SPECIFICATION

DIFFERENTIAL POWER TRANSFORMER RELAY (87) I. SCOPE : This specification should be applicable to differential relay intended for protecting the power three coil transformer. II. STANDARD OF MANUFACTURE AND TEST : IEC 255 : Electric relays. III. DESCRIPTION : 1. Construction : - The relay should operate on the basis of numeral measuring principle. - Display : LCD. - Terminals: Plug - in screw type. - The relay consists of a case used for flush mounting and should be supplied with all accessories for installation and operation. 2. Technical data : - The protective function : + Biased different protection for three phase power three coils transformer (one high voltage winding, two medium voltage windings). The relay should have the individual contacts per phase. + Restricted earth fault protection. + Over fluxing protection. + Measurement of phase, differential and bias currents. + Comprehensive self-checking and alarms. + Integral event recorder accessible from PC. + Flexible operating logic options via software function links. + Numerical display of setting values, measured values, recorded fault values, ... - DC supply : 90 240 Vdc. Tenderer may quote the relay with operating voltage of 110Vdc 10% and the voltage divider to be able to supply the operating voltage of 220Vdc to the relay. - Rated current (In) : 1A - Rated frequency : 50 Hz - Thermal withstand capability in current circuit : + Continuous : 04 x In + for 3s : 10 x In + for 1s :100 x In - Dynamic over load : 250 x In - Minimum operating time : 25 ms - Reset time : 30 ms Accuracy : + 3% set current value. + 1% of the time value. Environment : + Ambient temperature : 0 to 55oC + Humidity : 0 - 95%.
1/5

/var/www/apps/conversion/tmp/scratch_5/137134858.doc

HCMC PC

SPECIFICATION

DIFFERENTIAL POWER TRANSFORMER RELAY (87) 3. Accessory : - 01 test block 14 circuits, 10A-240VDC + Test block offers facilities for monitoring and secondary injection testing and power system protection scheme when used with test plug. + Test block can be fixed to relay without addition any equipment. - 01 test plug 14 circuits, 10A-240VDC - All other accessories for the installation and operation. IV/. TESTING REQUIREMENT : - The relay is subject to inspection during manufacturing. Routine and type tests of each relay including operational test at minimum, accuracy tests will be performed according to IEC 255 standard. - In order to ensure the quality of supplied goods , in case of bid winning , the Tenderer shall supply routine test and copies of type test report met the following requirements: a. Routine test shall be performed for each equipment. b. Type test report shall meet the followings : - Testing sample : The same as the supplied item (manufacturer, original country, manufactures code as specified in tender document). - Testing items : Including testing items according to IEC 255. - Testing values shall be corresponding values as stated in Section III of this specification. If in section III, there are no corresponding values, testing values will be selected according to the standard specified in section II of this specification. V/. REQUIREMENT OF TECHNICAL TENDER DOCUMENT : - Technical description, data sheets, catalogues and other material submitted with the quotation must enable the buyer's engineers to thoroughly evaluate the proposals as to its compliance with the inquiry specifications. - Minimum requirements : + Detailed summary of deviations to inquiry specification. + Completed inquiry data sheet expressed at clause VI. + Brochures and catalogues containing outline dimensions, main electrical data and installation details. + Certificate of quality management. - The proposal bidding has Type Test Report which meets the requirements as specified in item IV 2.b will be preferable. VI/. DATA SHEET : No 1. 2. 3. 4. 5. 6. DESCRIPTION Item No. Manufacturer Country Manufactures code Standards of factory and test Standards of quality REQUIREMENTS TENDERED

IEC 255

/var/www/apps/conversion/tmp/scratch_5/137134858.doc

2/5

HCMC PC

SPECIFICATION

DIFFERENTIAL POWER TRANSFORMER RELAY (87) 7. 8. management Member approve of certificate of management In case of bid winning , the Tenderer shall supply routine test and copies of type test report met the requirements of section IV . Type Display Terminals Case Function

Yes

9. 10. 11. 12. 13.

14. Contacts 15. DC supply Note : Tenderer may quote the relay with operating voltage of 110Vdc10% and the voltage divider to be able to supply the
/var/www/apps/conversion/tmp/scratch_5/137134858.doc

microprocessor LCD Plug-in screw type flush mounting + Biased different protection for three phase power three coils transformer (one high voltage winding and two medium voltage windings). The relay should have the individual contacts per phase. + Restricted earth fault protection. + Over fluxing protection. + Measurement of phase, differential and bias currents. + Comprehensive selfchecking and alarms. + Integral event recorder accessible from PC. + Flexible operating logic options via software function links. + Numerical display of setting values, measured values, recorded fault values, ... Individual contacts per phase. 90 - 240 VDC

3/5

HCMC PC

SPECIFICATION

DIFFERENTIAL POWER TRANSFORMER RELAY (87) operating voltage of 220Vdc to the relay. Input circuit : + Rated current + Rated frequency Thermal withstand ability in current circuit : + Continuous + For 3s + For 1s Dynamic current withstand Minimum operating time Reset time Accuracy of current value Accuracy of time value Ambient temperature Humidity Accessories : - 01 test block 14 circuits, 10A-240VDC

16. 17.

1A 50 Hz 4 x In 10 x In 100 x In 250 x In 25 ms 30 ms 3% of set current value 1% of set value 0-55C 0-95% Yes + Test block offers facilities for monitoring and secondary injection testing and power system protection scheme when used with test plug. + Test block can be fixed to relay without addition any equipment. Yes Yes

18. 19. 20. 21. 22. 23. 24. 25.

01 test plug 14 circuits, 10A-240VDC All other accessories for the installation and operation.

/var/www/apps/conversion/tmp/scratch_5/137134858.doc

4/5