Sie sind auf Seite 1von 11

LampiranB(i) (Lastupdated5/2/2013) ListofSpecifiedConditions/RequirementsforWaterSupply No. ProductName 1. A. WATERTANK FRPSectionalWater Tank StandardsApplied 1. SS245:1995 2. MS1390:2010Clause 12.1.

3 AcceleratedWeathering Test SpecifiedConditions/Requirements 1. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 2. Maximumcapacityallowedis500,000liters(100,000G) 3. Maximumheightallowedis4meter 4. Tankonlycanbeusedforsystemthatwillnotbesurrenderedtothe wateroperator 5. Minimum10yearswarrantyperiodfortankandsealantisrequired. 6. Usersareencouragedtoprovideprotectionforthetankfromdirect sunlight(i.e.roofetc.) 1. Tankshouldhaveaninterlockingmechanism. 1. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 2. Maximumcapacityallowedis100,000liters(22,000G) 3. Tankonlycanbeusedforsystemthatwillnotbesurrenderedtothewater operator. 1. Tankonlycanbeusedforsystemthatwillnotbesurrenderedtothewater operator. 2. Maximumcapacityallowedis500,000liters(100,000G) 3. Maximumheightallowedis4panels. 4. ThetankmustbelinedwithPElining;minimumthicknessofthePElining is2.0mm. 5. Minimum10yearswarrantyperiodfortanksandlinings. 6. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 1

2.

PEStorageTanks

3.

GFRP/FRP Cylindrical(One Piece)StorageTank

1. MS1225:Pt1:2007 2. MS1225:Pt2:2006 1. BSEN13280:2001 2. MS1241:1991

4.

PressedSteelTank

1. BS1564:1975

LampiranB(i) (Lastupdated5/2/2013) No. ProductName 5. StandardsApplied SpecifiedConditions/Requirements 1. Maximumcapacityallowedforelevatedtankis500,000Gandforground storagetankis750,000G. 2. Maximumheightallowedis5meteror4panelsorwhichoneislower. 3. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 4. Minimum10yearswarrantyperiodfortankandsealant/liningis required. 1. Tankonlycanbeusedforsystemthatwillnotbesurrenderedtothewater operator. 2. Maximumcapacityallowedis500,000litres(100,000G) 3. Maximumheightallowedis5meteror4panelsorwhichoneislower. 4. MinimumthicknessofthePELiningis2.0mm 5. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 5. Minimum10yearswarrantyperiodfortanksandsealant/liningis required. 1. Maximumcapacityallowedis1.0MG 2. Maximumheightallowedis5meter 3. Tankmustbesuppliedandinstalledbythesamesupplierorinstallerwho isappointedbythesupplier. 4. Minimum10yearswarrantyperiodfortankisrequired. 1. ORing/GasketshallbeofEPDM. 2. BodymaterialshallbeofDuctileIron. 3. Forvalvewhichismorethan600mmindiameter,wateroperatoris allowedtomakeanytestwhichtheyfeelnecessarybeforepurchasingis made. 1. ORing/GasketshallbeofEPDM. 2. BodymaterialshallbeofDuctileIron. 2

1. ANSI/AWWAD10309 SteelTankWith LiningorCoating (GlassFused/Glass Coated/EpoxyLining /HDPELining)

6.

CorrugatedSteel PanelsWith PolyethyleneLined WaterStorageTank

1. BS1449:Pt1:1991 2. SS245:1995Clause10.2.1 LeakageTest 3. SS245:1995Clause10.2.2 DeflectionTest

7.

CylindricalSteelTank 1. BS59501:2000 DoubleFoldSystem

B. VALVES 1. ButterflyValve

1. BSEN593:2004

2.

AirValve

1. JKR20200009701 2. ANSI/AWWAC5122004

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied 3. BSEN10744:2000 SpecifiedConditions/Requirements 3. Forvalvewhichismorethan600mmindiameter,wateroperatoris allowedtomakeanytestwhichtheyfeelnecessarybeforepurchasingis made 1. ORing/GasketshallbeofEPDM. 2. BodymaterialshallbeofDuctileIron. 3. Forvalvewhichismorethan600mmindiameter,wateroperatoris allowedtomakeanytestwhichtheyfeelnecessarybeforepurchasingis made

3.

GateValve

1. 2. 3. 4. 5. 6.

4.

CheckValve

MS1049:1986 BSEN12288:2010 BSEN1171:2002 JKR20200007700 BS51631:2004 BS51632:2004 1. BSEN12334:2001 2. BSEN14341:2006

1. ORing/GasketshallbeofEPDM. 2. BodymaterialshallbeofDuctileIron. 3. Forvalvewhichismorethan600mmindiameter,wateroperatoris allowedtomakeanytestwhichtheyfeelnecessarybeforepurchasingis made 1. ABS pipes should be used together with the ABS Fittings and solvent cementofthesamebrand. 2. MinimumratingforABSpipeisClass12. 1. UPVC pipes should be used together with the UPVC Fittings and solvent cementofthesamebrand. 2. MinimumratingforuPVCpipeisPN12. 1. MinimumratingforPEPipeisPN12.5 2. Polyethylene Pipe (PE) product should have a blue marking stripe (blue stripes)onthepipeasanidentification forwatersupplyusage.Theblue stripesmustcomplywiththefollowingcondition: 3

1.

C. PIPES Acrylonitrile ButadieneStyrene (ABS)Pipes Unplasticized Polyvinylchloride (uPVC)Pipes

1. MS1419:Part1:2007 2. AS/NZS3518:2004 1. MS 628: Part 1: 1999 AMD.1: 2001 & AMD.2: 2002 2. MS762:2007,AMD.1:2010 3. BSENISO14522:2009 1. MS1058:Part2:2005 2. ISO44272:2007 3. DIN8075(199908)

2.

3.

Polyethylene(PE) Pipe

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied SpecifiedConditions/Requirements a. mixtureofcompoundusedtoproducethebluestripeshavetousethe same PE polymers with the original PE polymers (PE 80/PE 80 or PE 100/PE100)asusedinthemanufactureofthePEpipe. b. PE 80 blue (light blue) compound should be used for PE 80 pipe and PE100 (dark blue) stripe for PE100 pipe in order to identify the classificationofPEmaterial. c. Minimumnumberofstripesshallbe4spacedat90interval. d. Thickness of stripes should be less than 10% of the wall thickness of thepipe. D. FITTING Acrylonitrile ButadieneStyrene (ABS)Fittings 2. Unplasticized Polyvinylchloride (uPVC)Fittings 1. 1. MS1419:Part1:2007 2. AS/NZS3518:2004 1. MS 628: Part 2: Section 2.1: 1999 2. BSENISO:14523:2009 3. BS43461:1969 4. BS43462:1970 1. MS1419:PT3:1997 1. MS628:Part2:Section2.2 :1999 1. ABS Fittings should be used together with the ABS pipes and solvent cementofthesamebrand. 1. UPVC Fittings should be used together with the UPVC pipes and solvent cementofthesamebrand.

E. SOLVENTCEMENT 1. ABSSolventCement

2.

UPVCSolvent Cement

1. ABSSolventCementshouldbeusedtogetherwiththeABSpipesandABS Fittingsofthesamebrand. 1. UPVC Solvent Cement should be used together with the UPVC pipes and UPVCFittingsofthesamebrand. 4

LampiranB(i) (Lastupdated5/2/2013) No. ProductName F. PUMP 1 Alltypesofpump StandardsApplied


Not Applicable

SpecifiedConditions/Requirements
Registered pumps are subject to the following conditions :1.1 For internal plumbing system that will be maintained by the owner premises 1.1.1 Booster pumps of capacity lower than 10m3/hr (<10m3/hr) shall have efficiencies of not less than 45%. 1.1.2 Booster pumps of capacity equal and exceeding 10m3/hr (10m3/hr) but lower than 30m3/hr (< 30m3/hr) shall have efficiencies of not less than 50%. 1.1.3 The efficiency of all types of booster pumps of higher capacity shall meet the minimum requirement tabulated under item 2.2.1 below. 1.1.4 Compliance with EFF1 rating for booster pump motors is voluntary. However, building conforming to Green Building Rating should have pump motors complying with EFF1 rating.

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied SpecifiedConditions/Requirements


1.2 For external reticulation system that will be handed over and maintained by the water operators. 1.2.1 Design Criteria for Pump sets:MaximumSpeed(rpm) PumpingRate PerPump (m3/hr) Pumping Hours Minimum Pump Efficiency (%) Maximum Pumping Head

Numberof Pumpsets

Total

Horizontal SplitCasing Pumps

EndSuction Pumps

30<100 OnDuty=1 Standby=1 2 12 60 75 2900

100<300

OnDuty=1 Standby=1

12

70

75

1500

2900

300<1000

OnDuty=2 Standby=2

12

75

75

1,500

1000

OnDuty=4 Standby=2

12

80

75

1,500

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied


1.2.2 1.2.2.1
No. 1.

SpecifiedConditions/Requirements
Material Condition:General conditions :Material The material shall be of Stainless Steel Grade 420 or better. All exposed bolts and nuts in the construction for the pump shall be cadmium treated or hot dipped galvanized.

Part Pump shaft

2.

Bolt and Nuts

1.2.2.2 Specific Conditions for Horizontal Split Casing Pump:-

No.

Part

Material Shall be axially split grey cast iron or ductile iron type, and be fitted with high tensile steel shafts running on ball or roller bearings with suitable lubricating arrangements.

1.

Pump casing

2.

Impeller, neck rings, sleeves, gland, lantern ring and bushes Gland seal

The material shall be of zinc-free bronze or stainless steel.

3.

The material shall be silicon carbide or tungsten carbide mechanical seal type.

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied


1.2.2.3 Specific Conditions For End Suction Pumps:No. 1. Part Gland seals Material The material shall be silicon carbide or tungsten carbide mechanical seal type. The material shall be of zinc-free bronze or stainless steel.

SpecifiedConditions/Requirements

2.

Impeller

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied


1.2.3

SpecifiedConditions/Requirements
Class Definition for Electrical Motors:All motors shall be of the High Efficiency Motor standard type, i.e. EFF1 CEMEP-EU standard, Class 1 as detailed in the table below. Motors of capacity greater than 90 kW shall have an efficiency of not less than 95.0%. Compliance to this Clause is mandatory for external pumping stations.

Motor Capacity (kW) 1.1 1.5 2.2 3 4 5.5

Motor Efficiency (%) for Class EFF1 2-Pole Motors 82.8 84.1 85.6 86.7 87.6 88.6 4-Pole Motors 83.8 85.0 86.4 87.4 88.3 89.2

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied


Motor Capacity (kW) 7.5 11 15 18.5 22 30 37 45 55 75 90 37 45 55 75 90 Motor Efficiency (%) for Class EFF1 2-Pole Motors 89.5 90.5 91.3 91.8 92.2 92.9 93.3 93.7 94.0 94.6 95.0 93.3 93.7 94.0 94.6 95.0 4-Pole Motors 90.1 91.0 91.8 92.2 92.6 93.2 93.6 93.9 94.2 94.7 95.0 93.6 93.9 94.2 94.7 95.0

SpecifiedConditions/Requirements

10

LampiranB(i) (Lastupdated5/2/2013) No. ProductName StandardsApplied


1.3 Water Treatment Plant Pump design is subject to the specifications set by the Consulting Engineers.

SpecifiedConditions/Requirements

11

Das könnte Ihnen auch gefallen