Beruflich Dokumente
Kultur Dokumente
Users Manual
www.barr-thorp.com
AT LEAST THE 10 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL SCHNEIDER ELECTRIC SALES OFFICE. Start-up Quick Guide
1. Check that the delivery corresponds to your order. 2. Before taking any commissioning actions read carefully the safety instructions
in Chapter SAFETY.
3. Before the mechanical installation, check the minimum clearances around the
application you want to use and confirm by pressing the enterbutton. If the Start-Up wizard is not active, follow the instructions 7a and 7b. 7a. Select the language of the keypad from the Menu M6, page 6.1. Instructions on using the keypad are given in Chapter CONTROL KEYPAD 7b. Select the application you want to use from the Menu M6, page 6.2. Instructions on using the keypad are given in Chapter CONTROL KEYPAD.
8. All parameters have factory default values. In order to ensure proper
operation, check the rating plate data for the values below and the corresponding parameters of parameter group G2.1. nominal voltage of the motor nominal frequency of the motor nominal speed of the motor nominal current of the motor motor cos All parameters are explained in the programming manual (CD).
9.
10. The ATV78 Variable Speed Drive is now ready for use.
Telemecanique is not responsible for the use of the Variable Speed Drives against the instructions.
www.barr-thorp.com
www.barr-thorp.com
ABOUT THE ATV78 USER'S MANUAL AND THE PROGRAMMING MANUAL (CD) Congratulations for choosing the Smooth Control provided by ATV78 Variable Speed Drives! The User's Manual will provide you with the necessary information about the installation, commissioning and operation of ATV78 Variable Speed Drives. We recommend that you carefully study these instructions before powering up the Variable Speed Drive for the first time.
4
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
5
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
6.2.1.2 Galvanic isolation barriers..........................................................................................42 6.2.2 Control terminal signals ................................................................................................................ 43 6.2.2.1 Digital input signal inversions......................................................................................44 6.2.2.2 Jumper selections on the VW3A78201 basic board ......................................................45 7. CONTROL KEYPAD......................................................................................................................... 47 7.1 Indications on the Keypad display .......................................................................................... 47 7.1.1 Drive status indications ................................................................................................................. 47 7.1.2 Control place indications............................................................................................................... 48 7.1.3 Status LEDs (green green red) ............................................................................................... 48 7.1.4 Text lines ...................................................................................................................................... 48 7.2 Keypad push-buttons ............................................................................................................. 49 7.2.1 Button descriptions ....................................................................................................................... 49 7.3 Navigation on the control keypad ........................................................................................... 50 7.3.1 Monitoring menu (M1)................................................................................................................... 52 7.3.2 Parameter menu (M2)................................................................................................................... 53 7.3.3 Keypad control menu (M3)............................................................................................................ 54 7.3.3.1 Selection of control place ...........................................................................................54 7.3.3.2 Keypad reference ......................................................................................................55 7.3.3.3 Keypad direction .......................................................................................................55 7.3.3.4 Stop button activated .................................................................................................55 7.3.4 Active faults menu (M4) ................................................................................................................ 55 7.3.4.1 Fault types ................................................................................................................56 7.3.4.2 Fault codes ...............................................................................................................57 7.3.4.3 Fault time data record ................................................................................................60 7.3.5 Fault history menu (M5) ................................................................................................................ 61 7.3.6 System menu (M6) ....................................................................................................................... 61 7.3.6.1 Language selection ....................................................................................................64 7.3.6.2 Application selection..................................................................................................64 7.3.6.3 Copy parameters.......................................................................................................65 7.3.6.4 Parameter comparison ...............................................................................................67 7.3.6.5 Security ....................................................................................................................68 7.3.6.6 Keypad settings .........................................................................................................69 7.3.6.7 Hardware settings......................................................................................................71 7.3.6.8 System info ...............................................................................................................73 7.3.7 Expander board menu (M7) .......................................................................................................... 76 7.4 Further keypad functions........................................................................................................ 76 8. COMMISSIONING............................................................................................................................ 77 8.1 Safety .................................................................................................................................... 77 8.2 Commissioning of the Variable Speed Drive .......................................................................... 77 9. FAULT TRACING ............................................................................................................................. 80
6
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Safety 1. SAFETY
ONLY A COMPETENT ELECTRICIAN MAY CARRY OUT THE ELECTRICAL INSTALLATION
1.1 Warnings
1 2 3 4 5 1
The components of the power unit of the Variable Speed Drive are live when ATV78 is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from the potential. The motor terminals U, V, W and the DC-link/brake resistor terminals /+ are live when ATV78 is connected to mains, even if the motor is not running. The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when ATV78 is disconnected from mains. If the Variable Speed Drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1). Only spare parts delivered by Telemecanique can be used.
2 3 4
7
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
MOTOR RUN CHECK LIST Before starting the motor, check that the motor is mounted properly a ensure that the machine connected to the motor allows the motor to started. Set the maximum motor speed (frequency) according to the motor and the machine connected to it. Before reversing the motor shaft rotation direction make sure that this can be done safely. Make sure that no power correction capacitors are connected to the motor cable. Make sure that the motor terminals are not connected to mains potential.
1 2 3 4 5
8
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
2.1 CE marking
The CE marking on the product guarantees the free movement of the product within the EEA (European Economic Area). It also guarantees that the product meets the various requirements placed upon it (such as the EMC Directive and possibly other directives according to the so-called new procedure). ATV78 Variable Speed Drives carry the CE label as a proof of compliance with the Low Voltage Directive (LVD) and the Electro Magnetic Compatibility (EMC). The company http://www.sgsfimko.com/ has acted as the Competent Body.
General
The EMC Directive provides that the electrical apparatus must not excessively disturb the environment it is used in, and, on the other hand, it shall have an adequate level of immunity toward other disturbances from the same environment. The compliance of ATV78 Variable Speed Drives with the EMC directive is verified with Technical Construction Files (TCF) checked and approved by SGS FIMKO, which is a Competent Body. The Technical Construction Files are used to authenticate the comformity of Telemecanique Variable Speed Drives with the Directive because such a large-sized product family is impossible to be tested in a laboratory environment and because the combinations of installation vary greatly. 2.2.2
Technical criteria
Our basic idea was to develop a range of Variable Speed Drives offering the best possible usability and cost-efficiency. EMC compliance was a major consideration from the outset of the design. ATV78 Variable Speed Drives are marketed throughout the world, a fact which makes the EMC requirements of customers different. As far as the immunity is concerned, all ATV78 Variable Speed Drives are designed to fulfil even the strictest requirements, while as regards the emission level, the customer may want to upgrade Telemecanique's already high ability to filter electro-magnetic disturbances. 2.2.3
EMC Classification
Class L (up to 160 KW): Provides filtering for the 2nd environment, restricted distribution according to EN 61800-3+A11 (IEC 18003). Class N (more than 200KW): The drives of this class do not provide EMC emission protection. This kind of drives are mounted in enclosures. All ATV78 Variable Speed Drives fulfil all EMC immunity requirements (standards EN 61000-6-1, EN 61000-6-2 and EN 61800-3+A11). Warning: This is a product of the restricted sales distribution class according to IEC 61800-3. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. Note: For changing the EMC protection class of your ATV78 Variable Speed Drive from class L to class N, please refer to the instructions given in Chapter 5.4.
9
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
ATV78 Variable Speed Drives have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete. Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier. If the delivery does not correspond to your order, contact the supplier immediately.
3.1 Storage
If the Variable Speed Drive is to be kept in store before use make sure that the ambient conditions are acceptable: Storing temperature 40+70C Relative humidity <95%, no condensation
3.2 Maintenance
In normal conditions, ATV78 Variable Speed Drives are maintenance-free. However, we recommend to clean the heatsink with compressed air whenever necessary. The cooling fan can easily be changed if necessary. It may also be necessary to check the tightening torques of the main power terminals at intervals.
3.3 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use. The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications. Neither can the manufacturer be held responsible for consequential damages. In all matters concerning the warranty, please contact the local Schneider electric sales office.
10
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
4.1 Introduction
Brake resistor* modu le
1) Main s
L1 L2 L3
Brake C hopper*
Rectifier
3~
Charg.res.
Motor
U Outpu t V EM C r W fil te
2)
3~
Fan
Power Supply
Control I/O
Control I/O
Control I/O
*Brake resistor is available as optionnal equipment. *Brake resistori s avail abl e as optional equipment for classes (FR4 to FR9). How er, t he br is standard equipment in classes ATV78 to FR6 to ATV78 Brakeevchopperake resist or can be installed internally in classes FR4 U22Yand is installed C16Y, externally in classes FR7 to FR9. whileke chopper belongs to t(he standard equipment in classes FR4 to chopper is required. Bra in greater classes above ATV78C20Y) an external FR6, while in greater classes (FR7 to F R9) it is optional.
Figure 4-1. ATV78 block diagram Figure 4-1 presents the block diagram of the ATV78 Variable Speed Drive. The Variable Speed Drive mechanically consists of two units, the Power Unit and the Control Unit. Pictures of the mechanical assemblage on pages 34 to 39 The three-phase AC-choke (1) at the mains end together with the DC-link capacitor (2) form an LC-filter, which, again, together with the diode bridge produce the DC-voltage supply to the IGBT Inverter Bridge (3) block. The AC-choke also functions as a filter against High Frequency disturbances from the mains as well as against those caused by the Variable Speed Drive to the mains. It, in addition, enhances the waveform of the input current to the Variable Speed Drive. The entire power drawn by the Variable Speed Drive from the mains is active power. The IGBT Inverter Bridge produces a symmetrical, 3-phase PWM-modulated AC-voltage to the motor. The Motor and Application Control Block is based on microprocessor software. The microprocessor controls the motor basing on the information it receives through measurements, parameter settings, control I/O and control keypad. The motor and application control block controls the motor control ASIC which, in turn, calculates the IGBT positions. Gate drivers amplify these signals for driving the IGBT inverter bridge.
11
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Technical data
The control keypad constitutes a link between the user and the Variable Speed Drive. The control keypad is used for parameter setting, reading status data and giving control commands. It is detachable and can be operated externally and connected via a cable to the Variable Speed Drive. Instead of the control keypad, also a PC can be used to control the Variable Speed Drive if connected through a similar cable. You can have your Variable Speed Drive equipped with a control I/O board which is either isolated or not isolated from the ground. The basic control interface and the parameters (the Basic Application) are easy to use. If a more versatile interface or parameters are required, a more suitable application can be chosen from the Application Package (CD). See the programming manual (CD) for more information on the different applications. A brake resistor is available as external option for ATV78 ATV78F. Optional I/O expander boards that increase the number of inputs and outputs to be used are also available. The input and output EMC filters have no influence on the basic functions of the Variable Speed Drive. They are, however, necessary for the fulfilment of the EMC directives.
12
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Low overload = Max current, 2 sec/20 sec, 110% overloadability, 1 min/10 min Following continuous operation at rated output current, 110% rated output current for 1 min, followed by a period of load current less than rated current, and of such duration that the rms output current, over the duty cycle, does not exceed rated output current. All sizes up to ATV78C16Y available with IP21 and IP54 enclosures. Above ATV78C20Y either IP00 or built into enclosure. Reference Maxi. Motor power rating in kW Motor power Transient according to mains voltage rating in HP current for mains voltage 525 V 550 V 660 V 690 V 575 V A ATV78U22Y 2,3 2,4 2,9 3 3,0 6,7 ATV78U30Y 3,0 3,2 3,8 4 3,0 9,0 ATV78U40Y 4,2 4,4 5,3 5,5 5,0 11,0 ATV78U55Y 5,7 6,0 7,2 7,5 7,5 15,0 ATV78U75Y 8,4 8,8 10,5 11 11 20,0 ATV78D11Y 11,4 12,0 14,3 15 15 27 ATV78D15Y 14,1 14,7 17,7 18,5 20 36 ATV78D18Y 16,7 17,5 21,0 22 25 44 ATV78D22Y 22,8 23,9 28,7 30 30 54 ATV78D30Y 28,5 29,9 35,9 37,5 40 68 ATV78D37Y 34 36 43 45 50 82 ATV78D45Y 42 44 53 55 60 104 ATV78D55Y 57 60 72 75 75 124 ATV78D75Y 68 72 86 90 100 160 ATV78D90Y 84 88 105 110 125 200 ATV78C11Y 100 105 126 132 150 250 ATV78C13Y 122 128 153 160 150 288 ATV78C16Y 152 159 191 200 200 300 ATV780C20Y 190 199 239 250 250 370 ATV780C25Y 240 251 301 315 300 440 ATV780C31Y 270 283 340 355 400 585 ATV780C35Y (1) 342 359 430 450 450 693 ATV780C45Y (1) 380 399 478 500 500 828 ATV780C50Y (1) 426 446 536 560 600 1004 ATV780C56Y (1) 479 502 603 630 650 1170 ATV780C63Y (1) 540 566 679 710 800 1170 ATV780C71Y (1) 609 638 765 800 800 1170 ATV780C80Y (1) 761 797 957 1000 1100 1410 ATV780M10Y (1) 0 0 0 1250 2060 0 0 0 1250 2360 0 0 0 2360 0 0 0 1500 2600 Table 4-1 power rating of ATV78 for standard torque application
Add
2 for IP21, 5 for IP54 1) Consult the local Schneider sales office for the availability of ATV780C35Y to ATV780M10Y
13
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Technical data
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default.
14
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Technical data
4.2.2
525 V 550 V 660 V 690 V 1,7 1,8 2,1 2,2 2,3 2,4 2,9 3 3,0 3,2 3,8 4 4,2 4,4 5,3 5,5 5,7 6,0 7,2 7,5 8 9 11 11 11 12 14 15 14 15 18 18,5 17 18 21 22 23 24 29 30 29 30 36 37,5 34 36 43 45 42 44 53 55 57 60 72 75 68 72 86 90 84 88 105 110 100 105 126 132 122 128 153 160 152 159 191 200 190 199 239 250 240 251 301 315 270 283 340 355 342 359 430 450 380 399 478 500 426 446 536 560 479 502 603 630 540 566 679 710 609 638 765 800 761 797 957 1000 0 0 0 0 0 0 0 0 0 1250 Table 4-2 power rating of ATV78 for constant torque application
ATV78(F)U22Y ATV78(F)U30Y ATV78(F)U40Y ATV78(F)U55Y ATV78(F)U75Y ATV78(F)D11Y ATV78(F)D15Y ATV78(F)D18Y ATV78(F)D22Y ATV78(F)D30Y ATV78(F)D37Y ATV78(F)D45Y ATV78(F)D55Y ATV78(F)D75Y ATV78(F)D90Y ATV78(F)C11Y ATV78(F)C13Y ATV78(F)C16Y ATV780(F)C20Y ATV780(F)C25Y ATV780(F)C31Y ATV780(F)C35Y (1) ATV780(F)C45Y (1) ATV780(F)C50Y (1) ATV780(F)C56Y (1) ATV780(F)C63Y (1) ATV780(F)C71Y (1) ATV780(F)C80Y (1) ATV780(F)M10Y (1)
Add 2 for IP21, 5 for IP54 1) Consult the local Schneider sales office for the availability of ATV780C35Y to ATV780M10Y
15
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Motor connection
Control characteristics
Switching frequency (see parameter 2.6.9) Frequency reference Analogue input Panel reference Field weakening point Acceleration time Deceleration time Braking torque Ambient operating temperature Storage temperature Relative humidity Air quality: - chemical vapours - mechanical particles Altitude Vibration EN50178/EN60068-2-6 Shock EN50178, EN60068-2-27 Enclosure class
0U Standard torque: Ambient temperature max. +40C, overload 1.1 x I (1 min./10 min.) Constant torque: Ambient temperature max. +50C, overload 1.5 x I (1 min./10 min.) Imax for two seconds, torque motor dependent Imax for 2 s every 20 s 0320 Hz (ATV78); 0.01 Hz (ATV78); Application dependent (ATV78F) Frequency control U/f Open Loop Sensorless Vector Control Closed Loop Frequency Control Closed Loop Vector Control (ATV78F only) ATV78 16 kHz; Factory default 1.5 kHz
Ambient conditions
Resolution 0.1% (10-bit), accuracy 1% Resolution 0.01 Hz 30320 Hz 03000 sec 03000 sec DC brake: 30% * TN (without brake option) 10C (no frost)+50C: Constant torque 10C (no frost)+40C: Standard torque 40C+70C 0 to 95% RH, non-condensing, non-corrosive, no dripping water IEC 60721-3-3, unit in operation, class 3C2 IEC 60721-3-3, unit in operation, class 3S2 100% load capacity (no derating) up to 1000 m 1% derating for each 100m above 1000.; max. 3000m 5150 Hz Displacement amplitude 1 mm (peak) at 315.8 Hz Max acceleration amplitude 1 G at 15.8150 Hz UPS Drop Test (for applicable UPS weights) Storage and shipping: max 15 G, 11 ms (in package) IP21/NEMA1 standard up to ATV78C16Y. IP54/NEMA12 option up to ATV78C16Y. Note! Keypad installation required for IP54
16
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Technical data
Immunity Emissions
Control connections
Analogue input voltage Analogue input current Digital inputs Auxiliary voltage Output reference voltage Analogue output Digital outputs Relay outputs
Protections
Mains supervision Motor phase supervision Unit overtemperature protection Motor overload protection Motor stall protection Motor underload protection Short-circuit protection of +24V and +10V reference voltages Table 4-1. Technical data
Fulfil all EMC immunity requirements EMC level L: EN 61800-3 (1996)+A11 (2000)(2nd environment) EN 50178 (1997), EN 60204-1 (1996), EN 60950 (2000, 3rd edition) (as relevant), CE, UL, CSA, FI, GOST R, IEC 61800-5; (see unit nameplate for more detailed approvals) 0+10V, R = 200k, (10V+10V joystick control) Resolution 0.1%, accuracy 1% 0(4)20 mA, R = 250 differential Positive or negative logic; 1830VDC +24V, 15%, max. 250mA +10V, +3%, max. load 10mA 0(4)20mA; RL max. 500; Resolution 10 bit; Accuracy 2% Open collector output, 50mA/48V 2 programmable change-over relay outputs Switching capacity: 24VDC/8A, 250VAC/8A, 125VDC/0.4A Min.switching load: 5V/10mA Trip limit 4.0*I instantaneously 1200VDC 460 VDC In case of earth fault in motor or motor cable, only the Variable Speed Drive is protected Trips if any of the input phases is missing Trips if any of the output phases is missing Yes Yes Yes Yes Yes
17
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Installation 5. INSTALLATION
5.1 Mounting
The Variable Speed Drive can be mounted in either vertical or horizontal position on the wall or on the back plane of a cubicle. Enough space shall be reserved around the Variable Speed Drive in order to ensure a sufficient cooling, see Figure 5-5, Table 5-6 and Table 5-7. Also see to that the mounting plane is relatively even. The Variable Speed Drive shall be fixed with four screws (or bolts, depending on the unit size). The dimensions of installation are presented in Figure 5-5 and Table 5-6. Lift units bigger than FR7 out of the package using a jib crane. ATV78(F)U22YATV78(F)D90Y
W2
D1
H1 H2
H3 W1
E1
Figure 5-1. ATV78 dimensions, IP21 Dimensions [mm] W1 W2 H1 H2 H3 D1 148 558 541 519 237 ATV78U22YATV78D22Y 195 190 630 614 591 292 ATV78D30YATV78D37Y 237 255 755 732 721 312 ATV78D55YATV78D90Y 285 Table 5-1. Dimensions for different Variable Speed Drive types, IP21 Type 9 9 9 E1 3 x 37 3 x 47 3 x 59
18
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Installation
ATV78(F)C11YATV78(F)C16Y
D1
D2
H4 W4
H3 W4
W1
W3
W2
H2 D3 H1
H3
D1 362
D2
D3
ATV78C11Y 480 400 165 9 ATV78C16Y Table 5-2. The dimensions ATV78, FR9
21
340 285
*Brake resistor terminal box (202.5 mm) not included, see page 36.
19
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Installation
ATV78(F)20YATV78(F)C31Y
W1
W2
1
W4 H6
H4 H1
H3 H2
H5 D1 W3
Figure 5-3. ATV78 dimensions, FR10 Note: Dimension of choke not included Type W1 ATV78C20Y ATV78C31Y W2 W3 W4 30 H1 500 425 325 Dimensions [mm] H2 H3 H4 H5 850 761 300 H6 17 D1 446 1 12 2 23
1120 879
20
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Installation
Installation of input chokes in C20Y and above The input choke carries out several functions in the ATV frequency converter. The input choke is needed as an essential component for motor control, to protect the input and DC-link components against abrupt changes of current and voltage as well as to function as a protection against harmonics. The input chokes are included in the standard delivery of the ATV frequency converters. The chokes listed below are used in the ATV frequency converter frame FR10:
Frequency converter (690VAC) ATV78C20Y ATV78C25Y ATV78C31Y Choke type Therm. current [Ith/A] 261 400 Nominal inductance/ Supply voltage [L/H] 575-690V(terminal) 187 (3) 126 (3) Calculated loss [W] 460 570
CHK0261N6A0 CHK0400N6A0
D3
Cable connections Always connect the supply cables to the choke terminals marked with #1 (see Figure 5-4). Choose the converter connection according to the table below:
Supply voltage 575-690Vac Converter connection (terminals) 3
1
S2
H1
3 2
W2
3 2
3 2
S1 D2 D1
Terminal numbers
W3
W3
S2 9 (9 St.) 11 (9 St.)
Weight [kg] 53 84
21
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Enough free space shall be left around the Variable Speed Drive to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below. If several units are mounted above each other the required free space equals C + D (see figure below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the inlet air to be used by the upper unit. Type Dimensions [mm] A A2 B C D C 30 20 160 80 ATV78U22Y ATV78D22Y 80 300 100 80 ATV78D30Y ATV78D55Y 80 150 80 300 200 ATV78U75Y ATV78D90Y 50 80 400 250 ATV78C11Y B B (350**) ATV78C16Y Table 5-6. Mounting space dimensions A A2 ** B C D = clearance around the freq. converter (see also A2 and B) = clearance needed on either side of the Variable Speed Drive for fan change (without disconneting the motor cables) = min. clearance for fan change = distance from one Variable Speed Drive to another or distance to cabinet wall = free space above the Variable Speed Drive = free space underneath the Variable Speed Drive
A A A2 A2
Type ATV78U22YATV78D22Y ATV78D30YATV78D55Y ATV78D75YATV78D90Y ATV78C11YATV78C16Y Table 5-7. Required cooling air.
22
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
ATV78(F)C20YATV78C31Y
The variable speed drives of frame FR10 and bigger are mounted in a cabinet. Enough space according to the table below must be left above and in front of the cabinet to ensure sufficient cooling and space for maintenance.
200 mm
800 mm
Figure 5-6. Space to be left free above (left) and in front of (right) the cabinet Cooling air required [m3/h) 2600
23
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in order to reduce the motor noise), this inevitably affects the power losses and cooling requirements according to the graphs below. Power losses for a Power losses for a switching frequency of switching frequency of 1,5 kHz 3,6 kHz W W 88,39 123,36 ATV78U22Y ATV78U30Y 99,84 139,33 ATV78U40Y 119,34 166,55 ATV78U55Y 160,26 223,65 ATV78U75Y 192,33 268,40 ATV78D11Y 289,00 403,31 ATV78D15Y 384,79 537,00 ATV78D18Y 408,32 569,83 ATV78D22Y 519,14 724,48 602,28 840,51 ATV78D30Y ATV78D37Y 762,35 1063,90 981,10 1369,18 ATV78D45Y ATV78D55Y 1412,42 1971,12 ATV78D75Y 1982,46 2766,63 ATV78D90Y 1933,16 2697,84 2534,46 3536,99 ATV78C11Y ATV78C13Y 3076,81 4293,86 ATV78C16Y 3604,00 5029,59 ATV780C20Y 4060,51 5666,67 ATV780C25Y 4785,16 6677,96 ATV780C31Y 5546,49 7740,44 ATV780C35Y 5993,09 8363,69 Table 5-8. Power loss Reference
24
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Figure 5-7. Changing of EMC protection class, ATV78(F)U22YATV78(F)D22Y ATV78(F)D30YATV78(F)D37Y: Remove this screw and replace with plastic screw M4
25
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
NOTE! Only a Telemecanique service person may change the EMC protection class of ATV78, ATV78(F)C11YATV78(F)C31Y.
26
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
6.
Power board
BR option
L1* L2* L3 M 3~
Figure 6-1. Principal wiring diagram of ATV78 power unit, ATV78(F)U22YATV78(F)D22Y (690V)
27
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Power board
BR (option)
L1* L2* L3
M 3~
Figure 6-2.Principal wiring diagram of ATV78 power unit, ATV78(F)D30YATV78(F)C16Y *When using 1-phase supply, connect the cables to terminals L1 and L2.
k6 4 fh8
28
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Power board
L1 L2 L3
B- B+/R+
R-
BR (option)
L1* L2* L3
M 3~
Figure 6-3. Principal wiring diagram of ATV power unit, ATV78(F)C20YATV78(F)C31Y The dotted lines refer to option component.
29
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
The mains cables are connected to terminals L1, L2 and L3 (to L1 and L2, if 1-phase supply is used) and the motor cables to terminals marked with U, V and W. See Figure 6-1 to Figure 6-3. A cable entry flange should be used when installing the motor cable at both ends in order to reach the EMC levels. See Table 6-1 for the cable recommmendations. Use cables with heat resistance of at least +60C. The cables and the fuses must be dimensioned according to the Variable Speed Drive nominal OUTPUT current which you can find on the rating plate. Dimensioning according to the output current is recommended because the Variable Speed Drive input current never significantly exceeds the output current. Installation of cables according to UL regulations is presented in Chapter 6.1.3. Table 6-2 shows the minimum dimensions of the Cu-cables and the corresponding fuse sizes. The dimensions of the fuses in the table have been given taking their function as a cable overload protection into account. Recommended fuse types: gG/gL (for FR6 to FR9), see Table 6-2. If the motor temperature protection of the drive (see ATV78 programming manual (CD)) is used as an overload protection, the cable shall be chosen accordingly. If three or more cables are used in parallel for bigger units each cable requires a separate overload protection. These instructions apply only to cases with one motor and one cable connection from the Variable Speed Drive to the motor. In any other case, ask the factory for more information. 2nd environment Cable type Level L Level N Mains cable 1 1 Motor cable 2 1 Control cable 4 4 Table 6-1. Cable types required to meet standards. Level L Level N: 1 = EN61800-3, 2nd environment. See page 9. = Power cable intended for fixed installation and the specific mains voltage. Shielded cable not required. = Power cable equipped with concentric protection wire and intended for the specific mains voltage. = Power cable equipped with compact lowimpedance shield and intended for the specific mains voltage. *360 earthing of both motor and FC connection required to meet the standard = Screened cable equipped with compact lowimpedance shield.
2 3
Note: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).
30
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
FR7
52 ATV78D37Y 63 62 ATV78D45Y FR8 80 80 ATV78D55Y 100 100 ATV78D75Y 125 125 ATV78D90Y FR9 ATV78C11Y 144 160 170 200 ATV78C13Y 208 250 ATV78C16Y Table 6-2. Cable and fuse sizes for ATV78
95-185 Cu/Al2
595
31
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Installation instructions
1 2 3
Before starting the installation, check that none of the components of the Variable Speed Drive is live. If the Variable Speed Drive is installed outside a switchgear, separate cubicle or electrical room, it must be equipped with a protection cover (see e.g. Figure 6-5) as provided by the regulations for IP21 protection class. For installations in a switchgear, separate cubicle or electrical room, the cable protection plate is normally not necessary. Place the motor cables sufficiently far from other cables: Avoid placing the motor cables in long parallel lines with other cables If the motor cables run in parallel with other cables, note the minimum distances between the motor cables and other cables given in table below. The given distances also apply between the motor cables and signal cables of other systems. The maximum length of the motor cables is 300 m. For longer cables, use an output choke. The motor cables should cross other cables at an angle of 90 degrees.
4 5
If cable insulation checks are needed, see Chapter 6.1.4. Connect the cables: Strip the motor and mains cables as advised in Table 6-3 and Figure 6-4. Remove the screws of the cable protection plate. Do not open the cover of the power unit! Make holes into and pass the cables through the rubber grommets on the bottom of the power unit (see e.g. Figure 6-6) Connect the mains, motor and control cables into their respective terminals (see e.g. Figure 6-6) For information on the installation of greater units, please contact the factory or your local distributor. For Information on cable installation according to UL regulations see Chapter 6.1.3. Make sure that the control cable wires do not come in contact with the electronic components of the unit. If an external brake resistor (option) is used, connect its cable to the appropriate terminal. Check the connection of the earth cable to the motor and the Variable Speed Drive terminals marked with . Connect the separate shield of the power cable to the earth terminals of the Variable Speed Drive, motor and the supply centre. Attach the cable protection plate with the screws. Ensure that the control cables or the cables of the unit are not trapped between the frame and the protection plate.
32
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Cabling and connections 6.1.2.1 Stripping lengths of motor and mains cables
Earth conductor Earth conductor
A1
C1
A2
C2
B1
D1
B2
D2
MAINS
MOTOR
nk6141 fh8
Figure 6-4. Stripping of cables Frame A1 B1 C1 ATV78(F)U22YD22Y 20 90 15 ATV78(F)D30YD45Y 25 120 25 ATV78(F)D55Y 23 240 23 ATV78(F)D75YD90Y 28 240 28 ATV78(F)C11YC16Y 28 295 28 Table 6-3. Cables stripping lengths [mm] D1 60 120 240 240 295 A2 20 25 23 28 28 B2 90 120 240 240 295 C2 15 25 23 28 28 D2 60 120 240 240 295
33
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Mains cable Mains cable Motor cable Figure 6-6. Cable installation in ATV78, FR6
34
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
DC terminals
35
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
DC terminals
36
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Earth terminals
37
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
R R+/B+ B
Figure 6-14. DC and brake resistor terminals on FR9; DC terminals marked with B and B+, brake resistor terminals marked with R and R+. When using brake resistor terminals on FR9 you must add braking unit kit VW3A78702.
38
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
To meet the UL (http://www.ul.com/) regulations, a UL-approved copper cable with a minimum heatresistance of +60/75C must be used. The tightening torques of the terminals are given in Table 6-4. Type ATV78U22YATV78D22Y ATV78D30YATV78D37Y ATV78D45YATV78D55Y ATV78D75YATV78D90Y ATV78C11YATV78C16Y Frame FR6 FR7 FR8 FR9 Tightening torque [Nm] 4 10 20/9* 40/22* 40/22* 70/40**
* Tightening torque of terminal connection to the isolative base in Nm/in-lbs. ** Apply counter torque to the nut on the other side of the terminal when tightening/loosening the terminal screw in order to avoid damage to the terminal mounting. 6.1.4
1. Motor cable insulation checks Disconnect the motor cable from terminals U, V and W of the Variable Speed Drive and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1M. 2. Mains cable insulation checks Disconnect the mains cable from terminals L1, L2 and L3 of the Variable Speed Drive and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1M. 3. Motor insulation checks Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1M.
39
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Usually, when the Variable Speed Drive is delivered from the factory, the control unit includes at least the standard compilation of two basic boards (I/O board and relay board) which are normally installed in slots A and B. On the next pages you will find the arrangement of the IOpalkit of the two basic boards, the wiringdiagrams and the terminalsignals. The I/O boards mounted at the factory are indicated in the type code. For more information on the option boards, see ATV78 option board manual. The control board can be powered externally (+24V) by connecting the external power source to the bidirectional terminal #6, see page 43. This voltage is sufficient for parameter setting and for keeping the fieldbus active. Note! If the 24V inputs of several Variable Speed Drives are parallelly connected we recommend to use a diode in terminal #6 in order to avoid the current to flow in opposite direction. This might damage the control board. See picture below.
External +24V
#6
#7
#6
#7
#6
#7
#6
#7
nk6_17
40
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control connections
The basic control connections are shown in Chapter 6.2.2. The signal descriptions of the Standard Application are presented in Chapter 2 of the programming manual(CD). If you use some other application check the programming manual for the signal descriptions of the respective application.
1 +10Vref 2 AI1+ 3 GND 4 AI2+ 5 AI26 24Vout 7 GND 8 DIN1 9 DIN2 10 DIN3 Basic I/O board 11 CMA VW3A78201 NXOPTA1 12 24Vout 13 GND 14 DIN4 15 DIN5 16 DIN6 17 CMB 18 AO1+ 19 AO120 DO1
in s l o t B VW3A78202
24 V GND
in s lo t A VW3A78201
21 22 23 24 25 26
Figure 6-19. General wiring diagram of the basic relay boards (VW3A78202)
41
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
1 0Vr ef GND +24 V GND AI1 AI2 + AI2 DIN1... DIN3 CM A DIN4... DIN6 CM B A O1+ A O2 DO1 RO1 /1 RO1 /2 RO1 /3 RO2 /1 RO2 /2 RO2 /3 TI1 + TI1 -
Gate drivers
C ont ro l I/O gr ou nd
L1 L2 L3
Di gita l in put group A Di gita l in put group B Analo gu e output Di gita l output
Control panel
Control board
Control board
U V W
42
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
1 2
3 4
GND/AI1 AI2+
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
GND/AI2 24 Vout (bidirectional) GND DIN1 DIN2 DIN3 CMA 24 Vout (bidirectional) GND DIN4 DIN5 DIN6 CMB AO1+ AO1 DO1
Analogue input common 24V auxiliary voltage I/O ground Digital input 1 Digital input 2 Digital input 3 Digital input common A for DIN1, DIN2 and DIN3. 24V auxiliary voltage
I/O ground Same as terminal #7 Digital input 4 Ri = min. 5k Digital input 5 1830V = "1" Digital input 6 Digital input common B for Must be connected to GND or 24V of I/O terminal or DIN4, DIN5 and DIN6 to external 24V or GND jumpperit (see page 46) Analogue signal (+output) Output signal range: Analogue output common Current 0(4)20mA, RL max 500 or Voltage 010V, RL >1k jumpperit (see page 46) Open collector output Maximum Uin = 48VDC Maximum current = 50 mA
Table 6-6. Control I/O terminal signals on basic I/O board VW3A78201
43
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
21 22 23 24 25 26
Relay output Switching capacity Min.switching load Relay output Switching capacity Min.switching load
Table 6-7. Control I/O terminal signals on basic relay board VW3A78202
Positive logic (+24V is the active signal) = the input is active when the switch is closed
44
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Cabling and connections 6.2.2.2 Jumper selections on the VW3A78201 basic board
The user is able to customise the functions of the Variable Speed Drive to better suit his needs by selecting certain positions for the jumpers on the VW3A78201 board. The positions of the jumpers determine the signal type of analogue and digital inputs. On the A1 basic board, there are four jumper blocks X1, X2, X3 and X6 each containing eight pins and two jumpers. The selectable positions of the jumpers are shown in Figure 6-23.
45
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
= Factory default
NOTE
! !
Check the correct positions of the jumpers. Running the motor with signal settings different from the jumper positions will not harm the Variable Speed Drive but may damage the motor. If you change the AI signal content also remember to change the corresponding board parameter in M7.
46
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
The control keypad is the link between the ATV78 Variable Speed Drive and the user. The ATV78 control , READY, keypad features an alphanumeric display with seven indicators for the Run status (RUN, STOP, ALARM, FAULT) and three indicators for the control place (I/O term/ Keypad/BusComm). There are also three Status Indicator LEDs (green - green - red), see Status LEDs (green green red) below. The control information, i.e. the number of menu, description of menu or the displayed value and the numeric information are presented on three text lines. The Variable Speed Drive is operable through the nine push-buttons of the control keypad. Furthermore, the buttons serve the purposes of parameter setting and value monitoring. The keypad is detachable and isolated from the input line potential.
RUN
ready
run
fault
II
III
Figure 7-1. Telemecanique control keypad and drive status indications Drive status indications controlkeypad 7.1.1 The drive status indications tell the user what the status of the motor and the drive is and whether the motor control software has detected irregularities in motor or Variable Speed Drive functions. 1 RUN = Motor is running; Blinks when the stop command has been given but the frequency is still ramping down. = Indicates the direction of motor rotation. STOP = Indicates that the drive is not running.
2 3 4 5 6
READY = Lights when AC power is on. In case of a trip, the symbol will not light up. ALARM = Indicates that the drive is running outside a certain limit and a warning is given. FAULT = Indicates that unsafe operating conditions were encountered due to which the drive was stopped.
47
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.1.2
The symbols I/O term, Keypad and Bus/Comm (see Figure 7-1) indicate the choice of control place made in the Keypad control menu (M3) (see chapter 7.3.3). a I/O term b Keypad c Bus/Comm 7.1.3 = I/O terminals are the selected control place; i.e. START/STOP commands or reference values etc. are given through the I/O terminals. = Control keypad is the selected control place; i.e. the motor can be started or stopped, or its reference values etc. altered from the keypad. = The Variable Speed Drive is controlled through a fieldbus.
The status LEDs light up in connection with the READY, RUN and FAULT drive status indicators. I II III = Illuminates with the AC power connected to the drive. Simultaneously, the drive status indicator READY is lit up. = Illuminates when the drive is running. Blinks when the STOP button has been pushed and the drive is ramping down. = Illuminates when unsafe operating conditions were encountered due to which the drive was stopped (Fault Trip). Simultaneously, the drive status indicator FAULT blinks on the display and the fault description can be seen, see chapter 7.3.4, Active Faults.
7.1.4
The three text lines (, , ) provide the user with information on his present location in the keypad menu structure as well as with information related to the operation of the drive.
= Location indication; displays the symbol and number of menu, parameter etc. Example: M2 = Menu 2 (Parameters); P2.1.3 = Acceleration time = Description line; Displays the description of menu, value or fault. = Value line; Displays the numerical and textual values of references, parameters etc. and the number of submenus available in each menu.
48
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Button descriptions
reset select enter = = = This button is used to reset active faults (see Chapter 7.3.4). This button is used to switch between two latest displays. May be useful when you want to see how the changed new value influences some other value. The Enter button serves for: 1) Confirmation of selections 2) Fault history reset (23 seconds) Browser button up Browse the main menu and the pages of different submenus. Edit values. Browser button down Browse the main menu and the pages of different submenus. Edit values. Menu button left Move backward in menu. Move cursor left (in parametermenu). Exit edit mode. Hold down for 23 seconds to return to main menu. Move forward in menu. Move cursor right (in parametermenu). Enter edit mode.
3 4
start
Start button. Pressing this button starts the motor if the keypad is the active control place. See Chapter 7.3.3. Stop button. Pressing this button stops the motor (unless disabled by parameter R3.4/R3.6). See Chapter 7.3.3.
stop
49
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
RUN
READY
Local
Monitor
V1 V14
The first menu level consists of menus M1 to M7 and is called the Main menu. The user can navigate in the main menu using the browser up and down. The desired submenu can be entered from the main menu using the menubuttonleft. When there still are pages to enter under the currently displayed menu or page, you can see an arrow ( ) in the lower right corner of the display and by pressing the Menu button right, you can reach the next menu level. The control keypad navigation chart is shown on the next page. Please note that the menu M1 is located in the lower left corner. From there you will be able to navigate your way up to the desired menu using the menu and browser buttons. More detailed descriptions of the menus you will find later in this Chapter.
50
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
R ADY E
M7
R EADY
READY
I / Ot er m
Expander boards
G7.1
I / O te r m
G7.1.1
I/ Ot erm
G1 G5
ST O P
I/O te rm
A: VW3A78201
Parameters
G1
G1
P1 P3
M6
R EAD Y
S.6.1
STOP
I /Ot e r m
R EADY
Syste m Menu
Language
enter
Change value
S1 S 9
E n gl i sh
Browse
READ Y
M5
I / te rm O
H.5.1
REA DY
I /O t e r m
READY
Fault history
H 1 H3
11 Output phase
T1 T7
Operation days
17
M4
ST O P
I/O te rm
FAU LT
F1
STOP
I /O te rm
FA ULT
T1
STOP
I/Ot erm
FAUL T
Activ e faults
or:
1 1 Output phase
F0
T1
T7
Operation days
17
ST OP
R EADY
M3
I /O t e r m
P.3.1
STOP
I /O t e r m
READY
Keypad control
Control Place
enter
P1 P 3
I/O Terminal
Browse
Change value
R EADY
R EADY
R EADY
M2
I/O t e r m
G.2.1
I/O te rm
P.2.1.1
Loc al
enter
Parameters
G 1 G9
Basic parameters
P1 P15
Min Frequency
13.95 Hz
M1
RU N
I /O t e r m
R EADY
RUN
REA DY
I / O te r m
V.1.1
Monitor
Output frequency
V1 V 1 5
Figure 7-3. Keypad navigation chart
13.95 Hz
No editing !
51
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.3.1
You can enter the Monitoring menu from the Main menu by pushing the Menu button right when the location indication M1 is visible on the first line of the display. How to browse through the monitored values is presented in Figure 7-4. The monitored signals carry the indication V#.# and they are listed in Table 7-1. The values are updated once every 0.3 seconds. This menu is meant only for signal checking. The values cannot be altered here. For changing values of parameters see Chapter 7.3.2.
RUN
R EADY
Lo ca l
V.1.2
FreqReference
13.95 Hz
RU N RE A D Y Lo cal RU N READ Y Local
M1
V.1.1
Moni to r
Output frequency
V1 V14
Figure 7-4. Monitoring menu Code Signal name Output frequency Frequency reference Motor speed Motor current Motor torque Motor power Motor voltage DC-link voltage Unit temperature Motor temperature Voltage input Current input DIN1, DIN2, DIN3 DIN4, DIN5, DIN6 DO1, RO1, RO2 Analogue output M1.1 Multimonitoring items 7 Table 7-1. Monitored signals Unit Hz Hz rpm A % % V V C % V mA
13.95 Hz
Description Frequency to the motor Calculated motor speed Measured motor current Calculated actual torque/nominal torque of the unit Calculated actual power/nominal power of the unit Calculated motor voltage Measured DC-link voltage Heat sink temperature Calculated motor temperature AI1 AI2 Digital input statuses Digital input statuses Digital and relay output statuses AO1 Displays three selectable monitoring values. See chapter 7.3.6.5.
mA
52
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.3.2
Parameters are the way of conveying the commands of the user to the Variable Speed Drive. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display. The value editing procedure is presented in Figure 7-5. Push the Menu button right once to move into the Parameter Group Menu (G#). Locate the parameter group desired by using the browser and push the Menu button right again to enter the group and its parameters. Use again the browser to find the parameter (P#) you want to edit. From here you can proceed in two different ways: Pushing the Menu button right takes you to the edit mode. As a sign of this, the parameter value starts to blink. You can now change the value in two different manners:
1 Just set the new desired value with the browser and confirm the change with the enterbutton.
Consequently, the blinking stops and the new value is visible in the value field.
2 Push the Menu button right once again. Now you will be able to edit the value digit by digit. This
editing manner may come in handy, when a relatively greater or smaller value than that on the display is desired. Confirm the change with the enterbutton.
The value will not change unless the Enter button is pushed. Pressing the menubuttonleft takes you back to the previous menu. Several parameters are locked, i.e. uneditable, when the drive is in RUN status. If you try to change the value of such a parameter the text *Locked* will appear on the display. The Variable Speed Drive must be stopped in order to edit these parameters. The parameters values can also be locked using the function in menu M6 (see Chapter Parameter lock (P6.5.2)). You can return to the Main menu anytime by pressing the menubuttonleft for 12 seconds. The basic application package includes seven applications with different sets of parameters. You will find the parameter lists in the Application Section of this manual. Once in the last parameter of a parameter group, you can move directly to the first parameter of that group by pushing the browser. See the diagram for parameter value change procedure on page 53. Note: Instead of connecting power to the Variable Speed Drive you can power up the control board from an external power source by connecting the external power source to bidirectional terminal #6 of the VW3A78201 board (see page 43) or to the corresponding +24V terminal on any other option board. This voltage is high enough for you to set parameter values or to keep the fieldbus active.
READY Keypad
Input signals
P1 P8
READY READY
READY
Parameters
M2
Keypad
G2.1
Keypad
G1 G8
READY
Basic parameters
P2.1.1
Keypad
P1 P18
READY
Min Frequency
13.95 Hz
P2.1.1
Keypad
Min Frequency
P2.1.1
enter
Keypad
13.95 Hz
Min Frequency
14.45 Hz
53
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.3.3
In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and change the direction of the motor. Enter the submenu level with the Menu button right. NOTE! There are some special functions that can be performed when in the M3 menu: button pushed Select the keypad as the active control place by keeping the down for 3 seconds when the motor is running. The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad. button pushed Select the keypad as the active control place by keeping the down for 3 seconds when the motor is stopped. The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad. Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by keeping the
enter
stop start
Note that if you are in any other than M3 menu these functions will not work. If you are in some other than M3 menu and try to start the motor by pressing the START button when the keypad is not selected as the active control place you will get an error message Keypad Control NOT ACTIVE.
Change the control place by entering the edit mode with the Menu button right. The options can then be browsed through with the browser. Select the desired control place with the enterbutton. See the diagram on the next page. See also 7.3.3 above.
ST O P
I / O te rm
RE A D Y
I / O te rm
STOP
READ Y
I/ O te rm
ST OP
READ Y
M3 Ke y p a d c o n t r o l
P1
ST O P
I/ O t e rm
P4
RE A D Y
I /O Remote
STOP
K eyp ad
I/O Remote
READ Y
P3.1 C o n t ro l P l a c e
e nt e r
K eyp ad
K e y pad
54
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display. When a fault brings the Variable Speed Drive to a stop, the location indication F1, the fault code, a short description of the fault and the fault type symbol (see Chapter 7.3.4.1) will appear on the display. In addition, the indication FAULT or ALARM (see Figure 7-1 or Chapter 7.1.1) is displayed and, in case of a FAULT, the redled on the keypad starts to blink. If several faults occur simultaneously, the list of active faults can be browsed with the browser. The memory of active faults can store the maximum of 10 faults in the order of appearance. The display can be cleared with the resetbutton and the read-out will return to the same state it was before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset signal from the I/O terminal. Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the drive. Normal state, no faults:
READY
M4
I/Oterm
Ac tive faults
F0
55
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
STOP
I/Oterm
FAULT
Operation hours
34:21:05
STOP
STOP
FAULT
FAULT
F1
I/Oterm
11 Output phase
T1
T13
Operations days
T1
I/O term
17
Figure 7-7. Fault display Fault type symbol A (Alarm) F (Fault) AR (Fault Autoreset) FT (Fault Trip) Table 7-2. Fault types Meaning This type of fault is a sign of an unusual operating condition. It does not cause the drive to stop, nor does it require any special actions. The 'A fault' remains in the display for about 30 seconds. An 'F fault' is a kind of fault that makes the drive stop. Actions need to be taken in order to restart the drive. If an 'AR fault' occurs the drive will also stop immediately. The fault is reset automatically and the drive tries to restart the motor. Finally, if the restart is not successful, a fault trip (FT, see below) occurs. If the drive is unable to restart the motor after an AR fault an FT fault occurs. The effect of the 'FT fault' is basically the same as that of the F fault: the drive is stopped.
56
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Overvoltage
Earth fault
Make the deceleration time longer. Use brake chopper or brake resistor (available as options up to FR10) Check motor cables and motor.
Charging switch
Reset the fault resetbuttonand restart. Should the fault re-occur, contact the distributor near to you.
6 7
System fault
- component failure - faulty operation Note exceptional fault data record, see 7.3.4.3. DC-link voltage is under the voltage limits defined in Table 4-1. most probable cause: too low a supply voltage Variable Speed Drive internal fault Input line phase is missing. Current measurement has detected that there is no current in one motor phase.
Cannot be reset from the keypad. Switch off power. DO NOT RE-CONNECT POWER! Contact your local Schneider electric sales office. If this fault appears simultaneously with Fault 1, check motor cables and motor Reset the fault resetbuttonand restart. Should the fault re-occur, contact your local Schneider electric sales office.
Undervoltage
10 11
Check supply voltage and cable. Check motor cable and motor.
57
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Fault code Fault Possible cause Correcting measures
12
Brake chopper supervision Variable Speed Drive undertemperature Variable Speed Drive overtemperature
Check brake resistor. If the resistor is ok, the chopper is faulty. Contact the distributor near to you.
13 14
Heatsink temperature is under 10C Heatsink temperature is over 90C. Overtemperature warning is issued when the heatsink temperature exceeds 85C. Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient temperature. Make sure that the switching frequency is not too high in relation to ambient temperature and motor load. Check motor. Decrease the motor load. If no motor overload exists, check the temperature model parameters.
15 16
Motor stalled Motor overtemperature Motor underload EEPROM checksum fault Counter fault Microprocessor watchdog fault
17 22
24 25
Motor stall protection has tripped. Motor overheating has been detected by Variable Speed Drive motor temperature model. Motor is overloaded. Motor underload protection has tripped. Parameter save fault faulty operation component failure Values displayed on counters are incorrect faulty operation component failure
Reset the fault resetbuttonand restart. Should the fault re-occur, contact the distributor near to you. Cancel prevention of start-up. Check motor cooling and loading Check thermistor connection (If thermistor input of the option board is not in use it has to be short circuited) Check loading. Check motor size. Contact your local Schneider electric sales office. Ensure that there is another device on the bus with the same configuration. Change control unit
26 29
Start-up of the drive has been prevented. The thermistor input of option board has detected increase of the motor temperature IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Cooling fan of the Variable Speed Drive does not start, when ON command is given Sent message not acknowledged. ATV78 Control Unit can not control
31 32 34 36
IGBT temperature (hardware) Fan cooling CAN bus communication Control unit
58
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Fault code 37 38 39 40 41 42 Fault Device Device added (same type) Device removed Device unknown IGBT temperature Encoder fault Possible cause ATV78F Power Unit and vice versa Option board or control unit changed same type of board or same power rating of drive Option board or drive added. Drive of same power rating or same type of board added. Option board removed. Drive removed. Unknown option board or drive. IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Note the exceptional Fault data record. See 7.3.4.3. Additional codes: 1 = Encoder 1 channel A is missing 2 = Encoder 1 channel B is missing 3 = Both encoder 1 channels are missing 4 = Encoder reversed Option board or control unit changed. Option board of different type or different power rating of drive. Option board or drive added. Option board of different type or drive of different power rating added. Current at the analogue input is < 4mA. control cable is broken or loose signal source has failed Digital input fault. The connection between the control keypad and the Variable Speed Drive is broken. The data connection between the fieldbus Master and the fieldbus board is broken Defective option board or slot Temperature limit values set for the PT100 board parameters have been exceeded Correcting measures Reset Reset Note: No fault time data record! Reset Note: No fault time data record! Contact your local Schneider electric sales office. Check loading. Check motor size. Check encoder channel connections. Check the encoder board.
43
Device changed (different type) Device added (different type) Analogue input Iin < 4mA (sel. signal range 4 to 20 mA) External fault Keypad communication fault Fieldbus fault
44
50
Reset Note: No fault time data record! Note: Application parameter values restored to default. Reset Note: No fault time data record! Note: Application parameter values restored to default. Check the current loop circuitry.
51 52 53
Check keypad connection and possible keypad cable. Check installation. If installation is correct contact your local Schneider electric sales office. Check board and slot. Contact your local Schneider electric sales office. Find the cause of temperature rise
54 56
59
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
Real time record If real time is set to run on the Variable Speed Drive the data items T1 and T2 will appear as follows: T.1 Counted operation days yyyy-mm-dd T.2 Counted operation hours hh:mm:ss, sss
60
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.3.5
The Fault history menu can be entered from the Main menu by pushing the Menu button right when the location indication M5 is visible on the first line of the keypad display. All faults are stored in the Fault history menu in which you can browse through them using the browser. Additionally, the Fault time data record pages (see Chapter 7.3.4.3) are accessible at each fault. You can return to the previous menu anytime by pushing the menubuttonleft. The memory of the Variable Speed Drive can store a maximum of 30 faults in the order of appearance. The number of faults currently in the fault history is shown on the valueline of the main page (H1 H#). The order of the faults is indicated by the location in the upper left corner of the display. The latest fault carries the indication F5.1, the second latest F5.2 etc. If there are 30 uncleared faults in the memory the next occurring fault will erase the oldest from the memory. Pressing the enterbutton for about 2 to 3 seconds resets the whole fault history. Then, the symbol H# will change to 0.
R EADY
I/O t erm I/ O t er m
R EA DY
5 ChargeSwitch
Operation hours
13:25: 43
READY
READY
READY
F5
I/O term
Fau lt h is tory
H5.1
I/Oterm
11 Output phase
T5.1.1
I/Ot erm
Op eration days
H1 H 3
PUSH
Figure 7-8. Fault history menu 7.3.6
T1 T7
enter
17
to reset
The System menu can be entered from the main menu by pushing the Menu button right when the location indication M6 is visible on the display. The controls associated with the general use of the Variable Speed Drive, such as application selection, customised parameter sets or information about the hardware and software are located under the System menu. The number of submenus and subpages is shown with the symbol S (or P) on the valueline. On page 62 you will find a list of the functions available in the System menu.
61
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Functions in the System menu
Code S6.1 Function Min Max Unit Default English Cust Selections English Deutsch Italiano Franais Basic Application Standard Application Local/Remote control Appl. Multi-Step Application PID Control Application Multi-Purpose Control Appl. Pump and Fan Control Appl. Store set 1 Load set 1 Store set 2 Load set 2 Load factory defaults All parameters All parameters All but motor parameters Application parameters Yes No
Language selection
S6.2
Application selection
Basic Application
S6.3
Copy parameters Parameter sets Load up to keypad Load down from keypad Parameter backup Parameter comparison Security Password Parameter locko Start-up wizard Multimonitoring items Keypad settings Default page Default page /Operate menu 0 65535 Timeout time 0 31 Contrast Always 65535 Backlight time Hardware settings Internal brake resistor Fan control HMI acknowledge. timeout HMI number of retries
200 1 5000 10 ms No
S6.3.1
S6.3.2 S6.3.3 P6.3.4 S6.4 S6.5 S6.5.1 P6.5.2 S6.5.3 S6.5.4 S6.6 P6.6.1 P6.6.2 P6.6.3 P6.6.4 P6.6.5 S6.7 P6.7.1 P6.7.2 P6.7.3 P6.7.4
0=Not used Change Enabled Change Disabled No Yes Change Enabled Change Disabled
s min
30 18 10
62
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
S6.8 S6.8.1
System information Total counters MWH counter Power On day counter Power on hours counter
kWh
hh:mm:ss
Trip counters MWH counter Clear MWH trip T6.8.2.2 counter Operating days T6.8.2.3 trip counter Operating hours T6.8.2.4 trip counter Clear operating T6.8.2.5 time counter S6.8.3 Software info Software S6.8.3.1 package System software S6.8.3.2 version Firmware S6.8.3.3 interface S6.8.3.4 System load S6.8.4 Applications Name of S6.8.4.# application D6.8.4.#.1 Application ID Applications: D6.8.4.#.2 Version Applications: D6.8.4.#.3 Firmware interface S6.8.5 Hardware I6.8.5.1 Info:Unit power I6.8.5.2 Info: Unit voltage Info: Brake I6.8.5.3 chopper Info: Brake I6.8.5.4 resistor S6.8.6 Expander boards Table 7-5. System menu functions
kWh
hh:mm:ss
kW V
63
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
System Menu
M6
I/Ot erm
S6.1
I/Oterm
Language
S1 S11
R E A DY I/Ot erm
English
R EADY I/Oterm
S6.1
L anguage
S6.1
enter
Langue
English
Figure 7-9. Selection of language
Francais
M6
I/Oterm
System Menu
S6.2
I/Oterm
Application
S1 S11
STOP READY
Standard
STOP READY
S6.2
I/Oterm
Application
S6.2
enter
I/Oterm
Application
Standard
Figure 7-10. Change of application
Multi-step
64
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
READY
READY
S6.3.1
I/O term
S6.3.1
I/Oterm
enter
CONFI RM
Parameter sets
Parameter sets
Sele ct
RE ADY
LoadFactDef
READY
CANCEL
S6.3.1 I/Oterm
S6.3.1 I/Oterm
Parameter sets
Parameter sets
Wait...
OK
65
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Upload parameters to keypad (To keypad, S6.3.2) This function uploads all existing parameter groups to the keypad provided that the drive is stopped. Enter the To keypad page (S6.3.2) from the Parameter copy menu. Push the Menu button right to enter the edit mode. Use the browser to select the option All parameters and press the enterbutton. Wait until 'OK' appears on the display.
RE ADY
READY
READY
S6.3
I/Oter m
Cop y Parameters
S6.3.2
I/Oter m
Up to keypad
S6.3.2
I/Oterm
e n te r
Up to keypad
P1 P4
RE ADY
Select
READY
All param.
S6.3.2
I/Oter m
Up to keypad
S6.3.2
I/Oter m
Up to keypad
Wait...
OK
Figure 7-12. Parameter copy to keypad Download parameters to drive (From keypad, S6.3.3) This function downloads one or all parameter groups uploaded to the keypad to a drive provided that the drive is in STOP status. Enter the From keypad page (S6.3.3) from the Parameter copy menu. Push the Menu button right to enter the edit mode. Use the browser to select either the option All parameters or Application parameters and press the enterbutton. Wait until 'OK' appears on the display. The procedure to download the parameters from keypad to drive is similar to that of from drive to keypad. See page 65.
66
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Automatic parameter backup (P6.3.4) On this page you can activate or inactivate the parameter backup function. Enter the edit mode by pressing the Menu button right. Choose Yes or No with the browser. When the Parameter backup function is activated ATV78 control keypad makes a copy of the parameters of the presently used application. When applications are changed, you will be asked if you wish the parameters of the new application to be uploaded to the keypad. For this to happen, push the enterbutton. If you wish to keep the copy of the parameters of the previously used application saved in the keypad push any other button. Now you will be able to download these parameters to the drive following the instructions given in chapter 7.3.6.3. If you want the parameters of the new application to be automatically uploaded to the keypad you have to do this for the parameters of the new application once on page 6.3.2 as instructed. Otherwise the panel will always ask for the permission to upload the parameters. Note: Parameters saved in the parameter settings on page S6.3.1 will be deleted when applications are changed. If you want to transfer the parameters from one application to another you have to upload them first to the keypad.
S6.4
I/Oterm
ParamComparison
S6.4.1 I/Oterm
S et1
C1
C3
OR
0
READY READY
S6.4.1 I/Oterm
S6.4.1.1 I/Oterm
Set1
P2.1.2= 50.0
P1
I/Oterm
P6
REA DY
20.0 Hz
EDIT VALUE
P2.1.2= 50.0
20.0 Hz
Figure 7-13. Parameter comparison
enter
CONFIRM CHANGE
67
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
S6.5.1
I/O term
Pas swor d
S6.5.1
I/O term
Pas sword
S6.5. 1
I/Oterm
enter
OR:
Password
Not in use
Figure 7-14. Password setting
00
Note! Store the password in a secure location! No changes can be made unless a valid password is entered! Parameter lock (P6.5.2) This function allows the user to prohibit changes to the parameters. If the parameter lock is activated the text *locked* will appear on the display if you try to edit a parameter value. NOTE: This function does not prevent unauthorised editing of parameter values. Enter the edit mode by pushing the Menu button right. Use the browser to change the parameter lock status. Accept the change with the enterbutton or return to the previous level with the menubuttonleft.
RE A D Y
READ Y
READ Y
M6
I/O term
S 6.5
I/Oterm
S6.5.2
I/Oterm
System Menu
Security
Parameter Loc k
S1 S 9
RE A D Y
P1 P4
READ Y
ChangeEnab le
S6.5.2
I/O term
S 6.5.2
en ter
I/Oterm
Parameter Lock
ChangeDisabl
68
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Start-up Wizard (P6.5.3) The Start-up Wizard is a feature of the control keypad to facilitate the commissioning of the Variable Speed Drive. If selected active, the Start-up Wizard prompts the operator for the language and application of his/her choice and then returns to the starting menu or page. Set the Start-up Wizard active in the following way: In the System Menu, find page P6.5.3. Press the Menu button right once to reach the edit mode. Use the browser to set value Yes and confirm the selection with the enterbutton. If you want to deactivate the function follow the same procedure and give the parameter value No.
READ Y READY READ Y
P6.5.3
I/O ter m
P6.5.3
I/O term
P6.5.3
I/O term
St ar tu p wiz ard
Startup wizard
enter
CONFIRM CANCEL
No
No
Yes
Figure 7-16. Activation of Start-up wizard Multimonitoring items (P6.5.4) Telemecanique alpha-numeric keypad features a display where you can monitor even three actual values at the same time (see chapter 7.3.1 and chapter Monitoring values in the manual of the application you are using). On page P6.5.4 of the System Menu you can define if it is possible for the operator to replace the values monitored with other values. See below.
RE A D Y
READ Y
RE A D Y
P6.5.4
I/O term
P6.5.4
I/Oterm
P6.5.4
enter
I/O term
ChangeEnable
ChangeEnable
Chan geDisable
REA D Y
READY
S 6.6
I/O ter m
P6.6.1
I/O term
Keypad settings
Default page
P1 P5
Figure 7-18. Keypad settings submenu
0.
69
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Default page (P6.6.1) Here you can set the location (page) to which the display automatically moves as the Timeout time (see page 70) has expired or as the power is switched on to the keypad. If the Default Page value is 0 the function is not activated, i.e. the last displayed page remains on the keypad display. Press the Menu button right once to enter the edit mode. Change the number of the Main menu with the Browser buttons. Pressing the Menu button right once again makes you able to edit the number of the submenu/page. If the page you want to move to by default is at the third level repeat the procedure. Confirm the new default page value with the Enter button. You can return to the previous step anytime by pushing the Menu button left.
R E AD Y RE ADY REA DY
P6.6.1I/Oter m
P6.6.1 I/Oter m
P6.6.1I/Oterm
enter
Defau lt page
Defau lt page
Default page
0.
Figure 7-19. Default page function
0.
1.
Default page in the operating menu (P6.6.2) Here you can set the location (page) in the Operating menu (in special applications only) to which the display automatically moves as the set Timeout time (see below) has expired or as the power is switched on to the keypad. See setting of Default page above. Timeout time (P6.6.3) The Timeout time setting defines the time after which the keypad display returns to the Default page (P6.6.1) see above. Move to the Edit menu by pressing the Menu button right. Set the timeout time you want and confirm the change with the Enter button. You can return to the previous step anytime by pushing the menubuttonleft.
READY READY READY
P6.6.3
I/O term
Timeout time
P6.6.3
I/Oter m
Timeout time
P6.6.3
I/Oterm
Timeout time
e n ter
90 s
Figure 7-20. Timeout time setting
90 s.
60 s.
Note: If the Default page value is 0 the Timeout time setting has no effect. Contrast adjustment (P6.6.4) In case the display is unclear you can adjust its contrast through the same procedure as that for the timeout time setting (see page 70). Backlight time (P6.6.5) Giving a value for the Backlight time, you can determine how long the backlight stays on before going out. You can select here any time between 1 and 65535 minutes or 'Forever'. For the value setting procedure seeTimeout time (P6.6.3).
70
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
READY
READY
READY
P6.7.2
I/O ter m
P6.7.2
I/O ter m
P6.7.2
enter
I/Oterm
Fan control
Fan control
Fan control
Con tinuo us
Con tinuous
Temperatu re
71
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
HMI acknowledge timeout (P6.7.3) This function allows the user to change the timeout of the HMI acknowledgement time. Note! If the Variable Speed Drive has been connected to the PC with a normal cable, the default values of parametres 6.7.3 and 6.7.4 (200 and 5) must not be changed. If the Variable Speed Drive has been connected to the PC via a modem and there is delay in transferring messages, the value of par. 6.7.3 must be set according to the delay as follows: Example: Transfer delay between the Variable Speed Drive and the PC = 600 ms The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay) The corresponding setting shall be entered in the [Misc]-part of the file PCsoftware.ini: Retries = 5 AckTimeOut = 1200 TimeOut = 6000
It must also be considered that intervals shorter than the AckTimeOut-time cannot be used in PC software monitoring. Enter the edit mode by pushing the Menu button right. Use the browser to change the acknowledgement time. Accept the change with the enterbutton or return to the previous level with the menubuttonleft.
READ Y
READY
P6.7.3
I/O ter m
P6.7.3
I/O term
enter
200ms
200ms
Figure 7-22. HMI acknowledge timeout Number of retries to receive HMI acknowledgement (P6.7.4) With this parameter you can set the number of times the drive will try receive acknowledgement if this does not succeed within the acknowledgement time (P6.7.3) or if the received acknowledgement is faulty. Enter the edit mode by pushing the Menu button right. The present value shown starts to blink. Use the browser to change the amount of retries. Accept the change with the enterbutton or return to the previous level with the menubuttonleft. See Figure 7-22 for the procedure of changing the value.
72
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
STOP
READY
READY
S6.8.2
P6.8.2.5
I/Oterm
P6.8.2.5
I/Oterm
Tr ip c o unte r s
C lr Optime cntr
T1 T5
STOP READY
Not reset
STOP READY
Not reset
STOP READY
P6.8.2.5
I/O term
P6.8.2.5 I/Oterm
enter
P6.8.2.5
I/Oterm
C lr Optim e cnt r
C lr Optime cntr
Reset
Figure 7-23. Counter reset
Reset
Not reset
73
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Software (S6.8.3) The Software information page includes information on the following Variable Speed Drive software related topics: Page Content 6.8.3.1 Software package 6.8.3.2 System software version 6.8.3.3 Firmware interface 6.8.3.4 System load Table 7-8. Software information pages Applications (S6.8.4) At location S6.8.4 you can find the Applications submenu containing information about not only the application currently in use but also all other applications loaded into the Variable Speed Drive. The information available is: Page Content Name of application 6.8.4.# 6.8.4.#.1 Application ID 6.8.4.#.2 Version 6.8.4.#.3 Firmware interface Table 7-9. Applications information pages
RE ADY
I / Oterm I/ Ot e rm
READY
Standard
D1 D3
READY
Versio n
2. 01
RE ADY
R EADY
S6.8.4
I/Oter m
A6. .4.1 8
I/Oterm
A1
A7
Basic
D1
D3
Application id
A6. .4.1.1 8
I/Oter m
Figure 7-24. Applications info page In the Applications information page, push the Menu button right to enter the Application pages of which there are as many as there are applications loaded into the Variable Speed Drive. Locate the application you want information about with the browser and then enter the Information pages with the Menu button right. Use again the Browser buttons to see the different pages.
74
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
Hardware (S6.8.5) The Hardware information page provides information on the following hardware-related topics: Page Content 6.8.5.1 Nominal power of the unit 6.8.5.2 Nominal voltage of the unit 6.8.5.3 Brake chopper 6.8.5.4 Brake resistor Table 7-10. Hardware information pages Expander boards (S6.8.6) In the Expander boards pages you find information about the basic and option boards connected to the control board (see Chapter 6.2). You can check the status of each board slot by entering the Expander boards page with the Menu button right and using the browser to choose the board whose status you wish to check. Push the Menu button right again to display the status of the board. The keypad will also display the program version of the respective board when you push either one of the browser. If no board is connected to the slot the text 'no board' will be shown. If a board is connected to a slot but the connection is somehow lost the text 'no conn.' is displayed. See Chapter 6.2 and Figure 6-15 and 6-16 for more information. For more information on the expander board-related parameters, see Chapter 7.3.7.
READY
I/Oterm I / O t erm
R EADY
B:VW3A78306 VW3A78202
E1 E2
READY
10001.0
E6.8.6.1.1
RE AD Y
I/O ter m
RE AD Y
S6.8.6
I/O ter m
Expander bo ards
E1 E5
I/O term
E1 E2
State
Run
Figure 7-25. Expander board information menus Debug menu (S6.8.7) This menu is meant for advanced users and application designers. Contact factory for any assistance needed.
75
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Control keypad
7.3.7 Expander board menu (M7)
The Expander board menu makes it possible for the user 1) to see what expander boards are connected to the control board and 2) to reach and edit the parameters associated with the expander board. Enter the following menu level (G#) with the Menu button right. At this level, you can browse through slots (see page 40) A to E with the browser to see what expander boards are connected. On the lowermost line of the display you also see the number of parameters associated with the board. You can view and edit the parameter values in the same way as described in chapter 7.3.2. See Table 7-11 and Figure 7-26. Expander board parameters
Code
P7.1.1.1 P7.1.1.2 P7.1.1.3
Parameter
AI1 mode AI2 mode AO1 mode
Min
1 1 1
Max
5 5 4
Default
3 1 1
Cust
Selections 1=020 mA 2=420 mA 3=010 V 4=210 V 5=10+10 V See P7.1.1.1 1=020 mA 2=420 mA 3=010 V 4=210 V
R E A DY
D:VW3A78307
Monitor
G1
RE ADY
G2
READY
V1
V2
RE ADY
M7
I/Oter m
G7.3
I/Oterm
G7.3.1 I/Oterm
Expander boards
G1
G7.3.1.1I/Oter m
G5
C:VW3A78306
Paramet ers
G1
G7.3.1.1 I/Oterm
G2
READY
P1 P 4
CHANG E VA L U E
enter
RE ADY
Slave address
Slave address
126
R E A DY I / Ot erm
126
CONFI RM CH A N GE
Baud rate
Au to
Figure 7-26. Expander board information menu
76
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Commissioning 8. COMMISSIONING
8.1 Safety
Before commissioning, note the following directions and warnings: 1 Internal components and circuit boards of the Variable Speed Drive (except for the galvanically isolated I/O terminals) are live when ATV78 is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The motor terminals U, V, W and the DC-link/brake resistor terminals /+ are live when ATV78 is connected to mains, even if the motor is not running. The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when ATV78 is disconnected from mains. Do not make any connections with the Variable Speed Drive connected to the mains. After having disconnected the Variable Speed Drive from the mains, wait until the fan stops and the indicators on the keypad go out (if no keypad is attached see the indicator through the keypad base). Wait 5 more minutes before doing any work on ATV78 connections. Do not even open the cover before this time has expired. Before connecting the Variable Speed Drive to mains make sure that the ATV78 front cover is closed. When run ning, the side of converter FR8 is burning hot. Do not touch with hands! When running, the back of Variable Speed Drive FR6 is burning hot. Therefore it MUST NOT be mounted onto a surface which is not fireproof.
4 5
6 7
HOT SURFACE
that the common inputs of digital input groups are connected to +24V or ground of the I/O terminal or the external supply.
3 4 5 6
Check the quality and quantity of cooling air (chapter 5.2 and Table 5-7). Check the inside of the Variable Speed Drive for condensation. Check that all Start/Stop switches connected to the I/O terminals are in Stop-position. Connect the Variable Speed Drive to mains.
77
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Commissioning 7
Set the parameters of group 1 (See ATV78 programming manual (CD)) according to the requirements of your application. At least the following parameters should be set: motor nominal voltage motor nominal frequency motor nominal speed motor nominal current
You will find the values needed for the parameters on the motor rating plate.
Perform run test without motor Perform either Test A or Test B: A Controls from the I/O terminals:
a) Turn the Start/Stop switch to ON position. b) Change the frequency reference (potentiometer) c) Check in the Monitoring menu M1 that the value of Output frequency changes according to the change
of frequency reference.
a) Change the control from the I/O terminals to the keypad as advised in Chapter 7.3.3.1. b) Push the startbutton on the keypad
change the
start
c) Move over to the Keypad control menu (M3) and Keypad Reference submenu (Chapter 7.3.3.2) and
frequency
d) Check in the Monitoring menu M1 that the value of Output frequency changes according to the change
of frequency reference.
stop
Run the start-up tests without the motor being connected to the process, if possible. If this is not possible, secure the safety of each test prior to running it. Inform your co-workers of the tests.
a) Switch off the supply voltage and wait up until the drive has stopped as advised at Chapter 8.1, step
5.
b) Connect the motor cable to the motor and to the motor cable terminals of the Variable Speed Drive. c) See to that all Start/Stop switches are in Stop positions. d) Switch the mains ON e) Repeat test 8A or 8B. 10 Connect the motor to the process (if the startup test was run without the motor being connected) a) Before running the tests, make sure that this can be done safely. b) Inform your co-workers of the tests.
78
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
79
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
When a fault is detected by the Variable Speed Drive control electronics, the drive is stopped and the symbol F together with the ordinal number of the fault, the fault code and a short fault description appear on the display. The fault can be reset with the resetbutton on the control keypad or via the I/O terminal. The faults are stored in the Fault history menu (M5) which can be browsed. The different fault codes you will find in the table below. The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The items written in white on black background present faults for which you can program different responses in the application. See parameter group Protections. Note: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display. Fault code 1 Fault Overcurrent Possible cause Variable Speed Drive has detected too high a current (>4*In) in the motor cable: sudden heavy load increase short circuit in motor cables unsuitable motor The DC-link voltage has exceeded the limits defined in Table 4-1. too short a deceleration time high overvoltage spikes in supply Current measurement has detected that the sum of motor phase current is not zero. insulation failure in cables or motor The charging switch is open, when the START command has been given. faulty operation component failure Stop signal has been given from the option board. Various causes, e.g. defective component Brake resistor short circuit or overload Correcting measures Check loading. Check motor. Check cables.
Overvoltage
Make the deceleration time longer. Use brake chopper or brake resistor (available as options) Check motor cables and motor.
Earth fault
Charging switch
Reset the fault resetbuttonand restart. Should the fault re-occur, contact the distributor near to you.
6 7
System fault
Cannot be reset from the keypad. Switch off power. DO NOT RE-CONNECT POWER! Contact factory. If this fault appears simultaneously with Fault 1, check motor cables and motor Reset the fault resetbuttonand - component failure restart. - faulty operation Note exceptional fault data record, Should the fault re-occur, contact the distributor near to you. see 7.3.4.3.
80
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Fault tracing
Undervoltage
DC-link voltage is under the voltage limits defined in Table 4-1. most probable cause: too low a supply voltage Variable Speed Drive internal fault
10 11 12
Input line Input line phase is missing. supervision Output phase Current measurement has detected supervision that there is no current in one motor phase. Brake no brake resistor installed chopper brake resistor is broken supervision brake chopper failure Variable Speed Drive undertemperature Variable Speed Drive overtemperatu re Heatsink temperature is under 10C
In case of temporary supply voltage break reset the faultresetbuttonand restart the Variable Speed Drive. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact the distributor near to you. Check supply voltage and cable. Check motor cable and motor. Check brake resistor. If the resistor is ok, the chopper is faulty. Contact the distributor near to you.
13
14
Heatsink temperature is over 90C. Overtemperature warning is issued when the heatsink temperature exceeds 85C.
15 16
17 22
24 25
26 29
Motor stall protection has tripped. Motor overheating has been detected by Variable Speed Drive motor temperature model. Motor is overloaded. Motor Motor underload protection has underload tripped. Parameter save fault EEPROM checksum faulty operation fault component failure Counter fault Values displayed on counters are incorrect Microprocess Reset the fault resetbuttonand faulty operation or watchdog component failure restart. fault Should the fault re-occur, contact the distributor near to you. Start-up Start-up of the drive has been Cancel prevention of start-up. prevented prevented. Thermistor The thermistor input of option board Check motor cooling and loading fault has detected increase of the motor Check thermistor connection temperature (If thermistor input of the option board is not in use it has to be short circuited)
Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient temperature. Make sure that the switching frequency is not too high in relation to ambient temperature and motor load. Check motor. Decrease the motor load. If no motor overload exists, check the temperature model parameters.
81
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Fault tracing
31 32 34 36 37 38 39 40 41 42 43
IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Cooling fan of the Variable Speed Drive does not start, when ON command is given CAN bus Sent message not acknowledged. communication Control unit Device changed (same type) Device added (same type) Device removed Device unknown IGBT temperature
Check loading. Check motor size. Contact the distributor near to you.
Ensure that there is another device on the bus with the same configuration. ATV78 Control Unit can not control Change control unit ATV78F Power Unit and vice versa Option board or control unit changed. Reset Same type of board or same power Note: No fault time data record! rating of drive. Option board or drive added. Reset Drive of same power rating or same Note: No fault time data record! type of board added. Option board removed. Reset Drive removed. Note: No fault time data record! Unknown option board or drive. Contact the distributor near to you. Check loading. Check motor size. Set the deceleration time longer. Use external brake resistor. Check encoder channel connections. Check the encoder board.
44
IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Brake resistor Brake resistor overtemperature overtemperatur protection has detected too heavy e braking Encoder fault Note the exceptional Fault data record. See 7.3.4.3. Additional codes: 1 = Encoder 1 channel A is missing 2 = Encoder 1 channel B is missing 3 = Both encoder 1 channels are missing 4 = Encoder reversed Device Option board or control unit changed. changed Option board of different type or (different type) different power rating of drive.
45
50
51 52
Reset Note: No fault time data record! Note: Application parameter values restored to default. Device added Option board or drive added. Reset (different type) Option board of different type or drive Note: No fault time data record! of different power rating added. Note: Application parameter values restored to default. Analogue input Current at the analogue input is < Check the current loop circuitry. Iin < 4mA (sel. 4mA. signal range 4 control cable is broken or loose to 20 mA) signal source has failed External fault Digital input fault. Keypad The connection between the control Check keypad connection and communication keypad and the Variable Speed Drive possible keypad cable. fault is broken.
82
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Fault tracing
53 54 56
The data connection between the Check installation. fieldbus Master and the fieldbus board If installation is correct contact the is broken nearest Telemecanique distributor. Check board and slot. Contact the nearest Telemecanique distributor. Temperature limit values set for the Find the cause of temperature rise PT100 board parameters have been exceeded
83
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
DIA2ED3031101 FR 2003-11
www.barr-thorp.com