TBG 210 ME 50Hz

Code: 17710010 Series: TBG ME

Technical and functional features


-Gas-fired burners, EN676. -Two-stage progressive/modulating operation. -Ability to operate with output modulation by means of automatic RWF40 regulator mounted on the control panel (to be ordered separately with the modulation kit). -Compatible with any type of combustion chamber, according to EN303 standard.. -High blowing efficiency, low electrical input, low noise. -Air-gas mixing at blast-pipe. -Burnt gas recycling blast-pipe able to achieve very low pollutant emissions, particularly with regard to nitrous oxides (NOx). -Maintenance facilitated by the fact that the mixing unit can be removed without having to remove the burner from the boiler. TBG 45 - 60 ME -Low NOx and CO gas-fired burners, EN676 "Classe III". -Modulation ratio 1:4. -Regulation of air flow rate for first and second stage with damper closure on standby to prevent in-flue heat dispersion. -Gas adjustment gas by throttle valve controlled by electronically controlled step servo motor. -Tightness gas valve control, EN676. -Comes with 4 and 7-poles connectors, 1flange and 1 insulating seal to connect the burner to the application. TBG 85 - 120 - 150 - 210 ME -Partial combustion gas recirculation blast-pipe with low NOx emissions (class II). -Ambidextrous hinged combustion head allowing an easy maintenance access without removing the burner from the boiler.. -Air capacity adjustment by means of linear opening damper using electronically controlled step servo motor. -Automatic closure of the air damper during stand-by.. -Electrical panel that connects by 4 and 7 pole plugs/sockets provided. -Electrical panel with protection rating of IP 55. -Sliding boiler coupling flange to adapt to the head protrusion of the various types of boilers. -High turndown ratio (1:5).

Design features
-Light die-cast aluminium ventilation unit. -Air intake with butterfly gate for the regulation of the air combusting flow rate, with sound insulation and designed for optimal air damper opening linearity. -Sliding boiler coupling flange to adapt the head protrusion to the various types of boilers. -Adjustable blast-pipe with stainless steel nozzle and deflector disk in steel. -Flame viewer. -Air pressure switch to ensure the presence of combustion air. -Regulation of the air combusting flow rate by means of an electric pitch-pitch servomotor. -Gas train gas with safety valve and electromagnetically activated working, minimum pressure switch, pressure regulator and gas filter. -Flame scanning by ionisation electrode. -Error proof connectors for gas train electrical supply. -7-pole outlet for burner electrical and thermostat connections, and 4-pole outlet for second stage control or for the connection of the capacity electronic regulator.

-Prepared for microamperometer connection with ionisation cable. -Electrical protection rating IP44. TBG 45 - 60 ME -High performance centrifugal fan. -Mono-phase electric motor to run fan for TBG 45, three-phase for TBG 60. -Synoptic control panel with led of operation and block and burner off, operation and block indicator. -Microchip sequence controller (electronic cam), built-in valve tightness control and eBus connection - EN 298..Operating sequence, modulating ratio, lockout fault code display. TBG 85 - 120 - 150 - 210 ME -Centrifugal fan in light aluminum alloy. -Three-phase light aluminum alloy electric motor. . -Combustion air input with sound insulation and designed for optimal air damper opening linearity. -Light die-cast aluminium alloy electrical panel. -Control panel with display diagram for working mode with indication lights, start/stop switch, burner shutoff selector and burner unblocking button; possibility to install RWF 40 electronic modulator. -Microchip sequence controller (electronic cam), built-in valve tightness control and eBus connection - EN 298.. -Operating sequence and fault code display.

Technical Data - TBG 210 ME 50Hz:


Minimum output Maximum output Minimum gas flow rate Maximum gas flow rate Motor rated power Electric Power Supply Phase Electric Power Supply Frequency 1 Electric Power Supply Current Electric Power Supply Voltage Weight Pack Width Pack Height Package depth Weight of Packaging 400 2100 40 211 3 3 50 AC 400 73 1080 700 770 94 kW kW m3/h m3/h kW N Hz V kg mm mm mm kg

Das könnte Ihnen auch gefallen