GENERAL NOTES FOR EXISTING AWS CELL SITES

1. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING SUBCONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH
THE EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE
CONSTRUCTION DRAWINGS. ANY DISCREPANCY FOUND SHALL BE BROUGHT TO THE ADENTloN OF CONTRACTOR.
2. SUBCONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL
DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS MUST BE VERIFIED. SUBCONTRACTOR SHALL
NOTIFY THE CONTRACTOR OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH
CONSTRUCTION.
3. THE EXISTING CELL SITE IS IN FULL COMMERCIAL OPERATION. ANY CONSTRUCTION WORK BY SUBCONTRACTOR
SHALL NOT DISRUPT THE EXISTING NORMAL OPERATION. ANY WORK ON EXISTING EQUIPMENT MUST BE COORDINATED
WITH CONTRACTOR. ALSO, WORK SHOULD BE SCHEDULED FOR AN APPROPRIATE MAINTENANCE WINDOW USUALLY IN
LOW TRAFFIC PERIODS AFTER MIDNIGHT.
4. SINCE THE CELL SITE IS ACTIVE, ALL SAFETY PRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND HIGH LEVELS
OF ELECTROMAGNETIC RADIATION. EQUIPMENT SHOULD BE SHUTDOWN PRIOR TO PERFORMING ANY WORK THAT
COULD EXPOSE THE WORKERS TO DANGER. PERSONAL RF EXPOSURE MONITORS ARE ADVISED TO BE WORN TO
ALERT OF ANY DANGEROUS EXPOSURE LEVELS.
5. SUBCONTRACTOR SHALL DETERMINE ACTUAL ROUTING OF CONDUIT, POWER AND T1 CABLES, GROUNDING CABLES AS
SHOWN ON THE POWER, GROUNDING AND TELCO PLAN DRAWING. SUBCONTRACTOR SHALL UTILIZE EXISTING TRAYS
AND/OR SHALL ADD NEW TRAYS AS NECESSARY. SUBCONTRACTOR SHALL CONFIRM THE ACTUAL ROUTING WITH THE
CONTRACTOR.
6. SUBCONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND
OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S
DESIGNATED LOCATION.
APV':5]
SAS l
pp
CHK.:

0 01/31/11
100% CONSTRUCTION
FG
DRAWING
1 05/09/11
100% CONSTRUCTION
TB
DRAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
REMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 PLANNING COMMENTS FG
PREPARED BY:
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868
POC CORPORATION

3140 GOLD CAMP DR, SUITE 30


RANCHO CORDOVA, CA 95670
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022

r-REV.:=DATE:=DESCRIPTION:=BY:=
'--DRAWN BY:

t t 8(

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
;:: PROJECT INFORMATION:
II
ISSUED FOR:
TITLE:
GENERAL NOTES,
LEGEND AND
ABBREVIATIONS
.2
1
3
II
GENERAL CONSTRUCTION NOTES:
13. THE CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO PROTECT EXISTING IMPROVEMENTS, PAVING, CURBS,
VEGETATION, GALVANIZED SURFACES, ETC., AND UPON COMPLETION OF WORK REPAIR ANY DAMAGE THAT
OCCURRED DURING CONSTRUCTION TO THE SATISFACTION OF AT&T.
14. KEEP GENERAL AREA CLEAN, HAZARD FREE, AND DISPOSE OF ALL DIRT, DEBRIS, RUBBISH AND REMOVE
EQUIPMENT NOT SPECIFIED AS REMAINING ON THE PROPERTY. LEAVE PREMISES IN CLEAN CONDITION AND FREE
FROM PAINT SPOTS, DUST OR SMUDGES OF ANY NATURE.
1. THE FACILITY IS AN UNOCCUPIED DIGITAL TELECOMMUNICATION FACILITY.
2. PLANS ARE NOT TO BE SCALED AND ARE INTENDED TO BE A DIAGRAMMATIC OUTLINE ONLY, UNLESS NOTED
OTHERWISE. THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND LABOR
NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
15. PENETRATIONS OF ROOF MEMBRANES SHALL BE PATCHED/FLASHED AND MADE WATERTIGHT USING LIKE MATERIALS
IN ACCORDANCE WITH NRCA ROOFING STANDARDS AND DETAILS. CONTRACTOR SHALL OBTAIN DETAILING
CLARIFICATION FOR SITE-SPECIFIC CONDITIONS FROM ENGINEER, IF NECESSARY, BEFORE PROCEEDING.
16. BEFORE ORDERING AND/OR BEFORE FABRICATING/CONSTRUCTING/INSTALLING ANY ITEMS, VERIFY THE TYPES AND
QUANTITIES.
17. CONTRACTOR SHALL PROVIDE SITE FOREMAN WITH A CELLULAR PHONE AND PAGER, AND KEEP SAME ON SITE
WHENEVER PERSONNEL ARE ON SITE.
18. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON THE SITE AND NOTIFY THE PROJECT
MANAGER OF ANY DISCREPANCES BEFORE STARTING ANY WORK.
19. KEEP GENERAL AREA CLEAN, HAZARD FREE, AND DISPOSE OF ALL DIRT, DEBRIS, RUBBISH AND REMOVE
EQUIPMENT NOT SPECIFIED AS REMAINING ON THE PROPERTY. LEAVE PREMISES IN CLEAN CONDITION AND FREE
FROM PAINT SPOTS, DUST, OR SMUDGES OF ANY NATURE.
20. CONTRACTOR TO PROVIDE COMPLETE SET OF AS BUILT DRAWINGS WITHIN 10 WORKING DAYS OF PROJECT
COMPLETION.
21. CONTRACTOR IS TO EXCAVATE 6" BELOW EXISTING GRADE AND SPRAY WITH WEED CONTROL. REPLACE WITH
CLASS II AGGREGATE BASE AND CRUSHED WASHED ROCK. AS SPECIFIED ON SITE PLAN.
22. CONTRACTOR SHALL PROVIDE TOILET FACILITY DURING ALL PHASES OF CONSTRUCTION.
23. PRIOR TO THE COMMENCEMENT OF CONSTRUCTION OR THE FABRICATION OF MATERIALS TO BE INSTALLED AT THE
SITE, THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS INCLUDING AS-BUILT DIMENSIONS OF EXISTING
STRUCTURES OR STRUCTURAL ELEMENTS HAVING A BEARING ON THE SCOPE OF THE WORK TO BE PERFORMED.
IF ANY DISCREPANCY IS FOUND BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND THE
DIMENSIONS OR CONDITIONS FOUND TO BE EXISTING IN THE FIELD, THE CONTRACTOR SHALL NOTIFY THE
ENGINEER AND OBTAIN DESIGN RESOLUTION PRIOR TO PROCEEDING WITH THE PoRTloN(S) OF THE WORK
AFFECTED. THE CONTRACTOR SHALL ASSUME SOLE LIABILITY FOR ANY FAILURE TO SO NOTIFY THE ENGINEER AND
OBTAIN RESOLUTION BEFORE PROCEEDING.
3. PRIOR TO THE SUBMISSION OF BIDS, THE CONTRACTORS SHALL VISIT THE JOB SITE AND BE RESPONSIBLE FOR
ALL CONTRACT DOCUMENTS, FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT THE WORK MAY BE
ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. ANY DISCREPANCIES ARE TO BE
BROUGHT TO THE ADENTION OF THE IMPLEMENTATION ENGINEER AND ENGINEER PRIOR TO PROCEEDING WITH THE
WORK.
4. THE CONTRACTOR SHALL OBTAIN, IN WRITING, AUTHORIZATION TO PROCEED BEFORE STARTING WORK ON ANY ITEM
NOT CLEARLY DEFINED OR IDENTIFIED BY THE CONTRACT DOCUMENTS.
5. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS UNLESS SPECIFICALLY INDICATED OTHERWISE OR WHERE LOCAL CODES OR REGULATIONS TAKE
PRECEDENCE.
6. ALL WORK PERFORMED AND MATERIALS INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE
CODES, REGULATIONS AND ORDINANCES. CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS,
ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE
PERFORMANCE OF THE WORK. MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS, AND LOCAL AND STATE JURISDICTIONAL
CODES, ORDINANCES AND APPLICABLE REGULATIONS.
7. THE GENERAL CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, USING THE BEST SKILLS AND ADENTION.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES,
SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT
INCLUDING CONTACT AND COORDINATION WITH THE IMPLEMENTATION ENGINEER AND WITH THE LANDLORD'S
AUTHORIZED REPRESENTATIVE.
8. SEAL PENETRATIONS THROUGH FIRE RATED AREAS WITH U.L. LISTED AND FIRE CODE APPROVED MATERIALS.
9. PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 2-A OR 2-A1aBC WITHIN 75 FEET
TRAVEL DISTANCE TO ALL PORTIONS OF THE PROJECT AREA DURING CONSTRUCTION.
10. NOT USED.
11. DETAILS ARE INTENDED TO SHOW END RESULT OF DESIGN. MINOR MODIFICATIONS MAY BE REQUIRED TO SUIT
JOB DIMENSIONS OR CONDITIONS, AND SUCH MODIFICATIONS SHALL BE INCLUDED AS PART OF THE WORK.
12. REPRESENTATIONS OF TRUE NORTH, OTHER THAN THOSE FOUND ON THE PLOT OF SURVEY DRAWING (SHEET
LS1), SHALL NOT BE USED TO IDENTIFY OR ESTABLISH THE BEARING OF TRUE NORTH AT THE SITE. THE
CONTRACTOR SHALL RELY SOLELY ON THE PLOT OF SURVEY DRAWING AND ANY SURVEYOR'S MARKINGS AT THE
SITE FOR THE ESTABLISHMENT OF TRUE NORTH, AND SHALL NOTIFY THE ENGINEER PRIOR TO PROCEEDING WITH
THE WORK IF ANY DISCREPANCY IS FOUND BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND
THE TRUE NORTH ORIENTATION AS DEPICTED ON THE CIVIL SURVEY. THE CONTRACTOR SHALL ASSUME SOLE
LIABILITY FOR ANY FAILURE TO NOTIFY THE ENGINEER.
GENERAL CONSTRUCTION NOTES
GROUND
HEADER
HANGER
HEIGHT
ISOLATED COPPER GROUND BUS
INCH(ES)
INTERIOR
PoUND(S)
LAG BOLts
LINEAR FEET (FOOT)
LONG(ITUDINAL)
MASONRY
MAXIMUM
MACHINE BOLT
MECHANICAL
MANUFACTURER
MINIMUM
MISCELLANEOUS
METAL
NEW
NUMBER
NOT TO SCALE
ON CENTER
OPENING
PRECAST CONCRETE
PERSONAL COMMUNICATION SERVICES
PLYWOOD
POWER PROTECTION CABINET
PRIMARY RADIO CABINET
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PRESSURE TREATED
POWER (CABINET)
QUANTITY
RADIUS
REFERENCE
REINFORCEMENT(ING)
REQUIRED
RIGID GALVANIZED STEEL
SCHEDULE
SHEET
SIMILAR
SPECIFICATION(S)
SQUARE
STAI NLESS STEEL
STANDARD
STEEL
STRUCTURAL
TEMPORARY
THICK(NESS)
TOE NAIL
TOP OF ANTENNA
TOP OF CURB
TOP OF FOUNDATION
TOP OF PLATE (PARAPET)
TOP OF STEEL
TOP OF WALL
TYPICAL
UNDER GROUND
UNDERWRITERS LABORATORY
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
WIDE(WIDTH)
WITH
WOOD
WEATHERPROOF
WEIGHT
CENTERLINE
PLATE, PROPERTY LINE
GRND.
HDR.
HGR.
HT.
ICGB.
IN.(")
INT.
LB.(#)
L.B.
L.F.
L.
MAS.
MAX.
M.B.
MECH.
MFR.
MIN.
MISC.
MTL.

N.T.S.
D.C.
oPNG.
PiC
PCS
PLY.
PPC
PRC
P.S.F.
P.S.I.
P.T.
PWR.
QTY.
RAD.(R)
REF.
REINF.
REQ'D.
RGS.
SCH.
SHT.
SIM.
SPEC.
SQ.
S.S.
STD.
STL.
STRUC.
TEMP.
THK.
T.N.
T.oA
T.o.C.
T.o.F.
T.o.P.
T.o.S.
T.o.W.
TYP.
U.G.
U.L.
U.N.o.
V.I.F.
W

W.P.

ANCHOR BOLT
ABOVE
ANTENNA CABLE COVER ASSEMBLY
ADDITIONAL
ABOVE FINISHED FLDOR
ABOVE FINISHED GRADE
ALUMINUM
ALTERNATE
ANTENNA
APPRoXIMATE(LY)
ARCHITECT(URAL)
AMERICAN WIRE GAUGE
BUILDING
BLOCK
BLOCKING
BEAM
BOUNDARY NAILING
BARE TINNED COPPER WIRE
BODoM OF FOOTING
BACK-UP CABINET
CABINET
CANTILEVER(ED)
CAST IN PLACE
CEILING
CLEAR
COLUMN
CONCRETE
CoNNECTloN(oR)
CONSTRUCTION
CONTINUOUS
PENNY (NAILS)
DOUBLE
DEPARTMENT
DOUGLAS FIR
DIAMETER
DIAGONAL
DIMENSION
DRAWING\S)
DOWEL(S
EACH
ELEVATION
ELECTRICAL
ELEVATOR
ELECTRICAL METALLIC TUBING
EDGE NAIL
ENGINEER
EQUAL
EXPANSION
EXISTING
EXTERIOR
FABRICATloN(oR)
FINISH FLOOR
FINISH GRADE
FINISH(ED)
FLOOR
FOUNDATION
FACE OF CONCRETE
FACE OF MASONRY
FACE OF STUD
FACE OF WALL
FINISH SURFACE
FOOT (FEET)
FOOTING
GROWTH (CABINET)
GAUGE
GALVANIZE(D)
GROUND FAULT CIRCUIT INTERRUPTER
GLUE LAMINATED BEAM
GLOBAL POSITIONING SYSTEM
AB.
ABV.
ACCA
Aoo'L
AF.F.
AF.G.
ALUM.
ALT.
ANT.
APPRX.
ARCH.
AWG.
BLDG.
BLK.
BLKG.
BM.
B.N.
BTCW.
B.o.F.
B/U
CAB.
CANT.
C.I.P.
CLG.
CLR.
COL.
CONC.
CONN.
CONST.
CONT.
d
oBL.
DEPT.
o.F.
oiA.
oIAG.
DIM.
oWG.
OWL.
EA.
EL.
ELEC.
ELEV.
EMT.
E.N.
ENG.
EO.
EXP.
EXST.(E)
EXT.
FAB.
F.F.
F.G.
FIN.
FLR.
FON.
F.O.C.
F.O.M.
F.O.S.
F.O.W.
F.S.
FT.(')
FTG.
G.
GA
GI.
G.F.I.
GLB. (GLU-LAM)
GPS
GENERAL NOTES FOR EXISTING AT&T CELL SITES:
ABBREVIATIONS
WOOD BLOCKING
ELECTRIC BOX
WOOD CoNT.
MECHANICAL GRND. CONN.
STEEL
EARTH
PLYWOOD
(E) BRICK
PROPERTY/LEASE LINE
MATCH LINE
(E) MASONRY
EXISTING ANTENNA
WORK POINT
ELECTRICAL CONDUIT
LIGHT POLE
SAND
NEW ANTENNA
ELEVATION REFERENCE
SECTION REFERENCE
FND. MONUMENT
SET POINT
1 1
SPOT ELEVATION
REVISION
DETAIL REFERENCE
CENTERLINE
GRID REFERENCE
TELEPHONE CONDUIT
COAXIAL CABLE
GRAVEL
GROUND CONDUCTOR
CADWELD
GROUND ROD
OVERHEAD SERVICE
CONDUCTORS
CHAIN LINK FENCING
TELEPHONE BOX
GROUT OR PLASTER
CONCRETE
GROUND BUS BAR
GROUND ACCESS WELL

---X---
---T---
--ou---


Q
Q

...--r

w
[!]
V
0
-$-
IJ..
&
0
@

4>
I
i!l#@iSK? tfA
I I
---A---
---E---
touNHUNNONuNJ
Quwamauwa
LEGEND
II
POC CORPORATION
0
100% CONSTRUCTION
FG
RAWING
100% CONSTRUCTION
TB
RAWING
2 CLIENT COMMENTS TB
3
EMOVED T-MOBILE
TB
QUIPMENT
LANNING COMMENTS FG

3140 GOLD CAMP DR, SUITE 30


RANCHO CORDOVA, CA 95670

ONSULTANT:
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868
4430 ROSEWOOD DRIVE
PLEASANTON, CA 94588
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
PROJECT INFORMATION:
REV.:=DATE:=DESCRIPTION:=SY:
nCURRENT ISSUE DATE:
J 08/18/11
ISSUED FOR:
G
SHEET TITLE:
I I
SITE PLAN
60' 0 30' 60' SCALE
1

II
......- i 1" = 60'-0"
EXISTING TREELINE
(TYP.)
NEW AT&T PROJECT AREA
ON GROUND LEVELr-:--,--.--,
EXISTING TREELINE
(TYP.)
1, THIS PROPOSAL IS FOR THE MODIFICATION OF AN EXISTING UNMANNED
TELECOMMUNICATIONS FACILITY CONSISTING OF INSTALLATION OF THE
FOLLOWING: NEW ONE (1) OUTDOOR CABINET (RBA72) AND TWO (2) NEW
PURCELL CABINETS (FLX12WS) MOUNTED ON NEW CONCRETE PAD, NEW
THREE (3) LTE ANTENNAS ADDED TO EXISTING MONOPINE, NEW SIX (6)
RRU'S MOUNTED ON EXISTING MONOPINE, NEW ONE (1) 3" FIBER/POWER
CONDUIT FROM OUTDOOR CABINETS TO RRU'S, NEW SIX (6) RET'S TWO (2)
RET'S PER ANTENNA CONFIGURATION, NEW ONE(l) FIBER/POWER DOME UNIT
(DC6-4B-60-1B-BF) AND NEW ONE (1) AT&T GPS ANTENNA MOUNTED ON
NEW EQUIPMENT CABINET,
2. THE EXISTING FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE
POTABLE WATER OR SEWER SERVICE.
SITE WORK GENERAL NOTES:
GENERAL NOTES:
3. THE EXISTING FACILITY IS UNMANNED AND IS NOT FOR HUMAN HABITAT.
(NO HANDICAP ACCESS IS REQUIRED).
4. OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION,
APPROXIMATELY 2 TIMES PER MONTH, BY AT&T TECHNICIANS.
5. NO NOISE, SMOKE, DUST OR ODOR WILL RESULT FROM THIS PROPOSAL.
6. OUTDOOR STORAGE AND SOLID WASTE CONTAINERS ARE NOT NEW.
7. ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
8. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING ANY DAMAGE
CAUSED BY THE CONSTRUCTION OPERATION.
9. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND
INSPECTION REQUIRED FOR CONSTRUCTION.
10. SUBCONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON
A DAILY BASIS.
11. INFORMATION SHOWN ON THESE DRAWINGS WAS OBTAINED FROM SITE VISITS
AND DRAWINGS PROVIDED BY THE SITE OWNER. SUBCONTRACTOR SHALL
NOTIFY AT&T OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR
PROCEEDING WITH CONSTRUCTION.
SITE PLAN
SCALE NOTE:
IF DIMENSIONS SHOWN ON PLAN DO NOT SCALE CORRECTLY,
CHECK FOR REDUCTION OR ENLARGEMENT FROM ORIGINAL PLANS,
1. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES
WHERE ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES,
AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL
BE RELOCATED AS DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE
USED BY THE SUBCONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND
OR NEAR UTILITIES. SUBCONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR
THE WORKING CREW. THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL
PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING &
EXCAVATION.
2. ALL SITE WORK SHALL BE AS INDICATED ON THE DRAWINGS AND PROJECT
SPECIFICATIONS.
3. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER
REFUSE SHALL BE REMOVED FROM THE SITE AND DISPOSED OF LEGALLY.
4. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY
FROM THE BTS EQUIPMENT AND TOWER AREAS.
5. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND.
FROZEN MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR
EMBANKMENT.
6. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH
UNIFORM GRADE PRIOR TO FINISHED SURFACE APPLICATION.
7. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES,
WHICH INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED
AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH
WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, SUBJECT TO THE
APPROVAL OF ENGINEERING, OWNER AND/OR LOCAL UTILITIES.
8. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT
COVERED BY THE TOWER, EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A
UNIFORM SLOPE AND STABILIZED TO PREVENT EROSION AS SPECIFIED IN THE
PROJECT SPECIFICATIONS.
9. SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING
CONSTRUCTION. EROSION CONTROL MEASURES, IF REQUIRED DURING
CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES FOR
EROSION AND SEDIMENT CONTROL.
10. ADD ELECTRICAL CONNECTIONS IN THE PUBLIC RIGHT OF WAY SHALL BE
INSTALLED UNDERGROUND TO THE NEAREST UTILITY POLE.
11. NO WORK SHALL BE DONE WITHIN THE PUBLIC RIGHT-OF-WAY WITHOUT THE
PRIOR APPROVAL AND PERMIT FROM THE ENVIRONMENTAL AND PUBLIC WORKS
MANAGEMENT DEPARTMENT - ADMINISTRATIVE SERVICES.
12. CONTRACTOR IS RESPONSIBLE FOR REPAIR OF ALL DAMAGED OFFSITE
IMPROVEMENTS CAUSED BY CONSTRUCTION. CALL PUBLIC WORKS INSPECTOR FOR
INSPECTION OF OFFSITE IMPROVEMENTS AT SUBSTANTIAL COMPLETION OF ONSITE
WORK.
13. NO CONSTRUCTION DEBRIS SHALL BE SPILLED OR STORED ONTO PUBLIC
RIGHT-OF-WAY.
14. NO RUNOFF SEDIMENT OR WASTES IS ALLOWED IN WATER LEAVING THE SITE.
15. ALL SITE UTILITIES SHALL BE CONSTRUCTED UNDERGROUND TO THE NEAREST
POLE.
16. ALL LABOR, EQUIPMENT AND MATERIAL REQUIRED FOR OFF-SITE IMPROVEMENTS
ARE THE RESPONSIBILITY OF THE CONTRACTOR.
II
II

0 01/31/11
100% CONSTRUCTION
FG
RAWING
05/09/11
100% CONSTRUCTION
TB
RAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
EMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 LANNING COMMENTS FG
ENLARGED SITE
PLAN

ONSULTANT:
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868

3140 GOLD CAMP DR, SUITE 3D
RANCHO CORDOVA, CA 95670
poe CORPORATION
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
4430 ROSEWOOD DRIVE
PLEASANTON, CA 94588
PROJECT INFORMATION:
REV.:=DATE:=DESCRIPTION:=BY:
SHEET TITLE:
PLANS PREPARED BY:
nCURRENT ISSUE DATE:
J 08/18/11

FOR:
100% CONSTRUCTION
DRAWING
- EXISTING BUILDING -
EXISTING DRIVEWAY
EXISTING AT&T
EQUIPMENT ON EXISTING
CONCRETE PAD
TREES (TYP.)
EXISTING CABLE TRAY
- EXISTING CONCRETE -
NEW 7' -4"x3'
PAD
EXISTING
PORTABLE
GENERATOR
/!1)
Q
NEW ONE (1) 3" FIBER/POWER CONDUIT .-r---
'" UNDERGROUND RUN FROM MAIN UNIT TO '--./
FIBER/POWER DOME UNIT. ALONG EXISTING
'"'
7
I
I
I
I
I
I
I
I
NEW 3'x4'
CONCRETE PAD
NEW TWO (2) AT&T OUTDOOR
CABINETS (FLX12WS) (STACKED)
EXISTING UTILITY RACK
FOR POWER & TELCO
CABINETS
NEW ONE (1) AT&T
OUTDOOR CABINET (RBA72) \.g}-------
EXISTING ELECTRIC VAULT
EXISTING 6'-0" HIGH CHAIN
FENCE WITH RAZOR WIRE
EXISTING SIX (6) AT&T PANEL 1
ANTENNAS TO REMAIN (TYP.-2 PER
SECTOR @ POSITIONS 1 AND 2) A-4
EXISTING 87' HIGH MONOPINE
NEW THREE (3) AT&T LTE ANTENNAS f
MOUNTED ON EXISTING MONOPINE t-
(TYP.-1 PER SECTOR 0 POSITION 3)
1. NEW AT&T CABINET TO BE CONNECTED TO EXISTING
DC POWER, TELCO CABINET & GROUND BAR.
2. NEW AT&T FIBER RUN TO BE MOUNTED ALONG SIDE
OF EXISTING COAX CABLE RUN. (GENERAL
CONTRACTOR TO VERIFY EXACT ROUTE PRIOR TO
CONSTRUCTION)
3. EXISTING AT&T ANTENNAS NOT SHOWN FOR CLARITY
SCALE NOTE:
IF DIMENSIONS SHOWN ON PLAN DO NOT
SCALE CORRECTLY, CHECK FOR REDUCTION
OR ENLARGEMENT FROM ORIGINAL PLANS.
NUA"BER'.2
ENLARGED SITE PLAN j> 1
APV':5]
SAS l
pp
CHK.:
100% CONSTRUCTION
FG
DRAWING
100% CONSTRUCTION
TB
ORAWING
CLIENT COMMENTS TB
REMOVED T-MOBILE
TB
QUIPMENT
PLANNING COMMENTS FG
2 06/16/11
3 07/29/11
poe CORPORATION
1 05/09/11


3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868

'--DRAWN BY:
r-REV.:=DATE:=DESCRIPTION:=BY:=
o 01/31/11
4 08/18/11
;::PLANS PREPARED BY:

t t 8(

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
;:: PROJECT INFORMATION:
II
ISSUED FOR:

-
II
EXISTING
PORTABLE
GENERATOR
;::SHEET TITLE:
EXISTING DOUBLE
EQUIPMENT LAYOUT
SWING ACCESS GATE
J
I
o 3" 6" l'
1 SCALE 1
2

II
--
I
1 3/4" l' 0" 1
EXISTING I
ELECTRIC
VAULT
234'-8"
NEW LEASE AREA
EXISTING
ELECTRIC
VAULT
EXISTING
ELECTRIC
TRANSFORMER
'. THREE (3)

"-,, CONCRETE PAD
"-
"-
"-
i"
i" /.:
I
"If "L'If"1f 'If
D
EW.-J)NM1) 3" FIBER/POWER CONDUIT
"V__..-C-tJuII'll)ERGRDUND RUN FROM MAIN UNIT TO
-/
NEW 7'-4"x3'f1V5\
CONCRETE
NEW 3'x4' (1\('5\
CONCRETE
NEW ONE (1) GPS ANTEN Af3\
MOUNTED ON EXISITNG UTI ITY R Kf-:- \t:!/A-"=.7:-+----.J
NEW EQUIPMENT LAYOUT
1 SCALE 1 1
1 3/4" l' 0" 1
o 3" 6" l'
..._ I
EXISTING
PORTABLE
GENERATOR
J
EXISTING DOUBLE
SWING ACCESS GATE
I
/
EXISTING I
ELECTRIC
VAULT
'If "If 'If
EXISTING
ELECTRIC
VAULT
"If
/
/ EXISTING CABLE TRAY
'If
EXISTING
ELECTRIC
TRANSFORMER
"If
.,.7
.,./
1. NEW AT&T CABINET TO BE CONNECTED TO EXISTING /
DC POWER, TELCO CABINET & GROUND BAR. .,. ----,
2. NEW AT&T FIBER RUN TO BE MOUNTED ALONG SIDE .,./
OF EXISTING COAX CABLE RUN INSIDE MONOPINE. /'
(GENERAL CONTRACTOR TO VERIFY EXACT ROUTE " /'
PRIOR TO CONSTRUCTION) / ....
3. EXISTING AT&T ANTENNAS NOT SHOWN FOR CLARITY .,.
.,./
.,./
.,./
.,./
.,./
.,./
.,./
.,./
.,./
V
SCALE NOTE:
IF DIMENSIONS SHOWN ON PLAN DO NOT
SCALE CORRECTLY, CHECK FOR REDUCTION
OR ENLARGEMENT FROM ORIGINAL PLANS.
EXISTING EQUIPMENT LAYOUT
II
poe CORPORATION
0
100% CONSTRUCTION
FG
RAWING
100% CONSTRUCTION
TB
RAWING
2 CLIENT COMMENTS TB
3
EMOVED T-MOBILE
TB
QUIPMENT
LANNING COMMENTS FG

1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL: (925) 606-5868

3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670
ONSULTANT:
4430 ROSEWOOD DRIVE
PLEASANTON, CA 94588
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
PROJECT INFORMATION:
REV.:=DATE:=DESCRIPTION:=SY:
nCURRENT ISSUE DATE:
J 08/18/11
ISSUED FOR:
NEW SIX (6) AT&T RRU'S
MOUNTED ON EXISTING
MONOPINE (1YP.-2 PER SHEET TITLE:
ANTENNA)
ANTENNA PLANS

LOWER ARRAY
II
0' 6" l' 2' SCALE
2
--
1/2" 1'-0"
UPPER ARRAY
EXISTING SIX (6) AT&T PANEL
ANTENNAS TO REMAIN (TYP.-2 PER
SECTOR @ POSITIONS 1 AND 2)
EXISTING 87' HIGH MONOPINE
NEW AT&T ONE (1) LTE ANTENNA 1
MOUNTED ON EXISTING MONOPINE C'f--'--+-------
POSITION 3 A-5
NEW AT&T ONE (1) LTE ANTENNA 1
MOUNTED ON EXISTING
2. NEW ANTENNA DIMENSION: 52" x 12" x 8"
NOTE:
1. ANTENNA CONFIGURATIONS BASED ON RFOS
REVISION 8.4 DATED 10-18-2010.
NEW AT&T ONE (1) FIBER/POWER
UNgN __-J
RUN AND DC POWER
NEW ANTENNA PLAN 1
SCALE
1/2" 1'-0"
2' 0' 6" l'
.-
EXISTING SIX (6) AT&T PANEL ANTENNAS TO REMAI
(TYP.-2 PER SECTOR @ POSITIONS 1 AND 2)
1. NEW AT&T CABINET TO BE CONNECTED TO
EXISTING DC POWER, TELCO CABINET & GROUND
BAR.
2. NEW AT&T FIBER RUN TO BE MOUNTED ALONG
SIDE OF EXISTING COAX CABLE RUN INSIDE
MONOPINE. (GENERAL CONTRACTOR TO VERIFY
EXACT ROUTE PRIOR TO CONSTRUCTION)
SCALE NOTE:
IF DIMENSIONS SHOWN ON PLAN DO NOT
SCALE CORRECTLY, CHECK FOR REDUCTION
OR ENLARGEMENT FROM ORIGINAL PLANS.
EXISTING ANTENNA PLAN
SCALE NOTE:
IF DIMENSIONS SHOWN ON PLAN DO NOT
SCALE CORRECTLY, CHECK FOR REDUCTION
OR ENLARGEMENT FROM ORIGINAL PLANS.
4430 ROSEWOOD DRIVE
PLEASANTON, CA 94588
1. NEW AT&T CABINET TO BE CONNECTED TO
EXISTING DC POWER, TELCO CABINET & GROUND
BAR.
2. NEW AT&T FIBER RUN TO BE MOUNTED ALONG
SIDE OF EXISTING COAX CABLE RUN INSIDE
MONOPINE. (GENERAL CONTRACTOR TO VERIFY
EXACT ROUTE PRIOR TO CONSTRUCTION)
PROJECT INFORMATION:
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
II
poe CORPORATION
0
100% CONSTRUCTION
FG
RAWING
100% CONSTRUCTION
TB
RAWING
2 CLIENT COMMENTS TB
3
EMOVED T-MOBILE
TB
QUIPMENT
LANNING COMMENTS FG
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868
3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670

ONSULTANT:
REV.:=DATE:=DESCRIPTION:=SY:
SHEET TITLE:
nCURRENT ISSUE DATE:
J 08/18/11
ISSUED FOR:
EXISTING TREE
EXISTING BUILDING
NEW ONE (1) 3" FIBER/POWER CONDUIT RUN ---'i"'l;:;-;;:'<
FROM MAIN UNIT TO FIBER/POWER DOME UNIT
ALONG EXISTING COAX CABLE RUN. ";"
SEE NOTE #2
NEW TWO (2) AT&T OUTDOOR
CABINETS (FLX12WS) (STACKED)I--:-=:--t---:,",=-+------'
EXISTING EQUIPMENT CABINETS
ON CONCRETE SLAB
EXISTING 87' HIGH MONOPINE--__
f--'-+--'--+-----...
(RBA72)
EL. 85'-0"
TOP OF BRANCHES
EL. 86' 0" AG.L.
EL. 93'-0" AG.L.
TOP OF EXISTING AT&T ANTENNAS
EL. 0' 0"
oGROUND LEVEL
EL. 87'-0" AG.L.
oTOP OF EXISTING AT&T MONOPINE
oEXISTING AT&T PANEL ANTENNAS RAD CENTER
EXISTING SIX (6) AT&T PANEL

TO REMAIN (TYP.-2 PER


SECTOR @ POSITIONS 1 AND 2)
NEW THREE (3) AT&T LTE ANTENNAS
( ) MOUNTED ON EXISTING MONOPINE
L,J!TE"--!:A""NT.!.!E"'N""N"'AS"--!:RA"""D--'C"'E"'NwTE"'RL.lJL"'O"'W"'E"R...!A:!CR"'RA"-Y'-'_____ (TYP.-1 PER SECTOR 0 POSITION 3)
_
"P EL. 75'-0" NEW SIX (6) AT&T RRU'S
MOUNTED ON EXISTING MONOPINE

NEW ONE (1) FIBER/POWER


'----1--=----1 18-8F)
MONOPINE FOR FIBER RUN AND
DC POWER
DOUBLE SWING ACCESS
(UPPER ARRAY) $
EL. 85'-0"
EXISTING 6'-0" HIGH CHAIN LINK
FENCE WITH RAZOR WIRE
EL. 93'-0" A.G.L.
TOP OF EXISTING AT&T ANTENNAS
EL. 87'-0" A.G.L.
TOP OF EXISTINEG
L
. $
r---- EXISTING AT&T EQUIPMENT CABINETS
EXISTING 87' HIGH MONOPINE
r-__j--,-+---,---!NEW ONE (1) AT&T
OUTDOOR CABINET (RBA72)
NEW AT&T LTE ANTENNAS RAD CENTER (LOWER ARRAY) $
U
EXISTING AT&T PANEL ANTENNAS RAD CENTER
ONE (1) 3" FIBER/POWER CONDUIT RUN
FROM MAIN UNIT TO FIBER/POWER DOME UNIT
ALONG EXISTING COAX CABLE RUN.
SEE NOTE #2
EXISTING TREE
TOP OF BRANCHES
EXISTING SIX (6) AT&T PANEL
ANTENNAS TO REMAIN
(TYP.-2 PER SECTOR @ POSITIONS
1 AND 2)
( ) EL. 79'-0"
1--:-'-::-+---- ------ .IJII: NEW AT&T RRU RAD CENTER *'
(TYP.-1 PER SECTOR 0 POSITION 3)
NEW ONE (1) FIBER/POWER DOME@
UNIT (DC6-48-18-8F) MOUNTED
EXISTING MONOPINE A-5
NEW SIX (6) AT&T RRU'S
MOUNTED ON EXISTING MONOPINE

ELEVATIONS

NUA"BER' .5
o 2' 4' 8' SCALE 0 2' 4' 8' SCALE
SOUTH ELEVATION __ 1/8" 1'-0" 1 WEST ELEVATION ...- 1/8" 1'-0" 2
II
II
poe CORPORATION
~ L Y L E
0
100% CONSTRUCTION
FG
RAWING
100% CONSTRUCTION
TB
RAWING
2 CLIENT COMMENTS 18
3
EMOVED T-MOBILE
TB
QUIPMENT
LANNING COMMENTS FG
ONSULTANT:
~ I ~

3140 GOLD CAMP DR. SUITE 3D


RANCHO CORDOVA, CA 95670
4430 ROSEWOOD DRIVE
PLEASANTON. CA 94588
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL: (925) 606-5868
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
PROJECT INFORMATION:
REV.:=DATE:=DESCRIPTION:=SY:
nCURRENT ISSUE DATE:
J 08/18/11
ISSUED FOR:
RRU INSTALLATION
3 RRU INSTALLATION
STAND OFF ARM
RING MOUNT
NEW STANO OFF ARM
BY VALMONT (PART NO.: MM01)
OR APPROVEO EQUAL
NEW QUAD UNrvERSAL RING MOUNT
BY VALMONT (PART NO.: UQB4) OR
APPROVEO EQUAL
2 RRU MOUNTING DETAIL
STAND OFF ARM
RING MOUNT
NEW STAND OFF ARM
BY VALMONT (PART NO.: MM01)
OR APPROVEO EQUAL
NEW UNIVERSAL RING MOUNT
BY KENWOOD (PART NO.: T1503KTUA)
OR APPROVEO EQUAL
1 ANTENNA MOUNTING DETAIL
PANEL
ANTENNA
ANTENNA DOWNTILT
MOUNTING KIT
(OPTIONAL)
EXISTING ANTENNA
PIPE MAST
ERICSSON RRUS11
DIMENSIONS. WxDxH: 431x183x452 mm
(17"x7.2"x17.8")
POWER CONSUMPTION: 200 WADS
TOTAL WEIGHT: 55 LBS.
TEMPERATURE: -4D' TO 55' C
ANTENNA MOUNTING DETAIL
II
EQUIPMENT AND
CONSTRUCTION
DETAILS
SHEET TITLE:
RRU SPECS 5
L.:::::::::::=
================:::::::::=:::::=====================================================================::J~ I S H E E T NUAMSER: .6
~
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
0 01/31/11
100% CONSTRUCTION
FG
DRAWING
1 05/09/11
100% CONSTRUCTION
TB
DRAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
REMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 PLANNING COMMENTS FG
PREPARED BY:
PDC CORPORATION

r-REV.:=DATE:=DESCRIPTION:=BY:=

t t 8(

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
;:: PROJECT INFORMATION:
II
ISSUED FOR:
jJs
..sc 4ai22 M8IhodA. Xe.rclI.A-c 2'130 1'rl3
eEl lEe 6107J.-'2 -0 "des 3"= t.l3!i!'i
C;OI 80' c.
linlmum Ccrr:lnLou5 Cperalln;J\':>iiue ,U.I
'WEIGHT
Svs-tern: 8,9 l:::s ($'-.01
: j3,9 11:6 N)
To:.l: (141.45 \\
Stand"'! 0 'Mod.lle lib (4.4.5 \),
STANDARDS
r,,,, f(:tllc,..)lr,.;;
510.-1'(;9 Prot error! ;Je\' ce
- ANSJtU_1449 - 3-d 6=Jition
- [EO C52.Ll
- 'EfJA LS-1 r 13: Gt43-1 :2C03 2,-d Edi:i::n:
- IS::
- :'1 (ndud '9
CfI Ccr ntc1i:xl Meltlcd
COMBINED WIND LOACINO
150rnIJ 1 ;_ 105',7 N)
19Srnp1 (:ijL:s.t/: 21:::.l.:Ilbs \9_C \J,
DC6-48-60-18-8F
DC Power Surge Protection

elJ
147(: rrrn:
DC64860188F SPECS
DG57 W/ WEED GUARD-
FABRIC UNDERNEATH
.- ...
.- ....:
.-
<.
.- ..
.- ..
.- .
I 1
;(
8" THICK CONCRETE SLAB
WITH #4 REINFORCING BAR
@ 12" D.C. EACH WAY
, :.::.:' /;;:: ': f-:-:-....,........,..,:----'----'--:------'------'
f' ".A:/ .'ill"... :". ." .".. '.
_;_;"'-:----;:,..:..... :.L." ....::.:..;_: ...!L. ... :----'") ':_.'-:....,..,.----;:"'"-._.'--':"-:"'-,
.".,., ... .':'J';"'. ,,""'''.:,''.'':
MILS MOISTURE BARRIER
AND 2 1/2" SAND BED FOR
SLAB ON GRADE
: Z
N '"
PER PLAN
6. INSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR SHALL BE
PER MANUFACTURER'S WRITIEN RECOMMENDED PROCEDURE. THE
ANCHOR BOLT, DOWEL OR ROD SHALL CONFORM TO
MANUFACTURER'S RECOMMENDATION FOR EMBEDMENT DEPTH OR AS
SHOWN ON THE DRAWINGS. NO REBAR SHALL BE CUT WITHOUT
PRIOR ENGINEERING APPROVAL WHEN DRILLING HOLES IN CONCRETE.
EXPANSION BOLTS SHALL BE PROVIDED BY RAMSET/REDHEAD OR
APPROVED EQUAL, UNLESS NOTED OTHERWISE.
7. GRAVEL SHALL BE NATURAL OR CRUSHED STONE WITH 100%
PASSING 1 INCH SIEVE.
8. DIMENSIONS SHOWN ARE EXACT MINIMUM PAD SIZES REQUIRED FOR
EQUIPMENT LAYOUTS - CONTRACTOR MAY ROUND UP TO THE
NEAREST FOOT (OR HALF FOOT) IF LEASE AREA AND SPACE PERMIT.
EXISTING GRADE
(VARIES)
CONCRETE PAD DETAIL
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301,
ACI 318, ACI 336, ASTM A184, ASTM A185 AND THE DESIGN AND
CONSTRUCTION SPECIFICATION PER CAST-IN-PLACE CONCRETE.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF
2500 PSI AT 28 DAYS, UNLESS NOTED OTHERWISE.
3. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60,
DEFORMED UNLESS NOTED OTHERWISE. WELDED WIRE FABRIC SHALL
CONFORM TO ASTM A185 WELDED STEEL WIRE FABRIC UNLESS
NOTED OTHERWISE. SPLICES SHALL BE CLASS "B" AND ALL HOOKS
SHALL BE STANDARD, UNO.
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED
FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON DRAWINGS:
CONCRETE CAST AGAINST EARTH 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
IN.
CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT
CAST AGAINST THE GROUND:
SLAB AND WP.J.L 3/4 IN.
BEAMS AND COLUMI>lS l 1/2 IN.
5. A CHAMFER 3/4" SHALL BE PROVIDED AT ALL EXPOSED EDGES OF
CONCRETE, UNO, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4.
CONCRETE AND REINFORCING STEEL NOTES:
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868
APV':5]
SAS l PP
CHK.:
3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670


'--DRAWN BY:
TITLE:
EQUIPMENT AND
CONSTRUCTION
DETAILS

NUMBER:
II
15
A7
PAD

jNf:N CONCRETE
L\
<l
I
EPOXY NEW 64 DOWELS ----______
o 12"
EXISTING CONCRETE I \

CONCRETE PAD CONNECTION
1 HILTI KWIK BOLT
TZ WITH 2 1/2" (MIN.)
EMBEDMENT DEPTH PER
ICC-ESR #1917
b
WASHER, LOCK
WASHER, FLAT
I INSULATING WASHER
r
CABINET
CABINET ANCHORAGE
I 3
CONTINUOUS BEAD OF
SILICONE SEALANT @
TOP OF UNISTRUT
(TYP.)
,---- EXISTING UTILITY RACK
POST
o -rnflp--f--- SECURE TO CABINET
ILI..l WITH BOLT
(TYPICAL OF 2)
GPS ANTENNA
PIPE CLAMP TO
UNISTRUT
COAX
CONNECTION '"
CUSHION
ASSEMBLY Il!....l....
1/2" COAXIAL-
CABLE TO EQUIPMENT
1 1/4" PIPE------l
, SKY
SURFACE AREA OF A HEMISPHERE AROUND THE GPS ANTENNA.
2. ALL GPS ANTENNA LOCATIONS MUST BE ABLE TO RECEIVE CLEAR
SIGNALS FROM A MINIMUM OF FOUR (4) SATELLITES. VERIFY WITH
HANDHELD GPS BEFORE FINAL LOCATION OF GPS ANTENNA.
3. THE WEIGHT OF THE ANTENNA MOUNT IS 6.5 LBS.
. IF ICE BRIDGE OR SIMILAR POST IS NOT GROUNDED, GROUND WITH
#2 AWG TINNED BARE COPPER WIRE EXOTHERMICALLY BONDED TO
POST AND CONNECTED TO GROUND RING.
GPSANTENNA
24"
30"
-RBA72 CABINET-
RBA72 EQUIPMENT DETAILS AND SPECS
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
0 01/31/11
100% CONSTRUCTION
FG
DRAWING
1 05/09/11
100% CONSTRUCTION
TB
DRAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
REMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 PLANNING COMMENTS FG
;::PLANS PREPARED BY:

POC CORPORATION
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL: (925) 606-5868
r-REV.:=DATE:=DESCRIPTION:=BY:=

t t 8(

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
;:: PROJECT INFORMATION:
II
ISSUED FOR:
1 1
30"
I RBA72 CABINETI
II I
-RBA72 CABINET
Il J
FRONT DOOR-
[ ]
t;J
z
[ ] (jj

NU SWING HANDLE- -i
"N WITH PADLOCK
"
HASP
[ ]

rn
'"
[ ]
[ ]
I I
I I
RBA72 ELEVATION
0
I
-SWING HANDLE
WITH PADLOCK
HASP
-FRONT DOOR
-
RBA72 CABINET
RBA72 ELEVATION f:\
------\V
36.1"
RBA72 CABINET-
I
o
o
2" CONDUIT KNOCKOUTS --0
(4) PLACES ON LEFT AND RIGHT SIDES 0
(6) PLACES LOWER REAR
(6) PLACES CABINET FLOOR
4
A-7
-
FRONT OOOR
REAR MOUNTING ------If--O
HOLES (2)
FRONT MOUNTING _-<J
HOLES (2)
I
I NOTE:
II EQUIPMENT WEIGHT 1900 LBS

APV':5]
SAS l
pp
CHK.:
3140 GOLD CAMP DR. SUITE 30
RANCHO CORDOVA. CA 95670

'--DRAWN BY:
-FRONT DOOR
-SWING HANDLE
FLX12WS CABINET
20"
r-

1---6" DEMARC BOX
__-.-__ 1 ---.!tJ;;"---L1FTING EYE
-. BOLT
'" N
o -6" DEMARC
BOX
H--FRONT DOOR
o
FLX12WS CABINET
24"
SWING- n
HANDLE 1]
_----. n-E-lIFTING EYE
-. BOLT
'" N
J
FLX12WS CABINET
@
" 1'------.---'1
FRONT
24"
I
I NOTE: III
II EQUIPMENT WEIGHT = 350 LBS EACH II
FLX12WS FRONT ELEVATION 0 FLX12WS SIDE ELEVATION (;:;\

15.5"
EQUIPMENT MOUNTING
12RU 19" RAILS. FRONT TO BACK
ADJUSTABLE
CONSTRUCTION MATERIALS
MATERIAL: ALUMINUM (LIGHTWEIGHT.
CORROSION-RESISTANT
PAINT: GR-487 TESTED & CERTIFIED
POWER COAT
DOOR/SIDE PANEL CONSTRUCTION
DOOR: FRONT DOOR WITH DOOR ALARM AND
OPTIONAL AIR CONDITIONER, HEAT EXHANGER,OR
THERMOELECTRIC COOLER
LATCHES: TWO-POINT LATCHED, PAD LOCKABLE
FLX12WS EQUIPMENT DETAILS AND SPECS
ENVIRONMENTAL OPTIONS
THERMOELECTRIC COOLER: 400W @ O'dT, +24VDC,
-48VDC OR 120VAC
AIR CONDITIONER: UP TO 2.000 BTU/HR AIR
CONDITIONER WITH HEATER
HEAT EXCHANGER: UP TO 39W/'C HEAT EXCHANGER,
+24VDC OR -48VDC
CABLE ENTRY
(3) 1/2"; (3) 1"; (1) 2" 31/2" OR 2" KNOCKOUTS
AC POWER OPTIONS
30A-MAIN POWER WITH OPTIONAL TRANSIENT VOLTAGE
SURGE PROTECTION. 15A GENERATOR CONNECTION CABLE
6-POSITION 19" RACK-MOUNTED (1 RU) OR 12-POSITION
(2U) AC LOAD CENTERS AVAILABLE IN VARIOUS
CONFIGURATIONS- CAN BE EQUIPPED WITH SURGE
PROTECTION DEVICES THAT OCCUPY 1-POSITION OR
2-POSITIONS AND 6-POSITION DIN-MOUNTED AC BREAKER
PANEL (120V OR 240V CONFIGURATIONS). OPTIONAL
DIN-MOUNTED TVSS
15A GFCI DUAL OUTLET RECEPTACLE CONVENIENCE OUTLET
MOUNTING OPTIONS
4" PLINTH
14" PLINTH
POLE MOUNT KIT
WALL MOUNT KIT
VERTICAL CABINET-ON-CABINET STACKING
LO 0..Jf--
VIEW IS LOOKING DOWN AT TOP OF PLINTH
(PLINTH SKIRT EXTENSION NOT SHOWN).
PLINTH BOLT DOWN PAillRN
;::SHEET TITLE:
EQUIPMENT AND
CONSTRUCTION
DETAILS

12
II
APV':5]
SAS l
pp
CHK.:
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD EOF 1-280
LOS ALTOS HILLS, CA64022


0 01/31/11
100% CONSTRUCTION
FG
DRAWING
05/09/11
100% CONSTRUCTION
TB
DRAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
REMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 PLANNING COMMENTS FG
PREPARED BY:
1062 CONCANNON 8LVD.
LIVERMORE, CA 94550
TEL, (925) 606-5868
POC CORPORATION

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
PROJECT INFORMATION:
3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670
r-REV.:=DATE:=DESCRIPTION:=BY:=
'--DRAWN BY:
II
ISSUED FOR:
/
<'l

EXISTING I
ELECTRIC
VAULT
EXISTING
PORTABLE
GENERATOR
.. ; ... ;,..
"'-
"'-
"'-
!"';.j,--------EXISTING AT&T
.;: EQUIPMENT ON EXISTING
:.<, H-FRAME

7
E-2
l' HIGH
EXISTING
ELECTRIC
VAULT
.,.7
.,./
.,./
.,./
EXISTING AT&T EQUIPMENT;.- ---,. /
ON EXISTING H-FRAMt.
EXISTING
EXISTING
ELECTRIC
TRANSFORMER
..... ,
................,.: CABINETS ON EXISTING
"'- '\ CONCRETE PAD
"'-
"
"'-
"'-
. I
NEW TWO (Z) AT&T OUTDOOR(2Y4\
CABINETS (FLX12WS)
NEW ONE (1) GPS ANTENNA(3V1O\
MOUNTED ON EXISITNG \. A-7 A A-7 )
UTILITY RACK
I-
NEW 3'.4' (1V5'\
CONCRETE PAD
EXISTING
PORTABLE
GENERATOR
EXISTING I
ELECTRIC
VAULT
EXISTING
ELECTRIC
VAULT
.,.7
.,./
.,./
.,./
EXISTING AT&T ---,./
ON EXISTING H-FRAMt.
NEW 7'-4"'.3' f1V5\
CONCRETE PAD .,./
.,./
.,./
.,./
.,./
EXISTING
ELECTRIC
TRANSFORMER
NEW (Z) 1-1/Z"_ CONDUIT------,<
FOR EACH FLX1ZWS CABINET .,./
(4 CONDUITS TOTAL) /
(RBA72) '., .: : '.' ..; EXISTING AT&T
.. .. .. EQUIPMENT ON EXISTING

AT&T
I " " " " " " GPS ANTENNA
"'-
"'-
"'-
.. ,
EXISTING l' HIGH ,.,;.,,;,:.,>'.':;':.',
" i"
"'-
"'-
m", '"
"'-,b:.... ;-.-:"'.;.C""' 7;;!<,.':
"'- CONCRETE PAD
"'-
"'-
"'-
"'-
I
NEW ONE (1) GPS ANTENNA(3V1O\
MOUNTED ON EXISITNG UTILITY RACK
I-
NEW 3'.4' (1V5'\
CONCRETE PAD
NEW TWO (Z) AT&T OUTDOOR(2Y4\
CABINETS (FLX1ZWS)
1. NEW AT&T CABINET TO BE CONNECTED TO EXISTING
DC POWER, TELCO CABINET & GROUND BAR,
Z, NEW AT&T FIBER RUN TO BE MOUNTED ALONG SIDE
OF EXISTING COAX CABLE RUN INSIDE MONOPINE,
(GENERAL CONTRACTOR TO VERIFY EXACT ROUTE
PRIOR TO CONSTRUCTION)
II
EQUIPMENT POWER
AND
GROUNDING PLANS
TITLE:
J
EXISTING DOUBLE
SWING ACCESS GATE
-If
D
NEW ONE (1) 3" FIBER/POWER CONDUIT
UNDERGROUND RUN FROM MAIN UNIT TO
FIBER/POWER DOME UNIT. ALONG EXISTING
/ COAX CABLE RUN. SEE NOTE H2.

J
EXISTING DOUBLE
SWING ACCESS GATE
-If /.
D
NEW ONE (1) 3" FIBER/POWER CONDUIT
UNDERGROUND RUN FROM MAIN UNIT TO
FIBER/POWER DOME UNIT. ALONG EXISTING
/ COAX CABLE RUN. SEE NOTE HZ,

.. NUNiE.1
II
CNU3657
LTE SITE: CCL03657
FA. #: 10067475 USID: 85230
PUISSIMA HILLS WATER
ARASTRADERO RD E OF 1-280
LOS ALTOS HILLS, CA 64022
-REV.:=DATE:=DESCRIPTION:=BY:=
0 01/31/11
100% CONSTRUCTION
FG
bRAWING
1 05/09/11
100% CONSTRUCTION
TB
bRAWING
2 06/16/11 CLIENT COMMENTS TB
3 07/29/11
rEMOVED T-MOBILE
TB
QUIPMENT
4 08/18/11 PLANNING COMMENTS FG
=PLANS PREPARED BY:

PDC CORPORATION

t9at&t

4430 ROSEWOOD DRIVE


PLEASANTON, CA 94588
= PROJECT INFORMATION:
nCURRENT ISSUE DATE:
J 08/18/11
ISSUED FOR:

TYPE TA TYPE VB IYE.E......E..l .IYEE......G.B

1 3 EXOTHERMIC CONNECTIONS 1 4
@
I
:SILICON
SEAL
AT
TOP
DUAL CADWELDS, TO----./
BE USED WITH #2 AWG
BCW TO GROUND RING
'------- 1" PVC SEALTITE----"
@
NOTE:
1. CONTRACTOR TO UTILIZE KOPR-SHIELD & BETTS) ON
ALL LUG CONNECTIONS. OR APPROVED EQUAL
2. ALL LUGS TO BE DUAL HOLE LONG BARREL AND \\1TIH
TOOL T\\1CE.
3. WEATHER PROOFING SHALL BE (TYPE AND PART
NUMBER AS SUPPLIED OR RECOMMENDED BY
CABLE MANUFACTURER.)
#2 AWG FROM EQUIPMENT
TO BE ..J'A'--
NOTES:
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND
AND ALWAYS DIRECT GROUND WIRE DOWN TO
GROUND BAR.
2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER
AS SUPPLIED OR RECOMMENDED BY CABLE
MANUFACTURER.
GROUND BAR\
1 2 GROUNDING BAR DETAIL
1
BOTTOM OF TOWER
r
2 BOLT PARALLEL CROSS RUN UNIVERSAL PIPE CLAMPS
SPLICER CLAMP .15L.1...Z5

7/1'!;(D) 3/4:', @,

-j',.,.::::'
o 0-"''0 0
@OD DO
3 ' ' 1
, 1" TOP OF TOWER

3 ,
2' 00"'0:::'
""'-"'"-,""'.0-,' 0 or 0 0 0
@: DO
, 1"
LEGEND
4
COPPER GROUND BAR, 1/4"X 4"X 10", NEWTON INSTRUMENT CO.
CAT. NO. B-6142 OR EQUAL. HOLE CENTERS TO MATCH NEMA
DOUBLE LUG CONFIGURATION. (ACTUAL GROUND BAR SIZE WILL
VARY BASED ON NUMBER OF GROUND CONNECTIONS)
INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-4 OR EQUAL
TYPICAL GROUND BAR
CD
o 5/B" LOCKWASHERS, NEWTON CO. CAT. NO. 3015-B OR EQUAL
o WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO. CAT NO.
A-6056 OR EQUAL
o 5/8-11 X 1" HHCS BOLTS, NEWTON INSTRUMENT CO. CAT NO.
3012-1 OR EQUAL
f.\ INSULATORS SHALL BE ELIMINATED WHEN BONDING DIRECTLY TO
'.V TOWER/MONOPOLE STRUCTURE. CONNECTION TO TOWER/MONOPOLE
STRUCTURE SHALL BE PER MANUFACTURERS RECOMMENDATIONS.
INOTE: ALL HARDWARE TO BE STAINLESS STEEL I
12. IF EQUIPMENT IS IN A C.L. FENCE ENCLOSURE, GROUND
ONLY CORNER POSTS AND SUPPORT POSTS OG GATE. IF
CHAIN LINK LID IS USED, THEN GROUND LID ALSO.
13. GROUNDING @ PPC CABINET SHALL BE VERTICALLY
INSTALLED.
14. ALL GROUNDING FOR ANTENNAS SHALL BE CONNECTED
SO THAT IT WILL BY-PASS MAIN BUSS BAR.
15. ALL EMT RUNS SHALL BE GROUNDED AND HAVE A
BUSHING. NO PVC ABOVE GROUND.
16. USE SEPARATE HOLES FOR GROUNDING @ BUSS BAR.
NO "DOUBLING-UP" OF LUGS.
17. POWER AND TELCO CABS. SHALL BE GROUNDED
(BONDED) TOGETHER.
18. NO "LB'S" ALLOWED ON GROUNDING RUNS.
11. GROUNDING ATIACHMENT TO TOWER SHALL BE AS PER
MANUFACTURER'S RECOMMENDATIONS OR AT GROUNDING
POINTS PROVIDED (2 MINIMUM).
1. ALL DETAILS ARE SHOWN IN GENERAL TERMS. ACTUAL
GROUNDING INSTALLATION REQUIREMENTS AND
CONSTRUCTION ACCORDING TO SITE CONDITIONS.
2. ALL GROUNDING CONDUCTORS: #2 AWG SOLID BARE
TINNED COPPER WIRE UNLESS OTHERWISE NOTED.
3. GROUND BAR LOCATED IN BASE OF EQUIPMENT WILL BE
PROVIDED, FURNISHED AND INSTALLED BY THE VENDOR.
4. ALL BELOW GRADE CONNECTIONS: EXOTHERMIC WELD
TYPE, ABOVE GRADE CONNECTIONS: EXOTHERMIC WELD
TYPE.
5. GROUND RING SHALL BE LOCATED A MINIMUM OF 24"
BELOW GRADE OR 6" MINIMUM BELOW THE FROST LINE.
6. INSTALL GROUND CONDUCTORS AND GROUND ROD
MINIMUM OF 1'-0" FROM EQUIPMENT CONCRETE SLAB,
SPREAD FOOTING, OR FENCE.
7. EXOTHERMIC WELD GROUND CONNECTION TO FENCE
POST: TREAT WITH A COLD GALVANIZED SPRAY.
8. GROUND BARS: A. EQUIPMENT GROUND BUS BAR (EGB)
LOCATED AT BOTIOM OF ANTENNA POLE/MAST FOR
MAKING GROUNDING JUMPER CONNECTIONS TO COAX
FEEDER CABLES SHALL BE FURNISHED AND INSTALLED BY
ELECTRICAL CONTRACTOR. JUMPERS (FURNISHED BY
OWNERS) SHALL BE INSTALLED AND CONNECTED BY
ELECTRICAL CONTRACTOR. B. MAIN GROUND BUS BAR
(MGB) LOCATED NEAR THE BASE OF THE RADIO
EQUIPMENT CABINET(S) SHALL BE FURNISHED AND
INSTALLED BY ELECTRICAL CONTRACTOR.
9. ALL GROUNDING INSTALLATIONS AND CONNECTIONS SHALL
BE MADE BY ELECTRICAL CONTRACTOR.
10. OBSERVE N.E.C. AND LOCAL UTILITY REQUIREMENTS FOR
ELECTRICAL SERVICE GROUNDING.
GROUNDING NOTES
APV':5]
SAS l PP
CHK.: --DRAWN BY:
1062 CONCANNON BLVD.
CA 94550
TEL: (925) 606-5B68
3140 GOLD CAMP DR, SUITE 30
RANCHO CORDOVA, CA 95670

=CONSULTANT:
UNISTRUT P1000 x 6"
LONG ATIACHED TO
NEW UNISTRUT COAX
CABLE HORIZONTAL
SUPPORT WITH
APPROPRIATE FITIINGS
#2 AWG BCW
(TYP. 2 PLACES)
UNISTRUT COAX CABLE
HORIZONTAL SUPPORT
12" TO 24"
I
NEW GPS ANTENNA
FINISHED GRADE
HARGER # 1OPS STEEL
WELL COVER
WEATHERPROOFING KIT I
(SEE NOTE 3) -------
CABLE GROUND KIT
#6 AWG STRANDED COPPER GROUND
WIRE (GROUNDED TO GROUND BAR)
(SEE NOTE 1 & 2)
ANTENNA CABLE
LOOP-UP #2, SOLlD-
FOR TO ACCESS
FOR TESTlNG
CONN. OF CABLE GRND KIT TO ANT. DETAIL
1 BOI T PARA! I [I UNIVERSAl PipE CI AMpS
.QLAME .5llli2.

CAST "r" SpliCER 1 AOI T PARA!! EI
.QLAME
MECHANICAL CONNECTIONS 1 5
I / NEW CABINET BASE
r---l=\o;--yl/ rNEW SLAB
NEW
EQUIP.
CABINET
LEGEND:
- EXOTHERMIC CONNECTION LU
\g7
- MECHANICAL TYPE CONNECTION LU
\g7
NOTES:
1. THIS IS A DIAGRAMMATIC REPRESENTATION ONLY. SEE GROUNDING
PLAN FOR SITE-SPECIFIC GROUNDING LAYOUT AND COMPONENTS.
2. SEE GROUND NOTES FOR ADDITIONAL INFORMATION.
3. USE #2/0 AWG, BCW FOR GROUND LEADS FROM BUS BARS TO
GROUND RING.
4. USE #2 AWG, BCW FOR BURIED GROUND LOOP AND GROUND
LEADS.
5. THE NUMBER AND SIZE OF GROUND BARS USED MAY PER SITE
CONDITIONS.
TYP. SYSTEM GROUNDING SCHEMATIC 17 GROUND ROD DETAIL 18 GROUND ROD WI TEST WELL 9 GPS ANTENNA GROUNDING 110
l #2 AWG, GREEN INSULATED FOR GROUND
FROM CABINET TO MAIN GROUND BAR
(TYP. OF 2)
0000000 00 00000
LEADS
#2 AWG BCW
TO CIGBE
GROUND BAR
(CIGBE)
=SHEET TITLE:
GROUNDING NOTES
AND DETAILS
II

ELECTRICAL NOTES:
t t
1. PROVIDE A MIN. 36" WORK CLEARANCE
1. PER MANUFACTURER'S RECOMMENDATIONS.
TO MAIN BREAKERS
1
8
IN FRONT OF PANELS/SERVICE EQUIP. 8(
2. E.C. SHALL MODIFY BRANCH CIRCUIT ARRANGEMENT
1
2. ALL BREAKERS IN THE ELEC. PANEL ARE

AS SHOWN IN THE PANEL SCHEDULE RATED 10.000 RMS SYMMETRICAL AMPS.
4430 ROSEWOOD DRIVE
240V MAX. 7S' C U.N.O.
PLEASANTON. CA 94S88
PANEL CIRCUIT SERVICE: 120 / 240 VN; lPH :SW
;::PROJECT INFORMATION:
AND DESIGNATION: 3. ALL WIRING SHALL BE COPPER 7S' C U.N.O.
LOAD SCHEDULE LOCATION: N/A
CONDUIT REQUIREMENTS (TYP. U.N.O.):
CNU3657
4.
LOAD LOAD PER PHASE (VA.)


.
LOAD PER PHASE (VA) LOAD UNDERGROUND: PVC (SCHED 40 OR 80) FROM EXISTING LTE SITE: CCL03657

.

,0.

S
DESCRIPTION

PHASE :;; :;;

PHASE DESCRIPTION INDOOR: EMT (RGS IN TRAFFIC AREAS) TRANSFORMER
FA. #: 10067475 USID: 85230
A B C N

A B C
OUTDOOR (ABOVE GRADE): RGS. 120/240V. IPH. 3W
1 BLANK - - - - - - - - - - - - 21lA 0-f-- -o21lA - - - - - - - - - - - - BLANK 2 PUISSIMA HILLS WATER
3 U'HTS ,
- - - - - X 21lA , - - - -0-::0-f-- -o"'J:o-- - - - , 21lA - X - lBD - ,Be , (E) GFl 4
ARASTRADERO RD E OF 1-280
5 -o----r--o- f-- -o----r--o-- 6
LOS ALTOS HILLS, CA 64022
(E) 850 BTS ,
2680 1440 - - - X 40A 2 - - - - - - 2 31lA - - - - - - - 1VSS
EXISTING CONDUIT AND
...-L--. ...-L--.
II
7
"
- - - ' ....D - - - - - - -----<5 '1lA 0-f-- -0'1lA 0------ - - - - - - - - - -
"
8 WIRING
9 (E) 1900 8TS ,
28BO 1440 - - - X 40A 2 - - - -o----r--o- f-- -o----r--o-- - - - 2 '1lA - - - - - - , SPARE 10
...-L--.
11
"
- - - ' ....D - - - - - - -----<;51lA0-I-- - - - - - - - - - - - -
"
12

-o----r--o- -0 I
dl
EXISTING GENERATOR
13 (E) UMTS , 2700 1350 - - - X 51lA 2 - - - f-- - - - - - - - - - - - - BLANK 14 EXISTING MTS 200A/240V PLUG 240V-200A
...-L--.
I
ISSUED FOR:
15
"
- - - '35D - - - - - -----<5 31lA 0-f-- -0 - - - - - - - - - - - - 16
MAIN BREAKER ARRANGEMENT I---
WITH SLIDE BAR LOCKING SURGE SUPPRESSOR ATLANTIC
100% CONSTRUCTION I 17 (E) PURCELl. , 1800 1800 - - - - 31lA , - - - -0-:;;;0-I-- -0 - - - - - - - - - - - - 18 DEVICE. (SERVICE RATED) SCIENTIFIC (#1401 N)
G) 19
NEW RM72 1 33llll - ,... - - X
'"
2

- -o----r--o- f-- -0 - - - - - - - - - - - - 20
'---rI
DRAWING CA8lN..
21
"
- - ,... - - - -

- f-- -0 - - - - - - - - - - - - 22
1/2"C. 3#10. 1#8GND 40A

r-REV.:=DATE:=DESCRIPTION:=BY:=
G) 23
NEW RBA.72 , 33llll - ,... - - X
'"
2
- -o----r--o- f-- -0 - - - - - - - - - - - - 24 0-- CA8lN..

EXISTING 42KHC 200A 120/240 MARCONI-
25
"
- - ,... - - - - - I-- -0 - - - - - - - - - - - - 26 PPC CABINET "PP1". UL APPROVED 0--
---
EXISTING AT&T 24-POSITION LOADEB 0 01/31/11
100% CONSTRUCTION
FG
DRAWING
@
NEW REM,72 (LOCATED INSIDE EXISTING EQUIPMENT 0--
---
CENTER INSIDE EXISTING CABINET _
27 CA8lN..
,
'200 '2OD - - - X
'"
,
- f-- -0 - - - - - - - - - - - - 28
COMPOUND @ GRADE) 0--
---
[PANEL 1-A] 100% CONSTRUCTION
0->-------0
1 OS/09/11
DRAWING
TB
29 BLANK - - - - - - - - - - - - - - - - - - - - - - - - 30 0--
---
I SUBTOTAL CONTINUOUS - - - '.D - SUBTOTAL
TOTAL KVA
0--
--- ADD NEW 2 POLE. 40A BREAKER FOR EB 2 D6/16/11 CLIENT COMMENTS TB CONTINUOUS D.2
ISUBTOTAl... NON-CONTINUOUS SUBTOTAL
CONTINUOUS x 1.25
3/4"C, 3118, 1118GND

---
(N) EQUIPMENT IN EXISTING BLANK _
0""
,_
NON CONTINUOUS REMOVED T-MOBILE
TOTAL KVA [lS']

POSITIONS 19 AND 21 3 07/29/11 TB
VOLTAGE: 120 / 240 CYCLE: 6D PHASE: , WIRES: 3
MANUFACTURER: NON-CONTINUOUS 19.9
---
QUIPMENT
NEW AT&T 3/4"C, 3118, 1#8GND NEUTRAL;
"RBAn" [lS']

ADD NEW 2 POLE, 40A BREAKER FOR EB
4 08/18/11 PLANNING COMMENTS FG TYPE AND CATALOG NUIolBER: -
MAIN BREAKER: "'I.e.: 42,000 I TRIP: 2<lOA lOTAL KVA 20.1
OUTDOOR
3/4"C. 2118. 1118GND
'4oA
---- (N) EQUIPMENT IN EXISTING BLANK -
MAIN LUGS: 250 At,lPS MAIN COPPER BUS:
NO EQUAl....: APPROVED EQUAL.: EQUIPMENT
[lS'] POSITIONS 23 AND 2S PREPARED BY:
TOTAl... AIolPS 53.SA CABINET
MAINS: TOP - BeTTO" - 1ol0UNllNG: SURFACE_ FLUSH -- I PDC CORPORATION
G)INsrAlL (N) 2 POLE 40A BREAKER(S) IN BlANK POSITIONS TO .. AIC RATING OF NEW BREAKER
@
ADD NEW 1 POLE, 40A BREAKER---l

FEED THE NEW CABINET(S) IN POSITION(S) 19. 21, AND 23. TO MATCH EXISTING FOR (N) EQUIPMENT IN EXISTING
25 loS SHOWN ABOVE AND PER PLAN. BLANK POSITION 27
@INsrAlL (N) 1 POLE 40A BREAKER(S) IN BlANK POSITIONS TO
EB
FEED THE NEW CABINET(S) IN POSITION(S) 27 loS SHOWN

ABOVE AND PER PLAN.


1062 CONCANNON BLVD.
LIVERMORE, CA 94550
TEL: (925) 606-586B
EXISTING PANEL SCHEDULE (BREAKER ASSIGNMENT PPC CABINET)
I
1 SINGLE LINE DIAGRAM
I

2

L .... L E
3140 GOLD CAMP DR, SUITE 3D
RANCHO CORDOVA, CA 9S670
'--DRAWN BY: CHK.:
APV':5]

pp
I
SAS l
TITLE:
PANEL SCHEDULE
AND
SINGLE LINE DIAGRAM

II