thermal status reaches 100%.
BLOCK
AlarmLevel
ALARM
t>tAlarm &
t
tAlarm
M>V/Hz>
t>tMin TRIP
t &
V/Hz> tMin
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) M IEEE law
voltage Ei (Ur / fr)
³1
M t
Tailor-made law
M>V/Hz>> tMax
Xleak
V/Hz>>
403
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and
frequency are separately checked against their respective limit values.
IEC05000329-2-en.vsd
IEC05000329 V3 EN
404
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
405
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ± 0.5% ± 10 ms
function
Maximum time delay for inverse (0.00–9000.00) s ± 0.5% ± 10 ms
function
Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms
8.5.1 Introduction
A voltage differential monitoring function is available. It compares the voltages
from two three phase sets of voltage transformers and has one sensitive alarm step
and one trip step.
406
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
is supervised for loss of individual phases whereas the U2 voltage is supervised for
loss of all three phases.
Loss of all U1or all U2 voltages will block the differential measurement. This
blocking can be switched off with setting BlkDiffAtULow = No.
VDCPTOV function can be blocked from an external condition with the binary
BLOCK input. It can for example, be activated from Fuse failure supervision
function SDDRFUF.
UDTripL1>
AND
UDTripL3>
AND
AND START
UDAlarmL1>
AND
UDAlarmL2> O tAlarm
AND
R t AND ALARM
UDAlarmL3>
AND
U1<L1
tAlarm
U1<L2 AND t U1LOW
AND
U1<L3 AND
OR
BlkDiffAtULow
U2<L1
t1
U2<L2 AND t U2LOW
AND
U2<L3
BLOCK
en06000382-2.vsd
IEC06000382 V3 EN
407
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
IEC06000528-2-en.vsd
IEC06000528 V2 EN
408
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
409
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
8.6.1 Introduction
Stator earth fault is a fault type having relatively high fault rate. The generator
systems normally have high impedance earthing, that is, earthing via a neutral point
resistor. This resistor is normally dimensioned to give an earth fault current in the
range 3 – 15 A at a solid earth-fault directly at the generator high voltage terminal.
The relatively small earth fault currents give much less thermal and mechanical
stress on the generator, compared to the short circuit case, which is between
conductors of two phases. Anyhow, the earth faults in the generator have to be
detected and the generator has to be tripped, even if longer fault time compared to
internal short circuits, can be allowed.
In normal non-faulted operation of the generating unit the neutral point voltage is
close to zero, and there is no zero sequence current flow in the generator. When a
phase-to-earth fault occurs the neutral point voltage will increase and there will be
a current flow through the neutral point resistor.
To detect an earth fault on the windings of a generating unit one may use a neutral
point overvoltage protection, a neutral point overcurrent protection, a zero
sequence overvoltage protection or a residual differential protection. These
protections are simple and have served well during many years. However, at best
these simple schemes protect only 95% of the stator winding. They leave 5% close
to the neutral end unprotected. Under unfavorable conditions the blind zone may
extend up to 20% from the neutral.
The 95% stator earth fault protection measures the fundamental frequency voltage
component in the generator star point and it operates when it exceeds the preset
value. By applying this principle approximately 95% of the stator winding can be
protected. In order to protect the last 5% of the stator winding close to the neutral
end the 3rd harmonic voltage measurement can be performed. In 100% Stator E/F
3rd harmonic protection either the 3rd harmonic voltage differential principle, the
neutral point 3rd harmonic undervoltage principle or the terminal side 3rd
harmonic overvoltage principle can be applied. However, differential principle is
strongly recommended. Combination of these two measuring principles provides
coverage for entire stator winding against earth faults.
410
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
RN Rf Transformer
uN x 1- x uT
Samples of the Samples of the
neutral voltage 1 or 100 % terminal voltage
from which the from which the
fundamental and 3rd harmonic
3rd harmonic voltage is filtered
Neutral point fundamental frequency
voltages are out
over-voltage protection 5% - 100%
filtered out over- voltage protection 10%– 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30% IEC10000202-1-en.vsd
IEC10000202 V1 EN
The 3rd harmonic voltage generated by the generator has the same phase angle in
the three phases. It has the characteristic of a zero sequence component. If the
generator is connected to the power system via a block transformer that cannot
transform zero sequence voltages between the voltage levels, the 3rd harmonic
voltage, that is U3N and U3T in fig 207, in the generator system is not influenced by
the external power system. At normal operation the generator third harmonic
voltage characteristic can be described as in figure 207.
Note that angle between U3N and U3T is typically close to 180°.
411
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
- U3 +
- DU3 +
+
U3T,L1
-
+
- U3N + U3T,L2
-
+
U3T,L3
-
U3T
U3N
en06000448.vsd
IEC06000448 V2 EN
412
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
U3N, and U3T are third harmonic phasors with real and imaginary parts. The factor
Beta must be set not to risk operation under non-faulted conditions.
The voltage U3N is measured via a voltage transformer between the generator
neutral point and earth. The voltage U3T can be measured in different ways. The
setting TVoltType defines how the protection function is fed from voltage
transformers at the high voltage side of the generator. (If U3T is lower than the set
level UT3BlkLevel, STEFPHIZ function is blocked. The choices of TVoltType are:
NoVoltage: There is no voltage measured from the generator terminal side. This
can be the case when there are only phase-to-phase voltage transformers available
at the generator terminal side. In this case the protection will operate as a simple
neutral point 3rd harmonic undervoltage protection, which must be blocked
externally during generator start-up and shut-down.
ResidualVoltage: The function is fed from an open delta connection of the phase to
earth connected voltage transformers at the generator terminal side,
U3T=(1/3)*U_Open_Delta.
AllThreePhases: The function is fed from the three phase to earth connected
voltage transformers at the generator terminal side. The 3rd harmonic voltage U3T
is calculated in the IED, U3T=(1/3)*(U3L1+U3L2+U3L3).
PhaseL1, PhaseL2, or PhaseL3: The function is fed from one phase voltage
transformer only. The 3rd harmonic zero sequence voltage is assumed to be equal
to any of the phase voltages, as the third harmonic voltage is of zero sequence type,
U3T=U3Lx.
A simplified block diagram describing the stator earth fault protection function
shown in figure 208.
413
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
Samples:
Generator 3rd
terminal TRIP
harmonic
voltage Complex UT3 Stator Earth
Fourier
filtering Fault
detection TRIP3H
giving UT3
3rd
harmonic
TRIPUN
based Start
Start
and trip
logic START3H
Samples:
Generator 3rd
neutral point STARTUN
harmonic Complex UN3
voltage Fourier
filtering
giving UN3
CB Status
Block
en06000449.vsd
IEC06000449 V2 EN
Figure 208: Simplified logic diagram for stator earth fault protection
414
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
IEC07000186 V1 EN
Figure 209: Simplified Start and Trip logical diagram of the 100% Stator earth
fault protection, 3rd harmonic based STEFPHIZ protection
There are two different cases of generator block configuration; with or without
generator circuit breaker. If there is no generator breaker the capacitive coupling to
earth is the same under all operating conditions. When there is a generator breaker,
the capacitive coupling to earth differs between the operating conditions when the
generator is running with the generator breaker open (before synchronization) and
with the circuit breaker closed. This can be shown as in figure 210.
- U3 +
- DU3 +
+ Ctr/3
U3T,L1
-
+
- U3N + Ctr/3
U3T,L2
-
+
U3T,L3 Ctr/3
-
en07000002-2.vsd
IEC07000002 V2 EN
With the circuit breaker open, the total capacitance will be smaller compared to
normal operating conditions. This means that the neutral point 3rd harmonic
voltage will be reduced compared to the normal operating condition. Therefore,
415
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
there is a possibility to reduce the sensitivity of the protection when the generator
circuit breaker is open.
With the setting CBexists change of the sensitivity is enabled. If the binary input
signal CBCLOSED is activated the set sensitivity is valid. If the generator circuit
breaker is opened the binary input CBCLOSED is deactivated and the sensitivity is
changed. This is done by changing the factor Beta which is multiplied with a set
constant FactorCBopen.
In addition to the binary outputs also some analog outputs are available from the
protection function in order to enable easier commissioning:
E3: the magnitude of the 3rd harmonic voltage induced in the stator given in
primary volts
UN3: the magnitude of the 3rd harmonic voltage measured in the neutral point of
the generator
UT3: the magnitude of the 3rd harmonic voltage measured in the terminal point of
the generator
ANGLE: the angle between the phasors UN3 and UT3 given in radians
UN: the fundamental frequency voltage measured in the neutral point of the generator
416
Technical reference manual
1MRK 502 027-UEN A Section 8
Voltage protection
417
Technical reference manual
Section 8 1MRK 502 027-UEN A
Voltage protection
418
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
f<
SYMBOL-P V1 EN
9.1.1 Introduction
Underfrequency occurs as a result of lack of generation in the network.
The operation is based on positive sequence voltage measurement and requires two
phase-phase or three phase-neutral voltages to be connected. For information about
how to connect analog inputs, refer to Application manual/IED application/
Analog inputs/Setting guidelines
419
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
magnitude, a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage IntBlockLevel the function is blocked
and no START or TRIP signal is issued.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for underfrequency protection SAPTUF can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time
delay depends on the voltage level; a high voltage level gives a longer time delay
and a low voltage level causes a short time delay. For the definite time delay, the
setting TimeDlyOperate sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings
UNom, UMin, Exponent, tMax and tMin set the time delay according to figure 212
and equation 126. The setting TimerOperation is used to decide what type of time
delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least
the user set time delay TimeDlyOperate. If the START condition, with respect to
the measured frequency ceases during this user set delay time, and is not fulfilled
again within a user defined reset time, TimeDlyReset, the START output is reset,
after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is
not sufficient for the signal to only return back to the hysteresis area.
Since the fundamental frequency in a power system is the same all over the system,
except some deviations during power oscillations, another criterion is needed to
decide, where to take actions, based on low frequency. In many applications the
voltage level is very suitable, and in most cases is load shedding preferable in areas
with low voltage. Therefore, a voltage dependent time delay has been introduced,
to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to
420
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.
UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3 and 4
1
0
1
Exponenent
TimeDlyOperate [s]
2
3
0.5 4
0
90 95 100
U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN
421
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
9.1.2.4 Blocking
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.1.2.5 Design
Block
BLOCK BLKDMAGN
OR
Comparator
U < IntBlockLevel
TimeDlyReset TRIP
100 ms
Comparator RESTORE
TimeDlyRestore
f > RestoreFreq
en05000726.vsd
IEC05000726 V1 EN
422
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
IEC06000279_2_en.vsd
IEC06000279 V2 EN
423
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
f>
SYMBOL-O V1 EN
424
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
9.2.1 Introduction
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs at sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over
frequency.
SAPTOF is used mainly for generation shedding and remedial action schemes. It is
also used as a frequency stage initiating load restoring.
The operation is based on positive sequence voltage measurement and requires two
phase-phase or three phase-neutral voltages to be connected. For information about
how to connect analog inputs, refer to Application manual/IED application/
Analog inputs/Setting guidelines
The time delay for Overfrequency protection SAPTOF (81) is a settable definite
time delay, specified by the setting TimeDlyOperate.
TRIP signal issuing requires that the overfrequency condition continues for at least
the user set time delay, TimeDlyReset. If the START condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
425
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
within a user defined reset time, TimeDlyReset, the START output is reset, after
that the defined reset time has elapsed. It is to be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.
9.2.2.3 Blocking
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.2.2.4 Design
BLOCK
BLKTRIP BLOCK
OR BLKDMAGN
Comparator
U < IntBlockLevel
Start
&
Trip
Voltage Time integrator Output
Logic
Definite Time Delay START START
Frequency Comparator
f > StartFrequency TimeDlyOperate
TRIP
TimeDlyReset
TRIP
en05000735.vsd
IEC05000735 V1 EN
426
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
IEC06000280_2_en.vsd
IEC06000280 V2 EN
427
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
df/dt >
<
SYMBOL-N V1 EN
9.3.1 Introduction
Rate-of-change frequency protection function (SAPFRC) gives an early indication
of a main disturbance in the system. SAPFRC can be used for generation shedding,
load shedding and remedial action schemes. SAPFRC can discriminate between
positive or negative change of frequency.
428
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
delay, the TRIP signal is issued. To avoid an unwanted TRIP due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of
the function is available, that is if the voltage is lower than the set blocking voltage
IntBlockLevel, the function is blocked and no START or TRIP signal is issued. If
the frequency recovers, after a frequency decrease, a restore signal is issued.
To avoid oscillations of the output START signal, a hysteresis has been included.
The RESTORE output of SAPFRC is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s
the restore functionality is disabled, and no output will be given. The restore
functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the
restore period, defined by the settings RestoreFreq and tRestore.
9.3.2.3 Blocking
429
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.3.2.4 Design
BLOCK
BLKTRIP
BLKRESET BLOCK
OR
Start
Rate-of-Change Time integrator &
Comparator
of Frequency Trip
If
Definite Time Delay Output
[StartFreqGrad<0 START START
Logic
AND
TimeDlyOperate
df/dt < StartFreqGrad]
OR
TimeDlyReset
[StartFreqGrad>0
AND
TRIP
df/dt > StartFreqGrad]
Then
START
100 ms
en05000835.vsd
IEC05000835 V1 EN
430
Technical reference manual
1MRK 502 027-UEN A Section 9
Frequency protection
IEC06000281-2-en.vsd
IEC06000281 V2 EN
431
Technical reference manual
Section 9 1MRK 502 027-UEN A
Frequency protection
432
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
10.1.1 Introduction
The protection module is recommended as a general backup protection with many
possible application areas due to its flexible measuring and setting facilities.
The built-in overcurrent protection feature has two settable current levels. Both of
them can be used either with definite time or inverse time characteristic. The
overcurrent protection steps can be made directional with selectable voltage
polarizing quantity. Additionally they can be voltage and/or current controlled/
restrained. 2nd harmonic restraining facility is available as well. At too low
polarizing voltage the overcurrent feature can be either blocked, made non
directional or ordered to use voltage memory in accordance with a parameter setting.
Additionally two overvoltage and two undervoltage steps, either with definite time
or inverse time characteristic, are available within each function.
433
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
When the generator is taken out of service, and non-rotating, there is a risk that the
generator circuit breaker flashes over or is closed by mistake.
There is a risk that the current into the generator at inadvertent energization will be
limited so that the “normal” overcurrent or underimpedance protection will not
detect the dangerous situation. The delay of these protection functions might be too
long. For big and important machines, fast protection against inadvertent
energizing should, therefore, be included in the protective scheme.
The user can select to measure one of the current quantities shown in table 240.
434
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
11 Phase2-Phase3 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L2 current phasor and
phase L3 current phasor (IL2-IL3)
12 Phase3-Phase1 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L3 current phasor and
phase L1 current phasor ( IL3-IL1)
13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which
is internally calculated as the algebraic magnitude difference between
the ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
The user can select to measure one of the voltage quantities shown in table 241:
435
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
13 MaxPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and ph-
ph voltage phasor with minimum magnitude. Phase angle will be set to
0° all the time
It is important to notice that the voltage selection from table 241 is always
applicable regardless the actual external VT connections. The three-phase VT
inputs can be connected to IED as either three phase-to-ground voltages UL1, UL2
& UL3 or three phase-to-phase voltages UL1L2, UL2L3 & UL3L1). This information
about actual VT connection is entered as a setting parameter for the pre-processing
block, which will then take automatic care about it.
The user can select one of the current quantities shown in table 242 for built-in
current restraint feature:
The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages, shall be entered as setting parameters for
every CVGAPC function.
436
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 240.
2. rated phase current of the protected object in primary amperes multiplied by
√3 (1.732 · Iphase), when the measured Current Quantity is selected from 10
to 15, as shown in table 240.
1. rated phase-to-earth voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 241.
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 241.
Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity
(see table 240) with the set pickup level. Non-directional overcurrent step will
pickup if the magnitude of the measured current quantity is bigger than this set
level. Reset ratio is settable, with default value of 0.96. However depending on
other enabled built-in features this overcurrent pickup might not cause the
overcurrent step start signal. Start signal will only come if all of the enabled built-
in features in the overcurrent step are fulfilled at the same time.
This feature will simple prevent overcurrent step start if the second-to-first
harmonic ratio in the measured current exceeds the set level.
Directional feature
The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 240) and
measured voltage phasor (see table 241). In protection terminology it means that
the General currrent and voltage protection (CVGAPC) function can be made
directional by enabling this built-in feature. In that case overcurrent protection step
will only operate if the current flow is in accordance with the set direction
437
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
(Forward, which means towards the protected object, or Reverse, which means
from the protected object). For this feature it is of the outmost importance to
understand that the measured voltage phasor (see table 241) and measured current
phasor (see table 240) will be used for directional decision. Therefore it is the sole
responsibility of the end user to select the appropriate current and voltage signals in
order to get a proper directional decision. CVGAPC function will NOT do this
automatically. It will just simply use the current and voltage phasors selected by
the end user to check for the directional criteria.
Table 243 gives an overview of the typical choices (but not the only possible ones)
for these two quantities for traditional directional relays.
Table 243: Typical current and voltage choices for directional feature
Set value for the Set value for the
parameter parameter Comment
CurrentInput VoltageInput
PosSeq PosSeq Directional positive sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power
NegSeq -NegSeq Directional negative sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power system voltage level (X/
R ratio)
3ZeroSeq -3ZeroSeq Directional zero sequence overcurrent function is
obtained. Typical setting for RCADir is from 0° to
-90° depending on the power system earthing (that
is, solidly earthed, earthed via resistor)
Phase1 Phase2-Phase3 Directional overcurrent function for the first phase is
obtained. Typical setting for RCADir is +30° or +45°
Phase2 Phase3-Phase1 Directional overcurrent function for the second phase
is obtained. Typical setting for RCADir is +30° or +45°
Phase3 Phase1-Phase2 Directional overcurrent function for the third phase is
obtained. Typical setting for RCADir is +30° or +45°
Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by
the relay operate angle, ROADir parameter setting; see figure 219).
438
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
U=-3U0
RCADir
Operate region
mta line
en05000252.vsd
IEC05000252 V1 EN
where:
RCADir is -75°
ROADir is 50°
• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined
by the I·cos(Φ) straight line and the relay operate angle, ROADir parameter
setting; see figure 219).
439
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
U=-3U0
RCADir
Operate region
mta line
en05000253.vsd
IEC05000253 V1 EN
where:
RCADir is -75°
ROADir is 50°
Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the pre-
set value. User can select one of the following three options:
It shall also be noted that the memory duration is limited in the algorithm to 100
ms. After that time the current direction will be locked to the one determined
during memory time and it will re-set only if the current fails below set pickup
level or voltage goes above set voltage memory limit.
440
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
IEC05000324 V1 EN
Figure 221: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Slope mode of operation
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
en05000323.vsd
IEC05000323 V1 EN
Figure 222: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Step mode of operation
This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will
as well affect the pickup current value for calculation of operate times for IDMT
441
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
curves (overcurrent with IDMT curve will operate faster during low voltage
conditions).
IMeasured
ea ain
ar tr
te es
ra ff *I r
pe e
O Co
es tr
I>R
IsetHigh
IsetLow
atan(RestrCoeff)
Restraint
en05000255.vsd
IEC05000255 V1 EN
This feature will simply prevent overcurrent step to start if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for
calculation of operate times for IDMT curves. This means that the IDMT curve
operate time will not be influenced by the restrain current magnitude.
When set, the start signal will start definite time delay or inverse (IDMT) time
delay in accordance with the end user setting. If the start signal has value one for
longer time than the set time delay, the overcurrent step will set its trip signal to
one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the end user setting.
Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 240) with the set pickup
level. The undercurrent step will pickup and set its start signal to one if the
magnitude of the measured current quantity is smaller than this set level. The start
signal will start definite time delay with set time delay. If the start signal has value
one for longer time than the set time delay the undercurrent step will set its trip
442
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
signal to one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the setting.
Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity
(see table 241) with the set pickup level. The overvoltage step will pickup if the
magnitude of the measured voltage quantity is bigger than this set level. Reset ratio
is settable, with default value of 0.99.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the overvoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.
Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the undervoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.
The inadvertent energizing function is realized by means of the general current and
voltage protection function (CAGVPC). CVGAPC is configured as shown in
figure 224.
443
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
CVGAPC
3IP
3UP TROC1
TROV1 S Q
TRUV1 R Q
BLKOC1
en08000288.vsd
IEC08000288 V1 EN
The setting of the general current and voltage function (typical values) is done as
shown in table 244.
Table 244: The setting of the general current and voltage function
Measured Quantity Pickup in % of generator Time delay in seconds
rating
Undervoltage U< Maximum generator < 70% 10.0 s
Phase to Phase
voltage
Overvoltage U> Maximum generator > 85% 1.0 s
Phase to Phase
voltage
Overcurrent I> Maximum generator > 50% 0.05 s
Phase current
In normal operation the overvoltage trip signal is activated and the undervotage trip
signal is deactivated. This means that the overcurrent function is blocked.
When the generator is taken out of service the generator voltage gets low. The
overvoltage trip signal will be deactivated and the undervoltage trip signal will be
444
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
activated after the set delay. At this moment the block signal to the overcurrent
function will be deactivated.
It the generator is energized at stand still conditions, that is, when the voltage is
zero, the overcurrent function will operate after the short set delay if the generator
current is larger than the set value.
When the generator is started the overvoltage trip signal will be activated the set
time delay after the moment when the voltage has reached the set value. At this
moment the blocking of the overcurrent function is activated.
The delay of the undervoltage function will prevent false operation at short circuits
in the external power grid.
The simplified internal logics, for CVGAPC function are shown in the following
figures.
IED
ADM CVGAPC function
individual currents
A/D conversion
Phasors &
samples
IEC05000169_2_en.vsd
IEC05000169 V2 EN
Figure 225: Treatment of measured currents within IED for CVGAPC function
Figure 225 shows how internal treatment of measured currents is done for
multipurpose protection function
445
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
The following currents and voltages are inputs to the multipurpose protection
function. They must all be expressed in true power system (primary) Amperes and
kilovolts.
1. Selects one current from the three-phase input system (see table 240) for
internally measured current.
2. Selects one voltage from the three-phase input system (see table 241) for
internally measured voltage.
3. Selects one current from the three-phase input system (see table 242) for
internally measured restraint current.
446
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
CURRENT
UC1
nd TRUC1
2 Harmonic
Selected current restraint
STUC2
UC2
TRUC2
2nd Harmonic
restraint
STOC1
OC1 TROC1
STOC2
OC2 TROC2
2nd Harmonic
restraint
Current restraint ³1
UDIRLOW
Directionality DIROC2
Voltage control /
restraint
STOV1
OV1 TROV1
STOV2
OV2 TROV2
STUV1
Selected voltage
UV1 TRUV1
STUV2
UV2 TRUV2
VOLTAGE
en05000170.vsd
IEC05000170 V1 EN
Figure 226: CVGAPC function main logic diagram for built-in protection elements
447
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
1. The selected currents and voltage are given to built-in protection elements.
Each protection element and step makes independent decision about status of
its START and TRIP output signals.
2. More detailed internal logic for every protection element is given in the
following four figures
3. Common START and TRIP signals from all built-in protection elements &
steps (internal OR logic) are available from multipurpose function as well.
Enable
second
harmonic Second
harmonic check
1 DEF time BLKTROC
selected DEF 1 TROC1
AND
OR
Selected current a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse
Selected voltage
Current
Restraint
Feature
Selected restrain current Imeasured > k Irestraint
en05000831.vsd
IEC05000831 V1 EN
Figure 227: Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
448
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
Operation_UC1=On
STUC1
en05000750.vsd
IEC05000750 V1 EN
Figure 228: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has
the same internal logic)
Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected
en05000751.vsd
IEC05000751 V1 EN
Figure 229: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
449
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected
en05000752.vsd
IEC05000752 V1 EN
Figure 230: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)
IEC05000372-2-en.vsd
IEC05000372 V2 EN
450
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
451
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
452
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
453
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
454
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
455
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
456
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
457
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
458
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
459
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
460
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
10.2.1 Introduction
The field winding, including the rotor winding and the non-rotating excitation
equipment, is always insulated from the metallic parts of the rotor. The insulation
resistance is high if the rotor is cooled by air or by hydrogen. The insulation
resistance is much lower if the rotor winding is cooled by water. This is true even if
the insulation is intact. A fault in the insulation of the field circuit will result in a
conducting path from the field winding to earth. This means that the fault has
caused a field earth fault.
461
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
Rotor earth fault protection can be integrated in the IED among all
other protection functions typically required for generator
protection. How this is achieved by using COMBIFLEX injection
unit RXTTE4 is described in Instruction 1MRG001910.
The protection function uses injection of an ac voltage to the generator field circuit.
The COMBIFLEX voltage injection unit RXTTE4, Part No 1MRK 002 108-AB
contains a voltage transformer with a primary winding for connection to 120 or 230
V, 50 or 60 Hz supply voltage. From the secondary winding of this internal voltage
transformer approximately 40 V AC is injected via series capacitors and resistors
into the rotor circuit. The injected voltage and current are fed to one voltage input
and one current input on the IED.
1A rated current input into REG670 must be used for this function.
The current caused by the injection is fed to a current input on the IED via injection
unit RXTTE4, as shown in figure 232.
462
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
Connection to be done by
the panel builder / field
contractor Optional
external resistor
RXTTE 4
REG 670 221 222
421
I
428
313
230 V AC
314
120 V AC
315
324 0
U 325
321
en07000185.vsd
IEC07000185 V1 EN
By using a two stage directional current measurement in the General current and
voltage protection (CVGAPC), as shown in figure 233, the earth fault current on
the DC side of the excitation is detected. The protection operates when the resistive
component of the measured injected current exceeds the pre-set operate level.
Stage one provides an alarm signal and stage two trips the generator after a short
time delay for fully developed rotor earth faults.
463
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
Operating Region
IINJECTED
UINJECTED
en06000447.vsd
IEC06000447 V1 EN
The sensitivity of the rotor earth fault protection is dependent of the rotor winding
capacitance to earth and the set pick-up current level of the General current and
voltage protection (CVGAPC). The sensitivity is shown in figure 234.
464
Technical reference manual
1MRK 502 027-UEN A Section 10
Multipurpose protection
10 0
10
ko hm
0 ,1
0 1 2 3 4 5
uF
3 0 mA 4 0 mA 50 mA 70 mA 10 0 mA 150 mA 2 0 0 mA 3 0 0 mA
en06000445.vsd
IEC06000445 V1 EN
The undervoltage stage of the General current and voltage protection (CVGAPC)
can be used to monitor the injection voltage and give alarm if the injection voltage
is absent. It shall be set to 80% of the rated value of the rated value of the injected
voltage with a time delay of about 10 s.
465
Technical reference manual
Section 10 1MRK 502 027-UEN A
Multipurpose protection
466
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
11.1.1 Introduction
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSRDIF) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
The FAIL output will be set to a logical one when the following criteria are fulfilled:
467
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of
the numerical value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than
the set operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSRDIF is enabled by setting Operation = On.
The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM
will be issued. In this case the FAIL and ALARM will remain activated 1 s after
the AND-gate resets. This prevents unwanted resetting of the blocking function
when phase current supervision element(s) operate, for example, during a fault.
IEC05000463 V1 EN
Figure 235: Simplified logic diagram for Current circuit supervision CCSRDIF
468
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
| åI phase | - | I ref |
Slope = 1
Operation
Slope = 0.8
area
I MinOp
| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 2.
IEC05000389-2-en.vsd
IEC05000389 V2 EN
469
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
11.2.1 Introduction
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage
470
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
transformer and the IED in order to avoid unwanted operations that otherwise
might occur.
The fuse failure supervision function basically has three different algorithms,
negative sequence and zero sequence based algorithms and an additional delta
voltage and delta current algorithm.
The zero sequence detection algorithm is recommended for IEDs used in directly
or low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3U0 without the presence of the residual current
3I0.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
modes makes it possible to choose different interaction possibilities between the
negative sequence and zero sequence based algorithm.
A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure,
which in practice is more associated with voltage transformer switching during
station operations.
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure 238:
The measured signals are compared with their respective set values 3U0< and
3I0>, 3U2< and 3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3U0> and the measured zero-
sequence current is below the set value 3I0<.
471
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq
Negative
sequence a 3U2
a>b
UL3 filter b
3U2>
IEC10000036-1-en.vsd
IEC10000036 V1 EN
The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local
HMI and monitoring tool in PCM600.
The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED itself in order to receive a block command from
472
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The input BLKSP is intended to be connected to the trip output at any of the
protection functions included in the IED. When activated for more than 20 ms, the
operation of the fuse failure is blocked during a fixed time of 100 ms. The aim is to
increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-out time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode selector. The additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function is not affected by the
position of the line disconnector since there will be no line currents that can cause
malfunction of the distance protection. If DISCPOS=0 it signifies that the line is
connected to the system and when the DISCPOS=1 it signifies that the line is
disconnected from the system and the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check and so on) except for the impedance
protection.
The function output BLKZ shall be used for blocking the impedance protection
function.
473
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b
AND
200 ms
DeadLineDet1Ph AND BLKZ
t OR AND
150 ms
MCBOP t
AND BLKU
60 sec
t OR OR
All UL > UsealIn<
AND
VoltZeroSeq 5 sec
VoltNegSeq OR t
AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-1-en.vsd
IEC10000033 V1 EN
Figure 239: Simplified logic diagram for main logic of Fuse failure function
474
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
A simplified diagram for the functionality is found in figure 240. The calculation of
the change is based on vector change which means that it detects both amplitude
and phase angle changes. The calculated delta quantities are compared with their
respective set values DI< and DU> and the algorithm, detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in
each phase separately. The following quantities are calculated in all three phases:
• The magnitude of the phase-ground voltage has been above UPh> for more
than 1.5 cycle
• The magnitude of DU is higher than the corresponding setting DU>
• The magnitude of DI is below the setting DI>
• The magnitude of the phase current in the same phase is higher than the setting
IPh>
• The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used
to reduce the risk of false fuse failure detection. If the current on the protected line
is low, a voltage drop in the system (not caused by fuse failure) is not by certain
followed by current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase
at the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way
only the first criterion can activate the delta function.
475
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
DUDI Detection
DUDI detection Phase 1
IL1 One cycle
delay
|DI|
a
a>b
DI< b
20 ms 1.5 cycle
a
a>b t t
UPh> b
UL1
a
a<b
b
IL1
a
a>b
IPh> b AND
OR AND
CBCLOSED AND OR
UL2
a
a<b
b
IL2
a
a>b
b AND
OR AND
AND OR
UL3
a
a<b
b
IL3
a
a>b
b AND
OR AND FuseFailDetDUDI
AND OR
OR
IEC10000034-1-en.vsd
IEC10000034 V1 EN
476
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
A simplified diagram for the functionality is found in figure 241. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated
IL3
a
a<b
b
IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b
UDLD<
intBlock
IEC10000035-1-en.vsd
IEC10000035 V1 EN
Figure 241: Simplified logic diagram for Dead Line detection part
A simplified diagram for the functionality is found in figure 242. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting
parameter Operation to On or Off.
477
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
• UZsIZs OR UNsINs; Both negative and zero sequence is activated and working
in parallel in an OR-condition
• UZsIZs AND UNsINs; Both negative and zero sequence is activated and
working in series (AND-condition for operation)
• OptimZsNs; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be
activated)
The delta function can be activated by setting the parameter OpDUDI to On. When
selected it operates in parallel with the sequence based algorithms.
If the fuse failure situation is present for more than 5 seconds and the setting
parameter SealIn is set to On it will be sealed in as long as at least one phase
voltages is below the set value USealIn<. This will keep the BLKU and BLKZ
signals activated as long as any phase voltage is below the set value USealIn<. If
all three phase voltages drop below the set value USealIn< and the setting
parameter SealIn is set to On also the output signal 3PH will be activated. The
signals 3PH, BLKU and BLKZ signals will now be active as long as any phase
voltage is below the set value USealIn<.
If SealIn is set to On fuse failure condition is stored in the non volatile memory in
the IED. At start-up (due to auxiliary power interruption or re-start due to
configuration change) the IED checks the stored value in its non volatile memory
and re-establishes the conditions present before the shut down. All phase voltages
must became above USealIn< before fuse failure is de-activated and inhibits the
block of different protection functions.
The output signal BLKU will also be active if all phase voltages have been above
the setting USealIn< for more than 60 seconds, the zero or negative sequence
voltage has been above the set value 3U0> and 3U2> for more than 5 seconds, all
phase currents are below the setting IDLD< (operate level for dead line detection)
and the circuit breaker is closed (input CBCLOSED is activated).
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode or OpDUDI. An additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
478
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function does not have to be
affected since there will be no line currents that can cause malfunction of the
distance protection.
The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions
occur:
The input BLOCK is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED. Through OR gate it can be connected to both
binary inputs and internal function outputs.
The input BLKTRIP is intended to be connected to the trip output of any of the
protection functions included in the IED and/or trip from external equipments via
binary inputs. When activated for more than 20 ms without any fuse fail detected,
the operation of the fuse failure is blocked during a fixed time of 100 ms. The aim
is to increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.
479
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b
AND
200 ms
DeadLineDet1Ph AND BLKZ
t OR AND
150 ms
MCBOP t
AND BLKU
60 sec
t OR OR
All UL > UsealIn<
AND
VoltZeroSeq 5 sec
VoltNegSeq OR t
AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-1-en.vsd
IEC10000033 V1 EN
Figure 242: Simplified logic diagram for fuse failure supervision function, Main
logic
480
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
IEC05000700-2-en.vsd
IEC05000700 V3 EN
481
Technical reference manual
Section 11 1MRK 502 027-UEN A
Secondary system supervision
482
Technical reference manual
1MRK 502 027-UEN A Section 11
Secondary system supervision
483
Technical reference manual
484
1MRK 502 027-UEN A Section 12
Control
Section 12 Control
SYMBOL-M V1 EN
12.1.1 Introduction
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time, which improves the network stability.
SESRSYN function includes a built-in voltage selection scheme for double bus and
1½ breaker or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and
can have different settings.
However this function can not be used to automatically synchronize the generator
to the network.
485
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares
them to both high and low threshold detectors. The output is given only when the
actual measured quantities match the set conditions.
The synchronizing function measures the conditions across the circuit breaker, and
also determines the angle change occurring during the closing delay of the circuit
breaker, from the measured slip frequency. The output is given only when all
measured conditions are simultaneously within their set limits. The issue of the
output is timed to give closure at the optimal time including the time for the circuit
breaker and the closing circuit.
For single circuit breaker and 1½ breaker circuit breaker arrangements, the
SESRSYN function blocks have the capability to make the necessary voltage
selection. For single circuit breaker arrangements, selection of the correct voltage
is made using auxiliary contacts of the bus disconnectors. For 1½ breaker circuit
breaker arrangements, correct voltage selection is made using auxiliary contacts of
the bus disconnectors as well as the circuit breakers.
The internal logic for each function block as well as, the input and outputs, and the
setting parameters with default setting and setting ranges is described in this
document. For application related information, please refer to the application manual.
Logic diagrams
The logic diagrams that follow illustrate the main principles of the synchronizing
function components such as Synchrocheck, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.
Synchrocheck
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.
When the function is set to OperationSC = On, the measuring will start.
The function will compare the bus and line voltage values with the set values for
UHighBusSC and UHighLineSC.
486
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
If both sides are higher than the set values, the measured values are compared with
the set values for acceptable frequency, phase angle and voltage difference:
FreqDiff, PhaseDiff and UDiff. If a compensation factor is set due to the use of
different voltages on the bus and line, the factor is deducted from the line voltage
before the comparison of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and may not exceed the set value.
Two sets of settings for frequency difference and phase angle difference are
available and used for the manual closing and autoreclose functions respectively, as
required.
The inputs BLOCK and BLKSC are available for total block of the complete
SESRSYN function and block of the Synchrocheck function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK and AUTOSYOK conditions.
Output INADVCLS, inadvertent circuit breaker closing, indicate that the circuit
breaker has been closed by some other equipment or function than SESRSYN. The
output is activated, if the voltage condition is fulfilled at the same time the phase
angle difference between bus and line is suddenly changed from being larger than
60 degrees to smaller than 5 degrees.
487
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
OperationSC = On
AND TSTAUTSY
AND
TSTSC
BLKSC AND
BLOCK OR
AUTOSYOK
AND
0-60 s
AND t
tSCA
UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1
FRDIFFA
FreqDiffA 1
PHDIFFA
PhaseDiffA 1
UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue
32 ms 100 ms
AND t INADVCLS
PhDiff > 60° AND
PhDiff < 5°
IEC07000114-3-en.vsd
IEC07000114 V3 EN
Synchronizing
When the function is set to OperationSynch = On the measuring will be performed.
The function will compare the values for the bus and line voltage with the set
values for UHighBusSynch and UHighLineSynch, which is a supervision that the
voltages are both live. If both sides are higher than the set values the measured
values are compared with the set values for acceptable frequency, rate of change of
frequency, phase angle and voltage difference FreqDiffMax, FreqDiffMin and
UDiffSynch.
Measured frequencies between the settings for the maximum and minimum
frequency will initiate the measuring and the evaluation of the angle change to
allow operation to be sent in the right moment including the set tBreaker time.
488
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
There is a phase angle release internally to block any incorrect closing pulses. At
operation the SYNOK output will be activated with a pulse tClosePulse and the
function reset. The function will also reset if the synchronizing conditions are not
fulfilled within the set tMaxSynch time. This prevents that the functions are, by
mistake, maintained in operation for a long time, waiting for conditions to be fulfilled.
The inputs BLOCK and BLKSYNCH are available for total block of the complete
function respective of the synchronizing part. TSTSYNCH will allow testing of the
function where the fulfilled conditions are connected to a separate output.
SYN1
OPERATION SYNCH
OFF
ON
TEST MODE
OFF
ON
STARTSYN SYNPROGR
AND
AND
S
BLKSYNCH
OR R
UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t
UHighLineSynch OR
FreqDiffMax
AND
TSTSYNOK
FreqDiffMin OR
tClose
FreqRateChange Pulse
AND
fBus&fLine ± 5 Hz tMax
AND
Synch
PhaseDiff < 15 deg SYNFAIL
PhaseDiff=closing angle
IEC06000636-2-en.vsd
IEC06000636 V2 EN
Energizing check
Voltage values are measured in the IED centrally and are available for evaluation
by the Energizing check function.
The function measures voltages on the busbar and the line to verify whether they
are live or dead. This is done by comparing with the set values UHighBusEnerg
and ULowBusEnerg for bus energizing and UHighLineEnerg and ULowLineEnerg
for line energizing.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
489
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
frequency difference between the bus frequency and the line frequency is measured
and shall not exceed a set value.
The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse
supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective
MENMODE, which for example, can be connected to a Binary to Integer function
block (B16I). Integers supplied shall be 1=off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input with connection of INTZERO output from Fixed Signals
(FIXDSIGN) function block will mean that the setting is done from Parameter
Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
SESRSYN function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
Voltage selection
The voltage selection module including supervision of included voltage
transformer fuses for the different arrangements is a basic part of the SESRSYN
function and determines the parameters fed to the Synchronizing, Synchrocheck
and Energizing check functions. This includes the selection of the appropriate Line
and Bus voltages and fuse supervision.
The voltage selection type to be used is set with the parameter CBConfig.
If No voltage sel. is set the default voltages used will be ULine1 and UBus1. This
is also the case when external voltage selection is provided. Fuse failure
supervision for the used inputs must also be connected.
The voltage selection function, selected voltages, and fuse conditions are the
Synchronizing, Synchrocheck and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type
contacts to supply Disconnector Open and Closed positions but, it is also possible
to use an inverter for one of the positions.
490
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The function checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1 and UB2OK-
UB2FF supervises the fuse for Bus 2. ULNOK and ULNFF supervises the fuse for
the Line voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively
be used dependent on the available signal. If a fuse-failure is detected in the
selected voltage source an output signal USELFAIL is set. This output signal is
true if the selected bus or line voltages have a fuse failure. This output as well as
the function can be blocked with the input signal BLOCK. The function logic
diagram is shown in figure 246.
B1QOPEN
B1SEL
B1QCLD AND
B2QOPEN B2SEL
1
B2QCLD AND
AND invalidSelection
bus1Voltage
busVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
AND selectedFuseOK
UB2OK AND
UB2FF OR USELFAIL
AND
ULN1OK
ULN1FF OR
BLOCK
en05000779.vsd
IEC05000779 V1 EN
Figure 246: Logic diagram for the voltage selection function of a single circuit breaker with double busbars
This voltage selection function uses the binary inputs from the disconnectors and
circuit breakers auxiliary contacts to select the right voltage for the Synchrocheck
(Synchronism and Energizing check) function. For the bus circuit breaker one side
491
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
of the circuit breaker is connected to the busbar and the other side is connected
either to line 1, line 2 or the other busbar depending on the arrangement.
The tie circuit breaker is connected either to bus 1 or line 1 on one side and the
other side is connected either to bus 2 or line 2. Four different output combinations
are possible, bus to bus, bus to line, line to bus and line to line.
The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2.
If a fuse-failure is detected in the selected voltage an output signal USELFAIL is
set. This output signal is true if the selected bus or line voltages have a fuse failure.
This output as well as the function can be blocked with the input signal BLOCK.
The function block diagram for the voltage selection of a bus circuit breaker is
shown in figure 247 and for the tie circuit breaker in figure 248
492
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
LN1QOPEN
AND
LN1SEL
LN1QCLD
B1QOPEN
LN2SEL
B1QCLD AND AND
OR
B2SEL
LN2QOPEN
LN2QCLD AND
AND invalidSelection
AND
B2QOPEN
B2QCLD AND
line1Voltage
lineVoltage
line2Voltage
bus2Voltage
UB1OK
UB1FF OR
OR
UB2OK AND
AND selectedFuseOK
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000780.vsd
IEC05000780 V1 EN
Figure 247: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement
493
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
LN1QOPEN
LN1SEL
LN1QCLD AND
B1SEL
1
B1QOPEN AND
AND
B1QCLD AND
line1Voltage
busVoltage
bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
OR invalidSelection
B2QOPEN AND
AND
B2QCLD AND
line2Voltage
lineVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
UB2OK AND selectedFuseOK
AND
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000781.vsd
IEC05000781 V1 EN
Figure 248: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.
494
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage
and the ULNOK and ULNFF inputs are related to the line voltage. Configure them
to the binary input or function outputs that indicate the status of the external fuse
failure of the busbar and line voltages. In the event of a fuse failure, the energizing
check function is blocked. The synchronizing and the synchrocheck function
requires full voltage on both sides and will be blocked automatically in the event of
fuse failures.
IEC10000046-1-en.vsd
IEC10000046 V1 EN
495
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
496
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
497
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
498
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
499
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
500
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.2.1 Introduction
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and earthing switches within a bay. Permission to operate
is given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
501
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
502
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.2.3.1 Introduction
The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay.
QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay.
IEC10000048-1-en.vsd
IEC10000048 V1 EN
503
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.2.4.1 Introduction
The signals from the local HMI or from an external local/remote switch are applied
via the function blocks LOCREM and LOCREMCTRL to the Bay control
(QCBAY) function block. A parameter in function block LOCREM is set to
choose if the switch signals are coming from the local HMI or from an external
hardware switch connected via binary inputs.
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 251, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
504
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
used. When a local HMI is used, the inputs are not used and are set to FALSE in
the configuration. The outputs from the LOCREM function block control the
output PSTO (Permitted Source To Operate) on Bay control (QCBAY).
LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD REM
BL_ CMD
LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD REM
BL_ CMD
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO 10 HMICTR 10
PSTO 11 HMICTR 11
PSTO 12 HMICTR 12
IEC10000052-1-en.vsd
IEC10000052 V1 EN
Figure 251: Configuration for the local/remote handling for a local HMI with two
bays and two screen pages
If the IED contains control functions for several bays, the local/remote position can
be different for the included bays. When the local HMI is used the position of the
local/remote switch can be different depending on which single line diagram screen
page that is presented on the local HMI. The function block Local remote control
(LOCREMCTRL) controls the presentation of the LEDs for the local/remote
position to applicable bay and screen page.
The switching of the local/remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.
505
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
IEC05000360-2-en.vsd
IEC05000360 V2 EN
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12
IEC05000361-2-en.vsd
IEC05000361 V2 EN
506
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
507
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.2.5.1 Introduction
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may
handle and operate on one three-phase device.
The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation.
The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.
Control handling
.
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.
Normal security means that only the command is evaluated and the resulting
position is not supervised. Enhanced security means that the command sequence is
supervised in three steps, the selection, command evaluation and the supervision of
position. Each step ends up with a pulsed signal to indicate that the respective step
in the command sequence is finished. If an error occurs in one of the steps in the
command sequence, the sequence is terminated and the error is mapped into the
enumerated variable "cause" attribute belonging to the pulsed response signal for
the IEC 61850 communication. The last cause L_CAUSE can be read from the
function block and used for example at commissioning.
Evaluation of position
In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the one-
phase switches, following principles will be applied:
508
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will
change position at any time due to a trip. Such situation is here called pole
discordance and is supervised by this function. In case of a pole discordance
situation, that is, the position of the one-phase switches are not equal for a time
longer than the setting tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause"
values from the switch modules Circuit breaker (SXCBR)/ Circuit switch
(SXSWI). At error the "cause" value with highest priority is shown.
Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC 61850 communication from the operator place.
The different block conditions will only affect the operation of this
function, that is, no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.
509
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
function is continuously in operation and gives the result to SCSWI. The result
from the synchrocheck function is evaluated during the close execution. If the
operator performs an override of the synchrocheck, the evaluation of the
synchrocheck state is omitted. When there is a positive confirmation from the
synchrocheck function, SCSWI will send the close signal EXE_CL to the switch
function Circuit breaker (SXCBR).
SCSWI SXCBR
EXE_CL
OR CLOSE
SYNC_OK
START_SY
SY_INPRO
SESRSYN
CLOSECB
Synchro Synchronizing
check function
IEC09000209_1_en.vsd
IEC09000209 V1 EN
Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer tSelect is used for supervising the time between the select and the
execute command signal, that is, the time the operator has to perform the command
execution after the selection of the object to operate.
510
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
IEC05000092 V1 EN
The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback
reservation granted from all bays involved in the reservation function.
select
command termination
tResResponse t1>tResResponse, then
timer 1-of-n-control in 'cause'
t1 is set
en05000093.vsd
IEC05000093 V1 EN
The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 257.
511
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
execute command
position L1 open
close
position L2 open
close
position L3 open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination *
position open
close
The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
execute command
SYNC_OK
tSynchrocheck
t1
START_SY
SY_INPRO
en05000095.vsd
IEC05000095 V1 EN
512
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC05000337-2-en.vsd
IEC05000337 V2 EN
513
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
514
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.2.6.1 Introduction
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of circuit breakers via output boards and to supervise the
switching operation and position.
The users of the Circuit breaker function (SXCBR) is other functions such as for
example, switch controller, protection functions, autorecloser function or an IEC
61850 client residing in another IED or the operator place. This switch function
executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate a switch operation to be
allowed, the function performs the execution command. In case of erroneous
conditions, the function indicates an appropriate "cause" value.
SXCBR has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.
Local/Remote switch
One binary input signal LR_SWI is included in SXCBR to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard
level. If the signal is set to FALSE it means that command from IED or higher
level is permitted. When the signal is set to TRUE all commands (for change of
position) from internal IED clients are rejected, even trip commands from
protection functions are rejected. The functionality of the local/remote switch is
described in figure 260.
Local= Operation at
RU
E switch yard level
T
en05000096.vsd
IEC05000096 V1 EN
Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autoreclosure and so on.
515
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
Substitution
The substitution part in SXCBR is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous for some reason. SXCBR will then
use the manually entered value instead of the value for positions determined by the
process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 261 explains these two timers during the execute phase.
516
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 262 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
517
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
518
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC05000338-2-en.vsd
IEC05000338 V2 EN
519
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.2.7.1 Introduction
The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or earthing switches via output
boards and to supervise the switching operation and position.
The users of the Circuit switch (SXSWI) is other functions such as for example,
switch controller, protection functions, autorecloser function, or a 61850 client
residing in another IED or the operator place. SXSWI executes commands,
evaluates block conditions and evaluates different time supervision conditions.
Only if all conditions indicate a switch operation to be allowed, SXSWI performs
the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value.
520
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.
Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If
the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in
figure 265.
Local= Operation at
RU
E switch yard level
T
en05000096.vsd
IEC05000096 V1 EN
Blocking principles
SXSWI includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autorecloser and so on.
521
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
Substitution
The substitution part in SXSWI is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because the real process value is erroneous of some reason. SXSWI will then use
the manually entered value instead of the value for positions determined by the
process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 266 explains these two timers during the execute phase.
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 267 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.
522
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
523
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
IEC05000339-2-en.vsd
IEC05000339 V2 EN
524
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
525
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.2.8.1 Introduction
The Bay reserve (QCRSV) function handles the reservation. QCRSV function
starts to operate in two ways. It starts when there is a request for reservation of the
own bay or if there is a request for reservation from another bay. It is only possible
to reserve the function if it is not currently reserved. The signal that can reserve the
own bay is the input signal RES_RQx (x=1-8) coming from switch controller
(SCWI). The signals for request from another bay are the outputs RE_RQ_B and
V_RE_RQ from function block RESIN. These signals are included in signal
EXCH_OUT from RESIN and are connected to RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay
only (TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.
If the RESERVED output is not set, the selection is made with the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus), which is
connected to switch controller SCSWI. If the bay already is reserved the command
sequence will be reset and the SCSWI will set the attribute "1-of-n-control" in the
"cause" signal.
When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-n-
control" in the "cause" signal.
526
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The reservation function can also be overridden in the own bay with the
OVERRIDE input signal, that is, reserving the own bay without waiting for the
external acknowledge.
If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The two QCRSV functions have to communicate and this is done through
the input EXCH_IN and EXCH_OUT according to figure 270. If more then one
QCRSV are used, the execution order is very important. The execution order must
be in the way that the first QCRSV has a lower number than the next one.
527
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 ³1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 ³1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B RESERVED
³1
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000088_2_en.vsd
IEC05000088 V2 EN
IEC05000340-2-en.vsd
IEC05000340 V2 EN
528
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
529
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.2.9.1 Introduction
The Reservation input (RESIN) function receives the reservation information from
other bays. The number of instances is the same as the number of involved bays
(up to 60 instances are available).
530
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
EXCH_IN INT
BIN
ACK_F_B
&
FutureUse
³1
ANY_ACK
BAY_ACK ³1
VALID_TX
&
BAY_VAL ³1
RE_RQ_B
³1
BAY_RES &
V _RE_RQ
³1
BIN
EXCH_OUT
INT
en05000089.vsd
IEC05000089 V1 EN
Figure 273 describes the principle of the data exchange between all RESIN
modules in the current bay. There is one RESIN function block per "other bay"
used in the reservation mechanism. The output signal EXCH_OUT in the last
RESIN functions are connected to the module bay reserve (QCRSV) that handles
the reservation function in the own bay. The value to the input EXCH_IN on the
first RESIN module in the chain has the integer value 5. This is provided by the use
of instance number one of the function block RESIN, where the input EXCH_IN is
set to #5, but is hidden for the user.
531
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA
en05000090.vsd
IEC05000090 V2 EN
IEC05000341-2-en.vsd
IEC05000341 V2 EN
RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN
532
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
533
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.3 Interlocking
12.3.1 Introduction
The interlocking functionality blocks the possibility to operate high-voltage
switching devices, for instance when a disconnector is under load, in order to
prevent material damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The interlocking functionality in each
IED is not dependent on any central function. For the station-wide interlocking, the
IEDs communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the
system at any given time.
After the selection and reservation of an apparatus, the function has complete data
on the status of all apparatuses in the switchyard that are affected by the selection.
Other operators cannot interfere with the reserved apparatus or the status of
switching devices that may affect it.
534
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a
bay. The interlocking logic in a module is different, depending on the bay function
and the switchyard arrangements, that is, double-breaker or 1 1/2 breaker bays have
different modules. Specific interlocking conditions and connections between
standard interlocking modules are performed with an engineering tool. Bay-level
interlocking signals can include the following kind of information:
Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI
Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module
Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI
IEC04000526 V1 EN
Bays communicate via the station bus and can convey information regarding the
following:
• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid
535
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
Station bus
Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay
..
WA1
WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2
QB9 QB9
en05000494.vsd
IEC05000494 V1 EN
When invalid data such as intermediate position, loss of a control IED, or input
board error are used as conditions for the interlocking condition in a bay, a release
for execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
536
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
The input signals EXDU_xx shall be set to true if there is no transmission error at
the transfer of information from other bays. Required signals with designations
ending in TR are intended for transfer to other bays.
12.3.3.1 Introduction
The Logical node for interlocking SCILO function is used to enable a switching
operation if the interlocking conditions permit. SCILO function itself does not
provide any interlocking functionality. The interlocking conditions are generated in
separate function blocks containing the interlocking logic.
The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals
537
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.
POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&
OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd
IEC04000525 V1 EN
IEC05000359-2-en.vsd
IEC05000359 V2 EN
538
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.3.4.1 Introduction
The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure 280.
QC
en04000504.vsd
IEC04000504 V1 EN
IEC05000347-2-en.vsd
IEC05000347 V2 EN
QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd
IEC04000546 V1 EN
539
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.3.5.1 Introduction
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure 282. The
function can be used for different busbars, which includes a bus-section circuit
breaker.
QA1
QC3 QC4
en04000516.vsd
A1A2_BS
IEC04000516 V1 EN
540
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC05000348-2-en.vsd
IEC05000348 V2 EN
541
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1
VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2
en04000542.vsd
IEC04000542 V1 EN
542
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2
VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd
IEC04000543 V1 EN
543
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
544
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.3.6.1 Introduction
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure 284.
A1A2_DC function can be used for different busbars, which includes a bus-section
disconnector.
QB
WA1 (A1) WA2 (A2)
QC1 QC2
A1A2_DC en04000492.vsd
IEC04000492 V1 EN
IEC05000349-2-en.vsd
IEC05000349 V2 EN
545
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
EXDU_BB
QBOP_EX1
VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES
EXDU_BB
QBOP_EX2
VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3
en04000544.vsd
IEC04000544 V1 EN
IEC04000545 V1 EN
546
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.3.7.1 Introduction
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 286. The
function can also be used for a single busbar arrangement with transfer busbar or
double busbar arrangement without transfer busbar.
547
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1
QA1
QC2
en04000514.vsd
IEC04000514 V1 EN
IEC05000350-2-en.vsd
IEC05000350 V2 EN
548
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC04000533 V1 EN
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000534.vsd
IEC04000534 V1 EN
549
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000535.vsd
IEC04000535 V1 EN
VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2
en04000536.vsd
IEC04000536 V1 EN
550
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd
IEC04000537 V1 EN
551
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
552
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
553
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.3.8.1 Introduction
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1
QA1 QA1
QC2 QC2
QB6 QB6
QC3 QC3
BH_LINE_A BH_LINE_B
QB9 QB9
QC1 QC2
QC9 QC9
BH_CONN
en04000513.vsd
IEC04000513 V1 EN
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.
554
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC05000352-2-en.vsd
IEC05000352 V2 EN
555
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB2OPTR
CQA1_CL QB2CLTR
CQB62_OP VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000353-2-en.vsd
IEC05000353 V2 EN
BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2
IEC05000351-2-en.vsd
IEC05000351 V2 EN
556
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC04000560 V1 EN
557
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd
IEC04000554 V1 EN
558
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000555.vsd
IEC04000555 V1 EN
CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd
IEC04000556 V1 EN
559
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd
IEC04000557 V1 EN
560
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2
VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000558.vsd
IEC04000558 V1 EN
CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd
IEC04000559 V1 EN
561
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
562
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
563
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
564
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
565
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.3.9.1 Introduction
566
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4
QA1 QA2
DB_BUS_A DB_BUS_B
QC2 QC5
QB61 QB62
QC3
QB9
DB_LINE
QC9
en04000518.vsd
IEC04000518 V1 EN
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A and DB_BUS_B are the connections from
the line to the busbars.
IEC05000354-2-en.vsd
IEC05000354 V2 EN
567
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
IEC05000356-2-en.vsd
IEC05000356 V2 EN
DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2
IEC05000355-2-en.vsd
IEC05000355 V2 EN
568
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
en04000547.vsd
IEC04000547 V1 EN
VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd
IEC04000548 V1 EN
569
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2
en04000552.vsd
IEC04000552 V1 EN
VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd
IEC04000553 V1 EN
570
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1
& en04000549.vsd
IEC04000549 V1 EN
VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd
IEC04000550 V1 EN
571
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd
IEC04000551 V1 EN
572
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
573
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
574
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.3.10.1 Introduction
The interlocking for line bay (ABC_LINE) function is used for a line connected to
a double busbar arrangement with a transfer busbar according to figure 296. The
function can also be used for a double busbar arrangement without transfer busbar
or a single busbar arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1
QA1
QC2
QB9
QC9
en04000478.vsd
IEC04000478 V1 EN
575
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
IEC05000357-2-en.vsd
IEC05000357 V2 EN
576
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2
en04000527.vsd
IEC04000527 V1 EN
577
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1EX3
en04000528.vsd
IEC04000528 V1 EN
578
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000529.vsd
IEC04000529 V1 EN
579
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1
VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
QB7_EX2
IEC04000530 V1 EN
580
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
IEC04000531 V1 EN
581
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
IEC04000532 V1 EN
582
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
583
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
584
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.3.11.1 Introduction
WA1 (A)
WA2 (B)
QB1 QB2
QC1
QA1
AB_TRAFO
QC2
QC3
QA2
QA2 and QC4 are not
QC4 used in this interlocking
QB3 QB4
en04000515.vsd
IEC04000515 V1 EN
585
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
IEC05000358-2-en.vsd
IEC05000358 V2 EN
586
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1
en04000538.vsd
IEC04000538 V1 EN
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000539.vsd
IEC04000539 V1 EN
587
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000540.vsd
IEC04000540 V1 EN
VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd
IEC04000541 V1 EN
588
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
589
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
12.3.12.1 Introduction
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals
OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is
not used.
Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS
0 (Breaker Good 0 0
intermediate)
1 (Breaker open) Good 1 0
2 (Breaker closed) Good 0 1
3 (Breaker faulty) Good 0 0
Any Invalid 0 0
Any Oscillatory 0 0
590
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC09000079_1_en.vsd
IEC09000079 V1 EN
12.4.1 Introduction
The logic rotating switch for function selection and LHMI presentation function
(SLGGIO) (or the selector switch function block) is used to get a selector switch
functionality similar to the one provided by a hardware selector switch. Hardware
selector switches are used extensively by utilities, in order to have different
functions operating on pre-set values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended purchase portfolio.
The logic selector switches eliminate all these problems.
591
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
in ascending order (if the present activated output is 3 – for example and one
operates the UP input, then the output 4 will be activated). When a signal is
received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 – for
example and one operates the DOWN input, then the output 2 will be activated).
Depending on the output settings the output signals can be steady or pulsed. In case
of steady signals, in case of UP or DOWN operation, the previously active output
will be deactivated. Also, depending on the settings one can have a time delay
between the UP or DOWN activation signal positive front and the output activation.
592
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
Control
Control Single Line Diagram Ctrl/Com
Measurements Commands Single Command
Events Selector Switch (GGIO)
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
1 2 3
../Com/Sel Sw/ ../Com/Sel Sw/
../Ctrl/Com/Sel Sw SLGGIO3
SLGGIO1 SLGGIO3
Damage ctrl 4 Damage ctrl 4
SLGGIO2
..
..
SLGGIO15
OK Cancel
4
5
The dialog window that appears
../Com/Sel Sw/ shows the present position (P:)
DmgCtrl 7
and the new position (N:), both
Damage ctrl: in clear names, given by the
user (max. 13 characters).
E
Modify the position with arrows.
The pos will not be modified (outputs
will not be activated) until you press
the E-button for O.K. IEC06000420-2-en.vsd
IEC06000420 V2 EN
Figure 301: Example 1 on handling the switch from the local HMI.
From the local HMI:
593
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
• if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions,
but only the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it
when building the Graphical Display Editor, under the "Caption". If used for the
control, the following sequence of commands will ensure:
Control
Control Single Line Diagram
Measurements Commands
Events
Disturbance records
Settings
Diagnostics
Test
Change to the "Switches" page Reset
of the SLD by left-right arrows. Authorization
Select switch by up-down Language
arrows
../Control/SLD/Switch
O I ../Control/SLD/Switch
SMBRREC control SMBRREC control
WFM Select switch. Press the
WFM
I or O key. A dialog box
Pilot setup appears.
Pilot setup
OFF OFF
Damage control E P: Disc N: Disc Fe
DAL
The pos will not be modified
(outputs will not be activated) until OK Cancel
you press the E-button for O.K.
../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DFW
IEC06000421-2-en.vsd
IEC06000421 V2 EN
Figure 302: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.
594
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
IEC05000658-2-en.vsd
IEC05000658 V2 EN
595
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
596
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.5.1 Introduction
The Selector mini switch VSGGIO function block is a multipurpose function used
for a variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line
diagram (SLD) on the local HMI.
• for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
The PSTO input is connected to the Local remote switch to have a selection of
operators place , operation from local HMI (Local) or through IEC 61850
597
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11
IEC06000508-2-en.vsd
IEC06000508 V3 EN
598
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.6.1 Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It
is especially used in the interlocking and reservation station-wide logics.
599
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
IEC07000200-2-en.vsd
IEC07000200 V2 EN
12.6.5 Settings
The function does not have any parameters available in the local HMI or PCM600.
12.7.1 Introduction
The Single point generic control 8 signals (SPC8GGIO) function block is a
collection of 8 single point commands, designed to bring in commands from
REMOTE (SCADA) to those parts of the logic configuration that do not need
extensive command receiving functionality (for example, SCSWI). In this way,
simple commands can be sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is supposed to be achieved by
600
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
other means, such as binary inputs and SPGGIO function blocks. The commands
can be pulsed or steady.
IEC07000143-2-en.vsd
IEC07000143 V2 EN
601
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
602
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.8.1 Introduction
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get
into the configuration of the commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).
There is a BLOCK input signal, which will disable the operation of the function, in
the same way the setting Operation: On/Off does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts
like an overriding, the function still receives data from the DNP3 master. Upon
deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.
603
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
IEC09000925-1-en.vsd
IEC09000925 V1 EN
604
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
605
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
606
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
607
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
608
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
609
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
610
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
611
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
612
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
613
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
614
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
615
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
616
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
617
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
618
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
12.9.1 Introduction
The IEDs can receive commands either from a substation automation system or
from the local HMI. The command function block has outputs that can be used, for
example, to control high voltage apparatuses or for other user defined functionality.
619
Technical reference manual
Section 12 1MRK 502 027-UEN A
Control
The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
IEC05000698-2-en.vsd
IEC05000698 V3 EN
620
Technical reference manual
1MRK 502 027-UEN A Section 12
Control
621
Technical reference manual
622
1MRK 502 027-UEN A Section 13
Logic
Section 13 Logic
I->O
SYMBOL-K V1 EN
13.1.1 Introduction
A function block for protection tripping is provided for each circuit breaker
involved in the tripping of the fault. It provides pulse prolongation to ensure a trip
pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.
The trip function block includes functionality for evolving faults and breaker lock-
out.
For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.
623
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
BLOCK
tTripMin TRIP
TRIN OR
AND t
Operation Mode = On
Program = 3Ph
en05000789.vsd
IEC05000789 V1 EN
SMPPTRC function for single-phase and two-phase tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- phase and two-phase tripping for those functions which do not
have their own phase selection capability, and therefore which have just a single
trip output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded SMPPTRC function. Examples of such
protection functions are the residual overcurrent protections. The expanded
SMPPTRC function has two inputs for these functions, one for impedance tripping
(for example, carrier-aided tripping commands from the scheme communication
logic), and one for earth fault tripping (for example, tripping output from a residual
overcurrent protection).
The expanded SMPPTRC function has three trip outputs TRL1, TRL2, TRL3
(besides the trip output TRIP), one per phase, for connection to one or more of the
IEDs binary outputs, as well as to other functions within the IED requiring these
signals. There are also separate output signals indicating single-phase, two-phase or
three-phase trip. These signals are important for cooperation with the autorecloser
SMBRREC function.
The expanded SMPPTRC function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- phase and two-phase tripping,
forcing all tripping to be three-phase.
The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three-
phase trip, if desired.
624
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
TRINL1
TRINL2
OR
TRINL3
1PTRZ OR
1PTREF
OR
TRIN RSTTRIP - cont.
AND
Program = 3ph
en05000517.vsd
IEC05000517 V1 EN
TRINP_3P
TRINP_A
PS_A ATRIP
OR
AND
TRINP_B
PS_B BTRIP
OR
AND
TRINP_C
PS_C CTRIP
OR
AND
OR
OR OR
-loop
-loop
OR
AND AND AND
IEC10000056-1-en.vsd
IEC10000056 V1 EN
625
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
150 ms
L1TRIP OR
t RTRIP
OR
2000 ms
t
OR
AND
150 ms
L2TRIP OR
t STRIP
OR
2000 ms
t
OR
AND
150 ms
L3TRIP OR
t TTRIP
OR
2000 ms
t
OR
AND
OR
OR AND
P3PTR
OR
-loop
en05000519.vsd
IEC05000519-WMF V1 EN
626
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
150 ms
L1TRIP - cont.
t OR RTRIP
OR
2000 ms
t
AND
150 ms
L2TRIP
t OR STRIP
OR
2000 ms
t AND
AND
150 ms
L3TRIP
t OR TTRIP
OR
2000 ms
t
AND
OR
AND
TRIP OR
OR
-loop
en05000520.vsd
IEC05000520-WMF V1 EN
627
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
BLOCK
RTRIP TRL1
AND
OR
STRIP TRL2
AND
OR
TTRIP TRL3
AND
OR
RSTTRIP
TRIP
OR
TR3P
AND AND
OR
-loop
AND 10 ms
TR1P
AND t
AND 5 ms
TR2P
AND t
OR
AND
-loop
en05000521.vsd
IEC05000521-WMF V1 EN
IEC05000707-2-en.vsd
IEC05000707 V2 EN
628
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
629
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
13.2.1 Introduction
Trip matrix logic TMAGGIO function is used to route trip signals and other logical
output signals to different output contacts on the IED.
TMAGGIO output signals and the physical outputs allows the user to adapt the
signals to the physical tripping outputs according to the specific application needs.
Internal built-in OR logic is made in accordance with the following three rules:
630
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 (TRUE) the first output signal (OUTPUT1) will get logical value 1
(TRUE).
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 (TRUE) the second output signal (OUTPUT2) will get logical value 1
(TRUE).
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 (TRUE) the third output signal (OUTPUT3) will get logical value 1 (TRUE).
PulseTime
t
&
ModeOutput1
Input 1
Output 1
Ondelay Offdelay
&
³1
³1 t t
Input 16
PulseTime
t
&
ModeOutput2
Input 17
Output 2
Ondelay Offdelay
&
³1
³1 t t
Input 32
PulseTime
t
&
ModeOutput3
Output 3
Ondelay Offdelay
&
³1
³1 t t
IEC09000612_1_en.vsd
IEC09000612 V1 EN
Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.
631
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
IEC09000830-1-en.vsd
IEC09000830 V1 EN
632
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
633
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
13.3.1 Introduction
A number of logic blocks and timers are available for the user to adapt the
configuration to the specific application needs.
• OR function block.
• PULSETIMER function block can be used, for example, for pulse extensions
or limiting of operation of outputs.
• GATE function block is used for whether or not a signal should be able to
pass from the input to the output.
• LOOPDELAY function block used to delay the output signal one execution
cycle.
• TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.
• SRMEMORY function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block's output should reset or return to the state
it was, after a power interruption. Set input has priority.
• RSMEMORY function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block's output should reset or return to the state
it was, after a power interruption. Reset input has priority.
IEC04000404_2_en.vsd
IEC04000404 V2 EN
634
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
IEC04000405_2_en.vsd
IEC04000405 V2 EN
635
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
IEC04000406_2_en.vsd
IEC04000406 V2 EN
IEC04000378_2_en.vsd
IEC04000378 V2 EN
636
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
IEC04000407-2-en.vsd
IEC04000407 V2 EN
637
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
XOR
INPUT1 OUT
INPUT2 NOUT
IEC04000409-2-en.vsd
IEC04000409 V2 EN
LOOPDELAY
INPUT OUT
IEC09000296-1-en.vsd
IEC09000296 V1 EN
638
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset.
SRMEMORY
SET OUT
RESET NOUT
IEC04000408_2_en.vsd
IEC04000408 V2 EN
639
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
RSMEMORY
SET OUT
RESET NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
IEC04000410-2-en.vsd
IEC04000410 V2 EN
640
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
IEC04000411-2-en.vsd
IEC04000411 V2 EN
641
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
642
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
IEC05000445-2-en.vsd
IEC05000445 V2 EN
643
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
13.5.1 Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
IEC07000128-2-en.vsd
IEC07000128 V2 EN
644
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
13.6.1 Introduction
Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) is used to transform a set of 16 binary (logical) signals into an integer.
B16IFCVI can receive remote values via IEC 61850 depending on the operator
position input (PSTO).
645
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
IEC09000624-1-en.vsd
IEC09000624 V1 EN
646
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
13.7.1 Introduction
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals.
647
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
IEC06000501-2-en.vsd
IEC06000501 V2 EN
648
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
13.8.1 Introduction
Integer to boolean conversion with logic node representation function (IB16FCVB)
is used to transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over IEC61850 depending on the
operator position input (PSTO).
The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in “Remote”. If PSTO is in ”Off”
or ”Local”, then no change is applied to the outputs.
649
Technical reference manual
Section 13 1MRK 502 027-UEN A
Logic
IEC09000399-1-en.vsd
IEC09000399 V1 EN
650
Technical reference manual
1MRK 502 027-UEN A Section 13
Logic
651
Technical reference manual
652
1MRK 502 027-UEN A Section 14
Monitoring
Section 14 Monitoring
14.1 Measurements
SYMBOL-RR V1 EN
SYMBOL-SS V1 EN
SYMBOL-UU V1 EN
SYMBOL-VV V1 EN
SYMBOL-TT V1 EN
SYMBOL-UU V1 EN
653
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
14.1.1 Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
654
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
processing blocks. The number of processed alternate measuring quantities
depends on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:
655
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
• Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
• Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
en05000657.vsd
IEC05000657 V1 EN
The logical value of the functional output signals changes according to figure 334.
The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.
656
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
Value 5
en05000500.vsd
(*)Set value for t: XDbRepInt
IEC05000500 V1 EN
657
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Value Reported
Y
99000529.vsd
IEC99000529 V1 EN
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the ±ΔY set limits. Even if amplitude dead-band reporting is
selected, there will be a 30 s "back-ground" cyclic reporting as well.
The last value reported, Y1 in figure 337 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).
658
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported
t
99000530.vsd
IEC99000530 V1 EN
Mode of operation
The measurement function must be connected to three-phase current and three-
phase voltage input in the configuration tool (group signals), but it is capable to
measure and calculate above mentioned quantities in nine different ways depending
on the available VT inputs connected to the IED. The end user can freely select by
a parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
1 L1, L2, L3 Used when
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3
three phase-
EQUATION1385 V1 EN
to-earth
I = ( I L1 + I L 2 + I L 3 ) / 3
voltages are
EQUATION1386 V1 EN available
2 Arone Used when
S = U L1 L 2 × I L1 - U L 2 L 3 × I L 3
* *
U = ( U L1 L 2 + U L 2 L 3 ) / 2 three two
phase-to-
(Equation 128)
I = ( I L1 + I L 3 ) / 2 phase
EQUATION1387 V1 EN
voltages are
EQUATION1388 V1 EN (Equation 129) available
3 PosSeq Used when
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq only
symmetrical
(Equation 130) three phase
EQUATION1389 V1 EN
I = I PosSeq
power shall
EQUATION1390 V1 EN (Equation 131) be measured
659
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
4 L1L2 Used when
S = U L1 L 2 × ( I L*1 - I L* 2 ) U = U L1 L 2 only UL1L2
phase-to-
(Equation 132)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN
phase
voltage is
EQUATION1392 V1 EN (Equation 133) available
5 L2L3 Used when
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3 only UL2L3
phase-to-
(Equation 134)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN
phase
voltage is
EQUATION1394 V1 EN (Equation 135) available
6 L3L1 Used when
S = U L 3 L1 × ( I L 3 - I L1 )
* *
U = U L 3 L1 only UL3L1
phase-to-
(Equation 136)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN
phase
voltage is
EQUATION1396 V1 EN (Equation 137) available
7 L1 Used when
S = 3 × U L1 × I L1
*
U = 3 × U L1 only UL1
phase-to-
(Equation 138) earth voltage
I = I L1
EQUATION1397 V1 EN
is available
EQUATION1398 V1 EN (Equation 139)
8 L2 Used when
S = 3 ×U L2 × I L2
*
U = 3 × U L2 only UL2
phase-to-
(Equation 140) earth voltage
I = IL2
EQUATION1399 V1 EN
is available
EQUATION1400 V1 EN (Equation 141)
9 L3 Used when
S = 3 ×U L3 × I L3
*
U = 3 × U L3 only UL3
phase-to-
(Equation 142)
I = I L3 earth voltage
EQUATION1401 V1 EN
is available
EQUATION1402 V1 EN (Equation 143)
* means complex conjugated value
It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating
modes that is, from 3 to 9 it calculates the three-phase power under assumption that
the power system is fully symmetrical. Once the complex apparent power is
calculated then the P, Q, S, & PF are calculated in accordance with the following
formulas:
P = Re( S )
EQUATION1403 V1 EN (Equation 144)
660
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Q = Im( S )
EQUATION1404 V1 EN (Equation 145)
S = S = P +Q
2 2
PF = cosj = P
S
EQUATION1406 V1 EN (Equation 147)
Additionally to the power factor value the two binary output signals from the
function are provided which indicates the angular relationship between current and
voltage phasors. Binary output signal ILAG is set to one when current phasor is
lagging behind voltage phasor. Binary output signal ILEAD is set to one when
current phasor is leading the voltage phasor.
661
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN (Equation 148)
where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
662
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.
Compensation facility
In order to compensate for small amplitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it
is possible to perform on site calibration of the power measurement. This is
achieved by setting the complex constant which is then internally used within the
function to multiply the calculated complex apparent power S. This constant is set
as amplitude (setting parameter PowAmpFact, default value 1.000) and angle
(setting parameter PowAngComp, default value 0.0 degrees). Default values for
these two parameters are done in such way that they do not influence internally
calculated value (complex constant has default value 1). In this way calibration, for
specific operating range (for example, around rated power) can be done at site.
However, to perform this calibration it is necessary to have an external power
meter with high accuracy class available.
Directionality
If CT earthing parameter is set as described in section "Analog inputs", active and
reactive power will be measured always towards the protected object. This is
shown in the following figure 339.
663
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Busbar
IED
P Q
Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN
Practically, it means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.
Frequency
Frequency is actually not calculated within measurement block. It is simply
obtained from the pre-processing block and then just given out from the
measurement block as an output.
664
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".
The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section "Measurement supervision".
665
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
CVMMXN
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC10000016-1-en.vsd
IEC10000016 V1 EN
CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC05000699-2-en.vsd
IEC05000699 V2 EN
VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC09000850-1-en.vsd
IEC09000850 V1 EN
666
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL
IEC05000701-2-en.vsd
IEC05000701 V2 EN
CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703-2-en.vsd
IEC05000703 V2 EN
VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL
IEC05000704-2-en.vsd
IEC05000704 V2 EN
667
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
668
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
669
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
670
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
671
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
672
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
673
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
674
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
675
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
676
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
677
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
678
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
679
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
680
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
681
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
682
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
14.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Event counter CNTGGIO -
S00946 V1 EN
14.2.2 Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.
683
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
To not risk that the flash memory is worn out due to too many writings, a
mechanism for limiting the number of writings per time period is included in the
product. This however gives as a result that it can take long time, up to several
minutes, before a new value is stored in the flash memory. And if a new
CNTGGIO value is not stored before auxiliary power interruption, it will be lost.
CNTGGIO stored values in flash memory will however not be lost at an auxiliary
power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters
at testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
14.2.3.1 Reporting
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.
14.2.3.2 Design
The function block has six inputs for increasing the counter values for each of the
six counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked and are not updated. Valid number is held.
The function block has an input RESET. At activation of this input all six counters
are set to 0.
684
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
IEC05000345-2-en.vsd
IEC05000345 V2 EN
685
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
14.3.1 Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The event function block is used for
LON and SPA communication.
Analog and double indication values are also transferred through EVENT function.
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given
a name from the Application Configuration tool. The inputs are normally used to
create single events, but are also intended for double indication events.
EVENT function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical
signals and binary input channels. The internal signals are time-tagged in the main
processing module, while the binary input channels are time-tagged directly on the
input module. The time-tagging of the events that are originated from internal
logical signals have a resolution corresponding to the execution cyclicity of
EVENT function. The time-tagging of the events that are originated from binary
input signals have a resolution of 1 ms.
686
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each
input is intended to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are
treated commonly for both the LON and SPA communication. The EventMask can
be set individually for each input channel. These settings are available:
• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect
It is possible to define which part of EVENT function generates the events. This
can be performed individually for the SPAChannelMask and LONChannelMask
respectively. For each communication type these settings are available:
• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16
For LON communication the events normally are sent to station level at change. It
is possibly also to set a time for cyclic sending of the events individually for each
input channel.
To protect the SA system from signals with a high change rate that can easily
saturate the event system or the communication subsystems behind it, a quota
limiter is implemented. If an input creates events at a rate that completely consume
the granted quota then further events from the channel will be blocked. This block
will be removed when the input calms down and the accumulated quota reach 66%
of the maximum burst quota. The maximum burst quota per input channel is 45
events per second.
687
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
IEC05000697-2-en.vsd
IEC05000697 V2 EN
688
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
689
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
690
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
14.4.1 Introduction
The Logical signal status report (BINSTATREP) function makes it possible for a
SPA master to poll signals from various other functions.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
691
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
INPUTn
OUTPUTn
t t
IEC09000732-1-en.vsd
IEC09000732 V1 EN
IEC09000730-1-en.vsd
IEC09000730 V1 EN
692
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
693
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
14.5.1 Introduction
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-
high limit. The measure value expander block (RANGE_XP) has been introduced
to enable translating the integer output signal from the measuring functions to 5
binary signals: below low-low limit, below low limit, normal, above high-high
limit or above high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose.
IEC05000346-2-en.vsd
IEC05000346 V2 EN
694
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
14.6.1 Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function block with
a, maximum of 40 analog and 96 binary signals.
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
695
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ring-
buffer. The local HMI is used to get information about the recordings. The
disturbance report files may be uploaded to PCM600 for further analysis using the
disturbance handling tool.
Figure 351 shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.
696
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
A4RADR DRPRDRE
Analog signals
Trip value rec
B1-6RBDR Disturbance
recorder
Event recorder
Indications
IEC09000337-2-en.vsd
IEC09000337 V2 EN
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile
flash memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.
Disturbance report
en05000161.vsd
IEC05000161 V1 EN
697
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
where the average recording time is 3.4 seconds. The memory limit does not affect
the rest of the disturbance report (Event list (EL), Event recorder (ER), Indications
(IND) and Trip value recorder (TVR)).
Number of recordings
100
3,4 s
80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s
6,3 s 50 Hz
40
60 Hz
Total recording time
en05000488.vsd
IEC05000488 V1 EN
Figure 353: Example of number of recordings versus the total recording time
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).
698
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Indications (IND)
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged), see section "Indications" for more detailed
information.
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.
699
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Trig point
TimeLimit
PreFaultRecT PostFaultRecT
1 2 3
en05000487.vsd
IEC05000487 V1 EN
PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the
operate time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as
any valid trigger condition, binary or analog, persists (unless limited by TimeLimit
the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording
was triggered. The limit time is used to eliminate the consequences of a trigger
that does not reset within a reasonable time interval. It limits the maximum
recording time of a recording and prevents subsequent overwriting of already
stored disturbances. Use the setting TimeLimit to set this time.
Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder
and triggering of the Disturbance report function. Out of these 40, 30 are reserved
for external analog signals from analog input modules (TRM) and line data
communication module (LDCM) via preprocessing function blocks (SMAI) and
summation block (3PHSUM). The last 10 channels may be connected to internally
calculated analog signals available as function block output signals (mA input
signals, phase differential currents, bias currents and so on).
700
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
Internal analogue signals INPUT34
INPUT35
INPUT36
...
INPUT40
IEC10000029-1-en.vsd
IEC10000029 V1 EN
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used).SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
701
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
If Operation = On, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.
Binary signals
Up to 96 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary
signal is selected to be recorded when:
The selected signals are presented in the event recorder, event list and the
disturbance recording. But they affect the whole disturbance report when they are
used as triggers. The indications are also selected from these 96 signals with local
HMI IndicationMask=Show/Hide.
Trigger signals
The trigger conditions affect the entire disturbance report, except the event list,
which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition
is fulfilled, there is no disturbance report, no indications, and so on. This implies
the importance of choosing the right signals as trigger conditions.
• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)
Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or
via station bus (IEC 61850). When the trigger is activated, the manual trigger
signal is generated. This feature is especially useful for testing. Refer to the
operator's manual for procedure.
Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a
trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to
702
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
generate a trigger from a logic zero, the selected signal will not be listed in the
indications list of the disturbance report.
Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the
average value is above the threshold level for an overvoltage or overcurrent trigger,
this trigger is indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.
This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in
the range of one cycle, 20 ms for a 50 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.
Post Retrigger
Disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be fetched.
IEC05000406-3-en.vsd
IEC05000406 V3 EN
703
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
A1RADR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
IEC05000430-3-en.vsd
IEC05000430 V3 EN
A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC05000431-3-en.vsd
IEC05000431 V3 EN
B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432-3-en.vsd
IEC05000432 V3 EN
Figure 359: B1RBDR function block, binary inputs, example for B1RBDR -
B6RBDR
704
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
705
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
706
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
707
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
708
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
709
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
710
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
711
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
712
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
713
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
714
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
715
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
14.7.1 Introduction
Continuous event-logging is useful for monitoring the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the Disturbance report
function. The list may contain up to 1000 time-tagged events stored in a ring-buffer.
716
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
The list can be configured to show oldest or newest events first with a setting on
the local HMI.
The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when the IED is configured. The same name is used in the
disturbance recorder function (DR), indications (IND)and the event recorder
function (ER).
The event list is stored and managed separate from the disturbance report
information (ER, DR, IND, TVR and FL).
14.8 Indications
14.8.1 Introduction
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know, for example binary signals
that have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (trigged).
717
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.
Green LED:
Yellow LED:
Red LED:
Indication list:
The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
The name of the binary input signal that appears in the Indication function is the user-
defined name assigned at configuration of the IED. The same name is used in
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).
718
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
14.9.1 Introduction
Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time-tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example functional analysis).
The event recorder logs all selected binary input signals connected to the
Disturbance report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
719
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder
function(ER).
The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the local HMI or PCM600.
Events can not be read from the IED if more than one user is
accessing the IED simultaneously.
14.10.1 Introduction
Information about the pre-fault and fault values for currents and voltages are vital
for the disturbance evaluation.
720
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase
angle before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the
IED.
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).
When the disturbance report function is triggered the sample for the fault
interception is searched for, by checking the non-periodic changes in the analog
input signals. The channel search order is consecutive, starting with the analog
input with the lowest number.
When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated
using the Recursive Least Squares (RLS) method. The calculation starts a few
samples after the fault sample and uses samples during 1/2 - 2 cycles depending on
the shape of the signals.
If no starting point is found in the recording, the disturbance report trig sample is
used as the start sample for the Fourier estimation. The estimation uses samples
during one cycle before the trig sample. In this case the calculated values are used
both as pre-fault and fault values.
The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function (DR).
The trip value record is stored as a part of the disturbance report information (ER,
DR, IND, TVR and fault locator) and managed in via the local HMI or PCM600.
721
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
14.11.1 Introduction
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system
behavior and related primary and secondary equipment during and after a
disturbance. Recorded information is used for different purposes in the short
perspective (for example corrective actions) and long perspective (for example
functional analysis).
The Disturbance recorder acquires sampled data from selected analog- and binary
signals connected to the Disturbance report function (maximum 40 analog and 96
binary signals). The binary signals available are the same as for the event recorder
function.
The disturbance recorder information for up to 100 disturbances are saved in the
IED and the local HMI is used to view the list of recordings.
722
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as
long as the fault condition prevails - plus a certain additional time. This is called
the post-fault time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common
for all functions within the disturbance report functionality.
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
• Saving the data for analog channels with corresponding data for binary signals
• Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
• Compression of the data, which is performed without losing any data accuracy
• Storing the compressed data in a non-volatile memory (flash memory)
The recording files comply with the Comtrade standard IEC 60255-24 and are
divided into three files; a header file (HDR), a configuration file (CFG) and a data
file (DAT).
The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions (ER,
TVR). The Disturbance handling tool use this information and present the
recording in a user-friendly way.
General:
723
Technical reference manual
Section 14 1MRK 502 027-UEN A
Monitoring
Analog:
Binary:
• Signal names
• Status of binary input signals
The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.
The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).
To be able to report 40 analog channels from the IED using IEC 60870-5-103 the
first 8 channels are placed in the public range and the next 32 are placed in the
private range. To comply the standard the first 8 must be configured according to
table 456.
724
Technical reference manual
1MRK 502 027-UEN A Section 14
Monitoring
The binary signals connected to BxRBDR are reported by polling. The function
blocks include function type and information number.
725
Technical reference manual
726
1MRK 502 027-UEN A Section 15
Metering
Section 15 Metering
S00947 V1 EN
15.1.1 Introduction
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then
read by the function. A scaled service value is available over the station bus. The
special Binary input module with enhanced pulse counting capabilities must be
ordered to achieve this functionality.
The reporting time period can be set in the range from 1 second to 60 minutes and
is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by the LON General Interrogation
command (GI) or IEC 61850.
727
Technical reference manual
Section 15 1MRK 502 027-UEN A
Metering
The reported value to station HMI over the station bus contains Identity, Scaled
Value (pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter
Quality consists of:
The transmission of the counter value by SPA can be done as a service value, that
is, the value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can
be connected to an Event function block, be time tagged, and transmitted to the
station HMI. This time corresponds to the time when the value was frozen by the
function.
The pulse counter function requires a binary input card, BIMp, that
is specially adapted to the pulse counter function.
Figure 360 shows the pulse counter function block with connections of the inputs
and outputs.
728
Technical reference manual
1MRK 502 027-UEN A Section 15
Metering
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
Each pulse counter function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC
Event function block.
The INVALID signal is a steady signal and is set if the Binary Input Module,
where the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-
up, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked.
There are two reasons why the counter is blocked:
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
IEC05000709-2-en.vsd
IEC05000709 V3 EN
729
Technical reference manual
Section 15 1MRK 502 027-UEN A
Metering
730
Technical reference manual
1MRK 502 027-UEN A Section 15
Metering
15.2.1 Introduction
Outputs from the Measurements (CVMMXN) function can be used to calculate
energy consumption. Active as well as reactive values are calculated in import and
export direction. Values can be read or generated as pulses. Maximum demand
power values are also calculated by the function.
The maximum demand values for active and reactive power are calculated for the
set time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until
reset with input signal RSTDMD or from the local HMI reset menu.
731
Technical reference manual
Section 15 1MRK 502 027-UEN A
Metering
CVMMXN ETPMMTR
P_INST P
Q_INST Q
STACC
TRUE
RSTACC
FALSE
RSTDMD
FALSE
IEC09000106.vsd
IEC09000106 V1 EN
IEC07000120-2-en.vsd
IEC07000120 V2 EN
732
Technical reference manual
1MRK 502 027-UEN A Section 15
Metering
733
Technical reference manual
Section 15 1MRK 502 027-UEN A
Metering
734
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
16.1 Overview
735
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
16.2.3.1 Introduction
IEC07000124-2-en.vsd
IEC07000124 V2 EN
736
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
SP16GGIO
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC07000125-2-en.vsd
IEC07000125 V2 EN
737
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
The function does not have any parameters available in the local HMI or PCM600.
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to
other IEC 61850 clients in the substation.
IEC05000408-2-en.vsd
IEC05000408 V2 EN
738
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
16.2.5.1 Introduction
739
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
one channel is compared with data package identity from the other channel, if the
same, the last package is discarded.
Redundancy
Supervision
Duo
Data Data
Switch A Switch B
1 2 1 2
Data
Data
AB CD IED
Configuration OEM
DUODRV PRPSTATUS
IEC09000758-2-en.vsd
IEC09000758 V2 EN
740
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
IEC09000757-1-en.vsd
IEC09000757 V1 EN
16.3.1 Introduction
An optical network can be used within the substation automation system. This
enables communication with the IED through the LON bus from the operator’s
workplace, from the control center and also from other terminals.
741
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
In this document the most common addresses for commands and events are
available. For other addresses, refer to section "Related documents".
It is assumed that the reader is familiar with LON communication protocol in general.
The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent
to the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for
example, interlocking information among the terminals without the need of a bus
master.
The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short
messages, such as measuring values, status information, and interlocking/blocking
signals. Explicit messages are used to transfer longer pieces of information, such as
events and explicit read and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for
multi-master implementations. The LON bus also has an open concept, so that the
terminals can communicate with external devices using the same standard of
network variables.
LON protocol
Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a
LonWorks network, is easily accessible on a single tool program. For more
information, refer to the operator's manual.
742
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
Vertical communication
Vertical communication describes communication between the monitoring devices
and protection and control IEDs. This communication includes sending of changed
process data to monitoring devices as events and transfer of commands, parameter
data and disturbance recorder files. This communication is implemented using
explicit messages.
Binary events
Binary events are generated in event function blocks EVENT:1 to EVENT:20 in
the 670 series IEDs. The event function blocks have predefined LON addresses.
table 475 shows the LON addresses to the first input on the event function blocks.
The addresses to the other inputs on the event function block are consecutive after
the first input. For example, input 15 on event block EVENT:17 has the address
1280 + 14 (15-1) = 1294.
For double indications only the first eight inputs 1–8 must be used. Inputs 9–16 can
be used for other type of events at the same event block.
As basic, three event function blocks EVENT:1 to EVENT:3 running with a fast
loop time (3 ms) is available in the 670 series IEDs. The remaining event function
blocks EVENT:4 to EVENT:9 runs with a loop time on 8 ms and EVENT:10 to
EVENT:20 runs with a loop time on 100 ms. The event blocks are used to send
binary signals, integers, real time values like analogue data from measuring
functions and mA input modules as well as pulse counter signals.
743
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
The first LON address in every event function block is found in table 475
Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:
• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)
The following type of signals from application functions can be connected to the
event function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the event function
744
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the event function block.
Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for
the first 8 inputs on an event function block.
Analog value
All analog values are reported cyclic, the reporting interval is taken from the
connected function if there is a limit supervised signal, otherwise it is taken from
the event function block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent
SPA-bus message is an explicit LON message, which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
only one SPA-bus message at a time to one node and waits for the reply before
sending the next message.
For commands from the operator workplace to the IED for apparatus control, That
is, the function blocks type SCSWI 1 to 32, SXCBR 1 to 18 and SXSWI 1 to 28;
the SPA addresses are according to table 476.
Horizontal communication
Network variables are used for communication between 500 series and 670 series
IEDs. The supported network variable type is SNVT_state (NV type 83).
SNVT_state is used to communicate the state of a set of 1 to 16 Boolean values.
745
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
This is an overview for configuring the network variables for 670 series IEDs.
LON
en05000718.vsd
IEC05000718 V2 EN
The network variable connections are done from the NV Connection window.
From LNT window select Connections/ NVConnections/ New.
746
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
en05000719.vsd
IEC05000719 V1 EN
There are two ways of downloading NV connections. Either the users can use the
drag-and-drop method where they can select all nodes in the device window, drag
them to the Download area in the bottom of the program window and drop them
there; or, they can perform it by selecting the traditional menu, Configuration/
Download.
747
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
en05000720.vsd
IEC05000720 V1 EN
Communication ports
The serial communication module (SLM) is used for SPA/IEC60870-5-103/DNP
and LON communication. This module is a mezzanine module, and can be placed
on the Main Processing Module (NUM). The serial communication module can
have connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre. The incoming optical fibre is connected to the
RX receiver input, and the outgoing optical fibre to the TX transmitter output.
When the fibre optic cables are laid out, pay special attention to the instructions
concerning the handling and connection of the optical fibres. The module is
identified with a number on the label on the module.
Table 476: SPA addresses for commands from the operator workplace to the IED for apparatus
control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
BL_CMD SCSWI05 1 I 5210 SPA parameters for block
command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block
command
Table continues on next page
748
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
749
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
750
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
751
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
752
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
753
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
754
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
755
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
756
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
757
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
758
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
759
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
16.4.1 Introduction
In this section the most common addresses for commands and events are available.
For other addresses, refer to section "Related documents".
It is assumed that the reader is familiar with the SPA communication protocol in
general.
760
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
The master requests slave information using request messages and sends
information to the slave in write messages. Furthermore, the master can send all
slaves in common a broadcast message containing time or other data. The inactive
state of bus transmit and receive lines is a logical "1".
SPA protocol
The tables below specify the SPA addresses for reading data from and writing data
to an IED with the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MIM3 to MIM16) are found
in table 480.
761
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
762
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are
found in table 481.
763
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module
function block are used, that is, the addresses for BI1 – BI16. For SPA addresses,
refer to section "Related documents".
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals
function block, SINGLECMD:1 to SINGLECMD:3, the address is for the first
output. The other outputs follow consecutively after the first one. For example,
output 7 on the SINGLECMD:2 function block has the 5O533 address.
764
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
Table continues on next page
765
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
Function block SPA address CMD Input SPA address CMD output
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558
Figure 372 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
IED for control of a circuit breaker.
A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:
1 are shown in table 482.
SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
^OUT2 #1.000 T
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7 AND PULSETIMER
^OUT8 INPUT1 OUT INPUT OUT To output board, OPEN
INPUT2 NOUT T
^OUT9 #1.000
INPUT3
^OUT10
INPUT4N
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
SYNCH OK
IEC05000717-2-en.vsd
IEC05000717 V2 EN
Figure 372: Application example showing a simplified logic diagram for control
of a circuit breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady
or pulsed signals. This is set in Parameter Setting Tool (PST) under: Setting /
General Settings / Control / Commands / Single Command.
Event function
Event function is intended to send time-tagged events to the station level (for
example, operator workplace) over the station bus. The events are there presented
in an event list. The events can be created from both internal logical signals and
binary input channels. All the internal signals are time tagged in the main
processing module, while the binary input channels are time tagged directly on
each I/O module. The events are produced according to the set event masks. The
event masks are treated commonly for both the LON and SPA channels. All events
according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest
event is overwritten and an overflow alarm appears.
Two special signals for event registration purposes are available in the IED,
Terminal Restarted (0E50) and Event buffer overflow (0E51).
766
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
The input parameters can be set individually from the Parameter Setting Tool
(PST) under: Setting / General Setting / Monitoring / Event Function as follows:
• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)
The Status and event codes for the Event functions are found in table 483.
These values are only applicable if the Event mask is masked ≠ OFF.
767
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC07000065-2-en.vsd
IEC07000065 V2 EN
The serial communication module (SLM) is used for SPA /IEC 60870-5-103/DNP
and LON communication. This module is a mezzanine module, and can be placed
on the Analog/Digital conversion module (ADM). The serial communication
module can have connectors for two plastic fibre cables (snap-in) or two glass fibre
cables (ST, bayonet) or a combination of plastic and glass fibre. Three different
types are available depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.
The procedure to set the transfer rate and slave number can be found in the
Installation and commissioning manual for respective IEDs.
16.4.3 Design
When communicating locally with a computer (PC) in the station, using the rear
SPA port, the only hardware needed for a station monitoring system is:
• Optical fibres
• Opto/electrical converter for the PC
• PC
When communicating remotely with a PC using the rear SPA port, the same
hardware and telephone modems are needed.
When communicating between the local HMI and a PC, the only hardware required
is a front-connection cable.
768
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
16.5.1 Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
16.5.2.1 General
769
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
The information types are supported when corresponding functions are included in
the protection and control IED.
Number of instances: 1
770
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
Number of instances: 1
Number of instances: 4
Function type for each function block instance in private range is selected with
parameter FunctionType. Default values are defined in private range 1 - 4. One for
each instance.
Information number must be selected for each output signal. Default values are 1 - 8.
Info. no. Message Supported
1 Output signal 01 Yes
2 Output signal 02 Yes
3 Output signal 03 Yes
4 Output signal 04 Yes
5 Output signal 05 Yes
6 Output signal 06 Yes
7 Output signal 07 Yes
8 Output signal 08 Yes
Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
771
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
Number of instances: 20
Function type is selected with parameter FunctionType for each function block
instance in private range. Default values are defined in private range 5 - 24. One
for each instance.
Information number is required for each input signal. Default values are defined in
range 1 - 8.
Number of instances: 1
Number of instances: 1
Fault indication block for faults in monitor direction with defined functions.
Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
78 Zone 1 Yes
79 Zone 2 Yes
80 Zone 3 Yes
81 Zone 4 Yes
82 Zone 5 Yes
76 Signal transmitted Yes
77 Signal received Yes
73 SCL, Fault location in ohm Yes
Number of instances: 1
773
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
Number of instances: 1
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
774
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no. Message Supported
148 IL1 Yes
144, 145, IL2 Yes
148
148 IL3 Yes
147 IN, Neutral current Yes
148 UL1 Yes
148 UL2 Yes
148 UL3 Yes
145, 146 UL1-UL2 Yes
147 UN, Neutral voltage Yes
146, 148 P, active power Yes
146, 148 Q, reactive power Yes
148 f, frequency Yes
Function type parameter for each block in private range. Default values are defined
in private range 25 – 27. One for each instance.
* Meas2 Yes
* Meas3 Yes
* Meas4 Yes
* Meas5 Yes
* Meas6 Yes
* Meas7 Yes
* Meas8 Yes
* Meas9 Yes
775
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
This section describes all data that is not exactly as specified in the standard.
ASDU23
776
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event
than start
The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is in 670 series, just as FAN, equal to disturbance number.
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever
he connects to the corresponding input.
777
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
Supported
Connectors
connector F-SMA No
connector BFOC/2.5 Yes
778
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
Supported
Disturbance data Yes
Private data Yes
Generic services No
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.
IEC05000689-2-en.vsd
IEC05000689 V2 EN
I103CMD
BLOCK 16-AR
FUNTYPE 17-DIFF
18-PROT
IEC05000684-2-en.vsd
IEC05000684 V2 EN
I103USRCMD
BLOCK OUTPUT1
PULSEMOD OUTPUT2
T OUTPUT3
FUNTYPE OUTPUT4
INFNO_1 OUTPUT5
INFNO_2 OUTPUT6
INFNO_3 OUTPUT7
INFNO_4 OUTPUT8
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000693-2-en.vsd
IEC05000693 V2 EN
779
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
FUNTYPE
IEC05000688-2-en.vsd
IEC05000688 V2 EN
I103USRDEF
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
FUNTYPE
INFNO_1
INFNO_2
INFNO_3
INFNO_4
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000694-2-en.vsd
IEC05000694 V2 EN
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
FUNTYPE
IEC05000692-2-en.vsd
IEC05000692 V2 EN
I103EF
BLOCK
51_EFFW
52_EFREV
FUNTYPE
IEC05000685-2-en.vsd
IEC05000685 V2 EN
780
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
I103FLTDIS
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
FUNTYPE
IEC05000686-2-en.vsd
IEC05000686 V2 EN
I103FLTSTD
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FUNTYPE
IEC05000687-2-en.vsd
IEC05000687 V2 EN
I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
FUNTYPE
IEC05000683-2-en.vsd
IEC05000683 V2 EN
781
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
FUNTYPE
IEC05000690-2-en.vsd
IEC05000690 V2 EN
I103MEASUSR
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
FUNTYPE
INFNO
IEC05000691-2-en.vsd
IEC05000691 V2 EN
782
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
783
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
784
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
785
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
786
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
787
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
788
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
789
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
IEC07000048-2-en.vsd
IEC07000048 V2 EN
790
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
791
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
792
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
IEC07000047-2-en.vsd
IEC07000047 V2 EN
793
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
794
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
16.8.1 Introduction
The IED can be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate
with other IEDs, these IEDs have a corresponding Multiple transmit function block
with 16 outputs to send the information received by the command block.
Sixteen signals can be connected and they will then be sent to the multiple
command block in the other IED. The connections are set with the LON Network
Tool (LNT).
The output signals, here OUTPUT1 to OUTPUT16, are then available for
configuration to built-in functions or via the configuration logic circuits to the
binary outputs of the IED.
MULTICMDRCV also has a supervision function, which sets the output VALID to
0 if the block does not receive data within set maximum time.
16.8.3 Design
16.8.3.1 General
The output signals can be of the types Off, Steady, or Pulse. The setting is done on
the MODE settings, common for the whole block, from PCM600.
795
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
• 0 = Off sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
• 1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values
sent from the station level.
• 2 = Pulse gives a pulse with one execution cycle duration, if a value sent from
the station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer
than the execution cycle time for the command function block.
IEC06000007-2-en.vsd
IEC06000007 V2 EN
MULTICMDSND
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC06000008-2-en.vsd
IEC06000008 V2 EN
796
Technical reference manual
1MRK 502 027-UEN A Section 16
Station communication
797
Technical reference manual
Section 16 1MRK 502 027-UEN A
Station communication
798
Technical reference manual
1MRK 502 027-UEN A Section 17
Remote communication
17.1.1 Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection,
or for transmission of only binary signals, up to 192 signals, in the other 670 series
IEDs. The binary signals are freely configurable and can, thus, be used for any
purpose, for example, communication scheme related signals, transfer trip and/or
other binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with an
LDCM (Line Data Communication Module). The LDCMs are then interfaces to a
64 kbit/s communication channel for duplex communication between the IEDs.
The IED can be equipped with up to two short range or medium range LDCM.
799
Technical reference manual
Section 17 1MRK 502 027-UEN A
Remote communication
Start Stop
Information CRC
flag flag
IEC01000134 V1 EN
The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in
the HDLC standard. The CRC is designed according to the standard CRC16
definition. The optional address field in the HDLC frame is not used instead a
separate addressing is included in the data field.
The address field is used for checking that the received message originates from
the correct equipment. There is always a risk that multiplexers occasionally mix the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC
function detects a faulty message, the message is thrown away and not used in the
evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and
eight binary signals which can be used for any purpose. The three currents are
represented as sampled values.
When the communication is used exclusively for binary signals, the full data
capacity of the communication channel is used for the binary signal purpose which
gives the capacity of 192 signals.
800
Technical reference manual
1MRK 502 027-UEN A Section 17
Remote communication
801
Technical reference manual
Section 17 1MRK 502 027-UEN A
Remote communication
802
Technical reference manual
1MRK 502 027-UEN A Section 17
Remote communication
IEC10000017-1-en.vsd
IEC10000017 V1 EN
803
Technical reference manual
804
1MRK 502 027-UEN A Section 18
IED hardware
18.1 Overview
xx04000458.ep
IEC04000458 V1 EN
Figure 380: 1/2 19” case with medium local HMI display.
805
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
xx04000459.ep
IEC04000459 V1 EN
Figure 381: 1/2 19” case with small local HMI display.
IEC05000762 V1 EN
Figure 382: 3/4 19” case with medium local HMI display.
xx05000763.eps
IEC05000763 V1 EN
Figure 383: 3/4 19” case with small local HMI display.
806
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
xx04000460.ep
IEC04000460 V1 EN
Figure 384: 1/1 19” case with medium local HMI display.
xx04000461.eps
IEC04000461 V1 EN
Figure 385: 1/1 19” case with small local HMI display.
807
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
808
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Table 533: Designations for 3/4 x 19” casing with 1 TRM slot
809
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
Table 534: Designations for 3/4 x 19” casing with 2 TRM slot
810
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Table 535: Designations for 1/1 x 19” casing with 1 TRM slot
811
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
Table 536: Designations for 1/1 x 19” casing with 2 TRM slots
18.2.1 Overview
Table 537: Basic modules
Module Description
Combined backplane module (CBM) A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM (when
included) is not connected directly to this board.
Universal backplane module (UBM) A backplane PCB that forms part of the IED
backplane with connectors for TRM (when
included), ADM etc.
Power supply module (PSM) Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.
812
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Module Description
Local Human machine interface (LHMI) The module consists of LED:s, an LCD, a push
button keyboard and an ethernet connector used
to connect a PC to the IED.
Transformer input module (TRM) Transformer module that galvanically separates
the internal circuits from the VT and CT circuits. It
has 12 analog inputs.
Analog digital conversion module (ADM) Slot mounted PCB with A/D conversion.
18.2.2.1 Introduction
The combined backplane module (CBM) carries signals between modules in an IED.
18.2.2.2 Functionality
The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The
CBM backplane and connected modules are 5V PCI-compatible.
Some pins on the Compact PCI connector are connected to the CAN bus, to be able
to communicate with CAN based modules.
If a modules self test discovers an error it informs other modules using the Internal
Fail signal IRF.
813
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.2.3 Design
Each PCI connector consists of 2 compact PCI receptacles. The euro connectors
are connected to the CAN bus and used for I/O modules and power supply.
1 2
en05000516.vsd
IEC05000516 V1 EN
Pos Description
1 CAN slots
2 CPCI slots
814
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
1 2
en05000755.vsd
IEC05000755 V1 EN
Pos Description
1 CAN slots
2 CPCI slots
en05000756.vsd
IEC05000756 V1 EN
Pos Description
1 CBM
815
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.3.1 Introduction
The Universal Backplane Module (UBM) is part of the IED backplane and is
mounted above the CBM. It connects the Transformer input module (TRM) to the
Analog digital conversion module (ADM) and the Numerical module (NUM).
18.2.3.2 Functionality
The Universal Backplane Module connects the CT and VT analog signals from the
transformer input module to the analog digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on
the front panel as well as the internal ethernet contacts are connected to the UBM
which provides the signal path to the NUM board.
18.2.3.3 Design
It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).
• for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and
one 96 pin euro connector, see figure 390
• for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and
one 96 pin euro connector, see figure 391.
The 96 pin euro connector is used to connect the NUM board to the backplane. The
48 pin connectors are used to connect the TRM and ADM.
816
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
TRM ADM
NUM
AD Data
X1 X2
X3 X4
RS485
X10 X10
Front Ethernet
LHMI connection
port
Ethernet X5
en05000489.vsd
IEC05000489 V1 EN
en05000757.vsd
IEC05000757 V1 EN
en05000758.vsd
IEC05000758 V1 EN
817
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
en05000759.vsd
IEC05000759 V1 EN
Pos Description
1 UBM
18.2.4.1 Introduction
For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM
is the compact PCI system card i.e. it controls bus mastering, clock distribution and
receives interrupts.
18.2.4.2 Functionality
818
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP
slots onto which mezzanine cards such as SLM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC/PC-MIP slots and external PCI
accesses through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a
flash file system.
The NUM is equipped with a real time clock. It uses a capacitor for power backup
of the real time clock.
No forced cooling is used on this standard module because of the low power
dissipation.
Compact
Flash Logic
PMC
connector
PC-MIP
connector
UBM
Memory Ethernet
North
bridge
Backplane
PCI-PCI-
connector
bridge
CPU
en04000473.vsd
IEC04000473 V1 EN
819
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.5.1 Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output
is available.
18.2.5.2 Design
There are two types of the power supply module. They are designed for different
DC input voltage ranges see table 539. The power supply module contains a built-
in, self-regulated DC/DC converter that provides full isolation between the
terminal and the external battery system.
Block diagram
Input connector
Power
Filter supply
Backplane connector
Supervision
99000516.vsd
IEC99000516 V1 EN
820
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.7.1 Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The
module has twelve inputs in different combinations of currents and voltage inputs.
Either protection class or metering class CT inputs are available.
18.2.7.2 Design
The transformer module has 12 input transformers. There are several versions of
the module, each with a different combination of voltage and current input
transformers.
Basic versions:
The rated values and channel type, measurement or protection, of the current inputs
are selected at order.
The TRM is connected to the ADM and NUM via the UBM.
For configuration of the input and output signals, refer to section "Signal matrix
for analog inputs SMAI".
821
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
Table 541: TRM - Energizing quantities, rated values and limits for measuring transformer
modules
Quantity Rated value Nominal range
Current Ir = 1 or 5 A (0-1.8) × Irat Ir = 1 A
(0-1.6) × Irat Ir = 5 A
822
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.8.1 Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC
slot. The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards
according to table 542. The OEM card should always be mounted on the ADM
board. The UBM connects the ADM to the transformer input module (TRM).
18.2.8.2 Design
The Analog digital conversion module input signals are voltage and current from
the transformer module. Shunts are used to adapt the current signals to the
electronic voltage level. To gain dynamic range for the current inputs, two shunts
with separate A\D channels are used for each input current. In this way a 20 bit
dynamic range is obtained with a 16 bit A\D converter.
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz
and are reported to the numerical module (NUM) with 1 kHz at 50 Hz system
frequency and 1,2 kHz at 60 Hz system frequency.
823
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
Channel 1
AD1 Channel 2
Channel 3
Channel 4
AD2
Channel 5
1.2v Channel 6
AD3 Channel 7
Channel 8
Channel 9
AD4 Channel 10
Channel 11
Channel 12
PMC
level shift
PC-MIP
2.5v
PCI to PCI
PC-MIP
en05000474.vsd
IEC05000474 V1 EN
824
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.9.1 Introduction
The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the
inputs to be used with the pulse counter function. The binary inputs are freely
programmable and can be used for the input of logical signals to any of the
functions. They can also be included in the disturbance recording and event-
recording functions. This enables extensive monitoring and evaluation of operation
of the IED and for all associated electrical circuits.
18.2.9.2 Design
The Binary input module contains 16 optical isolated binary inputs. The voltage
level of the binary input is selected at order.
For configuration of the input signals, refer to section "Signal matrix for binary
inputs SMBI".
Figure 396 shows the operating characteristics of the binary inputs of the four
voltage levels.
825
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
[V]
300
176
144
88
72
38
32
19
18
xx06000391.vsd
IEC06000391 V1 EN
Guaranteed operation
Operation uncertain
No operation
IEC99000517-ABC V1 EN
This binary input module communicates with the Numerical module (NUM) via
the CAN-bus on the backplane.
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 397 and 398.
826
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
[mA]
30 / 50
1
35 70 [ms]
en07000104-2.vsd
IEC07000104 V2 EN
Figure 397: Approximate binary input inrush current for the two standard
versions of BIM.
[mA]
30
1
3.5 7.0 [ms]
en07000105.vsd
IEC07000105 V1 EN
Figure 398: Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.
827
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
Backplane connector
Process connector
99000503.vsd
IEC99000503 V1 EN
828
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Table 544: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
18.2.10.1 Introduction
The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.
18.2.10.2 Design
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 400.
829
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section "Signal matrix for binary
outputs SMBO".
Output module
xx00000299.vsd
IEC00000299 V1 EN
830
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Relay
Relay
Relay
Relay
Relay
Process connector
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Backplane connector
Process connector
Relay Micro-
controller
Relay
Relay
CAN
Relay
Relay Memory
Relay
Relay
99000505.vsd
IEC99000505 V1 EN
831
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.11.1 Introduction
The binary input/output module is used when only a few input and output channels
are needed. The ten standard output channels are used for trip output or any
signaling purpose. The two high speed signal output channels are used for
applications where short operating time is essential. Eight optically isolated binary
inputs cater for required binary input information.
18.2.11.2 Design
The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase
the disturbance immunity during normal protection operate times. This is achieved
with a high peak inrush current while having a low steady-state current, see figure
397. Inputs are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure 396.
I/O events are time stamped locally on each module for minimum time deviance
and stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output
relays. One of the outputs has a change-over contact. The nine remaining output
contacts are connected in two groups. One group has five contacts with a common
and the other group has four contacts with a common, to be used as single-output
channels, see figure 402.
The binary I/O module also has two high speed output channels where a reed relay
is connected in parallel to the standard output relay.
832
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
For configuration of the input and output signals, refer to sections "Signal matrix
for binary inputs SMBI" and "Signal matrix for binary outputs SMBO".
IEC1MRK002801-AA11-UTAN-RAM V1 EN
Figure 402: Binary in/out module (IOM), input contacts named XA corresponds
to rear position X31, X41, and so on, and output contacts named
XB to rear position X32, X42, and so on
The binary input/output module version with MOV protected contacts can for
example be used in applications where breaking high inductive load would cause
excessive wear of the contacts.
833
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
The test voltage across open contact is lower for this version of the
binary input/output module.
xx04000069.vsd
IEC04000069 V1 EN
Table 547: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1000 V rms 800 V DC
1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load
with L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Table continues on next page
834
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Breaking capacity for AC, cos φ > 250 V/8.0 A 250 V/8.0 A
0.4
Breaking capacity for DC with L/R 48 V/1 A 48 V/1 A
< 40 ms 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Table 548: IOM with MOV - contact data (reference standard: IEC 60255-23)
Function or quantity Trip and Signal relays Fast signal relays (parallel
reed relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open 250 V rms 250 V DC
contact, 1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive
loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A
j>0.4
Breaking capacity for DC with L/ 48 V/1 A 48 V/1 A
R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
18.2.12.1 Introduction
The milli-ampere input module is used to interface transducer signals in the –20 to
+20 mA range from for example OLTC position, temperature or pressure
transducers. The module has six independent, galvanically separated channels.
18.2.12.2 Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
835
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
For configuration of the input signals, refer to section "Signal matrix for mA
inputs SMMI".
The analog inputs measure DC current in the range of +/- 20 mA. The A/D
converter has a digital filter with selectable filter frequency. All inputs are
calibrated separately The filter parameters and the calibration factors are stored in a
non-volatile memory on the module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The
module communicates, like the other I/O-modules on the serial CAN-bus.
Memory Micro-
controller
99000504.vsd
IEC99000504 V1 EN
836
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.13.1 Introduction
The serial and LON communication module (SLM) is used for SPA, IEC
60870-5-103, DNP3 and LON communication. The module has two optical
communication ports for plastic/plastic, plastic/glass or glass/glass. One port is
used for serial communication (SPA, IEC 60870-5-103 and DNP3 port or
dedicated IEC 60870-5-103 port depending on ordered SLM module) and one port
is dedicated for LON communication.
18.2.13.2 Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. Three variants of the SLM is available with different combinations
of optical fiber connectors, see figure 405. The plastic fiber connectors are of snap-
in type and the glass fiber connectors are of ST type.
837
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
IEC05000760 V1 EN
IEC05000761 V1 EN
1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103/DNP3
4 Transmitter, SPA/IEC 60870-5-103/DNP3
838
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Observe that when the SLM connectors are viewed from the rear
side of the IED, contact 4 above is in the uppermost position and
contact 1 in the lowest position.
18.2.14.1 Introduction
18.2.14.2 Functionality
839
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.14.3 Design
The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine
card on the ADM. The OEM is a 100base Fx module and available as a single
channel or double channel unit.
PCI - bus Connector
100Base-FX
EEPROM
Transmitter ST fiber optic
Ethernet Controller connectors
100Base-FX
Receiver
100Base-FX
Transmitter
ID chip ST fiber optic
Ethernet Controller
connectors
100Base-FX
EEPROM
IO - bus Connector Receiver
en04000472.vsd
IEC04000472 V1 EN
ID chip
Receiver
IO bus
LED
Ethernet cont.
25MHz oscillator
Transmitter
Receiver
LED
PCI bus
Ethernet cont. PCI to PCI
bridge
25MHz oscillator
Transmitter
en05000472.vsd
IEC05000472 V1 EN
840
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.15.1 Introduction
The line data communication module (LDCM) is used for communication between
the IEDs situated at distances <110 km or from the IED to optical to electrical
converter with G.703 interface located on a distances <3 km away. The LDCM
module sends and rereceives data, to and from another LDCM module. The IEEE/
ANSI standard format is used.
The line data communication module is used for binary signal transfer. The module
has one optical port with ST connectors see figure 409.
Alternative cards for Medium range (1310 nm single mode) and Short range (850
nm multi mode) are available.
18.2.15.2 Design
The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:
• the ADM
• the NUM
841
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
ID
ST
16.000
IO-connector
MHz
32,768
MHz
ST
en07000087.vsd
IEC07000087 V1 EN
Figure 409: The SR-LDCM layout. PCMIP type II single width format with two
PCI connectors and one I/O ST type connector
X1
C
ADN 2.5V
ID
2841
PCI9054
FPGA TQ176
DS DS
256 FBGA
3904 3904
MAX
3645
3
2
en06000393.vsd
IEC06000393 V1 EN
Figure 410: The MR-LDCM and LR-LDCM layout. PCMIP type II single width
format with two PCI connectors and one I/O FC/PC type connector
842
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
18.2.16.1 Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.
18.2.16.2 Design
The antenna with a console for mounting on a horizontal or vertical flat surface or
on an antenna mast. See figure 411
843
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
1 6
4 7
xx04000155.vsd
IEC04000155 V2 EN
where:
1 GPS antenna
2 TNC connector
3 Console, 78x150 mm
4 Mounting holes 5.5 mm
5 Tab for securing of antenna cable
6 Vertical mounting position
7 Horizontal mounting position
Always position the antenna and its console so that a continuous clear line-of-sight
visibility to all directions is obtained, preferably more than 75%. A minimum of
50% clear line-of-sight visibility is required for un-interrupted operation.
844
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
99001046.vsd
IEC99001046 V1 EN
Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a
male SMA connector in the receiver end to connect the antenna to GTM. Choose
cable type and length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to
the antenna or to the receiver. Short-circuit the end of the antenna
cable with some metal device, when first connected to the antenna.
When the antenna is connected to the cable, connect the cable to the
receiver. REx670 must be switched off when the antenna cable is
connected.
845
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.2.17.1 Introduction
The IRIG-B time synchronizing module is used for accurate time synchronizing of
the IED from a station clock.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
18.2.17.2 Design
The IRIG-B module have two inputs. One input is for the IRIG-B that can handle
both a pulse-width modulated signal (also called unmodulated) and an amplitude
modulated signal (also called sine wave modulated). The other is an optical input
type ST for PPS to synchronize the time between several protections.
32 MHz FPGA
connector
PCI-con
OPTO_INPUT
ST-
PCI-bus
Registers
PCI-Controller
PCI-con
4 mm barrier
IRIG- IRIG_INPUT
connector
Amplitude
ID-chip Decoder
BNC-
modulator
Capture1 Isolated
ZXING
receiver
Zero-cross
Capture2 detector
MPPS
IO-con
PPS
TSU Isolated
DC/DC
CMPPS 5 to +- 12V
en06000303.vsd
IEC06000303 V1 EN
846
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
A1
DC//DC
ST
C
Y2
C
C
A1
C
O
T
3
2
O
en06000304.vsd
IEC06000304 V1 EN
Figure 414: IRIG-B PC-MIP board with top left ST connector for PPS 820 nm
multimode fibre optic signal input and lower left BNC connector for
IRIG-B signal input
847
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.3 Dimensions
A
D
B C
xx08000164.vsd
IEC08000164 V1 EN
848
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
K
F
G
H J
xx08000166.vsd
IEC08000166 V1 EN
Figure 416: Case without rear cover with 19” rack mounting kit
849
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
A
D
B
C
xx08000163.vsd
IEC08000163 V1 EN
850
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
K
F
G
J
H
xx08000165.vsd
IEC08000165 V1 EN
Figure 418: Case with rear cover and 19” rack mounting kit
xx05000503.vsd
IEC05000503 V1 EN
851
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
A C
B
E
D
xx08000162.vsd
IEC08000162 V1 EN
852
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
xx06000182.vsd
IEC06000182 V1 EN
Figure 421: A 1/2 x 19” size 670 series IED side-by-side with RHGS6.
G
D
B
E
F
C
xx05000505.vsd
IEC05000505 V1 EN
853
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
B
E
C
D
en04000471.vsd
IEC04000471 V1 EN
854
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
[1.48
[6.97]
[4.02] [18.31]
[0.33] [0.79] [7.68]
[18.98]
Dimension
mm [inches] xx06000232.eps
IEC06000232 V1 EN
[7.50]
en06000234.eps
[inches]
IEC06000234 V1 EN
Figure 425: Dimension drawing of a three phase high impedance resistor unit
57 [2.24]
Dimension
mm [inches]
xx06000233.vsd
IEC06000233 V1 EN
855
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.4.1.1 Overview
• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
• 1/4 x 19” (RHGS6 6U)
Only a single case can be mounted in each cut-out on the cubicle panel, for class
IP54 protection.
856
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
xx08000161.vsd
IEC08000161 V1 EN
857
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
18.4.2.1 Overview
All IED sizes can be mounted in a standard 19” cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening
screws for the angles.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19”
or 3/4 x 19” either to the left or right side of the cubicle.
Please note that the separately ordered rack mounting kit for side-by-
side mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19”.
858
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
1a
1b
xx08000160.vsd
IEC08000160 V1 EN
18.4.3.1 Overview
All case sizes, 1/2 x 19”, 3/4 x 19” and 1/1 x 19”, can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.
859
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
When mounting the side plates, be sure to use screws that follows
the recommended dimensions. Using screws with other dimensions
than the original may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication
modules with fiber connection; Serial SPA/IEC 60870-5-103,
DNP3 and LON communication module (SLM), Optical Ethernet
module (OEM) and Line data communication module (LDCM).
3
4
2
6
xx04000453.vs d
DOCUMENT127716-IMG2265 V1 EN
860
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
4 Mounting bar 2 -
5 Screw 6 M5x8
6 Side plate 2 -
The IED can be equipped with a rear protection cover, which is recommended to
use with this type of mounting. See figure 430.
To reach the rear side of the IED, a free space of 80 mmis required on the unhinged
side.
3
1
80 mm 2
en06000135.vsd
IEC06000135 V1 EN
Figure 430: How to reach the connectors on the rear side of the IED.
18.4.4.1 Overview
IED case sizes, 1/2 x 19” or 3/4 x 19” and RHGS cases, can be mounted side-by-
side up to a maximum size of 19”. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19” rack panel mounting kit must be used. The
mounting kit has to be ordered separately.
861
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.
2
1
xx04000456.vsd
IEC04000456 V1 EN
An 1/2 x 19” or 3/4 x 19” size IED can be mounted with a RHGS (6 or 12
depending on IED size) case. The RHGS case can be used for mounting a test
switch of type RTXP 24. It also has enough space for a terminal base of RX 2 type
for mounting of, for example, a DC-switch or two trip IEDs.
862
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
1 2
1 2 1 2
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
xx06000180.vsd
IEC06000180 V1 EN
Figure 432: IED in the 670 series (1/2 x 19”) mounted with a RHGS6 case
containing a test switch module equipped with only a test switch
and a RX2 terminal base
18.4.5.1 Overview
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.
863
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
1 2
xx06000181.vsd
IEC06000181 V1 EN
Figure 433: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x
19” IED).
18.5.1 Enclosure
Table 556: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)
864
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
Table 557: Water and dust protection level according to IEC 60529
865
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
866
Technical reference manual
1MRK 502 027-UEN A Section 18
IED hardware
867
Technical reference manual
Section 18 1MRK 502 027-UEN A
IED hardware
868
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
This chapter describes the hardware equipment used for sensitive rotor earth fault
protection and 100% stator earth fault protection by injection. The descriptions
includes diagrams from different elevations indicating the location of connection
terminals and modules as well as dimensions and drilling plan.
19.1 Overview
The purpose of the injection unit REX060 is to protect the stator and the rotor of a
generator against an earth fault by injection of a voltage signal to the neutral point
of the generator or VT open delta secondary (100 % stator earth fault protection)
and to the exciter point of the field circuit (rotor earth fault protection).
For local operation, the REX060 unit is provided with a control panel on the front.
869
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
IEC11000053-1-en.vsd
IEC11000053 V1 EN
870
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
Table 569: HMI keys on the front of the injection unit REX060
Key Function
The Injection switch enables injection at rotor and stator 2
s after switching on. A LED indicates that the injection
switch is set to enable injection. The injection switch can
be padlocked in off position in order to cut-off both
injection signals.
X1 X2
IEC11000019-2-en.vsd
IEC11000019 V1 EN
871
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
IEC11000037-1-en.vsd
IEC11000037 V1 EN
REX061 shall be mounted close to the generator in order to limit the exposure of
the field circuit. Alternatively it can be located in the excitation cubicle.
X1
IEC11000038-1-en.vsd
IEC11000038 V1 EN
872
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
IEC11000039-1-en.vsd
IEC11000039 V1 EN
REX062 shall be mounted close to the IED. It is recommended that REX060 and
REX062 are mounted in the same cubicle as the IED.
IED and
Injection Power
connectors Top view connector Back view Front view
5
Stator Injection
Power Supply
Rotor Injection
18 18
X62 X82
1 1
5 5
Power
Stator
Rotor
BackPlane
IEC11000018-1-en.vsd
IEC11000018 V1 EN
873
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
19.2.1 Introduction
The injection unit REX060 is used to inject voltage and current signals to the
generator or motor stator and rotor circuits. REX060 generates two square wave
signals with different frequencies for injection into the stator and rotor circuits
respectively. The response from the injected voltage and currents are then
measured by the REX060 unit and amplified to a level suitable for the analog
voltage inputs of IED.
19.2.2 Design
REX060 consists of a standard enclosure (6U, 1/2 x 19"). In this enclosure, the
modules for stator (SIM) and/or rotor (RIM) earth fault protection are installed.
The stator injection transformer is also installed inside the enclosure.
On the front of the enclosure there is a backlit LCD, control buttons and a key switch.
In figure 440 below the content of display is shown for a REX060 with one SIM
and one RIM module. Row 1 contains mains frequency information. Row 2-3
contains stator information and row 4-5 rotor. Column 1 (empty) gives status,
column 2 and 3 are informative and column 4 contains variables, settable by the
keypad.
Column
Row 1 2 3 4
1 System f [Hz] : 50
2 STATOR f [Hz] : 087
When the injection unit REX060 is energized, the ABB logotype is shown
followed by current REX060 revision status. When the start up sequence is
completed, the main menu (normal display content) is shown. The duration of the
start up sequence is a few seconds.
874
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
LCD backlight is active during a period of 30 seconds after pressing any button.
Backlight activation by pressing a button will not cause any normal button action.
Column 1 is a status column (empty in the above picture), where the following
symbols are displayed when applicable:
Overvoltage reset
Stator module (SIM) and rotor module (RIM) injection outputs are protected
against voltages exceeding maximum operating range (10% of rated VT/DT for the
stator and 75 % of max voltage during gain dependent time for the rotor) by a relay
blocking the injection circuit. This blocking is controlled by measuring the sense
voltage, and remains blocked by stored status in non-volatile memory. Injection
block is released by performing the following sequence:
1. Power off the REX060
2. Simultaneous press the C and key buttons
3. Power on the REX060 and wait until status indication Over-voltage is
removed from display
Both rotor and stator have two levels of protection, injection circuit interruption
controlled by the voltage sense input and a fuse for over-current protection. The
voltage controlled interruption, overvoltage, will normally occur prior to
interruption by fuse and the reset sequence is described above. A blown fuse
875
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
requires module disassembling to replace the fuse (F 4 A 250 V for stator and F
160 mA 250 V for rotor). However, if this occurs it is recommended to identify the
reason for the over-current and take necessary actions to reduce the current before
restarting the unit. The problem must be outside the injection unit since this unit
cannot provide enough energy to blow the fuse.
Saturation
When the voltage or current amplifiers in an injection module saturates due to high
voltage level, it is indicated with a warning symbol in the status column in the
REX060 display . Besides this a binary out for the specific module is set active to
indicate to the IED that the signal may not be reliable due to saturation and could
cause incorrect measurements.
Binary in
The injection can be blocked by application in the IED. For this purpose, two
binary inputs to the REX060 exist:
• BLOCK on X61 terminal 1, 2 or 3: Prohibits injection on the injection unit
inserted in X62
• BLOCK on X81 terminal 1, 2 or 3: Prohibits injection on the injection unit
inserted in X82
The used terminal is depending on actual binary voltage, pin 1 for 220 V, 2 for 110
V, 3 for 48 V and 4 for return (common).
Binary out
Power status
• X11 terminal 3:
876
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
19.3.1 Introduction
REX061 isolates the injection circuit from the rotor exciter voltage.
The REX061 coupling capacitor unit grounding point and grounding brush of the
rotor shaft should be properly interconnected.
19.3.2 Design
Measure points are added to the capacitor box that enables the measuring of rotor
voltages without any connection to a hazardous voltage, by the use of protective
impedance. This enables the usage of standard oscilloscope or handheld DVM.
877
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
REX061
Coupling Capacitor unit
Measuring point +
Ground (measuring)
Rotor+
Injection
Ground (injection)
Rotor-
Measuring point-
PE
IEC11000040-3-en.vsd
IEC11000040 V1 EN
19.4.1 Introduction
REX062 is typically used when injection is done via a grounding transformer.
19.4.2 Design
REX062 for stator protection is used when either injection via a grounding
transformer (i.e. not via a VT) is used or when maximum voltage posed on
injection equipment by the generator is bigger than 120V.
878
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
REX062
Shunt Resistor unit
Injection A External A
Fuse
Injection B External B
I sense A
PE
I sense B
IEC11000041-2-en.vsd
IEC11000041 V1 EN
A blown REX062 fuse requires a module disassembling to replace the fuse (F 6.3
A 250 V). However, if this occurs it is recommended to identify the reason for the
over-current and do needed actions to reduce the current.
REX060 REG670
Injection unit X11:4 +
EL
Power Supply Module X11:5 -
Exciter REX061
Coupling Capacitor unit Ready; X11:1 BI
source
Common; X11:2 RL+
X1:1; Rotor + Fail; X11:3 (BI)
Rotor X82:1; InjA Rotor Module (RIM)
Injection; X1:9 X82:3; InjA Block 220V; X81:1
Block 110V; X81:2 BO
Ground; X1:10 X82:4; InjB
Block 48V; X81:3
X1:7; Rotor - X82:5; InjB Block Common; X81:4 RL-
X82:2; InjShB
PE
I Out; X81:10
X81:16; IA sense
A
X81:12; UA sense
U Out; X81:9
B
X81:13; UB sense
Blocked; X81:5 BI
Saturation; X81:6 BI
REX062 Common; X81:7 RL+
Shunt Resistor unit Stator Module (SIM)
X62:1; InjExtA
X1:2; Injection A External A; X1:9 X62:3; InjA Block 220V; X61:1
Block 110V; X61:2 BO
R X1:4; Injection B External B; X1:10 X62:4; InjB
Stator Block 48V; X61:3
I sense A; X1:6 X62:5; InjB Block Common; X61:4 RL-
Distribution X62:2; InjExtB
Transformer I sense B; X1:8
PE X61:14; IA sense I Out; X61:10
A
Blocked; X61:5 BI
Saturation; X61:6 BI
PE Common; X61:7 RL+ PE
IEC11000017-1-en.vsd
IEC11000017 V1 EN
879
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
19.5.1 Hardware
Table 571: REX060 Technical data
Specifications Values
Case size 6U, 1/2 19”; 223.7 x 245 x 267 mm (W x D x H)
Weight 8.0 kg
Firmware 1p0r00, loaded in the HMI & Logic module
Specifications Values
Case size 218 x 150 x 243 mm (W x D x H)
Weight 4.8 kg
Assembling 6 x 5 mm screws (3 at bottom and 3 at top)
880
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
881
Technical reference manual
Section 19 1MRK 502 027-UEN A
Injection equipment hardware
882
Technical reference manual
1MRK 502 027-UEN A Section 19
Injection equipment hardware
883
Technical reference manual
884
1MRK 502 027-UEN A Section 20
Labels
Section 20 Labels
2
3
6
6 5
7
xx06000574.ep
IEC06000574 V1 EN
885
Technical reference manual
Section 20 1MRK 502 027-UEN A
Labels
IEC06000577-CUSTOMER-SPECIFIC V1 EN
IEC06000576-POS-NO V1 EN
886
Technical reference manual
1MRK 502 027-UEN A Section 20
Labels
4
en06000573.ep
IEC06000573 V1 EN
1 Warning label
2 Caution label
3 Class 1 laser product label
IEC06000575 V1 EN
4 Warning label
887
Technical reference manual
Section 20 1MRK 502 027-UEN A
Labels
IEC11000226 V1 EN
1d
IEC11000233-1-en.vsd
IEC11000233 V1 EN
IEC11000234-1-en.vsd
IEC11000234 V1 EN
888
Technical reference manual
1MRK 502 027-UEN A Section 20
Labels
IEC11000227 V1 EN
1 Warning label
2 Caution label
3 ESD label
4 Warning label
IEC11000229 V1 EN
889
Technical reference manual
Section 20 1MRK 502 027-UEN A
Labels
IEC11000228 V1 EN
1 Warning label
2 Caution label
3 ESD label
4 Warning label
IEC11000231 V1 EN
890
Technical reference manual
1MRK 502 027-UEN A Section 20
Labels
IEC11000230 V1 EN
1 Warning label
2 Caution label
3 ESD label
4 Warning label
891
Technical reference manual
892
1MRK 502 027-UEN A Section 21
Connection diagrams
This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.
893
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002801-AC 1 V1 EN
894
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
895
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
896
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
897
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
898
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
899
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
900
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
901
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
902
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
903
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
904
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
905
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
906
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
907
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
908
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002501-BA 1 V1 EN
909
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002501-BA 2 V1 EN
910
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002501-BA 3 V1 EN
911
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002501-BA 4 V1 EN
912
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002501-BA 5 V1 EN
913
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002551-BA 1 V1 EN
914
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002551-BA 2 V1 EN
915
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002556-BA 1 V1 EN
916
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002556-BA 2 V1 EN
917
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-AA V1 EN
918
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-BA 1 V1 EN
919
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-BA 2 V1 EN
920
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-BA 3 V1 EN
921
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-BA 4 V1 EN
922
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-BA 5 V1 EN
923
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-CA 1 V1 EN
924
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-CA 2 V1 EN
925
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-CA 3 V1 EN
926
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-CA 4 V1 EN
927
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-DA 1 V1 EN
928
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-DA 2 V1 EN
929
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-DA 3 V1 EN
930
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-DA 4 V1 EN
931
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-DA 5 V1 EN
932
Technical reference manual
1MRK 502 027-UEN A Section 21
Connection diagrams
1MRK002504-DA 6 V1 EN
933
Technical reference manual
Section 21 1MRK 502 027-UEN A
Connection diagrams
1MRK002504-DA 7 V1 EN
934
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
22.1 Application
Stage 3
Time
Stage 2 Stage 2
Fault point
position
en05000130.vsd
IEC05000130 V1 EN
935
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
Time
Fault point
position
en05000131.vsd
IEC05000131 V1 EN
The inverse time characteristic makes it possible to minimize the fault clearance
time and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of
following factors, in a simple case with two protections in series:
936
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A1 B1
Feeder
I> I>
Time axis
en05000132.vsd
IEC05000132 V1 EN
where:
t=0 is The fault occurs
t=t1 is Protection B1 trips
In most applications it is required that the times shall reset as fast as possible when
the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type
of delayed reset time of the overcurrent function. This can be the case in the
following applications:
937
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
• If there is a risk of intermittent faults. If the current IED, close to the faults,
starts and resets there is a risk of unselective trip from other protections in the
system.
• Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for
other protection functions. It can often be valuable to have a reset delay to
assure the release function.
If current in any phase exceeds the set start current value (here internal signal
startValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the
current level used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is
reached or until the current drops below the reset value (start value minus the
hysteresis) and the reset time has elapsed.
For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are
chosen.
The general expression for inverse time curves is according to equation 149.
æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN (Equation 149)
where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.
938
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can
be seen:
ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN (Equation 150)
where:
top is the operating time of the protection
The time elapsed to the moment of trip is reached when the integral fulfils
according to equation 151, in addition to the constant time delay:
t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø
EQUATION1191 V1 EN (Equation 151)
For the numerical protection the sum below must fulfil the equation for trip.
n æ æ i( j ) ö p ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN (Equation 152)
where:
j=1 is the first protection execution cycle when a fault has been
detected, that is, when
i
>1
in >
EQUATION1193 V1 EN
For inverse time operation, the inverse time characteristic is selectable. Both the
IEC and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 448.
939
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
Operate
time
tMin
Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN
In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current start value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN (Equation 154)
where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current
940
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN (Equation 155)
where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current
If the curve type programmable is chosen, the user can make a tailor made inverse
time curve according to the general equation 156.
æ ö
ç A
÷
t[ s ] = ç + B÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1196 V1 EN (Equation 156)
Also the reset time of the delayed function can be controlled. There is the
possibility to choose between three different reset time-lags.
• Instantaneous Reset
• IEC Reset
• ANSI Reset.
If instantaneous reset is chosen the timer will be reset directly when the current
drops below the set start current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the
current drops below the set start current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after
fault clearance (when the current drops below the start current level minus the
hysteresis). The timer will reset according to equation 157.
941
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
2
çç ÷ -1 ÷
è è in > ø ø
EQUATION1197 V2 EN (Equation 157)
where:
The set value tr is the reset time in case of zero current after fault clearance.
For the definite time delay characteristics the possible reset time settings are
instantaneous and IEC constant time reset.
For ANSI inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time.
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous and IEC set constant time reset).
For the programmable inverse time delay characteristics all three types of reset
time characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time. If the current dependent type is used settings pr, tr
and cr must be given, see equation 158:
æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
pr
çç ÷ - cr ÷
è è in > ø ø
EQUATION1198 V2 EN (Equation 158)
For RI and RD inverse time delay characteristics the possible delay time settings
are instantaneous and IEC constant time reset.
942
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
943
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10
ms
IEC Normal Inverse A=0.14, P=0.02 IEC 60255-3, class 5 +
40 ms
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-999) in steps of 0.01 IEC 60255, class 5 + 40
Operate characteristic: A=(0.005-200.000) in steps ms
of 0.001
æ A ö B=(0.00-20.00) in steps of
t = ç P + B÷ × k 0.01
ç (I - C ) ÷ C=(0.1-10.0) in steps of 0.1
è ø
P=(0.005-3.000) in steps of
EQUATION1370-SMALL V1 EN
0.001
Reset characteristic: TR=(0.005-100.000) in steps
of 0.001
TR CR=(0.1-10.0) in steps of 0.1
t = ×k PR=(0.005-3.000) in steps of
(I PR
- CR ) 0.001
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 +
40 ms
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
944
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
U> = Uset
U = Umeasured
945
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
946
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
U> = Uset
U = Umeasured
947
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070750 V2 EN
948
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070751 V2 EN
949
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070752 V2 EN
950
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070753 V2 EN
951
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070817 V2 EN
952
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070818 V2 EN
953
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070819 V2 EN
954
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070820 V2 EN
955
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070821 V2 EN
956
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070822 V2 EN
957
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070823 V2 EN
958
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070824 V2 EN
959
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070825 V2 EN
960
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
A070826 V2 EN
961
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
A070827 V2 EN
962
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN
963
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN
964
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN
965
Technical reference manual
Section 22 1MRK 502 027-UEN A
Inverse time characteristics
GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN
966
Technical reference manual
1MRK 502 027-UEN A Section 22
Inverse time characteristics
GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN
967
Technical reference manual
968
1MRK 502 027-UEN A Section 23
Glossary
Section 23 Glossary
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
969
Technical reference manual
Section 23 1MRK 502 027-UEN A
Glossary
970
Technical reference manual
1MRK 502 027-UEN A Section 23
Glossary
971
Technical reference manual
Section 23 1MRK 502 027-UEN A
Glossary
972
Technical reference manual
1MRK 502 027-UEN A Section 23
Glossary
973
Technical reference manual
Section 23 1MRK 502 027-UEN A
Glossary
974
Technical reference manual
1MRK 502 027-UEN A Section 23
Glossary
975
Technical reference manual
Section 23 1MRK 502 027-UEN A
Glossary
976
Technical reference manual
977
Contact us
www.abb.com/substationautomation