CHECK LIST FOR FIRE PUMP- NFPA 20 SYSTEMSGENERAL SUBMITTAL REQUIREMENTS:

This checklist must be completed/answered by consultant(s) by ticking [ ] appropriate boxes (ii) Submit a separate sheet containing explanatory notes against all negated answers (iii) It is axiomatic that the submission has been made by the consultants only upon having read and clearly understood all the relevant provisions of the current Fire Protection, Fire Prevention and Fire/Emergency Control(FP, FP&FF) Regulations

FIRE PUMP INFORMATION [ horizontal or vertical]

1 Manufacturer details provided 2 Model number details provided 3 Manufacturer specification sheet(s) provided 4 Proof that all equipment components are listed 5 GPM rating provided on the plans 6 Head rating provided on the plans 7 RPM's provided on the plans 8 Piping size and type is detailed 9

YES YES YES YES YES YES YES YES

NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO

OS & Y valve in suction pipe is correctly detailed in the YES plans YES YES YES YES YES YES

10 Size of suction pipe and type is detailed 11 Check valve in pump discharge assembly 12 Eccentric taper reducer for suction is detailed (taper at bottom)

13 Vortex plate is provided when stored water is used 14 Indicating valve on the system side of the check valve 15 Pressure relief valve located between pump and pump discharge

FIRE PUMP INFORMATION [horizontal or vertical]

1 Emergency lighting provided in pump room

YES

NO

Automatic sprinkler protection provided in the pump room

YES YES

NO NO NO NO

3 Pump room floor drain provided

4 5

Pump room wiring in rigid or liquid tight flexible metal YES conduit Double backflow preventer valve is detailed YES

ADDITIONAL INFORMATION VERTICAL PUMPS 1 Submergence level of pump impellers 2 Well screen and suction and strainer details 3 Dimensions of well 4 YES YES YES NO NO NO NO

Air relief valves, water level detectors, pressure gauges, YES etc DRIVER INFORMATION 1 Manufacturer and specification information provided 2 Model number provided 3 Rated horsepower provided 4 RPM's provided 5 Electric or diesel information provided 6 Hours of fuel supply given ELECTRIC DRIVERS 1 Electrical circuit schematic provided 2 3 Schematic for secondary power circuit and transfer equipment YES YES YES YES YES YES YES

NO

NO NO NO NO

NO NO NO NO

Controller near motors(more than 12" above floor and 3 YES ' clearance to the rear) YES

4 Controller listed for electric motor drivers

5 Alarm signal provided to an attended location

YES

NO

6 Transfer switch specification and listing provided 7 One transfer switch provided for each individual pump DIESEL DRIVERS 1 Listed fire pump used 2

YES YES

NO NO

YES

NO NO NO NO NO NO NO NO NO

Closed circuit and liquid cooling details provided in the YES plans YES YES

3 Equipped with over speed shutdown device 4 Instrument panel with tachometer, oil pressure, and temperature gauges

5 Two batteries provided for each engine- rack supported YES 6 Batteries have two means for recharging shown YES

7 Pump room & engine has adequate ventilation provided YES 8 Fuel tank is at least 1 gallon per horsepower plus a 5% cushion YES YES

9 The controller is listed for diesel pump use 10 Controller near motors(more than 12" above floor and 3 ' clearance to the rear)

11 Alarm signal provided to an attended location JOCKEY PUMP INFORMATION 1 Jockey pump location and piping is detailed 2 Jockey pump specification sheet(s) provided with the plans Jockey pump check valve is detailed on the discharge 3 pipe

YES

NO

YES YES YES

NO NO NO

WATER SUPPLY INFORMATION 1 Minimum supply provided 2 Connection to water supply 3 FDC location is acceptable (within 50' of a public fire hydrant) YES YES YES NO NO NO

OTHER DETAILS Dedicated ATS for individual Fire pumps sets provided 1 YES for electric driven pumps Dedicated and direct Power supply for the fire pumps 2 sets provided from the main distributin board of the source (DEWA Transformer) YES

NO NO

Minimum 1m from all sides provided for easy 3 access/maintenance of fire protection system maintained YES inside the room 4 Controllers are placed inside the pump room with easy accessiblity YES YES YES YES Title

NO

NO NO NO NO Date

5 Control logic/pressure switch setting details provided 6 Adequate and appropriate ventilations for pump 7 Factory test curve & related test documents provided For Contractor

Signatures/S eals

For Client/Consultant

Title