xEnergy Switchboards
Valid from April 2006
Reliably and safely controlling, switching and managing power. In industry, in buildings and in machine construction. Innovative protection concepts. With built-in diagnostics and communication functions. Housed in modern switchboard systems.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Of course, we all like the idea of progress, but often what we really need are tangible, practical solutions innovations we can implement and use right now. And that is precisely why Moeller has developed xEnergy. This new switchboard system has been designed so that you can configure your projects efficiently to meet your own specific requirements from planning and assembly to installation. It provides the ideal basis for building infrastructures up to 4000 A. xEnergy cleverly combines switching and protective devices, mounting systems and enclosure components, so that you can work quickly and efficiently in your workshop and easily integrate future innovations as they arise. Ideal modules, intelligent system platform Is it possible to bridge the divide between increasingly stringent technological and safety requirements on the one hand, and
cost reduction on the other? Moellers answer to this question is a resounding 'Yes' and it has developed the latest generation of switchboard systems to prove its point. Moellers new xEnergy system range thinks ahead by allowing for tomorrows requirements today. The xEnergys switching and protective devices, mounting and switchboard systems together form a single technical and cost-effective economic unit that offers you the best in power management, switching and control. How does it work? Quite simply: the new systems modular design allows for a wide range of intelligent combinations. That means you save time, money and space. And because you can also rely on Moellers excellent reputation for safety, you can implement individual projects in functional buildings or office and industrial buildings simply, quickly and flexibly.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Functionality is a fundamental, individuality is the future The xEnergy switchboard system consists of IEC/EN 60439 type-tested function modules. These have an internal separation up to Form 4, and comply with various national or regional installation requirements, such as DIN VDE, CEI, NF or UNE. This means you can design customised solutions for use in several different countries. The xEnergy system offers you a wide range of options for implementing power distribution reliably, economically and fully in accordance with your customers requirements. You can use feeder and coupling sections for circuit-breakers up to 4000 A, and individually equipped outgoer sections with fixed compartment modules for switching and protective devices up to 630 A. Outgoer sections up to 630 A for switch-fuse strips, fuse rails and fuse switch-disconnectors are also available. Control sections and empty sections can be combined as required for installing ancillary components such as motor starters, PFC modules, frequency inverters, soft starters or for automa-
tion solutions. The mounting systems for rail-mounted service installation devices can be used in conventional service distribution boards. The express list allows fast projecting of the most frequent applications without using any additional aids such as catalogues or Confix.
Projecting is simply carried out on the functional level. 1. 2. 3. 4. Select the function Select the current rating Type of network Panel elements
4 steps = 4 article numbers - that's all you need to plan your section. The switchboard can be delivered either as "flat pack" or fully assembled.
IZM and NZM circuit-breakers for xEnergy power sections n Type-tested switchgear assemblies (TTA) up to 4000 A n Clear and symmetrical design with only one circuit-breaker per section reduces the number of busbar connections and saves mounting requirements n Internal separation up to Form 4 increases personnel and system protection n Fast and direct allocation of circuit-breaker mounting kits for the mechanical fastening of circuit-breakers n High level of flexibility in the terminal area thanks to alternative connection options
NZM and PKZ circuit-breakers for xEnergy outgoer sections n 3-pole and 4-pole switching and protective devices, type-tested switchboard systems (TTA) up to 630 A n Max. 38 fixed compartment modules in one section (H 50 mm), optimum device utilisation despite high packing density n Flexible module mounting to Form 4 with different device mounting depths, however with standard operating front n Simple module mounting to Form 2 on one mounting depth n Highly flexible combination possible for functional areas and busbars in accordance with IEC/EN 60439 and national installation practice
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
xEnergy Switchboards
Switchboards
Power sections Outgoing sections Empty sections Optional equipment
Page 2 ff.
Page 3 Page 6 Page 10 Page 13
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
1
xEnergy Switchboards
xEnergy - Summary
Type-tested switchgear assemblies (TTA) in accordance with IEC/EN60439-1 Designed for Moeller switchgear Suitable for TN-C, TN-C-S, TN-S, TT and IT network systems Main busbar systems, rear-mounted, up to 3200 A Clear separation into functional units of Form 2b or 4b for increased protection against contact with live parts and passage of solid foreign bodies Degree of protection IP 31 or IP 55 Height 2000 mm Colour RAL 7035
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
2
xEnergy Switchboards
Power Sections for Incomers and Outgoers with Open Circuit Breakers 800 - 3200 A
IZM Power Sections
VT05506
Form 4
For cable connection from below For busbar position at the rear top Height of section - 2000 mm / depth of section - 600 mm Each XSI.. section requires 2 XBSB.. main busbar supports
Ie up to (A) Icc up to (400 V AC) (kA) Degree Type of Prot. Designation Article No. Units per package
425 600
IZMB(N)1-...
800-1600 65
1 1 1 1 1 1
IZMB(N)1-... 800-1600 65 IZMB(N,H)2-... 800-3200 100 IZMB(N)1-... 800-1600 65 IZMB(N,H)2-... 800-3200 100
800
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
3
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Power Sections for Incomers and Outgoers with Compact Circuit Breakers 800 - 1600 A
NZM4 Power Sections
VT06106
Form 2
For cable connections from below For busbar position at the rear top Height of section - 2000 mm / depth of section - 600 mm Each XSN.. section requires 2 XBSB.. main busbar supports
Ie up to (A) Icc up to (400 V AC) (kA) Degree Type of Prot. Designation Article No. Units per package
1 1 1 1 1 1 1 1
Withdrawable Design 425 NZM..4 800-1600 100 600 NZM..4 800-1600 100
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
4
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Power Sections for Incomers and Outgoers with Compact Circuit Breakers 800 - 1600 A
NZM4 Power Sections
VT06606
Form 4
For cable connections from below For busbar position at the rear top Height of section - 2000 mm / depth of section - 600 mm Each XSN.. section requires 2 XBSB.. main busbar supports
Ie up to (A) Icc up to (400 V AC) (kA) Degree Type of Prot. Designation Article No. Units per package
Fixed Design for NZM 4 with Manual or Remote Control 425 NZM..4 800-1600 100 IP31 XSNF0443 IP55 XSNF0445 600 NZM..4 800-1600 100 IP31 XSNF0643 IP55 XSNF0645 Withdrawable Design for NZM 4 with Manual Control 425 NZM..4 800-1600 100 IP31 XSNW0443 IP55 XSNW0445 600 NZM..4 800-1600 100 IP31 XSNW0643 IP55 XSNW0645
1 1 1 1 1 1 1 1
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
5
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Outgoing Sections for Outgoers with Compact Circuit Breakers up to 630 A
Horizontally Mounted NZM 1-3 3
For installation of mounting plates of 600 mm module width Door to switchgear area in the width of the relevant section is encluded in the scope of delivery For busbar position at the rear top or rear bottom Height of section - 2000 mm / depth of section - 600 mm Each XSB.. section of a width of 1000 mm requires 3 XBSB.. main busbar supports, 4 main busbar supports are required for a width of 1200 mm Distribution bar supports are included in the scope of delivery
VT06306
Form 2
1000 1200
400 600
1 1 1 1
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
6
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Outgoing Sections for Outgoers with Compact Circuit Breakers up to 630 A
Horizontally Mounted NZM 1-3 3
Suitable for mounting plates of 600 mm module width Door to switchgear area is to be ordered separately For busbar position at the rear top or rear bottom Height of section - 2000 mm / depth of section - 600 mm Each XSB.. section featuring a width of 1000 mm requires 3 XBSB.. main busbar supports, 4 main busbar supports are required for a section width of 1200 mm Distribution bar supports are included in the scope of delivery
VT06506
Form 4
1000 1200
400 600
1 1 1 1
With ventilation - IP31 1000 / 1200 600 Closed - IP55 1000 / 1200 600 Transparent - IP55 1000 / 1200 600
1) 2)
1 1 1
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
7
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Outgoing Sections for Switch-Fuse Units up to 630 A F
Switch-Fuse Units, Horizontal F
For busbar position at the rear top or rear bottom Height of section - 2000 mm / depth of section - 600 mm Each XSS.. section of a width of 1000 mm requires 3 XBSB.. main busbar supports, 4 XBSB.. main busbar supports are required for a section width of 1200 mm Distribution bar supports are included in the scope of delivery
VT05706
1000 1200
IP31 IP31
XSS10 XSS12
106614 106615
1 1
Height (mm)
Type Designation
25 50 75 150
1 1 1 1
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
8
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Outgoing Sections for Fuse Rails up to 630 A
Fuse Rails, Vertical
For busbar positions at the rear top or rear bottom Height of section - 2000 mm / depth of section - 600 mm Each XSL.. section of a width of 600 mm requires 2 XBSB.. main busbar supports, widths of 800 or 1000 mm require 3 main busbar supports each
VT05606
IP 31 IP 31 IP 31
1 1 1
Width (mm)
Type Designation
50 100
1 1
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Separate N Conductor
VT09506
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
9
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Empty Sections for Individual Units on Mounting Plates as High as the Section, Separate Mounting Plates or Mounting Frames for Installation Outgoers
VT05906
IP 31 IP 55 IP 31 IP 55 IP 31 IP 55
1 1 1 1 1 1
Type Designation
1 1 1
Type Designation
XSMNB20
285511
Type Designation
XSMIB20
284257
Main Busbar Supports 1600 - 3200 A TN-C, TN-C-S, TN-S, IT, TT Icw (1s) up to 100 kA
VT09406
Ie (A)
Busbar cross sectional areas L1, L2, L3, fully rated N (mm2)
Type Designation
3-wire circuit L1, L2, L3 w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10 4-wire circuit L1, L2, L3, N w 1600 2 x 40 x 10 2000 2 x 60 x 10 2500 2 x 80 x 10 3200 3 x 80 x 10
1 1 1 1 1 1 1 1
Ie (A)
Type Designation
2 x 40 x 10 2 x 60 x 10 2 x 80 x 10 3 x 80 x 10
1 1 1 1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
10
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Mounting Kits for Outgoing Sections with Circuit Breakers up to 630 A or Separate Mounting Plates for Empty Sections
Type of Device Ie up to (A) Module Height (mm) (mm) Module Width Type Designation Article No. Units per package
1 1 1 1 1
1 1 1 1 1
1 1 1 1
1 1 1 1
100 150 200 300 400 100 150 200 300 400 100 150 200 300 400
425
600
800
XME0404M XME0604M XME0804M XME1204M XME1604M XME0406M XME0606M XME0806M XME1206M XME1606M XME0408M XME0608M XME0808M XME1208M XME1608M
283929 284727 283941 285684 283949 283933 284728 283945 285686 283951 285689 285690 285691 285692 285693
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
600
1 1 1 1
The PKZ2 with remote control R...-PKZ2 cannot be installed. The PKZM4 with front-mounted normal contactor relay NHI-E-... cannot be installed; please use sidemounted contactor relays. The installation of a GSTA is only possible without a front panel or when using a front panel without a cut-out. The mounting kit includes aluminium DIN-rails and a set of fastening material; for Form 2b, XME...M mounting plates must be added as partitions. The S...PKZ... drive and CL-... power limiter ... cannot be installed.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
11
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Mounting Kits for Outgoing Sections with Circuit Breakers up to 630 A or Separate Mounting Plates for Empty Sections
Type of Device Ie up to (A) Module Height (mm) (mm) Module Width Type Designation Article No. Units per package
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
12
Notes: Please refer to page 14 for the scope of delivery. For selecting, projecting and assembly details refer to page 15, please.
xEnergy Switchboards
Optional Equipment
Depth of Section (mm) Width of Section (mm) Type Designation Article No. Units per package
Optional; the section always comes with a closed top panel 600 425 600 800 1000 1200 XAD0406 XAD0606 XAD0806 XAD1006 XAD1206 283485 283488 283811 283814 283816 1 1 1 1 1
Bottom Plate, in Serveral Parts, for Power Sections XSI.., XSN.., Outgoing Sections with Fuse Rails XSL.. and Empty Sections XSE
600 425 600 800 1000 XSPBM0406 XSPBM0606 XSPBM0806 XSPBM1006-1 284287 284290 284293 104529 1 1 1 1
Bottom Plate, in Several Parts, for Outgoing Sections with Compact Circuit Breakers XSB.. or Switch-Fuse Units XSS.. F
600 1000 1200 XSPBM1006 284296 XSPBM1206 284299 1 1
VT08106
VT07906
VT05006
Closure with a 3 mm two-way key bit comes as standard equipment with the doors XALP 283821 1
VT1698
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
13
xEnergy Switchboards
Scope of Delivery / Information on Type-tested xEnergy Sections t
Scope of delivery for all sections
Basic frame incl. green design element Rear panel Top panel - closed Cable strain relief rail Connection set for sections Crossbar for busbar supports Bar support for PE or PEN
Scope of delivery - only Power Sections in Form 4 for Incomers and Outgoers with Open Circuit Breakers IZM, 800 - 3200 A
Mounting kit for open circuit breakers of type IZM, 3-pole, fixed mounting or withdrawable design Switch cover for operation from outside Doors to switchgear area at top and bottom, incl. locking system for 3mm two-way key bit, left-hinged Partitions for internal separation Form 4b
Scope of delivery-only Power Sections in Form 2 for Incomers and Outgoers with Compa ct Circuit Breakers NZM4, 800-1600 A o 1
Mounting kit for compact circuit breakers of type NZM4, 3-pole, fixed mounting or withdrawable design Door to section, incl. locking system for 3mm two-way key bit, left-hinged, to be operated from behind the door or from outside when using an extension shaft and door coupling rotary handle Partitions for internal separation Form 2b
Scope of delivery-only Power Sections in Form 4 for Incomers and Outgoers with Compact Circuit Breakers NZM4, 800 - 1600 A o
Mounting kit for compact circuit breakers of type NZM4, 3-pole, fixed mounting or withdrawable design Switch cover for operation from outside Doors to switchgear areas at top and bottom, incl. locking system for 3 mm two-way key bit, left-hinged Partitions for internal separation Form 4b
Scope of delivery - Outgoing Sections for Compact Circuit Breakers Type NZM 1 - 3 up to 630 A
Mounting kit for outgoers with circuit breaker Door to switchgear area in the width of the section (Form 2b) / door to terminal area (Form 4b), incl. locking system for 3 mm two-way key bit Partitions for internal separation Forms 2b / 4b and for the right-hand adjacent section Distribution bar support, 4-wire circuit, 1600A Bar support for PE and N or PEN in the terminal area
Scope of delivery - Outgoing Sections for Outgoers with Horizontal Switch-Fuse Units F
Mounting kit for switch-fuse units, to be operated from outside, with ventilation Door to terminal area, incl. locking system for 3mm two-way key bit Partitions for internal separation Form 2b and right-hand adjacent section Mounting kit for distribution bar, 3 or 4-wire circuit, 1600A Bar support for PE and N or PEN in the terminal area
Scope of delivery - Outgoing Sections for Outgoers with Vertical Fuse Rails
Mounting kit for fuse rails, to be operated from outside Doors to switchgear areas at top and bottom, incl. locking system for 3 mm two-way key bit, left-hinged Partitions for internal separation Form 3b Mounting kit for horizontal distribution bar, 1600A
Scope of delivery - Mounting Kits for Horizontally Mounted Compact Circuit Breakers NZM 1- 3 up to 630A in Outgoing Sections or on Separate Mounting Plates for Empty Sections
Mounting plate for circuit breakers, with holes prepared for cable insertion, incl. all fastening elements Front covers with cut-outs for circuit breakers incl. all fastening elements and hinges "Mounting plates" for XMMC.. modular installation devices consisting of DIN-rails incl. all fastening elements (no mounting plate included)
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
14
xEnergy Switchboards
Information on selecting, projecting and assembly that must be given particular consideration
General inofrmation valid for all sections:
Copper for main busbars, distribution bars and circuit breaker busbars (NZM4 / IZM) is not included in the scope of delivery. Please pay attention to the information on terminal systems and connections to main busbar systems detailed in Moellers instructions BA4810-0015 on TTA assemblies. Please note the current reduction values with regard to the rated currents stated, see Moellers special catalogue FK4810-1143, chapter 14. In addtion, all the data of the switch-fuse unit and fuse bar manufacturers must be taken into account as well. If you wish to add any units to the switchgear, always refer to the catalogue or call the product support to check whether they are compatible. Please give special consideration to the increased section width required when using an IZM with mechanical locking. Example: IZM size 1 with mechanical locking system can only be installed in the 600 mm wide section (not in the 425 mm section). For additional accessories (e.g. bottom panels, ) please refer to Moellers special catalogue FK4810-1143
Power Sections for Incomers and Outgoers with 800 - 3200 A Circuit Breakers
Please order IZM circuit breakers and optional equipment separately from the HPL0211 catalogue, chapter IZM. The IZM-XRT door sealing frame and - for IP55 - the IZM-XDT protective cover must always be ordered separately. Please order NZM4 circuit breakers and optional equipment separately from the HPL0211 catalogue, chapter NZM.
Mounting Kits for Horizontally Mounted Compact Circuit Breakers NZM 1- 3 up to 630A in Outgoing Sections or on Separate Mounting Plates for Empty Sections
For instructions on how to connect the switchgear to the sectional distribution bar system, please refer to Moellers assembly instructions in BA 4810-015. In order to meet Form 4b requirements, it might be necessary to plan some additional terminals. Front plates can only be used for Form 4 sections. Mounting plates for NZM and PKZ switchgear are sized for the basic versions of these devices. Whether it is possible to install additional equipment (e.g. contactor relays) or not must be checked on the basis of the dimensioned drawings in Moellers special catalogue FK4810-1143, chapter 15.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
15
xEnergy Switchboards
Switchboards
Power sections Outgoing sections Empty sections Optional equipment
Page 17 ff.
Page 17 Page 18 Page 21 Page 21
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
16
xEnergy Switchboards
Power Sections for Open Circuit Breakers IZM, 800 - 3200 A in Form 4 Dimensions (mm)
XSI0..
b1
55
650
2000
2030
650
b1 600
b2 575
Power Sections for Compact Circuit Breakers NZM4, 800 - 1600 A in Form 4 Dimensions (mm)
XSNF0... Fixed design
121.5 73
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
17
25
b2
650
b1
xEnergy Switchboards
Outgoing Sections for Horizontally Mounted Compact Circuit Breakers NZM 1-3 up to 30 A in Form 2 and Form 4 3 Dimensions (mm)
XSB1..2..
80
b1
405/580
2000
1900
2030
335/510
b2
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
18
50
52
273
a1
a2
275
275
xEnergy Switchboards
Outgoing Sections for Outgoers with Horizontal Switch-Fuse Units F Dimensions (mm)
XSS1..
b1
220
55
2000
1050
2030
b1 600
b2 575
a 1000 1200
220
a1 590 590
a2 369 569
b2
a1 25 a
a2
Dimensions (mm)
XSS1..
600 238 108
30
185
185 SSA-185
220
415
53
b1
762.5
180
180
1505
30
237.5
220
762.5
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
19
2000
200
229
575
xEnergy Switchboards
Outgoing Sections for Outgoers with Vertical Fuse Rails Dimensions (mm)
XSL..
b1
250.8 215.8
a
185
2000
662.5
185
b1 600
b2 575
b2
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
20
662.5
725
854
15
b1
xEnergy Switchboards
Empty Sections for Individual Mounting Units Dimensions (mm)
XSE0..
b1 17.5 35 125.5
80
50
b1 600 800
b2 575 775
b2
a1 a
50
24g1
18g1 a
b3
a 322 497 697 Type XME0404M XME0604M XME0804M XME1204M XME1604M XME0406M XME0606M XME0806M XME1206M XME1606M XME0408M XME0608M XME0808M XME1208M XME1608M h1 97 147 197 297 397 97 147 197 297 397 97 147 197 297 397 b1 314 314 314 314 314 489 489 489 489 489 689 689 689 689 689
h2
h3
h2 50 100 150 250 350 50 100 150 250 350 50 100 150 250 350
h1
b2 300 300 300 300 300 475 475 475 475 475 675 675 675 675 675
h3 90 140 190 290 390 90 140 190 290 390 90 140 190 290 390
b3 283 283 283 283 283 458 458 458 458 458 658 658 658 658 658
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
21
1879
xEnergy Switchboards
Mounting Options for Mounting Plates and Front Plates Dimensions (mm)
Form 4b
19 b
a max. 193
b max. 264
c 64
275
4 1 c 294 a
600
b 141
a 141 a
100
75
33.7
44
33.7
b 67.4
55 o 11 a 67.4 a
70.5
25
180
180
235
180
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
22
87.5
150
250
825
55
79.5
62
Moeller Eugenia 1 A-3943 Schrems Tel. +43 (0) 28 53/702-9* Fax: +43 (0) 28 53/702-76509 E-Mail: info@moeller.net Internet: www.moeller.at
2006 by Moeller Subject to alteration Catalogue Express list SK0207-1162 GB (04/06) Printed in Austria (04/06) Print: Rabl, Schrems Article No.: 106774
4 015081 065448
With Xclever home, Moeller offers the complete electrical installation from one source for a safe and easily controllable buiding. All Xclever home product groups stand out because of their high safety standards and simple and easy application. Combines all functional and assembly safety advantages. From circuitbreakers and modular installation devices to over-voltage protection. The complete distribution program for safe electrical installations from 63 to 2500 Amps. For houses, blocks of flats or functional buildings. Covers all requirements of operation in buildings. The system opens new business possibilities for new and renovated buildings. A clever, complete range that can be flexibly extended for the installation of future-orientated data networks.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616