IDMTL EARTH FAULT AND OVERCURRENT RELAY

RSN200

Made In Japan

W High Transient Withstand E N EMC Compliant

Fault Clearance Safety Reset

Kasuga Digital IDMTL Type RSN200 Earth Fault and Overcurrent Relay is designed to protect electrical equipment and networks against overcurrent and ground fault. The relay comply to BS 142 and IEC 255. Some useful features of the relay : User friendly Compact in size Earth Fault can be configured to be either IDMTL or DTL Earth Fault and Overcurrent setting is selectable to either 1.3/10 or 3/10 curve Wider ranges setting in smaller steps Recall past % phase trip from memory store in the relay Fully microprocessor controlled relay Built in surge arrester to absorb overvoltage/transient Mechanical trip reset button to guard against automatic reset before fault is identified High set setting available Auto and manual scrolling of reading display selectable

Layout
Display of %A (100%=/5A) indicator O/C & E/F indicator

Display of Setting indicator

Scroll mode indicator Test Button Display and Setting Selection Keys

Trip/Reset Button

SPECIFICATIONS
1. Model 2. Supply Voltage 3. Current Setting Overcurrent: Earth Fault: 4. Time Setting Range Overcurrent IDMTL: Earth Fault IDMTL: DTL: RSN200 AC230V 15% 50/60Hz (other voltages are available) 20- 120% (1% step), 120-200%(5% step) 2-50% (1% step) 0.09-3.0 sec at 10 times of setting current (3/10) 0.039-1.3 sec at 10 times of setting current (1.3/10) 0.09-3.0 sec at 10 times of setting current (3/10) 0.039-1.3 sec at 10 times of setting current (1.3/10) 0.1-2.0 sec (0.1 sec step)

5. High-set (Instantaneous protection) 6. Pick-up current 7. Reset Current Value 8. Tripping Relay 9. LED indication

2.0-10.0 times of setting current 100~105% of setting current (Setting Value of pick-up current) - 10% Mechanical hold type Relay Contact : 1c 250VAC, 5A (cos =1) Real time 3-digit display of individual phase Current with auto/manual scroll Digital display for setting parameters Trip current indication for individual phase R = Red colour, S = Yellow colour, T = Blue colour, E/F = Green colour Scroll = Red colour Auxilliary power supply = Green LED % (A) = Red colour, Check = Red colour

10. Life 11. Enclosure Standard DIN case: Protection structure : Material: Weight:

Electrical and Mechanical more than 10,000 operation DIN 96 x 96 x 108mm, (Panel cutout 910.8 x 910.8 mm) IP 30 ABS resin complying with UL94VO Relay: Approx. 500g

Characteristics
1. 2. 3. 4. 5. Ambient temperature Ambient humidity Voltage accuracy Repeat accuracy Time multiplier accuracy
Multiple of setting current Accuracy

-10 ~ +50C 45 ~ 85% RH <3% <3% <4% or 60m sec whichever is greater (10 times of setting current)
2 5 6% or 90m sec whichever is the greater 10 4% or 60m sec whichever is the greater 20 4% or 60m sec whichever is the greater

10% or 150m sec whichever is the greater

6. 7. 8. 9. 10.

Temperature accuracy Insulation resistance Withstand overcurrent Power consumption C.T. input consumption

11. Voltage withstand

<10% at 2020C >100M 20 times for 3 sec (100A for O/C, 20A for E/F) Approx. 3.5VA O/C Approx. 0.12VA at 5A E/F Approx. 0.02VA at 1A 2 KV for 1 minute between all case terminals connected together and the case earth terminal 1.5KV for a minute between independent circuit including contact circuit

IDMTL EARTH FAULT AND OVERCURRENT RELAY RSN200


Environmental Withstand
1. Impulse test 2. Temperature 3. Humidity 4. Vibration 5. Electromagnetic wave 6. Electrostatic discharge 5KV peak, 1.2/50 sec (0.5J) between all terminals and case, earth and between adjacent terminal IEC 68-2-1 / 68-2-2 Storage and transit - 25C to + 70C IEC 68-2-3 56 days @ 93% RH and + 40C IEC 255-21-1 0.5G between 10 Hz and 150 Hz Non-operation for radio frequency at 130-180MHz and 900-1000MHz (by Walkie talkie of 5W) IEC 61000-4-2 Air discharge method 8KV Contact discharge method 6 KV IEC 61000-4-4 2KV between power supply terminals
Scale Characteristics 1.3/10 Inverse
Multiplies of Current Time Multiplier (TM) 0.03 0.10 0.15 0.20 0.30 0.40 0.50 0.80 1.00 0.13 0.44 0.65 0.87 1.31 1.74 2.17 3.48 4.35 X2 X3 Standard Operating Time 0.08 0.27 0.41 0.55 0.82 1.10 1.37 2.19 2.73 0.05 0.19 0.28 0.37 0.56 0.74 0.93 1.48 1.86 X5

7. Electrical fast transient/burst

Scale Characteristics 3/10 Inverse


Multiplies of Current Time Multiplier (TM) 0.03 0.05 0.10 0.20 0.30 0.50 0.80 1.00
For other setting range, please refer to chart on back page

X2

X3 Standard Operating Time

X5

0.30 0.50 1.00 2.00 3.00 5.02 8.02 10.03

0.19 0.32 0.63 1.26 1.89 3.15 5.04 6.30

0.13 0.21 0.43 0.86 1.28 2.14 3.42 4.28

IDMTL EARTH FAULT AND OVERCURRENT RELAY RSN200


Characteristic as per IEC 255-3 and BS 142

TIME CURRENT CHARACTERISTIC

TIME CURRENT CHARACTERISTIC

100 1.3/10 Inverse

100 3.0/10 Inverse

10

10

OPERATING TIME (sec)

OPERATING TIME (sec)

t=1.00 t=0.70 t=0.50 t=0.40 t=0.30 t=0.20

t=1.00 t=0.70 t=0.50 t=0.40 t=0.30 t=0.20

t=0.10

0.1

t=0.10

0.1

t=0.05

t=0.03 t=0.05

t=0.03

inst.

inst.

0.01

10
MULTIPLES OF SETTING CURRENT

100

0.01

10
MULTIPLES OF SETTING CURRENT

100