Compact: functions and characteristics

motor protection trip units selection (cont.)

For motor protection, Compact circuit breakers may be fitted with: c magnetic trip units, wich provide shortcircuit protection;
P (kW) (400 V, 50 Hz) Ir (A) 0.37 1.5 1.1 2.5 3 6 18.5 40 37 80 110 205

c electronic trip units, specifically designed to provide: v short-circuit protection, v overload protection, v phase-failure protection.
220 160 320 250 500 800 560 1000 670 1250

E26530

48

100

160

Compact NS80H-MA Compact NS100 NS250 Compact NS400 NS630 Compact C801 C1251

MA MA STR22ME MA STR43ME STR35ME (LR OFF) STR55UE

trip units trip units


rating (A)

20 to 70C NS100N/H/L NS160N/H/L NS250N/H/L NS400N/H/L NS630N/H/L C801N/H/L C1001N/H/L C1251N/H

STR22ME
10, 12.5, 20, 25, 40, 50, 80,100 150 c c c c c 220

STR43ME
120 200 320 500

STR35ME
800

STR55UE
1000 1250

1000 1250 800

c c c c c c c c c c c

protection overload (long time)


tripping Ir threshold (A) tripping class (IEC 947-4) tripping time (s) (minimaxi) to 1.5 x Ir to 6 x Ir to 7.2 Ir built into the trip unit tripping time for phase failures (s) tripping threshold (A) Im or Isd adjustable (10 settings) adjustable (40 settings) 0.6...1 x In 0.4...0.8 x In 10 10A 10 20 fixed 120320 615 410 c between 3.5 and 6 s adjustable 144198 270357 433595 5.87.3 10.913.1 17.421.8 45 7.39.1 1215 c 4 s 10% adjust. (32 settings) adjustable (32 settings) 0.4...1 x In 0.4...1 x In 10 10A 10 20 fixed 96120 67.5 4.25.2 30

adjustable 4860 96120 192240 384480 33.7 67.5 1215 2430 2.12.6 4.25.2 8.310.4 1721

phase-failure (complied with the standard IEC 947-4-1)

short-circuit (short time)


accuracy max. overcurrent time before tripping (ms) total breaking time (ms) tripping threshold (A) Ii fixed 13 x Ir 20% fixed 10 60 fixed 15 x In adjustable (8 settings) 6...13 x Ir 15% fixed 10 60 fixed 13 x Ir maxi adjust. (8 settings) 1.5...10 x Ir 15% adjustable 0 60 140 230 60 140 230 350 fixed = In x ... 15 15 12 8(type L) adjustable (8 settings) 1.5...10 x Ir 15% adjustable 0 60 140 230 60 140 230 350 adjustable = In x ... 2...15 2...15 2...8(type L)

short-circuit (instantaneous)
2...12

other functions
SDTAM module motor overload light c c c c (standard)

electronic trip unit STR22ME for Compact NS100 to NS250 circuit breakers
E26984

E26985

1
1 7 8

Ir In=50A
Ir
37.5 40 35.5 42.5 45 47.5 30 50 31.5

ImSTR 22 ME
7,2Ir 7,0s Ir 13 Ir

u1,05 Ir IEC 947.4 / cl.10

3 4 5
test

33.5

Ir

13Ir

protection

c LT (long time) overload protection with adjustable Ir threshold (1), in compliance with tripping class 10 as defined by IEC 947-4 (2); c single-phasing protection (trips in 3.5 and 6 s); c ST (short-time) short-circuit protection: v fixed tripping threshold (13 x Ir) (3), v fixed time delay (4); c INST (instantaneous) short-circuit protection, with fixed threshold (15 x In) (5). trip unit STR22ME rating (A) threshold settings (A) 10 6 6.3 6.7 7.1 12.5 7.5 7.9 8.4 8.9 20 12 12.6 13.4 14.2 25 15 15.7 16.7 17.7 40 24 25.5 27 28.5 50 30 31.5 33.5 35.5 80 48 51 54 57 100 60 63 67 71 150 90 95 101 107 220 132 140 148 157

c single - phasing protection. The single phasing complies with the recommendations of standard IEC 947-4-1. It becomes operational whenever a phase current imbalance of 40% or more is present.

7.5 9.4 15 18.7 30 37.5 60 75 113 166

8 10 16 20 32 40 64 80 120 177

8.5 10.6 17 21.2 34 42.5 68 85 127 187

9 11.2 18 22.5 36 45 72 90 135 198

9.5 11.9 19 23.7 38 47.5 76 95 142 209

10 12.5 20 25 40 50 80 100 150 220

other functions

Indications Load indication by LED in front (7): c off when: I < 1.05 x Ir; c flashing when: I u 1.05 x Ir. Test Test connector in front (8) for connection to a mini test kit or calibration test kit to check circuit breaker operation after fitting the trip unit or other accessories. Contactor tripping module SDTAM (early thermal fault signal, optional): c opens the contactor in the event of an overload. It is thus possible to differentiate between tripping due to overloads and shortcircuits;

c may also be used to signal a thermal fault; c must be reset manually (locally or remotely); c compatible with the following control voltages: v 24 to 72 V DC and 24 to 48 V AC, v 110 to 240 V AC / DC; c fits in place of the MN or MX auxiliary voltage releases.