Sie sind auf Seite 1von 34

HARMONIC SOURCES AND CONTROL

CHAPTER-1 INTRODUCTION
1.1 Introduction
The project undertaken at jocil is to study the existing Harmonics in Power System and to analyze its effects. It will be most useful once the harmonics levels and orders are found so that relevant solutions for Clean power may be envisaged. In the present project work it has been proposed to investigate the sources of harmonics and control. Jaya lakshmi Oil and Chemical Industries Limited has been taken for case study.

1.2 Organization Of The Project Work


Linear loads draw current that is precisely proportional to the voltage and is also an almost perfect sinusoid. This is because these loads do not depend on the voltage to determine their impedance. Their response at any given frequency is completely linear. Non-linear loads do not respond in this way. When presented with a sinusoidal voltage, the current is not proportional to the voltage and is not sinusoidal. The non-sinusoidal current consumed is due to the device impedance changing over a complete voltage cycle A load is NON-LINEAR when the current it draws does not have the same waveform as the supply voltage. The harmonic spectrum depends on the type of load i.e., switchingmode power supplies, motors during start-up, transformers during switch-on, frequency controlled motors. Loads that make use of semi conductor devices like transistor.. The harmonic level has a great effect on the performance of the system components and equipments. Harmonic map for the distribution system is necessary for appreciating system operation upgrade. During the next decade, an increase of the nonlinear loads up to 70% is expected. Understanding electrical system problems will help in implementing appropriate solutions. Phase shifting transformers can efficiently mitigate harmonic

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

distortion. They are rigid and more economically than harmonic filters. Besides, they are secure for resonance problem that may arise in passive filter applications utilizing passive harmonic filters require recurrent analysis, measurements and precautions from system reconfigurations or upgrading and load changes for save system operation. The best way to deal with harmonics problems is through prevention: choosing equipment and installation practices that minimize the level of harmonics in any one circuit or portion of a facility. Many power quality problems, including those resulting from harmonics, occur when new equipment is haphazardly added to older systems. However, even within existing facilities, the problems can often be solved with simple solutions such as fixing poor or nonexistent grounding on individual equipment or the facility as a whole, moving a few loads between branch circuits, or adding additional circuits to help isolate the sensitive equipment from what is causing the harmonic distortion.

1.3 Statement Of The Problem


In this project work an attempt has been made to analyze the actual causes for harmonics and how we control them. For this purpose data of harmonics existing as on 0106-2011. In the operation division, Dokiparru, Guntur has been collected.

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

CHAPTER-2 HARMONICS
2.1 Introduction
Linear loads draw current that is precisely proportional to the voltage and is also an almost perfect sinusoid. This is because these loads do not depend on the voltage to determine their impedance. Their response at any given frequency is completely linear. Non-linear loads do not respond in this way. When presented with a sinusoidal voltage, the current is not proportional to the voltage and is not sinusoidal. The nonsinusoidal current consumed is due to the device impedance changing over a complete voltage cycle.

2.2 Definitions
Harmonics are integral of some fundamental frequency that, when added To gether, result in a distorted waveform i.e

Distorted sine wave causes harmonics. Distorted current wave causes current harmonics. Distorted voltage wave causes voltage harmonics. Nth order harmonics is of n. Fs frequency. Generally odd harmonics are prevalent because of half wave symmetric

2.3 About The Harmonics


The power company typically supplies a reasonably smooth sinusoidal waveform: Supply Frequency-50 Hzs ...but nonlinear devices will draw distorted waveforms, which are comprised of harmonics of the source. Typical Harmonics are 3rd,5th, 7th & 11th 3rd = 150 Hzs. 5th = 250 Hzs.

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

7th= 350 Hzs. 11th = 550 Hzs

Each harmonic order has a particular Phase sequence relationship with respect to fundamental.

By convention the fundamental is assumed to have positive phase sequence. All higher order harmonics have either positive ,negative or zero phase sequence with respect to fundamental.

Table.2.1. Sequence and order of harmonics Sequence Order

Zero(0)

0,3,6,9,12,15,18,21,24.3q

Positive (+)

1,4,7,10,13,16,19,22,25.3q +1

Negative (-)

2,5,8,11,14,17,20,23,26..3q- 1

Some references refer to clean or pure power as those without any harmonics. But such clean waveforms typically only exist in a laboratory. Harmonics have been around for a long time and will continue to do so. In fact, musicians have been aware of such since the invention of the first string or woodwind instrument. Harmonics (called overtones in music) are responsible for what makes a trumpet sound like a trumpet, and a clarinet like a clarinet.

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

In European countries and other parts of the world, this frequency is usually 50 Hz. Aircraft often uses 400 Hz as the fundamental frequency. At 60 Hz, this means that sixty times a second, the voltage waveform increases to a maximum positive value, then decreases to zero, further decreasing to a maximum negative value, and then back to zero. The rate at which these changes occur is the trigometric function called a sine wave, as shown in figure 1. This function occurs in many natural phenomena, such as the speed of a pendulum as it swings back and forth, or the way a string on a violin vibrates when plucked.

Fig 2.1. Sine wave

Figure2.2 Fundamental with two harmonics

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

In order to be able to analyze complex signals that have many different frequencies present, a number of mathematical methods were developed. One of the more popular is called the Fourier Transform. However, duplicating the mathematical steps required in a microprocessor or computer-based instrument is quite difficult. So more compatible processes, called the FFT for Fast Fourier transform, or DFT for Discrete Fourier Transform, are used. These methods only work properly if the signal is composed of only the fundamental and harmonic frequencies in a certain frequency range (called the Nyquist frequency, which is one-half of the sampling frequency). The frequency values must not change during the measurement period. Failure of these rules to be maintained can result in mis-information. For example, if a voltage waveform is comprised of 60 Hz and 200 Hz signals, the FFT cannot directly see the 200 Hz. It only knows 60, 120, 180, 240,..., which are often called bins. The result would be that the energy of the 200 Hz signal would appear partially in the 180Hz bin, and partially in the 240 Hz bin. An FFT-based processer could show a voltage value of 115V at 60 Hz, 18 V at the 3rd harmonic, and 12 V at the 4th harmonic, when it really should have been 30 V at 200 Hz. These in-between frequencies are called inter harmonics. There is also a special category of inter harmonics, which are frequency values less than the fundamental frequency value, called sub-harmonics. For example, the process of melting metal in an electric arc furnace can result large currents that are comprised of the fundamental , inter harmonic, and sub harmonic frequencies being drawn from the electric power grid. These levels can be quite high during the melt-down phase, and usually effect the voltage waveform.

2.4 Problem Of Harmonics


Most electrical loads (except half-wave rectifiers) produce symmetrical current waveforms, which mean that the positive half of the waveform looks like a mirror image of the negative half. This results in only odd harmonic values being present. Even harmonics
6

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

will disrupt this half-wave symmetry. The presence of these even harmonics should cause the investigator to suspect there is a half-wave rectifier on the circuit. This also results from a full wave rectifier when one side of the rectifier has blown or damaged components. Early detection of this condition in a UPS system can prevent a complete failure when the load is switched onto back-up power. To determine what is normal or acceptable levels, a number of standards have been developed by various organizations. ANSI/IEEE C57.110 Recommended Practice for Establishing Transformer Compatibility When Supplying No sinusoidal Load Currents is a useful document for determining how much a transformer should be derated from its nameplate rating when operating in the presence of harmonics. There are two parameters typically used, called K-factor and TDF (transformer de reading factor). Some power quality harmonic monitors will automatically calculate these values. IEEE 519-1992 Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems provides guidelines from determining what acceptable limits are. The harmonic limits for current depend on the ratio of Short Circuit Current (SCC) at PCC (or how stiff it is) to average Load Current of maximum demand over 1 year, as illustrated in Table 5. Note how the limit decreases at the higher harmonic values, and increases with larger ratios.

2.5 Sources Of Harmonics


How this electricity is used by the different type of loads can have an effect on purity of the voltage waveform. Some loads cause the voltage and current waveforms to lose this pure sine wave appearance and become distorted. This distortion may consist of predominately harmonics, depending on the type of load and system impedances. Since this article is about harmonics, we will concentrate on those types of sources. The main sources of harmonic current are at present the phase angle controlled rectifiers and inverters. These are often called static power converters. These devices take

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

AC power and convert it to another form, sometimes back to AC power at the same or different frequency, based on the firing scheme. The firing scheme refers to the controlling mechanism that determines how and when current is conducted. One major variation is the phase angle at which conduction begins and ends. A typical such converter is the switching-type power supplies found in most personal computers and peripheral equipment, such as printers. While they offer many benefits in size, weight and cost, the large increase of this type of equipment over the past fifteen years is largely responsible for the increased attention to harmonics. Figure shows below how a switching-type power supply works. The AC voltage is converted into a DC voltage, which is further converted into other voltages that the equipment needs to run. The rectifier consists of semi-conductor devices (such as diodes) that only conduct current in one direction. In order to do so, the voltage on the one end must be greater than the other end. These devices feed current into a capacitor, where the voltage value on the cap at any time depends on how much energy is being taken out by the rest of the power supply. When the input voltage value is higher than voltage on the capacitor, the diode will conduct current through it. This results in a current waveform as shown in Figure 5, and harmonic spectrum in Figure 6. Obviously, this is not a pure sinusoidal waveform with only a 60 Hz frequency component.

2.5.1 Harmonics Generating loads


A load is NON-LINEAR when the current it draws does not have the same waveform as the supply voltage. The harmonic spectrum depends on the type of load i.e., switching-mode power supplies, motors during start-up, transformers during switch-on, frequency controlled motors. Loads that make use of semi conductor devices like transistor. i.e.static rectifies. (AC/DC conversation using SCRS),

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

1. static frequency converters, static inverters like a. Static power converters (AC-DC conversion using SCRS) b. Static rectifiers c. Static frequency converter d. Static uninterruptible power supplies e. Static induction regulators. 2. Variable impedance loads, using electric arcs, arc furnaces, welding units, fluorescent tubes, discharge lamps, Light control brightness etc. 3. Loads using strong magnetizing currents saturated transformer, inductance furnaces, reactors etc.

2.5.2 Harmonic Analysis


There are some simple methods for estimating the harmonic voltage due to an installation and whether a capacitor may cause an un wanted resonance.The steps in simple harmonic analysis are 1. Obtain information on supply system. This is usually given in the form of the short circuit current or fault level, from which an equipment impedance can be calculated. 2 Estimate the major harmonic sources in an installation. 3. For each harmonic order ,model the power system and installation. It is assumed that inductive reactance will increase with frequency,capactive reactive reactance will decrease while reactance remain unchanged. 4. Determine the voltage at the point of common coupling from the distorting current injected and calculated harmonic impedance

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

2.6 Types Of Harmonics


Generally voltage harmonics depend on grid / source stability, current harmonics and network impedance. Current harmonics mainly depends upon the loads. These high voltages and currents cause additional system losses, breakdown of equipment insulation, capacitor fuse melting, errors in metering and protective relays and interference with other consumers which may result in fall in efficiency. 1. Voltage Harmonics 2. Current Harmonics

2.6.1.Voltage Harmonics
Voltage harmonics can effects sensitive equipment throughout your facility. Voltage harmonics arise when current harmonics are able to create sags in the voltage supply. When any device draws current it creates a voltage dip which is required for the current to flow. The voltage dip is visible with larger loads when turning on a table saw and seeing the lights dim down. The amount of sag depends on many factors like transformer impedance wire size. Current harmonics create voltage harmonics, but the magnitude of the voltage harmonics depends on the stiffness of your electrical distributions system impedance.

2.6.2.Current Harmonics
Current harmonics do have an effect on the electrical equipment supplying harmonic current to the devices (transformers, conductors). Current harmonics can cause issues with distribution equipment which has to handle the current from the utility transformer all the way down to the device, but generally dont affect other equipment connected to electrical system. Harmonic currents can cause excessive heating to transformers. For electrical systems feeding single phase loads the third harmonics has gain attention in design consideration and transformer selection for causing the neutral conductor to draw excessive current.

10

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Figure 2.3. Current Waveform

Figure 2.3. Harmonic Spectrum of Current Waveform Shown in Figure 2.2

11

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

2.7. Measuring Of Harmonics


Hand-held harmonic meters can be useful tools for making spot checks for known harmonic problems. However, harmonic values will often change during the day, as different loads are turned on and off within the facility or in other facilities on the same electric utility distribution system. This requires the use of a harmonic monitor or power quality monitor with harmonic capabilities (such as shown in Figure 8), which can record the harmonic values over a period of time.

Figure 2.4. Power Quality Monitor with Harmonic Analysis

Typically, monitoring will last for one business cycle. A business cycle is how long it takes for the normal operation of the plant to repeat itself. For example, if a plant runs three identical shifts, seven days a week, then a business cycle would be eight hours. More typically, a business cycle is one week, as different operations take place on a Monday, when the plant equipment is restarted after being off over the weekend, then on a Wednesday, or a Saturday, when only a Skelton crew may be working.

12

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Certain types of loads also generate typical harmonic spectrum signatures that can point the investigator towards the source. This is related to the number of pulses, or paths of conduction. The general equation is h = ( n * p ) +/- 1, where h is the harmonic number, n is any integer (1,2,3,..) and p is the number of pulses in the circuit, and the magnitude decreases as the ration of 1/h (1/3, 1/5, 1/7, 1/9,...). Table 4 shows examples of such.

2.8. Limits of Harmonics


As per IS 13021, following are limits for various Harmonics. Table 2.2 limits for various Harmonics. Harmonics Number 9th 7th 5th 2nd 3rd 11th THD % of harmonic value 3% 4% 7% 5% 30% 2% 8%

2.9. Case Studies 2.9.1 Case Study 1


oxygen plant line voltage(v) L1 L2 L3 line currents(A) L1 77.3 L2 86 L3 78.4 L1 %THD L2 L3 5,7,11,13 harmonic dominant

428.2 432.1 427.4

13.8% 14.8% 11.2%

13

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

2.9.2 Case Study2


line voltage(v) L1 L2 L3 line currents(A) L1 394 L2 410 L3 400 L1 %THD L2 L3 5,7 harmonic dominants

436.2 435.4 434.3

2.7% 2.7% 2%

14

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

2.9.3 Case Study3


line voltage(v) L1 L2 L3 line currents(A) L1 61.8 L2 L3 %THD L1 10.2 L2 10.8 L3 9.4 5,7,11 harmonic dominants

432.9 428.9 426.6

76.6 66.3

15

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

CHAPTER-3 IDENTIFYING THE HARMONICS


Without obvious symptoms such as nuisance breaker trips or overheated transformers, how do you determine whether harmonic current or voltages are a cause for concern? Here are several suggestions for simple, inexpensive measurements that a facility manager or staff electrician could take, starting at the outlet and moving upstream Measure the peak and root mean square (RMS) voltage at a sample of receptacles. The crest factor is the ratio of peak to RMS voltage. For a perfectly sinusoidal voltage, the crest factor will be 1.4. Low crest factor is a clear indicator of the presence of harmonics. Note that these measurements must be performed with a true RMS meterone that doesnt assume a perfectly sinusoidal waveform. Inspect distribution panels. Remove panel covers and visually inspect components for signs of overheating, including discolored or receded insulation or discoloration of terminal screws. If you see any of these symptoms, check that connections are tight (since loose connections could also cause overheating), and compare currents in all conductors to their ratings. Measure phase and neutral currents at the transformer secondary with clamp-on current probes. If no harmonics are being generated, the neutral current of a threephase distribution system carries only the imbalance of the phase currents. In a wellbalanced three-phase distribution system, phase currents will be very similar, and current in the neutral conductor should be much lower than phase current and far below its rated current capacity. If phase currents are similar and neutral current exceeds their imbalance by a wide margin, harmonics are present. If neutral current is above 70percent of the conductors rated capacity, you need to mitigate the problem.

16

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Compare transformer temperature and loading with nameplate temperature

rise and capacity ratings. Even lightly loaded transformers can overheat if harmonic current is high. A transformer that is near or over it srated temperature rise but is loaded well below it srated capacity is a clear sign that harmonics are at work. (Many transformers have built-in temperature gauges. If yours does not, infrared thermo graphy can be used to detect overheating.) In addition to these simple measurements, many power-monitoring devices are now commercially available from a variety of manufacturers to measure and record harmonic levels. These instruments provide detailed information on THD, as well as on the intensity of individual harmonic frequencies. After taking the appropriate measurements to determine whether you have high levels of harmonics and, if so, to find the source, you will be well-positioned to choose the best solution.

3.1 Effects Of Harmonics 3.1.1 Potential effects of harmonics


Power system problems related to harmonics are rare but it is possible for a number of undesirable effects to occur. High levels of harmonic distortion can cause such effects as increased transformer, capacitor, motor or generator heating, mis operation of electronic equipment (which relies on voltage zero crossing detection or is sensitive to wave shape), incorrect readings on meters, mis operation of protective relays, interference with telephone circuits, etc. The likelihood of such ill effects occurring is greatly increased if a resonant condition occurs. Resonance occurs when a harmonic frequency produced by a non-linear load closely coincides with a power system natural frequency.

3.1.2 Effects of Harmonics on Transformers


1. Increase in No load Loss. 2. Increase in Load Loss.

17

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

3. Increase in Energy loss. 4. Over heating of transformer which leads to faster Insulation deterioration Lower Transformer life Premature failure of transformer, etc

1. Harmonic current Effect on IR loss The RMS value of the load current is increased due to harmonic component, loss increases accordingly. 2. Harmonic current effect on the winding eddy current los Winding eddy current loss in power frequency spectrum tends to proportional to the square of the load current and square of the frequency. It is the characteristic that can cause excessive winding loss and hence higher temperature. 3. Harmonic current effect on other stray loss These loss also increase with square of the load current and by a harmonic exponent factor of 0.8 or less. 4. DC component of load current A DC component of load current increase the magnetizing current and audible sound level. IR

3.1.3 Effects Of Harmonics On The Equipments


Equipment responds to harmonics differently depending on there method of operation. for example incandescent lights and most types of household electric heaters and stoves are not effected adversely at all.

18

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

On the other hand, induction motor windings are over heated by the harmonics, causing accelerated degradation of insulation and losses of life .harmonic voltages can give correspondingly higher currents than do 50hz voltages and one can easily under estimated the degree of additional heating in the motor. the operation of some equipment depends on an accurate voltage wave shape and they can malfunction when harmonics are present. Examples of this equipment containing scrs (thyristor) such as light dimmers and seem welders. Harmonics due to many single phase distorting loads spread across three phases, such as occurs in commercial office buildings, can give neutral currents exceeding the active line currents. when harmonics are absent ,the neutral conductor carries a very small current and it has been the practice to rate the neutral for all of or maybe for half of the active line current .with excessive levels of harmonics due to single phase loads, there is a risk of over loading the neutral with two possible consequences. overheating the neutral conductor with losses of conductor life and possible risk of fire there have been some claims that high neutral earth voltages can affect digital equipment and local area networks(LANS) if the earthing system is poor. In the supply system, substation transformers and power factor correction capacitors are most affected. transformers are affected by a distorted current waveform which can cause extra heating leading to reduction in their service life. capacitors can affected by the applied voltage waveform which can cause overheating of the di-electric with a risk of explosion.Many plant engineers are aware only of power supply problems which lead to immediate malfunctioning or equipment trips. We have seen that harmonic effects can lead to equipment overheating and reduction in service life by a factor of up to half with consequent economic losses. Unlike most other supply problems, harmonics can go un

19

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

noticed for many years unless equipment temperature or the voltage waveform is routinely monitored.

3.1.4 Effects on Network


overvoltage and harmonic distortion in own network. overvoltage and harmonic distortion that can disturb other subscribers in the same network.

Resonance phenomena between inductive and capacitive parts of the network.

3.2 Problems Caused By Harmonics


1. Overheating of transformers (K- Factor), and rotating equipment 2. Increased hysteresis losses 3. Neutral overloading / unacceptable neutral-to-ground voltage Distorted voltage and current waveforms 4. Failed capacitor banks 5. Breakers and fuses tripping, Unreliable operation of electronic equipment, and Generators 6. Erroneous register of electric meters 7. Wasted energy / higher electric bills -KWD & KWH. 8. Wasted capacity Inefficient distribution of power 9. Increased maintenance cost of equipment and machinery 10. Cogging & Crawling of Induction Motor. 11. Blinking of Incandescent Lights - Transformer Saturation 12. Flickering of Fluorescent Lights Transformer Saturation 13. Neutral Conductor and Terminal Failures Additive Triple Currents

20

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

14. Overheating of Metal Enclosures - Inductive Heating 15. Power Interference on Voice Communication Harmonic Noise

3.3 Solution To Harmonic Problems


The best way to deal with harmonics problems is through prevention: choosing equipment and installation practices that minimize the level of harmonics in any one circuit or portion of a facility. Many power quality problems, including those resulting from harmonics, occur when new equipment is haphazardly added to older systems. However, even within existing facilities, the problems can often be solved with simple solutions such as fixing poor or nonexistent grounding on individual equipment or the facility as a whole, moving a few loads between branch circuits, or adding additional circuits to help isolate the sensitive equipment from what is causing the harmonic distortion. If the problems cannot be solved by these simple measures, there are two basic choices: to reinforce the distribution system to withstand the harmonics or to install devices to attenuate or remove the harmonics. Reinforcing the distribution system means installing double-size neutral wires or installing separate neutral wires for each phase, and/or installing oversized or K rated transformers, which allow for more heat dissipation. There are also harmonic-rated circuit breakers and panels, which are designed to prevent overheating due to harmonics. This option is generally more suited to new facilities, because the costs of retrofitting an existing facility in this way could be significant. Strategies for attenuating harmonics, from cheap to more expensive, include passive harmonic filters, isolation transformers, harmonic mitigating transformers (HMTs), the Harmonic Suppression System (HSS) from Harmonics Ltd., and active filters.

3.4 Impact Of Harmonics 3.4.1 Impact of harmonics on power factor


PF is a ratio of useful power to perform real work to the apparent power supplied by a utility, which measures the efficiency of utilization of a power distribution system. The
21

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

PF for a system delivering only linear loads is called the displacement power factor. Today many electrical systems have harmonic currents on their lines. Harmonics are caused by non linear loads and their current causes the apparent power to exceed the active and reactive powers by a substantial amount. The apparent power for non linear loads can be calculated using the equations. KVA = (P+Q+D) Where, D = distortion volt amperes P = active power at all frequency Q = reactive power at all frequency Q = Vk Ik sink The presence of harmonics increases the apparent power that must be delivered, therefore lowering the PF. In these situations the form of power factor is called DISTORTION POWER FACTOR. In a system consisting of both linear and nonlinear loads. The true power factor is a sum of cosine of both displacement and distortion angles. If harmonic currents are introduced in to their system the true PF will always be lower than the displacement PF.

3.4.2 Impact of harmonics on capacitors


Harmonic component affects the performance of a capacitor unit significantly due to diminishing reactance at higher frequencies, which adds to its loading substantially and can be analyzed as follows. This means that the capacitor will offer low reactance to the higher harmonics and will tend to magnify the harmonic effect due to higher harmonic current. In fact, harmonic currents have a greater heating effects compared to fundamental current. The effective current caused by all the harmonics present in the system can be expressed as

22

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Where, Over current resulting to an over voltage across the capacitor units, which would flick greater dielectric stress on capacitor elements. Since the harmonic disorders occur at higher frequencies then the fundamental, they cause higher dielectric losses.

Fig 3.1. capacitors The rating of the capacitor unit will does vary in a square proportion of the effective harmonic voltage and in direct proportion to the harmonic frequency. This rise in the KVAR, however will not contribute to the improvement of system PF, but only to the overloading of the capacitor themselves.

3.4.3 Impact of harmonics on motor


For frequencies higher than the fundamental, 3phase induction motors can be approximated by positive / negative shunt impedances. Where Rw is the motor winding resistance, k is the harmonic order; X is the fundamental frequency reactance. The harmonic voltage distortion is translated to harmonic fluxes with in the motor. Harmonic fluxes do not contribute significantly to motor path, but induces additional losses by several percent

Fig 3.2. Motor

23

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

.CHAPTER-4

DECREASING OF HARMONICS
Care should be undertaken to make sure that the corrective action taken to minimize the harmonic problems dont actually make the system worse. This can be the result of resonance between harmonic filters, PF correcting capacitors and the system impedance. Isolating harmonic pollution devices on separate circuits with or without the use of harmonic filters are typical ways of mitigating the effects of such. Loads can be relocated to try to balance the system better. Neutral conductors should be properly sized according to the latest NEC-1996 requirements covering such. Whereas the neutral may have been undersized in the past, it may now be necessary to run a second neutral wire that is the same size as the phase conductors. This is particularly important with some modular office partition-type walls, which can exhibit high impedance values. The operating limits of transformers and motors should be derated, in accordance with industry standards from IEEE, ANSI and NEMA on such. Use of higher pulse converters, such as 24-pulse rectifiers, can eliminate lower harmonic values, but at the expense of creating higher harmonic values.

4.1 Harmonic Mitigation Requirement


Need and cause analysis Root cause identification Solutions analysis. Optimize solution based on effectiveness, speed of implementation and viability Propose solutions along with cost benefits and return on investment Undertake, and implement proposal.

Harmonic mitigation transformer actually do relieve problematic harmonics. HMTs can be quite cost-effective in the right application, because they can both improve reliability and reduce energy costs. The right application includes transformers that are heavily or

24

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

moderately loaded and where high levels of harmonic currents are present. In addition, HMTs are very effective in supporting critical loads that are backed up by a UPS. UPSs and backup generators tend to have high impedance, which results in high voltage distortion under nonlinear loading. Because of this, equipment that operates flawlessly when supplied by utility power may malfunction when the backup system engages during a utility outage. Note that some of these power systems have output filters (either passive or active) to control harmonic levels. The pre senceor absence of such filters should be determined before adding an HMT.

4.1.1 Harmonic mitigation solutions

4.2 Types Of Filters

25

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

4.2.1 Passive Filters


Passive filters (also called traps) include devices that provide low-impedance paths to

divert harmonics to ground and devices that create a higher-impedance path to discourage the flow of harmonics. Both of these devices, by necessity, change the impedance characteristics of the circuits into which they are inserted. Another weakness of passive harmonic technologies is that, as their name implies, they cannot adapt to changes in the electrical systems in which they operate. This means that changes to the electrical system (for example, the addition or removal of power factor correction capacitors or the addition of more nonlinear loads) could cause them to be overloaded or to create resonances that could actually amplify, rather than diminish, harmonics. Passive filters use resistors, capacitors, and inductors (RLC networks). To minimize distortion in the filter characteristic, it is desirable to use inductors with high quality factors (remember the model of a practical inductor includes a series resistance), however these are difficult to implement at frequencies below 1 kHz. Drawbacks They are particularly non-ideal (lossy) They are bulky and expensive

Fig 4.1 Passive filters

26

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

4.2.2 Active Filters


Active filters overcome these drawbacks and are realized using resistors, capacitors, and active devices (usually op-amps) which can all be integrated: Active filters replace inductors using op-amp based equivalent circuits.

Active filters in contrast, continuously adjust their behavior in response to the harmonic current content of the monitored circuit, and they will not cause resonance. Like an automatic transmission in a car, active filters are designed to accommodate a full range of expected operating conditions upon installation, without requiring further adjustments by the operator. SOLID-STATE control of ac power using thyristors and other semiconductor switches is widely employed to feed controlled electric power to electrical loads, such as adjustable speed drives (ASD's), furnaces, computer power supplies, etc. Such controllers are also used in HV dc systems and renewable electrical power generation. As nonlinear loads, these solid-state converters draw harmonic and reactive power components of current from ac mains. In three-phase systems, they could also cause unbalance and draw excessive neutral currents. The injected harmonics, reactive power burden, unbalance, and excessive neutral currents cause low system efficiency and poor power factor. They also cause disturbance to other consumers and interference in nearby communication networks. Conventionally passive L-C filters were used to reduce harmonics and capacitors were employed to improve the power factor of the ac loads. However, passive filters have the demerits of fixed compensation, large size, and resonance. The increased severity of harmonic pollution in power networks has attracted the attention of power electronics and power system engineers to develop dynamic and adjustable solutions to the power quality problems. Such equipment, generally known as active filters (AF's) are also called active power line conditioners (APLC's), instantaneous reactive power compensators (IRPC's), active power filters (APF's), and active power quality conditioners(APQC's).

27

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Fig. 4.2 Active filters Active filter-features Nominal outputs of 50A,100A & 300A High dynamic response. Up to 5afhi can be operated in parallel. Very compact design. Easy to integrate into existing installation. Suppression of all harmonic currents up to 49th order Comprehensive communication facilities. Harmonic attenuation factor up to 97%. Avoidance of risk for resonance and takes care for unbalanced loads.

4.2.4 De-tuned filters


Tuned away from the predominant harmonics. Blocks harmonics above tuned frequency. Acts as a controlled filter safeguard capacitors. Safeguard capacitors. Percentage tuning factor is defined as Standard detuned filters are available for 7% tuning factor

28

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

4.2.5 Tuned filters


Tuned closer to predominant harmonics. Combination of tuned & detuned nature. Acts as uncontrolled filter. Susceptible for failure on load profile change / modification.

4.3 Filter design highlights


Selection of size Selection of configuration. Selecting of tuning factor. Location Sizing of components Verification of parallel & series resonance conditions. Detailed computer simulation to verify resonance & transient condition Verification of optimality through computer software.

4.4 Economic Problem


Evaluating the life-cycle costs and effectiveness of harmonics mitigation technologies can be very challengingbeyond the expertise of most industrial facility managers. After performing the proper measurement and analysis of the harmonics problem, this type of evaluation requires an analysis of the costs of the harmonics problem (downtime of sensitive equipment, reduced power factor, energy losses or potential energy savings) and the costs of the solutions. A good place to start in performing this type of analysis is to ask your local utility or electricity provider for assistance. Many utilities offer their own power quality mitigation services or can refer you to outside power quality service providers

29

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

CHAPTER-5 REGULATION FOR INSTALLATION


These are imposed by the electricity supply authority to protect other electricity consumers from the effects of excessive harmonics. They are usually based on agreed level of voltage distortion which can be tolerated by correctly designed equipment. This is specified in terms of total harmonic distortion (THD). The internationally accepted maximum THD compatibility level in a low voltage level is 8%, and to achieve this with a high degree of confidence it is usual to aim for a rather low level as the planning level, typically 5%. Individual harmonics are subjected to limits. From the point of view of the supply authority, the relevant harmonic voltage is at the point of common coupling (PCC) with other power consumers. The harmonic levels with in the consumers premises may be higher because of the impedance of cables and transformers. In large installations measures may be necessary to prevent harmonic problems with in a site. Since there are no stationary requirements, a relaxed version of the authority limits can be applied internally. It is not advisable to allow the 8% THD limit to be exceeded, because the majority of equipment will have been designed to be immune only up to this level. Calculating the voltage distortion of a proposed installation can be an expensive matter, because it requires existing harmonics to be measured over a period of time, the system parameters such as source impedance to be derived, and the effect of planned new load to be estimated.

5.1 IEEE-519 Regulation


IEEE-519 is a recommended guideline for designing electrical systems in buildings, NOT a mandatory standard. The IEEE-519 recommended practice defines dedicated, general, and special classifications. Hospitals and airports fit into the special category

30

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

while most others fit in the general classification. Systems with only VSD loads are defined by IEEE as dedicated and allow higher distortion Limits for general installations are 5% Total Harmonic Voltage Distortion (THVD) and 12% Total Harmonic Current Distortion (THID). Limits for special applications are 3% THVD and 8% THID. Dedicated systems allow 10%THVD and up to 22% THID. IEEE States that the estimated load current should be an average running current for a 1 year period. If not known 80% of Full Load Amps is a good approximation. IEEE-519 should not be blindly specified. Owners and engineers must be educated on applying IEEE-519. Raising costs for customers without rational clarification of the guidelines is not the optimum engineering solution - its like specifying 100,000 CFM when only 20,000CFM is required. IEE-519 is a system issue more than a particular equipment issue.IEE-519 sets limits on the voltage and current harmonics distortion at the point of common coupling (PCC, usually the secondary of the supply transformer) . The total harmonic distortion is dependant on the percent of harmonics distortion from each non-linear device with respect to the total capacity of the transformer and the relative load of the system. Table 5.1 Input impedance of harmonics

31

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

Reactors are by far, the most economical way of reducing harmonic distortion on a drive system. Actual harmonic distortion is determined for linear and non-linear loads both on the system. Harmonics distortion depends on the percentage of non-linear loads on the system. Table 5.2 Percentage of non-linear loads

32

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

CONCLUSION
The harmonic level has a great effect on the performance of the system components and equipments. Harmonic map for the distribution system is necessary for appreciating system operation upgrade. During the next decade, an increase of the nonlinear loads up to 70% is expected. Understanding electrical system problems will help in implementing appropriate solutions. Phase shifting transformers can efficiently mitigate harmonic distortion. They are rigid and more economically than harmonic filters. Besides, they are secure for resonance problem that may arise in passive filter applications utilizing passive harmonic filters require recurrent analysis, measurements and precautions from system reconfigurations or upgrading and load changes for save system operation. Solving harmonic problem is not just for satisfying standard regulations, it is an economical business. It decreases the overall power losses on the system, includes voltage profile and improves power factor. It also saves a deferred capacity for both transformers and lines and improves the life time of the system components and equipments. Finally, care full considerations are necessary when studying harmonic problems in many power systems and on instrumentation requirements for measurements. Important issues must be included as types of loads, power factor characteristics, harmonic generating characteristics, frequency response characteristics of the supply system, power factor correction in the customer facility and harmonic filters in the customer facility. It is recommended to precede a no sinusoidal tariff schemes towards a regulatory tariff system for the non linear loads.

33

DEPARTEMENT OF EEE

HARMONIC SOURCES AND CONTROL

BIBILIOGRAPHY
TEXTBOOKS
As 2279.2 -1991,disturbances in mains supply networks,part:2 Limitations of harmonics caused by industrial equipment, standards Australia,1991 Arrillaga,J., Bradley,D.A., and Bodger ,P.S..Power system harmonics,John Wiely,1985. IEEE:bibiliography of powersystem harmonics ,part:1,IEEE Trans.,1984,PAS103,PP.2460-2469. IEEE:Bibilography of power system harmonics ,part:1,IEEE Trans.,1984,PAS103,PP.2470-2479

34

DEPARTEMENT OF EEE

Das könnte Ihnen auch gefallen