TEME-12-120-A1

ARRAY AND BATTERY SIZING Construction of Shuqaiq-2 (SHQ-2) 380kV S/S Project (PTS-12SN305) Solar Power System for Repeater Site between Shuqaiq-2 380kV S/S and Bisha 380kV BSP

1.0 Given Design Requirements


1.01 1.02 1.03 1.04 1.05 1.06 1.07 Total Load Requirement System Voltage Battery Backup time Maximum Output Voltage Minimum Output Voltage Average Battery Voltage Array radiation @ 35 degree inclination angle in worst month 423 48 7 56 42 48 5.22 W V Days V V V KWh/m2/day

4.0 System Sizing Calculation


4.01 4.02 4.03 4.04 4.05 Continuous Load (Including Losses of DC-DC or DC-AC if any) Daily Load in Ah Required daily Ah considering minimum 0 % excess cacpity in worst month Daily system load (Ah) considering module derating of 20 % Final Daily system load (Ah) considering module aging of 0 % Solar Array Sizing 4.06 4.07 Proposed module type Module Peak Power in Wp as per manufacturer data sheet Voltage at Peak power of TE130/140-36P module Current at Peak power of TE130/140-36P module Daily Ah produced by a single module type TE130/140-36P No parallel modules required to support a 254 Ah/d Load Proposed parallel strings of modules Daily Ah produced by 12 parallel module type TE130/140-36P Excess Energy generation from load No of modules in series 4.16 % 4.17 4.18 4.19 Total No of modules proposed Array to Load Ratio (Array Wp / Load W) TOTAL Peak Power of the system in Wp Peak Array Current Battery Bank Sizing Type Calculated Capacity for required discharge period of 7 Days Proposed Single cell capacity at C168 - 1,14V No of Parallel strings required Total Bank Capacity available Available Capacity Vs Calculated Actual Autonomy available considering all sizing factors C168 - 1,14V SUN + 735 TE130/140-36P 135 Wp 17.20 V 7.85 A 40.98 Ah 6.19 12 491.72 Ah 93.7% 4 48 15.3 6480Wp 118A Ni-Cad 2596.52 Ah 757.68 Ah 4 3030.7 Ah 116.7% 8.2 days 423 W 211.50Ah 211.50Ah 253.80Ah 253.80Ah

2.0 Sizing Factors to include


Solar Array Factors 2.01 2.02 2.03 Module Aging Factor Module derating factor (overall) Minimum array excess capacity in worst month Battery Factors 2.04 2.05 2.06 2.07 2.08 Battery Aging Factor Low Temperature Capacity Compensation Factor (as per manufacturer) Design Margin Minimum state of charge at the end of autonomy period Battery Inefficiency factor 1.25 1.0204 1.10 20.00 10% at 10 Deg C 0 20.00 0 % % %

4.08 4.09 4.13 4.11 4.12 4.13 4.14

3.0 Additional Design Assumptions


3.01 3.02 3.03 3.04 Converter efficiency (if any) Battery Recharge Period with load connected after autonomy discharge (14days) Battery Recharge Period with load disconnected after autonomy discharge Battery Recharge Capacity (20% to 90% SOC) 100.00 9.81 4.75 70% % Days Days

4.21 4.22 4.23 4.24 4.25