Beruflich Dokumente
Kultur Dokumente
DVS/DHS/DVSI 500
DVS DVS/DVSI 500
900/ 968 748
DHS 500
830
440/479
DHS
30
438 665
DVS/DHS/DVSI 500
DVSI
535 237 6xM8
4 38
DVS/DHS/DVSI
Voltage/Frequency Phase Power Current Maximum air flow R.p.m. Max. temp. of transported air Max. temp. of transported air when speed-controlled Sound pressure level DVS/DHS at 4/10 m Sound pressure level DVSI at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, two-step, 400V D/Y Speed control, stepless Wiring diagram p. 12-15 Thyristor Transformer Transformer V/50 Hz ~ W A m3/s (m3/h) min-1 C C dB(A) dB(A) kg
500E6
230 1 450 2,2 1,45 (5200) 905 40 40 46/38 (DHS+2dB) 37/29 45/45/52 F IP54 S-ET 10 RTRE 3 REU 3 + S-ET 10 REE 4 6
500DV
400 3 1190 2,10 2,19 (7900) 1325 40 40 56/48 (DHS+2dB) 47/39 49/49/57 F IP 54 STDT 16 RTRD 4 RTRDU 4 S-DT2SKT 18
500DS
400 3 440 1,00 1,50 (5400) 870 40 40 46/38 (DHS+2dB) 37/29 42/42/49 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT 18
SSD p. 506
FDS p. 505
ASK p. 507
VKS p. 507
ASS p. 508
ASF p. 507
VKM p. 507
Transformer p. 454/455
Thyristor p. 456
182
Update 051121
Roof fans
Y = connection
DVS/DHS/DVSI 500E6
LwA Inlet LwA Surrounding DVSI LwA Surrounding dB(A) 60 53 With SSD 450/499/500 LwA Inlet dB(A) 57 51 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 67 54 56 61 62 62 58 53 45 dB(A) 69 56 58 63 64 64 60 55 47 53 51 56 52 53 49 48 40 38 31 42 33 31 28
DVS/DHS/DVSI 500DV
LwA Inlet LwA Surrounding DVSI LwA Surrounding dB(A) 70 63 With SSD 450/499/500 LwA Inlet dB(A) 67 61 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 77 64 66 70 72 71 68 63 56 dB(A) 79 66 68 72 74 73 70 65 58 63 61 65 61 63 59 57 50 48 42 51 43 41 39
Y
M20x1,5
DVS/DHS/DVSI 500DS
LwA Inlet LwA Surrounding DVSI LwA Surrounding dB(A) 60 53 With SSD 450/499/500 LwA Inlet dB(A) 57 51 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 67 54 56 61 62 62 58 53 45 dB(A) 69 56 58 63 64 64 60 55 47 53 51 56 52 53 49 48 40 38 31 42 33 31 28
Electrical accessories
Isolator p. 462
Regulator p. 466
Update 050419
183
Roof fans
DVS/DHS/DVSI 560
DVS Speed-controllable Integral thermal contacts Low sound level Maintenance-free and reliable Vertical or horizontal exhaust
DHS
The DVS/DHS models have impellers with backwardcurved blades and external rotor motors. All three phase motors are D/Y connected allowing two-speed operation if required. The motors are suspended on effective vibration dampers. The casing is made from aluminum and the base frame is powder-coated galvanised steel. Suitable for coastal applications. The impellers are manufactured from aluminium. To protect the motors from overheating the DVS/DHS have thermal contacts with external leads for connection to a motor protection device. DVSI DVSI with 50 mm mineral wool insulation for low noise level.
DVS/DHS/DVSI
Voltage/Frequency Phase Power Current Maximum air flow R.p.m. Max. temp. of transported air Max. temp. of transported air when speed-controlled Sound pressure level DVS/DHS at 4/10 m Sound pressure level DVSI at 4/10 m Weight Insulations class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, two-step, 400V D/Y Wiring diagram p. 12-15 Transformer Transformer V/50 Hz ~ W A m3/s (m3/h) min-1 C C dB(A) dB(A) kg
560DV
400 3 1900 3,50 2,92 (10500) 1210 40 40 58/50 (DHS+2dB) 49/41 58/58/70 F IP 54 STDT 16 RTRD 4 RTRDU 4 S-DT2SKT 18
560DS
400 3 720 1,50 2,10 (7550) 830 40 40 49/41 (DHS+2dB) 40/32 47/47/59 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT 18
Accessories
SSD p. 506
FDS p. 505
ASK p. 507
VKS p. 507
ASS p. 508
ASF p. 507
VKM p. 507
184
Update 050419
Roof fans
Y = connection
Y = connection
DVS/DHS/DVSI 560DV
LwA Inlet LwA Surrounding DVSI LwA Surrounding dB(A) 72 65 With SSD 560/630 LwA Inlet dB(A) 70 64 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 79 66 68 72 74 73 70 65 58 dB(A) 81 68 70 74 76 75 72 67 60 65 63 67 64 65 63 59 52 50 44 56 49 46 45
DVS/DVSI 560
605 939 1100 480 30
DHS 560
DVS/DHS/DVSI 560DS
LwA Inlet LwA Surrounding DVSI LwA Surrounding Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 70 57 59 64 65 65 61 56 48 dB(A) 72 59 61 66 67 67 63 58 50 dB(A) 63 56 56 54 59 56 56 54 51 43 41 34 48 40 37 35
M20x1,5 293
05
DVS/DHS/DVSI 560
14(4x)
Electrical accessories
Transformer p. 454/455
Regulator p. 466
Isolator p. 462
Update 050419
185
Roof fans
DVS/DHS/DVSI 630/710
DVS Speed-controllable Integral thermal contacts Low sound level Maintenance-free and reliable Vertical or horizontal exhaust
DHS
The DVS/DHS models have impellers with backwardcurved blades and external rotor motors. All three phase motors are D/Y connected allowing two-speed operation if required. The motors are suspended on effective vibration dampers. The casing is made from aluminum and the base frame is powder-coated galvanised steel. Suitable for coastal applications. The impellers are manufactured from aluminium. To protect the motors from overheating the DVS/DHS have thermal contacts with external leads for connection to a motor protection device. DVSI DVSI with 50 mm mineral wool insulation for low noise level.
DVS/DHS/DVSI
Voltage/Frequency Phase Power Current Maximum air flow R.p.m. Max. temp. of transported air Max. temp. of transported air when speed-controlled Sound pressure level DVS/DHS at 4/10 m Sound pressure level DVSI at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, two-step, 400V D/Y Wiring diagram p. 12-15 Transformer Transformer V/50 Hz ~ W A m3/s (m3/h) min-1 C C dB(A) dB(A) kg
630DS
400 3 1100 2,10 2,78 (10000) 860 50 50 53/45 (DHS+2dB) 44/36 65/65/79 F IP 54 STDT 16 RTRD 4 RTRDU 4 S-DT2SKT 18
710DS
400 3 2000 4,0 4,58 (16500) 890 40 40 58/50 (DHS+2dB) 49/41 88/88/104 F IP 54 STDT 16 RTRD 7 RTRDU 7 S-DT2SKT 18
Accessories
SSD p. 506
FDS p. 505
ASK p. 507
VKS p. 507
ASS p. 508
ASF p. 507
VKM p. 507
186
Update 050912
Roof fans
Y = connection
Y = connection
DVS/DHS/DVSI 630DS
LwA Inlet LwA Surrounding DVSI LwA Surrounding dB(A) 67 60 With SSD 560/630 LwA Inlet dB(A) 65 59 Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 74 61 63 68 69 69 65 60 52 dB(A) 76 63 65 70 71 71 67 62 54 60 58 63 60 60 58 55 47 45 38 52 44 41 39
DVS/DVSI 630
1150/ 1315 560/600 30
DVS/DVSI 710
1350/ 1483 660/729 40
605 939
674 1035
DHS 630
1100
DHS 710
1282 520 40
DVS/DHS/DVSI 710DS
LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD 710 LwA Inlet Mid-frequency band, Hz Hz Tot 63 125 250 500 1k 2k 4k 8k dB(A) 79 66 68 73 74 74 70 65 57 dB(A) 81 68 70 75 76 76 72 67 59 dB(A) 72 65 dB(A) 69 63 65 62 68 65 65 60 60 52 50 43 54 45 42 46
480 30
M20x1,5 293
05
14(4x)
74
Electrical accessories
Transformer p. 454/455
Regulator p. 466
Isolator p. 462
Update 050419
187