Client Name : M/s Hindustan Coca-Cola Beverages Pvt.

Ltd Project Name : Bangalore Green Field Project Number : 012 - 01137 - 00 Name of Vendor : Quotation Reference Quotation Date : :

Sl.No.
1 2 Make and Origin Model- Type
ESP (mmwg) ISP (mmwg)

Description

Details

Remark

Construction
3.1 Panel Insulation 3.2 Panel Thickness 3.3 Panel Profile

Double skin panel with l access door CFC free PUF In-Situ injection to density of 40+/ 2 Kg/m3 Double skin with 25+/-2 mm thickness Backward curved DIDW,dynamically balanced 55000 CFM x 3 nos + 25000 CFM x 01 no not more than 10 M/s

4
4.1 4.2 4.3 4.4 4.5 4.6 4.7

Type of Blower
Make /Model Air flow . Machine Outlet- in CFM/CMH and QTY Fan outlet velocity MPS Blower motor BKW Blower motor KW Fan RPM Fan Efficiency

Not less than 75 %

Make of motor
5.1 Blower Motor specifications Energy efficient IE--3 motor with minimum 90 % efficiency

Type of drive 6.1 Dimensions W x D x H (mm) 6.2 Weight in kgs 6.3 Whether Single / Three Phase Whether Marine lights/Limit switch/ Mechanical 6.4 Door guard included 6.5 Provision for Cable entry and Water inlet/outlet 6.6 Field wiring details 6.7 Total power in KW 6.8 Connected Load in KW

Client Name : M/s Hindustan Coca-Cola Beverages Pvt. Ltd Project Name : Bangalore Green Field Project Number : 012 - 01137 - 00 Name of Vendor : Quotation Reference Quotation Date : :

Sl.No.
1 2 Make and Origin Model- Type
ESP (mmwg) ISP (mmwg)

Description

Details

Remark

Construction
3.1 Panel Insulation 3.2 Panel Thickness 3.3 Panel Profile

4
4.1 4.2 4.3 4.4 4.5 4.6 4.7

Type of Blower
Make /Model Air flow . Machine Outlet- in CFM/CMH and QTY Fan outlet velocity MPS Blower motor BKW Blower motor KW Fan RPM Fan Efficiency

Double skin panel with individual access door for individual sections CFC free PUF In-Situ injection to density of 40+/ 2 Kg/m3 Double skin with 43+/-2 mm thickness Thermal Break profile Backward curve DIDW,dynamically balanced 40000 CFM x 3 nos and 26000 CFM x 2 nos not more than 10 M/s

Not less than 75 % Energy efficient IE--3 motor with minimum 90 % efficiency

Make of motor
5.1 Blower Motor specifications

Type of drive
6.1 Dimensions W x D x H (mm) 6.2 Weight in kgs 6.3 Whether Single / Three Phase Whether Marine lights/Limit switch/ Mechanical 6.4 Door guard included 6.5 Provision for Cable entry and Water inlet/outlet 6.6 Field wiring details 6.7 Total power in KW 6.8 Connected Load in KW

Client Name : M/s Hindustan Coca-Cola Beverages Pvt. Ltd Project Name : Bangalore Green Field Project Number : 012 - 01137 - 00 Name of Vendor : Quotation Reference Quotation Date : :

Sl.No.
1 2 Make and Origin Model- Type
Cooling efficiency ESP (mmwg) ISP (mmwg)

Description

Details

Remark

Minimum 95 %

Construction
3.1 Panel Insulation 3.2 Panel Thickness

Double skin panel with individual access door for individual sections CFC free PUF In-Situ injection to density of 40+/ 2 Kg/m3 Double skin with 43+/-2 mm thickness Thermal Break profile Backward curve DIDW,dynamically balanced 40000 CFM x 3 nos and 26000 CFM x 2 nos not more than 10 M/s

4
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11

Panel Profile Type of Blower Make /Model Air flow . Machine Outlet- in CFM/CMH and QTY Fan outlet velocity MPS Blower motor BKW Blower motor KW Fan RPM Fan Efficiency ESP ( mm wg) ISP (mmwg) Make of motor

Not less than 75 %

4.12 Blower Motor specifications

Energy efficient IE--3 motor with minimum 90 % efficiency

5
5.1 5.2 5.3 5.4 5.6 5.7 5.8 5.9 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0

Type of drive Make of sensible heat exchanger Material of sensible Heat exchanger Material Size of Adiabatic Heat exchanger Material of Adiabatic Heat exchanger /Make Filter EFFICIENCY Make/Type/Size of filters Nos. of Filters / Face velocity in MPS Media of filter used Make of pump Head in Mts. Kw of the Pump motor / Quantity/Phase U-V treatment unit Type of Secondary Fan/Make/ Model Quantity - in Nos. Secondary Fan Motor in KW/HP - RPM Sec. Fan static in mm.of WG. /output in CFM Dimensions W x D x H (mm) Weight in kgs Whether Single / Three Phase Whether Marine lights/Limit switch/ Mechanical Door guard included Provision for Cable entry and Water inlet/outlet GA drawing with plumbing details Field wiring details Plumbing details Total power in KW Connected Load in KW Water consumption LPH Anti bacterial & food grade Anti bacterial & food grade Anti bacterial & food grade 3 stages required ( 20 micron ,10 micron , 5 micron) 90% efficiency Not more than 500 FPM Food grade antibacterial Grundfoss make only

5.5 Filtering stages

40000 CFM x 3 nos and 26000 CFM x 2 nos

Client Name : M/s Hindustan Coca-Cola Beverages Pvt. Ltd Project Name : Bangalore Green Field Project Number : 012 - 01137 - 00 Name of Vendor : Quotation Reference Quotation Date : :

Sl.N o.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Description
Make and Origin Model- Type Refrigerant used Size of refrigerant piping in mm FAN motor type Indoor details Type of fan Make /Model Air flow . Machine Outlet- in CFM/CMH Fan outlet velocity MPS Fan motor BKW Fan motor KW Fan RPM Make of motor Type of drive Dimensions W x D x H (mm) Weight in kgs Whether Single / Three Phase Field wiring details Total power in KW Connected Load in KW Dimensions W x D x H (mm) Outdoor details Type of fan Make /Model Air flow . Machine Outlet- in CFM/CMH Fan outlet velocity MPS Fan motor BKW Fan motor KW Fan RPM Make of motor Type of drive Dimensions W x D x H (mm) Weight in kgs Whether Single / Three Phase Field wiring details Total power in KW Connected Load in KW

Details

R-407 C /R-134 A /R-410 (environment friendly gas) Energy efficient IE--3 motor with minimum 90 % efficiency

22 23 24 25 26 27 28 29 30 31 32 33 34 35 36