Sie sind auf Seite 1von 212

Relion 615 series

Feeder Protection and Control REF615 Application Manual

Document ID: 1MRS756378 Issued: 2012-05-11 Revision: K Product version: 4.0

Copyright 2012 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Table of contents

Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5 Intended audience..............................................................................5 Product documentation.......................................................................5 Product documentation set............................................................5 Document revision history.............................................................6 Related documentation..................................................................7 Symbols and conventions...................................................................7 Symbols.........................................................................................7 Document conventions..................................................................8 Functions, codes and symbols......................................................8

Section 2

REF615 overview...........................................................11
Overview...........................................................................................11 Product version history................................................................12 PCM600 and IED connectivity package version..........................12 Operation functionality......................................................................13 Optional functions........................................................................13 Physical hardware............................................................................13 Local HMI.........................................................................................16 Display.........................................................................................16 LEDs............................................................................................17 Keypad........................................................................................17 Web HMI...........................................................................................18 Authorization.....................................................................................19 Audit trail......................................................................................20 Communication.................................................................................22

Section 3

REF615 standard configurations....................................25


Standard configurations....................................................................25 Addition of control functions for primary devices and the use of binary inputs and outputs..................................................28 Connection diagrams........................................................................30 Presentation of standard configurations...........................................36 Standard configuration A..................................................................37 Applications.................................................................................37 Functions.....................................................................................37 Default I/O connections..........................................................38 Default disturbance recorder settings.....................................39 Functional diagrams....................................................................40

REF615 Application Manual

Table of contents

Functional diagrams for protection.........................................40 Functional diagrams for disturbance recorder and trip circuit supervision...................................................................47 Functional diagrams for control and interlocking....................48 Standard configuration B..................................................................51 Applications.................................................................................51 Functions.....................................................................................51 Default I/O connections..........................................................53 Default disturbance recorder settings.....................................54 Functional diagrams....................................................................54 Functional diagrams for protection.........................................55 Functional diagram for disturbance recorder and trip circuit supervision...................................................................62 Functional diagrams for control and interlocking....................63 Standard configuration C..................................................................67 Applications.................................................................................67 Functions.....................................................................................67 Default I/O connections..........................................................68 Default disturbance recorder settings.....................................69 Functional diagrams....................................................................70 Functional diagrams for protection.........................................70 Functional diagram for disturbance recorder and trip circuit supervision...................................................................75 Functional diagrams for control and interlocking....................76 Standard configuration D..................................................................78 Applications.................................................................................78 Functions.....................................................................................79 Default I/O connections..........................................................80 Default disturbance recorder settings.....................................81 Functional diagrams....................................................................82 Functional diagrams for protection.........................................82 Functional diagram for disturbance recorder and trip circuit supervision...................................................................88 Functional diagrams for control and interlocking....................89 Standard configuration E..................................................................93 Applications.................................................................................93 Functions.....................................................................................93 Default I/O connections..........................................................95 Default disturbance recorder settings.....................................96 Functional diagrams....................................................................97 Functional diagrams for protection.........................................97 Functional diagram for disturbance recorder and trip circuit supervision.................................................................104 Functional diagrams for control and interlocking..................106
2 REF615 Application Manual

Table of contents

Standard configuration F................................................................110 Applications...............................................................................110 Functions...................................................................................110 Default I/O connections........................................................113 Default disturbance recorder settings...................................114 Functional diagrams..................................................................114 Functional diagrams for protection.......................................115 Functional diagram for disturbance recorder and trip circuit supervision.................................................................123 Functional diagrams for control and interlocking..................125 Standard configuration G................................................................129 Applications...............................................................................129 Functions...................................................................................129 Default I/O connections .......................................................131 Default disturbance recorder settings...................................133 Sensor settings.....................................................................133 Functional diagrams .................................................................134 Functional diagrams for protection ......................................135 Functional diagram for disturbance recorder and trip circuit supervision.................................................................143 Functional diagrams for control and interlocking..................145 Standard configuration H................................................................149 Applications...............................................................................149 Functions...................................................................................149 Default I/O connections........................................................151 Default disturbance recorder settings...................................152 Functional diagrams..................................................................153 Functional diagrams for protection.......................................153 Functional diagram for disturbance recorder and trip circuit supervision.................................................................161 Functional diagrams for control and interlocking..................163 Standard configuration J.................................................................168 Applications...............................................................................168 Functions...................................................................................168 Default I/O connections........................................................171 Default disturbance recorder settings...................................172 Functional diagrams..................................................................173 Functional diagrams for protection.......................................173 Functional diagram for disturbance recorder and trip circuit supervision.................................................................181 Functional diagrams for control and interlocking..................183 Functional diagrams for power quality..................................187

Section 4
REF615 Application Manual

Requirements for measurement transformers..............189


3

Table of contents

Current transformers......................................................................189 Current transformer requirements for non-directional overcurrent protection................................................................189 Current transformer accuracy class and accuracy limit factor....................................................................................189 Non-directional overcurrent protection.................................190 Example for non-directional overcurrent protection..............191

Section 5

IED physical connections.............................................193


Inputs..............................................................................................193 Energizing inputs.......................................................................193 Phase currents.....................................................................193 Residual current...................................................................193 Phase voltages.....................................................................193 Residual voltage...................................................................194 Sensor inputs.......................................................................194 Auxiliary supply voltage input....................................................194 Binary inputs..............................................................................194 Optional light sensor inputs.......................................................196 Outputs...........................................................................................197 Outputs for tripping and controlling............................................197 Outputs for signalling.................................................................197 IRF.............................................................................................199

Section 6

Glossary.......................................................................201

REF615 Application Manual

1MRS756378 K

Section 1 Introduction

Section 1

Introduction

1.1

This manual
The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.

1.2

Intended audience
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and principles.

1.3
1.3.1

Product documentation
Product documentation set
The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The engineering guide provides information for IEC 61850 engineering of the 615 series protection IEDs with PCM600 and IET600. This guide concentrates especially on the configuration of GOOSE communication with these tools. The guide can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. For more details on tool usage, see the PCM600 documentation. The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also

REF615 Application Manual

Section 1 Introduction

1MRS756378 K

recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service.

1.3.2

Document revision history


Document revision/date A/2007-12-20 B/2008-02-08 C/2008-07-02 D/2009-03-04 E/2009-07-03 F/2010-06-11 G/2010-06-29 H/2010-09-24 K/2012-05-11 Product version 1.0 1.0 1.1 2.0 2.0 3.0 3.0 3.0 4.0 History First release Content updated Content updated to correspond to the product version Content updated to correspond to the product version Content updated Content updated to correspond to the product version Terminology updated Content updated Content updated to correspond to the product version

Download the latest documents from the ABB Web site http://www.abb.com/substationautomation.

REF615 Application Manual

1MRS756378 K

Section 1 Introduction Related documentation


Name of the document Modbus Communication Protocol Manual DNP3 Communication Protocol Manual IEC 60870-5-103 Communication Protocol Manual IEC 61850 Engineering Guide Engineering Manual Installation Manual Operation Manual Technical Manual Document ID 1MRS756468 1MRS756709 1MRS756710 1MRS756475 1MRS757121 1MRS756375 1MRS756708 1MRS756887

1.3.3

1.4
1.4.1

Symbols and conventions


Symbols
The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

REF615 Application Manual

Section 1 Introduction 1.4.2 Document conventions


A particular convention may not be used in this manual.

1MRS756378 K

Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push-button navigation in the LHMI menu structure is presented by using the push-button icons. and . To navigate between the options, use HMI menu paths are presented in bold. Select Main menu/Settings. LHMI messages are shown in Courier font. To save the changes in non-volatile memory, select Yes and press . Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE.

1.4.3

Functions, codes and symbols


Table 1:
Function Protection Three-phase non-directional overcurrent protection, low stage Three-phase non-directional overcurrent protection, high stage Three-phase non-directional overcurrent protection, instantaneous stage Three-phase directional overcurrent protection, low stage Three-phase directional overcurrent protection, high stage Non-directional earth-fault protection, low stage PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 DPHLPDOC1 DPHLPDOC2 DPHHPDOC1 EFLPTOC1 EFLPTOC2 Non-directional earth-fault protection, high stage Non-directional earth-fault protection, instantaneous stage Directional earth-fault protection, low stage EFHPTOC1 EFIPTOC1 DEFLPDEF1 DEFLPDEF2 Directional earth-fault protection, high stage Table continues on next page DEFHPDEF1 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) 3I> -> (1) 3I> -> (2) 3I>> -> Io> (1) Io> (2) Io>> (1) Io>>> Io> -> (1) Io> -> (2) Io>> -> 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 67-1 (1) 67-1 (2) 67-2 51N-1 (1) 51N-1 (2) 51N-2 (1) 50N/51N 67N-1 (1) 67N-1 (2) 67N-2

REF615 functions, codes and symbols


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

1MRS756378 K

Section 1 Introduction
Function Admittance based earth-fault protection IEC 61850 EFPADM1 EFPADM2 EFPADM3 Wattmetric based earth-fault protection WPWDE1 WPWDE2 WPWDE3 Transient / intermittent earth-fault protection Harmonics based earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection INTRPTEF1 HAEFPTOC1 EFHPTOC1 NSPTOC1 NSPTOC2 Phase discontinuity protection Residual overvoltage protection PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 Three-phase undervoltage protection PHPTUV1 PHPTUV2 PHPTUV3 Three-phase overvoltage protection PHPTOV1 PHPTOV2 PHPTOV3 Positive-sequence undervoltage protection Negative-sequence overvoltage protection Frequency protection PSPTUV1 NSPTOV1 FRPFRQ1 FRPFRQ2 FRPFRQ3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 Arc protection ARCSARC1 ARCSARC2 ARCSARC3 Power quality Current total demand distortion Voltage total harmonic distortion Voltage variation Table continues on next page CMHAI1 VMHAI1 PHQVVR1 PQM3I (1) PQM3U (1) PQMU (1) PQM3I (1) PQM3V (1) PQMV (1) IEC 60617 Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF Io>HA Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) U1< (1) U2> (1) f>/f<,df/dt (1) f>/f<,df/dt (2) f>/f<,df/dt (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3) IEC-ANSI 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF 51NHA 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 47U+ (1) 47O- (1) 81 (1) 81 (2) 81 (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

REF615 Application Manual

Section 1 Introduction
Function Control Circuit-breaker control Disconnector control CBXCBR1 DCXSWI1 DCXSWI2 Earthing switch control Disconnector position indication ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 Earthing switch indication ESSXSWI1 ESSXSWI2 Auto-reclosing Synchronism and energizing check Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision SSCBR1 TCSSCBR1 TCSSCBR2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement Sequence current measurement Residual current measurement Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement Frequency measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 FMMXU1 3I I1, I2, I0 Io 3U Uo U1, U2, U0 P, E f CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF DARREC1 SECRSYN1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I SYNC IEC 61850 IEC 60617

1MRS756378 K

IEC-ANSI I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79 25

CBCM TCM (1) TCM (2) MCS 3I 60

3I I1, I2, I0 In 3U Vn U1, U2, U0 P, E f

10

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview

Section 2

REF615 overview

2.1

Overview
REF615 is a dedicated feeder IED (intelligent electronic device) designed for the protection, control, measurement and supervision of utility substations and industrial power systems including radial, looped and meshed distribution networks with or without distributed power generation. REF615 is a member of ABBs Relion product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. The IED provides main protection for overhead lines and cable feeders in distribution networks. The IED is also used as back-up protection in applications, where an independent and redundant protection system is required. Depending on the chosen standard configuration, the IED is adapted for the protection of overhead line and cable feeders in isolated neutral, resistance earthed, compensated and solidly earthed networks. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service. The 615 series IEDs support a range of communication protocols including IEC 61850 with GOOSE messaging, IEC 60870-5-103, Modbus and DNP3.

REF615 Application Manual

11

Section 2 REF615 overview 2.1.1 Product version history


Product version 1.0 1.1 Product history Product released

1MRS756378 K

IRIG-B Support for parallel protocols added: IEC 61850 and Modbus X130 BIO added: optional for variants B and D CB interlocking functionality enhanced TCS functionality in HW enhanced Non-volatile memory added Support for DNP3 serial or TCP/IP Support for IEC 60870-5-103 Voltage measurement and protection Power and energy measurement New standard configurations E and F Disturbance recorder upload via WHMI Fuse failure supervision New configurations G and H Additions to configurations A, B, E and F Application configurability support Analog GOOSE support Large display with single line diagram Enhanced mechanical design Increased maximum amount of events and fault records Admittance-based earth-fault protection Frequency measurement and protection Synchronism and energizing check Combi sensor inputs Multi-port Ethernet option New configuration J Additions/changes for configurations A-H Dual fibre optic Ethernet communication option (COM0032) Generic control point (SPCGGIO) function blocks Additional logic blocks Button object for SLD Controllable disconnector and earth switch objects for SLD Wattmetric based E/F Harmonics based E/F Power Quality functions Increased maximum amount of events and fault records

2.0

3.0

4.0

2.1.2

PCM600 and IED connectivity package version


Protection and Control IED Manager PCM600 Ver. 2.4 SP1 or later REF615 Connectivity Package Ver. 4.0 or later Parameter Setting Firmware Update Disturbance Handling Signal Monitoring Lifecycle Traceability Signal Matrix Communication Management Configuration Wizard
REF615 Application Manual

12

1MRS756378 K

Section 2 REF615 overview

Label Printing IED User Management Application Configuration Graphical Display Editor Event Viewer

Download connectivity packages from the ABB Web site http:// www.abb.com/substationautomation

2.2
2.2.1

Operation functionality
Optional functions
Arc protection Autoreclosing Modbus TCP/IP or RTU/ASCII IEC 60870-5-103 DNP3 TCP/IP or serial Admittance based earth-fault (configuration A, B, E, F, G and J only) Watt-metric based earth-fault (configuration A, B, E, F, G and J only) Harmonics based earth-fault (configuration B, D, F and J only) Power quality functions (configuration J only)

2.3

Physical hardware
The IED consists of two main parts: plug-in unit and case. The content depends on the ordered functionality.

REF615 Application Manual

13

Section 2 REF615 overview

1MRS756378 K

Table 2:
Main unit Plug-in unit -

Plug-in unit and case


Slot ID Content options HMI Auxiliary power/BO module Small (4 lines, 16 characters) Large (8 lines, 16 characters) 48-250 V DC/100-240 V AC; or 24-60 V DC 2 normally-open PO contacts 1 change-over SO contacts 1 normally-open SO contact 2 double-pole PO contacts with TCS 1 dedicated internal fault output contact Only with configurations B, D, E, F, G, H and J: 8 binary inputs 4 SO contacts Only with configurations A and B: 3 phase current inputs (1/5 A) 1 residual current input (1/5 A or 0.2/1 A)1) 1 residual voltage input (60-120 V) 3 binary inputs Only with configurations C, D, E, F, H and J: 3 phase current inputs (1/5 A) 1 residual current input (1/5 A or 0.2/1 A)1) 4 binary inputs

X100

X110

BI/O module

X120

AI/BI module

Case

X130

AI/BI module

Only with configurations E and F: 3 phase voltage inputs (60-120 V) 1 residual voltage input (60-120 V) 4 binary inputs Only with configuration G: 3 combi sensor inputs (three-phase current and voltage) 1 residual current input (0.2/1 A)1) Only with configuration H and J: 3 phase voltage inputs (60-210 V) 1 residual voltage input (60-210 V) 1 reference voltage input for SECRSYN1 (60-210 V) 4 binary inputs Optional for configurations B and D: 6 binary inputs 3 SO contacts See technical manual for details about different type of communication modules.

Sensor input module AI/BI module

Optional BI/O module X000 Optional communication module

1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring core-balance current transformers.

Rated values of the current and voltage inputs are basic setting parameters of the IED. The binary input thresholds are selectable within the range 18176 V DC by adjusting the binary input setting parameters. The connection diagrams of different hardware modules are presented in this manual. See the installation manual for more information about the case and the plug-in unit.

14

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview

Table 3:
Conf. A B C D E F G H J

Number of physical connections in standard configurations


CT 4 4 4 4 4 4 1 4 4 Analog channels VT Combi sensor 1 1 52) 52) 5 5 33) Binary channels BI BO 3 11 (17)1) 4 12 (18)1) 16 16 8 16 16 6 10 (13)1) 6 10 (13)1) 10 10 10 10 10

1) With optional BIO module 2) One of the five channels reserved for future applications 3) Combi sensor inputs for three-phase current and voltage

REF615 Application Manual

15

Section 2 REF615 overview

1MRS756378 K

2.4

Local HMI

REF615
Overcurrent Dir. earth-fault Voltage protection Phase unbalance Thermal overload Breaker failure Disturb. rec. Triggered CB condition monitoring Supervision Arc detected Autoreclose shot in progr.

A070704 V3 EN

Figure 1:

Example of 615 series LHMI

The LHMI of the IED contains the following elements: Display Buttons LED indicators Communication port

The LHMI is used for setting, monitoring and controlling.

2.4.1

Display
The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.

16

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview

Table 4:
Character size

Characters and rows on the view


Rows in view 5 rows 10 rows with large screen 4 rows 8 rows with large screen Characters on row 20 min 8

Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels)

The display view is divided into four basic areas.


1 2

3
A070705 V3 EN

Figure 2:
1 Header 2 Icon 3 Content

Display layout

4 Scroll bar (displayed when needed)

2.4.2

LEDs
The LHMI includes three protection indicators above the display: Ready, Start and Trip. There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected with the LHMI, WHMI or PCM600.

2.4.3

Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons you can give open or close commands to objects in the primary circuit, for example, a circuit breaker, a contactor or a

REF615 Application Manual

17

Section 2 REF615 overview

1MRS756378 K

disconnector. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.

A071176 V1 EN

Figure 3:

LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port

2.5

Web HMI
The WHMI enables the user to access the IED via a Web browser. The supported Web browser versions are Internet Explorer 7.0, 8.0 or 9.0. WHMI is disabled by default.

WHMI offers several functions. Programmable LEDs and event lists System supervision Parameter settings Measurement display Disturbance records Phasor diagram Single-line diagram

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

18

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview

A070754 V4 EN

Figure 4:

Example view of the WHMI

The WHMI can be accessed locally and remotely. Locally by connecting your laptop to the IED via the front communication port. Remotely over LAN/WAN.

2.6

Authorization
The user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords. The default passwords can be changed with Administrator user rights. User authorization is disabled by default but WHMI always uses authorization.

REF615 Application Manual

19

Section 2 REF615 overview

1MRS756378 K

Table 5:
Username VIEWER OPERATOR

Predefined user categories


User rights Read only access Selecting remote or local state with Changing setting groups Controlling Clearing indications (only locally)

ENGINEER

Changing settings Clearing event list Clearing disturbance records Changing system settings such as IP address, serial baud rate or disturbance recorder settings Setting the IED to test mode Selecting language All listed above Changing password Factory default activation

ADMINISTRATOR

For user authorization for PCM600, see PCM600 documentation.

2.6.1

Audit trail
615 series IEDs offer a large set of event logging functions. Normal process related events can be viewed by the normal user with Event Viewer in PCM600. Critical system and IED security related events are logged to a separate non-volatile audit trail for the administrator. Audit trail is a chronological record of system activities that enable the reconstruction and examination of the sequence of events and/or changes in an event. Past user and process events can be examined and analyzed in a consistent method with the help of Event List and Event Viewer in PCM600. The IED stores 2048 system events to non-volatile audit trail. Additionally, 1024 process events are stored in non-volatile event list. Both audit trail and event list work according to the FIFO principle. User audit trail is defined according to the selected set of requirements from IEEE 1686. The logging is based on predefined usernames or user categories. The user audit trail events are supported in IEC 61850-8-1, PCM600, LHMI and WHMI.
Table 6:
Enum Configuration change Firmware change Setting group remote Table continues on next page User changed setting group remotely

Audit trail events


Explanation/note Configuration files changed

20

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview


Enum Setting group local Control remote Control local Test on Test off Setting commit Time change View audit log Login Logout Firmware reset Audit overflow Reset issued by user or tool Too many audit events in the time period Administrator accessed audit trail Explanation/note User changed setting group locally DPC object control remote DPC object control local Test mode on Test mode off Settings has been changed

PCM600 Event Viewer can be used to view the audit trail events together with normal events. Since only the administrator has the right to read audit trail, authorization must be properly configured in PCM600. The audit trail cannot be reset but PCM600 Event Viewer can filter data. Some of the audit trail events are interesting also as normal process events. To expose the audit trail events also as normal process events, define the level parameter via Configuration/Authorization/ Authority logging.
Table 7:
Audit trail event None Configuration change Firmware change Setting group remote Setting group local Control remote Control local Test on Test off Setting commit Time change View audit log Login Table continues on next page Configuration change x x

Audit trail events


Authority logging Setting group x x x x Setting group, control x x x x x x x x Settings edit x x x x x x x x x

REF615 Application Manual

21

Section 2 REF615 overview


Audit trail event Logout Firmware reset Audit overflow Authority logging

1MRS756378 K

2.7

Communication
The IED supports a range of communication protocols including IEC 61850, IEC 60870-5-103, Modbus and DNP3. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the IEDs, is only enabled by the IEC 61850 communication protocol. The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the standard COMTRADE file format. The IED can send and receive binary signals from other IEDs (so called horizontal communication) using the IEC61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. Further, the IED supports sending and receiving of analog values using GOOSE messaging. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. The IED can simultaneously report events to five different clients on the station bus. The IED can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus. All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernetbased communication systems via the RJ-45 connector (100Base-TX) or the fibreoptic LC connector (100Base-FX). An optional serial interface is available for RS-232/RS-485 communication. For the correct operation of redundant loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The IED itself does not support link-down detection or RSTP. The ring recovery process is based on the aging of MAC addresses and link-up/link-down events can cause temporary breaks in communication. For better performance of the self-healing loop, it is recommended that the external switch furthest from the 615 IED loop is assigned as the root switch (bridge priority = 0) and the bridge priority increases towards the IED loop. The end links of the IED loop can be attached to the same external switch or to two adjacent external switches. Selfhealing Ethernet ring requires a communication module with at least two Ethernet interfaces for all IEDs.

22

REF615 Application Manual

1MRS756378 K

Section 2 REF615 overview

Bridge priority 32768 Port priority


64 48 32

16384
16 0

0
0

36864
80 96 112

45056
176 160 128

40960
144 112 128

32768
48 32

16384
16

RE_615

RE_615

RE_615

RE_615

RE_615
GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V1 EN

RE_615

RE_615

RE_615

Figure 5:

Self-healing Ethernet ring solution

The Ethernet ring solution supports the connection of up to thirty 615 series IEDs. If more than 30 IEDs are to be connected, it is recommended that the network is split into several rings with no more than 30 IEDs per ring.

REF615 Application Manual

23

24

1MRS756378 K

Section 3 REF615 standard configurations

Section 3

REF615 standard configurations

3.1

Standard configurations
REF615 is available in nine alternative standard configurations. The standard signal configuration can be altered by means of the graphical signal matrix or the graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions using various logical elements, including timers and flip-flops. By combining protection functions with logic function blocks, the IED configuration can be adapted to user-specific application requirements.

Table 8:
Description

Standard configurations
Std. conf. A B C D E F G H J

Non-directional overcurrent and directional earth-fault protection and CB control Non-directional overcurrent and directional earth-fault protection, CB condition monitoring, CB control and with the optional I/O module control of two network objects Non-directional overcurrent and non-directional earth-fault protection and CB control Non-directional overcurrent and non-directional earth-fault protection, CB condition monitoring, CB control and with the optional I/O module control of two network objects Non-directional overcurrent and directional earth-fault protection with phase-voltage based measurements, CB condition monitoring and CB control Directional overcurrent and directional earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage protection, CB condition monitoring and CB control Directional overcurrent and directional earth-fault protection, phase-voltage based protection and measurement functions, CB condition monitoring, CB control and sensor inputs Non-directional overcurrent and non-directional earth-fault protection, phase-voltage and frequency based protection and measurement functions, synchro-check , CB condition monitoring and CB control Directional overcurrent and directional earth-fault protection, phase-voltage and frequency based protection and measurement functions, synchro check, CB condition monitoring and CB control

Table 9:
Functionality Protection

Supported functions
A B C D E F G H J

Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Table continues on next page

REF615 Application Manual

25

Section 3 REF615 standard configurations


Functionality Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Harmonics based earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Table continues on next page A 1)2) 1)2) 1)2) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) 2)7) 9) 2) 2) 2) B 1)2) 1)2) 1)2) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) o 1)2)5) 2)7) o 5)7)8) 9) 2) 2) 2) C 1) 1) 1) 1) D 1) 1) 1) 1) o 5)7)8) E 1)4) 1)4) 1)4) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) 2)7) 9) 4) 4) 4) F 1)4) 1)4) 1)4) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) 2)7) o 5)7)8) 9) 4) 4) 4) G 1)3) 1)3) 1)3) o 1)5)6) o 1)5)6) o 1)5)6) o 1)5)6) o 1)5)6) o 1)5)6) 9) 6) 6) 6)

1MRS756378 K

H 1) 1) 1) 1) 4) 4) 4)

J 1)4) 1)4) 1)4) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) o 1)4)5) 2)7) o 5)7)8) 9) 4) 4) 4)

26

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


A o o o B o o o C o o o D o o o E o o o F o o o G o o o H o o o J o o o

Functionality Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 Negative-sequence overvoltage protection, instance 1 Frequency protection, instance 1 Frequency protection, instance 2 Frequency protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Synchronism and energizing check Condition Monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Power Quality Table continues on next page

o -

8) 8) 8) 8) 8) 8) o -

o -

8) 8) 8) 8) 8) 8) o -

8) 8) 8) 8) 8) 8) o -

8) 8) 8) 8) 8) 8) o -

8) 8) 8) 8) 8) 8) o -

8) 8) 8) 8) 8) 8) o

8) 8) 8) 8) 8) 8) o

REF615 Application Manual

27

Section 3 REF615 standard configurations


Functionality Current total demand distortion, instance 1 Voltage total harmonic distortion, instance 1 Voltage variation, instance 1 Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement, including power factor Frequency measurement = Included, = Optional at the time of the order 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) A B C D E F G -

1MRS756378 K

H -

J o 10) o 10) o 10)

I0 selectable by parameter, I0 measured as default. U0 measured is always used U0 calculated and negative sequence voltage selectable by parameter, U0 calculated as default. U0 selectable by parameter, U0 measured as default. One of the following can be ordered as an option: Admittance based E/F, Wattmetric based E/F or Harmonics based E/F. The option is an addition to the existing E/F of the original configuration. The Admittance based and Wattmetric based optional E/F has also a predefined configuration in the relay. The optional E/F can be set on or off. U0 calculated is always used. I0 measured is always used. Available in IED and SMT but not connected to anything in logic. Io selectable by parameter, Io calculated as default. This option includes Current total demand distrortion, Voltage total harmonic distortion and Voltage variation.

3.1.1

Addition of control functions for primary devices and the use of binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the configuration, additional binary inputs and/or outputs are needed to complement the standard configuration. If the number of inputs and/or outputs in a standard configuration is not sufficient, it is possible either to modify the chosen IED standard configuration in order to release some binary inputs or binary outputs which have originally been configured for other purposes, or to integrate an external input/output module, for example RIO600, to the IED. The external I/O modules binary inputs and outputs of can be used for the less timecritical binary signals of the application. The integration enables releasing some initially reserved binary inputs and outputs of the IEDs standard configuration.

28

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The suitability of the IEDs binary outputs which have been selected for primary device control should be carefully verified, for example make and carry and breaking capacity. If the requirements for the primary device control circuit are not met, using external auxiliary relays should be considered.

REF615 Application Manual

29

Section 3 REF615 standard configurations

1MRS756378 K

3.2

Connection diagrams

A071288 V6 EN

Figure 6:

Connection diagram for the A and B configurations [1]

[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B 30 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071290 V5 EN

Figure 7:

Connection diagram for the C and D configurations

[2]

[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D REF615 Application Manual 31

Section 3 REF615 standard configurations

1MRS756378 K

GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V4 EN

Figure 8:

Connection diagram for the E and F configurations

32

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-5D0135B3-3890-497A-8AAA-0362730C8682 V1 EN

Figure 9:

Connection diagram for the E and F configurations

REF615 Application Manual

33

Section 3 REF615 standard configurations

1MRS756378 K

GUID-B70F0C14-52B2-4213-8781-5A7CA1E40451 V1 EN

Figure 10:

Connection diagram for the G configuration

34

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-E8E2F79F-3DD8-46BD-8DE7-87A30133A7AE V1 EN

Figure 11:

Connection diagram for the H and J configuration

REF615 Application Manual

35

Section 3 REF615 standard configurations

1MRS756378 K

3.3

Presentation of standard configurations


Functional diagrams
The functional diagrams describe the IED's functionality from the protection, measuring, condition monitoring, disturbance recording, control and interlocking perspective. Diagrams show the default functionality with simple symbol logics forming principle diagrams. The external connections to primary devices are also shown, stating the default connections to measuring transformers. The positive measuring direction of directional protection functions is towards the outgoing feeder. The functional diagrams are divided into sections with each section constituting one functional entity. The external connections are also divided into sections. Only the relevant connections for a particular functional entity are presented in each section. Protection function blocks are part of the functional diagram. They are identified based on their IEC 61850 name but the IEC based symbol and the ANSI function number are also included. Some function blocks, such as PHHPTOC, are used several times in the configuration. To separate the blocks from each other, the IEC 61850 name, IEC symbol and ANSI function number are appended with a running number, that is an instance number, from one upwards. If the block has no suffix after the IEC or ANSI symbol, the function block has been used, that is, instantiated, only once. The IEDs internal functionality and the external connections are separated with a dashed line presenting the IEDs physical casing.

Signal Matrix and Application Configuration


With Signal Matrix and Application Configuration in PCM600, it is possible to modify the standard configuration according to the actual needs. The IED is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and for making cross-references between the physical I/O signals and the function blocks. The Signal Matrix tool cannot be used for adding or removing function blocks, for example, GOOSE receive function blocks. The Application Configuration tool is used for these kind of operations. If a function block is removed with Application Configuration, the function related data disappears from the menus as well as from the 61850 data model, with the exception of some basic function blocks, which are mandatory and thus cannot be removed from the IED configuration by removing them from the Application Configuration.

36

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

3.4
3.4.1

Standard configuration A
Applications
The standard configuration for non-directional overcurrent and directional earthfault protection is mainly intended for cable and overhead-line feeder applications in isolated and resonant-earthed distribution networks. The configuration also includes additional options to select earth-fault protection based on admittance or wattmetric based principle. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.4.2

Functions
Table 10:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Table continues on next page PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 INTRPTEF1 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF

Functions included in the standard configuration A


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

37

Section 3 REF615 standard configurations


Function Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Auto-reclosing Condition Monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Residual voltage measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 RESVMMXU1 3I I1, I2, I0 Io Uo TCSSCBR1 TCSSCBR2 TCS (1) TCS (2) CBXCBR1 DARREC1 I <-> O CB O -> I IEC 61850 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB 79

TCM (1) TCM (2)

3I I1, I2, I0 In Vn

3.4.2.1

Default I/O connections


Table 11:
Binary input X120-BI1 X120-BI2 X120-BI3

Default connections for binary inputs


Default usage Blocking of overcurrent instantaneous stage Circuit breaker closed position indication Circuit breaker open position indication Connector pins X120-1,2 X120-3,2 X120-4,2

38

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

Table 12:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2

Default connections for binary outputs


Default usage Close circuit breaker Circuit breaker failure protection trip to upstream breaker Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 General start indication General operate indication Connector pins X100-6,7 X100-8,9 X100-15,16,17,18,1 9 X100-20,21,22,23,2 4 X100-10,11,12 X100-13,14,15

Table 13:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Non-directional overcurrent operate Directional/intermittent earth fault operate Double (cross country) earth fault or residual overvoltage operate Negative seq. overcurrent/phase discontinuity operate Thermal overload alarm Breaker failure operate Disturbance recorder triggered Not connected Trip circuit supervision alarm Arc protection operate Auto reclose in progress

3.4.2.2

Default disturbance recorder settings


Table 14:
Channel 1 2 3 4 5 6 7 8 9

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io Uo -

Table continues on next page

REF615 Application Manual

39

Section 3 REF615 standard configurations


Channel 10 11 12 Selection and text -

1MRS756378 K

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

3.4.3

Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.4.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections.

40

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071316 V4 EN

Figure 12:

Overcurrent protection

Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication.

REF615 Application Manual

41

Section 3 REF615 standard configurations

1MRS756378 K

DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1

DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (1) 67N-1 (1)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0 BLOCK

I0>> 51N-2
START OPERATE

LED3 (NEF OPERATE)

ENA_MULT Calculated Io

INTERMITTENT EARTH-FAULT PROTECTION DEFLPDEF2

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

INTRPTEF1

I0 >

67NIEF
START OPERATE BLK_EF U0 BLOCK

OR DEFHPDEF1 LED2 (EF OPERATE)

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

OR ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

LED2 (WDE OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE

OR

LED2 (ADM OPERATE)

BLOCK RELEASE

WPWDE3

EFPADM3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE BLOCK RELEASE

A071318 V6 EN

Figure 13:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only, or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE). In addition, there is a dedicated protection stage (INTRPTEF) either for transient-based earth-fault protection or for cable intermittent earth-fault protection in compensated networks. A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for protection against double earth-fault situations in isolated or compensated

42

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

networks. This protection function uses the calculated residual current originating from the phase currents. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earth-fault protection operate indication.

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 14:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 3.

REF615 Application Manual

43

Section 3 REF615 standard configurations

1MRS756378 K

PHASE DISCONTINUITY PROTECTION PDNSTOC1

I2 / I1 46PD
3I BLOCK START OPERATE

LED4 (NPS/PD OPERATE)

THERMAL OVERLOAD PROTECTION T1PTTR1

3 > 49F
3I OPERATE ALARM BLK_OPR BLK_CLOSE ENA_MULT START

LED5 (OVERLOAD ALARM)

PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate EFPADM2-operate EFPADM3-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE2-operate WPWDE3-operate X120_BI2 (CB Closed)

BREAKER FAILURE PROTECTION OR CCBRBRF1 LED6 (CBFP OPERATE) +

3I>/Io -> BF 51BF/51NBF


3I Io START CB_FAULT BLOCK POSCLOSE TRRET TRBU CB_FAULT_AL

X100
PO2

8 9

CBFP trip to upstream breaker

A071320 V6 EN

Figure 15:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

44

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate X120_BI3 (CB Open) PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected INTRPTEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC

OR

OR

A071322 V6 EN

Figure 16:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions.

REF615 Application Manual

45

Section 3 REF615 standard configurations

1MRS756378 K

The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

46

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER

3.4.3.2

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate OR PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21

OR

OR INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC1-inpro DARREC1-close_cb DARREC1-unsuc_recl

BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32 BI#33 BI#34 BI#35 BI#36

NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open)

OR

OR OR

OR

BI#37

OR

OR

TCSSCBR1 TRPPTRC1 - trip TRPPTRC2 - trip OR


BLOCK ALARM

OR

LED9 (TCS ALARM)

TCSSCBR2
BLOCK ALARM

A071324 V6 EN

Figure 17:

Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected. Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9.

REF615 Application Manual

47

Section 3 REF615 standard configurations

1MRS756378 K

By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.

3.4.3.3

Functional diagrams for control and interlocking

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate DARREC1-open cb CBXCBR1-exe_op

MASTER TRIP #1
X100

+
TRPPTRC1
BLOCK TRIP

16

PO3
OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

Open CB / trip coil 1


17 15 18 19

TCS1

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate CCBRBRF1-trret ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate
A071326 V6 EN

MASTER TRIP #2
X100

+
TRPPTRC2
BLOCK TRIP

20 22

PO4
21 23 24

Open CB / trip coil 2

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS2

Figure 18:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary
48 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

A071328 V5 EN

Figure 19:

Circuit breaker control

The ENA_CLOSE input, which enables the closing of the circuit breaker, is a status of the Master Trip in the breaker control function block CBXCBR. The open operation is always enabled. If the ENA_CLOSE signal is completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

REF615 Application Manual

49

Section 3 REF615 standard configurations

1MRS756378 K

COMMON ALARM / INDICATION 1 & 2


PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start EFPADM1-start EFPADM2-start EFPADM3-start INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start WPWDE1-start WPWDE2-start WPWDE3-start

X100
OR

+ SO1
TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+ SO2

13
Operate Indication

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

14

OR

A071330 V5 EN

Figure 20:

Alarm indication

The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100: 13-15)

TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.

50

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

3.5
3.5.1

Standard configuration B
Applications
The standard configuration for non-directional overcurrent and directional earthfault protection is mainly intended for cable and overhead-line feeder applications in isolated and resonant-earthed distribution networks. The configuration also includes additional options to select earth-fault protection based on admittance, wattmetric or harmonic based principle. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.5.2

Functions
Table 15:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Table continues on next page PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 INTRPTEF1 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF

Functions included in the standard configuration B


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

51

Section 3 REF615 standard configurations


Function Harmonics based earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Measurement Disturbance recorder Three-phase current measurement, instance 1 Table continues on next page RDRE1 CMMXU1 3I SSCBR1 TCSSCBR1 TCSSCBR2 CBCM TCS (1) TCS (2) CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I IEC 61850 HAEFPTOC1 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 Io>HA Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 51NHA 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79

CBCM TCM (1) TCM (2)

3I

52

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Sequence current measurement Residual current measurement, instance 1 Residual voltage measurement IEC 61850 CSMSQI1 RESCMMXU1 RESVMMXU1 IEC 60617 I1, I2, I0 Io Uo IEC-ANSI I1, I2, I0 In Vn

3.5.2.1

Default I/O connections


Table 16:
Binary input X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1 X120-BI2 X120-BI3

Default connections for binary inputs


Default usage Directional earth fault protection's basic angle control Circuit breaker low gas pressure indication Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Connector pins X110-3,4 X110-5,6 X110-6,7 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2 X120-3,2 X120-4,2

Table 17:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2 X110-SO1 X110-SO2 X110-SO3

Default connections for binary outputs


Default usage Close circuit breaker Circuit breaker failure protection trip to upstream breaker Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 General start indication General operate indication Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Connector pins X100-6,7 X100-8,9 X100-15,16,17,18,1 9 X100-20,21,22,23,2 4 X100-10,11,12 X100-13,14,15 X110-14,15,16 X110-17,18,19 X110-20,21,22

Table 18:
LED 1 2 3

Default connections for LEDs


Default usage Non-directional overcurrent operate Directional/intermittent earth fault operate Double (cross country) earth fault or residual overvoltage operate

Table continues on next page

REF615 Application Manual

53

Section 3 REF615 standard configurations


LED 4 5 6 7 8 9 10 11 Default usage Negative seq. overcurrent/phase discontinuity operate Thermal overload alarm Breaker failure operate Disturbance recorder triggered Circuit breaker condition monitoring alarm Trip circuit supervision alarm Arc protection operate Auto reclose in progress

1MRS756378 K

3.5.2.2

Default disturbance recorder settings


Table 19:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io Uo -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

3.5.3

Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12

54

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.5.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections.

A071332 V5 EN

Figure 21:

Overcurrent protection

REF615 Application Manual

55

Section 3 REF615 standard configurations

1MRS756378 K

Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication. The upstream blocking from the start of the overcurrent second high stage (PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.

56

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1

DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (1) 67N-1 (1)


I0 START OPERATE I0 BLOCK

I0>> 51N-2
START OPERATE

X110 3 4

U0 BLOCK

LED3 (NEF OPERATE)

BI 2 (BACTRL)

ENA_MULT RCA_CTL

ENA_MULT Calculated Io

INTERMITTENT EARTH-FAULT PROTECTION DEFLPDEF2

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

INTRPTEF1

I0 >

67NIEF
START OPERATE BLK_EF U0 BLOCK

OR DEFHPDEF1

LED2 (EF OPERATE)

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

OR ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

LED2 (WDE OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE

OR

LED2 (ADM OPERATE)

BLOCK RELEASE

HARMONIC EARTH-FAULT PROTECTION (Optional) EFPADM3 HAEFPTOC1

WPWDE3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE I0 BLOCK RELEASE

I0>HA 51NHA
START I_REF_RES OPERATE BLOCK

A071334 V6 EN

Figure 22:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE) or harmonic based earth-fault protection (HAEFPTOC). In addition, there is a dedicated protection stage (INTRPTEF) either for transient-based earth-fault protection or for cable intermittent earth-fault protection in compensated networks. A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for protection against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents.

REF615 Application Manual

57

Section 3 REF615 standard configurations

1MRS756378 K

The binary input 2 (X110:3-4) is intended for directional earth-fault protection blocks relay characteristic angle (RCA: 0/-90) or operation mode (I0Sin/ I0Cos) change. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earthfault protection operate indication.

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 23:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 3.

58

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

PHASE DISCONTINUITY PROTECTION PDNSTOC1

I2 / I1 46PD
3I BLOCK START OPERATE

LED4 (NPS/PD OPERATE)

THERMAL OVERLOAD PROTECTION T1PTTR1

3 > 49F
3I OPERATE ALARM BLK_OPR BLK_CLOSE ENA_MULT START

LED5 (OVERLOAD ALARM)

PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate EFPADM2-operate EFPADM3-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE2-operate WPWDE3-operate X120_BI2 (CB Closed)

BREAKER FAILURE PROTECTION OR CCBRBRF1 LED6 (CBFP OPERATE) +

3I>/Io -> BF 51BF/51NBF


3I Io START CB_FAULT BLOCK POSCLOSE TRRET TRBU CB_FAULT_AL

X100
PO2

8 9

CBFP trip to upstream breaker

A071320 V6 EN

Figure 24:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

REF615 Application Manual

59

Section 3 REF615 standard configurations

1MRS756378 K

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

OR

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON

X110 6 7

X120_BI3 (CB Open) BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected INTRPTEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate


A071338 V7 EN

SYNC

OR

Figure 25:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions.

60

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

REF615 Application Manual

61

Section 3 REF615 standard configurations


3.5.3.2

1MRS756378 K

Functional diagram for disturbance recorder and trip circuit supervision


DISTURBANCE RECORDER

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate OR PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21

OR

OR INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC1-inpro DARREC1-close_cb DARREC1-unsuc_recl

BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32 BI#33 BI#34 BI#35 BI#36

NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open)

OR

OR OR

OR

BI#37

OR

OR

TCSSCBR1 TRPPTRC1 - trip TRPPTRC2 - trip OR


BLOCK ALARM

OR

LED9 (TCS ALARM)

TCSSCBR2
BLOCK ALARM

A071324 V6 EN

Figure 26:

Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected. Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9.

62

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.

3.5.3.3

Functional diagrams for control and interlocking


MASTER TRIP #1
X100

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate DARREC1-open cb CBXCBR1-exe_op

+
TRPPTRC1
BLOCK TRIP

16

PO3
OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

Open CB / trip coil 1


17 15 18 19

TCS1

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate CCBRBRF1-trret ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate
A071326 V6 EN

MASTER TRIP #2
X100

+
TRPPTRC2
BLOCK TRIP

20 22

PO4
21 23 24

Open CB / trip coil 2

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS2

Figure 27:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary

REF615 Application Manual

63

Section 3 REF615 standard configurations

1MRS756378 K

input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

A071344 V6 EN

Figure 28:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 20: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)

Primary device position

64

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE signal is completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8.

REF615 Application Manual

65

Section 3 REF615 standard configurations

1MRS756378 K

COMMON ALARM / INDICATION 1 & 2


PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start EFPADM1-start EFPADM2-start EFPADM3-start INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start WPWDE1-start WPWDE2-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

X100
OR

+ SO1
TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+ SO2

13
Operate Indication

14

OR

X110

+
PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

17
Over Current Operate Alarm

SO2
OR TPGAPC2
IN1 IN2 OUT1 OUT2

19 18

+ SO3

20
Earth Fault Operate Alarm

OR

22 21

A071346 V6 EN

Figure 29:

Alarm indication

The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100: 13-15)

66

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.

3.6
3.6.1

Standard configuration C
Applications
The standard configuration for non-directional overcurrent and non-directional earthfault protection is mainly intended for cable and overhead-line feeder applications in directly or resistance earthed distribution networks. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.6.2

Functions
Table 21:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Table continues on next page PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 EFLPTOC1 EFLPTOC2 EFHPTOC1 EFIPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) Io> (1) Io> (2) Io>> (1) Io>>> I2> (1) I2> (2) I2/I1> 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 51N-1 (1) 51N-1 (2) 51N-2 (1) 50N/51N 46 (1) 46 (2) 46PD

Functions included in the standard configuration C


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

67

Section 3 REF615 standard configurations


Function Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Auto-reclosing Condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 3I I1, I2, I0 Io TCSSCBR1 TCSSCBR2 TCS (1) TCS (2) CBXCBR1 DARREC1 I <-> O CB O -> I IEC 61850 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB 79

TCM (1) TCM (2)

3I I1, I2, I0 In

3.6.2.1

Default I/O connections


Table 22:
Binary input X120-BI1 X120-BI2 X120-BI3 X120-BI4

Default connections for binary inputs


Default usage Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Reset of master trip lockout Connector pins X120-1,2 X120-3,2 X120-4,2 X120-5,6

Table 23:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2

Default connections for binary outputs


Default usage Close circuit breaker Circuit breaker failure protection trip to upstream breaker Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 General start indication General operate indication Connector pins X100-6,7 X100-8,9 X100-15,16,17,18,1 9 X100-20,21,22,23,2 4 X100-10,11,12 X100-13,14,15

68

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

Table 24:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Non-directional overcurrent operate Non-directional earth fault operate Sensitive earth fault operate Negative seq. overcurrent/phase discontinuity operate Thermal overload alarm Breaker failure operate Disturbance recorder triggered Not connected Trip circuit supervision alarm Arc protection operate Auto reclose in progress

3.6.2.2

Default disturbance recorder settings


Table 25:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

REF615 Application Manual

69

Section 3 REF615 standard configurations 3.6.3 Functional diagrams

1MRS756378 K

The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a summation connection of the phase current transformers.

3.6.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections.

70

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071348 V3 EN

Figure 30:

Overcurrent protection

Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication.

REF615 Application Manual

71

Section 3 REF615 standard configurations

1MRS756378 K

EARTH FAULT PROTECTION


EFLPTOC1 I0 > 51N-1
I0 BLOCK ENA_MULT START OPERATE

EFHPTOC1 I0 >> 51N-2


I0 BLOCK ENA_MULT START OPERATE

OR EFIPTOC1 I0 >>> 50N


I0 BLOCK ENA_MULT START OPERATE

LED2 (EF OPERATE)

SENSITIVE EARTH FAULT PROTECTION


EFLPTOC2 I0 > 51N-1
I0 BLOCK ENA_MULT START OPERATE

LED3 (SEF OPERATE)

A071350 V4 EN

Figure 31:

Non-directional earth-fault protection

Four stages are offered for non-directional earth-fault protection. One stage is dedicated to sensitive earth-fault protection. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for the sensitive earth-fault protection operate indication.

72

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071352 V4 EN

Figure 32:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

REF615 Application Manual

73

Section 3 REF615 standard configurations

1MRS756378 K

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1 79
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate EFLPTOC1-operate EFHPTOC1-operate
INIT_1 INIT_2 INIT_3 INIT_4 INIT_5 INIT_6 DEL_INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

X120_BI3 (CB Open)

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

CB_POS CB_READY INC_SHOTP

OR

INHIBIT_RECL RECL_ON SYNC

A071354 V5 EN

Figure 33:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different
74 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

3.6.3.2

Functional diagram for disturbance recorder and trip circuit supervision


DISTURBANCE RECORDER

RDRE1
PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start EFLPTOC1-start EFHPTOC1-start EFIPTOC1-start EFLPTOC2-start PDNSPTOC1-start T1PTTR1-start CCBRBRF1-trret CCBRBRF1-trbu OR
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 TRIGGERED

LED7 (DR TRIGGERING)

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate EFLPTOC1-operate EFHPTOC1-operate EFIPTOC1-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open)

OR

EFLPTOC2-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC1-inpro DARREC1-close_cb DARREC1-unsuc_recl

BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32 BI#33

OR

OR

TCSSCBR1 TRPPTRC1 - trip TRPPTRC2 - trip OR


BLOCK ALARM

OR

LED9 (TCS ALARM)

TCSSCBR2
BLOCK ALARM

A071356 V4 EN

Figure 34:
REF615 Application Manual

Disturbance recorder
75

Section 3 REF615 standard configurations

1MRS756378 K

All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected. Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.

3.6.3.3

Functional diagrams for control and interlocking

A071358 V4 EN

Figure 35:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary
76 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

A071360 V4 EN

Figure 36:

Circuit breaker control

The ENA_CLOSE input, which enables the closing of the circuit breaker, is a status of the Master Trip in the breaker control function block CBXCBR. The open operation is always enabled. If the ENA_CLOSE signal is completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

REF615 Application Manual

77

Section 3 REF615 standard configurations

1MRS756378 K

COMMON ALARM / INDICATION 1 & 2


PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start EFLPTOC1-start EFHPTOC1-start EFIPTOC1-start EFLPTOC2-start PDNSPTOC1-start

X100
OR

+ SO1
TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate EFLPTOC1-operate EFHPTOC1-operate EFIPTOC1-operate EFLPTOC2-operate PDNSPTOC1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

11 12

+ SO2

13
Operate Indication

OR

14

A071362 V4 EN

Figure 37:

Alarm indication

The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14)

TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.

3.7
3.7.1

Standard configuration D
Applications
The standard configuration for non-directional overcurrent and non-directional earthfault protection is mainly intended for cable and overhead-line feeder applications in directly or resistance earthed distribution networks. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

78

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations Functions


Table 26:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Harmonics based earth-fault protection Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Table continues on next page CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 EFLPTOC1 EFLPTOC2 EFHPTOC1 EFIPTOC1 HAEFPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) Io> (1) Io> (2) Io>> (1) Io>>> Io>HA I2> (1) I2> (2) I2/I1> 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3) 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 51N-1 (1) 51N-1 (2) 51N-2 (1) 50N/51N 51NHA 46 (1) 46 (2) 46PD 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

3.7.2

Functions included in the standard configuration D


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

79

Section 3 REF615 standard configurations


Function Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 3I I1, I2, I0 Io SSCBR1 TCSSCBR1 TCSSCBR2 CBCM TCS (1) TCS (2) IEC 61850 ESSXSWI1 ESSXSWI2 DARREC1 IEC 60617 I <-> O ES (1) I <-> O ES (2) O -> I

1MRS756378 K

IEC-ANSI I <-> O ES (1) I <-> O ES (2) 79

CBCM TCM (1) TCM (2)

3I I1, I2, I0 In

3.7.2.1

Default I/O connections


Table 27:
Binary input X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1 X120-BI2 X120-BI3 X120-BI4

Default connections for binary inputs


Default usage Auto reclose external start command Circuit breaker low gas pressure indication Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Reset of master trip lockout Connector pins X110-3,4 X110-5,6 X110-6,7 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2 X120-3,2 X120-4,2 X120-5,6

Table 28:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2

Default connections for binary outputs


Default usage Close circuit breaker Circuit breaker failure protection trip to upstream breaker Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 General start indication General operate indication Connector pins X100-6,7 X100-8,9 X100-15,16,17,18,1 9 X100-20,21,22,23,2 4 X100-10,11,12 X100-13,14,15

Table continues on next page 80 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Binary output X110-SO1 X110-SO2 X110-SO3 Default usage Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Connector pins X110-14,15,16 X110-17,18,19 X110-20,21,22

Table 29:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Non-directional overcurrent operate Non-directional earth fault operate Sensitive earth fault operate Negative seq. overcurrent/phase discontinuity operate Thermal overload alarm Breaker failure operate Disturbance recorder triggered Circuit breaker condition monitoring alarm Trip circuit supervision alarm Arc protection operate Auto reclose in progress

3.7.2.2

Default disturbance recorder settings


Table 30:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
REF615 Application Manual 81

Section 3 REF615 standard configurations 3.7.3 Functional diagrams

1MRS756378 K

The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a summation connection of the phase current transformers.

3.7.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections.

82

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071364 V4 EN

Figure 38:

Overcurrent protection

Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication. The upstream blocking from the start of the overcurrent second high stage (PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.

REF615 Application Manual

83

Section 3 REF615 standard configurations

1MRS756378 K

EARTH-FAULT PROTECTION EFLPTOC1

I0> (1) 51N-1 (1)


I0 BLOCK ENA_MULT START OPERATE

OR

LED2 (EF OPERATE)

SENSITIVE EARTH-FAULT PROTECTION EFHPTOC1 EFLPTOC2

I0>> (1) 51N-2 (1)


I0 BLOCK ENA_MULT START OPERATE I0

I0> (2) 51N-1 (2)


START OPERATE BLOCK ENA_MULT

LED3 (SEF OPERATE)

HARMONIC EARTH-FAULT PROTECTION (Optional) EFIPTOC1 HAEFPTOC1

I0>>> 50N/51N
I0 BLOCK ENA_MULT START OPERATE I0

I0>HA 51NHA
START I_REF_RES OPERATE BLOCK

GUID-319BCA20-DC11-4110-8E70-F9E9474CDA07 V1 EN

Figure 39:

Non-directional earth-fault protection

Four stages are offered for non-directional earth-fault protection. One stage is dedicated to sensitive earth-fault protection. Based on the order code, the configuration can also include an optional harmonic-based earth-fault (HAEFPTOC) protection. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for the sensitive earth-fault protection operate indication.

84

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A071352 V4 EN

Figure 40:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

REF615 Application Manual

85

Section 3 REF615 standard configurations

1MRS756378 K

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1 79
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate EFLPTOC1-operate EFHPTOC1-operate X110_BI2 (AR ext. Start) X120_BI3 (CB Open)
INIT_1 INIT_2 INIT_3 INIT_4 INIT_5 INIT_6 DEL_INIT_3 DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

X110 6 7
BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

OR

A071370 V5 EN

Figure 41:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions.

86

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. The INIT6 input in the autorecloser function block is controlled by a binary input 2 (X110:3-4) enabling the use of the external start command. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

REF615 Application Manual

87

Section 3 REF615 standard configurations


3.7.3.2

1MRS756378 K

Functional diagram for disturbance recorder and trip circuit supervision


DISTURBANCE RECORDER

RDRE1
PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start EFLPTOC1-start EFHPTOC1-start EFIPTOC1-start EFLPTOC2-start PDNSPTOC1-start T1PTTR1-start CCBRBRF1-trret CCBRBRF1-trbu OR
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 TRIGGERED

LED7 (DR TRIGGERING)

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate EFLPTOC1-operate EFHPTOC1-operate EFIPTOC1-operate

OR

EFLPTOC2-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC1-inpro DARREC1-close_cb DARREC1-unsuc_recl

BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32 BI#33

OR

X110 3 4

BI2 (AR_ext_start)

ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open)

OR

TCSSCBR1 TRPPTRC1 - trip TRPPTRC2 - trip OR


BLOCK ALARM

OR

LED9 (TCS ALARM)

TCSSCBR2
BLOCK ALARM

A071372 V5 EN

Figure 42:

Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected, as well as the autorecloser external start command from the binary input 2 (X110:3-4). Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.

88

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for control and interlocking

3.7.3.3

A071358 V4 EN

Figure 43:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

REF615 Application Manual

89

Section 3 REF615 standard configurations

1MRS756378 K

A071376 V5 EN

Figure 44:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 31: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)

Primary device position

90

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8.

REF615 Application Manual

91

Section 3 REF615 standard configurations

1MRS756378 K

A071378 V4 EN

Figure 45:

Alarm indication

The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22)

TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.

92

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

3.8
3.8.1

Standard configuration E
Applications
The standard configuration for non-directional overcurrent and directional earthfault protection is mainly intended for cable and overhead-line feeder applications in isolated and resonant-earthed distribution networks. The configuration also includes additional options to select earth-fault protection based on admittance or wattmetric based principle. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.8.2

Functions
Table 32:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Table continues on next page PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 INTRPTEF1 3I> (1) 3I>> (1) 3I>> (2) 3I>>> (1) Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF 51P-1 (1) 51P-2 (1) 51P-2 (2) 50P/51P (1) 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF

Functions included in the standard configuration E


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

93

Section 3 REF615 standard configurations


Function Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Table continues on next page 94 RDRE1 CMMXU1 CSMSQI1 3I I1, I2, I0 SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I IEC 61850 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79

CBCM TCM (1) TCM (2) MCS 3I 60

3I I1, I2, I0

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement IEC 61850 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 IEC 60617 Io 3U Uo U1, U2, U0 P, E IEC-ANSI In 3U Vn U1, U2, U0 P, E

3.8.2.1

Default I/O connections


Table 33:
Binary input X110-BI1 X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1 X120-BI2 X120-BI3 X120-BI4

Default connections for binary inputs


Default usage MCB open Directional earth fault protection's basic angle control Circuit breaker low gas pressure alarm Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Lock-out reset Connector pins X110-1,2 X110-3,4 X110-5,6 X110-7,6 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2 X120-3,2 X120-4,2 X120-5,6

Table 34:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3

Default connections for binary outputs


Default usage Close circuit breaker Breaker failure backup trip to upstream breaker General start indication General operate indication Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Connector pins X100-6,7 X100-8,9 X100-10,11,(12) X100-13,14 X100-15-19 X100-20-24 X110-14,15 X110-17,18 X110-20,21

REF615 Application Manual

95

Section 3 REF615 standard configurations

1MRS756378 K

Table 35:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Non-directional overcurrent protection operated Directional earth-fault protection operated Double (cross country) earth fault or residual overvoltage protection operated Negative-sequence overcurrent or phase discontinuity protection operated Thermal overload protection operated Circuit-breaker failure protection backup protection operated Disturbance recorder triggered Circuit-breaker condition monitoring alarm Supervision alarm Arc fault detected Autoreclose in progress

3.8.2.2

Default disturbance recorder settings


Table 36:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io Uo U1 U2 U3 -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

96

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations Functional diagrams


The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.8.3

3.8.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections. Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks.

REF615 Application Manual

97

Section 3 REF615 standard configurations

1MRS756378 K

GUID-37D627C4-6097-4322-BACC-161CC6039EC5 V2 EN

Figure 46:

Overcurrent protection

All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication. The upstream blocking from the start of the overcurrent second high stage (PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.

98

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1

DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (1) 67N-1 (1)


I0 START OPERATE I0

I0>> 51N-2
START OPERATE

X110 3 4

U0 BLOCK

CCRDIF_FAIL

BLOCK

LED3 (NEF OPERATE)

BI 2 (BACTRL)

ENA_MULT RCA_CTL

ENA_MULT Calculated Io

INTERMITTENT EARTH-FAULT PROTECTION DEFLPDEF2

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

INTRPTEF1

I0 >

67NIEF
START OPERATE BLK_EF U0 BLOCK

OR DEFHPDEF1

LED2 (EF OPERATE)

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

OR ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

LED2 (WDE OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE

OR

LED2 (ADM OPERATE)

BLOCK RELEASE

WPWDE3

EFPADM3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE BLOCK RELEASE

GUID-1F3C1F26-6F11-4250-9476-82C47C3AC570 V3 EN

Figure 47:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE) or harmonic based earth-fault protection (HAEFPTOC). In addition, there is a dedicated protection stage (INTRPTEF) either for transient-based earth-fault protection or for cable intermittent earth-fault protection in compensated networks. A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for protection against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents.

REF615 Application Manual

99

Section 3 REF615 standard configurations

1MRS756378 K

The binary input 2 (X110:3-4) is intended for directional earth-fault protection blocks relay characteristic angle (RCA: 0/-90) or operation mode (I0Sin/ I0Cos) change. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earthfault protection operate indication.

GUID-3A78AEF7-8219-42C1-9BB9-FBAED53FF38F V1 EN

Figure 48:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 3.

100

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

PHASE DISCONTINUITY PROTECTION PDNSTOC1

I2 / I1 46PD
3I START OPERATE

CCRDIF_FAIL

BLOCK

LED4 (NPS/PD OPERATE)

THERMAL OVERLOAD PROTECTION T1PTTR1

3 > 49F
3I OPERATE ALARM BLK_OPR BLK_CLOSE ENA_MULT START

LED5 (OVERLOAD ALARM)

PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate EFPADM2-operate EFPADM3-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE2-operate WPWDE3-operate X120_BI2 (CB Closed)

BREAKER FAILURE PROTECTION OR CCBRBRF1 LED6 (CBFP OPERATE) +

3I>/Io -> BF 51BF/51NBF


3I Io START CB_FAULT BLOCK POSCLOSE TRRET TRBU CB_FAULT_AL

X100
PO2

8 9

CBFP trip to upstream breaker

GUID-8BD4614B-2C4D-475E-ADC3-A376E213BF3C V3 EN

Figure 49:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

REF615 Application Manual

101

Section 3 REF615 standard configurations

1MRS756378 K

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

OR

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON

X110 6 7

X120_BI3 (CB Open) BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected INTRPTEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate


A071338 V7 EN

SYNC

OR

Figure 50:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions.

102

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

REF615 Application Manual

103

Section 3 REF615 standard configurations


3.8.3.2

1MRS756378 K

Functional diagram for disturbance recorder and trip circuit supervision


DISTURBANCE RECORDER

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate OR PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21

OR

OR INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate OR DARREC-inpro

BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32 BI#33 BI#34 BI#35 BI#36

NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det DARREC-close-cb DARREC-unsuc-recl

OR

OR

OR

BI#37 BI#38 BI#39

OR

OR

OR

BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open) SEQRFUF_3PH SEQRFUF_U CCRDIF_FAIL


GUID-4BE45287-D708-41F3-851A-084A9AC3265E V3 EN

Figure 51:

Disturbance recorder

All start and operate signals from the protection stages are routed either to trigger the disturbance recorder or to be recorded by the disturbance recorder, depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected.

104

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-48DD2A49-CF29-4088-914B-7AE1629E18CA V2 EN

Figure 52:

Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as an open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9. Failures in current measuring circuits are detected by CCRDIF. When a failure is detected, blocking signal is activated in current protection functions that are measuring calculated sequence component currents, and unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.

REF615 Application Manual

105

Section 3 REF615 standard configurations


3.8.3.3 Functional diagrams for control and interlocking
MASTER TRIP #1
X100

1MRS756378 K

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate BI4 (Lock-out reset) DARREC1-open cb CBXCBR1-exe_op PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate CCBRBRF1-trret ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

+
TRPPTRC1
BLOCK TRIP

16

PO3
OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

Open CB / trip coil 1


17 15 18 19

TCS1

MASTER TRIP #2
X100 20 22

+
TRPPTRC2
BLOCK TRIP

PO4
21 23 24

Open CB / trip coil 2

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS2

GUID-4963C315-60C2-4C60-BE7F-B18D87A8D35E V3 EN

Figure 53:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

106

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-4DED2926-A92A-4F6A-BCAA-7D9CD24ACFC8 V3 EN

Figure 54:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 37: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)

Primary device position

REF615 Application Manual

107

Section 3 REF615 standard configurations

1MRS756378 K

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

108

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

COMMON ALARM / INDICATION 1 & 2


PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start EFPADM1-start EFPADM2-start EFPADM3-start INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start WPWDE1-start WPWDE2-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

X100
OR

+ SO1
TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+ SO2

13
Operate Indication

14

OR

X110

+
PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate

17
Over Current Operate Alarm

SO2
OR TPGAPC2
IN1 IN2 OUT1 OUT2

19 18

+ SO3

20
Earth Fault Operate Alarm

OR

22 21

GUID-572DA8CC-7A7D-4F9F-87C5-272A4283FB3E V3 EN

Figure 55:

Alarm indication

The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8.

REF615 Application Manual

109

Section 3 REF615 standard configurations

1MRS756378 K

The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22)

TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.

3.9
3.9.1

Standard configuration F
Applications
The standard configuration for directional overcurrent and directional earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage protection is mainly intended for comprehensive protection and control functionality of circuit breaker controlled asynchronous motors. With minor modifications this standard configuration can be applied also for contactor controlled motors. The configuration also includes additional options to select earthfault protection based on admittance, wattmetric or harmonic based principle. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.9.2

Functions
Table 38:
Function Protection Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage Table continues on next page PHIPTOC1 DPHLPDOC1 DPHLPDOC2 DPHHPDOC1 3I>>> (1) 3I> -> (1) 3I> -> (2) 3I>> -> 50P/51P (1) 67-1 (1) 67-1 (2) 67-2

Functions included in the standard configuration F


IEC 61850 IEC 60617 IEC-ANSI

110

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Harmonics based earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 Negative-sequence overvoltage protection, instance 1 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Table continues on next page IEC 61850 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 INTRPTEF1 HAEFPTOC1 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 PHPTUV1 PHPTUV2 PHPTUV3 PHPTOV1 PHPTOV2 PHPTOV3 PSPTUV1 NSPTOV1 T1PTTR1 CCBRBRF1 INRPHAR1 IEC 60617 Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF Io>HA Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) U1< (1) U2> (1) 3Ith>F 3I>/Io>BF 3I2f> IEC-ANSI 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF 51NHA 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 47U+ (1) 47O- (1) 49F 51BF/51NBF 68

REF615 Application Manual

111

Section 3 REF615 standard configurations


Function Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 3I I1, I2, I0 Io 3U Uo U1, U2, U0 P, E SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I IEC 61850 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79

CBCM TCM (1) TCM (2) MCS 3I 60

3I I1, I2, I0 In 3U Vn U1, U2, U0 P, E

112

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Default I/O connections
Table 39:
Binary input X110-BI1 X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1 X120-BI2 X120-BI3 X120-BI4

3.9.2.1

Default connections for binary inputs


Default usage MCB open Directional earth fault protection's basic angle control Circuit breaker low gas pressure indication Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Lock-out reset Connector pins X110-1,2 X110-3,4 X110-5,6 X110-7,6 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2 X120-3,2 X120-4,2 X120-5,6

Table 40:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4

Default connections for binary outputs


Default usage Close circuit breaker Breaker failure backup trip to upstream breaker General start indication General operate indication Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Voltage protection operate alarm Connector pins X100-6,7 X100-8,9 X100-10,11,(12) X100-13,14 X100-15-19 X100-20-24 X110-14,15 X110-17,18 X110-20,21 X110-23,24

Table 41:
LED 1 2 3 4 5 6 7 8

Default connections for LEDs


Default usage Overcurrent protection operated Earth-fault protection operated Voltage protection operated Negative-sequence overcurrent or phase discontinuity protection operated Thermal overload protection operated Circuit-breaker failure protection backup protection operated Disturbance recorder triggered Circuit-breaker condition monitoring alarm

Table continues on next page REF615 Application Manual 113

Section 3 REF615 standard configurations


LED 9 10 11 Default usage Supervision alarm Arc fault detected Autoreclose in progress

1MRS756378 K

3.9.2.2

Default disturbance recorder settings


Table 42:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io Uo U1 U2 U3 -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

3.9.3

Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents and 3U the three phase voltages. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open-delta connected voltage transformers.

114

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.9.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections. Four overcurrent stages are available for overcurrent and short-circuit protection. Three of them include directional functionality (DPHxPDOC). The non-directional instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2) are available for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the shown protection function blocks.

GUID-F0BE506C-0A96-4AA2-AC55-FFD9BCD23951 V2 EN

Figure 56:

Directional overcurrent protection

All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication.

REF615 Application Manual

115

Section 3 REF615 standard configurations

1MRS756378 K

The upstream blocking from the start of the directional overcurrent second low stage (DPHLPDOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.
DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1 INTERMITTENT EARTH-FAULT PROTECTION INTRPTEF1

I0> -> (1) 67N-1 (1)


I0 START OPERATE I0 U0 BLOCK

I0 >

X110 3 4
BI 2 (BACTRL)

U0 BLOCK ENA_MULT RCA_CTL

67NIEF
START OPERATE BLK_EF

DEFLPDEF2

DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

I0>> 51N-2
START OPERATE

CCRDIF_FAIL

BLOCK

ENA_MULT Calculated Io

DEFHPDEF1

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

ROV-operate

OR

LED2 (EF OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE BLOCK RELEASE

HARMONIC EARTH-FAULT PROTECTION (Optional) EFPADM3 HAEFPTOC1

WPWDE3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE I0 BLOCK RELEASE

I0>HA 51NHA
START I_REF_RES OPERATE BLOCK

GUID-F82FE8A6-6AA1-44D9-8FE2-8B2C51CEA7AA V3 EN

Figure 57:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE) or harmonic based earth-fault protection (HAEFPTOC). In addition, there is a dedicated protection stage (INTRPTEF) either for transient-based earth-fault protection or for cable intermittent earth-fault protection in compensated networks.

116

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for protection against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. The binary input 2 (X110:3-4) is intended for directional earth-fault protection blocks relay characteristic angle (RCA: 0/-90) or operation mode (I0Sin/ I0Cos) change. All operate signals are connected to the Master Trip as well as to the alarm LED 2.
PHASE DISCONTINUITY PROTECTION PDNSTOC1

I2 / I1 46PD
3I START OPERATE

CCRDIF_FAIL

BLOCK

LED4 (NPS/PD OPERATE)

THERMAL OVERLOAD PROTECTION T1PTTR1

3 > 49F
3I OPERATE ALARM BLK_OPR BLK_CLOSE ENA_MULT START

LED5 (OVERLOAD ALARM)

DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM2-operate EFPADM3-operate WPWDE2-operate WPWDE3-operate X120_BI2 (CB Closed)

BREAKER FAILURE PROTECTION OR CCBRBRF1 LED6 (CBFP OPERATE) +

3I>/Io -> BF 51BF/51NBF


3I Io START CB_FAULT BLOCK POSCLOSE TRRET TRBU CB_FAULT_AL

X100
PO2

8 9

CBFP trip to upstream breaker

GUID-5F0B30AD-0B3F-4B6D-BFAC-7209FA9DAACD V3 EN

Figure 58:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication, and LED 5 is used for the thermal overload protection alarm indication. The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection
REF615 Application Manual 117

Section 3 REF615 standard configurations

1MRS756378 K

function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

118

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

OR

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON

X110 6 7

X120_BI3 (CB Open) BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected INTRPTEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate


GUID-EC907A8E-9CF0-4150-A394-FFBAF30A8725 V3 EN

SYNC

OR

Figure 59:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions.

REF615 Application Manual

119

Section 3 REF615 standard configurations

1MRS756378 K

The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

120

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-BCEB1C2E-BC64-4E79-8329-A5D9FCD7AB2F V2 EN

Figure 60:

Overvoltage and undervoltage protection

Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.

REF615 Application Manual

121

Section 3 REF615 standard configurations

1MRS756378 K

GUID-A77D0608-E3F2-4D3D-8907-15034FC42D51 V2 EN

Figure 61:

Positive-sequence undervoltage and negative-sequence overvoltage protection

Positive-sequence undervoltage (PSPTUV) and negative-sequence overvoltage (NSPTOV) protection functions enable voltage-based unbalance protection. The operation signals of voltage-sequence functions are connected to alarm LED 3, which is a combined voltage protection alarm LED.

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 62:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 2.
122 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagram for disturbance recorder and trip circuit supervision

3.9.3.2

DISTURBANCE RECORDER

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate OR DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29

OR

OR

OR

DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det DARREC-close-cb DARREC-unsuc-recl

OR

OR

INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate

BI#30 BI#31 BI#32 BI#33 BI#34 BI#35 BI#36

OR

BI#37

OR

SEQRFUF_3PH SEQRFUF_U CCRDIF_FAIL BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open) ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC-inpro

BI#38 BI#39 BI#40 BI#41 BI#42 BI#43 BI#44 BI#45 BI#46 BI#47 BI#48 BI#49

OR

OR

OR

OR

GUID-A2EBA677-AEF4-451B-807B-20F50D5894C7 V3 EN

Figure 63:

Disturbance recorder

All start and operate signals from the protection stages are routed either to trigger the disturbance recorder or to be recorded by the disturbance recorder, depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected.

REF615 Application Manual

123

Section 3 REF615 standard configurations

1MRS756378 K

GUID-F06A3FEF-2C72-49A4-928F-D301335EC2C6 V3 EN

Figure 64:

Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as an open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9. Failures in current measuring circuits are detected by CCRDIF. When a failure is detected, blocking signal is activated in current protection functions that are measuring calculated sequence component currents, and unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.

124

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for control and interlocking
DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate BI 4 (Lock-out reset) DARREC-open cb CBXCBR1-exe_op DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate CCBRBRF1-trret ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate MASTER TRIP #2 MASTER TRIP #1

3.9.3.3

X100

+
TRPPTRC1
BLOCK TRIP

16 Open CB / trip coil 1 17 15 18 19

PO3 OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS1

X100 20 22 Open CB / trip coil 2 21 TCS2 23 24

+
TRPPTRC2
BLOCK TRIP

PO4

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

GUID-300441A3-AE3C-4BBF-8C5A-B5CA8BA4EF53 V3 EN

Figure 65:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19).

REF615 Application Manual

125

Section 3 REF615 standard configurations

1MRS756378 K

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

GUID-DE498CFB-A256-4275-9A1F-5EF3B09046F4 V3 EN

Figure 66:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.

126

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

Table 43:

Device positions indicated by binary inputs 5 and 6


Input to be energized Input 5 (X110:8-9) Input 6 (X110:10-9) x x x x

Primary device position Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

REF615 Application Manual

127

Section 3 REF615 standard configurations

1MRS756378 K

DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start EFPADM1-start EFPADM2-start EFPADM3-start WPWDE1-start WPWDE2-start WPWDE3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate

COMMON ALARM / INDICATION 1 & 2

OR

X100

+
SO1 TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+
SO2

13
Operate Indication

14

OR

X110

+
OR TPGAPC2
IN1 IN2 OUT1 OUT2

17
Over Current Operate Alarm

SO2

19 18

+
SO3 OR

20
Earth Fault Operate Alarm

22 21

+
SO4

23
Voltage Protection Operate Alarm

TPGAPC3 OR
IN1 IN2 OUT1 OUT2

24

GUID-79EB68EE-F160-402E-A841-BC6D074E7294 V3 EN

Figure 67:

Alarm indication

128

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22)

TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four generic timers (TPGAPC1..4) are available in the IED. The remaining one not described in the functional diagram is available in PCM600 for connection where applicable.

3.10
3.10.1

Standard configuration G
Applications
The standard configuration for non-directional earth-fault, voltage and frequency protection is mainly intended for cable and overhead-line feeder applications in direct or resistance earthed distribution networks. The configuration also includes additional options to select earth-fault protection based on admittance or wattmetric principle The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.10.2

Functions
Table 44:
Function Protection Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Table continues on next page PHIPTOC1 DPHLPDOC1 DPHLPDOC2 3I>>> (1) 3I> -> (1) 3I> -> (2) 50P/51P (1) 67-1 (1) 67-1 (2)

Functions included in the standard configuration G


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

129

Section 3 REF615 standard configurations


Function Three-phase directional overcurrent protection, high stage Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 Negative-sequence overvoltage protection, instance 1 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Table continues on next page IEC 61850 DPHHPDOC1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 PHPTUV1 PHPTUV2 PHPTUV3 PHPTOV1 PHPTOV2 PHPTOV3 PSPTUV1 NSPTOV1 T1PTTR1 CCBRBRF1 INRPHAR1 IEC 60617 3I>> -> Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) U1< (1) U2> (1) 3Ith>F 3I>/Io>BF 3I2f>

1MRS756378 K

IEC-ANSI 67-2 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 47U+ (1) 47O- (1) 49F 51BF/51NBF 68

130

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Sequence voltage measurement Three-phase power and energy measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 VMMXU1 VSMSQI1 PEMMXU1 3I I1, I2, I0 Io 3U U1, U2, U0 P, E 3I I1, I2, I0 In 3U U1, U2, U0 P, E SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF CBCM TCM (1) TCM (2) MCS 3I 60 CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79 IEC 61850 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3) IEC-ANSI 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

3.10.2.1

Default I/O connections


Table 45:
Binary input X110-BI1 X110-BI2 X110-BI3

Default connections for binary inputs


Default usage Circuit breaker closed indication Circuit breaker open indication Circuit breaker low gas pressure indication Connector pins X110-1,2 X110-3,4 X110-5,6

Table continues on next page REF615 Application Manual 131

Section 3 REF615 standard configurations


Binary input X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 Default usage Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication

1MRS756378 K

Connector pins X110-7,6 X110-8,9 X110-10,9 X110-11,12 X110-13,12

Table 46:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4

Default connections for binary outputs


Default usage Close circuit breaker Breaker failure backup trip to upstream breaker General start indication General operate indication Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Voltage protection operate alarm Connector pins X100-6,7 X100-8,9 X100-10,11,(12) X100-13,14 X100-15-19 X100-20-24 X110-14,15,16 X110-17,18,19 X110-20,21,22 X110-23,24

Table 47:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Overcurrent protection operated Earth-fault protection operated Voltage protection operated Negative-sequence overcurrent or phase discontinuity protection operated Thermal overload protection operated Circuit-breaker failure protection backup protection operated Disturbance recorder triggered Circuit-breaker condition monitoring alarm Supervision alarm Arc fault detected Autoreclose in progress

132

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Default disturbance recorder settings
Table 48:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

3.10.2.2

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io U1 U2 U3 -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

3.10.2.3

Sensor settings Rogowski sensor setting example


In this example, a 80 A/0.150 V at 50 Hz sensor is used and the application has a 150 A nominal current (In). As the Rogowski sensor is linear and does not saturate, the 80 A/0.150 V at 50 Hz sensor also works as a 150 A/0.28125 V at 50 Hz sensor. When defining another primary value for the sensor, also the nominal voltage has to be redefined to maintain the same transformation ratio. However, the setting in the IED (Rated Secondary Value) is not in V but in mV/Hz, which makes the same setting value valid for both 50 and 60 Hz nominal frequency. Rated Secondary Value is calculated with the formula:

REF615 Application Manual

133

Section 3 REF615 standard configurations

1MRS756378 K

In Kr I pr fn
In Ipr fn Kr RSV

= RSV

GUID-6A480073-5C35-4319-8B38-402608D4C098 V1 EN

the application nominal current the sensor rated primary current network nominal frequency the sensor rated voltage (in mV) at the rated current the Rated Secondary Value in mV/Hz

In this example, this is then:


150 A 150mV mV 80 A = 5.625 50Hz Hz
GUID-13DE42A0-29C0-4FE0-B00B-1215B37E3B7B V1 EN

With this information, the IED Rogowski sensor settings can be set.
Table 49:
Primary Current Rated Secondary Value Nominal Current

Example setting values


150 A 5.625 mV/Hz

150 A

Unless otherwise specified, the Nominal Current setting should always be the same as the Primary Current setting.

3.10.3

Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings.

134

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents and 3U the three phase voltages. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open-delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.10.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections. Four overcurrent stages are available for overcurrent and short-circuit protection. Three of them include directional functionality (DPHxPDOC) and one nondirectional instantaneous stage (PHIPTOC1). The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the shown protection function blocks.

GUID-3A5BC077-38FE-436B-B5FC-B7259E991B3A V1 EN

Figure 68:

Directional overcurrent protection

All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent protection.

REF615 Application Manual

135

Section 3 REF615 standard configurations

1MRS756378 K

The upstream blocking from the start of the directional overcurrent second low stage (DPHLPDOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.
DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1 DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (1) 67N-1 (1)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

I0>> 51N-2
START OPERATE

CCRDIF_FAIL

BLOCK

ENA_MULT Calculated Io

LED2 (EFHPTOC1 OPERATE)

DEFLPDEF2

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

OR

LED2 (EF OPERATE)

DEFHPDEF1

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

OR ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

LED2 (WDE OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE

OR

LED2 (ADM OPERATE)

BLOCK RELEASE

WPWDE3

EFPADM3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE BLOCK RELEASE

GUID-1B89C44D-E560-4A69-B3FF-F723E6F32AD3 V2 EN

Figure 69:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only, or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE).

136

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for protection against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. All operate signals are connected to the Master Trip and also to the alarm LEDs. LED 2 is used for directional earth-fault.

GUID-1FA9FD40-94F8-449B-9459-B8636F28F8DB V1 EN

Figure 70:

Thermal overload protection

The thermal overload protection (T1PTTR1) provides indication on overload situations. LED 5 is used for the thermal overload protection alarm indication.

GUID-DF067AB4-DCBA-44CF-A95A-44B2248382BC V1 EN

Figure 71:

Negative sequence and phase discontinuity protection

Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The operate signal of the phase discontinuity
REF615 Application Manual 137

Section 3 REF615 standard configurations

1MRS756378 K

protection is connected to the Master Trip and also to an alarm LED. LED 4 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication.
BREAKER FAILURE PROTECTION CCBRBRF1 LED6 (CBFP OPERATE) +

DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM2-operate EFPADM3-operate WPWDE2-operate WPWDE3-operate X110_BI1 (CB Closed)

3I>/Io -> BF 51BF/51NBF


3I Io TRRET TRBU CB_FAULT_AL

X100
PO2

OR

START CB_FAULT BLOCK

POSCLOSE

8 9

CBFP trip to upstream breaker

GUID-8293B89D-5E82-4F3D-A04A-A3695184AC3F V2 EN

Figure 72:

Circuit breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.

138

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

GUID-8F763D1C-AFD0-4F5C-A410-54A286B8B5F9 V2 EN

Figure 73:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.

REF615 Application Manual

139

Section 3 REF615 standard configurations

1MRS756378 K

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate DPHHPDOC1-operate DPHLPDOC2-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

OR

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC

X110 6 7

X110_BI2 (CB Open) BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

OR

X110 4 5
BI3 (CB Gas Pressure Alarm)

GUID-58EB259F-66F3-47FB-A8EC-86827E49E4F3 V2 EN

Figure 74:

Autoreclosing

The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

140

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-9DBFA490-E41B-4E4B-B519-9FCA442E3D74 V1 EN

Figure 75:

Overvoltage and undervoltage protection

Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.

GUID-C956665C-599A-4EF5-9821-EAD02FF4EF0F V1 EN

Figure 76:

Positive-sequence undervoltage and negative-sequence overvoltage protection

REF615 Application Manual

141

Section 3 REF615 standard configurations

1MRS756378 K

Positive-sequence undervoltage (PSPTUV) and negative-sequence overvoltage (NSPTOV) protection functions enable voltage-based unbalance protection. The operation signals of voltage-sequence functions are connected to alarm LED 3, which is a combined voltage protection alarm LED.

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 77:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 2.

142

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagram for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER

3.10.3.2

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate OR DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27

OR

OR

OR

DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det

BI#28

OR

OR

EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate

BI#29 BI#30 BI#31 BI#32 BI#33 BI#34 BI#35

OR

SEQRFUF_3PH SEQRFUF_U CCRDIF_FAIL BI 2 (CB Closed) BI 3 (CB Open) ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC-inpro DARREC-close-cb DARREC-unsuc-recl

BI#36 BI#37 BI#38 BI#39 BI#40 BI#41 BI#42 BI#43 BI#44 BI#45 BI#46 BI#47

OR

OR

OR

OR

GUID-E37B8348-2881-46DF-843F-3A7AB81FE1A3 V2 EN

Figure 78:

Disturbance recorder

All start and operate signals from the protection stages are routed either to trigger the disturbance recorder or to be recorded by the disturbance recorder, depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the two binary inputs from X110 are also connected.

REF615 Application Manual

143

Section 3 REF615 standard configurations

1MRS756378 K

GUID-CE169E2B-B258-4E17-A631-0796214D3627 V1 EN

Figure 79:

Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as an open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9. Failures in current measuring circuits are detected by CCRDIF. When a failure is detected, blocking signal is activated in current protection functions that are measuring calculated sequence component currents, and unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.

144

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for control and interlocking
DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate DARREC-open cb CBXCBR1-exe_op DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate CCBRBRF1-trret EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate MASTER TRIP #2 MASTER TRIP #1

3.10.3.3

X100

+
TRPPTRC1
BLOCK TRIP

16 Open CB / trip coil 1 17 15 18 19

PO3 OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS1

X100 20 22 Open CB / trip coil 2 21 TCS2 23 24

+
TRPPTRC2
BLOCK TRIP

PO4

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

GUID-C18D52E2-C85E-45F4-93E0-5081024F3B13 V2 EN

Figure 80:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary

REF615 Application Manual

145

Section 3 REF615 standard configurations

1MRS756378 K

input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

GUID-E4885797-0852-4754-80DB-E094BE033192 V2 EN

Figure 81:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 50: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)

Primary device position

146

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

REF615 Application Manual

147

Section 3 REF615 standard configurations

1MRS756378 K

DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start EFHPTOC1-start PDNSPTOC1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start EFPADM1-start EFPADM2-start EFPADM3-start WPWDE1-start WPWDE2-start WPWDE3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFHPTOC1-operate PDNSPTOC1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFHPTOC1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate

COMMON ALARM / INDICATION 1 & 2

OR

X100

+
SO1 TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+
SO2

13
Operate Indication

14

OR

X110

+
OR TPGAPC2
IN1 IN2 OUT1 OUT2

17
Over Current Operate Alarm

SO2

19 18

+
SO3 OR

20
Earth Fault Operate Alarm

22 21

+
SO4 TPGAPC3 OR
IN1 IN2 OUT1 OUT2

23
Voltage Protection Operate Alarm

24

GUID-7750871D-CD1D-4675-9584-9ACE54A56A20 V2 EN

Figure 82:

Alarm indication

148

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22) Operation (trip) of any stage of the voltage protection function SO4 (X110:23-24)

TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four generic timers (TPGAPC1..4) are available in the IED. The remaining one not described in the functional diagram is available in PCM600 for connection where applicable.

3.11
3.11.1

Standard configuration H
Applications
The standard configuration for non-directional overcurrent and non-directional earthfault, phase-voltage and frequency protection and measurement functions is mainly intended for cable and overhead-line feeder applications in directly or resistanceearthed distribution networks. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.11.2

Functions
Table 51:
Function Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Table continues on next page PHLPTOC1 PHHPTOC1 3I> (1) 3I>> (1) 51P-1 (1) 51P-2 (1)

Functions included in the standard configuration H


IEC 61850 IEC 60617 IEC-ANSI

REF615 Application Manual

149

Section 3 REF615 standard configurations


Function Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Frequency protection, instance 1 Frequency protection, instance 2 Frequency protection, instance 3 Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector control, instance 1 Table continues on next page CBXCBR1 DCXSWI1 I <-> O CB I <-> O DCC (1) IEC 61850 PHHPTOC2 PHIPTOC1 EFLPTOC1 EFLPTOC2 EFHPTOC1 EFIPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 PHPTUV1 PHPTUV2 PHPTUV3 PHPTOV1 PHPTOV2 PHPTOV3 FRPFRQ1 FRPFRQ2 FRPFRQ3 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 3I>> (2) 3I>>> (1) Io> (1) Io> (2) Io>> (1) Io>>> I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) f>/f<,df/dt (1) f>/f<,df/dt (2) f>/f<,df/dt (3) 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 51P-2 (2) 50P/51P (1) 51N-1 (1) 51N-1 (2) 51N-2 (1) 50N/51N 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 81 (1) 81 (2) 81 (3) 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

I <-> O CB I <-> O DCC (1)

150

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Synchronism and energizing check Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement Frequency measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 FMMXU1 3I I1, I2, I0 Io 3U Uo U1, U2, U0 P, E f 3I I1, I2, I0 In 3U Vn U1, U2, U0 P, E f SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF CBCM TCM (1) TCM (2) MCS 3I 60 IEC 61850 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 SECRSYN1 IEC 60617 I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I SYNC IEC-ANSI I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79 25

3.11.2.1

Default I/O connections


Table 52:
Binary input X110-BI1 X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1

Default connections for binary inputs


Default usage Busbar VT secondary MCB open Line VT secondary MCB open Circuit breaker low gas pressure indication Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Connector pins X110-1,2 X110-3,4 X110-5,6 X110-7,6 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2

Table continues on next page REF615 Application Manual 151

Section 3 REF615 standard configurations


Binary input X120-BI2 X120-BI3 X120-BI4 Default usage Circuit breaker closed indication Circuit breaker open indication Lock-out reset

1MRS756378 K

Connector pins X120-3,2 X120-4,2 X120-5,6

Table 53:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4

Default connections for binary outputs


Default usage Close circuit breaker Breaker failure backup trip to upstream breaker General start indication General operate indication Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Voltage protection operate alarm Connector pins X100-6,7 X100-8,9 X100-10,11,(12) X100-13,14 X100-15-19 X100-20-24 X110-14,15,16 X110-17,18,19 X110-20,21,22 X110-23,24

Table 54:
LED 1 2 3 4 5 6 8 9 10 11

Default connections for LEDs


Default usage Overcurrent protection operated Earth-fault protection operated Combined protection operated indication Synchronism or energizing check OK Frequency protection Circuit-breaker failure protection backup protection operated Circuit-breaker condition monitoring alarm Supervision alarm Arc fault detected Autoreclose in progress

3.11.2.2

Default disturbance recorder settings


Table 55:
Channel 1 2 3

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3

Table continues on next page

152

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Channel 4 5 6 7 8 9 10 11 12 Selection and text Io Uo U1 U2 U3 U1B -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

3.11.3

Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents and 3U the three phase voltages. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open-delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.11.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail and picture the factory set default connections.

REF615 Application Manual

153

Section 3 REF615 standard configurations

1MRS756378 K

GUID-2AF21F47-B720-41A8-98CA-FEC94F5244CC V1 EN

Figure 83:

Non-directional overcurrent protection

Four overcurrent stages are offered for overcurrent and short-circuit protection. The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the described protection function blocks. All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1 is used for overcurrent and LED 4 for negative-sequence overcurrent protection operate indication. LED 4 is also used for phase discontinuity protection operate indication. The upstream blocking from the start of the overcurrent second high stage (PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.

154

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-816ECD29-2D22-4C2A-9BF1-625A48657362 V1 EN

Figure 84:

Non-directional earth-fault protection

Four stages are offered for non-directional earth-fault protection. One stage is dedicated to sensitive earth-fault protection. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault.

REF615 Application Manual

155

Section 3 REF615 standard configurations

1MRS756378 K

GUID-6EDB21C6-F84E-4FF6-942B-0A17D43F952F V1 EN

Figure 85:

Negative sequence and phase discontinuity protection

Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2) are offered for phase unbalance protection. The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED. LED 3 is used for the phase discontinuity protection operate indication, the same as for negative sequence overcurrent protection operate indication.

GUID-20D34999-565D-4376-8537-A27A9D57D9FE V1 EN

Figure 86:

Circuit breaker failure protection

156

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up (TRBU) operate indication.

ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

GUID-8F763D1C-AFD0-4F5C-A410-54A286B8B5F9 V2 EN

Figure 87:

Arc protection

Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional functions. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.

REF615 Application Manual

157

Section 3 REF615 standard configurations

1MRS756378 K

AUTORECLOSING (Optional) DARREC1

0 -> 1 79
PHIPTOC1-operate PHHPTOC2-operate PHHPTOC1-operate EFLPTOC2-operate EFHPTOC1-operate X120_BI3 (CB Open)
INIT_1 INIT_2 INIT_3 INIT_4 INIT_5 INIT_6 DEL_INIT_3 DEL_INIT_4 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

X110 6 7

BI4 (CB Spring Charged)

BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate

INC_SHOTP INHIBIT_RECL RECL_ON SYNC

OR

X110 4 5
BI3 (CB Gas Pressure Alarm)

SECRSYN-sync_ok

GUID-B25B20B6-AED0-4400-9146-96E0755DCD8D V2 EN

Figure 88:

Autoreclosing

The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the operation of selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

158

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-09BE5AE5-818D-4131-B963-241D17E0484C V1 EN

Figure 89:

Overvoltage and undervoltage protection

Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.

REF615 Application Manual

159

Section 3 REF615 standard configurations

1MRS756378 K

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 90:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to alarm LED 2.

GUID-189240C6-E7AE-4314-87C2-3EC3AC84E6CC V1 EN

Figure 91:

Frequency protection

The selectable underfrequency or overfrequency protection (FRPFRQ) prevents damage to network components under unwanted frequency conditions. The function contains a selectable rate of change of the frequency (gradient) protection to detect an increase or decrease in the fast power system frequency at

160

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

an early stage. This can be used as an early indication of a disturbance in the system. The operation signal is connected to alarm LED 5.

3.11.3.2

Functional diagram for disturbance recorder and trip circuit supervision


DISTURBANCE RECORDER

RDRE1
PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate EFLPTOC1-operate EFLPTOC2-operate EFHPTOC1-operate EFIPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det OR PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start EFLPTOC1-start EFLPTOC2-start EFHPTOC2-start EFIPTOC1-start PDNSPTOC1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start FRPFRQ1-start FRPFRQ2-start FRPFRQ3-start CCBRBRF1-trret CCBRBRF1-trbu
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 TRIGGERED

LED7 (DR TRIGGERING)

OR

OR

OR

OR

OR EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h OR

BI#29 BI#30 BI#31 BI#32 BI#33 BI#34 BI#35

OR

SEQRFUF_3PH SEQRFUF_U CCRDIF_FAIL BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open) SECRSYN-inpro SECRSYN-sync_ok SECRSYN-cl_fail_al SECRSYN-cmd_fail_al ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC-inpro DARREC-close-cb DARREC-unsuc-recl

BI#36 BI#37 BI#38 BI#39 BI#40 BI#41 BI#42 BI#43 BI#44 BI#45 BI#46 BI#47 BI#48 BI#49 BI#50 BI#51 BI#52

GUID-B439B2BF-732E-4B6B-987B-B4C587E3A38C V2 EN

Figure 92:

Disturbance recorder

All start and operate signals from the protection stages are routed either to trigger the disturbance recorder or to be recorded by the disturbance recorder, depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals, the synchrocheck signals and the three binary inputs from X120 are also connected.

REF615 Application Manual

161

Section 3 REF615 standard configurations

1MRS756378 K

GUID-7FB70959-1A66-44B0-BA48-98A2DA5EA90F V1 EN

Figure 93:

Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as an open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9. Failures in current measuring circuits are detected by CCRDIF. When a failure is detected, blocking signal is activated in current protection functions that are measuring calculated sequence component currents, and unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.

162

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for control and interlocking

3.11.3.3

GUID-7BCB289E-DD3D-4DC3-B95A-C836E336A7DC V1 EN

Figure 94:

Synchrocheck

The main purpose of the synchronism and energizing check (SECRSYN) is to provide control over the closing of the circuit breakers in power networks to prevent the closing if the conditions for synchronism are not detected. The energizing function allows closing, for example, when one side of the breaker is dead. SECRSYN measures the bus and line voltages and compares them to set conditions. When all the measured quantities are within set limits, the output SYNC_OK is activated for allowing closing or closing the circuit breaker. The SYNC_OK output signal of SECRSYN is connected to ENA_CLOSE input of CBXCBR through control logic.

REF615 Application Manual

163

Section 3 REF615 standard configurations

1MRS756378 K

GUID-22CD6BDE-5E33-4637-BB4E-D6EA73D782F4 V1 EN

Figure 95:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

164

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-F33E9B27-93E1-4AE0-9839-A27D76B9A724 V2 EN

Figure 96:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 56: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)

Primary device position

REF615 Application Manual

165

Section 3 REF615 standard configurations

1MRS756378 K

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

166

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start EFLPTOC1-start EFLPTOC2-start EFHPTOC1-start EFIPTOC1-start PDNSPTOC1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start FRPFRQ1-start FRPFRQ2-start FRPFRQ3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate EFLPTOC1-operate EFLPTOC2-operate EFHPTOC1-operate EFIPTOC1-operate PDNSPTOC1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate

COMMON ALARM / INDICATION 1 & 2

OR

X100

+
SO1 TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+
SO2

13
Operate Indication

14

OR

X110

PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate EFLPTOC1-operate EFLPTOC2-operate EFHPTOC1-operate EFIPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate

+
OR TPGAPC2
IN1 IN2 OUT1 OUT2

17
Over Current Operate Alarm

SO2

19 18

OR SO3

20
Earth Fault Operate Alarm

22 21

PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate

+
TPGAPC3 OR
IN1 IN2 OUT1 OUT2

23
Voltage Protection Operate Alarm

SO4

24

GUID-A4229C25-A92A-46A4-AAFB-1E39530E1E36 V2 EN

Figure 97:

Alarm indication

The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured
REF615 Application Manual 167

Section 3 REF615 standard configurations

1MRS756378 K

current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22) Operation (trip) of any stage of the voltage or frequency protection function SO4 (X110:23-24)

TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four generic timers (TPGAPC1..4) are available in the IED. The remaining one not described in the functional diagram is available in PCM600 for connection where applicable.

3.12
3.12.1

Standard configuration J
Applications
The standard configuration for directional overcurrent and directional earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage protection, and frequency protection and measurement functions is mainly intended for cable and overhead-line feeder applications in isolated or resonant-earthed distribution networks. The configuration also includes additional options to select earth-fault protection based on admittance, wattmetric or harmonic based principle. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

3.12.2

Functions
Table 57:
Function Protection Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Table continues on next page PHIPTOC1 DPHLPDOC1 3I>>> (1) 3I> -> (1) 50P/51P (1) 67-1 (1)

Functions included in the standard configuration J


IEC 61850 IEC 60617 IEC-ANSI

168

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Wattmetric based earth-fault protection, instance 1 Wattmetric based earth-fault protection, instance 2 Wattmetric based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Harmonics based earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 Negative-sequence overvoltage protection, instance 1 Table continues on next page IEC 61850 DPHLPDOC2 DPHHPDOC1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 EFPADM1 EFPADM2 EFPADM3 WPWDE1 WPWDE2 WPWDE3 INTRPTEF1 HAEFPTOC1 EFHPTOC1 NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 PHPTUV1 PHPTUV2 PHPTUV3 PHPTOV1 PHPTOV2 PHPTOV3 PSPTUV1 NSPTOV1 IEC 60617 3I> -> (2) 3I>> -> Io> -> (1) Io> -> (2) Io>> -> Yo> -> (1) Yo> -> (2) Yo> -> (3) Po> -> (1) Po> -> (2) Po> -> (3) Io> -> IEF Io>HA Io>> (1) I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) U1< (1) U2> (1) IEC-ANSI 67-1 (2) 67-2 67N-1 (1) 67N-1 (2) 67N-2 21YN (1) 21YN (2) 21YN (3) 32N (1) 32N (2) 32N (3) 67NIEF 51NHA 51N-2 (1) 46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 47U+ (1) 47O- (1)

REF615 Application Manual

169

Section 3 REF615 standard configurations


Function Frequency protection, instance 1 Frequency protection, instance 2 Frequency protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Power quality Current total demand distortion Voltage total harmonic distortion Voltage variation Control Circuit-breaker control Disconnector control, instance 1 Disconnector control, instance 2 Earthing switch control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication, instance 1 Earthing switch indication, instance 2 Auto-reclosing Synchronism and energizing check Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Table continues on next page 170 RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 3I I1, I2, I0 Io SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS (1) TCS (2) MCS 3I FUSEF CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 SECRSYN1 I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) O -> I SYNC CMHAI1 VMHAI1 PHQVVR1 PQM3I PQM3U PQMU IEC 61850 FRPFRQ1 FRPFRQ2 FRPFRQ3 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 f>/f<,df/dt (1) f>/f<,df/dt (2) f>/f<,df/dt (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3)

1MRS756378 K

IEC-ANSI 81 (1) 81 (2) 81 (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)

PQM3I PQM3V PQMV

I <-> O CB I <-> O DCC (1) I <-> O DCC (2) I <-> O ESC I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES (1) I <-> O ES (2) 79 25

CBCM TCM (1) TCM (2) MCS 3I 60

3I I1, I2, I0 In

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Function Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement Frequency measurement IEC 61850 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 FMMXU1 IEC 60617 3U Uo U1, U2, U0 P, E f IEC-ANSI 3U Vn U1, U2, U0 P, E f

3.12.2.1

Default I/O connections


Table 58:
Binary input X110-BI1 X110-BI2 X110-BI3 X110-BI4 X110-BI5 X110-BI6 X110-BI7 X110-BI8 X120-BI1 X120-BI2 X120-BI3 X120-BI4

Default connections for binary inputs


Default usage Busbar VT secondary MCB open Line VT secondary MCB open Circuit breaker low gas pressure indication Circuit breaker spring charged indication Circuit breaker truck in (service position) indication Circuit breaker truck out (test position) indication Earthing switch closed indication Earthing switch open indication Blocking of overcurrent instantaneous stage Circuit breaker closed indication Circuit breaker open indication Lock-out reset Connector pins X110-1,2 X110-3,4 X110-5,6 X110-7,6 X110-8,9 X110-10,9 X110-11,12 X110-13,12 X120-1,2 X120-3,2 X120-4,2 X120-5,6

Table 59:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4

Default connections for binary outputs


Default usage Close circuit breaker Breaker failure backup trip to upstream breaker General start indication General operate indication Open circuit breaker/trip coil 1 Open circuit breaker/trip coil 2 Upstream overcurrent blocking Overcurrent operate alarm Earth fault operate alarm Voltage and frequency protection operate alarm Connector pins X100-6,7 X100-8,9 X100-10,11,(12) X100-13,14 X100-15-19 X100-20-24 X110-14,15 X110-17,18 X110-20,21 X110-23,24

REF615 Application Manual

171

Section 3 REF615 standard configurations

1MRS756378 K

Table 60:
LED 1 2 3 4 5 6 7 8 9 10 11

Default connections for LEDs


Default usage Overcurrent protection operated Earth-fault protection operated Combined protection operated indication Synchronism or energizing check OK Thermal overload protection operated Circuit-breaker failure protection backup protection operated Disturbance recorder triggered CB condition monitoring Supervision alarm Arc fault detected Autoreclose in progress

3.12.2.2

Default disturbance recorder settings


Table 61:
Channel 1 2 3 4 5 6 7 8 9 10 11 12

Default analog channel selection and text settings


Selection and text IL1 IL2 IL3 Io Uo U1 U2 U3 U1B -

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

172

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations Functional diagrams


The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents and 3U the three phase voltages. The signal marked with Io represents the measured residual current via a core balance current transformer. The signal marked with Uo represents the measured residual voltage via open-delta connected voltage transformers. The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current originating from the measured phase currents.

3.12.3

3.12.3.1

Functional diagrams for protection


The functional diagrams describe the IEDs protection functionality in detail, and the factory-set default connections. Four overcurrent stages are available for overcurrent and short-circuit protection. Three of them include directional functionality (DPHxPDOC). The non-directional instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1 (X120:1-2). Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2) are available for phase unbalance protection. The inrush detection blocks (INRPHAR1) output BLK2H enables either blocking the function or multiplying the active settings for any of the shown protection function blocks.

REF615 Application Manual

173

Section 3 REF615 standard configurations

1MRS756378 K

GUID-F0BE506C-0A96-4AA2-AC55-FFD9BCD23951 V2 EN

Figure 98:

Directional overcurrent protection and inrush indication

All operate signals are connected to the Master Trip and to the alarm LEDs. The LED 1 is used for overcurrent and the LED 3 for negative-sequence overcurrent protection operate indication. The LED 3 is also used for phase discontinuity protection operate indication and for voltage protection indication. The upstream blocking from the start of the directional overcurrent second low stage (DPHLPDOC2) is connected to the output SO1 (X110:14-16). This output is used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay.

174

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

DIRECTIONAL EARTH-FAULT PROTECTION DEFLPDEF1

INTERMITTENT EARTH-FAULT PROTECTION INTRPTEF1

I0> -> (1) 67N-1 (1)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0 U0 BLOCK

I0 >

67NIEF
START OPERATE BLK_EF

DEFLPDEF2

DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION EFHPTOC1

I0> -> (2) 67N-1 (2)


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE I0

I0>> 51N-2
START OPERATE

CCRDIF_FAIL

BLOCK

ENA_MULT Calculated Io

DEFHPDEF1

I0>> -> 67N-1


I0 U0 BLOCK ENA_MULT RCA_CTL START OPERATE

ROV-operate

OR

LED2 (EF OPERATE)

WATTMETRIC EARTH-FAULT PROTECTION (Optional) WPWDE1

ADMITTANCE EARTH-FAULT PROTECTION (Optional) EFPADM1

P0> -> (1) 32N (1)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (1) 21YN (1)


START OPERATE BLOCK RELEASE

WPWDE2

EFPADM2

P0> -> (2) 32N (2)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (2) 21YN (2)


START OPERATE BLOCK RELEASE

HARMONIC EARTH-FAULT PROTECTION (Optional) EFPADM3 HAEFPTOC1

WPWDE3

P0> -> (3) 32N (3)


I0 U0 BLOCK RCA_CTL START OPERATE I0 U0

Y0> -> (3) 21YN (3)


START OPERATE I0 BLOCK RELEASE

I0>HA 51NHA
START I_REF_RES OPERATE BLOCK

GUID-E23D63E4-3409-425F-820C-E875F5A1EE2C V1 EN

Figure 99:

Directional earth-fault protection

Three stages are offered for directional earth-fault protection. According to the order code, the directional earth-fault protection method can be based on conventional directional earth-fault (DEFxPDEF) only or alternatively together with admittance criteria (EFPADM) or wattmetric earth-fault protection (WPWDE) or harmonic based earth-fault protection (HAEFPTOC). In addition, there is a dedicated protection stage (INTRPTEF) either for transient-based earth-fault protection or for cable intermittent earth-fault protection in compensated networks. A dedicated non-directional earth-fault protection block (EFHPTOC) protects against double earth-fault situations in isolated or compensated networks. This

REF615 Application Manual

175

Section 3 REF615 standard configurations

1MRS756378 K

protection function uses the calculated residual current originating from the phase currents. All operate signals are connected to the Master Trip and also to the alarm LED 2.
PHASE DISCONTINUITY PROTECTION PDNSTOC1

I2 / I1 46PD
3I START OPERATE

CCRDIF_FAIL

BLOCK

LED4 (NPS/PD OPERATE)

THERMAL OVERLOAD PROTECTION T1PTTR1

3 > 49F
3I OPERATE ALARM BLK_OPR BLK_CLOSE ENA_MULT START

LED5 (OVERLOAD ALARM)

DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF2-operate DEFHPDEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM2-operate EFPADM3-operate WPWDE2-operate WPWDE3-operate X120_BI2 (CB Closed)

BREAKER FAILURE PROTECTION OR CCBRBRF1 LED6 (CBFP OPERATE) +

3I>/Io -> BF 51BF/51NBF


3I Io START CB_FAULT BLOCK POSCLOSE TRRET TRBU CB_FAULT_AL

X100
PO2

8 9

CBFP trip to upstream breaker

GUID-5F0B30AD-0B3F-4B6D-BFAC-7209FA9DAACD V3 EN

Figure 100:

Phase discontinuity, thermal overload and circuit breaker failure protection

The phase discontinuity protection (PDNSPTOC1) protects for interruptions in the normal three-phase load supply, for example, in downed conductor situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED and the disturbance recorder. The thermal overload protection (T1PTTR1) provides indication on overload situations. The operate signal of the phase discontinuity protection is connected to the Master Trip and also to an alarm LED. The LED 3 is used for the phase discontinuity protection operate indication, the same as for negative-sequence overcurrent protection operate indication, and the LED 5 is used for the thermal overload protection alarm indication. The breaker-failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase- and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own breaker through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker feeding upstream. For this
176 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

purpose, the TRBU operate output signal is connected to the output PO2 (X100: 8-9). The LED 6 is used for back-up (TRBU) operate indication.
ARC PROTECTION (Optional) ARCSARC1

ARC (1) 50L/50NL (1)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

OR

LED10 (ARC PROTECTION)

ARCSARC2

ARC (2) 50L/50NL (2)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

ARCSARC3

ARC (3) 50L/50NL (3)


3I Io BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET

AUTORECLOSING (Optional) DARREC1

0 -> 1
PHIPTOC1-operate DPHHPDOC1-operate DPHLPDOC2-operate DEFLPDEF2-operate EFPADM2-operate WPWDE2-operate DEFHPDEF1-operate EFPADM3-operate WPWDE3-operate

79
INIT_1 INIT_2 INIT_3 OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD AR_ON READY

OR

INIT_4 INIT_5 INIT_6 DEL_INIT_3

LED11 (AR IN PROGRESS)

DEL_INIT_2 UNSUC_RECL

OR

DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON

X110 6 7

X120_BI3 (CB Open) BI4 (CB Spring Charged)

PDNSPTOC1-operate NSPTOC1-operate NSPTOC2-operate CBXCBR1-selected INTRPTEF1-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate SECRSYN-sync_ok


GUID-314E2B2B-3BF1-4351-982E-E881178D64CE V1 EN

SYNC

OR

Figure 101:

Arc protection

REF615 Application Manual

177

Section 3 REF615 standard configurations

1MRS756378 K

ARC protection (ARCSARC1...3) and autorreclosing (DARREC1) are included as optional functions. The ARC protection offers individual function blocks for three ARC sensors that can be connected to the IED. Each ARC protection function block has two different operation modes, with or without the phase and residual current check. The operate signals from the ARC protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclose function can be blocked with the INHIBIT_RECL input. By default, some selected protection function operations are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the CBXCBR-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_READY input in DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time. The autoreclose sequence in progress indication is connected to the alarm LED 11.

178

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

GUID-BCEB1C2E-BC64-4E79-8329-A5D9FCD7AB2F V2 EN

Figure 102:

Overvoltage and undervoltage protection

Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) protect against abnormal phase voltage conditions. The voltage function operation is connected to the alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function, and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.

REF615 Application Manual

179

Section 3 REF615 standard configurations

1MRS756378 K

GUID-A77D0608-E3F2-4D3D-8907-15034FC42D51 V2 EN

Figure 103:

Positive-sequence undervoltage and negative-sequence overvoltage protection

Positive-sequence undervoltage (PSPTUV) and negative-sequence overvoltage (NSPTOV) protection functions enable voltage-based unbalance protection. The operation signals of the voltage-sequence functions are connected to the alarm LED 3, which is a combined voltage protection alarm LED.

GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V2 EN

Figure 104:

Residual overvoltage protection

The residual overvoltage protection (ROVPTOV) provides earth fault protection by detecting abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. The operation signal is connected to the alarm LED 2.
180 REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

The selectable underfrequency or overfrequency protection (FRPFRQ) prevents damage to network components under unwanted frequency conditions. The function contains a selectable rate of change of the frequency (gradient) protection to detect an increase or decrease in the fast power system frequency at an early stage. This can be used as an early indication of a disturbance in the system. The operation signal is connected to the alarm LED 3.

3.12.3.2

Functional diagram for disturbance recorder and trip circuit supervision

DISTURBANCE RECORDER

RDRE1
DEFLPDEF1-start EFPADM1-start WPWDE1-start DEFLPDEF2-start EFPADM2-start WPWDE2-start DEFHPDEF1-start EFPADM3-start WPWDE3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate OR DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 BI#7 BI#8 BI#9 TRIGGERED

LED7 (DR TRIGGERING)

OR INTRPTEF1-operate EFHPTOC1-start PDNSPTOC1-start T1PTTR1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start CCBRBRF1-trret CCBRBRF1-trbu

BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29

OR

OR

OR

DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-arc_flt_det ARCSARC2-arc_flt_det ARCSARC3-arc_flt_det DARREC-close-cb DARREC-unsuc-recl FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate

OR

OR

INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate INRPHAR1-blk2h T1PTTR1-operate

BI#30 BI#31 BI#32 BI#33 BI#34 BI#35 BI#36

OR

BI#37

OR

SEQRFUF_3PH SEQRFUF_U CCRDIF_FAIL BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open) ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC-inpro FRPFRQ1-start FRPFRQ2-start FRPFRQ3-start SECRSYN-inpro SECRSYN-sync_ok SECRSYN-cl_fail_al SECRSYN-cmd_fail_al

BI#38 BI#39 BI#40 BI#41 BI#42 BI#43 BI#44 BI#45 BI#46 BI#47 BI#48 BI#49 BI#50 BI#51 BI#52 BI#53 BI#54 BI#55 BI#56 BI#57

OR

OR

OR

OR

OR

GUID-A43CDD30-D1E8-4E71-A6DF-C3BB34C8980F V1 EN

Figure 105:

Disturbance recorder

All start and operate signals from the protection stages are routed either to trigger the disturbance recorder or to be recorded by the disturbance recorder, depending
REF615 Application Manual 181

Section 3 REF615 standard configurations

1MRS756378 K

on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected.

GUID-4ECE78AD-FBD1-437D-9D94-FEF176F031B0 V1 EN

Figure 106:

Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as an open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9. Failures in current measuring circuits are detected by CCRDIF. When a failure is detected, blocking signal is activated in current protection functions that are measuring calculated sequence component currents, and unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.

182

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations


Functional diagrams for control and interlocking

3.12.3.3

DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate BI 4 (Lock-out reset) DARREC-open cb CBXCBR1-exe_op DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate CCBRBRF1-trret ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate

MASTER TRIP #1

X100

+
TRPPTRC1
BLOCK TRIP

16 Open CB / trip coil 1 17 15 18 19

PO3 OR

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

TCS1

MASTER TRIP #2

X100 20 22 Open CB / trip coil 2 21 TCS2 23 24

+
PO4 TRPPTRC2
BLOCK TRIP

OR

OPERATE CL_LKOUT RST_LKOUT With lock-out mode selection

GUID-50C1054D-5894-4058-AC25-37F6D984D510 V1 EN

Figure 107:

Master trip

The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker

REF615 Application Manual

183

Section 3 REF615 standard configurations

1MRS756378 K

from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

GUID-C2B1BF1B-DE6E-4905-AE22-4330C9B22DF6 V1 EN

Figure 108:

Circuit breaker control

There are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.

184

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

Table 62:

Device positions indicated by binary inputs 5 and 6


Input to be energized Input 5 (X110:8-9) Input 6 (X110:10-9) x x x x

Primary device position Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position

The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously.

REF615 Application Manual

185

Section 3 REF615 standard configurations

1MRS756378 K

DPHLPDOC1-start DPHLPDOC2-start DPHHPDOC1-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start DEFLPDEF1-start DEFLPDEF2-start DEFHPDEF1-start INTRPTEF1-start EFHPTOC1-start PDNSPTOC1-start PHPTOV1-start PHPTOV2-start PHPTOV3-start PSPTUV1-start NSPTOV1-start PHPTUV1-start PHPTUV2-start PHPTUV3-start ROVPTOV1-start ROVPTOV2-start ROVPTOV3-start EFPADM1-start EFPADM2-start EFPADM3-start WPWDE1-start WPWDE2-start WPWDE3-start FRPFRQ1-start FRPFRQ2-start FRPFRQ3-start DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate INTRPTEF1-operate EFHPTOC1-operate PDNSPTOC1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate PSPTUV1-operate NSPTOV1-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate DPHLPDOC1-operate DPHLPDOC2-operate DPHHPDOC1-operate PHIPTOC1-operate DEFLPDEF1-operate DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate EFHPTOC1-operate ROVPTOV1-operate ROVPTOV2-operate ROVPTOV3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHPTUV1-operate PHPTUV2-operate PHPTUV3-operate PSPTUV1-operate NSPTOV1-operate PHPTOV1-operate PHPTOV2-operate PHPTOV3-operate FRPFRQ1-operate FRPFRQ2-operate FRPFRQ3-operate

COMMON ALARM / INDICATION 1 & 2

OR

X100

+
SO1 TPGAPC1
IN1 IN2 OUT1 OUT2

10
Start Indication

11 12

+
SO2

13
Operate Indication

14

OR

X110

+
OR TPGAPC2
IN1 IN2 OUT1 OUT2

17
Over Current Operate Alarm

SO2

19 18

+
SO3 OR

20
Earth Fault Operate Alarm

22 21

+
SO4

23
Voltage Protection Operate Alarm

24
TPGAPC3 OR
IN1 IN2 OUT1 OUT2

GUID-3EDD7516-25EC-4D20-BBB0-F8BFA8C61750 V1 EN

Figure 109:

Alarm indication

The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured

186

REF615 Application Manual

1MRS756378 K

Section 3 REF615 standard configurations

current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-14) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22)

TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four generic timers (TPGAPC1..4) are available in the IED. The remaining one not described in the functional diagram is available in PCM600 for connection where applicable.

3.12.3.4

Functional diagrams for power quality


The standard configuration offers a set of power quality functions. The total demand distortion of current can be supervised by CMHAI function, and correspondingly the total harmonics distortion of voltage can be supervised by VMHAI. The configuration also offers a short-duration voltage variation measurement function PHQVVR. This can be used for detecting voltage sags, swells and interruptions per-phase. The power quality functions are not connected in the standard configuration by default. Depending on the application, the needed logic connections can be made by PCM600.

REF615 Application Manual

187

188

1MRS756378 K

Section 4 Requirements for measurement transformers

Section 4

Requirements for measurement transformers

4.1
4.1.1

Current transformers
Current transformer requirements for non-directional overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be chosen carefully. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity, and co-ordination of protection. However, when the CT is correctly selected, a fast and reliable short circuit protection can be enabled. The selection of a CT depends not only on the CT specifications but also on the network fault current magnitude, desired protection objectives, and the actual CT burden. The protection settings of the IED should be defined in accordance with the CT performance as well as other factors.

4.1.1.1

Current transformer accuracy class and accuracy limit factor


The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary current to the rated primary current. For example, a protective current transformer of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protective current transformers, the accuracy class is designed by the highest permissible percentage composite error at the rated accuracy limit primary current prescribed for the accuracy class concerned, followed by the letter "P" (meaning protection).
Table 63:
Accuracy class

Limits of errors according to IEC 60044-1 for protective current transformers


Current error at rated primary current (%) 1 3 Phase displacement at rated primary current minutes centiradians 60 1.8 Composite error at rated accuracy limit primary current (%) 5 10

5P 10P

The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protection. The 5P class provides a better accuracy. This should be noted also if there are accuracy requirements for the metering functions (current metering, power metering, and so on) of the IED.

REF615 Application Manual

189

Section 4 Requirements for measurement transformers

1MRS756378 K

The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy. Beyond this level, the secondary current of the CT is distorted and it might have severe effects on the performance of the protection IED. In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limit factor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden. The actual accuracy limit factor is calculated using the formula:
Fa Fn
A071141 V1 EN

Sin + Sn Sin + S

Fn Sin S

the accuracy limit factor with the nominal external burden Sn the internal secondary burden of the CT the actual external burden

4.1.1.2

Non-directional overcurrent protection The current transformer selection


Non-directional overcurrent protection does not set high requirements on the accuracy class or on the actual accuracy limit factor (Fa) of the CTs. It is, however, recommended to select a CT with Fa of at least 20. The nominal primary current I1n should be chosen in such a way that the thermal and dynamic strength of the current measuring input of the IED is not exceeded. This is always fulfilled when I1n > Ikmax / 100, Ikmax is the highest fault current. The saturation of the CT protects the measuring circuit and the current input of the IED. For that reason, in practice, even a few times smaller nominal primary current can be used than given by the formula.

Recommended start current settings


If Ikmin is the lowest primary current at which the highest set overcurrent stage is to operate, the start current should be set using the formula: Current start value < 0.7 x (Ikmin / I1n) I1n is the nominal primary current of the CT.

190

REF615 Application Manual

1MRS756378 K

Section 4 Requirements for measurement transformers

The factor 0.7 takes into account the protection IED inaccuracy, current transformer errors, and imperfections of the short circuit calculations. The adequate performance of the CT should be checked when the setting of the high set stage overcurrent protection is defined. The operate time delay caused by the CT saturation is typically small enough when the overcurrent setting is noticeably lower than Fa. When defining the setting values for the low set stages, the saturation of the CT does not need to be taken into account and the start current setting is simply according to the formula.

Delay in operation caused by saturation of current transformers


The saturation of CT may cause a delayed IED operation. To ensure the time selectivity, the delay must be taken into account when setting the operate times of successive IEDs. With definite time mode of operation, the saturation of CT may cause a delay that is as long as the time the constant of the DC component of the fault current, when the current is only slightly higher than the starting current. This depends on the accuracy limit factor of the CT, on the remanence flux of the core of the CT, and on the operate time setting. With inverse time mode of operation, the delay should always be considered as being as long as the time constant of the DC component. With inverse time mode of operation and when the high-set stages are not used, the AC component of the fault current should not saturate the CT less than 20 times the starting current. Otherwise, the inverse operation time can be further prolonged. Therefore, the accuracy limit factor Fa should be chosen using the formula: Fa > 20*Current start value / I1n The Current start value is the primary pickup current setting of the IED.

4.1.1.3

Example for non-directional overcurrent protection


The following figure describes a typical medium voltage feeder. The protection is implemented as three-stage definite time non-directional overcurrent protection.

REF615 Application Manual

191

Section 4 Requirements for measurement transformers

1MRS756378 K

A071142 V1 EN

Figure 110:

Example of three-stage overcurrent protection

The maximum three-phase fault current is 41.7 kA and the minimum three-phase short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59. The start current setting for low-set stage (3I>) is selected to be about twice the nominal current of the cable. The operate time is selected so that it is selective with the next IED (not visible in the figure above). The settings for the high-set stage and instantaneous stage are defined also so that grading is ensured with the downstream protection. In addition, the start current settings have to be defined so that the IED operates with the minimum fault current and it does not operate with the maximum load current. The settings for all three stages are as in the figure above. For the application point of view, the suitable setting for instantaneous stage (I>>>) in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the criteria given by the current transformer selection formula is fulfilled and also the IED setting is considerably below the Fa. In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons.

192

REF615 Application Manual

1MRS756378 K

Section 5 IED physical connections

Section 5

IED physical connections

5.1
5.1.1
5.1.1.1

Inputs
Energizing inputs
Phase currents
The IED can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied. However, at least terminals X120/7-8 must be connected.
Table 64:
Terminal X120-7, 8 X120-9, 10 X120-11, 12

Phase current inputs included in configurations A, B, C, D, E, F, H and J


Description IL1 IL2 IL3

5.1.1.2

Residual current
Table 65:
Terminal X120-13, 14

Residual current input included in configurations A, B, C, D, E, F, H and J


Description Io

Table 66:
Terminal X1301, 2

Residual current input included in configuration G


Description Io

5.1.1.3

Phase voltages
Table 67:
Terminal X130-11, 12 X130-13, 14 X130-15, 16

Phase voltage input included in configurations E, F, H and J


Description U1 U2 U3

REF615 Application Manual

193

Section 5 IED physical connections

1MRS756378 K

Table 68:
Terminal X130-9, 10

Reference voltage input for SECRSYN1 included in configurations H and J


Description U12B

5.1.1.4

Residual voltage
Table 69:
Terminal X120-5, 6

Additional residual voltage input included in configurations A and B


Description Uo

Table 70:
Terminal X130-17, 18

Additional residual voltage input included in configurations E, F, H and J


Description Uo

5.1.1.5

Sensor inputs
Table 71:
Terminal X131 X132 X133

Combi sensor inputs included in configuration G


Description IL1 U1 IL2 U2 IL3 U3

5.1.2

Auxiliary supply voltage input


The auxiliary voltage of the IED is connected to terminals X100/1-2. At DC supply, the positive lead is connected to terminal X100-1. The permitted auxiliary voltage range (AC/DC or DC) is marked on the top of the LHMI of the IED.
Table 72:
Terminal X100-1 X100-2

Auxiliary voltage supply


Description + Input - Input

5.1.3

Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for remote control of IED settings.

194

REF615 Application Manual

1MRS756378 K

Section 5 IED physical connections

Binary inputs of slot X110 are available with configurations B, D, E, F, G, H and J.


Table 73:
Terminal X110-1 X110-2 X110-3 X110-4 X110-5 X110-6 X110-6 X110-7 X110-8 X110-9 X110-9 X110-10 X110-11 X110-12 X110-12 X110-13

Binary input terminals X110-1...13


Description BI1, + BI1, BI2, + BI2, BI3, + BI3, BI4, BI4, + BI5, + BI5, BI6, BI6, + BI7, + BI7, BI8, BI8, +

Binary inputs of slot X120 are available with configurations C, D, E, F, H and J.


Table 74:
Terminal X120-1 X120-2 X120-3 X120-2 X120-4 X120-2 X120-5 X120-6

Binary input terminals X120-1...6


Description BI1, + BI1, BI2, + BI2, BI3, + BI3, BI4, + BI4, -

Binary inputs of slot X120 are available with configurations A and B.


Table 75:
Terminal X120-1 X120-2 X120-3 Table continues on next page

Binary input terminals X120-1...4


Description BI1, + BI1, BI2, +

REF615 Application Manual

195

Section 5 IED physical connections


Terminal X120-2 X120-4 X120-2 Description BI2, BI3, + BI3, -

1MRS756378 K

Binary inputs of slot X130 are optional for configurations B and D.


Table 76:
Terminal X130-1 X130-2 X130-2 X130-3 X130-4 X130-5 X130-5 X130-6 X130-7 X130-8 X130-8 X130-9

Binary input terminals X130-1...9


Description BI1, + BI1, BI2, BI2, + BI3, + BI3, BI4, BI4, + BI5, + BI5, BI6, BI6, +

Binary inputs of slot X130 are available with configurations E, F, H and J.


Table 77:
Terminal X130-1 X130-2 X130-3 X130-4 X130-5 X130-6 X130-7 X130-8

Binary input terminals X130-1...8


Description BI1, + BI1, BI2, + BI2, BI3, + BI3, BI4, + BI4, -

5.1.4

Optional light sensor inputs


If the IED is provided with the optional communication module with light sensor inputs, the pre-manufactured lens-sensor fibres are connected to inputs X13, X14 and X15, see the terminal diagrams.For further information, see arc protection.

196

REF615 Application Manual

1MRS756378 K

Section 5 IED physical connections

The IED is provided with connection sockets X13, X14 and X15 only if the optional communication module with light sensor inputs has been installed. If the arc protection option is selected when ordering an IED, the light sensor inputs are included in the communication module.
Table 78:
Terminal X13 X14 X15

Light sensor input connectors


Description Input Light sensor 1 Input Light sensor 2 Input Light sensor 3

5.2
5.2.1

Outputs
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. On delivery from the factory, the trip signals from all the protection stages are routed to PO3 and PO4.
Table 79:
Terminal X100-6 X100-7 X100-8 X100-9 X100-15 X100-16 X100-17 X100-18 X100-19 X100-20 X100-21 X100-22 X100-23 X100-24

Output contacts
Description PO1, NO PO1, NO PO2, NO PO2, NO PO3, NO (TCS resistor) PO3, NO PO3, NO PO3 (TCS1 input), NO PO3 (TCS1 input), NO PO4, NO (TCS resistor) PO4, NO PO4, NO PO4 (TCS2 input), NO PO4 (TCS2 input), NO

5.2.2

Outputs for signalling


Output contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot X110 or SO1, SO2 and SO3 in slot X130 (optional) can be used for signalling on

REF615 Application Manual

197

Section 5 IED physical connections

1MRS756378 K

start and tripping of the IED. On delivery from the factory, the start and alarm signals from all the protection stages are routed to signalling outputs.
Table 80:
Terminal X100-10 X100-11 X100-12 X100-13 X100-14

Output contacts X100-10...14


Description SO1, common SO1, NC SO1, NO SO2, NO SO2, NO

Output contacts of slot X110 are available with configurations B, D, E, F, G, H and J.


Table 81:
Terminal X110-14 X110-15 X110-16 X110-17 X110-18 X110-19 X110-20 X110-21 X110-22 X110-23 X110-24

Output contacts X110-14...24


Description SO1, common SO1, NO SO1, NC SO2, common SO2, NO SO2, NC SO3, common SO3, NO SO3, NC SO4, common SO4, NO

Output contacts of slot X130 are available in the optional BIO module (BIOB02A). Output contacts of slot X130 are optional for configurations B and D.
Table 82:
Terminal X130-10 X130-11 X130-12 X130-13 X130-14 X130-15 X130-16 X130-17 X130-18

Output contacts X130-10...18


Description SO1, common SO1, NO SO1, NC SO2, common SO2, NO SO2, NC SO3, common SO3, NO SO3, NC

198

REF615 Application Manual

1MRS756378 K

Section 5 IED physical connections IRF


The IRF contact functions as an output contact for the self-supervision system of the protection IED. Under normal operating conditions, the IED is energized and the contact is closed (X100/3-5). When a fault is detected by the self-supervision system or the auxiliary voltage is disconnected, the output contact drops off and the contact closes (X100/3-4).
Table 83:
Terminal X100-3 X100-4 X100-5

5.2.3

IRF contact
Description IRF, common Closed; IRF, or Uaux disconnected Closed; no IRF, and Uaux connected

REF615 Application Manual

199

200

1MRS756378 K

Section 6 Glossary

Section 6

Glossary

615 series

Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment American National Standards Institute American Standard Code for Information Interchange Binary input Binary input/output Binary output Circuit breaker Current transformer A distributed network protocol originally developed by Westronic. The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution. Double-point control Electromagnetic compatibility A standard for connecting a family of frame-based computer networking technologies into a LAN First in, first out Generic Object-Oriented Substation Event Human-machine interface Hardware Input/output International Electrotechnical Commission 1. Communication standard for protective equipment 2. A serial master/slave protocol for point-to-point communication International standard for substation communication and modeling A communication protocol based on the IEC 61850 standard series Intelligent electronic device Integrated Engineering Toolbox in PCM600
201

ANSI ASCII BI BI/O BO CB CT DNP3

DPC EMC Ethernet FIFO GOOSE HMI HW I/O IEC IEC 60870-5-103

IEC 61850 IEC 61850-8-1 IED IET600


REF615 Application Manual

Section 6 Glossary

1MRS756378 K

IP address

A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol. Inter-Range Instrumentation Group's time code format B Local area network Connector type for glass fibre cable Liquid crystal display Light-emitting diode Local human-machine interface A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Modbus RTU protocol which uses TCP/IP and Ethernet to carry data between devices Protection and Control IED Manager Power output Also known as MTA or base angle. Characteristic angle. Remote I/O unit Galvanic connector type Serial interface standard Serial link according to EIA standard RS485 Rapid spanning tree protocol Remote terminal unit Simplified notation for representing a three-phase power system. Instead of representing each of three phases with a separate line or terminal, only one conductor is represented. Single-line diagram Signal output Transmission Control Protocol/Internet Protocol Trip-circuit supervision Wide area network Web human-machine interface

IRIG-B LAN LC LCD LED LHMI Modbus

Modbus TCP/IP PCM600 PO RCA RIO600 RJ-45 RS-232 RS-485 RSTP RTU Single-line diagram

SLD SO TCP/IP TCS WAN WHMI

202

REF615 Application Manual

203

Contact us

ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 Fax +358 10 22 41094 www.abb.com/substationautomation

1MRS756378 K Copyright 2012 ABB. All rights reserved.

Das könnte Ihnen auch gefallen