Engine KW
Generator KVA
LOAD FACTOR
Load factor = % of time X % of load Time at specific load % of time = -------------------------Total operating time Specific load % of load = ----------------Rated load
LOAD FACTOR Sample Genset rated at 550 KW Runs two hours a week During two hours it runs at 400 KW for 1.5 hours = 0.73 %
90 minutes % of time = ---------------- = 0.75 % 120 minutes Load factor = 0.73 X 0.75 = 54.75 %
CAT generator rating is based on temperature rise Refer to NEMA ( National Electric Manufactures Association ) And IEC ( International Electro-technical Commission ) Generator class F H F H F H Temp. rise 80 105 125 130 150 Gen-set rating Continuous Prime Prime Standby Standby
Sample: Prime power F class has 105OC rise The total temp rise is 155OC
Basic generator
Field common operating rpm 1000 rpm 1200 rpm 1500 rpm 1800 rpm