BRANCH JOINT INSTALLATION MANUAL

Selection of refrigerant piping size and use of Branch Joint


1 Prepare the pipe to be connected in the field. 2 Determine the piping sizes of each part from table 3, 4, 5. 3 Determine the branch joint from table 1. 4 When pipe is cut with a pipe cutter or the like remove burr, dust and foreign materials inside the pipe and connect the pipe. 5 Always weld while flowing nitrogen, otherwise, the product may not operate due to sludge within the pipe.

Table 2. Contents of branch joint kit


Branch Joint Contents Gas side:1EA Liquid side:1EA Insulation Gas side:1EA Liquid side:1EA Manual 1EA

Table 3. Branch pipe for connection between Outdoor Units


Outdoor Units Branch Joint pipe ARCNN20 ARCNN20,ARCNN30

Table 1. Branch Join Kit


[unit:mm]

Models
I.D. 12.7

Gas pipe
I.D12.7 I.D. 15.88 I.D9.52

Liquid pipe
I.D6.35 I.D9.52

2 3

ARBLN01621
I.D. 15.88 I.D19.05 O.D15.88 I.D22.2 I.D19.05 I.D12.7 I.D. 15.88 I.D19.05 I.D9.52 I.D9.52 I.D25.4 I.D12.7 I.D28.58 O.D25.4 I.D12.7 I.D15.88 I.D19.05 O.D19.05 I.D22.2 I.D19.05 I.D22.2 I.D15.88 I.D12.7 I.D31.8 I.D19.05 I.D19.05 I.D15.88 O.D22.2 I.D31.8 I.D28.58 O.D19.05 O.D31.8 I.D22.2 O.D12.7 I.D6.35 I.D9.52 I.D28.58 I.D9.52 O.D12.7 I.D15.88 I.D12.7 I.D15.88 I.D12.7 I.D9.52 O.D19.05 I.D22.2 I.D25.4 I.D12.7 I.D6.35 I.D12.7 I.D6.35 I.D6.35 I.D9.52 I.D6.35

Table 4. Refrigerant pipe diameter from branch to branch (Fig1.- B,C,D)


Downward Indoor Unit total capacity [kW(Btu/h)] < 5.6 (19,100) < 16 (54,600) < 22.4 (76,400) < 33 (112,600)
I.D19.05 I.D15.88 I.D12.7 I.D12.7

I.D12.7 O.D9.52

Liquid pipe [mm(inch)] 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8) 12.7(1/2) 15.88(5/8) 19.05(3/4) 19.05(3/4)

Gas pipe [mm(inch)] 12.7(1/2) 15.88(5/8) 19.05(3/4) 22.2(7/8) 28.58(9/8) 28.58(9/8) 34.9(13/8) 41.3(15/8)

I.D15.88

ARBLN03321

I.D28.58

< 47 (160,400) < 71 (242,300) < 104 (354, 900)

ARBLN07121
I.D19.05

104 (354,900)

I.D34.9

I.D34.9 I.D41.3 I.D38.1

I.D34.9 I.D38.1 I.D28.58 I.D28.58

I.D15.88

I.D19.05

I.D19.05 I.D22.2 I.D15.88 I.D12.7

Table 5. Between branching and Indoor Unit (Fig1 -a,b,c,d,e)


Liquid pipe Indoor Unit capacity [kW(Btu/h)] [mm(inch)] 6.35(1/4) 9.52(3/8) 9.52(3/8) Gas pipe [mm(inch)] 12.7(1/2) 15.88(5/8) 19.05(3/4)

I.D22.2 I.D34.9 I.D22.2 I.D22.2 O.D19.05 I.D15.88 I.D19.05

ARBLN14521

I.D41.3 O.D34.9 I.D41.3 I.D38.1 O.D38.1

< 5.6(19,100) < 16.0(54,600) < 22.4(76,400)

O.D22.2 I.D15.88 I.D19.05

I.D12.7 O.D28.58 I.D19.05 O.D15.88 I.D22.2

O.D15.88 I.D9.52 I.D12.7

O.D12.7 I.D6.35 I.D9.52

For example. Indicated 9.52 is the outer diameter(O.D..) of field jointed piping

Figure1. Line Branch method


Example) 5 Indoor Units connected Example) 5 Indoor Units connected Example) 5 Indoor Units connected
Sub Main

Example) 5 Indoor Units connected

10m or less

10m or less

L50m

L50m

L150m 40m

L150m L50m 40m

L150m 40m L50m

L150m 40m

h15m

h15m

h15m

h15m

A : Outdoor Unit B : 1st branch (Y branch) C : Indoor Units D : Downward Indoor Unit

A : Outdoor Unit B : 1st branch (Y branch) C : Indoor Units D : Downward Indoor Unit

A B C D E

: Outdoor Unit : 1st branch (Y branch) : Indoor Units : Downward Indoor Unit : Connection branch pipe between Outdoor Units: ARCNN20

A B C D E F

: Outdoor Unit : 1st branch (Y branch) : Indoor Units : Downward Indoor Unit : Connection branch pipe between Outdoor Units: ARCNN20 : Connection branch pipe between Outdoor Units: ARCNN30

Total pipe length = A+B+C+D+a+b+c+d+e 300m


* Equivalent pipe length A+B+C+D+e 150m A+B+C+D+e 175m Longest pipe length after 1st branch l B+C+D+e 40m Difference in height(Outdoor Unit Indoor Unit) H H 50m (40m : Outdoor Unit is lower than Indoor Units)** Difference in height (Indoor Unit Indoor Unit) h h 15m

Total pipe length = A+B+C+D+a+b+c+d+e 300m


* Equivalent pipe length A+B+C+D+e 150m A+B+C+D+e 175m Longest pipe length after 1st branch l B+C+D+e 40m Difference in height(Outdoor Unit Indoor Unit) H H 50m (40m : Outdoor Unit is lower than Indoor Units)** Difference in height (Indoor Unit Indoor Unit) h h 15m

Total pipe length = A+B+C+D+a+b+c+d+e 300m


* Equivalent pipe length A+B+C+D+e 150m A+B+C+D+e 175m Longest pipe length after 1st branch l B+C+D+e 40m Difference in height(Outdoor Unit Indoor Unit) H H 50m (40m : Outdoor Unit is lower than Indoor Units)** Difference in height (Indoor Unit Indoor Unit) h h 15m

Total pipe length = A+B+C+D+a+b+c+d+e 300m


* Equivalent pipe length A+B+C+D+e 150m A+B+C+D+e 175m Longest pipe length after 1st branch l B+C+D+e 40m Difference in height(Outdoor Unit Indoor Unit) H H 50m (40m : Outdoor Unit is lower than Indoor Units)** Difference in height (Indoor Unit Indoor Unit) h h 15m

L Longest pipe length

L Longest pipe length

L Longest pipe length

L Longest pipe length

Insulation of Branch Joint


Fig. 2 Example
Tape (field spply) Insulation material (field spply) Liquid pipe

Fig. 3 Example
Pipe cover Insulation material (field spply)

Mount Liquid pipe 1 to pipe cover 2 in matching. Seal the joing section of pipe cover with inslated sealing tape(field supply). (Refer to Fig. 2) Apply the same procedures to the gas pipe also.
Lapped space of taping Tape (field spply)

Note 1. Apply insulation to all refrigerant piping (field supply). When using the insulation materials being marketed, employ heat resistant insulation material (heat resistant temperature: 120C or more) Note 2. As the pipe cover contracts slightly conduct taping in the field securely by providing lapped parts as shown in so that no gap will exit on the piping cover and field supply insulation material.