Sie sind auf Seite 1von 26

MONI-RMC

Trace-heating remote module for control

MoniTrace remote modules for control (RMC) provide multiple relay outputs for switching heating cable circuits controlled by the MoniTrace 200N trace-heating control and monitoring unit. RMC units are modular and may be configured with 2 to 32 relay outputs. A single MoniTrace 200N unit communicates with up to 10 RMC via a single, twisted pair RS-485 cable to provide distributed control of up to 128 heating cable circuits. Control and monitoring The MoniTrace 200N controls and monitors multiple trace-heating circuits based on pipe or ambient temperatures. These temperatures are collected locally by MoniTrace remote monitoring modules (RMM) connected on the same RS-485 network. Based on temperature inputs

from RMM, the MoniTrace 200N determines which heating cable circuits are to be energised and sends this information to RMC, which then turn on or off the heating cable power contactors. Because temperature inputs and control outputs are located near equipment to be sensed or controlled, wiring costs are reduced significantly. Alarm inputs Each RMC unit includes two inputs to monitor the status of circuit breakers or power contactors. For example, one input may be used for a common circuit breaker trip alarm, providing an alarm indication at the MoniTrace 200N panel if any circuits fail due to earth fault or overcurrent events. Alarms may be reported remotely through an alarm relay

in the MoniTrace 200N or through an RS-485 connection to a host computer supporting the Modbus protocol. Up to 16 MONI-RMC-2DI 2 channel digital input moduls can be added if required. Configurations The MoniTrace RMC are modular, electronic devices that mount on a DIN 35 rail. RMC units must be installed in panels or enclosures suitable for the area classification and environment. For each RMC installation, purchase one MONIRMC-BASE kit, which includes the network processor, digital inputs, and end terminator; one MONI-RMC-PS24 24-Vdc power supply; and up to 16 MONI-RMC2RO 2-channel relay output modules, as required.

ss dre Ad

x1

0 x1

MONI-RMC-BASE unit with four MONI-RMC-2RO modules removed

DOC-389 Rev.7 07/03

129

Control and Monitoring

O N T xD R xD C R C

I/O

R U N I/O E R R

2 31 075

MONI-RMC

Dimensions (in mm)


90 38 12 75 12

V
ON TxD RxD

IN

24V 0V
CRC

D1 D2

100
24V D1 D2 L

IO/RN IO/ER

0V
Address x 1

x 10

750-312

MONI-RMC-PS24 power supply (optionel)

RS-485 network connection module

Overall width = 125 mm + 12 mm per relay module (+ 90 mm for optional power supply) General Area of use Ambient operating temperature range Ambient storage temperature range Relative humidity Protection Supply voltage Supply current Relay outputs Quantity per RMC 1 to 16 two-channel modules (2 to 32 relay outputs) 128 Mechanical, normally open, non-floating 250 Vac, 30 Vdc AC/DC 2 A 60W/500VA (resistive) 4 kV 1 x 106 at 0.35 A to 0.2 x 106 at 2 A 0.08 mm22.5 mm2 (cage clamp) Ordinary areas 0C to 55C 40C to 70C Max. 95%, noncondensing IP2X per IEC 529 24 Vdc <2A

Control and Monitoring

Total relay outputs via RMCs Type Voltage, maximum Current, maximum Maximum power Isolation Life (operations) Connection terminals Supply module Voltage Current Connection terminals Digital inputs Quantity per RMC Type Current consumption Isolation Connection terminals

230 VAC/DC 10A Cage clamp type for cables from 0.08 mm2 to 2.5 mm2

Up to 16 two-channel modules (2 to 32 digital inputs) Solid-state, 24 Vdc source 5mA 500 V 0.08 mm22.5 mm2 (cage clamp)

DOC-389 Rev.7 07/03

130

456

78

9 01

456

78

9 01

23

35
750-400 750-612 750-512 750-600

23

Supply module Network processor Digital inputs Relay module End termination

MONI-RMC

Connection details
Contactor 1 Digital input 1 Contactor 2

Contactor coil

24 Vdc
ON TxD RxD CRC
24V 0V

V IN

15 16

D1 D2

OUTPUT, 24Vdc 2 A

SYSTEM

Power supply (typical)


Address x 1

IO/RN IO/ER

24V 24V

D1 D2

0V

0V

L N

RS-485 Contactor coil supply

Communication to MONI-200N-E Type Connection terminals Cable Length Quantity Address Mounting method Electromagnetic compatibility Immunity Emissions Ordering details & Weight MoniTrace remote module for control (RMC) Base unit* Two-channel relay output module** Two-channel digital input module*** 24-Vdc power supply MONI-RMC-BASE MONI-RMC-2RO MONI-RMC-2DI MONI-RMC-PS24 309735-000 920455-000 062367-000 972049-000 0.5 kg 55 g 50 g 0.7 kg Complies with EN 50 082-2 (heavy industrial) Complies with EN 50 081-2 (heavy industrial) Part description PN Weight RS-485 0.08 mm22.5 mm2 (cage clamp) 1 shielded twisted pair 1200 m max. Up to 10 RMC may be connected to one 200N Switch-selectable on RMC, 10 addresses, 5059 Clips to DIN 35 rail

* Purchase one base for each RMC installation. Includes network processor, two digital inputs, end termination, and RS-485 connection module with ribbon cable. ** Purchase one module for each set of two relay outputs required. Minimum of one module (2 relay outputs), maximum of 16 (32 relay outputs) per RMC base. *** Purchase one module for each set of two digital inputs required. Minimum of one module (2 digital inputs), maximum of 16 (32 digital inputs) per RMC base. Additional module for each pair of digital inputs required. One MONI-RMC-2DI module is included in each RMC-BASE unit

DOC-389 Rev.7 07/03

131

Control and Monitoring

456

78

9 01

456

78

9 01

x 10

WAGO I/0 750-312

AC INPUT

23
23

750-400 750-612 750-512

750-512 750-600

MONI-PT100-NH

Temperature sensor for ordinary area

2 wire Pt100 sensor with glass fiber reinforced polycarbonate junction box for installation in ordinary area.

Area of use sensor marking Sensor Type

Ordinary area NA

Pt100-Sensor (2 wire) DIN IEC 751, Class B Tip: stainless steel Extension cable: silicone 50C to +180C 50C to +180C (+215C maximum 1000 hrs), max. exposure temp. tip: +400C 2m Extension cable ca 4.6 mm, tip ca 6.0 mm Extension cable: 5 mm, the measuring tip should not be bended

Control and Monitoring

Material Temperature measuring range Temperature range extension cable Length Diameter Minimum bending radius Enclosure Ingress protection Material Dimensions Cable gland Operating temperature Lid sealing gasket material Cover screws Mounting

IP66 Glass fiber reinforced polycarbonate (gray) With = 65 mm Height = 65 mm Depth = 57 mm M20 (polyamide) suitable for cable diameters ranging from 10 mm to 14 mm 30C to +80C CFC-free Polyurethane Plastic For pipe mount use JB-SB-26 wall mount Surface mount via molded holes at 50 x 50 mm

Installation and connection Terminals Terminal sizing Ordering details Part Description PN
DOC-389 Rev.7 07/03

3 front entry cage clamp terminals (terminals 2 and 3 are bridged) Terminals suitable for cables from 0.15 mm2 to 2.5 mm2

MONI-PT100-NH 140910-000

132

MONI-PT100-EXE

Temperature sensor for hazardous areas (Zone 1)

3 wire Pt100 sensor connected to a black glass fiber reinforced polyester junction box (IP65) with 4 front entry cage clamp terminals. M20 EEx e cable gland preinstalled.

Area of use Sensor marking

Hazardous environment Zone I EEx e II T6 BASEEFA02ATEX0059X

Sensor Type Material: Temperature measuring range Maximum exposure temp. tip Length Diameter Minimum bending radius Enclosure Material Ingress protection Dimensions Cable entry Operating temperature Sealing gasket material Cover screws Mounting Glass fiber reinforced polyester (black) IP65 With= 80 mm Height = 75 mm Depth = 55 mm M20 ( EEx e) suitable for cable diameters ranging from 10 mm to 14 mm 50C to +55C tongue and groove system with silicone seal Stainless steel M4 threaded For pipe mount use JB-SB-26 wall mount Surface mount via molded holes at 68 x 45 mm

extension cable and tip both stainless steel (MI). 100C to +500C +585C 2m ca 3 mm, tip ca 5 mm extension cable: 20 mm, the measuring tip should not be bended

Installation and connection Terminals Terminal sizing Ordering details Part Description PN
DOC-389 Rev.7 07/03

4 front entry cage clamp terminals suitable for cables from 0.5 mm2 to 2.5 mm2

MONI-PT100-EXE 967094-000 133

Control and Monitoring

Pt100, 3 wire. DIN IEC 751, Class B.

MONI-PT100-4/20MA

3 Wire PT100 sensor with 4 to 20 mA transmitter for hazardous area (Zone 1)

PT100 sensor connected to a 4-20 mA transmitter built in a black glass fiber reinforced polyester junction box with M20 cable gland (Blue).

Area of use Sensor marking

Hazardous environment Zone I EEx ia IIC T6 CESI 02 ATEX 115 BASEEFA03ATEX0201U PTB 01 ATEX 1061 U

Sensor

Control and Monitoring

Type Material Temperature measuring range: Maximum exposure temp. tip Length Diameter Minimum bending radius Enclosure Ingress protection Material Dimensions Cable gland Operating temperature Sealing gasket material Cover screws For pipe mounting use Installation and connection: Terminals Terminal sizing
Ordering details

Pt100, 3 wire. DIN IEC 751, Class B. extension cable and tip both stainless steel (MI). 50C to +250C (transmitter) +585C 2 m. ca 3 mm, tip ca 5 mm extension cable: 20 mm, the measuring tip should not be bended

IP65 Glass fiber reinforced polyester (black) With= 80 mm Heigth = 75 mm Depth = 55 mm M20, blue ( EEx e) suitable for cable diameters ranging from 10 mm to 14 mm 20C to +55C tongue and groove system with silicone seal Stainless steel M4 threaded JB-SB-26

2 screw terminals suitable for cables from 0.5 mm2 to 1.5 mm2

Part Description PN
DOC-389 Rev.7 07/03

MONI-PT100-4/20MA 704058-000

134

MONI-PT100-EXE-SENSOR

Temperature sensor without junction box for hazardous area (Zone 1)

Certified EEx e II cable gland preinstalled on the sensor lead (M16, Brass, inclusive sealing washer, locknut and earth tag

Area of use Sensor marking

Hazardous environment Zone I EEx e II BASEEFA03ATEX0201U

Sensor Type Material Temperature measuring range Maximum exposure temperature Length Diameter Minimum bending radius Installation and connection M16 (Brass) compression gland pre-installed on the sensor. Sealing washer, earth tag and locknut included. Maximum operating temperature (for the gland) Ordering details Part Description PN MONI-PT100-EXE-SENSOR 529022-000 50C to +55C Pt100, 3 wire. DIN IEC 751, Class B. Stainless steel (MI). 100C to +500C +585C 2m extension cable ca 3 mm, tip ca 5 mm extension cable: 20 mm, the measuring tip should not be bended

DOC-389 Rev.7 07/03

135

Control and Monitoring

DET-3000

Hand held cable fault locator

The DET-3000 is a cable fault locater working on the principles of Time Domain Reflectrometry or TDR. The DET-3000 is a hand held cable fault locater from the latest generation. The DET-3000 gives genuine universal performance for short and long range applications on all types of metallic cable including many types of heating cable. Innovative features result in a versatile, cable-test instrument that is remarkably easy to use. Large back-lit display, tactile push buttons and ability to operate in temperatures as low as 20C allow use in a vast range of locations and conditions. The DET-3000 operates accurate to 20 cm on shortest range. Automatic cable attenuation compensation ensures easy location of faults at all distances. Key features

Principles of operation. If a cable is metal and it has at least two conductors, it can be tested by a TDR. TDRs will troubleshoot and measure all types of cables. The TDR works on the same principle as radar. A pulse of energy is transmitted down the cable under test. When that pulse reaches the end of the cable, or a fault along the cable, part or all of the pulse energy is reflected back to the instrument. The TDR measures the time it takes for the signal to travel down the cable, see the problem, and reflect back. The TDR then converts this time to distance and displays the information as a waveform and/or distance reading.

The DET-3000 can be used to locate and identify faults in all types of metallic paired cables including heating cables. TDRs can locate both major or minor cabling problems including; sheath faults, broken conductors, water damage, loose connectors, crimps, cuts, smashed cables, shorted conductors, system components, and a variety of other fault conditions. In addition, TDRs can be used to test reels of cable for shipping damage, cable shortages, cable usage, and inventory management. The speed and accuracy of the DET-3000 makes it today's preferred method of cable fault location.

Control and Monitoring

Easy single-handed operation Light Hand-held instrument for long and short range applications Usable for high variety of metallic cables Cable attenuation compensation and narrow pulse for clear and simple trace display Large, high resolution display Back lit LCD effective down to 20C Tactile push buttons Proven durability

DOC-389 Rev.7 07/03

136

DET-3000

Specifications Ranges (nominal) Accuracy Resolution Propagation velocity Pulse Characteristics Output Impedance Measuring leads Output sockets Protection 10 m, 30 m, 100 m, 300 m, 1000 m, 3000 m 0.9% of range 1% of range Variable velocity factor, 0.2 to 0.99 pvf Unit remembers last figure used With Amplitude 7ns to 2s automatically selected to best suit the measuring range 5V nominal when unterminated (SQUARE pulses)

25 , 50, 75 and 100 switchable The DET-3000 comes with 100 Ohm testleads 2 x 4 mm on 19 mm pitch The unit will not be damaged by inadvertent direct connection via the 100 Ohm testleads to 250Vac. However it is unsafe to use the unit in this way. Installations should always be isolated from the mains supply prior of taking measurements with the DET-3000. For safety reasons the DET-3000 should not be used on live installations. Always verify prior of starting the measurements that the complete installation is isolated from the mains. Liquid crystal, 128 x 64 pixels with back light Single vertical line meters or feet user selectable. 9 VDC nominal 6 x AA size LR6 Alkaline batteries (not rechargeable) Battery live 16 hours @20C ambient no backlight Operation Temperature Storage temperature Humidity 20C to +55C 30C to +70 93% RH at +40C

Display Cursor Units Power

Environment

Ingress Protection Safety EMC

Water resistant to BS 2011, Part 2.1 R/IEC 68-2-18, Test Ra EC Directive 73/23/EEC, as amended by 3/68/EEC BS EN 41003: 1997 EC Directive 89/336/EEC, as amended by EC directive 93/68/EEC BS EN 50082-1: 1992 BS EN 55011: 1991 (Group 1 Class B) The equipment is specified for operation in residential, commercial and light industrial environments. 250 x 100 x 55 mm 1.1 Kg (including batteries, soft-case, testlead, manual)

Size (mm) Weight (kg) Ordering Details Part Description PN

DET-3000 546866-000

DOC-389 Rev.7 07/03

137

Control and Monitoring

SB-100

Support bracket

Kit contents 1 support bracket 1 footplate 1 pack containing 2 2 2 2 2 2 2 2 M4 M4 M4 M4 M6 M6 M6 M6 x 20 cheesehead screw nuts plain washers spring lock washers x 30 slotted cheesehead screws nuts plain washers spring lock washers

Support bracket Material 1.5 mm sheet stainless steel The support bracket is a three piece construction that is welded together Surface treatment Chemically passivated Dimensions

Accessories

Dimensions are shown on the drawing below with the tolerance of 0.5 mm. Ordering details Part Description PN Pack size Requires two pipe straps (not supplied)
DOC-389 Rev.7 07/03

SB-100 192932-000 1 per pack Refer to page 150 (Pipe straps)

138

R
Dimensions (in mm)

SB-100

160 10,05
1,5

9
20

20
45,47

10

61 39

160 126 115 111,5 111 38

42

1,5 100 25 65 R 10 117 230 147 173 60 87 147 7 4 25 46 50 57 70 105

7 12

87

Application

SB-100

34

7 4

5 4 46 25 3,2 4

146

6,5 42 45 49 60 150

40 30

AT-TS-13 AT-TS-14 JB-16-02 JB-81 JB-82 JB-EX-04 JB-EX-20 JB-EX-21 JB-EX-27 JB-EX-28 JBU-100-E JBU-100-EP LL-LIM-P-01 MONI-PT100-EXE MONI-PT100-NH RAYSTAT-CONTROL-10 RAYSTAT-EX-02 RAYSTAT-EX-03 RAYSTAT-ECO-10
25 6,75 1,5 40

100

DOC-389 Rev.7 07/03

139

Accessories

SB-101

Support bracket

Kit contents 1 support bracket 1 pack containing 2 2 2 2 2 2 2 2 M4 M4 M4 M4 M6 M6 M6 M6 x 20 cheesehead screw nuts plain washers spring lock washers x 30 slotted cheesehead screws nuts plain washers spring lock washers

1 pack containing

Support bracket Material 1.5 mm sheet stainless steel The support bracket is a two piece construction that is welded together Surface treatment Chemically passivated Dimensions

Accessories

Dimensions are shown on the drawing below with the tolerance of 0.5 mm. Ordering details Part Description PN Pack size Requires two pipe straps (not supplied)
DOC-389 Rev.7 07/03

SB-101 990944-000 1 per pack Refer to page 150 (Pipe straps)

140

R
Dimensions (in mm)
40 R50
2 1

SB-101

120

160

R3

2 40 146 160 140 110 105


1

158,5

Applications

SB-101

1,5

AT-TS-13 AT-TS-14 JB-16-02 JB-81 JB-82 JB-EX-04 JB-EX-20 JB-EX-21 JB-EX-27 JB-EX-28 JBU-100-E JBU-100-EP LL-LIM-P-01 MONI-PT100-EXE MONI-PT100-NH RAYSTAT-CONTROL-10 RAYSTAT-EX-02 RAYSTAT-EX-03 RAYSTAT-ECO-10

160

148

140

110

56

90

39 85 140

DOC-389 Rev.7 07/03

141

Accessories

SB-110

Support bracket

Kit contents 1 support bracket 1 pack containing 2 2 2 2 2 2 2 2 M4 M4 M4 M4 M6 M6 M6 M6 x 20 cheesehead screw nuts plain washers spring lock washers x 30 slotted cheesehead screws nuts plain washer spring lock washers

Support bracket Material 2 mm sheet stainless steel The support bracket is a two piece construction that is spotwelded together Surface treatment Chemically passivated Dimensions Dimensions are shown on the drawing below with the tolerance of 0.5 mm.

Accessories

Ordering details Part Description PN Pack size Requires two pipe straps (not supplied) SB-110 707366-000 1 per pack Refer to page 150 (Pipe straps)

DOC-389 Rev.7 07/03

142

R
Dimensions (in mm)
2 3 130 115 110 90 70 68 45 106 82 50 5 6.5 230 7 4 6.5 (4x)
13 5

SB-110

Application

SB-110

R 10

AT-TS-13 AT-TS-14 JB-16-02 JB-81 JB-82 JB-EX-04 JB-EX-20 JB-EX-27 JB-EX-28 JBU-100-E JBU-100-EP LL-LIM-P-01 MONI-PT100-EXE MONI-PT100-NH MONI-PT100-4/20MA RAYSTAT-CONTROL-10 RAYSTAT-EX-04 RAYSTAT-ECO-10 RAYSTAT-EX-02 RAYSTAT-EX-03

DOC-389 Rev.7 07/03

143

Accessories

50 130 115 110 90 70 68 45 20 5


9

50

SB-111

Support bracket

Kit contents 1 support bracket 1 pack containing 2 2 2 2 2 2 2 2 M4 M4 M4 M4 M6 M6 M6 M6 x 20 cheesehead screw nuts plain washers spring lock washers x 30 slotted cheesehead screws nuts plain washers spring lock washers

Support bracket Material 2 mm sheet stainless steel The support bracket is a two piece construction that is spotwelded together Surface treatment Chemically passivated Dimensions Dimensions are shown on the drawing below with the tolerance of 0.5 mm.

Accessories

Ordering details Part Description PN Pack size Requires two pipe straps (not supplied) SB-111 579796-000 1 per pack Refer to page 150 (Pipe straps)

DOC-389 Rev.7 07/03

144

R
Dimensions (in mm)
2

SB-111

Application
20 7 100 98 R 50

SB-111

35

130 115 110 90 70 68 45

AT-TS-13 AT-TS-14 JB-16-02 JB-81 JB-82 JB-EX-04 JB-EX-20 JB-EX-27 JB-EX-28 JBU-100-E JBU-100-EP LL-LIM-P-01 MONI-PT100-EXE MONI-PT100-NH MONI-PT100-4/20MA RAYSTAT-CONTROL-10 RAYSTAT-ECO-10 RAYSTAT-EX-02 RAYSTAT-EX-03 RAYSTAT-EX-04
R 10 2

R3
40

106 82 50

130 115 110 90 70 68 45

130

5 6.5

40

6.5 (4x)

DOC-389 Rev.7 07/03

145

Accessories

SB-120

Support bracket

Kit contents 1 support bracket 1 pack containing 4 4 4 4 M6 M6 M6 M6 x 30 slotted cheesehead screws nuts plain washers spring lock washers

Support bracket Material Making Surface treatment Chemically passivated Dimensions Dimensions are shown on the drawing below with the tolerance of 0.5 mm. 2 mm sheet stainless steel Die stamped: SB-120

Accessories

Ordering details Part Description PN Pack size Requires two pipe straps (not supplied) SB-120 165886-000 1 per pack Refer to page 150 (Pipe straps)

DOC-389 Rev.7 07/03

146

R
Dimensions (in mm)

SB-120

Application T-M-20-S/+x-y/EX T-M-20-S/+x+y

SB-120

DOC-389 Rev.7 07/03

147

Accessories

JB-SB-26

Support bracket

Pack contents

1 4 4 4

Support Bracket M4 x 20 mm cheesehead screws M4 nuts M4 washers

Support Bracket Material Marking Ordering details Part description PN Pack size Requires two pipe straps (not supplied) JB-SB-26 338265-000 1 per pack Refer to page 150 (Pipe straps) Grade 316 stainless steel to BS 1449: Part 2: 1983 Die stamped JB-SB-26

Accessories
DOC-389 Rev.7 07/03

148

R
Dimensions (in mm)
50 80 68 45

JB-SB-26

Application
2

JB-SB-26

MONI-PT100-NH MONI-PT100-EXE MONI-PT100-4/20MA

50 80 68 45

5 12 places

100

30

50

DOC-389 Rev.7 07/03

149

Accessories

Accessories

Warning labels

Warning labels indicate the presence of electrical trace-heating under the insulation of the pipe or other equipment. (min. of 1 label per 6 m of trace-heating line) Language Croatian Czech Danish Dutch English Finnish French German / French / Italian German Hungarian Italian Latvian Lithuanian Norwegian Norwegian / English Polish Portugese Romanian Russian Slovenian Spanish Swedish Label reference ETL-HR ETL-CZ ETL-DK LAB-I-23 LAB-I-01 LAB-ETL-SF LAB-I-05 LAB-ETL-CH ETL-G LAB-ETL-H ETL-I LAB-I-32 LAB-ETL-LIT ETL-N LAB-ETL-NE ETL-PL LAB-ETL-POR ETL-RO LAB-ETL-R ETL-SLO ETL-Spanish LAB-ETL-S PN 938764-000 731605-000 C97690-000 749153-000 938-947-000 756479-000 883061-000 148648-000 597779-000 623725-000 C97688-000 841822-000 105300-000 C97689-000 165899-000 258203-000 945960-000 902104-000 574738-000 538156-000 C97686-000 691703-000

Pipe straps

Metal straps for pipe mounting of integrated power connections, above the insulation tees and end seals as well as support brackets and the tubular insulation entry. Banding: stainless steel Pipe outer diameter in mm 20-47 40-90 60-288 60-540 (inches) Pipe strap PSE-047 PSE-090 PSE-280 PSE-540 PN 700333-000 976935-000 664775-000 364489-000

(1/2" - 11/4") (11/4" - 3") (2" - 10") (2" - 20")

HARD-SPACER-SS-25MM-25M

Stainless steel spacer for fixing the heating cable on walls, tanks and vessels, etc Width spacer: 12.5 mm Fixing distance for cables: each 25 mm Length: 25 m/roll PN 107826-000

Accessories
DOC-389 Rev.7 07/03

150

R
Fixing tapes

Accessories
Self-adhesive tape for fixing the heating cables on pipes or other equipment.

GT-66

Glass cloth tape for attaching heating cable to pipe. Not for stainless-steel pipes or for installation temperatures below 4.4C. 20 m per roll, 12 mm width PN C77220-000 Glass cloth tape for attaching heating cable to pipe. For stainless-steel pipes or for any installation below 4.4C. 16 m per roll, 12 mm width PN C77221-000

GS-54

ATE-180

Aluminium tape* for attaching heating cables and thermostat sensors to pipes and tanks. Minimum installation temperature: 0C 55 m per roll, 63.5 mm width PN 846243-000

* Power output of selfregulating heating cables might increase when installed with aluminium tape or other heat transfer aids. Please use TraceCalc or contact your Tyco Thermal Controls representative for further details.

Protective grommet

G-02

Silicone grommet that protects the heating cable at sharp edges such as endplates of insulation cladding, flanges etc. It can be cut-to-length and resists temperatures up to 215C. PN 412549-000

Thermostat kit

HWA-WAGOTSTAT-KIT

Kit with supplementary terminals to connect thermostats of type RAYSTAT-EX-02 to the junction boxes JBS, JBM and JBU. The kit includes 2 terminals WAGO 284 series (1 x L, 1 x PE), 1 power cable gland GL-36-M25, 1 end plate and 1 installation instruction PN 966659-000

Glands

GL-33

3/4" NPT power cable gland for RAYSTAT-EX-02 (EEx d II C) Nickel plated brass For use with armoured power cables with outer sheath diameter of 12 mm - 21 mm and inner sheath diameter of 8.5 mm - 16 mm PN 493217-000 3/4" NPT power cable gland for RAYSTAT-EX-02 (EEx d II C) Nickel plated brass For use with non-armoured power cables with outer sheath diameter of 8.5 mm - 16 mm. PN 931945-000 M25 power cable gland (EEx e) Polyamide For use with non-armoured power cables with outer diameter range 8 mm - 17 mm Spare part for JBS-100, JBM-100 and JBU-100 PN 774424-000

GL-34

GL-36-M25

DOC-389 Rev.7 07/03

151

Accessories

R
GL-38-M25METAL

Accessories

M25 power cable gland (EEx e II and EEx d II C) for use with junction boxes with internal earth plate (-EP) or metal boxes. For use with armoured power cables with sheath diameter of 12 mm - 21 mm and inner sheath diameter of 8.5 mm - 16 mm. PN 056622-000

GL-44-M20-KIT

Cable gland EExe (M20), polyamide for use with PI cables with a diameter range of 5-13 mm. With green / yellow sleeve. PN 1244-000 848

GL-45-M32

Cable gland EExe (M32), polyamide for use with power cables with a diameter range of 12-21 mm. PN 1244-000 847

Adaptors

ADPT-PG16M25-EEXE

Pg16 (female) to M25 (male) adaptor (EEx e) Polyamide, ATEX approved adaptor with captive sealing ring (o-ring) For use with cables with outer diameters up to 15 mm PN 541892-000

REDUCERM25/PG16-EEXE

M25 (female) to Pg16 (male) reducer (EEx e) Polyamide, ATEX approved reducer with captive sealing ring (o-ring) For use with cables with outer diameters up to 13 mm PN 953780-000 M25 (male) to M20 (female) reducer EExd Brass, ATEX approved reducer with captive sealing ring (o-ring) PN 404287-000 M25 (male) to M20 (female) reducer EExd including a locknut and fibre washer Brass, ATEX approved reducer with captive sealing ring (o-ring) PN 630617-000

REDUCERM25/20-EEXD

REDUCERM25/20

REDUCER-M25/ M20-PA

M25 (male) to M20 (female) reducer Polyamide, ATEX approved reducer with captive sealing ring (o-ring) Ordinary area PN 184856-000 M32 (male) to M25 (female) reducer (EEx e) ATEX approved reducer. Polyamide. PN 1244-000 859

REDUCER-M32/ M25-EEXE

Accessories

ADPT-M20/25EEXD

M20 (male) to M25 (female) Brass, ATEX approved adaptor with captive sealing ring (o-ring) For use with cables with outer diameters up to 14 mm PN 684953-000

DOC-389 Rev.7 07/03

152

R
Small pipe adaptors with part number JBS-SPA Small pipe adaptor required for pipes 1 (DN25), applicable for JBS-100, E-100, E-100-L E90515-000 (bag of 5 adaptors) Small pipe adaptor required for pipes 1 (DN25), applicable for JBM-100, T-100 E55673-000 (bag of 5 adaptors)

Accessories

JBM-SPA

Plugs

HWA-PLUG-M20EXE-PLASTIC

M20 stopping plug EExe Polyamide Spare part for various junction boxes. PN 1244-000 845

HWA-PLUG-M25EXE-PLASTIC

M25 stopping plug Polyamide Spare part for JBS-100, JBM-100, JBU-100 PN 434994-000

Transmitter

TCONTROL-ISOL-01 Isolator for MONI-PT100-4/20MA Galvanically isolated module for EEx ia protection of MONI-PT100-4/20MA sensor between the hazardous area and the ordinary area. Surface or DIN 35 rail mounted. A seperate 24 Vdc power supply such as MONI-RMC-PS24 is required. PN 670021-000

Power supply

MONI-RMC-PS24

24 Vdc power supply Wide range input (100-240 Vac) power supply to provide 24 Vdc input for MONI-RMC-BASE or TCONTROL-ISOL-01 products. Surface or DIN 35 rail mounted. PN 972049-000

DOC-389 Rev.7 07/03

153

Accessories

Belgi / Belgique
Electrical Tracing Geestbeekweg 5 3210 Lubbeek Tel. (016) 35 39 90 Fax (016) 25 27 26

Hrvatska
ELGRI d.o.o. S. Mihalica 2 10000 Zagreb Tel. (1) 6050188 Fax (1) 6050187

Romania
Santel Impex Srl. Str C-tin Radulescu Motru Nr6 Bl. 35, Sc C, Ap 117, Sect 4 75164 Bucuresti Tel. (1) 330 7199/2591 Fax (1) 330 1229/2591

Bulgaria
ERZET Engineering Kompl. Bratja Miladinovi/bl57/vch.4A BG-8000 Burgas Tel./fax (56) 3 4198 Mobile (88) 639 903 Fax (UK) +44 8701368787

Italia
Tyco Electronics Raychem SPA Centro Direzionale Milanofiori Palazzo E5 20090 Assago, Milano Tel. (02) 57 57 61 Fax (02) 57 57 62 01

Schweiz / Suisse
Tyco Thermal Controls N.V. Office Baar Haldenstrasse 5 Postfach 2724 6342 Baar Tel. (041) 766 30 80 Fax (041) 766 30 81

esk Republika
Raychem HTS s.r.o. Novodvorsk 82 14200 Praha 4 Phone 241 009 215 Fax 241 009 219

Lithuania/Latvia
V. Demjanov Pavenciu Str. 39-22 5500 LT Mazheikiai Tel. (9) 841156 Fax (9) 396272

Suomi
Tyco Thermal Controls Nordic AB Stationsvgen 4 S-430 63 Hinds Puh. 0800 11 67 99 Telekopio 0800 11 86 74

Danmark
Tyco Thermal Controls Nordic AB Stationsvgen 4 S-430 63 Hinds Tel. 80 88 29 92 Fax 80 88 29 91

Magyarorszg
Raychem Ges.m.b.H. Magyarorszgi Kzvetlen Kpviselet Grassalkovich ut 255. 1239 Budapest Tel. (1) 289 20 40 Fax (1) 289 20 45

Sverige
Tyco Thermal Controls Nordic AB Stationsvgen 4 S-430 63 Hinds Tel. 0301-228 00 Fax 0301-212 10

Deutschland
Tyco Thermal Controls GmbH Englerstrae 11 69126 Heidelberg Tel. (0 62 21) 30 43-0 Fax (0 62 21) 30 43-43

Nederland
Tyco Thermal Controls b.v. Van Heuven Goedhartlaan 121 1181 KK Amstelveen Tel. (020) 6400411 Fax (020) 6400469

Trkiye
HENA Ltd. Ressam Vecih Bereketoglu Sokak Candan Ap. No 8/1 Caddebostan 81060 Kadiky, Istanbul Tel. (216) 363 1212 Fax (216) 360 3816

Espaa
Tracelec C/Josep V. Foix, 10 Apdo. 1326-43080 43007 Tarragona Tel. (34) 977 290 039 Fax (34) 977 290 032

Norge
Tyco Thermal Controls Norway AS Malerhaugveien 25 Postboks 6076 - Etterstad 0602 Oslo Tel. +47 66 81 79 90 Fax +47 66 80 83 92

United Kingdom
Tyco Thermal Controls (UK) Ltd 3 Rutherford Road Stephenson Industrial Estate Washington, Tyne & Wear NE37 3HX, United Kingdom Tel. 44 (191) 419 8200 Fax 44 (191) 419 8201

France
Tyco Thermal Controls SA B.P. 738 95004 Cergy-Pontoise Cedex Tl. (01) 34 40 73 30 Fax (01) 34 40 73 33

sterreich
Tyco Thermal Controls N.V. Lubbeek Office Wien Brown-Boveri Strasse 6/14 2351 Wiener Neudorf Tel. (0 22 36) 86 00 77 Fax (0 22 36) 86 00 77-5

ROSSI i drugie strany SNG


1998 Tyco Thermal Controls DOC-389 Rev.7 07/03 Printed in Belgium on chlorine-free bleached paper.

Polska
Raychem Polska Sp. z o.o. Tyco Thermal Controls ul. Farbiarska 69 C 02-862 Warszawa Tel. (022) 54 52 950 Fax (022) 54 52 951

RAJXEM 125315, g. Moskva Leningradskij prospekt, dom 72, ofis 807 Tel.: (095) 7211888 Faks: (095) 7211891

Our products satisfy the requirements of the relevant European Directives.

Yugoslavia
Minel-Keying Dositejeva 24 YU 23300 Kikinda Tel. (230) 34519 Fax (230) 23479

www.tycothermal.com
DigiTrace, Isopad, Raychem, RAYSTAT and Tracer are trademarks of Tyco Electronics. Cage clamp is a trademark of WAGO.

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect or consequential damages arising from the sale, resale, use or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes, without notification to the Buyer, to processing or materials that do not affect compliance with any applicable specification.

This document was supplied to you by: