Sie sind auf Seite 1von 109

GENERATOR PROTECTION TYPES OF PROTECTION

TYPE OF PRIME - MOVER AND CONSTRUCTION MW AND VOLTAGE RATINGS MODE OF OPERATION METHOD OF CONNECTION TO POWER SYSTEMS METHOD OF EARTHING

GENERATOR PROTECTION
PRIME MOVERS
STEAM TURBINES GAS TURBINES HYDRO DIESEL

GENERATOR PROTECTION
CONSTRUCTION
CYLINDRICAL ROTOR SALIENT POLE

MODE OF OPERATION
BASE LOAD PEAK LOAD STAND - BY

GENERATOR PROTECTION
CONNECTION TO POWER SYSTEM
DIRECT

GENERATOR PROTECTION
CONNECTION TO POWER SYSTEM
DIRECT

VIA TRANSFORMER

GENERATOR PROTECTION
METHOD OF EARTHING

SOLID

GENERATOR PROTECTION
METHOD OF EARTHING

SOLID

RESISTANCE

GENERATOR PROTECTION
METHOD OF EARTHING

SOLID

RESISTANCE

HIGH IMPEDANCE

GENERATOR PROTECTION REQUIREMENTS


DETECT FAULTS ON THE GENERATOR PROTECT FROM ABNORMAL OPERATING CONDITIONS ISOLATE SO GENERATOR G O FROM O UNCLEARED C SYSTEM S S FAULTS

ACTIONS REQUIRED
URGENT

NOT URGENT ALARM

GENERATOR PROTECTION DIFFERENTIAL PROTECTION

PROVIDES HIGH SPEED PROTECTION FOR ALL FAULT TYPES MAY BE HIGH IMPEDANCE TYPE OR BIASED DIFFERENTIAL TYPE

GOOD QUALITY CTS ARE REQUIRED AT LINE AND NEUTRAL ENDS

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE

~
Differential Relay Stabilising g Resistor
ZG9323

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE

~
If V RCT 2RL

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE
V = If x { RCT + 2RL } Z = V / IS RSTAB = Z - RRELAY

~
If V

RCT 2RL

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE
STABILISING RESISTOR CALCULATION Rstab = If x ( RCT + 2 RL) Is ( VA ) Is2

WHERE If = MAXIMUM THROUGH FAULT CURRENT RCT = RESISTANCE OF CT WINDING 2RL = TWO WAY LEAD RESISTANCE VA = RELAY BURDEN Is = RELAY SETTING

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE
EXAMPLE 50 MVA Xd = 18 % RCT = 3 Ohms SETTING = 0.5A 11KV F L. F. L C. C = 2624 Amps

C. T. RATIO = 3000 / 1 2RL = 2 Ohms

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE
FAULT CURRENT ( IF ) = 50 x 103 1.732 x 11 x 0.18 = 4.86 A ( Sec ) RSTAB = = = IF x ( RCT + 2 RL ) Is 4.86 x (3 + 2 ) 0.5 48.6 - 4 = ( VA ) Is2 1 0.52 44.6 Ohms = 14579 A

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


HIGH IMPEDANCE TYPE
CT REQUIREMENT ACCURACY CLASS KNEE POINT VOLTAGE VK : PS CLASS > 2 IF ( RCT + 2RL )

MAGNETISING CURRENT IMAG < 3 % OF In AT VK / 2

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


LOW IMPEDANCE TYPE

~
BIAS COIL BIAS COIL
ZG9323

OPERATING COIL

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


LOW IMPEDANCE TYPE

DIFF. CURREN D NT

OPERATE

RESTRAIN

BIAS CURRENT

GENERATOR PROTECTION DIFFERENTIAL PROTECTION


OVERALL DIFFERENTIAL PROTECTION SCHEME

~
RELAY

UAT

ICT

GENERATOR PROTECTION OVERALL DIFFERENTIAL PROTECTION


BIASED RELAYS SHOULD ONLY BE USED NO MAG - INRUSH AS TRANSFORMER VOLTAGE IS GRADUALLY DEVELOPED HOWEVER MAG - INRUSH CURRENT WILL FLOW FOR THE FOLLOWING CONDITION WHEN A THROUGH FAULT IS CLEARED WHEN A LARGE STATION TRANSFORMER CONNECTED TO G T BUSBAR IS ENERGISED

GENERATOR PROTECTION INTERTURN FAULT PROTECTION


LONGITUDINAL DIFFERENTIAL SYSTEM DOES NOT DETECT INTERTURN FAULTS INTERTURN FAULT PROTECTION NOT COMMONLY PROVIDED BECAUSE FAULTS ARE RARE EVEN IF THEY OCCUR OCCUR, THEY WILL QUICKLY DEVELOP INTO STATOR EARTH FAULTS

GENERATOR PROTECTION INTERTURN FAULT PROTECTION


HIGH IMPEDANCE TYPE PROTECTION
R Y B DIFFERENTIAL RELAY

STABILISING RESISTOR

GENERATOR PROTECTION INTERTURN FAULT PROTECTION


LOW IMPEDANCE TYPE PROTECTION
R Y B DIFFERENTIAL RELAY

GENERATOR PROTECTION INTER TURN FAULT PROTECTION


HIGH IMPEDANCE TYPE PROTECTION
SETTINGS RELAY PICK - UP = SHOULD BE LESS THAN DIFFERENTIAL CURRENT DUE TO SINGLE TURN SHORT CIRCUIT Rstab = SAME AS DIFFERENTIAL PROTECTION EXCEPT FAULT CURRENT ( If ) = MVA x 103 1.732 x KV x Xd x 2

GENERATOR PROTECTION COMBINED DIFFERENTIAL & INTERTURN


HIGH IMPEDANCE TYPE PROTECTION
R Y B RELAY

GENERATOR PROTECTION ZERO SEQ. VOLTAGE MEASUREMENT

SHORT CIRCUIT OF ONE OR MORE TURNS WILL CAUSE THE GENERATED E M F TO CONTAIN ZERO SEQUENCE COMPONENT EXTERNAL EARTHFAULTS WILL ALSO PRODUCE A ZERO SEQUENCE VOLTAGE - MOST OF THE VOLTAGE WILL BE EXPENDED ON EARTHING RESISTOR HENCE, DROP ACROSS THE WINDING SHOULD BE MEASURED

GENERATOR PROTECTION INTERTURN FAULT PROTECTION


ZERO SEQUENCE VOLTAGE DETECTION

TUNED RELAY SHOUD BE USED R VR =VA + VB + VC

GENERATOR PROTECTION STATOR EARTH FAULT PROTECTION


CAUSED BY INSULATION FAILURE LEADS TO BURNING OF MACHINE CORE, WELDING OF LAMINATIONS REBUILDING OF MACHINE CORE CAN BE A VERY EXPENSIVE PROCESS HENCE EARTH FAULT PROTECTION IS A MUST

GENERATOR PROTECTION STATOR EARTH FAULT PROTECTION


DEPENDS ON SYSTEM EARTHING 95 % STATOR EARTH FAULT PROTECTION 100% STATOR EARTH FAULT PROTECTION RELAYS WITH INVERSE CHARACTERISTICS PREFERRED

GENERATOR PROTECTION

95 % S. E. F. PROTECTION - CURRENT OPERATED


R

~
R 10 % - 40 %

SUITABLE FOR RESISTANCE AND SOLIDLY EARTHED SYSTEMS

GENERATOR PROTECTION

95 % S. E. F. PROTECTION - VOLTAGE OPERATED

~
64 SUITABLE FOR HIGH IMPEDANCE EARTHED SYSTEMS SHOULD BE A TUNED RELAY R

GENERATOR PROTECTION NEED FOR 100 % S. E. F. PROTECTION


OVERCURRENT AND OVERVOLTAGE RELAYS WILL NOT DETECT EARTH FAULT NEAR NEUTRAL

DIFFERENT METHODS

SUB - HARMONIC INJECTION THIRD HARMONIC UNDERVOLTAGE COMPARISON OF THIRD HARMONIC VOLTAGE AT NEUTRAL AND LINE ENDS

GENERATOR PROTECTION SUB - HARMONIC INJECTION METHOD

WILL NOT DETECT OPEN CIRCUITING OF GROUND TRANSFORMER PRIMARY OR SECONDARY CHANGES THE EARTHING PARAMETERS WHICH IS NOT DESIRABLE OFF - LINE SUPERVISION IS REQUIRED COST OF IMPLEMENTAION AND MAINTENANCE IS VERY HIGH

GENERATOR PROTECTION THIRD HARMONIC UNDERVOLTAGE

SUFFICIENT NEUTRAL THIRD HARMONIC VOLTAGE SHOULD BE AVAILABLE

IT WILL ALSO BE OUT - OF - SERVICE IF SUFFICIENT VOLTAGE HAS NOT DEVELOPED DURING LIGHTLY LOADED CONDITIONS

GENERATOR PROTECTION THIRD HARMONIC VOLTAGE COMPARISON

LINE SIDE AND NEUTRAL SIDE THIRD HARMONIC VOLTAGES ARE COMPARED

V L3

V N3

NORMAL CONDITION

GENERATOR PROTECTION THIRD HARMONIC VOLTAGE COMPARISON


GROUND FAULT AT NEUTRAL END ( VN 3 = 0 )

V N3

V L3

GENERATOR PROTECTION THIRD HARMONIC VOLTAGE COMPARISON


GROUND FAULT AT NEUTRAL END ( VN 3 = 0 )

V N3
GROUND FAULT AT LINE END ( VL 3 = 0 )

V L3

V N3

V L3

GENERATOR PROTECTION
FAULT AT 50 % OF GENERATOR WINDING

V L3
DEAD ZONE THE V L 3 , V N 3 BALANCE WILL BE MAINTAINED THE 100 % UNIT MAY NOT DETECT HENCE , USE A 95 % UNIT ALSO

V N3

GENERATOR PROTECTION 100 % STATOR EARTH FAULT


95 % MODULE 100 % MODULE GENERATOR WINDING

0%

100 %

95 % MODULE SHOULD BE CONNECTED TO GROUNDING TRANSFORMER SECONDARY SHOULD BE TUNED

GENERATOR PROTECTION 100 % STATOR EARTH FAULT PROTECTION


DEFINITE TIME DELAYED 100 % UNIT INVERSE TIME DELAYED 0 - 95 % UNIT IMMUNITY AGAINST FUSE FAILURE PROVIDES MONITORING POINTS FOR MEASUREMENT OF OPERATING QUANTITIES USED IN MANY 500 MW AND 210 MW GENERATING SETS

GENERATOR PROTECTION UNBALANCED LOADING


GIVES RISE TO NEGATIVE PHASE SEQUENCE STATOR CURRENT WHICH CAUSES CONTRA - ROTATING MAGNETIC FIELDS

STATOR FLUX CUTS ROTOR AT TWICE SYNCHRONOUS SPEED INDUCING DOUBLE FREQUENCY CURRENT IN FIELD SYSTEM AND ROTOR BODY

RESULTING . . . . .

GENERATOR PROTECTION UNBALANCED LOADING


RESULTING EDDY CURRENTS CAUSE OVERHEATING MACHINES ARE ASSIGNED I2 S = CONTINUOUS NPS RATING I22 t = SHORT TIME NPS RATING IF SYSTEM UNBALANCE APPROACHES MACHINE CONTINUOUS WITHSTAND THEN PROTECTION IS REQUIRED

GENERATOR PROTECTION
TYPICAL NPS CURRENT WITHSTAND TABLE
TYPE OF MACHINE
TURBO ALTERNATOR TURBO ALTERNATOR TURBO ALTERNATOR TURBO ALTERNATOR SALIENT POLE

TYPE OF COOLING
DIRECT HYDROGEN 30 LB / SQ. FT CONVENTIONAL HYDROGEN 30 LB / SQ. FT CONVENTIONAL HYDROGEN 15 LB / SQ. FT CONVENTIONAL HYDROGEN 0.5 LB / SQ. FT CONVENTIONAL AIR

I2 S
10 15 15 15 40

I 22 t
7 12 15 20 60

GENERATOR PROTECTION NEGATIVE PHASE SEQUENCE PROTECTION I22 t = K


WHERE I2 = t = NEGATIVE SEQUENCE COMPONENT WITHSTAND TIME (SECS)

K = CONSTANT PROPORTIONAL TO THE THERMAL CAPACITY OF GENERATOR

GENERATOR PROTECTION OVERLOAD


OVER - TEMPERATURE IN STATOR AND ROTOR INSULATION FAILURE

OVERLOAD PROTECTION

PICK - UP

ABOVE THE MAX LOAD CURRENT

ALTERNATIVELY , CURRENT OPERATED THERMAL REPLICA RELAYS

GENERATOR PROTECTION VOLTAGE RELAYS

FIELD EXCITATION SYSTEM USUALLY PREVENTS UNDER- AND OVER- VOLTAGE CONDITIONS

OVER - VOLTAGE CONDITION OCCURS WHEN


1 ) PRIME - MOVER OVERSPEEDS DUE TO SUDDEN LOSS OF LOAD 2 ) VOLTAGE REGULATOR IS DEFECTIVE

GENERATOR PROTECTION
OVER VOLTAGE
ENDANGERS INTEGRITY OF INSULATION OVERFLUXING DEFINITE TIME DELAYED / INVERSE TIME OVERVOLTAGE IS PROVIDED

UNDER VOLTAGE
DEFINITE TIME DELAYED UNDERVOLTAGE PROTECTION IS GENERALLY PROVIDED BACK - UP FOR OTHER MAIN PROTECTION RELAYS

GENERATOR PROTECTION FUSE FAILURE PROTECTION


USED FOR BLOCKING PROTECTION RELAYS PRIMARY AND SECONDARY FUSES SHOULD BE MONITORED

GENERATOR PROTECTION VT FUSE FAILURE PROTECTION


PT - 1
MVAPM32 (1)

MVAPM32 (2) MVAPM32 (1)

PT - 2

(+)

C1 C2

MVAPM32 (2)

(-)

MVAPM32 (1)

MVAPM32 (2)

C1 : C2 :

PT - 1 FAILURE PT - 2 FAILURE

GENERATOR PROTECTION
Loss of Excitation

Generator Capability Curve

Can be translated to R-X Plane ( MVA , ) Z = ( Z, ) [ secy.]

( KV2 / MVA ) . ( CTR / PTR )

KV : Voltage for which the capability curve is valid

GENERATOR PROTECTION
Loss of Excitation

Causes
Accidental tripping of field breaker Short circuit in the field P Poor b brush h contact t t AVR failure Loss of AC supply to the excitation system Loss of field to the pilot exciter

GENERATOR PROTECTION
Loss of Excitation

Consequences

Generator damage
Induction generator rotor heating

Synchronous

Slip frequency induced currents High currents

stator heating

Stator end iron heating Hydrogenerators : saliency

GENERATOR PROTECTION
Loss of Excitation Consequences

Effects on the system

Substantial reactive drain System instability Voltage collapse

GENERATOR PROTECTION
Loss of Excitation Field Failure Characteristic X

R Xd/ 2

Xd

GENERATOR PROTECTION
L Loss of f Excitation E it ti

Protection X

R Xd/ 2

Xd

GENERATOR PROTECTION
L Loss of f Excitation E it ti

Protection

Time delays required for field failure protection


Delay on pick-up Delay on drop-off drop off

Measuring Element TDDO TDPU

GENERATOR PROTECTION
Pole Slipping

System considerations
System complexity Performance criteria Machine design advancements

GENERATOR PROTECTION
Pole Slipping

C Causes

Prolonged fault clearing Excessive system impedances Underexcited operation Low system voltage Line switching operations

GENERATOR PROTECTION
Pole Slipping

Steady - state stability


Response to small and gradual changes in the y system P = ( Vs.Vr / X ) Sin Vs , Vr : sending & receiving end voltages X : Reactance between Vs and Vr : Power angle

GENERATOR PROTECTION
Pole Slipping Consequences High currents, voltage swings

St t winding Stator i di stress t Pulsating torques Transients in the step -up transformer

GENERATOR PROTECTION
Pole Slipping

Characteristics EA ZA X B ZB ZL ZA A P R ZL ZB EB

GENERATOR PROTECTION
Pole Slipping jX

Protection - Type ZTO


Directional cum blinder Directional identifies severe swings Blinder identifies swings leading to pole - slip Timer distinguishes fault conditions
Locus of Pole Slip

R stable g swing

GENERATOR PROTECTION Motoring


Failure of mechanical input

Synchronous Generator

Synchronous Motor

Prime mover is the main concern

GENERATOR PROTECTION Motoring


Prime Mover Diesel Engine Motoring Power 5 % - 25 % Possible Damage Risk of fire or explosion l i Mechanical

Gas Turbine

10% - 15 %

Hydro - Turbine

0.2 % - 2 %

Blade & runner cavitation Thermal stress damage

Steam turbine

0.5 % - 3 %

GENERATOR PROTECTION Motoring


Protection Considerations

Automatic disconnection Non-electrical means of protection Electrical detection Sensitive reverse p power relay y Three-phase detection CT / PT accuracy

GENERATOR PROTECTION Motoring


Protection Considerations

P Va Q

Reverse power relay High operating angle range Time delays -- Transients -- Asymmetrical faults Disabling -- Pumped storage schemes -- Synchronous compensation

Ia

GENERATOR PROTECTION
Abnormal Voltages

Over voltages - Causes


AVR failure Operator Errors Lightly loaded conditions Load rejection Hydro generators

GENERATOR PROTECTION
Abnormal Voltages

Overvoltages - Consequences

Damage to insulation Over fluxing Damage to isolated loads

GENERATOR PROTECTION
Abnormal Voltages

Overvoltages - Protection

Definite Time relays 100 % - 120 % threshold 1s - 3s delay Instantaneous relay, if desired 130% - 150 % threshold

GENERATOR PROTECTION
Ab Abnormal lV Voltages l

Undervoltage Function
A V R failure B k Back-up f uncleared for l df faults lt -- Parallel connected generators Prevents damage to loads I t l ki Interlocking

GENERATOR PROTECTION
Abnormal Frequency

Basics

Load - frequency link Load shedding schemes Relieve overload on generators Minimise risk of damage g Minimise possibility of cascading Restoration of normal frequency

GENERATOR PROTECTION
Abnormal Frequency

Underfrequency - Causes
Loss of Generation Overload S t System split lit Load shedding Underfrequency

GENERATOR PROTECTION
Abnormal Frequency

Under frequency - Consequences

Generator

Reduced output capability Thermal damage Overfluxing

Turbines

Blade stresses Mechanical resonances

GENERATOR PROTECTION
Ab Abnormal lF Frequency Prohibited operation

Restricted Time Operating Frequency Limits Continuous operation Restricted Time Operating Frequency Limits

Prohibited operation

Duration

Frequency

50

GENERATOR PROTECTION
Abnormal Frequency q y

Underfrequency q y - Consequences q

Plant Auxiliaries - Steam Loss of Capacity at reduced speeds Plant Pl tA Auxiliaries ili i - Nuclear N l Coolant Pump outputs reduced Combustion Turbines H d generators Hydro t

GENERATOR PROTECTION
Abnormal Frequency

Under frequency - Protection


Suggested criteria ( I E E E )

Establish trip points & time delays based on turbine limits Co-ordination with automated load shedding Failure of any single relay should not cause machine tripping

GENERATOR PROTECTION
Abnormal Frequency q y

Under frequency - Protection


Suggested criteria ( I E E E )

Failure of any single relay should not jeopardise the protection scheme Scheme should be in operation whenever the unit is synchronised y / supplying pp y g auxiliaries Separate S t alarms l for f reduced d df frequency / pending trip

GENERATOR PROTECTION
Abnormal Frequency q y

Over frequency
Fault clearing

- Causes

Over shedding Loss of Load

GENERATOR PROTECTION
Abnormal Frequency q y

Overfrequency
Fault clearing

- Causes

Overshedding Loss of Load

Load rejection

GENERATOR PROTECTION
Abnormal Frequency

Overfrequency
Fault clearing

- Causes
Over frequency

Overshedding Loss of Load

Load rejection

GENERATOR PROTECTION
Abnormal Frequency q y

Over frequency q y - Considerations


High speed sets : centrifugal forces Control action possible p Protection - backup to governor - Hydroturbines - Time delays

GENERATOR PROTECTION
O fl i Overfluxing

Causes

Prior to synchronisation - Operator / System errors

Failure of excitation system - Loss of nearby generators - Operation in overexcited mode

Load rejection

GENERATOR PROTECTION
Overfluxing Overexcitation High Flux Density

GENERATOR PROTECTION
Overfluxing Overexcitation High Flux Density

Saturation of Iron

GENERATOR PROTECTION
Overfluxing Overexcitation High Flux Density

Saturation of Iron Leakage Paths

GENERATOR PROTECTION
Overfluxing Overexcitation High Flux Density

Saturation of Iron Leakage Paths Eddy Currents

GENERATOR PROTECTION
O fl i Overfluxing Overexcitation High Flux Density

Saturation of Iron Leakage Paths Eddy Currents Heat Interlaminar voltage

GENERATOR PROTECTION
O fl i Overfluxing

Protection

Combined with transformer protection Volts / Hz limiter Definite - time relays y Inverse - time relays t V Hz

GENERATOR PROTECTION
Back up Protection Back-up

Voltage Controlled Overcurrent Protection


Overload Ch Characteristic t i ti Current Pick - up

Is

Fault Characteristic

Vs Voltage

GENERATOR PROTECTION
B k Back-up P t ti Protection

Voltage Controlled Overcurrent - Settings Under voltage switching threshold


No switching under single phase - earth faults Should switch for remote - end faults

GENERATOR PROTECTION
B k Back-up P t ti Protection

Voltage Restrained Overcurrent Protection

More suited for indirect connected generators g Curre ent Pick k-up Equivalent to impedance devices I> KI>

VS2 VS1 Voltage

GENERATOR PROTECTION
Back-up Back up Protection

Voltage Restrained Over current Protection Settings


I> VS1 : : Maximum possible load current No switching for earth-faults Should pick - up for remote end feeder fault

K I > & VS2 :

GENERATOR PROTECTION
B k Back-up P t ti Protection

Basics

Subtransient Period

Xd , ( 0.1 - 0.2 p.u. )

Td

Transient Period

Xd , Td ( 0.15 0 15 - 0.35 0 35 p.u. ) Xd ( 1.2 - 1.8 p.u. )

Steady - State Period

C Co-ordination di ti with ith d downstream t relays l Low pick - up required

GENERATOR PROTECTION
Back up Protection Back-up

Distance Type Back Back-up up

~
21

Single zone with mho / offset mho characteristic

GENERATOR PROTECTION
B k Back-up P t ti Protection

Distance Type yp Back-up p


Settings T cover the To th longest l t outgoing t i line li Z = ZT ZL n ZT + n ZL

= Transformer impedance = Outgoing line impedance = Number of parallel connected generators

GENERATOR PROTECTION
B k Back-up P t ti Protection

Back-up Earth fault Protection


Direct Connected Machines Indirect Connected Machines Coordination -- Pickup for remote - end earth faults. 51N

GENERATOR PROTECTION
B k Failure Breaker F il

Considerations

Faults involving low currents Abnormal operating conditions

Use high sensitivity detectors OR Use auxiliary contacts from breaker

GENERATOR PROTECTION
G Generator t Tripping Ti i

Tripping Modes

Class A

HV breaker , Field breaker, , Turbine For faults in the generator zone

Class B

Turbine Trip HV Breaker & Field Breaker interlocked with low forward power relay

Class C

HV breaker

GENERATOR PROTECTION
S t System Effects Eff t

Concerns
Accidental Energizing

Shaft Torques

Unbalanced Currents Improper p ope Synchronising Sy c o s g Abnormal Voltages Transient Instability

GENERATOR PROTECTION
S t System Effects Eff t

Accidental Energisation

Operating Errors

Energisation through the HV disconnect switch - Breaker Head Flashover Hi h di High dielectric l t i stress t +S Small ll contact t t gaps

GENERATOR PROTECTION
S t System Effects Eff t

Accidental Energisation - Consequences


Induced Currents Rapid heating of the rotor surface Mechanical damage Hi h primary High i currents t ( Because machine impedance

Xd )

GENERATOR PROTECTION
S t System Effects Eff t

Accidental Energisation - Protection


Voltage Supervised O / C relays Frequency supervised O / C relays Auxiliary contact enabled O/C relays Di t Distance R Relays l Directional I D M T relays y

GENERATOR PROTECTION
Generator Tripping FB

Suggested Trip L i ( IEEE ) Logic

Device
87 59G 32 40 46 21/51V 78 81 64F

GB

PM

Alarm

GENERATOR PROTECTION
R t Earth Rotor E th Faults F lt

Considerations

First Earth Fault

Not Harmful Raises the probability of second fault Unbalanced fluxes Rotor vibration

Second Earth Fault

GENERATOR PROTECTION

VTUM VTUM O CTIG


CTIG

VTT 11
VTT 11

U/V

VAA

TD DO

VAA

Dead Machine Tripping Backup Tripping

GENERATOR PROTECTION
TYPICAL CLASSIFICATION OF TRIPPING
PROTECTIVE RELAY Generator Differential Relay Generator Transformer Differential Relay Unit Overall Differential Relay Generator Stator E/F Relay (100%) Generator Stator E/F Relay (95%) Generator Transformer Overfluxing Relay Generator Under frequency Relay Generator Rotor Earth Fault Relay Generator Pole slipping Relay Generator Field Failure Relay Generator Low Forward Power Relay TRIPPING MODE Class A Class A Class A Class A Class A Class B Class C After some time (say 30mins) II stage Class B II stage Class C Class B Without Under voltage For interlock in Class B tripping I stage alarm I stage alarm I stage alarm REMARKS

GENERATOR PROTECTION
TYPICAL CLASSIFICATION OF TRIPPING
PROTECTIVE RELAY Generator Reverse Power Relay Generator Distance Backup Impedance Relay Generator Voltage Restrained Relay Generator Transformer H.V. side Backup O/C relay Generator Transformer H.V. side Backup E/F relay Unit Auxiliary Transformer Differential Relay Generator Negative Sequence Current Relay Generator Definite time O/C Relay Unit Auxiliary Transformer H.V. side O/C Relays (Backuup) Generator Transformer Buchholz Relay Generator Transformer Winding Temperature Device Generator Transformer Oil Temperature Device Class A Class A II-stage Class C II-stage Class C II-stage I-stage alarm I-stage alarm I-stage alarm TRIPPING MODE Class A Class C Class A Class C Class B Class A Class C I-stage alarm For alarm REMARKS

GENERATOR PROTECTION
TYPICAL CLASSIFICATION OF TRIPPING
PROTECTIVE RELAY Generator Transformer Oil Level Device Unit Auxiliary Transformer Buchholz Relay(s) Unit Auxiliary Transformer(s) Oil Temperature Device(s) Class C TRIPPING MODE REMARKS Alarm I-stage alarm I-stage alarm II-stage-trip unit switch gear incomer breaker(s) and Auto change-over to station service

Unit Auxiliary Transformer(s) Oil Temperature Devices

I-stage alarm II-stage-trip unit switch gear incomer breaker(s) and Auto change-over.

Unit Auxiliary Transformer(s) Oil Level Device

Alarm

Das könnte Ihnen auch gefallen