Sie sind auf Seite 1von 1

www.flowtechinc.

com
Phone: 860-291-8886 Fax: 860-291-9908 Specialists in Variable Frequency Drives and Critical Airflow Control

SERVICE REPORT
Installation/Start-up Warranty Non-Warranty Customer Training Consultative Other
Address:

Date:

Flow Tech Job Number:

03-12-2013
Equipment Manufacturer:

Service Representative:

ABB
Equipment Model Number:

Derek Labbie
Equipment S/N:

ACH501-050-4-00P2
Labor Authorization #:

Returned Material Authorization #:

Customer
Customer / End-user: UCHC

CT

City: Farmington Telephone:

State:

Zip Code:

Contact: Dave Casella

Email:

Fax:

Special Invoicing Information/Customer Purchase Order :

Equipment Identification / Comments / Action


Tag:AHU-3 Fan2 and AHU-2-F-1

AHU-3-F-2=VFD was off on a "ext/mot fault". Went through control wiring and followed problem back to the overload relay. I reset the relay and VFD fault cleared and VFD started. The nameplate full load amperage of the motor is 48A, the overload looks to be rated for the amperage of the motor. I recommend changing the overload heaters, it looks like the originals are still being used and should be replaced to avoid further issues. Please look below for details on overload and heaters. The VFD is now working and I placed into auto operation. FURNAS CAT NO. 48GC37AA4 with E77 heater AHU-2-F-2= bad transformer fuse "little fuse FLM 1 1/2 amp, need to order and return back to replace

Labor / Travel / Expenses


Date: Work Hrs Trav Hrs

2/25/13 2/26/13 3/13/13

2.5 1.5 2

1 1 1

Rate

Mileage

Description:

Look at 2 VFDs with issues REPLACE FUSE IN AHU-2-F2, reset tripped OLs replace OL heaters in AHU-3-F-1, AHU-3-F-2, and AHU-2-F-1 And replace burned out bulbs(3), and one bad bulb socket
Part Number:

Parts
Quantity Description

OL heater-(3)E78 and (6)E77

Derek Labbie Salesperson Follow-

Service Representative Signature: up: Customer Signature:


Flow Tech, Inc.

10 Bidwell Road, South Windsor, CT 06074