Stop valves, type SVA-DL & SVA-DH 250 - 300

REFRIGERATION AND AIR CONDITIONING

Technical leaet

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

Contents

Page Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Material specication: SVA-DL 250 - 300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 SVA-DH 250 - 300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Dimensions and weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Code numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

RD7AS102

Danfoss A/S (RC-CMS / MWA), 05 - 2004

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250 - 300

Introduction

SVA-DL and SVA-DH are angleway stop valves designed to meet all industrial refrigeration application requirements. SVA-DL (Delta pressure Low) is designed with a restriction in the opening function. High dierential pressure can be applied from the side port and reduced pressure can be applied from bottom port. SVADL is a two-step valve for pressure relief. SVA-DH (Delta pressure High) is designed without restriction in the opening function. As a result of its balanced design this valve is able to open at all dierential pressures with limited torque. Features Applicable to all common refrigerants including R 717 and non corrosive gases/ liquids dependent on sealing material compatibility Optional accessories: - Heavy duty industrial handwheel for frequent operation - Vented cap for infrequent operation Available in angleway version with extended bonnet for insulated systems The valve caps can be wire-sealed, to prevent operation by unauthorised persons.

The angleway stop valves are carefully designed to give favourable ow conditions. Easy to dismantle for inspection and repair. Both SVA-DL & DH stop valves have internal backseating enabling the spindle seal to be replaced with the valve still under pressure. The valves are designed to give favourable ow characteristics and are easy to dismantle for servicing. The valve cone is designed to ensure perfect closing.

Internal PTFE backseating The bonnet is suitable for installation in insulated low temperature applications. The housing and bonnet are made from low temperature steel in accordance with the requirements of the Pressure Equipment Directive and other international classication authorities For an updated list of certications on the products please contact your local Danfoss Sales Company

Danfoss A/S (RC-CMS / MWA), 05 - 2004

RD7AS102

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

Design

Connections Available with the following connections: Butt-weld DIN 2448 Butt-weld ANSI B 36.10 - DN250: Schedule 40 - DN300: STD Housing and bonnet Made from special, cold-resistant steel approved for low temperature operations. Bolts Stainless steel, Quality A2-70 Valve cone assembly The valve cone assembly can be turned on the spindle, thus there is no friction between cone and seat when the valve is opened and closed. A Teon tightening ring provides perfect sealing at a minimum closing torque. Spindle Made of polished stainless steel, ideal for O-ring sealing. Packing gland The packing gland comprises a spring loaded seal packing which ensures perfect tightness in the range: 60/+150C (76/+302F). Furthermore, the packing glands incorporate a scraper ring to prevent the penetration of dirt and ice.
Pressure Equipment Directive (PED) SVA-DL and DH valves are approved and CE marked in accordance with the Pressure Equipment Directive - 97/23/EC. For further details / restrictions - see Installation Instruction.

Marking Each valve type is clearly marked with type, size and performance range.

Example of marking ring, SVA-DH

SVA-DL & DH valves Nominal bore Classied for Category III DN 250 mm (10 in.) Fluid group I IV DN 300 mm (12 in.)

RD7AS102

Danfoss A/S (RC-CMS / MWA), 05 - 2004

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250 - 300

Technical data

Refrigerants Applicable to all common non-ammable refrigerants including R 717 and non- corrosive gases/liquids dependent on sealing material compatibility. For further information please see installation instruction for SVA-DL and SVA-DH. Flammable hydrocarbons are not recommended. For further information please contact your local Danfoss Sales Company. Temperature range

SVA-DL and SVA-DH 60/+150C (76/+302F) Pressure range SVA-DL and SVA-DH 40 bar g (580 psi g) at 60C to +60C (76F to +140F) 36 bar g (522 psi g) at +60C to +80C (+140F to +176F) 32 bar g (464 psi g) at +80C to +120C (+176F to +248F) 28 bar g (406 psi g) at +120C to +150C (+248F to +302F)

Pressure/temperature range

Pressure [bar]

Temperature [C]

Danfoss A/S (RC-CMS / MWA), 05 - 2004

RD7AS102

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

Function

SVA-DL The SVA-DL stop valve is designed with a restriction in the ow direction (dierential pressure). To ensure the most favourable valve performance the ow must be directed from the side port towards the valve cone. Operation of the valve with ow in this direction is made possible by the two-step opening valve cone as illustrated below. The sketches below give the minimum pressures at which the the valve can be operated manually and tightness can be achieved.

SVA-DH The SVA-DH stop valve is designed without restrictions in either ow direction or dierential pressure. Due to the balanced valve cone design the torque required to operate the valve is minimized and the valve can be opened and closed against high pressure with ow in any direction.

Pressure
SVA-DL SVA-DH

Pmax = 40 bar

Pmax = 40 bar

SVA 250: Pmax = 9 bar SVA 300: Pmax = 6 bar

Pmax = 40 bar

Flow
SVA-DL SVA-DH

RD7AS102

Danfoss A/S (RC-CMS / MWA), 05 - 2004

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250 - 300

Material specication

SVA-DL 250 - 300

No. 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 27 28 29 30 31 33 34 35 36

Part Housing Bonnet (plate) Spindle Cone Set screw Balls Packing Gland O-ring U-sleeve sealing O-ring Bolts Gasket Handwheel Washer Lock nut Cap Gasket for cap Soft backseat Identication ring Wear ring Guide for spindle Gasket Front for valve cone Bolts Insert, valve cone Lifting eye bolts Backing for valve cone Gasket Wear ring Retaining ring

Material Steel Steel Steel Steel Steel Stainless steel Steel Cloroprene (Neoprene) Teon (PTFE) + Stainless steel Cloroprene (Neoprene) Stainless steel Fiber, Non-asbestos Steel Stainless steel Stainless steel+nylon Aluminium Nylon (PA 6) Teon (PTFE) Stainless steel Teon (PTFE) Spheroidal graphite cast iron Teon (PTFE) Steel Steel Spheroidal graphite cast iron Steel Steel Teon (PTFE) Teon (PTFE) Spring steel

EN G20Mn5 QT EN 10213-3 P275NL1 EN 10028-3 X5CrNi18-10 DIN 17440

ISO

ASTM LCC, A352

A2-70

A2-70

Type 308

Danfoss A/S (RC-CMS / MWA), 05 - 2004

RD7AS102

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

Material specication

SVA-DH 250 - 300

No. 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

Part Housing Bonnet (plate) Spindle Valve cone Tube for valve cone Set screw Balls Packing Gland O-ring U-sleeve sealing O-ring Bolts Gasket Handwheel Washer Lock nut Cap Gasket for cap Soft backseat Identication ring Wear ring Guide for spindle Bolts Spring washer U-sleeve sealing Wear ring Gasket Front for valve cone Bolts Insert, valve cone Lifting eye bolts

Material Steel Steel Steel Steel Stainless steel Steel Stainless steel Steel Cloroprene (Neoprene) Teon (PTFE) + Stainless steel Cloroprene (Neoprene) Stainless steel Fiber, Non-asbestos Steel Stainless steel Stainless steel+nylon Aluminium Nylon (PA 6) Teon (PTFE) Stainless steel Teon (PTFE) Spheroidal graphite cast iron Steel Steel Teon (PTFE) + Stainless steel Teon (PTFE) Teon (PTFE) Steel Steel Spheroidal graphite cast iron Steel

EN G20Mn5 QT EN 10213-3 P275NL1 EN 10028-3 X5CrNi18-10 DIN 17440

ISO

ASTM LCC, A352

A2-70

A2-70

Type 308

RD7AS102

Danfoss A/S (RC-CMS / MWA), 05 - 2004

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250 - 300

Connections DIN

Size mm

Size in.

OD mm

T mm

OD in.

T in.

Type

K v m 3/h

C v Usgal/min

Welding DIN (2448)


250 300 10 12 273 323.9 6.3 7.1 10.75 12.75 0.25 0.28 SVA-DH SVA-DL SVA-DH SVA-DL 1405 1610 1870 2082 1630 1868 2169 2415

ANSI

Size mm

Size in.

OD mm

T mm

OD in.

T in.

Type

K v m 3/h

C v Usgal/min

Welding ANSI (B 36.10)


250 300 10 12 273 323.9 6.3 7.1 10.75 12.75 0.25 0.28 SVA-DH SVA-DL SVA-DH SVA-DL 1405 1610 1870 2082 1630 1868 2169 2415

Dimensions and weights

SVA-DH, SVA-DL 250 -300, angleway version


With handwheel With vented cap

Valve size

K mm in. mm in. 102 4 102 4

max. 1 745 29.33 852 33.54

max. 2 782 30.79 842 33.14

G 210 8.27 240 9.45

H 334 13.14 384 15.12

Weight 130 kg 287 lb 190 kg 419 lb

SVA-DL / SVA-DH
SVA 250 SVA (10) SVA 300 SVA (12) 400 15.75 500 19.69 86 3.39 86 3.39

Specied weights are approximate values only

Danfoss A/S (RC-CMS / MWA), 05 - 2004

RD7AS102

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

Ordering

The table below can be used to identify the valve required. Please note that the type codes only serve to identify the valves, some of which may not form part of the standard product range. For further information please contact your local Danfoss Sales Company. Type codes
Valve type Nominal size in mm SVA-DL SVA-DH Stop valve Stop valve (p Low) (p High) Available connections D (Valve size measured on the connection diameter) Connections 250 300 D A Other euipment CAP H-WHEEL DN250 DN300 X X A X X

Butt weld connection: DIN 2448


Butt weld connections: ANSI B 36.10 DN250: Schedule 40 DN300: STD Aluminum cap Steel handweel

Important! Where products need to be certied according to specic certication societies or where higher pressures are required, the relevant information should be included at the time of ordering. Code numbers
mm 250 250 250 250 250 250 250 250 300 300 300 Size in. 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12 SVA-DL 250 D CAP SVA-DL 250 D H-HEEL SVA-DL 250 A CAP SVA-DL 250 A H-WHEEL SVA-DH 250 D CAP SVA-DH 250 D H-WHEEL SVA-DH 250 A CAP SVA-DH 250 A H-WHEEL SVA-DL 300 D CAP SVA-DL 300 D H-WHEEL SVA-DL 300 A CAP SVA-DL 300 A H-WHEEL SVA-DH 300 D CAP SVA-DH 300 D H-WHEEL SVA-DH 300 A CAP SVA-DH 300 A H-WHEEL 148B3760 148B3761 148B3762 148B3763 148B3764 148B3765 148B3766 148B3767 148B3770 148B3771 148B3772 148B3773 148B3774 148B3775 148B3776 148B3777 Type Code number

A = D=

ANSI butt-weld DIN butt-weld

300 300 300 300 300

H-WHEEL: Handwheel CAP: Vented cap

10

RD7AS102

Danfoss A/S (RC-CMS / MWA), 05 - 2004

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250 - 300

Danfoss A/S (RC-CMS / MWA), 05 - 2004

RD7AS102

11

Technical leaet

Stop valves, type SVA-DL & SVA-DH 250-300

12

RD7AS102