SE6000B-3P Static Exciter

Modificaiton: SE6000B-3P-UIC The SE6000B-3P is a complete self contained Static Exciter designed for replacement of existing rotating exciters, saturable reactors and other electronic types of exciters. Retrofitting the SE6000B-3P to replace other systems is a very simple and straightforward process and normally can be performed in a very short time. Because of oversized heat sinks, it does not have to be installed in a fan-cooled housing. The SE6000B-3P can be configured to be used as an adjustable power supply for industrial applications such as heating processes, synchronous motor control and many other applications that require and an adjustable DC current up to 600adc. Special modifications can be made to this exciter to allow it to be controlled by signals from devices such as PLCs, Genset or VAR controllers and other types of devices used for generator or load control.

Simple, Reliable, And Affordable


Specifications: Input Voltage Output Voltage Output Amperage HZ Regulation Source Regulation Type External Control Voltage Protection Physical Size Weight Voltage Regulator Firing Module Build Up System

190 to 240vac 3 phase 1 to 250vdc 600adc Continuous 50/60 External Sensing 120vac 3 phase Flat Response +/-10vdc Internal Fusing 31.5 x 36 x 12in 90lbs VM120-3 FM4 External Flash

Warning!
Only a professional switchboard and generator technician should attempt to install this product! Follow all standard safety precautions before and during installation. Wear protective eyewear and clothing while installing and during adjustments.

Installation Instructions
1. 2. 3. Remove the SE6000B-3P Static Exciter assembly from its packing crate and inspect for shipment damage. Mount the SE6000B-3P in a protected cabinet or safety enclosure. If this exciter was shipped without the regulator and firing module installed, mount the lower removable plate (Fig.2), onto the static exciter and wire up by matching the numbers and colors on TB1 and TB2. If this application is configured with voltage control supplied from a PLC or Genset controller, confirm that this exciter is configured for that application. Connect up the external wiring to the SE6000B-3P and shown in (Fig. 1) Set the droop resistor to the highest resistive value by moving the slider in the correct direction (Fig. 5) Confirm that all wiring is properly connected to the SE6000B-3P and that the current transformer located on phase B. If you are using an external flashing source, confirm that the positive and negative connections to the exciter field terminals are attached in the correct polarity and the source is isolated from ground or other equipment. Adjust the external voltage adjustment potentiometer to the midrange position. (If used with a manual potentiometer.) If using an external control device, set the device to have a +5v offset before starting up.

4. 5. 6. 7. 8.

You are now ready to power up the generator and exciter


1. 2. 3. 4. 5. Start up the generator and bring up to operating speed. Apply 24vdc to the exciter by closing the Start / Stop switch. Apply the external flashing source to the generator fields. Remove this source as soon as the generator begins to build voltage on its own. The exciter will take over at this point. Adjust the external control voltage adjustment to obtain your desired AC voltage from the generator. (If using an external control device, set the initial generator voltage up with the internal voltage pot located on the Static Exciter.) Observe the generator for correct operation for 15 minutes and then place the generator online. (This is done only after initial installation and does not need to be repeated again after the installation)

Special Note:
Do not make any adjustments on the firing module (Fig. 3) without contacting Power-Tronics, Inc., first! You will need an oscilloscope to make any adjustments on this module!

For technical assistance please call: 830.895.4700 or email to: pti@power-tronics.com

Fig. 1

Fig. 2

Voltage Regulator Assembly


SE6000B-3P-UIC

FM4 Firing Card

VM120-3P Voltage Regulator

UIC200

Fig. 3

Fig. 4

Do not adjust any of these potentiometers without first contacting Power-Tronics, Inc.

Voltage Adjust

Increase

Fig. 5 Reactive Droop Compensation

From Current Transformer

Move the slider down to decrease sensitivity to load changes

To B terminal on TB3, SE6000B-3P

Reactive Droop Resistor


Recommended Spare Parts: Qty 2 3 3 1 1 1 Description Main SCR Assembly Main Diode Main Fuses Voltage Regulator Firing Module Relay, 24vdc Part Number 5R2-234 5R2-235 5CF-399 VM120-3P FM4 5R3-430

PRODUCT WARRANTY
Power-Tronics, Inc., assumes no liability for damages due to incorrect voltage or other voltage related damages resulting from either output of the generator or input to the generator exciter system. These problems should be protected with external devices provided by the customer such as fuses, surge suppressors, over/under voltage and frequency controls, manual disconnects or any other protective device. Power-Tronics, Inc., warranties only parts and workmanship of this product for a period of 2 years from the original date of purchase from Power-Tronics, Inc. Under warranty, Power-Tronics, Inc. will replace, exchange or repair the defective product without labor or parts cost to the customer. Remaining warranty of the original product will be transferred to the replaced or repaired product. To obtain warranty, a copy of the original purchase receipt must be sent in with the defective product, which clearly shows the purchase date and serial number of the defective part. A repair request form must be sent in with the product before repairs will begin. You can obtain this form through contacting Power-Tronics, Inc. Send repairs to: Power-Tronics, Inc., 2802 Cobbler Ln., Kerrville Texas USA 78028. Send in repairs only by UPS or FedEx. Any one of the following conditions will void the warranty: Overheating of the power supply components. Overheating of the SCRs or freewheeling diodes. Physical damage to the printed circuit cards, housing or components. Unauthorized repair or alteration of this product. Conductive or corrosive contamination. Removal of our company identification from the product. Removal of any conformal coating of the printed circuit cards or other components. Damage due to overheating or alteration. Inappropriate or infeasible application. Installation by anyone other than a fully qualified and experienced professional electrical generator service and repair technician or engineer. Misuse. Damage to this product resulting from external sources such as field windings, brush and slip ring arcing and other driven devices. Use with any external device not manufactured by Power-Tronics, Inc. Damage to the product resulting from the customers electrical load. No other warranty is expressed or implied.