Section 2.

The Load Combination Equations


Last Revised:

ASCE 7-05 provides load combination equations for both LRFD and ASD. The ones that you will use will depend on which of the two design philosophies that have been chosen for your project. You will note that several of the load combination equations have multiple permeations due to use of "or" or "+" in the equations (both wind, W, and seismic, E, are considered to be + loads). This is true of both the LRFD and ASD combinations. Load and Resistance Factor Design If you chose to use LRFD for your design philosophy, then you are to make sure that your structure is capable of supporting the loads resulting from the seven ASCE 7-05 basic load combination equations. LRFD applies load factors to service level loads so that they are safely comparable to member strengths (which are generally inelastic) while maintaining the actual (service) loads in the elastic region. Member strength (the maximum load that the member will support) is generally between 1.3 to 1.4 times the force that will cause yielding in a member. These load factors are applied in the load combination equations and vary in magnitude according to the load type. The magnitude of the LRFD load factors reflect the predictability of the loads. For example, the load factor for D is generally lower than the load factor for L in any given equation where there is equal probability of simultaneous occurrence of the full value of each load type. This is because dead loads are much more predictable than live loads and, hence, do not require as great of a factor of safety. Example: Analysis of a structure shows that a particular member supports 5 kips dead load and 6 kips live load. Using LRFD LC-2, the combined design load equals 1.2 times the dead load plus 1.6 times the live load, or 15.6 kips. The factor for dead load (1.2) is lower than the factor for live load (1.6) because dead load is more predictable than live load. The load factors are all greater than 1.0 since we want to compare the result to the ultimate strength of the member instead of the yielding strength of the member yet we don't want yielding to occur. The ultimate strength is generally about 1.3-1.4 times the yield strength of the member. Allowable Strength Design For ASD there are eight basic load combination equations. You will notice that the large load factors found in the LRFD load combinations are absent from the ASD version of the ASCE 7-05 load combination equations. Also, the predictability of the

loads is not considered. For example both D and L have the same load factor in equations where they are both likely to occur at full value simultaneously. The probability associated with accurate load determination is not considered at all in the ASD method. Hence the major difference between LRFD and ASD. Example: Analysis of a structure shows that a particular member supports 5 kips dead load and 6 kips live load. Using ASD LC-2, the combined design load equals the dead load plus the live load, or 11.0 kips. The factor for dead load (1.0) is the same as the factor for live load (1.0), hence not accounting for the fact that the dead load is more predictable than the live load. The result of the load combination equation is then generally compared against the yielding strength of the member to ensure elastic behavior. The Load Combination Equations The published load combination equations are: LRFD 1. 2. 3. 4. 5. 6. 7. 1.4(D + F) 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R) 1.2D + 1.6(Lr or S or R) + ((0.5 or 1.0)*L or 0.8W) 1.2D + 1.6W + (0.5 or 1.0)*L + 0.5(Lr or S or R) 1.2D + 1.0E + (0.5 or 1.0)*L + 0.2S 0.9D + 1.6W + 1.6H 0.9D + 1.0E + 1.6H

When atmospheric ice is included, ASCE 7-05 requires modifications to equations (2), (4), and (6), effectively resulting in three new equations which are listed here: 2ice. 1.2(D + F + T) + 1.6(L + H) + 0.2Di + 0.5S 4ice. 1.2D + (0.5 or 1.0)*L + Di + Wi + 0.5S 6ice. 0.9D + Di + Wi + 1.6H
*

Note that the load factor for L in equations (3), (4), and (5) is permitted to equal 0.5 for occupancies in which the unit live load is less than or equal to 100 psf, except for garages or areas occupied as places of public assembly. ASD 1. 2. 3. 4. 5. 6. 7. 8. D+F D+H+F+L+T D + H + F + (Lr or S or R) D + H + F + 0.75(L + T) + 0.75(Lr or S or R) D + H + F + (W or 0.7E) D + H + F + 0.75(W or 0.7E) + 0.75L + 0.75(Lr or S or R) 0.6D + W + H 0.6D + 0.7E + H

For the purposes of this text, we will identify the equations and their permutations by the labels defined as defined in Table 2.1. When atmospheric ice is included, ASCE 7-05 requires modifications to equations (2), (3), and (7), effectively resulting in three new equations which are listed here: 2ice. D + H + F + L + T + 0.7Di 3ice. D + H + F + 0.7Di + 0.7Wi + S 6ice. 0.6D + 0.7Di + 0.7Wi + H Table 2.1 ASCE 7-05 Load Combination Equation Permutations LRFD
LRFD-LC1 LRFD-LC2a LRFD-LC2b LRFD-LC2c LRFD-LC2i LRFD-LC3a LRFD-LC3b LRFD-LC3c LRFD-LC3d LRFD-LC3e LRFD-LC3f LRFD-LC4a LRFD-LC4b LRFD-LC4c LRFD-LC4i LRFD-LC5a LRFD-LC5b LRFD-LC6a LRFD-LC6b LRFD-LC6i LRFD-LC7a LRFD-LC7b 1.4(D+F) ASD-LC1 1.2(D + F + T) + 1.6(L + H) + 0.5Lr ASD-LC2 1.2(D + F + T) + 1.6(L + H) + 0.5S ASD-LC2i 1.2(D + F + T) + 1.6(L + H) + 0.5R ASD-LC3a 1.2(D + F + T) + 1.6(L + H) + 0.2Di + ASD-LC3b 0.5S * 1.2D + 1.6L + (0.5 or 1) L ASD-LC3c
r

ASD
D+F D+H+F+L+T D + H + F + L + T + 0.7Di D + H + F + Lr D+H+F+S D+H+F+R D + H + F + 0.7Di + 0.7W i + S D + H + F + 0.75(L + T) + 0.75Lr D + H + F + 0.75(L + T) + 0.75S D + H + F + 0.75(L + T) + 0.75R D+H+F+W D+H+F-W D + H + F + 0.7E D + H + F - 0.7E D + H + F + 0.75W + 0.75L + 0.75Lr D + H + F + 0.75W + 0.75L + 0.75S D + H + F + 0.75W + 0.75L + 0.75R D + H + F - 0.75W + 0.75L + 0.75Lr D + H + F - 0.75W + 0.75L + 0.75S D + H + F - 0.75W + 0.75L + 0.75R D + H + F + 0.75(0.7E) + 0.75L + 0.75Lr D + H + F + 0.75(0.7E) + 0.75L + 0.75S D + H + F + 0.75(0.7E) + 0.75L + 0.75R D + H + F - 0.75(0.7E) + 0.75L + 0.75Lr D + H + F - 0.75(0.7E) + 0.75L + 0.75S

1.2D + 1.6Lr + 0.8W 1.2D + 1.6S + (0.5 or 1) L 1.2D + 1.6S + 0.8W 1.2D + 1.6R + (0.5 or 1) L 1.2D + 1.6R + 0.8W
* *

ASD-LC3i ASD-LC4a ASD-LC4b ASD-LC4c ASD-LC5a

* ASD-LC5b 1.2D + 1.6W + (0.5 or 1) L + .5Lr * ASD-LC5c 1.2D + 1.6W + (0.5 or 1) L + .5S * ASD-LC5d 1.2D + 1.6W + (0.5 or 1) L + .5R ASD-LC6a 1.2D + (0.5 or 1.0)*L + D + W + 0.5S i i

1.2D + E + (0.5 or 1) L + 0.2S ASD-LC6b * 1.2D - E + (0.5 or 1) L + 0.2S ASD-LC6c


*

0.9D + 1.6W + 1.6H 0.9D - 1.6W + 1.6H 0.9D + Di + W i + 1.6H 0.9D + E + 1.6H 0.9D - E + 1.6H

ASD-LC6d ASD-LC6e ASD-LC6f ASD-LC6g ASD-LC6h ASD-LC6i

* Note that the load factor for L in LRFD ASD-LC6j equations (3), (4), and (5) is permitted to equal ASD-LC6k 0.5 for occupancies in which the unit live load is less than or equal to 100 psf, except for garages

or areas occupied as places of public assembly.ASD-LC6l Otherwise the load factor for L equals 1.0. ASD-LC6m ASD-LC7a ASD-LC7b ASD-LC8a ASD-LC8b

D + H + F - 0.75(0.7E) + 0.75L + 0.75R 0.6D + 0.7Di + 0.7W i + H 0.6D + W + H 0.6D - W + H 0.6D + 0.7E + H 0.6D - 0.7E + H