EMC PROGRAM ON THE ACCELERATOR RINGS

K. Okamura (KEK), Y. Watanabe (JAEA)


TOPICS

Basic concept of grounding in the accelerator ring Cabling and grounding in the RCS Cabling and grounding in the main ring Cabling and grounding of injection/extraction pulse power system Grounding and shielding of RF system Ceramic breaks of the main ring Noise immunity reinforcement plan of beam monitors

BASIC CONCEPT OF GROUNDING IN THE ACCELARATOR RING


Vacuum chambers including monitors are grounded in the tunnel. Beam pipes passing through magnets are isolated from the magnet. RF, kicker, collimator, and SEP are grounded in the tunnel. BM, QM, SM, and StM are grounded in the power supply building. Ion pumps are isolated from beam pipes. Ceramic breaks are provided at upstream point of BMs. In RCS, ceramic breaks are provided with every magnet using ceramic duct.

CABLING AND GROUNDING IN THE RCS


Policy
All power cable is twisted and shielded. Cable shielding is grounded in one-sided. Power supply housing is insulated from floor and water pipe. Main circuit is only grounded in neutral point. Chokes Switchgear Transformer Power supply Capacitor banks

Neutral point

Magnets

Earth point (Utility)

Earth point (Magnet)

To Chokes

CERAMIC BREAKS RCSCeramics duct

capacitor

Dipole magnet

Epoxy resin Titanium sleeve

Ceramics vacuum duct installed in dipole magnet Ceramics duct is installed in every dipole and quadrupole magnets.

CABLING AND GROUNDING POLICY IN THE MAIN RING


Main circuits are fed by cables with shields. Magnets are not grounded in the tunnel but at power supply side. Grounding cables are installed separately with each magnet family B, 11 Q-families, 3 S-families) . Grounding cables are also installed between a transformer and a power supply. Grounding of cable racks is under consideration.
BUILDING TRANS YARD P Potential of the Power Line 0 TUNNEL N

GROUNDING CONNECTION OF QUADRUPOLE AND SEXTUPOLE MAGNETS Earth Cable are separately fed by each magnet family and has open end symmetrically.

Q**,S ++

QFP,SDB

**:FN,DN,FX,DX FR,FS,FT,DR,DS,DT ++:FA,DA

Potential 0

Potential 0

GROUNDING CONNECTION OF BENDING MAGNETS Building D3


BM
N P N P

BM1

Grounding Cable are separately fed by each power supply building


N P P N N P

BM

Building D1

BM 6

BM 3

BM 4

Building D2

PULSE MAGNET POWER SUPPLY FOR INJECTION AND EXTRACTION SYSTEM Coils are not grounded in the tunnel but grounded in power supply buildings through power cables. Magnetic core, vacuum duct, and frame are grounded both in the tunnel and buildings. Each grounding points are connected by cables.
Vacuum Chamber

400mm2

400mm2

PULSE MAGNET POWER SUPPLY FOR A KICKER SYSTEM Outer conductor of a coaxial cable is connected to frames at both end. Magnetic core, vacuum chamber, and frame are grounded in a tunnel, also grounded in a building through the coaxial cable.

HV PS

GROUNDING AND SHIELDING OF RF SYSTEM

In general, grounding is designed so that drive current must directly return to each corresponding power supply. 1.2MW anode power supplies are switched mode power supply w/ IGBT inverters. Tri-axial cable for tube anode supply is used for shielding high frequency EMI noise. Single point grounding is performed. However, cavity /amplifier chassis are grounded w/ resistor for safety

CERAMIC BREAKS OF THE MAIN RING

ARC section (#1,#2, #3): Breaks at an upper stream point of each bending magnet

Noise immunity reinforcement plan of beam monitors


Grounding is done in the tunnel or the control room (power supply buildings). (possible to ground at the both ends, optionally) Beam pipe will be grounded in the tunnel via each BPM, to prevent from charging up. Use high shielding efficiency cables
Proper use of noise-shielded transformers. Use common mode chokes

high shielding efficiency cables


Screening effectiveness depends on the construction of outer conductor: flexible rigid!
Semi-rigid, corrugated metal > longitudinal metale.g. aluminium) foil > braid wire

from the HUBER+SUHNER cable catalgue

Example: induced noise on the cable under noisy environment with a switching power supply outer conductor RG58 c/u: copper braid wire ( 5 m) S04272B: longitudinal metal foil ( 4 m )

other factors to be considered radiation hardness, cost

DC

10MHz

Beam position monitors (BPMs)


Tunnel

The shielding of coaxial cables are connected to the beam pipe via connectors.

option: commom mode choke coil. Grounding in the tunnel.

ch.1&2 ch.3&4 Connection to the GND depends on noise observation. noise cut trans.

High shielding efficiency coaxial cables surrounded by another shield.

Control room (power supply building)

AC100V Grounding in the control room

SUMMARY
EMC program of the accelerator ring is mainly focused on grounding. Two golden rules of grounding are one point grounding and safety. Power supply, beam pipes, vacuum pumps are grounded separately. Grounding of cable rack is under consideration. As to beam monitors, high efficiency shielding cables are selected