Sie sind auf Seite 1von 12

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Automation Technology > Operator control and monitoring systems > HMI Software > SCADA system SIMATIC WinCC > SIMATIC WinCC > Tag Logging WinCC -- Configuring Tag Logging -- Configuring Archives How do you use the "Selected ID" property in the WinCC V7.0 control "WinCC User Archive"? How do you configure the size of Alarm Logging archives in SIMATIC WinCC? Why does SIMATIC WinCC save the backup files in the "Alternative destination path" even though a destination path is specified and the backup medium has sufficient memory space? Which license do the archive servers require? How are "Alarm Logging" and "Tag Logging" selected during client startup? What should you watch out for when doing a backup configuration in WinCC V6.0 and higher in combination with a redundant server pair? What is the meaning of the setting options "Time of the segment change" in the "Archive Configuration" dialog? How are backup files aligned in the target path and alternative target path?

How do you use the "Selected ID" property in the WinCC V7.0 control "WinCC User Archive"?

Introduction A new "WinCC UserArchiveControl" has been developed for WinCC version V7.0. Here, you can no longer select and define "Selected ID" as known from the old control under the option "Properties" > "Control Properties". Solution 1. As from WinCC V7.0 SP1, the "Selected ID" property is also included in the new "WinCC UserArchiveControl". You can download the Service Pack in Entry ID: 34896004. 2. You can continue to use the OCX of WinCC version V6.x under the designation "WinCC User Archive - Table Element (Classic)". For this, you add an element of the "Control" type from "Smart Objects" in the Object Palette. If OCX is not available for selection in the controls, you must register the OCX. For this, please proceed as instructed below. Registering the "WinCC User Archive - Table Element (Classic)" No. Procedure 1 Add/Remove "Control" Open the "Graphics Designer". Select the "Controls" tab in "Object Palette". Now right-click on the "ActiveX Controls" column and click on "Add/Remove..."

Fig. 01 2 "Register OCX..." Now click on the "Register OCX..." button.

1 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Fig. 02 3 OCX path Select the path for the OCX. The path is: X:\Program Files\ Common Files\Siemens \bin\CCUACtls.ocx.

Fig. 03 Acknowledge with "Open". "WinCC User Archive - Table Element (Classic)" is now registered. The OCX is selected automatically with the registration. Acknowledge the subsequent selection

2 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

with "OK". 4 OCX inserted in Controls Now you have inserted the OCX in the Object Palette. You can locate it by selecting "Controls" > "ActiveX Controls".

Fig. 04

How do you configure the size of Alarm Logging archives in SIMATIC WinCC?

Archive configuration As from SIMATIC WinCC V6.0, you can configure the size of your Alarm Logging archives. For this, there is the "Archive Configuration" entry in the Alarm Logging Editor via which you can make the settings for your archives. Procedure For WinCC V6.0 up to and including SP2 For WinCC V6.0 as from SP3 Procedure for WinCC V6.0 up to and including SP2 The archive types that you can configure in the "Properties" dialog are displayed as subitems. For this you right-click on an archive type and then in the pop-up menu you select the "Properties" item.

3 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Fig. 01 In this dialog, you can define the memory size of your long-term archive and the segment change times.

Fig. 02 In SIMATIC WinCC V6.0 onwards, you can export your Alarm Logging archives via the Backup Configuration. This dialog is also in the Properties of the long-term archive.

4 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Fig. 03 In the short-term archive, you can configure the number of messages to be reloaded and displayed in the short-term archive window after power failure.

Fig. 04 Note A detailed description of the configurations described above is available in the WinCC Online Help. Procedure for WinCC V6.0 as from SP3 For configuration, you right-click on the "Message archive" and then in the pop-up menu you select the "Properties" item.

5 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Fig. 05 In this dialog, you can define the memory size of your message archive and the segment change times.

Fig. 06 You can also export your Alarm Logging archives via the Backup Configuration. For this, you select the Backup Configuration tab.

6 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Fig. 07 To configure the number of messages to be displayed again in Runtime after a power failure, you right-click on "Message archive" and then in the pop-up menu you select the "Reload after power failure" item.

Fig. 08 Note A detailed description of the configurations described above is available in the WinCC Online Help. Why does SIMATIC WinCC save the backup files in the "Alternative destination path" even though a destination path is specified and the backup medium has sufficient memory space?

7 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Description: To execute the backup of both the Alarm Logging and the Tag Logging runtime data correctly, in WinCC you must specify an existing folder in the destination path. It is not enough just to state the drive name.

Fig. 1: Backup configuration Note: The folder for storing the backup files has to be created manually in advance, because WinCC cannot create it automatically. Which license do the archive servers require?

Configuration Notes: Different licenses are required for the different archive servers: Central archive server: WinCC RT 128 tags WinCC server license WinCC archive power pack (number of tags being archived, e.g. 30K, there are 512 archive tags in the basic license) Long-term archive server No WinCC license (WinCC isn't installed) The WinCC/Dat@Monitor or the WinCC/connectivity pack can be used to view the data. These licenses should be installed during use. File server:

8 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

No WinCC license How are "Alarm Logging" and "Tag Logging" selected during client startup?

Instructions: A client does not have its own alarm / tag-logging system. It is supplied with the data from the server - therefore, the entries for alarm / tag logging cannot be selected in the startup list either. In order to display the data from the server, the package only has to be generated under "Server Data" on the server. It contains the alarm / tag-logging information for the client and displays the data on the client.

What should you watch out for when doing a backup configuration in WinCC V6.0 and higher in combination with a redundant server pair?

Configuration Notes Automatic backup of the WinCC Runtime data is integrated in the standard WinCC as from WinCC V6.0. In the "Backup Configuration" tab you can make special settings in the archive configuration for the archives "TagLoggingFast", "TagLoggingSlow" and "Message archive". Click the "Help" button for a brief description of the setting options. You can define two paths, a "Destination path" and an "Alternative destination path", to which the archive segments of the archives "TagLoggingFast", "TagLoggingSlow" and "Message archive" are exported.

Fig. 01 The "Destination path" input field is for defining the path in which the archive backup files are to be stored. The "Alternative destination path" input field is for defining an alternative destination path. The "Alternative destination path" can be used if it is not possible to export to the regular destination path, for example, because there is not enough space on the backup medium or the network path is not available for the backup (network failure). Note: You should make sure that the destination path and the alternative destination path are not exclusively accessible via the network, because there is no data backup if there are network problems. If the alternative destination path is local and the "Backup on both paths" setting is disabled, then you only have to regularly move the alternative destination path to the destination path in the network. This ensures that there is always a data backup even if there are network problems. After duplicating or loading the WinCC project on the standby server, the archive configuration settings are then identical on the server and the standby server. You must not make any changes to the destination paths of the standby server. Depending on the version of WinCC V6.x, there are differences in the backup behavior with regard to the WinCC redundancy option.

9 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

No. WinCC version V6.x 1 Up to and including WinCC V6.0 SP2 The archive backup is made not only on the active server but also on the standby server. Both servers store their exported segments in the appropriately configured paths. There is no name conflict, because the name of the computer concerned (server name) prefixes the file name of the export segment in each case. As from WinCC V6.0 SP3 The archive backup is made only on the active server. No archive backup is made on the standby server. Important Only if the destination paths are identical on both servers will the data be complete in the backup directory concerned in each case. Note: If you are working with English as user interface language in WinCC, please note that the selection "signing off activated" is a translation error. It should read "signature activated". Fig. 01

What is the meaning of the setting options "Time of the segment change" in the "Archive Configuration" dialog?

Instructions You can set each cyclic storage separately (TagLoggingFast, TagLoggingSlow and AlarmArchive) with regard to size of the single elements and the size of all segments. Furthermore, you have the option of specifying when a segment is to be made. The following figure shows the mask for entering the archive configuration for the "TagLoggingFast" cyclic storage.

10 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

Figure 01 A description of the parameters to be set is given if you press the "Help" button in the Archive Configuration dialog. More information is available in the WinCC Online Help under: "WinCC Information System > Working with WinCC > Setting Up an Alarm System > Archiving Messages > Configuring Message Archiving > Configuring Message Archive" "WinCC Information System > Working with WinCC > Archiving Process Values > Configuration of Process Value Archiving > Configuring the Process Value Archive" "WinCC Information System > Working with WinCC > Archiving Process Values > Basics of Archiving Process Values > Swapping Out Process Values" This entry provides additional information on the meaning of the entries in the "Time of the segment change" group. Depending on the time base used for the "Time period covered by a single segment" inputs, not all of the default values of the "Time of the segment change" group effective. The only input values of the "Time of the segment change" group that are active at Runtime are those that cover a shorter period than the time base for the "Time period covered by a single segment" values. The table below helps to illustrate the interrelations. "Time period covered by a single segment" "Hour(s)" "Day(s)" "Week(s)" "Month(s)" "Year(s)" Examples If you specify the value "1 hour" for "Time period covered by a single segment", then only the "Minute" input field is active in the "Time of the segment change" group. Active inputs fields of the "Time of the segment change" group "Minute" "Hour", "Minute" "Weekday", "Hour", "Minute" "Day of the month", "Hour", "Minute" "Month", "Day of the month", "Hour", "Minute"

11 -> 12

08.04.2013 17:56

Siemens Industry Online Support - Automation Service, Automation Su...

https://support.automation.siemens.com/WW/llisapi.dll?func=ll&objId...

If you specify the value "8 hours" for "Time period covered by a single segment", then only the "Minute" input field is active in the "Time of the segment change" group. If you specify the value "1 month" for "Time period covered by a single segment", then only the "Day of the month", "Hour" and "Minute" input fields are active in the "Time of the segment change" group. Changes in the Archive Configuration dialog only become effective after the next segment change. More information on the topic of segment change is also available in Entry ID 22273427. How are backup files aligned in the target path and alternative target path?

Instructions: The target path and an alternative target path can be configured in the course of the backup configuration. If the target path is not available at the time of backup (export) (e.g. if the disk is full or the network drive is inaccessible), the data can be archived on an alternative target path. Once both paths are available again, WinCC doesn't automatically align the data in the target path and alternative target path. The corresponding archive backup files can be copied manually or by script to another path. Make sure that you transfer the two files belonging to an archive backup (*.LDF and *.MDF). Entry ID:29443389 Date:2011-03-07 My tags :
Siemens AG 2013 - Corporate Information - Privacy Policy - Terms of Use

Create new bookmark/tag

12 -> 12

08.04.2013 17:56

Das könnte Ihnen auch gefallen