Convective Flow due to Stack Effect

One way to ventilate a building that is hotter or colder on the inside than outside is to use what is known as "stack effect". Because of the temperature difference, the air inside the building is either more or less dense than the air outside. If there is an opening high in the building and another low in the building, a natural flow will be caused. If the air in the building is warmer than the outside, this warmer air will float out the top opening, being replaced with cooler air from outside. If the air inside is cooler than that outside, the cooler air will drain out the low opening, being replaced with warmer air from outside. One common use for stack effect would be nighttime flushing of a building's interior, to cool it for the next day. The rate at which air flows depends on several factors, the inside and outside air temperatures, the area of the openings, and the height difference between the top and bottom openings. The 1997 ASHRAE Fundamentals handbook gives the following relationship:
Q = 60 * Cd * A * sqrt(2 * g * (Hn - Hb) * ((Ti - To) / Ti)) where Q = flow rate in cfm, Cd = 0.65 (for unobstructed openings), A = opening area, square feet, Ti = indoor temp (Rankine), To = outdoor temp (Rankine), Hn = height of "neutral pressure point" (for simple systems, assume 1/2 way between top and bottom openings). Hb = height of bottom opening g = gravity.

To calculate flow rate, fill in the boxes below. Area:


2

square feet.
10 85 70

Height difference:

feet. F. F

Indoor Temperature: Flow Rate:


0

Outdoor Temperature:

CFM.

For a more complete discussion of this, and especially of unusual situations, please see the discussion in the ASHRAE Fundamentals handbook. You might want to compare the flow rates of this natural ventilation to those of forced ventilation. For example, a typical "whole house fan", available at Home Depot for $130, is rated at 4500 CFM (but consumes about 200 watts of electricity). Note also that for stack effect, flow rate diminishes as the ventilation proceeds, bringing the temperature difference down. The purpose of ventilation is to flush the indoor space out with outdoor air. As the outdoor air replaces indoor air, it either adds heat to or removes heat from the inside space. Knowing the flow rate, the specific heat of air, the density of air, and the temperature difference, we can calculate the effective heating or cooling rate, and express the result in BTU per hour, or BTUH (for reference, air conditioners are often rated in "tons" of cooling capacity, one ton being 12,000 BTU per hour): Heat Transfer Rate:
0

BTUH, which is about

Watts.

You can see that the potential for stack effect cooling is rather low, compared to mechanical refrigeration. However, it does work, has no moving parts, and requires no extra energy input. Consider it as part of a complete plan that includes a significant effort to reduce daytime heat gain (especially from the sun). An interesting variation on this theme is the so-called "solar chimney". Imagine that at the top of the building, air flows through a duct that is heated by the sun. The added height and temperature difference could combine to significantly increase air flow, if designed carefully

Flujo convectivo debido a Stack Efecto


Una manera de ventilar un edificio que est ms caliente o ms fro en el interior que en el exterior es utilizar lo que se conoce como "efecto de chimenea". Debido a la diferencia de temperatura, el aire en el interior del edificio es ms o menos denso que el aire exterior. Si hay una alta apertura en el edificio y bajo otro en el edificio, un flujo natural ser causado. Si el aire en el edificio es ms caliente que el exterior, este aire ms clido flotar fuera de la abertura superior, siendo reemplazado con aire ms fro desde el exterior. Si el aire es ms fresco en el interior que en el exterior, el aire fro se drenar la apertura baja, siendo reemplazado por aire ms caliente del exterior. Un uso comn de efecto de chimenea sera lavado en la noche de interior de un edificio, para que se enfre para el da siguiente. La velocidad a la que fluye el aire depende de varios factores, las temperaturas del aire dentro y fuera de, el rea de las aberturas, y la diferencia de altura entre las aberturas superior e inferior. El 1997 ASHRAE Fundamentals manual da la siguiente relacin:
Q = 60 * Cd * A * sqrt (2 * g * (Hn - Hb) * ((Ti - To) / Ti)) donde Q = tasa de flujo en pies cbicos por minuto, Cd = 0,65 (para las aberturas obstruidas), A = rea de la abertura, pies cuadrados, Ti = temperatura interior (Rankine), To = temperatura exterior (Rankine), Hn = altura del "punto de presin neutral" (para los sistemas simples, supongamos 1/2 camino entre la parte superior y las aberturas inferiores). Hb = altura de la abertura inferior g = gravedad.

Para calcular la tasa de flujo, rellene las siguientes casillas. rea:


2

metros cuadrados.
10 85 70

Diferencia de altura: temperatura interior: Temperatura exterior: Velocidad de flujo:


0

pies. F. F CFM.

Para una discusin ms completa de esto, y especialmente de situaciones inusuales, por favor vea la discusin en el manual ASHRAE Fundamentals. Es posible que desee comparar los caudales de la ventilacin natural para los de ventilacin forzada. Por ejemplo, un tpico "ventilador para toda la casa", disponible en Home Depot por $ 130, tiene una potencia de 4500 CFM (pero consume unos 200 vatios de electricidad). Tenga en cuenta tambin que para efecto de chimenea, flujo de agua disminuye a medida que avanza de ventilacin, con lo que la diferencia de temperatura hacia abajo. El propsito de la ventilacin es para limpiar el espacio interior con el aire exterior. A medida que el aire exterior reemplaza aire interior, o bien aade calor a o elimina el calor del espacio interior. Conociendo la velocidad de flujo, el calor especfico del aire, la densidad del aire, y la diferencia de temperatura, se puede calcular el calentamiento efectivo o la velocidad de enfriamiento, y expresar el resultado en BTU por hora, o BTUH (para referencia, acondicionadores de aire son a menudo clasificado en "toneladas" de capacidad de refrigeracin, una tonelada de ser 12.000 BTU por hora): Tasa de transferencia de calor:
0

BTUH, que es aproximadamente

Watts.

Se puede ver que el potencial de enfriamiento pila efecto es ms bien baja, en comparacin con la refrigeracin mecnica. Sin embargo, tiene trabajo, no tiene partes mviles y no requiere aporte de energa extra. Considrelo como parte de un plan completo que incluye un esfuerzo importante para reducir la ganancia de calor durante el da (especialmente del sol). Una variacin interesante de este tema es el llamado "chimenea solar". Imagine que en la parte superior del edificio, el aire fluye a travs de un conducto que es calentado por el sol. La altura aadido y diferencia de temperatura podran combinarse para aumentar de manera significativa el flujo de aire, si se disean con cuidado.

Natural Ventilation Systems


Example 4
Size the fresh air intake and shaft outlet openings for the building shown below.

(a)

Use the formulae given below to calculate the openings based on summer temperatures and compare this with the results given in Figure 5.3, given in the text. (b) Use Figure 5.4 to estimate winter opening areas required for spring and winter conditions. (c) Calculate air velocity rates at fresh air intakes in summer and winter.

DATA: The rooms measure 12 m x 12 m x 4m high. Occupancy = 60 people

Summertime: hour in summer.

The flow rate required for each Office is 8 air changes per This is to reduce internal temperature rise due to heat

gains. Spring & Winter: The flow rate required for each Office is 3 air changes per hour. This is to supply occupants with sufficient fresh air calculated as follows; 8 l/s/person x 60 people = 480 l/s = 0.48 m3/s = 1728 m3/h / room volume 576 m3 = 3 AC/h The inside and outside spring temperatures are 10oC and 0oC respectively. The inside and outside winter temperatures are 21oC and 0oC respectively. ANSWER (a): Air flow rate for each room / 3600 m3/s

Q Q Q

= = =

Room volume x Air change rate 12 x 12 x 4 x 8 / 3600 576 x 8 / 3600 = 1.28

A = Q / Cd [ ( 2 / ins) ins . g . (h npl h) (Tins - Tout / Tins ) ]


Fresh Air Openings: For Ground floor room; A = 298 / 301 ) A = A = A = A = 1.28 / 0.61 [ ( 2 / 1.1656 ) 1.1656 x 9.81 ( 14 2) ( 301 1.28 / 0.61 [ 1.716 x 1.1656 x 9.81 x 12 x 0.00997 ] 1.28 / 0.61 [ 0.19557 x 12 ] 1.28 / 0.61 x 2.347 0.89 m2.

For First floor room; A = 1.28 / 0.61 [ 0.19557 . (14 6 ) ]

A A A

= = =

1.28 / 0.61 [ 0.19557 x 8 ] 1.28 / 0.61 x 1.565 1.34 m2.

For Second floor room; A A A A = = = = 1.28 / 0.61 [ 0.19557 . (14 10 ) ] 1.28 / 0.61 [ 0.19557 x 4 ] 1.28 / 0.61 x 0.782 2.68 m2.

Stack Outlet Opening: Air flow rate for each room Total air flow rate Q = Q total = 1.28 m3/s 1.28 x 3

3.84 m3/s

A outlet = Q total / Cd [ ( 2 / ins) ins . g . (h h npl) (Tins Tout / Tins ) ]


A = 298 / 301 ) A = A = A = A = A = 3.84 / 0.61 [ ( 2 / 1.1656 ) 1.1656 x 9.81 ( 16 14) ( 301 3.84 / 0.61 [ 1.716 x 1.1656 x 9.81 x 2 x 0.00997 ] 3.84 / 0.61 [ 0.19557 x 2 ] 3.84 / 0.61 x 0.391 3.84 / 0.2385 16.1 m2.

A table can be drawn to accommodate data for summer time. Inside to outside temperature difference = 28oC - 25oC =

3deg.C

Building Level

Air flow rate (Q) (m3/s)

Area (A) by Calculation (m2)

Height from opening to NPL (m)

Q/A from graph below (m3/s/m2)

Ground floor fresh air opening First floor fresh air opening Second floor fresh air opening Stack outlet

1.28 1.28 1.28 3.84

0.89 1.34 2.68 16.10

12 8 4 2

0.92 0.77 0.55 0.37

ANSWER (b): A table can be drawn for spring and winter conditions. The air flow rate from DATA = 0.48 m3/s Spring inside to outside temperature difference = 0oC = 10deg.C Winter inside to outside temperature difference = 0oC = 21deg.C

10oC 21oC -

Building Level

Air flow rate (Q) (m3/s) 0.48

Height from opening to NPL (m) 12

Condition Spring Winter Spring Winter Spring Winter Spring Winter

Q/A from graph below (m3/s/m2) 1.75 2.50 1.40 2.05 1.00 1.45 0.51 0.75

A/Q 0.571 0.400 0.714 0.488 1.000 0.690 1.961 1.333

Area Gra = A/Q (m

Ground floor fresh air opening First floor fresh air opening Second floor fresh air opening

0.2

0.1

0.48

0.3

0.2

0.48

0.4

0.3

Stack outlet

1.44

2.8

1.9

Note that the fresh air and stack outlet areas required in winter are less than in spring. Also the spring and winter areas are much less than the summer areas. This means that automatic dampers would need to be used to change the air flows.

ANSWER (c): Air velocity (m/s) = (m2) Volume flow rate (m3/s) / Cross sectional area

Building Level

Condition Summer

Air flow rate (Q) (m3/s) 1.28 0.48 1.28 0.48 1.28 0.48

Area by Grap (m2) 1.39 0.19 1.66 0.23 2.33 0.33

Ground floor fresh air opening

Winter Summer
First floor fresh air opening

Winter
Second floor fresh air opening

Summer Winter

It would be important to check that the velocity in winter does not exceed comfort criteria in the room. The manufacturers catalogue for the fresh air intake louvres should give appropriate data.

Sistemas de ventilacin natural


La ventilacin natural es la ventilacin sin la ayuda de ventiladores y otros equipos mecnicos de aire en movimiento. La ventilacin natural utiliza ninguna energa o poca energa por lo tanto reduce los costos de construccin en ejecucin. El aire se mueve naturalmente debido a la flotabilidad efecto cuando existe una diferencia de temperatura y se eleva aire menos denso. Esto se llama el efecto de chimenea . El aire tambin se mueve sin ayuda por el viento. Estos efectos pueden ser utilizados en un edificio para crear un "libre" sistema de ventilacin que no requiere ventiladores.

Algunos sistemas incorporan ventiladores y son parcialmente ventilacin natural, pero con un mayor grado de control.

Los sistemas naturales de ventilacin de uso


En edificios grandes, donde grandes cantidades de aire se deben cambiar en las habitaciones, la ventilacin natural se puede utilizar si se utilizan caractersticas especiales. Tambin es el edificio comercial debe ser el sistema de ventilacin controlada para cumplir los criterios de confort en las habitaciones. Esto se puede lograr por cuidado diseo del edificio y usar la tecnologa para proporcionar una ventilacin adecuada. El siguiente diagrama muestra una distribucin del edificio que utiliza el efecto de chimenea para aumentar la ventilacin natural.

Salidas de escape a nivel del techo puede ser disfrazada o utilizado como una caracterstica del diseo de los edificios, como se muestra a continuacin.

Rejillas de ventilacin de bajo nivel se muestra a continuacin

Otro sistema de ventilacin natural utiliza el sol para ayudar al movimiento del aire. Los ejes verticales en el edificio son frente de vidrio de modo que el sol calienta el aire en su interior y hace que se eleve fuera de las aberturas al nivel del techo. Las aberturas de alto nivel en este caso son las chimeneas de acero inoxidable. Cuando el aire sale de las chimeneas de aire de reemplazo techo plano se extrae de las habitaciones en el eje y por lo tanto ventilado naturalmente. Esto se muestra a continuacin.

Una de las dificultades con ventilacin natural es que los edificios deben ser diseados especialmente para incorporar caractersticas para ayudar al flujo de aire, estas caractersticas no se ven muy bien desde el interior y el exterior y se disfrazan a veces.

Eficacia
La eficacia de la ventilacin natural para edificios comerciales depende de varios criterios. Se trata de la fuerza del viento y direccin , tamao de las aberturas, las temperaturas del aire y la altura del edificio . Para una ventilacin controlada efectiva el diseador no debe basarse nicamente en el viento, pero ms en el efecto de chimenea y controles de aire . Amortiguadores se puede utilizar para controlar introduciendo aire y / o salir de un sistema de ventilacin natural.

Estos amortiguadores podra estar relacionado con sensores de presencia, sensores de temperatura, temporizadores y otros sensores meteorolgicos para dar un control automtico de ventilacin que es la clave para un sistema til. El diagrama a continuacin muestra algunas de las caractersticas de un sistema de ventilacin natural para un edificio de cuatro pisos.

Diseo de sistemas de ventilacin natural


CIBSE gua Manual de aplicaciones AM10 (1997) La ventilacin natural en los edificios no da detalles de diseo. Seccin 4.2 de AM10 da detalles de cmo controlar los sistemas de ventilacin natural. Seccin 5 proporciona mtodos de clculo de los caudales de ventilacin efecto impulsada por el viento y la pila

Pila Clculos Driven ventilacin


Pila clculos de ventilacin de la forma ms simple ignorar los efectos del viento , aunque estos pueden tenerse en cuenta en un anlisis ms complejo.

Las presiones desarrolladas en los sistemas de pila se puede determinar a partir de la siguiente frmula.

P s = T ins )
donde; P s = ins = g = h1 = h2 = dato (m) T fuera = T ins =

- ins . g. T ins (h 2 - h 1 ) (1 / T hacia fuera - 1 /

Stack Efecto de la presin (Pa) Densidad del aire en el interior de la pila (kg / m 3 ) debida a la gravedad (9,81 m / s Aceleracin 2 ) Altura de la entrada de la pila por encima de dato (m) Altura de la toma de corriente de la pila por encima de Temperatura del aire exterior de la pila ( o K) Temperatura del aire en el interior de la chimenea ( o K)

La siguiente ecuacin se puede usar para determinar las tasas de flujo de aire en la ventilacin accionada pila o las reas de apertura deseada.

Q = Cd.A T salida / T ins ) ]

[ (2 / insins . g. (H npl - h) (T ins -

donde; Q = Caudal de aire a travs de una abertura grande (m 3 / s) Cd = coeficiente de descarga (0,61 para las aberturas grandes) A = rea de apertura (m 2 ) ins = Densidad del aire en el interior de la pila (kg / m 3 ) g = debida a la gravedad (9,81 m / s Aceleracin 2 ) h npl = Altura del nivel de presin neutral por encima de referencia (m) h = altura de la abertura superior de referencia (m) T fuera = Temperatura del aire exterior de la pila ( o K) T ins = Temperatura del aire en el interior de la chimenea ( o K)

Nivel de Presin Neutral


Aqu es donde la presin exterior es igual a la presin interna. En este nivel no habra flujo de aire dentro o fuera del edificio.

Esto es por lo general hasta lo alto de un edificio de lo contrario el efecto chimenea no funcionaba. El nivel de presin neutral para la mayora de los edificios es de unos 0,25 metros sobre el nivel del techo de la planta superior.

Temperaturas
Las temperaturas de las habitaciones internas necesitan ser calculados desde las ganancias de calor en verano elevar la temperatura ambiente. Esto se puede hacer usando software donde la temperatura verano se puede predecir requeridos junto con las tasas de flujo de aire para mantener las temperaturas de las habitaciones a niveles aceptables. El Hevacomp paquete de software y otros programas pueden ser utilizados. Temperaturas fuera de verano se puede obtener de la gua CIBSE Una seccin 2. Parecera que la temperatura exterior en verano rara vez supera los 27 o C , y si la temperatura se eleva por encima de 27 o C es slo para un mximo de 4 das en el sur deInglaterra y menos de un da en el norte de la Reino Unido Si una chimenea solar se utiliza para ayudar a la presin de succin pila entonces la temperatura en el interior de la pila tendra que ser alterado. Es importante para obtener temperaturas precisas dentro y fuera desde esta diferencia crea la fuerza impulsora dentro de la pila o la diferencia de presin para mover el aire hasta la pila hacia el exterior.

Ejemplo 1
Calcular el rea de la abertura de ventilacin previstos en un sistema de ventilacin de la pila para el edificio se muestra a continuacin.

DATOS: El caudal que se requiere cada habitacin es de 4 cambios de aire por hora. Cada aula mide internamente 24 mx 10 mx 4 m de alto. RESPUESTA: El caudal de aire de cada habitacin Q = volumen x habitacin Aire tasa de cambio / 3600 Q = 24 x 10 x 4 x 4 / 3600 Q = 960 x 4 / 3600 = 1.07 m 3 / s

Reorganizacin de la frmula anterior para el rea (A) da;

A = Q / C d [ (2 / ins ) ins . g. (H npl - h) (T ins T salida / T ins ) ]


Para el sitio de la planta baja; A = 1,07 298/301) A = 1,07 ] A = 1,07 A = 1,07 A = 1,121 m 2 . / 0,61 [ (2 / 1,1656) 1,1656 x 9,81 (9-1) (301 a

/ 0,61 [ 1,716 x 1,1656 x 9,81 x 8 x 0,00997 / 0,61 [0,19557 x 8] / 0,61 x 1,565

Para el sitio de la primera planta; A 301) A A A = 1,07 / 0,61 [ (2 / 1.1656) 1.1656 x 9,81 (9-5) (301-298 /

= 1,07 / 0,61 [0,19557 x 4] = 1,07 / 0,61 x 0,782 = 2,242 m 2 .

Nota: El piso superior tiene menos presin de succin pila para aberturas son ms grandes.

Ejemplo 2
Calcular el rea de la abertura de ventilacin requerido y el tamao de la lumbrera de aire fresco se requiere en un sistema de ventilacin de la pila para el edificio se muestra a continuacin.

DATOS: El caudal requerido para la sala de clase es de 10 cambios de aire por hora. La habitacin mide internamente la clase 18 mx 10 mx 4 m de alto. The Fresh louvre aire tiene un rea de 50% gratis. RESPUESTA: El caudal de aire de cada habitacin Q = volumen x habitacin Aire tasa de cambio / 3600 Q Q s = = 18 x 10 x 4 x 10 / 3600 720 x 10 / 3600 = 2,0 m 3 /

Reorganizacin de la frmula anterior para el rea (A) da;

A = Q / C d [ (2 / ins ) ins . g. (H npl - h) (T ins T salida / T ins ) ]


A = 296/299) A = A = A = 2,0 / 0,61 [ (2 / 1.1605) 1.1605 x 9,81 (8-1) (299 -

2,0 / 0,61 [ 1,723 x 1,1605 x 9,81 x 7 x 0,01003] 2,0 / 0,61 [1,377] 2,0 / 0,84

= 2,38 m 2 rea de aire fresco necesario

El aire fresco del Louvre tiene un rea libre del 50% por lo que el tamao de las lamas es; Louvre area = rea de aire fresco / (porcentaje de rea libre / 100) Louvre rea = 2,38 / (50 / 100) Louvre rea = 4,76 m 2 .

Chimenea de salida
La abertura en la parte superior de una pila puede ser dimensionado de una manera similar a las entradas de aire fresco. La diferencia de altura en la frmula es entre la NPL y la salida de la chimenea. El flujo a travs de la salida de la chimenea es la suma de todos los flujos a travs de las habitaciones en un edificio a cargar la pila.

Una salida = Q totales / (T ins - T salida / T ins ) ]

C d [ (2 / ins ) ins . g. (H - h npl )

donde; Q totales = total de aire caudal a travs de la chimenea (m 3 / s) Cd = coeficiente de descarga (0,61 para las aberturas grandes) Una salida = salida Stack zona (m 2 ) ins = Densidad del aire en el interior de la pila (kg / m 3 ) g = debida a la gravedad (9,81 m / s Aceleracin 2 ) h npl = Altura del nivel de presin neutral por encima de referencia (m) h = Altura de la salida de la chimenea por encima de referencia (m) T fuera = Temperatura del aire exterior de la pila ( o K) T ins = Temperatura del aire en el interior de la chimenea ( o K)

Ejemplo 3

Calcular la salida de la chimenea rea de abertura requerida en el sistema dado en el Ejemplo 1.

DATOS: El caudal que se requiere cada habitacin es de 4 cambios de aire por hora. Cada aula mide internamente 24 mx 10 mx 4 m de alto. RESPUESTA: Caudal de aire por cada habitacin Q = en Ex.1) Flujo total de aire tipo Q totales = 3 m /s 1,07 m 3 / s (ya aplicado 1,07 x 2 = 2,14

Una salida = Q totales / (T ins - T salida / T ins ) ]


A = 2,14 298/301) A = 2,14 7] A = 2,14 A = 2,14 A = 8,97 m 2 . /

C d [ (2 / ins ) ins . g. (H - h npl )

0,61 [ (2 / 1.1656) 1.1656 x 9.81 (11 - 9) (301 a

/ 0,61 [ 1,716 x 1,1656 x 9,81 x 2 x 0,0099 / 0,61 [0,19557 x 2] / 0,61 x 0,391

Accesorios de cada de presin


En un anlisis riguroso de un sistema de ventilacin de la pila de la cada de presin de herrajes, tales como la ingesta y lumbreras de escape no debe exceder la presin de accionamiento de la pila y la pila de cada de presin. La conduccin a presin (dP s ) se puede encontrar a partir de la frmula al comienzo de esta seccin y la cada de presin de la pila y los accesorios se puede determinar por el mtodo normal para los accesorios de conductos.

Utilizando las curvas de Q / A


Las curvas siguientes se pueden utilizar para calcular las tasas de flujo de aire si las reas de aberturas son conocidos.

Sistemas de ventilacin natural

Ejemplo 4
Tamao de la entrada de aire fresco y aberturas de salida del eje para el edificio se muestra a continuacin. (A) Utilizar las frmulas dadas a continuacin para calcular las aberturas basado en las temperaturas del verano y compararlo con los resultados dados en la figura 5.3, que figura en el texto. (B) Utilice la Figura 5.4 para estimar las reas necesarias para la apertura de invierno y primavera condiciones invernales. (C) Calcular las tasas de velocidad del aire en las entradas de aire fresco en el verano y el invierno.

DATOS: La habitaciones miden 12 mx 12 mx 4 m de altura. Ocupacin = 60 personas Verano: El caudal requerido para cada oficina es de 8 cambios de aire por hora en verano. Esto es para reducir el aumento de la temperatura interna debido a las ganancias de calor. Primavera e invierno: El caudal requerido para cada oficina es de 3 cambios de aire por hora.

Esto es suministrar ocupantes con suficiente aire fresco calcula como sigue; 8 l / s / persona x 60 personas = 480 l / s = 0,48 m 3 / s = 1728 m 3 / h / volumen de la sala 576 m 3 = 3 AC / h Las temperaturas de la primavera en el interior y el exterior son 10 o C y 0 o C, respectivamente. Las temperaturas de invierno, dentro y fuera de los 21 o C y 0 o C, respectivamente. Respuesta (R): El caudal de aire de cada habitacin Q Aire tasa de cambio / 3600 Q = Q = 8 / 3600 =

volumen x habitacin

12 x 12 x 4 x 8 / 3600 576 x 1,28 m 3 / s

A = Q / C d [ (2 / ins ) ins . g. (H npl - h) (T ins - T salida / T ins ) ]


Las aberturas de aire fresco: Para el sitio de la planta baja; A = 1,28 298/301) A = 1,28 7] A = 1,28 A = 1,28 A = 0,89 m 2 . / 0,61 [ (2 / 1.1656) 1.1656 x 9.81 (14 - 2) (301 a

/ 0,61 [ 1,716 x 1,1656 x 9,81 x 12 x 0,0099 / 0,61 [0,19557 x 12] / 0,61 x 2,347

Para el sitio de la primera planta; A A A A = 1,28 / 0,61 [0,19557. (14 - 6)] = 1,28 / 0,61 [0,19557 x 8] = 1,28 / 0,61 x 1,565 = 1,34 m 2 .

Por segunda habitacin del piso; A A A A = 1,28 / 0,61 [0,19557. (14 - 10)] = 1,28 / 0,61 [0,19557 x 4] = 1,28 / 0,61 x 0,782 = 2,68 m 2 .

Pila abertura de salida: Caudal de aire por cada habitacin Q = Flujo total de aire tipo Q totales = 3 3 = 3,84 m / s 1,28 m 3 / s 1,28 x

Una salida = Q totales / (T ins - T salida / T ins ) ]


A = 3,84 298/301) A = 3,84 ] A = 3,84 A = 3,84 A = 3,84 A = 16,1 m 2 . /

C d [ (2 / ins ) ins . g. (H - h npl )

0,61 [ (2 / 1.1656) 1.1656 x 9.81 (16 - 14) (301 a

/ 0,61 [ 1,716 x 1,1656 x 9,81 x 2 x 0,00997 / 0,61 [0,19557 x 2] / 0,61 x 0,391 / 0,2385

Una tabla se puede extraer para dar cabida a los datos de la hora de verano. Dentro de diferencia de temperatura exterior = 28 o C 25 o C = 3deg.C Caudal de aire (Q) (M 3 / s) Altura desde la apertura hasta NPL (M) Q / A en el grfico a continuacin (M 3 / s / m 2 )

Edificio Nivel

Zona (A) por Clculo (M 2 )

Abertura en el piso de tierra aire fresco Planta primera abertura de aire fresco Segundo piso abertura de aire fresco Pila de salida

1,28 1,28 1,28 3,84

0,89 1,34 2,68 16,10

12 8 4 2

0,92 0,77 0,55 0,37

RESPUESTA (b): Una tabla se pueden extraer para la primavera y las condiciones invernales. La tasa de flujo de aire desde DATOS = 0,48 m 3 / s Dentro de primavera a diferencia de la temperatura exterior = 10 o C -0oC = 10deg.C

Dentro de Invierno a diferencia de la temperatura exterior 0oC = 21deg.C

21 o C -

Edificio Nivel

Q / A en el Altura desde Caudal de grfico a la apertura aire (Q) Condicin continuacin hasta NPL 3 (M / s) (M 3 / s / (M) m 2) 0,48 12 Primavera Invierno Primavera Invierno Primavera Invierno Primavera Invierno 1,75 2,50 1,40 2,05 1,00 1,45 0,51 0,75

AQ/

rea Grf =A/Q (m

Abertura en el piso de tierra aire fresco Planta primera abertura de aire fresco Segundo piso abertura de aire fresco

0,571 0,400 0,714 0,488 1,000 0,690 1,961 1,333

0,2

0,1

0,48

0,3

0,2

0,48

0,4

0,3

Pila de salida

1,44

2,8

1,9

Tenga en cuenta que las zonas de aire fresco y la pila de salida requerida en invierno son menos que en primavera. Tambin las zonas de primavera e invierno son mucho menores que las reas de verano. Esto significa que los amortiguadores automticos tendra que ser usado para cambiar los flujos de aire.

RESPUESTA (c): Velocidad del aire (m / s) = seccin transversal (m 2 ) Volumen de caudal (m 3 / s) / rea de la

Edificio Nivel

Condicin Verano Invierno Verano Invierno Verano Invierno

Caudal de aire (Q) (M 3 / s) 1,28 0,48 1,28 0,48 1,28 0,48

rea de Grfico (M 2 ) 1,39 0,19 1,66 0,23 2,33 0,33

Abertura en el piso de tierra aire fresco Planta primera abertura de aire fresco Segundo piso abertura de aire fresco

Sera importante comprobar que la velocidad en invierno no supera los criterios de confort de la habitacin. El catlogo del fabricante para las rejillas de entrada de aire fresco debe dar informacin adecuada