Beruflich Dokumente
Kultur Dokumente
SYMBOL DESCRIPTION
FLUORESCENT LIGHT FITTING
GENERAL NOTES
1. 2. WALLMOUNTED LIGHT FITTING PENDANT LIGHT WALL DOWNLIGHT DOWN LIGHT EXIT SIGN AREA LIGHT 5. 6. 7. 8. 4. 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE SPECIFICATION AND SCHEDULE THE ELECTRICAL SERVICES WORKS SHALL BE COORDINATED WITH ALL OTHER TRADES AND SUIT THE SCHEDULING PLAN THE ELECTRICAL INSTALLATION SHALL COMPLY WITH THE CURRENT EDITION OF NFPA 70(NATIONAL ELECTRICAL CODE) WHERE PRACTICAL ALL EXISITING CEILING AND WALL MOUNTED LUMINAIRES SHALL BE REMOVED AND REPLACED BY NEW FITTINGS AS SHOWN (UNO) ALL EXISITNG ILLUMINATED EXIT SIGNS SHALL BE REMOVED AND REPLACED BY NEW FITTINGS AS SHOWN ALL EXISITNG LIGHT SWITCHES SHALL BE REMOVED AND REPLACED BY NEW SWITCHES ALL EXISITING POWER RECEPTACLES SHALL BE REMOVED AND REPLACED BY NEW RECEPTACLES THE EXISITING VOICE AND DATA COMMUNICATION OUTLETS AND WIRING SHALL BE REMOVED AND REPLACED BY A NEW STRUCTURED CABLING SYSTEM AS DETAILED. 9. 10. 11. 12. THE EXISITNG NURSE CALL SYSTEM SHALL BE REMOVED AND REPLACED BY A NEW NURSE CALL SYSTEM AS DETAILED EXISTING SERVICES TO BUILDING 12 TO BE RETAINED AS IS EXISITNG RADIO COMMUNICATIONS SYSTEM SERVING BUILDINGS 3, 5 & 8 TO BE RETAINED AS IS. ALL EXISTING BATHROOM AND TOILET EXHAUST FAN CONTROLLERS TO BE REPLACED BY ELECTRONIC RUN-ON 13. TIMERS ACTIVATED BY LIGHT SWITCH. ALL EXISTING CEILING FANS TO BE REMOVED AND/OR REPLACED AS DETAILED ON THE MECHANICAL DRAWINGS. REPLACE ALL FAN SPEED CONTROLLERS TO SUIT. 14. ALL EXISTING SWITCHBOARDS TO HAVE CIRCUIT BREAKERS AND CHASSIS REPLACED AND TO HAVE MAIN SWITCH ADDED.
CLOCK OUTLET CEILING FAN NEW REMOVE EXISTING RELOCATE NHD F HAND DRYER SWITCH / FAN SWITCH SWITCHBOARD/PANEL BOARD SURGERY LIGHTING BATTERY UNIT LIGHTING SWITCH PANEL
N R E RL
PE
PHOTOELECTRIC SENSOR
RECEPTACLES
SYMBOL DESCRIPTION
SINGLE RECEPTACLE DUPLEX RECEPTACLE G F B S ab DUPLEX RECEPTACLE (GFCI TYPE) DOUBLE DUPLEX RECEPTACLE FLOOR MOUNTED DUPLEX RECEPTACLE BLANK PLATE SPECIAL RECEPTACLE DENOTES LOCATED ABOVE BENCH HEIGHT
FIRE
SYMBOL DESCRIPTION
NURSE CALL
SYMBOL
NCAP NC SC SCP SCC
DESCRIPTION
NURSE CALL ANNUNCIATOR PANEL NURSE CALL INDICATOR LIGHT STAFF CALL BUTTON STAFF CALL PATIENT PENDANT STAFF CALL PULL CORD
COMMUNICATIONS
SYMBOL
PABX
DESCRIPTION
EXISTING TELEPHONE FRAME TC1 PRIVATE BRANCH EXCHANGE SYSTEM MAIN COMMUNICATIONS FRAME COMMUNICATION SWITCH
2 BD
NEW DOUBLE RJ45 OUTLETS NEW COMMUNICATIONS BUILDING DISTRIBUTOR NEW PA SPEAKER
HVAC
SYMBOL
A/C
DESCRIPTION
AIR CONDITIONING UNIT COMPRESSOR AIR CONDITIONING GRILL
M
B.MEGGITT J. JOHNSON 22.09.09 22.09.09 23.04.10 23.04.10
1 0
SO SO
JJ JJ
N.T.S
H. JOSHI E.SCHMIDT
ELECTRICAL 6500080-00-E-001
1
NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND PROVIDE LIGHTNING PROTECTION TO NEW FLAGPOLE AND REINSTATE PROTECTION TO EXISTING FLAGPOLES EXISTING COMMUNICATION TOWER TO BE RETAINED ALL AREA LIGHTS TYPE AL1 UNO, LOCATED AS PER EXISTING PROVIDE NEW AREA LIGHT AND NEW UNDERGROUND DUCT FROM EXISTING AREA LIGHTS ALLOW TO REPLACE EXISTING AREA LIGHTING CIRCUIT WIRING RELOCATE EXISTING POST TOP FITTING TO SEATING AREA NEW 150kVA PACKAGED GENERATOR SET (BASE OPTION) NEW 400kVA PACKAGED GENERATOR SET (ADDITIVE BID ITEM) PROVIDE NEW PUBLIC ADDRESS SYSTEM TO MAIN ENTRY AND CORRIDOR COMPRISING OF AN AMPLIFIER IN THE PHARMACY, DESK TOP MICROPHONES (5 OFF) AND SURFACE MOUNTED SPEAKERS (5 OFF), PLUS POWER SUPPLY.
MICROPHONE IN DENTAL RECEPTION (NOTE 10) MICROPHONE IN OUT PATIENTS RECEPTION (NOTE 10) NEW BACKBONE WIRING IN SURFACE PVC DUCT ON UNDERSIDE OF ROOF SLAB. EXISTING IT MAIN SERVERS (TO BE RELOCATED) LOWER LEVEL REFER E-101, 102, 103 & 104 BUILDING 10 REFER E-151, 152, 153 & 154 BUILDING 10A
NEW SUBMAIN TO BUILDING 10 ANNEX TO BE INSTALLED THROUGH CEILING SPACE AND ACROSS ROOF ALONG SAME ROUTE AS NEW CHILLED WATER PIPEWORK, IN DUCT FIXED TO PIPE BRACKETS NEW SWITCHBOARD TO NEW ANNEX NEW IT MAIN SERVERS (UPPER LEVEL) NEW BACKBONE WIRING IN SURFACE PVC DUCT
N10A M
N10 EQ10
REFER E-051 & E-052
N6
NOTE 7 BUILDING 6 REFER E-071 & E-072 REFER E-081 & E-082 REFER E-091 & E-092
NOTE 5
BUILDING 5
M N5
REFER NOTE 3 EXISTING FRAME NEW SURFACE MOUNTED PA SPEAKER (NOTE 10) AMPLIFIER & MICROPHONE (NOTE 10) MICROPHONE IN PUBLIC HEALTH (NOTE 10) APPROXIMATE CONDUIT ROUTE (EXISTING) BUILDING 4
EQ6
N6A
BUILDING 7
BUILDING 8 BUILDING 9
BUILDING 3
MSB
NOTE 2
BUILDING 1
N3/5
N N
UPPER LEVEL
NOTE 5
BUILDING 2
N4/11
REFER E-011 & E-022 WF4 WF4
N N11A N11B
EXISTING AERIAL COMMS CABLING BETWEEN BUILDINGS 8 & 11
N N
MICROPHONE IN OUT PATIENTS ENTRY (NOTE 10) SUBMAIN TO DROP DOWN EXISTING DUCT TO MSB BELOW EXISTING MAIN SWITCHBOARD (ON LOWER LEVEL) N3A, CB3, EQ3A (UPPER LEVEL) NOTE 5 EXISTING 500kVA PAD MOUNTED TRANSFORMER EXISTING AIR COOLED CHILLERS (TO BE REPLACED) EXISTING UNDERGROUND BULK DIESEL FUEL TANK
N E N
NOTE 5
LOWER LEVEL EXISTING WATER TREATMENT PLANT (TO BE REFURBISHED) RELOCATE PANEL INSIDE NEW PUMP ENCLOSURE. EXISTING WATER SERVICES PUMP PANEL EQ3/13. PROVIDE NEW WIRING TO 2 REPLACEMENT WATER PUMPS PLUS NEW ACTUATOR VALVES (5 OFF), TRANSMITTER AND SOLENOID VALVE.
SITE PLAN
1" = 40'
B.MEGGITT
1 0A 0
ISSUED FOR CONSTRUCTION FINAL READY TO ADVERTISE SET FINAL READY TO ADVERTISE SET
JJ JJ SO
JJ JJ JJ
ELECTRICAL 6500080-00-E-002
1
N12
NOTES
1. 2. EXISTING SUBMAINS GENERALLY TO BE RETAINED. EXISTING SWITCHGEAR ON MSB TO BE REPLACED WITH NEW SUITABLE RATED EQUIPMENT.
BUILDING 12
NEW PANEL BOARDS N11A N11B
BUILDING 11
N10
N10A
N10B
EQ10
DENTAL
BUILDING 10
HOT WATER EWH3 N8 LS8 CB8
BUILDING 8
HOT WATER EWH4 N6 N6A LNDRY NEW SUBMAINS EQ6
BUILDING 6
HOT WATER EWH1 NEW PANEL BOARD NEW SUBMAINS HOT WATER EWH2 N4A N4 X-RAY NEW SUPPLY TO NEW LARGER CHILLER SETS N5
BUILDING 5
EQ4
LS4
IS2
CB4
BUILDING 4
CHILLER 1 N3 N3A CHILLER 2 EQ3A N1 EQ3 INCINERATOR WATER PUMP FUEL PUMP FAP PABX IS3D CB3 IS3L
BUILDING 3 BUILDING 1
DS
DEQ
DLS
DCB
ATS NO.2
ATS NO.1
~ ~
ELECTRICAL 6500080-00-E-003
1
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
N.T.S
H. JOSHI E. SCHMIDT
NOTES :
1. THESE ARRANGEMENTS ARE BASED ON AVAILABLE SITE DATA AND AS SUCH MAY NOT BE TOTALLY ACCURATE. THIS CONTRACTOR SHALL VERIFY ALL DETAILS AND UPDATE THE DRAWING TO REFLECT THE CORRECT ARRANGEMENTS. REMOVE EXISTING GENERATOR AND REPLACE WITH A 150kVA PACKAGED GENERATOR. REPLACE ALL EXISTING SWITCHGEAR ON HOSPITAL MAIN SWITCHBOARDS, DS, DLS, DEQ, DCB AND EQ3. SCHEDULE WORK TO SUIT DECANTING PLAN TO MINIMISE ANY INTERRUPTIONS. REMOVE CHILLERS AND ASSOCIATED PUMPS FROM DEQ SUPPLY. PROVIDE NEW 400kVA GENERATOR, NEW 1400A CIRCUIT BREAKER NEW SUBMAINS AND ATS 4 AS BASE OPTION (ADDITIVE BID ITEMS). REMOVE EXISTING MANUAL CHANGE OVER SWITCHES FOR CHILLER AND RECONNECT SUBMAINS FROM CIRCUITS DS 14 AND DS 15. REPLACE EXISTING SUBMAINS TO CHILLERS 1 AND 2 WITH 3 x 1C x 500 MCM WITH EXISTING NEUTRAL RETAINED. FIT SURGE SUPPRESSORS TO MAIN SWITCHBOARD.
2. 3.
4. 5.
6.
7. 8.
10
11
12
13
14
15
16
17
18
19
20
DLS
DEQ
3 25KA
EQUIPMENT BRANCH
DCB
3 25KA
CRITICAL BRANCH
ATS 3 ATS 1
MAIN SWITCHBOARD
KWH ATS 4 NOTE 5 16 x 1C x 600 MCM NEW SUBMAINS (NOTE 5) 8 x 1C x 350 MCM NOTE 5 1400
NOTE 7
NOTE 5
NEW 400kVA CONTAINERISED PACKAGED GENERATOR SET WITH INTEGRAL FUEL TANK (ADDITIVE BID ITEM)
6PDT SW
6PDT SW
DEQ4
DEQ5
DS14
DS15
B.MEGGITT
1 0A 0
ISSUED FOR CONSTRUCTION FINAL READY TO ADVERTISE SET FINAL READY TO ADVERTISE SET
JJ JJ SO
JJ JJ JJ
ELECTRICAL 6500080-00-E-004
1
BD5
CAT 6 UTP HORIZONTAL CABLING RJ45 CAT6 OUTLETS WIRELESS ACCESS POINTS FIELD VOICE CAT 6 UTP (SERVES BUILDINGS 5,6 & 10) FIBRE DATA
BD11
FIBRE DATA FIELD VOICE CAT 6 UTP (SERVES BUILDING 11) CAT 6 UTP HORIZONTAL CABLING RJ45 CAT6 OUTLETS WIRELESS ACCESS POINTS
BUILDING 5
BUILDING 11
BD2
CAT 6 UTP HORIZONTAL CABLING RJ45 CAT6 OUTLETS FIELD VOICE CAT 6 UTP (SERVES BUILDINGS 1,2, 3 & 4) 25 PAIR CAT3 VOICE TIE TO EACH COMMS PATCH PANEL 4 CORE OM3 50/125m MULTI-MODE FIBRE + 4 X 4 PAIR CAT 6 UTP BACKBONE TO EACH COMMS PATCH PANEL FIBRE DATA
BD9
FIBRE DATA FIELD VOICE CAT 6 UTP (SERVES BUILDINGS 7,8 & 9) 25 PAIR CAT3 VOICE TIE TO EACH COMMS PATCH PANEL CAT 6 UTP HORIZONTAL CABLING RJ45 CAT6 OUTLETS WIRELESS ACCESS POINTS
BUILDING 8
BUILDING 9
BUILDING 2
BUILDING 9
BUILDING 3
NEW EXISITNG
CD 10A
EXISITNG COPPER REPLACED TO SUIT NEW PATCH PANEL LOCATION (50 PAIR CAT 3)
BUILDING 2
REMOVE REDUNDANT WIRING, TEST SYSTEM AND UPDATE RECORD CARDS.
EXISITNG COPPER
NCAP
(LOCATION AT NURSES STATION)
BUILDING 8
EXISITNG PABX
BUILDING 7
COMMUNICATION SCHEMATIC
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
N.T.S
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-00-E-005
1
NOTES
NOTE 12
1. 2. 3. 4. 5. 6. 7. 8. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND PROVIDE NEW HAND DRYERS AS SHOWN REPLACE EXISTING LIGHT SWITCH AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER. EXHAUST FANS TO BE REPLACED. REMOVE EXISITING COMMS SWITCH AND PRESENT TO THE HOSPITAL ALL NEW LUMINAIRES TYPE SF1 UNLESS NOTED OTHERWISE REPLACE 12 LUMINAIRES IN PHARMACY WITH 9 NEW LUMINAIRES REPLACE 9 LUMINAIRES IN PUBLIC HEALTH WITH 6 NEW LUMINAIRES REPLACE 11 LUMINAIRES IN DEMONSTRATION WITH 8 NEW LUMINAIRES EMERGENCY CIRCUIT CB4/1 SUPPLIES SELECTED LUMINAIRES IN BUILDING 1 MODIFY EXISTING CIRCUIT SUPPLYING TOILET EXHAUST FANS TO SUIT NEW ROOF MOUNTED EXHAUST FAN PROVIDE 4 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO ILLUMINATE NEW ACCESS WALKWAY COMPLETE WITH NEW LOCAL SWITCH REPLACE ALL EXISITNG SURFACE MOUNTED WEATHER RESISTANT LUMINAIRES WITH NEW TYPE SF12 FITTINGS (16 OFF)
2
N4/9 WF1
4
N1/1 WF1
6
LS4/3 NOTE 3
G
NOTE 6
WF3 EM3
N
MALE WC
N1/1
9 ONLY FITTINGS
PHARMACY
N EM3
EM3
N
FEMALE WC
NHD
F
N1/3 6 ONLY FITTINGS
PUBLIC HEALTH
N1
STORE
SF2
OFFICE
EXISTING COMMUNICATION SWITCH (NOTE 4) WF1 EHD N EX1 N1/1 N4/5 REMOVE REMNANTS OF OLD EXIT LIGHT N1/1
NOTE 7 N
WAITING
EM3
D
8 ONLY FITTINGS WF5
DEMONSTRATION
EXAMINATION ROOM
N1/3
NOTE 3
F N4/9
EXAMINATION ROOM
WF1 N1/5
NOTE 8
B
N1/5
.
-
3/32" = 1'
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-01-E-011
1
NOTES
1. 2. REPLACE ALL EXISTING RECEPTACLES. REPLACE EXISTING SURFACE MOUNTED RACEWAY AND ASSOCIATED RECEPTACLES. CONNECT NEW RECEPTACLES TO ALTERNATE CIRCUITS AS EXISTING. LOCATE NEW COMMS OUTLETS ON WALL ADJACENT POWER RECEPTACLES. ALL COMMS OUTLETS TO BE SERVED FROM BUILDING 2, BD2. N1/8 & 1/10 ARE NEW.
2
N1/2
3. 4. 5.
CB4/2 2 M ab ab
MALE WC
ab ab
N1/8
PHARMACY
CB4/4 N1/10
FEMALE WC
F
N1/7
N1
STORE OFFICE
2
PUBLIC HEALTH
2 2
WAITING
D
NOTE 2 ab
2 2 ab CB4/6
2 M
EXAMINATION ROOM
ab
N1/9,11
DEMONSTRATION
ab
EXAMINATION ROOM
B
N1/6
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-01-E-012
1
NOTES
1. 2. 3. 4. 5. 6. 7. 8. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND PROVIDE NEW HAND DRYERS AS SHOWN EXISTING X-RAY VIEWERS TO BE REPLACED REPLACE EXISITING LIGHT SWITCH AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER ALL NEW LUMINAIRES TYPE SF1 UNO SAFE LIGHT CONTROLLED BY SWITCH ADJACENT DOOR. WHITE LIGHT CONTROL BY PULL CORD SWITCH EXISTING X-RAY PANELBOARD AND SUPPLY TO X-RAY EQUIPMENT TO BE RETAINED AS IS REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING AND MAKE SAFE. EMERGENCY CIRCUITS CB4/1 AND CB4/3 SUPPLY SELECTED LUMINAIRES IN BUILDING 2. ALL SF 3 FITTINGS TO BE CONNECTED TO EMERGENCY CIRCUIT CB4/5. REMOVE EXISTING AMSCO SURGICAL LUMINAIRE AND ASSOCIATED CONTROL PANEL. REMOVE EXISTING SURFACE MOUNTED FLUORESCENT LUMINAIRES. PROVIDE NEW CIRCUIT FOR NEW DARK ROOM EXHAUST FAN EF-2E. PROVIDE 3 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO ILLUMINATE NEW ACCESS WALKWAY COMPLETE WITH NEW LOCAL SWITCH
6 F
10
11
LS4/3
N4/3
N4/5
EX1
13.
E
N
WF1
EX1 R
WF1
EXAMINATION ROOM
N4/1
EX1
WF1
WF1
SF4 SF5
WF6 SF5
WF1
N4/3
D
LS4/3
WF1
LAB TECH
FRIDGE SPACE
NHD
WF2 F
WC
WF6 SF5
CORRIDOR
LS4/3
EX1 N
X-RAY NOTE ROOM
X-RAY PANELBOARD
EX1
FRIDGE SPACE
EX1 N
7
WF1
N4/1
N4/9
C
LABORATORY EM3
WF3
XRV4 (NOTE 3) XRV4 (NOTE 3) EX1 WF6 XRV2 (NOTE 3) SF3 SF3 SF3 N
CURTAIN
CURTAIN
N
FRIDGE SPACE
SC
C EM2
N4/3
SF3 N SF3 N
EMERGENCY ROOM
NC
B
R
RL
WF1 SF3
LS4/5
WF1
MEDIA STORAGE
SF2
CHEMISTRY / ADMIN
LS4/5
SF3 N SF3 N
A
EXISTING GRAVEL
N4/3
NOTE 10
NOTE 11 NOTE 8
EXISTING GRAVEL
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-02-E-021
1
NOTES
1. 2. 3. 4. 5. REPLACE ALL EXISTING RECEPTACLES. ENTIRE ELECTRICAL INSTALLATION WITHINNEW EMERGENCY ROOM TO BE NEW. ENTIRE ELECTRICAL INSTALLATION WITHIN NEW CHEMISTRY/ADMIN TO BE NEW. ENTIRE ELECTRICAL INSTALLATION WITHIN NEW BACT/PARA TO BE NEW. NEW RACEWAY TO INCLUDE RECEPTACLES AT 18" CENTRES. REMOVE EXISTING CENTRIFUGE TRANSFORMER AND WIRING. NEW PATCH PANEL TO BE HINGED 18U WALL MOUNTED PANEL WITH LOCKABLE GLASS DOOR. ALL COMMS OUTLETS TO BE SERVED FROM BD2, AND LOCATED ADJACENT POWER RECEPTACLES. RETAIN EXISTING PANEL BOARD FOR X-RAY MACHINE, AND ASSOCIATED SUBMAIN AND CIRCUITS. EXISTING AHU TO BE UPGRADED. EXISTING ELECTRICAL SUPPLY TO BE RETAINED.
6 F
10
11
6. 7. 8. 9.
CORRIDOR
10.
N4/15 CB4/12
N4/13
E
REMOVE EXISTING SURFACE MOUNTED RACEWAY 2
EXAMINATION ROOM VESTIBULE
NOTE 9
2
CONTROL ROOM
GDARK
ROOM
LAB TECH
G
FRIDGE SPACE SAFETY CABINET SPACE
2
FILM STORAGE
WC
N4/21
X-RAY ROOM
ab
FRIDGE SPACE
NOTE 4 NOTE 6
N4/17 2
NOTE 10
ab ab
ab
CB4/7 CB4/11
LABORATORY
ab
FRIDGE SPACE
NOTE 7
BD2
B
PROVIDE NEW RECEPTACLE ON SIDES OF NEW ISLAND BENCH, WIRED WITHIN FLOOR SLAB UTILISING CIRCUIT FEEDING EXISTING BENCH. ab
MEDIA STORAGE
ab ab
GLASS WASH
NOTE 3
CURTAIN
NOTE 2
2 ab ab 2 ab
A
EXISTING GRAVEL
N4/17 RETAIN EXISTING ELECTRICAL SUPPLY TO PIPET WASHER (N4/20 ) AND STILL (N4/28) EXISTING ELECTRICAL SERVICES ASSOCIATED WITH STERILISING & GLASS WASH EQUIPMENT TO BE RETAINED (EQ4/11, N4/25). CB4/23 (NEW CIRCUIT) NEW ISOLATION PANEL
EXISTING GRAVEL
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-02-E-022
1
NOTES
1. 2. 3. 4. 5. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND REMOVE EXISTING FITTING AND REPLACE WITH NEW UNITS ALL NEW LUMINAIRES TYPE SF1 UNO REPLACE EXISITING LIGHT SWITCHES AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER REPLACE 11 EXISTING LUMINAIRES IN CENTRAL SERVICE WITH 8 NEW LUMINAIRES. EMERGENCY CIRCUITS CB3/1 AND CB3/3 SUPPLY SELECTED LUMINAIRES IN BUILDING 3. NON-ESSENTIAL LUMINAIRES ON UPPER LEVEL, BUILDING 3 SUPPLIED FROM CIRCUITS N3A/1 AND N3A/3 PROVIDE 6 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO LUMINAIRE NEW ACCESS WALKWAY COMPLETE WITH NEW WALL SWITCH REPLACE ALL FLUORESCENT LAMPS IN SURGERY WITH 4' 28w T5 LAMPS (60 LAMPS PER SURGERY). MODIFY LUMINAIRE TO SUIT AND FIT NEW HINGED GASKETTED PRISMATIC FRAMED DIFFUSERS (10 PER SURGERY) EACH NEW SURGERY LIGHTING BATTERY UNITS TO BE 2kVA, 120V RATED WITH 90 MINUTE BATTERY.
12
13
14
15
6. 7. 8.
Ga
9.
WF5
STRETCHER
SF4 NOTE 2 SURGERY LIGHTING BATTERY UNIT TO BE REPLACED. (NOTE 10) EXISTING EMERGENCY LIGHTS TO BE RELOCATED. CB3/2,4
10.
F NOTE 4 SF5
FEMALE LOCKER
CLEAN-UP ROOM
NOTE 10 XRV4
G
LS4/5
SF5
C NC SC
N EX1
CORRIDOR
EM3
N TL1
SURGERY ROOM
Fa
SF5 WF1
F
LS4/3 WF1
NOTE 5
AUTOCLAVE
SF4
CENTRAL STERILE
C
NEW SURGERY ROOM
SF5
E
N4/5 EX1 N CORRIDOR N N
CURTAIN
D
WF1
SC
NC SC C R SF2
STRETCHER MEDIACAL EQUIP
NOTE 10
CLEAN-UP ROOM
RECOVERY
NOTE 2
NOTE 2 R N4/5
SF4 NOTE 2
CB3/3
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-03-E-031
1
NOTES
1. 2. REPLACE ALL EXISTING RECEPTACLES. ALL COMMS OUTLETS TO BE SERVED FROM BUILDING 2 (BD2) LOCATE NEW COMMS OUTLETS ADJACENT POWER RECEPTACLES. EXISTING ELECTRICAL SUPPLY ARRANGEMENTS TO STERALISERS TO BE RETAINED (N3A/13, EQ3/10). EXISTING ELECTRICAL SUPPLY ARRANGEMENTS TO STILL TO BE RETAINED (EQ3/11). EXISTING ISOLATED SYSTEM PANEL TO BE REPLACED.
12 H
13
14
15
3. 4. 5.
Ga
N3A/6 EXISTING EMERGENCY BATTERY UNIT TO BE REPLACED
G
2 N3A/4 IS3S/3
Fa
CB3/6 ab
ab
ab
2 NOTE 5 NOTE 3
ab
NOTE 4
IS3S
NOTE 5 NOTE 5 ab ab 2 ab ab ab
IS3D
E
EXISTING ISOLATOR POWER SYSTEM PANEL IS3L TO BE REPLACED.
IS3D/5 IS3D/3
IS3L
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-03-E-032
1
12 I
EXTENT OF EXISTING RC RAMP ABOVE
13
14
DL 53/1
15
NOTES
1. 2. 3. 4. 5. 6. 7. 8. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND REMOVE EXISTING FITTING AND REPLACE WITH NEW UNITS ALL NEW LUMINAIRES TYPE SF1 UNO REPLACE EXISITING LIGHT SWITCHES AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER REPLACE 11 EXISTING LUMINAIRES IN CENTRAL SERVICE WITH 8 NEW LUMINAIRES. EMERGENCY CIRCUITS CB3/1 AND CB3/3 SUPPLY SELECTED LUMINAIRES IN BUILDING 3. NON-ESSENTIAL LUMINAIRES ON UPPER LEVEL, BUILDING 3 SUPPLIED FROM CIRCUITS N3A/1 AND N3A/3 PROVIDE 6 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO LUMINAIRE NEW ACCESS WALKWAY COMPLETE WITH NEW WALL SWITCH REMOVE EXISTING DIESEL GENERATOR SET AND ITS ASSOCIATED DAY STORAGE TANK, RADIATOR AND EXHAUST FLUE. REPLACE LOUVRE ONCE RADIATOR IS REMOVED. PROVIDE ADDITIONAL LIGHTING TO CHILLER ENCLOSURE, EXTEND FROM EXISTING CIRCUIT. REMOVE REDUNDANT WIRING, UPDATE RECORD CARD AND TEST.
NEW STORE
STORE
SF9
H
OPEN TO ABOVE
9. 10.
EXISTING PABX
11.
Ga
PABX
SF9
SF9 N
SF9
STORE
N3/1
STORE/OFFICE
EM1
N3/3
SF9 REMOVE EXISITING BARE BATTEN FITTING AND PULL CORD SWITCH AND MAKE GOOD
SF9 SF9
Fa
REPAIR & INCINERATOR
SF9
SF9
SF8
SF8 WF4
N3/3 NEW DIESEL FUEL TRANSFER PUMP EXISTING DIESEL FUEL TRANSFER PUMP EXISTING FIRE ALARM CONTROL PANEL EXISITING DIESEL FUEL DAY TANK TO BE REMOVED
INCINERATOR
SF9
SF9
N3 SF8
WF4
STORE
SF9
SF9
EM1
MECHANICAL ROOM
SF8
WF4 EXISTING HOSPITAL MAIN SWITCHBOARD (MSB) WF4 EXISITING PAD MOUNTED TRANSFORMER WF4 WF4 N N NOTE 10 NOTE 10
SF8
N3/1
STORE
SF9
SF9 SF8
PUMP PUMP
SF2
C
DLS 3/1
DLS 3/3
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON 22.09.09 22.09.09 23.04.10 23.04.10
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-03-E-033
1
12 I
EXTENT OF EXISTING RC RAMP ABOVE
13
14
15
NOTES
1. 2. 3. 4. 5. 6. 7. 8. REPLACE ALL EXISTING RECEPTACLES. RECONNECT TO REPLACEMENT INCINERATOR. REMOVE EXISTING EMERGENCY GENERATOR. PROVIDE NEW SUPPLIES TO NEW CHILLERS. CONTRACTOR TO CONFIRM CIRCUIT NUMBER FOR THIS AREA. ALL RECEPTACLES IN PLANT ROOMS TO BE METAL CLAD INDUSTRIAL TYPE. ALL COMMS OUTLETS TO BE SERVED FROM BUIDING 2 (BD2). REMOVE EXISTING EMERGENCY GENERATOR AND ASSOCIATED EXHAUST SYSTEM AND WALL MOUNTED FUEL TANK. PROVIDE NEW CIRCUIT TO SERVE NEW FUEL TRANSFER PUMP (EQ3/5). PROVIDE NEW CIRCUIT TO SERVE STORE ROOM A/C UNIT (N3/6).
N3/6
A/C
STORE
NOTE 10
H
OPEN TO ABOVE
9. 10.
Ga
2 2
NOTE 5
2 AHU N
Fa
REPAIR & INCINERATOR
NEW FUEL TRANSFER PUMP (EQ3/5) EXISTING FUEL TRANSFER PUMP (EQ3/3)
INCINERATOR
LS/6
STORE
MECHANICAL ROOM
PUMP
NOTE 8
PUMP
PUMP
PUMP
STORE
N3/2
NEW CHILLER #1
NEW CHILLER #2
C
HOSPITAL MAIN SWITCHBOARD NEW CHILLED WATER PUMPS (DLS/9 & DLS/10) RETAIN EXISTING SUPPLY ARRANGEMENT TO NEW CHILLED WATER PUMPS (DEQ/5 & DS/13) NEW SUBMAINS IN 4" DUCT SURFACE MOUNTED TO RETAINING WALL SIMILAR TO EXISTING.
.
-
3/32" = 1'
1 0A 0
ISSUED FOR CONSTRUCTION FINAL READY TO ADVERTISE SET FINAL READY TO ADVERTISE SET
JJ JJ JJ
HJ HJ HJ
ELECTRICAL 6500080-03-E-034
1
NOTES
1. 2. 3. 4. 5. 6. 7. 8. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND EXISTING WEATHER RESISTANT FLUORESCENT FITTINGS TO BE REPLACED EXISTING X-RAY VIEWERS TO BE RETAINED REMOVE EXISITING COMMS SWITCH AND PRESENT TO THE HOSPITAL ALL NEW LUMINAIRES TYPE SF1 UNO REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING AND MAKE SAFE. EMERGENCY CIRCUITS CB4/1 AND CB4/3 SUPPLY SELECTED LUMINAIRES IN BUILDING 4. PROVIDE 4 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO LUMINAIRE NEW ACCESS WALKWAY COMPLETE WITH NEW WALL SWITCH PROVIDE NEW SUPPLY TO NEW EXHAUST FAN FROM PANEL N4.
10
11
9.
NOTE 6
N4/6
N4/2
LS4/3
N4/4
H
ENTRANCE MALL
NOTE 2 SF12
WAITING AREA
NOTE 2 SF12
WF1
EXAMINATION
EXAMINATION ROOM
EXAMINATION ROOM
Ga
NOTE 2 SF12
NOTE 2 SF12
NOTE 2
RL
BILLING RECEPTION
NOTE 2 SF1
SF1 NOTE 2
RL
EXAMINATION ROOM
NOTE 2
XRV2 (NOTE 3)
STORE HWC JANITOR STORE
N EM3
N4/2
Fa
SF1
OFFICE
SF1 NOTE 2
R
SF1
SF1 NOTE 2
WF1
WF1
STORE
SF2
N4/2
F
N4/5 LS4/3 WF1 N4/5 NOTE 9 WF1 WF1 WF1 LS4/3
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
JJ SO
HJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-04-E-041
1
NOTES
1. 2. 3. 4. 5. REPLACE ALL EXISTING RECEPTACLES. PROVIDE NEW COMMS OUTLETS ADJACENT POWER RECEPTACLES. PROVIDE NEW RECEPTACLES ON NEW WALL CONNECTED TO NEW CIRCUIT N4A/3 ALL COMMS OUTLETS TO BE SERVED FROM BUILDING 2 (CPP2) ALLOW TO RECONNECT TO NEW REPLACEMENT HOT WATER UNIT (HWU) 45kW 125A
10
11
N4/19
N4/14
N4/18
H
ENTRANCE MALL EXAMINATION ROOM EXAMINATION ROOM
2
EXAMINATION ROOM
WAITING AREA
Ga
RECEPTION
2
EXAMINATION ROOM EXAMINATION ROOM
N4A/2
M 2
BILLING RECEPTION
G
N4A
2
CORRIDOR
2
EXAMINATION ROOM
NOTE 3 2
NOTE 3
2
STORE
Fa
NOTE 3
OFFICE
HWU
HWC
CB4/12
STORE
JANITOR STORE
F
NOTE 5 N4/16
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-04-E-042
1
NOTES
1. 2. 3. 4. 5. 6. REFER DRAWING NO. 6500080-00-E-001 FOR GENERAL NOTES AND LEGEND ALL NEW LUMINAIRES TYPE SF1 UNO REPLACE EXISTING LIGHT SWITCH AND EXHAUST FAN CONTROLLER WITH A COMBINE ELECTRONIC SWITCH WITH RUN ON TIMER REMOVE EXISITING COMMS SWITCH AND PRESENT TO THE HOSPITAL PROVIDE NEW HAND DRYERS AS SHOWN REPLACE EXISTING LUMINAIRES IN THESE AREAS WITH REDUCED NUMBER OF NEW LUMINAIRES REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING EMERGENCY CIRCUIT LS4/2 SERVES SELECTED LUMINAIRES IN MEDICAL RECORDS & ADMIN OFFICES PROVIDE 4 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO ILLUMINATE NEW ACCESS WALKWAY COMPLETE WITH NEW LOCAL SWITCH PROVIDE NEW SUPPLY TO NEW AHU 'Q' FROM PANEL N5
7. 8. 9.
L
N5/5
N5/2
NOTE 6
NOTE 6
N5/4
10.
NOTE 6
A/C OFFICE
A/C
N5/4
OFFICE EXAMINATION ROOM AUDIOLOGY EXAMINATION ROOM
OFFICE
OFFICE
EM3 N NOTE 6
EXAMINATION ROOM
N5/3
AHU RECEPTION
N5/4
K
N5
N
EX1
N FEMALE WC F
WF2
N5/4
N EM3
LIBRARY
N5/2
NOTE 5
MEDICAL RECORDS
NHD
NOTE 3
EM1 N
SCREENING AREA
NOTE 6
SF4
HWC
HWC WF2
N5/1
EXISTING TELEPHONE FRAME TC1
NOTE 5 VESTIBULE
NHD
NOTE 3
MALE WC
N EM3 EX1
FHR
J
LS4/2 (NOTE 8) N4/9 N5/4 LS4/4
WF1
WF1
N5/6
CB5/4
N5/6
NOTE 6
CB4/5
NOTE 7
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-05-E-051
1
NOTES
1. 2. 3. 4. REPLACE ALL EXISTING RECEPTACLES. PROVIDE NEW COMMS OUTLETS ADJACENT POWER RECEPTACLES. REMOVE REDUDANT 3 PHASE ISOLATOR AND ASSOCIATED WIRING. NEW PATCH PANEL TO BE HINGED 18U WALL MOUNTED PANEL WITH LOCKABLE GLASS DOOR. ALLOW TO RECONNECT TO NEW REPLACEMENT EWH (15kW). EXISTING EXHAUST FANS TO BE REPLACED.
5. 6.
N5/11
N5/10
L
N5/9 F F F
OFFICE
2 ab
EXAMINATION ROOM
OFFICE
OFFICE
2 ab ab
RECEPTION
ab NOTE 3 M 2 2 2 2 2
EXAMINATION ROOM
N5
FEMALE WC
ab
N5/12
2 2
HWC
LIBRARY
N5/7
HWC
ab
ab 2 2 2
MALE WC
J
EXISTING COMMUNICATIONS FRAME TC1. REMOVE REDUNDANT WIRING AND UPDATE RECORD CARD. NEW FIRE ALARM PANEL. N5/21
2
FHR
NOTE 5
NOTE 6
N5/8
N5/15
CB4/2
N5/13
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-05-E-052
1
NOTES
1. 2. 3. 4. REFER TO DRAWING NO. 6500080-00-E-001 REFURBISH EXISTING LIGHTS WITHIN KITCHEN EXHAUST HOOD (4 OFF INCANDESCENT LAMPS) EXISTING REDUNDANT CABLING TO OLD HOT WATER UNIT TO BE MADE OFF ALL NEW LUMINAIRES TYPE SF1 UNO
N6/3
NOTE 2
N6/1
DINING ROOM
SF10
KITCHEN
SF10
SF9
SF9
N3/3
WF4
N EX1
F
SF10
SF10 SF9
LAUNDRY
SF9
JANITOR N
SF9
SF9
EX1 N
N6
N
N6/3
EX1
SF9
N WC
SF9
EX1
SF4
REFUSE
STORE
WF4
SF10
SF10
EQ6
HWC FHR
N6A
WF5
WF1 LS8/3
RD1
RD1
RD1
RD1
RD1
RD1
RD1
RD1
N6/3
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-06-E-061
1
NOTES
1. 2. REPLACE ALL EXISTING RECEPTACLES. RETAIN EXISTING SUPPLY ARRANGEMENT TO HOT WATER CYLINDER WASHING MACHINES AND DRYERS IN LAUNDRY. REMOVE REDUNDANT 3 PHASE SUPPLY TO OLD HOT WATER CYLINDER AND MAKE GOOD. RETAIN EXISTING SUPPLY ARRANGEMENT TO KITCHEN HOOD AND COOKING EQUIPMENT. ALLOW TO RECONNECT TO REPLACEMENT WASTE DISPOSERS (WD). RECONNECT EXISTING HOT WATER UNIT (EWH4 TO PANEL BOARD N6 (CURRENTLY SERVED FROM MAIN SWITCHBOARD). CONTRACTOR TO CHECK EXISTING LOAD ON BOARD N6 AND CONFIRM.
3. 4.
N6/2
N6/8
ab
DINING ROOM
ab WASHER
KITCHEN
DRYER NOTE 2
WD NOTE 3
WD WASHER
LAUNDRY
ab
N6
STORE WC REFUSE
EQ6
HWC FHR
N6A
N6/5
N6/22
N6/12
N6A/6
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-06-E-062
1
NOTES
1. 2. 3. 4. REFER TO DRAWING NO. 6500080-00-E-001 BUILDING 7 SERVED FROM PANEL BOARD IN BUILDING 8 EXISTING CEILING FANS TO BE REMOVED OR REPLACED AS PER MECHANICAL SERVICES DRAWING PROVIDE NEW SUPPLY TO NEW AHU FROM PANEL EQ3 PROVIDE NEW SUPPLY TO NEW EXTRACT FAN FROM N8 PROVIDE 3 OFF TYPE SF14 LUMINAIRES IN ROOF VOID TO ILLUMINATE NEW AIR HANDING UNIT, COMPLETE WITH LOCAL SWITCH REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING AND MAKE SAFE. EXISTING FIBRE OPTIC BACKBONE TO BE REPLACED BY NEW FIBRE AND UTP BACKBONE INSTALLED WITHIN NEW PVC DUCT.
19
20
N8/7
21
22
23
24
25
5. 6.
7.
WF10 WF10 WF10 WF10
BUILDING 6
MM LL KK
NOTE 7 N8/10
WF8 WF8
PEDIATRICS WARD
SCP
8.
WF5
WC
SC
WF5
SC
WC
SF11
NOTE 7
WF8
WF8
SCP
N8/11
EX1
LS8/3 N8/12 EXISTING FIBRE OPTIC CABLE CLIPPED TO CORRIDOR WALL REFER NOTE 8
WF1
SCP
F
SCP
F
SCP
PEDIATRICS ISOLATION F F
PEDIATRICS ISOLATION
PEDIATRICS WARD
WF8
WF8
WF8
SCP
WF8
SCP
SCP
WF1
CORRIDOR
WF1
WF8
WF8
N8/7
LS8/3
JJ
NC
NC
NC
NC
N8/13
WF9
WF9
CORRIDORWF9
WF9
WF9
WF9
EX1
GG
N8/15 LS8/3
WF8
SCP
NC SC SC
NC SC
NC
WC
SF1
WF8
F
WF5
SC
SF3 SF3
EM3
EX2
WC
CORRIDOR
WF5 SF3
NC SC
WF8
SCP
WF8
SCP
WF1
N8/16
EE
LS8/3 N8/17
WF11
UP
WF1
NEW LABOUR ROOM CURTAIN
F MATERNITY WARD
WF8
SCP
SF1
WF8
SHOWER
SCC
DELIVERY ROOM
NEW SF3
N TL1
SF3
WF5
SF3 SF3
SF3
WF5
SHOWER
SCC
WF8
SCP
WF8
SCP
LS8/3 N8/18
WF1 EX1 WF1
EM3
DD CC BB
NOTE 5
WF10 WF10 WF10 WF10 WF1
N8/7
N8/
N8/7
LS8/2
WF11
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-07-E-071
1
NOTES
1. 2. 3. 4. 5. 6. REPLACE ALL EXISTING RECEPTACLES. RECEPTACLES FED FROM SWITCHBOARDS IN BUILDING 8. REMOVE EXISTING RECEPTACLES AND ASSOCIATED WIRING FROM WALL (TO BE DEMOLISHED). RECEPTACLES IN WET AREAS TO INCORPORATE INTEGRAL GROUND FAULT INTERRUPTER. CONTRACTOR TO CONFIRM CIRCUIT NUMBER. PROVIDE POWER SUPPLY TO NEW MAGNETIC HOLD OPEN DEVICES TO NEW FIRE RATED DOORS.
19
20
21
22
23
24
25
BUILDING 6
NOTE 4
MM LL KK
N8/10,12
PEDIATRICS WARD PEDIATRICS ISOLATION N8/10 WC
NOTE 4
N8/11,13
WC
G N8/11
PEDIATRICS ISOLATION
PEDIATRICS WARD
ab NOTE 5
N8/12
N8/13
CORRIDOR
JJ
CB8/3,13
F
CORRIDOR
GG
N8/15 (NOTE 4)
CB8/2
WC
WC
CORRIDOR
N8/16,18 G N8/16 G
MATERNITY WARD
EE
UP
CURTAIN SHOWER
N8/15
N8/15,17
N8/17
SHOWER
DD CC BB
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-07-E-072
1
NOTES
1. 2. REFER TO DRAWING NO. 6500080-00-E-001 NEW HAND DRYERS EXISTING CEILING FANS TO BE REMOVED OR REPLACED AS PER MECHANICAL SERVICES DRAWING PROVIDE 4 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO ILLUMINATE NEW ACCESS WALKWAY COMPLETE WITH NEW LOCAL SWITCH PROVIDE NEW SUPPLY TO NEW AHU FROM PANEL EQ3 REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING AND MAKE SAFE. CONTRACTOR TO CONFIRM CIRCUITING ARRANGEMENTS IN CORRIDOR AND NON-WARD AREAS.
N8/9 N8/7
3.
24
WF10
25
WF10
26
WF10
27
WF10
28
WF10
29
30
4.
5. 6.
SF11 NOTE 6
LL KK
ICU
7.
WF5
SC
WC F
PRIVATE ROOM F
PRIVATE ROOM F
N8/3
WF1
EX1 WF1
WF8
SCP
WF8
SCP
N8/19
EX1
WF8
WC
WF8
SCP
WF8
SCP
WF5
SC
N8/21 N8/7
SCP
JJ
CORRIDOR
N8/3
NC
N8/9
EXISTING FIBRE OPTIC CABLE CLIPPED TO CORRIDOR WALL REFER NOTE 2
WF9
WF9
WF9
WF9
WF9
CORRIDOR
WF9
WF9
WF9
GG
EX2
LS8/2
WF1
WF9
WF9
WF9 EM3
WF9
WF9
FF
WF1 WF1
NC
NURSE STATION
NC NCAP LSP
RD1
N
SCC
EHD
TOILET
EHD
WF2
STORAGE
SHOWER
RETAIN ANTENNA FOR RADIO COMMUNICATION's ON ROOF ABOVE
RD1
SF1
DRUG ROOM
SF1
EHD
RD1
SF1
REGISTRATION ROOM
RD1
SF1
RD1
SHOWER
N8/7
SF10
BATH
DD
WF1
SF1 WF9
DOCTOR ON-CALL
WF12
RACKING
WF9
BATH
WF1 SF10
WF1
N8/8
NOTE 2
NHD
SF9 WF5
SF9
WF9
CC
WF10 WF11
LS8/2
N8/7
WF10
SF1
NOTE 2
NHD
HWC
A/C
LS8/2
RACKING
WF5
SF8 CB8
DIRTY UTILITY
SF9
SF9
CLEAN UTILITY
WF10
LS8
NURSES STORAGE
SF8
RACKING
SF8
N8 N8
SF9
SF9
OUTDOOR CONDENSER FOR NURSES STATION A/C ON ROOF ABOVE
WF11
LS8/2
AA
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-08-E-081
1
NOTES
1. 2. REPLACE ALL EXISTING RECEPTACLES. CONTRACTOR TO CONFIRM CIRCUIT ARRANGEMENT FOR NURSES STATION AND ADJACENT ROOMS. PROVIDE NEW RECEPTACLES AND ASSOCIATED WIRING TO NEW TOILET WALLS. PROVIDE NEW WEATHERPROOF RECEPTACLE IN NEW JANITORS TOILET, CONNECTED TO CIRCUIT N8/38. EXISTING HWU TO BE RETAINED (EWH 3 45kW)
24
25
26
NOTE 3
27
B
28
29
30
3. 4. 5.
LL KK
ICU
WC
PRIVATE ROOM
PRIVATE ROOM
N8/33
N8/19
N8/21
N8/19
PRIVATE ISOLATION ROOM
N8/21
N8/19
N8/19,21
WC
N8/19
JJ
N8/3,13
CORRIDOR
CORRIDOR
GG
ab 2 ab 2 ab F ab F F ab ab ab 2 2
FF
STORAGE SHOWER
N8/34
MEN'S TOILET
N8/34
NURSERY ISOLATION DRUG ROOM CLEAN-UP STATION NURSERY INCUBATOR REGISTRATION ROOM
WOMEN'S TOILET
CB8/5
N8/36
G
RACKING
G
RACKING
SHOWER
N8/33
N8/33
DD CC
BATH BATH
N8/36
DOCTOR ON-CALL
WC
UTILITY LINEN
N8/33 NOTE 5
RACKING
HWC
CB8
NURSES STORAGE
DIRTY UTILITY
CLEAN UTILITY
JANITOR'S CLOSET
A/C
LS8 N8 N8
G
RACKING
AA
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-08-E-082
1
NOTES
1. 2. REFER TO DRAWING NO. 6500080-00-E-001 EXISTING SURFACE MOUNTED COUNDIT ALONG CORRIDOR WALKWAY TO BUIDING 12 TO BE RETAINED AS IS REMOVE EXISITING COMMS SWITCH AND PRESENT TO THE HOSPITAL EXISTING LUMINAIRES TO BE RETAINED IN TRAINING ROOM ALL CIRCUITS ORIGINATE FROM BUILDING 8 SWITCHBOARDS 3.EXISTING CEILING FANS TO BE REMOVED OR REPLACED AS PER MECHANICAL SERVICES DRAWING EXISTING SPLIT AIR CONDITIONING UNITS ARE CURRENTLY SUPPLIED FROM BUILDING 12. AMEND SUCH THAT UNITS ARE SUPPLIED FROM BUILDING 8 (PANEL N8). NEW WIRING TO BE INSTALLED CLIPPED TO EXISTING ROOF TRUSSES IN A NEAT AND UNOBTRUSIVE MANNER. PROVIDE NEW WALL MOUNTED WEB CAM TO PROVIDE COVERAGE OF EXTERNAL DOORS WIRED BACK TO THE BUILDING 8 NURSES STATION.
N8/9
3. 4. 5. 6.
WF10
WF10
WF10
NOTE 7 A/C
WF10
7.
8.
A/C
N8/25 N8/8
WF8
NURSES LOUNGE
WF8
SCP
SF1 N WF8
SF1 N
WF8
A/C
SF1 N
WF10
A/C NOTE 7
NEW PATCH PANEL EXISTING COMMUNICATION SWITCH (NOTE 3)
WF8
WF8
WF8
WF8
WF8 N8/27
NC
NC
WF9
CORRIDOR
WF9
EX1 N
WF9
WF9
WF9
WF9
CORRIDOR
WF9
WF9
WF9
NOTE 8
EX1 WF9
WF10
NC
NC
NC
A/C
WF8 SCP
F 2-BED MEDICAL/ SURGICAL WARD
N8/31 WF10
A/C
SCP
SCP
N8/30
WF8
WF8
WF8
WF8
NOTE 7
EX1
WF10
WF10
WF10
WF10 WF11
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-09-E-091
1
NOTES
1. 2. 3. 4. REPLACE ALL EXISTING RECEPTACLES. RECEPTACLES FED FROM SWITCHBOARDS IN BUILDING 8. NEW PATCH PANEL TO BE HINGED 12U WALL MOUNTED PANEL WITH LOCKABLE GLASS DOOR PROVIDE NEW POWER SUPPLY TO NEW MAGNETIC HOLD OPEN DEVICES FITTED TO NEW FIRE RATED DOORS.
NEW 2.4kW HOT WATER UNIT AND CIRCULATING PUMP (1kW). N8/47
2
NURSES LOUNGE
A/C
2
CHIEF NURSE OFFICE
A/C
2 2 N8/25,27
NOTE 4
CORRIDOR
F
CORRIDOR
CB8/3,13
NOTE 4
A/C 2
4-BED MEDICAL/ SURGICAL WARD 2-BED MEDICAL/ N8/28 SURGICAL WARD 2-BED MEDICAL/ N8/29 SURGICAL WARD
TRAINING ROOM
N8/28,30 2 2 N8/29,31
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-09-E-092
1
NOTES
1. 2. 3. REFER TO DRAWING NO. 6500080-00-E-001 ALL NEW LUMINAIRES TYPE SF1 UNO REPLACE EXISTING LIGHT SWITCH AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER REMOVE REDUNDANT WIRING FROM EXTERNAL SEATING AND MAKE SAFE CONTRACTOR TO VERIFY CIRCUIT DETAILS FOR EXISTING FINANCE OFFICE EMERGENCY CIRCUIT LS4/6 SUPPLIES SELECTED LUMINAIRES IN BUILDING 10 PROVIDE 4 OFF TYPE SF14 LUMINAIRES WITHIN ROOF VOID TO ILLUMINATE NEW ACCESS WALKWAY COMPLETE WITH NEW LOCAL SWITCH LIGHT SWITCH TO ALSO CONTROL NEW FRESH AIR FAN (REFER DWG H-101) SAFE LIGHT CONTROLLED BY SWITCH ADJACENT TO DOOR. WHITE LIGHT CONTROLLED BY PULL CORD SWITCH.
4. 5. 6.
7
N10/3 LS4/6
8
N10/3
10
7.
8. 9.
OPERATORY
OPERATORY
OPERATORY
PRIVATE OFFICE
Q
N10/1
FHR
NOTE 7
CORRIDOR
EX1
WF6
DARK ROOM
SF7
NOTE 9
SF6
SF2
PLANT ROOM
LAB
STERILE ROOM
ENTRY
SECRETARY / RECEPTIONIST
N10/1
DB
EX1
P
MULTI N PURPOSE ROOM A/C R
SF2 N10/1
N
CORRIDOR
N
NOTE 4
NOTE5
BUILDING 5
NOTE 8
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-10-E-101
1
NOTES
1. 2. 3. REPLACE ALL EXISTING RECEPTACLES UNO. LOCATE NEW COMMS OUTLETS ADJACENT POWER RECEPTACLES. NEW RACEWAY TO INCORPORATE RECEPTACLES AT 18" CENTRES.
7
EXISTING ARRANGEMENTS IN THESE 3 ROOMS TO BE RETAINED N10/12
10
OPERATORY
OPERATORY
OPERATORY
PRIVATE OFFICE
N10/11
Q
REPLACE EXISTING SURFACE MOUNTED RACEWAY (NOTE 3) EXISTING PANEL BOARD AND ASSOCIATED CIRCUITS TO BE RETAINED
FHR
2
PLANT ROOM LAB
2 ab
DARK ROOM (original) STERILE ROOM ENTRY
M ab 2
SECRETARY / RECEPTIONIST
DB
P
N10/6, 8, 10 2
MULTI PURPOSE ROOM
2 N10/7 N10/5
O
2 2 2
BUILDING 5
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-10-E-102
1
NOTES
1. 2. 3. REFER TO DRAWING NO. 6500080-00-E-001 ALL NEW LUMINAIRES TYPE SF1 UNO REPLACE EXISTING LIGHT SWITCH AND EXHAUST FAN CONTROLLER WITH A COMBINED ELECTRONIC SWITCH WITH RUN-ON TIMER EMERGENCY CIRCUIT LS4/6 SUPPLIES SELECTED LUMINAIRES IN BUILDING 10
4.
7
N10/2
9
N10/4
10
R
VOC. REHAB. ASSIST. AND SECRETARY
ENVIRONMENTAL HEALTH
Q
LOCATED UNDER DECK ABOVE.
SF11
EX1 NOTE 3 F
WC FHR
CORRIDOR
SF8
ENVIRONMENTAL LABORATORY
P
LS4/6 N10/4
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-10-E-103
1
NOTES
1. 2. REPLACE ALL EXISTING RECEPTACLES UNO. LOCATE NEW COMMS OUTLETS ADJACENT POWER RECEPTACLES.
10
R
N10/15 2
VOC. REHAB. ASSIST. AND SECRETARY VOC. REHAB. ADMINISTRATOR
ENVIRONMENTAL HEALTH
2 2 2
N10/9
Q
CORRIDOR FHR WC
2 N10 EQ10
STORAGE / PLANT ROOM ENVIRONMENTAL LABORATORY
AHU 'K'
P
N10/17 N10/18
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-10-E-104
1
NOTES
1. 2. 3. REFER TO DRAWING NO. 6500080-00-E-001 REPLACE ALL EXISTING INCANDESCENT FITTINGS IN STORE WITH NEW FLUORESCENT LUMINAIRES PROVIDE NEW DAYLIGHT SENSOR ON ROOF IN PLACE OF EXISTING.
1 C
N11A/12
4
EXISTING DAYLIGHT SENSOR ON ROOF
PE NOTE 3
N11A
SF1
MAINTENANCE OFFICE A/C
SF8 SF1
SF8
SF9
A/C
N
N SF1
WF1
N11A/14
MAINTENANCE SHOP
SF9
STORAGE SF9
SF1
SF1
SF8
SF9
SF9 SF1
A/C
SF1
SF2
A/C
EXISTING COMMUNICATION SWITCH (NOTE 3)
FALL
B
STAIR
WF1
A/C
SF9
MEDICAL STORAGE
SF9
MENTAL HEALTH OFFICE A/C
A/C
A/C A/C
A/C
SF9
SF1
SF1
A/C
A
N11A/13 REMOVE EXISTING FLOODLIGHTS AND PIR N11A/14 EXISTING CANOPY BELOW
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-11-E-111
1
NOTES
1. REMOVE ALL EXISTING RECEPTACLES AND OUTLETS AND ASSOCIATED TRUNKING AND WIRING FROM BUILDING 11 AND PROVIDE NEW SERVICES AS NOTED. WIRING TO BE INSTALLED WITHIN HOLLOW PARTITIONS OR SURFACE MOUNTED ON BLOCK WALLS. ALL RECEPTACLES IN MAINTENANCE SHOP TO BE METAL CLAD INDUSTRIAL TYPE. MODIFY EXISTING CIRCUITS FEEDING HVAC SPLIT UNITS TO SUIT NEW REPLACEMENT UNITS AND NEW LOCATIONS (N11A/7-11). NEW PATCH PANEL TO BE HINGED 18U WALL MOUNTED PANEL WITH LOCKABLE GLASS DOOR.
2. 3. 4.
N11A/1
N11A/2
N11A/3
N11A/4
5.
1 C
NOTE 4
N11A
2 NOTE 3 S
MENTAL HEALTH RECEPTION/OFFICE
NOTE 4
STORAGE
NOTE 4
2 2
MAINTENANCE OFFICE
MAINTENANCE SHOP
ab ab ab S
FALL
2 N11A/5
MEDICAL STORAGE
2 2 NOTE 4
N11A/6
NOTE 4
A
EXISTING CANOPY BELOW
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-11-E-112
1
NOTES
1. 2. REFER TO DRAWING NO. 6500080-00-E-001 REPLACE ALL EXISTING INCANDESCENT FITTINGS IN STORE WITH NEW FLUORESCENT LUMINAIRES
1 C
WC
N11B/1
N11B/3
STORE
SF9
SF8
SF9
SF9
A/C
HYPERBARIC CHAMBER
A/C FALL
SF9
SF8
B
N11B
OFFICE COMMUNITY HEALTH CENTRE
COMPRESSOR
SF1 SF1
A/C
WF1 N
SF1
CLASSROOM
EXECTUIVE DIRECTOR
SF1
SF1
A/C
WF1 N
UP
N11B/3
ADMIN.
STAFF LOUNGE
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-11-E-113
1
NOTES
1. REMOVE ALL EXISTING RECEPTACLES AND OUTLETS AND ASSOCIATED TRUNKING AND WIRING FROM BUILDING 11 AND PROVIDE NEW SERVICES AS NOTED. WIRING TO BE INSTALLED TO BE HOLLOW PARTITIONS OR SURFACE MOUNTED ON BLOCK WALLS. MODIFY EXISTING CIRCUITS FEEDING HVAC SPLIT UNITS TO SUIT NEW REPLACEMENT UNITS AND NEW LOCATIONS (N11B/8-12). PROVIDE NEW 3 PHASE SUPPLY TO NEW LIFT N11B/7.
2. 3. 4.
N11B/2
N11B/5
1 C
WC
STORE
NOTE 3
FALL
B
OFFICE COMMUNITY HEALTH CENTRE
N11B
COMPRESSOR
NOTE 4 NOTE 3
2
CLASSROOM
EXECTUIVE DIRECTOR
NOTE 3
2
UP
ADMIN.
N11B/4
STAFF LOUNGE
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-11-E-114
1
NOTES
1. 2. 3. 4. REFER TO DRAWING NO. 6500080-00-E-001 ALL LUMINAIRES TYPE RF1 UNO ALL SERVICES NEW PROVIDE 3 OFF TYPE SF14 LUMINAIRES WITH IN ROOF VOID TO ILLUMINATE ACCESS WALKWAY TO AHU, COMPLETE WITH LOCAL SWITCH.
10
10A
11
12A
13A
N10B/1
N10B/2
N10B/1
N10B/3
R
N10B/4
WC
RD2
NHD
STAFF LOUNGE
DEPUTY DIRECTOR
WC
NHD
AHU-D
RD2
N10B/3
N10B
I.T. OFFICE
STAFF OFFICE
N10B/1
CONFERENCE ROOM
W 01
EX1
Q
SF12 SF12 N10A/10
W04
W01
N10A/11
N10B/3
O
UP
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-15-E-151
1
NOTES
1. 2. 3. MOUNT RECEPTACLES IN TOILETS AT 48" ABOVE FLOOR. MOUNT RECEPTACLES IN STAFF LOUNGE ABOVE JOINERY. ALL OTHER OUTLETS TO BE LOCATED 12" ABOVE FLOOR.
10
10A
11
N10B/8
12A
13A
WC
STAFF LOUNGE
ab
DEPUTY DIRECTOR
HOSPITAL ADMINISTRATOR
DIRECTORS OFFICE
N10B/9
2 N10B/7 G
ab ab
2 2 2
WC
P
2 N10B
STAFF OFFICE
I.T. OFFICE
2 2 2
CONFERENCE ROOM
N10B/6
2 2
Q
N10B/11
N10B/10
O
UP
.
-
BUILDING 10 ANNEX
YAP STATE HOSPITAL
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-15-E-152
1
NOTES
1. 2. 3. REFER TO DRAWING NO. 6500080-00-E-001 ALL LUMINAIRES TYPE RF1 UNO ALL SERVICES NEW
10
10A
11
12A
13A
N10A/4
N10A/1
N10A/3
N10A/2
R
NHD EM3 WC MALE
NHD
FEMALE WC EM3
EX1
EX1
N10A
TRAINING ROOM-1
TRAINING ROOM-2
P
N10A/1
EQUIPMENT CUP'D
SF2
OFFICE
EX1
EX1
Q
SF12
O
UP
.
-
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-15-E-153
1
NOTES
1. 2. MOUNT RECEPTACLES IN TOILETS AT 48" ABOVE FLOOR. ALL OTHER OUTLETS TO BE LOCATED AT 12" ABOVE FLOOR.
N10A/6
N10A/7
10
10A
11
12A
13A
13A
R
MALE WC
FEMALE WC
2 2
2 N10A/8
ELECTRICAL/ JANITOR
N10A
TRAINING ROOM-1
TRAINING ROOM-2
EQUIPMENT CUP'D
OFFICE
O
UP
.
-
BUILDING 10 ANNEX
YAP STATE HOSPITAL
3/32" = 1'
B.MEGGITT J. JOHNSON
1 0
SO SO
JJ JJ
3/32"=1' (1:128)
H. JOSHI E. SCHMIDT
ELECTRICAL 6500080-15-E-154
1