Beruflich Dokumente
Kultur Dokumente
Installing of CT:
Window type CT's should be mounted with the H1 side of the window towards the power source. The X1 secondary terminal is the polarity terminal (Figure 3).The polarity marks of a current transformer indicate that when a primary current enters at the polarity mark (H1) of the primary, a current in phase with the primary current and proportional to it in magnitude will leave the polarity terminal of the secondary (X1).
Normally CT's should not be installed on "Hot" services. The power should be disconnected when the CT's are installed. Many times this is not possible because of critical loads such as computers, laboratories, etc. that cannot be shut down. Split core CT's should not be installed on "Hot" un insulated bus bars under any conditions.
Short pulses (<50ns) peak current can be up to 4 times the CT maximum current. SMA and BNC connectors can withstand repetitive 3000 volts peak for short time. If the CT output signal is too high, attenuators can be used.
Ka = Kn X (Nn/Na)
Ka= Actual Turns Ration. Kn=Name Plate T/C Ratio. Nn=Name Plate Number of Primary Turns. Na=Actual Number of Primary Turns. Example: 100:5 Current Transformers. 1. Primary Turns=1Nos:
: Ip/Is = Ns/Np
Ip = Primary Current Is = Secondary Current Np = Number of Primary Turns Ns = Number of Secondary Turns Example: A 300:5 Current Transformer. The ratio of the current transformer can be modified by altering the number of secondary turns by forward or back winding the secondary lead through the window of the current transformer. By adding secondary turns, the same primary current will result in a decrease in secondary output. By subtracting secondary turns, the same primary current will result in greater secondary output. Again using the 300:5 example adding five secondary turns will require 325 amps on the primary to maintain the 5 amp secondary output or: 325 p / 5s = 65s / 1p Deducting 5 secondary turns will only require 275 amps on the primary to maintain the 5 amp secondary output or: 275p / 5s = 55s / 1p The above ratio modifications are achieved in the following manner:
Current Transformer Ratio Modification: CT RATIO 100:5A 200:5A 300:5A 100:5A 200:5A 300:5A 100:5A 200:5A 300:5A NUMBER OF PRIMARY TURNS 2 2 2 3 3 3 4 4 4 MODIFIED RATIO 50:5A 100:5A 150:5A 33.3:5A 66.6:5A 100:5A 25:5A 50:5A 75:5A
A primary turn is the number of times the primary conductor passes through the CT's window. The main advantage of this ratio modification is you maintain the accuracy and burden capabilities of the higher ratio. The higher the primary rating the better the accuracy and burden rating. You can make smaller ratio modification adjustments by using additive or subtractive secondary turns. For example, if you have a CT with a ratio of 100:5A. By adding one additive secondary turn the ratio modification is 105:5A, by adding on subtractive secondary turn the ratio modification is 95:5A. Subtractive secondary turns are achieved by placing the "X1" lead through the window from the H1 side and out the H2 side. Additive secondary turns are achieved by placing the "X1" lead through the window from the H2 and out the H1 side. So, when there is only one primary turn each secondary turn modifies the primary rating by 5 amperes. If there is more than one primary turn each secondary turn value is changed (i.e. 5A divided by 2 primary turns = 2.5A). The following table illustrates the effects of different combinations of primary and secondary turns: CT RATIO 100:5A
PRIMARY TURNS 1 1 1 2 2 2 3 3 3
RATIO ADJUSTMENT 100:5A 105:5A 95:5A 50:5A 52.5:5A 45.0:5A 33.3:5A 34.97:5A 31.63:5A
Testing of CT
A number of routine and type tests have to be conducted on CT s before they can meet the standards specified above. The tests can be classified as : 1. Accuracy tests to determine whether the errors of the CT are within specified limits. 2. Dielectric insulation tests such as power frequency withstand voltage test on primary and secondary windings for one minute, inter-turn insulation test at power frequency voltage, impulse tests with 1.2u/50 wave, and partial discharge tests (for voltage >=6.6kv) to determine whether the discharge is below the specified limits. 3. Temperature rise tests. 4. Short time current tests. 5. Verification of terminal markings and polarity.
Polarity Test:
In situations where the secondary bushing identification is not available or when a transformer has been rewound, it may be necessary to determine the transformer polarity by test. The following procedure can be used. The H1 (left-hand) primary bushing and the left-hand secondary bushing are temporarily jumpered together and a test voltage is applied to the transformer primary. The resultant voltage is measured between the right-hand bushings. If the measured voltage is greater than the applied voltage, the transformer is Additive Polarity because the polarity is such that the secondary voltage is being added to the applied primary voltage. If, however, the measured voltage across the right-hand bushings is less than the applied primary voltage, the transformer is Subtractive Polarity. Note: For safety and to avoid the possibility of damaging the secondary insulation, the test voltage applied to the Primary should be at a reduced voltage and should not exceed the rated secondary voltage. In the example below, if the T.C is actually rated 480 - 120 volts, the transformer ratio is 4:1 (480 / 120 = 4). Applying a test voltage of 120 volts to the primary will result in a secondary voltage of 30 volts (120 / 4 = 30). If transformer is subtractive polarity, the voltmeter will read 90 volts (120 - 30 = 90). If the voltmeter reads 150 volts, the transformer is additive polarity (120 + 30 = 150).The red arrows indicate the relative magnitude and direction of the primary and secondary voltages.
Ratio Test
The ratio is defined as the number of turns in the secondary as compared to the number of turns in the primary. Apply one volt per turn to the secondary of the CT under test. Raise voltage slowly while observing meters. When one volt per turn has been reached on the secondary voltmeter, one volt should appear on the primary meter. If the CT saturates before one volt per turn is reached, apply a smaller voltage which is a convenient fraction of one volt per turn. (e.g. .5v per turn). The Primary voltmeter should read the chosen fraction of a volt. If a multi-ratio CT is being tested, the selector switch can be placed in the "External Meter" position. The primary voltmeter can be used to read the voltage between taps on the secondary winding while a known voltage per turn is applied to the winding, either between taps or to the full winding. CAUTION: TO PROTECT AGAINST INSULATION FAILURE, DO NO EXCEED MORE THAN 1000 VOLTS ON ANY OF THE SECONDARY WINDINGS OF THE CT UNDER TEST. Leads should be connected to the test set EXT VOLTS binding posts only when the selector switch is in the EXT METER CONNECTION position.
Saturation Test
IEEE defines saturation as "the point where the tangent is at 45 to the secondary exciting amperes." (See Figures). With the test set secondary binding posts X1 and X2 connected to the CT secondary and the H1 and H2 binding posts connected to the CT primary, increase output observing the ammeter and secondary voltmeter. Increase voltage until a small increase in voltage causes a large increase in current. Most CT's will saturate at 1 amp or less and 600 volts or less. Note: It may be necessary to plot a curve to detect the saturation point. See Figures and ANSI/IEEE C57.13 for illustrations of typical curves for Class C transformers.