Air System Sizing Summary for Quality lab

Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

Air System Information


Air System Name Equipment Class Air System Type Quality lab SPLT AHU SZCAV Number of zones Floor Area Location 1 1340.0 ft Bangalore, India

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Total coil load Sensible coil load Coil CFM at Jul 1700 Max block CFM Sum of peak zone CFM Sensible heat ratio ft/Ton BTU/(hr-ft) Water flow @ 10.0 F rise 12.7 152.2 103.1 5638 5638 5638 0.677 105.7 113.6 N/A Tons MBH MBH CFM CFM CFM Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jul 1700 98.5 / 82.6 72.7 / 61.9 53.8 / 51.9 48.8 0.210 55 56.0 1 of 1 0.0 F F F F % F OK F

Supply Fan Sizing Data


Actual max CFM Standard CFM Actual max CFM/ft 5638 CFM 5049 CFM 4.21 CFM/ft Fan motor BHP Fan motor kW n/a 4.42 kW

Outdoor Ventilation Air Data


Design airflow CFM CFM/ft 607 CFM 0.45 CFM/ft CFM/person 13.60 CFM/person

Hourly Analysis Program v4.51

Page 1 of 4

System Psychrometrics for Quality lab


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

July DESIGN COOLING DAY, 1700

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 98.5 72.7 53.8 56.6 56.6 69.1 69.6 Specific Humidity (lb/lb) 0.02342 0.01075 0.00870 0.00870 0.00870 0.00922 0.00922 Sensible Heat (BTU/hr) 16943 103055 15072 68296 2743 Latent Heat (BTU/hr) 36685 49116 12422 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet Outlet

Airflow (CFM) 607 5638 5638 5638 5638 5638 5638

CO2 Level (ppm) 400 1281 1281 1281 1281 1388 1388

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) 65021 Zone T-stat Cond Mode (BTU/hr) Cooling 68296 Zone Temp (F) 69.1 Zone Airflow (CFM) 5638 CO2 Level (ppm) 1388 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 2 of 4

System Psychrometrics for Quality lab


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 59.0 67.4 66.4 69.2 69.2 68.4 68.4 Specific Humidity (lb/lb) 0.00588 0.00588 0.00588 0.00588 0.00588 0.00588 0.00588 Airflow (CFM) 607 5638 5638 5638 5638 5638 5638 CO2 Level (ppm) 400 481 481 481 481 491 491 Sensible Heat (BTU/hr) -5504 5014 15072 -4554 0 Latent Heat (BTU/hr) 0 0 0 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet Outlet

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) -204 Zone T-stat Cond Mode (BTU/hr) Cooling -4554 Zone Temp (F) 68.4 Zone Airflow (CFM) 5638 CO2 Level (ppm) 491 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 3 of 4

Psychrometric Analysis for Quality lab


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

Location: Bangalore, India Altitude: 3021.0 ft. Data for: July DESIGN COOLING DAY, 1700
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet 1

0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000

Specific Humidity ( lb/lb )

2 3 4 56

30

40

50

60

70 80 Temperature ( F )

90

100

Hourly Analysis Program v4.51

Page 4 of 4