Sie sind auf Seite 1von 4

MEAC2000 EU Measuring Data Computer Europe

Data Acquisition and Storage Evaluation and Reporting Data Output and Display

p r o D U C t I n f o r M At I o n

MEAC2000 EU Continuous, Conform, Configured


A r E A S o f A p p l I C At I o n

Electronic evaluation acc. European directive 2000/76/EC


Biological waste treatment Biomass incineration Cement industry Crematory Waste incineration

Electronic evaluation acc. European directive 2001/80/EC


Chemical industry Painting plant Power and heat generation Refinery Small combustion Steel industry

D AtA A C q U I S I t I o n
Logging of measuring and operating data every minute Data acquisition unit (DAU) I/O field modul (FM) Serial linked Ethernet (optional) Local near CEMS DAU incl. buffer storage (7 days)

E v A l U At I o n
Cyclic calculations per minute acc. EU directives (see above) EN 14181 QAL3 (optional) Regional regulations (on request) Transparent data modeling Averages and sums Counters and operation times Scaling and standardization Status signals and events Functions and operators Access to internal results Test and simulation system Archiving of calculation results Automatic Reporting Legal: Averages, Classes, Events Customized: MEx data export to MS Excel / XML (optional)

D AtA o U t p U t
Configurable output interfaces DAU / FM / SCU Printer CSV file OPC client Modbus RTU / TCP slave PROFIBUS DP slave File transfer via modem to MEAC remote access system Monitor display Bar graphs, curves, tables Process diagram (optional) Network distribution (optional) Event alarming OSD E-mail (optional)

Analog logging

Digital logging OPC: directly connected to SICK CEMS with SCU via Ethernet Modbus: directly connected to SICK MCS100E via serial link DCS connection (operating data) Storage every minute File system Automatic local backup Remote redundancy (optional) p E r f o r M A n C E f E At U r E S

Remote control via modem /internet

Up to 16 decentralized Data Acquisition devices 1 central Emission PC (EPC) with Windows XP Modular application software of vers. 1.28 EU for EPC Multiple language support Different access levels Customized parameterization Data recalculation with the buffered values Manual input of analog and status values (optional) System integration into companys LAN Connection to process control system (DCS) Data transfer to authoritys MEAC remote access system Remote access to EPC for service
2 MEAC2000 EU | SICK

Complex and flexible evaluation Substitute values for reference components O2 reference calculation fixed and firing-related Validation of averages with 95 % confidence intervals Multiple fixed integration times for averages Frequency distribution of averages in a class system Special classes for CEMS availability and different operating states of the plant Fixed/rolling limit values and different monitoring rules Calculation of total mass emissions Calculation of virtual components and status signals with formula interpreter

2010-08 Subject to change without notice

SYStEM ovErvIEW Data acquisition unit (DAU) Transfer of logged and processed data to the Emission PC. Data buffering in case of transfer failures. Field module (FM) is available for small applications. Emissions pC (EpC) Windows system with Evaluation software for received data. Data distribution via network to Client PCs or via modem to Remote access PC. Connection to process control system available. Evaluation Software 1.28 EU Windows application software running on the Emission PC with modules for processing, recording and display of data.

Decentralized data acquisition Field module Centralized evaluation

Distributed visualization of operator systems

Transmission of data to authority

DAU Options

Soft WArE MoDUlES

System administration Login, adjustments, system log, data model log, report configuration, data recalculation System control Acquisition, storage, calculation, evaluation, communication, long-term archiving System simulation Parallel processing in fast motion with test data model

Data model configuration Parameterization of plant units, constants, status signals, formula, components, counters, analog/digital outputs Current display Configurable diagrams and printouts of current data Historic display Configurable diagrams, printouts and CSV export of historic data

2010-08 Subject to change without notice

MEAC2000 EU | SICK

8010981/2010-08 DIV03 Printed in Germany Subject to change without prior notice.

technical data Evaluation parameters

MEAC2000 EU

Cycle time Integration time Value types Report types


Device parameters Dimensions

1 min 3, 10, 20, 30, 60, 120, 240, 480 min Minute, average (AV), AV trend, day, daily trend, month, year Bulgarian No. 6 (via option MEx), Croatian (via option MEx XML), French DRIRE, UK EA, customized
EPC: Midi Tower or 19, 4 HU, 466 mm (D) DAU: 19, 3 HU, 135 x 450 x 240 mm (HxWxD) FM: 65 x 51 (HxW) EPC: +5 +30 C DAU: 5 +50 C FM: 10 +50 C 2000/76/EC, 2001/80/EC, EN 14181 EPC: IP 20 DAU: IP 54 FM: IP 20 CE DAU: 16 ... 80 inputs, 5 ... 30 mA, potential-free like up to 10V, 100 resistance FM: 2 ... 16 inputs, 0 ... 20 mA, single-ended, not potential-free DAU: 8 ... 32 outputs, 0 ... 25 mA, not potential-free FM: 2 ... 16 outputs, 0 ... 20 mA, not potential-free DAU: 32 ... 256 inputs, 24 V internal/external, potential-free FM: 4 ... 32 inputs, 24 V DAU: 12 ... 96 outputs, 48 V 500 mA, change-over relay FM: 4 ... 24 outputs, 24 V 500 mA EPC: RS-232 (9/25 poles), RS-485 (9 poles), Ethernet (RJ45) DAU: RS-232 (9 poles) FM: RS-485 (9 poles) EPC: Modbus RTU slave via RS-232/485, Modbus TCP slave via Ethernet, PROFIBUS DP slave via RS-485, OPC DA 2.0 client via Ethernet DAU: Proprietary via RS-232 (TTY, RS-485/422, FO, Ethernet as options) FM: Modbus RTU slave via RS-485 (Ethernet as option) Data Acquisition Unit (DAU) incl. memory; I/O Field Modul (FM) Emission PC (EPC) with Windows XP and 2 hard disks Client PC (CPC) for work stations (optional) Remote access PC (RPC) for plant supervisor or authority (optional) Evaluation software version 1.28 EU (Data model is required) Network access for CPC (optional) Remote access system for RPC (optional, data transfer software for EPC is required when using modem connection) Remote service (optional) Process display (optional) Manual input (optional) MEx automatic report export to MS Excel or XML (optional, report template and configuration is required) MEx configurator (optional) QAL3 driver (optional, SICK QAL3 Master is required)

Ambient condition Ambient temperature

Conformities Evaluation Protection class

EMC Inputs, outputs, Interfaces Analog input modules Analog output modules Digital input modules Digital output modules Interfaces

Bus protocols

General System components

Software

Languages

Croatian, Dutch, English, French, German, Hungarian, Italian, Lithuanian, Macedonian, Portuguese, Russian, Serbian, Slovenian, Slovakian, Spanish (other languages on request)

SICK MAIHAK GmbH | Germany Nimburger Str. 11 | 79276 Reute | www.sick.com Phone +49 7641 469-0 | Fax +49 7641 469-1149 | info.pa@sick.de