Sie sind auf Seite 1von 1

Protection, Substation Automation, Power Quality and Measurement

6.2 Protection Systems

Motor feeders The energization of motors causes a starting current of initially 5 to 6 times the rated current (locked rotor current). A typical time-current curve for an induction motor is shown in g. 6.2-113. In the rst 100 ms, a fast-decaying asymmetrical inrush current also appears. With conventional relays, it was common practice to set the instantaneous overcurrent stage of the short-circuit protection 20 to 30 % above the locked rotor current with a short-time delay of 50 to 100 ms to override the asymmetrical inrush period. Numerical relays are able to lter out the asymmetrical current component very rapidly so that the setting of an additional time delay is no longer applicable. The overload protection characteristic should follow the thermal motor characteristic as closely as possible. The adaptation is made by setting the pickup value and the thermal time constant, using the data supplied by the motor manufacturer. Furthermore, the locked-rotor protection timer has to be set according to the characteristic motor value. Time grading of overcurrent relays (51) The selectivity of overcurrent protection is based on time grading of the relay operating characteristics. The relay closer to the infeed (upstream relay) is time-delayed against the relay further away from the infeed (downstream relay). The calculation of necessary grading times is shown in g. 6.2-113 by an example for denite-time overcurrent relays. The overshoot times take into account the fact that the measuring relay continues to operate due to its inertia, even if when the fault current is interrupted. This may be high for mechanical relays (about 0.1 s) and negligible for numerical relays (20 ms). Inverse-time relays (51) For the time grading of inverse-time relays, in principle the same rules apply as for the denite-time relays. The time grading is rst calculated for the maximum fault level and then checked for lower current levels (g. 6.2-114). If the same characteristic is used for all relays, or if when the upstream relay has a steeper characteristic (e.g., very much over normal inverse), then selectivity is automatically fullled at lower currents. Differential relay (87) Transformer differential relays are normally set to pickup values between 20 and 30 % of the rated current. The higher value has to be chosen when the transformer is tted with a tap changer. Restricted earth-fault relays and high-resistance motor / generator differential relays are, as a rule, set to about 10 % of the rated current.

10,000 1,000 Time in seconds 100 10 1 0.1 0.01 0.001 0 1 2 3 4 5 6 7 8 9 10

Current in multiplies of full-load amps Motor starting current Locked-rotor current Overload protection characteristic High set instantaneous O/C stage Motor thermal limit curve Permissible locked-rotor time

Fig. 6.2-113: Typical motor current-time characteristics

Time

51

51

51

Main Feeder Maximum feeder fault level

0.2-0.4 seconds Current

Fig. 6.2-114: Coordination of inverse-time relays

lnstantaneous overcurrent protection (50) This is typically applied on the nal supply load or on any protection relay with sufcient circuit impedance between itself and the next downstream protection relay. The setting at transformers, for example, must be chosen about 20 to 30 % higher than the maximum through-fault current. The relay must remain stable during energization of the transformer.

Siemens Energy Sector Power Engineering Guide Edition 7.0

321

Das könnte Ihnen auch gefallen