Sie sind auf Seite 1von 67

HARYANA POWER GENERATION CORPORATION PANCHKULA, HARYANA DESEIN PRIVATE LIMITED CONSULTING ENGINEER NEW DELHI

CENTRAL ELECTRICITY AUTHORITY SEWA BHAWAN, R K PURAM, NEW DELHI DCR Thermal Power Project (2 x 300 MW), Yamunanagar DESIGN BASIS REPORT FOR BTG ELECTRICAL SYSTEM
DOCUMENT NO. 50-F248C-D01-01

RELIANCE ENERGY LIMITED REL TOWER, A-2, SECTOR-24 NOIDA (U.P) 201301
DEVELOPMENT CONSULTANTS PRIVATE LIMITED CONSULTING ENGINEERS
24B PARK STREET, KOLKATA - 700 016, INDIA

SHANGHAI ELECTRIC (GROUP) CORPORATION (SEC)


3669 jindu Road,shanghai,China

SOUTHWEST ELECTRIC POWER DESIGN INSTITUTE


18 dongfeng Road,chengdu,China

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

DOCUMENT CONTROL SHEET


PROJECT : DCR THERMAL POWER PROJECT 2 X 300 MW UNITS HARYANA POWER GENERATION CORPORATION DESIGN BASIS REPORT FOR BTG ELECTRICAL SYSTEM 50-F248C-D01-01 1

CLIENT

DOCUMENT TITLE :

DOCUMENT NO. REV. NO.

: :

ENDORSEMENTS

30.12.05

Revised as per MOM with HPGC dt. 05-08 Dec-05 FIRST ISSUE LXL / GJ
PREP. BY SIGN.(INITIAL)

01.04.05

LGR
REVW. BY SIGN.(INITIAL)

ZJ / RJC
APPD BY SIGN.(INITIAL)

REV. NO.

DATE

DESCRIPTION

SOUTHWEST ELECTRIC POWER DESIGN INSTITUTE


18 dongfeng Road,chengdu,China
DOCUMENT NO.: 50-F248C-D01-01 Page 1

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

CONTENTS
CLAUSE NO. DESCRIPTION PAGE No

1 General....................................................................................... 1 1.1 Intent of Design Basic Report................................................. 1 1.2 Scope of Design ...................................................................... 1 1.3 Design Philosophy................................................................... 1 2 Design criteria of equipment and system ................................... 3 2.1 Generator system .................................................................... 3 2.2 Generator surge protection system ....................................... 21 2.3 Generator neutral grounding system ..................................... 22 2.4 Generator Metering ............................................................... 23 2.5 Synchronization ..................................................................... 24 3 Equipment description .............................................................. 24 3.1 Generator system .................................................................. 24 3.2 Generator surge protection system ....................................... 26 3.3 Generator neutral grounding system ..................................... 27 3.4 Excitation system .................................................................. 28 3.5 Generator Protection Relay ................................................... 30 3.6 Generator metering panel ..................................................... 33 3.7 Generator fault recorder panel .............................................. 33 4 Generator control & operation philosophy Records.................. 34 5 Main Equipments list ................................................................ 34

DOCUMENT NO.: 50-F248C-D01-01

Page 2

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

DRAWINGS 50-F248C-D01-02 50-F248C-D01-03 ANNEXURE ANNEXURE I

DESCRIPTION Single line diagram for generator protection & metering Generator Protection Action List

Sizing calculation for generator neutral grounding system ANNEXURE II Date sheet for generator ANNEXURE III Generator capability curve ANNEXURE IV ANNEXURE V Generator saturation curve ANNEXURE VI Generator vee curve ANNEXURE VII Exciter characteristic curve
1 1 1 Generator overfluxing capability curve 1 1

DOCUMENT NO.: 50-F248C-D01-01

Page 3

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

1 General 1.1 Intent of Design Basic Report In this design basis report, the design criteria and principle of electrical system and equipment in SEC scope, the equipment main parameters, control & operation philosophy, metering & protection are described. 1.2 Scope of Design The design scope of electrical part includes the followings: the generator control and protection system, generator surge protection and neutral grounding system,. 1.3 Design Philosophy 1.3.1 Code & Standard Electrical equipment and system will be designed, constructed, tested and installed in accordance with the latest editions of IEC codes. Generator will be as per IEC-34 and their latest amendments, whenever applicable. IE rule shall be complied for statutory requirement, CBIP guidelines shall be kept in view for good engineering practice.
1

1.3.2 Environmental condition The equipment shall be capable of continuous full load operation under the following conditions:

DOCUMENT NO.: 50-F248C-D01-01

Page 1

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Average Grade Level Design Ambient Air Temperature Wind Pressure Highest Average monthly relative humidity Annual average relative humidity Seismic Zone (As per relevant IS)

270.0Meter (above MSL) (+) 50 (Max.) (-) 0.6 (Min.) 150kg/m2 84% 68% (Max.) 48% (Min.) IV

1.3.3 Voltage Levels Following voltage levels will be adopted for power station auxiliaries.
Energy network apparatus AC motors rated above 175 kW AC motors rated up to and including 175 kW, power receptacles and three phase AC loads DC Motors Control, indication & protection circuits for HT/LT circuit breakers and emergency lighting Control & indication for contactor operated 415 V motors Space heater(no more than 1.2kW) for motors and cubicles Space heater(more than 1.2kW) for motors Interior lighting, receptacles and general power 220 V +10% to -15% 220 V +10% to -15% 110V10% 240V10% 415V10% 240V10% 2 wire DC 25KA Unearthed 415V10% 3Ph, 50 Hz. (+)/(-) 5% 50KA for 1 Sec Effectively earthed Voltage 6600V10% No. of phases & frequency 3Ph, 50 Hz. (+)/(-) 5% Fault Level 40KA for 1 Sec Grounding Non-effectively earthed

2 wire DC 1Ph50 Hz, (+)/(-) 5% 1Ph50 Hz, (+)/(-) 5% 3Ph,50 Hz, (+)/(-) 5% 3Ph50 Hz, (+)/(-) 5%

25KA 50KA for 1 Sec 50KA for 1 Sec 50KA for 1 Sec 50KA for 1 Sec

Unearthed Effectively earthed Effectively earthed Effectively earthed Effectively earthed Page 2

DOCUMENT NO.: 50-F248C-D01-01

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

2 Design criteria of equipment and system 2.1 Generator system 2.1.1 General description of generator Two 300 MW generators with stator winding inner water cooled, core and rotor winding hydrogen cooled, are separately connected to 220kV switchgear via generator-transformer. The output under VWO condition of generator is 315 MW and the generator have a short circuit ratio of 0.6 15 % tolerance as per IEC-34 with an inertia constant of generator and exciter of 1.14(kWs/kVA). Generator rated terminal voltage is 20kV. The generator is capable of continuous operation at rated output within frequency range of 47.5 Hz to 51.5 Hz and voltage range of 0. 95 p.u to 1.05 p.u. and is capable of withstanding three-phase, phase-to-phase-to-ground, phase-to-phase, and phase-to-ground faults, both internal and external, without damage before the unit shut down by protection. The generator is provided with class F insulation with temperature rise limited to class B insulation limits. The generator enclosure is provided IP54 degree of protection and the noise level shall not exceed 90 dB at a height of 1.5 meters above the floor level in elevation and at a distance of 1 meter horizontally from the nearest surface of generator.
1 1

2.1.2 Design description of generator

The generator supplied was designed and manufactured under the license of Westinghouse Electrical Corp.(WEC) in accordance with ANSI C50.10, ANSI C50.13, IEC34-1 and IEC34-3. It is an updated hydrogen and water inner cooled generator, joint - developed by Shanghai Electrical Machinery Manufacturing Works (SEMMW) (now STGC) and Westinghouse Electric Corp. (WEC). 2.1.2.1Generator ventilation and cooling system
DOCUMENT NO.: 50-F248C-D01-01 Page 3

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

The ventilation system provides uniform cooling of the entire generator frame using hydrogen as the cooling medium. This time-proven system, supplied on large steam turbine-driven generators for decades, permits a generator to be designed for optimum physical size and electrical capacity. Hydrogen gas circulates in a closed circuit inside the generator by two singlestage axial blowers, mounted on both ends of the rotor. The blowers are located immediately ahead of the coolers so that the gas temperature rise due to the blower losses will not be added to the total temperature rises of the electrical components. All generator components, rotor winding, stator core, end region flux shield structures and lead box, except the stator winding, are hydrogen cooled. The hydrogen is cooled by the hydrogen-to-water coolers located vertically at both ends of the generator. Cold gas from the coolers flows in two symmetrical paths, with the exception that there is gas flow in the lead box on the exciter end. The stator core and rotor winding are cooled by separate but parallel flow circuits. The air gap serves as a plenum to return the gas back to the axial blower. For the rotor, the cold gas is admitted at each end of the rotor through the annular space under the rotor winding retaining rings. The most part of the flow enters the main rotor body sub-slots machined underneath each rotor winding slot. From these sub-slots the gas flows into the radial vent ducts on rotor winding and discharges into the air gap through holes in the rotor wedges. A fraction of gas flow is diverted to cool the rotor end turn, This flow is divided into two paths, the straight and the arc path. For the straight path, it flows axially towards the main rotor body and discharges through radial ducts into the air gap. The arc portion of the end turns are cooled by hydrogen flowing circumferentially towards the pole centerline and discharging into the air gap through scooped passages at the end of the rotor body.
1

The stator core is radially ventilated. The cooling gas is forced to the
DOCUMENT NO.: 50-F248C-D01-01 Page 4

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

space between the core and the generator frame by the axial blowers on both ends. From this space it flows radially inwards through radial vents and towards the air gap. The stator coils, parallel rings, main leads and terminal bushings are cooled directly with de - ionized water. Cooling water flows from main inlet pipe into the inlet water manifold, then enters the teflon hose of each coil bar at exciter end, passes through the whole length of the hollow conductors in coils and the teflon hoses at the other ends, then exits to the water outlet manifold at the turbine end where it picks up the drain water from the phase leads and terminal bushings and returns to the water tank. Hot water is cooled by water coolers before pumped back to the stator winding. 2.1.2.2 Frame The generator is of an integral frame construction, reducing erection expenses and giving protection to the internal components during transportation and erection. It may be splitted into 3 sections for shipment in order to reduce the maximum weight and dimensions for transportation in conformity with those specified by customers, and is then site - assembled to be an integral piece, having a good gas-tight frame and maximum protection to the internal components. The generator frame is a heavily ribbed cylinder which supports the stator core and windings, bearing brackets, and rotor assembly. The frame and the enclosing bearing brackets are fabricated from steel plates.
1

The generator frame is designed to be explosion-safe. This means that the frame will contain and withstand an internal explosion of the most explosive mixture of hydrogen and air at the most probable conditions of occurrence, i.e., at atmospheric pressures during gas changing operations, without damage to life or property external to the machine. Some internal
DOCUMENT NO.: 50-F248C-D01-01 Page 5

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

damage may occur with such an explosion. Four hydrogen coolers each of which has two sections are mounted vertically at each corner of the generator frame. The generator frame is supported by frame feet along its length on foundation seating plates. Foundation bolts resist short-circuit torques applied to the frame. Shims between frame feet and seating plates are provided for generator alignment with respect to the steam turbine generator shaft system. A number of jack screws are also provided in the generator frame feet for vertical alignment. Axial anchors for the frame feet and also for the seating plates allow for thermal expansion of the generator in both axial directions from the centerline of the generator. Transverse anchors engage the bearing brackets on each end of the generator to maintain the generator lateral position while allowing the axial expansion. 2.1.2.3 Stator core design The stator core is composed of high permeability, low loss silicon steel laminations coated on both side with an effective class F varnish. The laminations are aligned and held together by dovetail key bars at the outside diameter which also serve as tension members to clamp the core axially by means of cast austenitic steel end plates. The end plates are sufficiently rigid to apply pressure evenly over the core cross section when loaded by the key bars at the outside diameter. The end plates are non - magnetic and with sufficient yield strength. The key bars are attached to the spring beams. The core is thus attached to the frame via the spring beams which reduce the amplitude of the double frequency core vibratory force transmitted to the generator frame and foundation. The mounting is such that very little of the core vibratory force is transmitted to the housing, but the core is rigidly restrained against load and short circuit torques.
1

The stator core is tested for integrity during the manufacturing operation
DOCUMENT NO.: 50-F248C-D01-01 Page 6

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

using a "loop testing" procedure. This procedure which simulates actual operation consists of circulating rated magnetic flux through the core laminations and inspecting the core for local hot spots by using a thermal vision camera capable of detecting small temperature differences. Any local hot spots, which are indications of deterioration in progress, are to be repaired. The lack of core problems in SEMMW (now STGC) generators is attributed to attention to core design and testing for core integrity as described above. At the bore diameter equally spaced slots run the entire length of the stator core. These slots extend into the core for assembly of the stator coils. A copper end-shield with a laminated magnetic shield protects the end plate and the core tooth area from end region flux. 2.1.2.4 Stator winding design 1. Water cooled stator coils The stator winding consists of water inner-cooled, single turn, half coils wound in open slots and secured in place by glass-epoxy wedges. Each stator coil is made up of two half coils shaped on a former and joined together after assembly in the slots. The stator coils of this generator are composed of insulated solid copper strands and insulated hollow copper conductors. Each strand and hollow conductor is wrapped with an electrical grade continuous filament type epoxy resin glass fiber to form a smooth continuous uniform insulation at all points. The strands together with hollow conductors undergo 540Robel transposition in the slot portion of the coil.. This glass covering is then treated to give a smooth surface finish which is tough and flexible and will withstand abrasion from each other in the coil of the stator winding during operation.
1

Effective cooling of the stator coils is achieved by the cold deionized water. The water flows from the inlet manifold at the exciter end of generator into the coil ends thru teflon insulating hoses, then discharges from the stator
DOCUMENT NO.: 50-F248C-D01-01 Page 7

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

coil at other end, where it is collected by teflon insulating hoses on a discharge manifold. The parallel rings and lead terminals are composed of insulated hollow copper conductors for direct water cooling. All six terminals of the three phase winding are brought out at the exciter end of the lead box beneath the floor level through gas tight porcelain bushings. Resistance temperature detectors are provided to measure the temperature of the stator coils and their hot water discharge and to detect any abnormal conditions. Leads from the temperature detectors are connected to terminal boards. 2. Stator Coil Insulation
1

Epoxy-Mica insulation is used to provide the ground wall insulation on the stator coil. To give good dielectric and mechanical strength, the ground insulation is continuously wound with several layers of epoxy resin micapaper tape then cured at high pressure and temperature in the former. Epoxy-Mica insulation is a tough, yet thermally flexible dielectric barrier with excellent electrical and physical properties. The excellent dielectrical properties of the resin, coupled with good insulation consolidation, results in Epoxy-Mica with lower dielectric loss tan , increased dielectric strength, and remarkable improvement of voltage endurance. Its consistently low dielectric loss is less affected by temperature and voltage variation than other types of insulation. Epoxy-Mica insulation has great thermal endurance and long life. The character of the resin provides solid, yet elastic physical bonds between mica papers. The resilient nature of the resinbond permits elastic cyclic displacement of adjacent mica papers and provides restoring force within the insulation ground-wall. This makes Epoxy-Mica insulation ideally suitable for cyclic duty operation. The insulation is also inert to ordinary chemicals, oils, and solvents and has an unusually high moisture resistance. Continued improvements have made Epoxy-Mica insulation a superior insulation for high-voltage coils, satisfying the requirement of class F insulation.
DOCUMENT NO.: 50-F248C-D01-01 Page 8

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Effective corona suppression is provided by the use of a low-resistance, conducting varnish on the coil slot section to contain the dielectric stress within the solid insulation and a combine process of a low resistance conducting varnish and a high-resistance, semi-conducting varnish in the endturns to grade voltage stress along the coil surface. Quality Assurance checks are performed on each coil and the complete winding to verify insulation integrity. Each coil is given a high-potential test well in excess of final winding high-potential test values before being wound into the machine. Each set of coils includes extras which are chosen at random from the set for testing to destruction, thus giving further verification of insulation integrity. Additional high-potential tests are performed both during and after completion of the stator winding. 3 . Stator Winding Bracing Of equal importance with the insulation system is the method of slot-fill and bracing used to protect the stator coils from the vibratory stresses experienced during steady-state operation and from the transient disturbances which can be experienced during abnormal operating conditions. The ANSI and IEC Standards set the requirements for steady-state operation and define the abnormal operating conditions which must be met. Each coil is secured in the slot by a glass-epoxy wedge assembled in wedge grooves in the slot. Epoxy impregnated conforming materials are placed under the bottom coil and between the bottom and the top coils to suit the coil in slot. The tightness is maintained by the prestressed driving strip (PSDS or ripple spring)-- a wave glass fiber epoxy strip-- directly below the slot wedge, maintaining radial pressure on coils and slot wedges. distribute the load of the PSDS. Flat filler strips are also utilized on one side of the coil to provide a tight fit
DOCUMENT NO.: 50-F248C-D01-01 Page 9

Flat glass-epoxy filler strips are assembled above the coils in the slots to

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

in the slot. These supporting members virtually eliminate potentially damaging coil vibration caused by the electromagnetic forces that are present. The entire stator is thermally cured under pressure to consolidate slot contents and reduce vibratory stresses due to coil motion. The consolidation of ground wall and filler materials and the use of ripple spring between coils and wedges gives unsurpassed slot compactness for long service life. The radial winding clamp composed of high-strength glass epoxy clamping plates and non-magnetic bolts together with support rings and bracing brackets provides radial, structural consolidation of the end winding. The radial clamps provide clamping forces well in excess of the vibratory forces between the top and bottom coils. This reduces vibration of the individual coils relative to the strain blocks used between top and bottom coils, as well as to the diamond spacer assemblies used between adjacent coils. This reduced radial vibration will prevent relative motion and wear between the coils and the strain blocks. Clamping plates and non-magnetic bolts secure the coils to the bracing brackets. De-coupled end winding support bracing consist of bracing brackets, teflon slip layers and spring structure through which the bracing brackets attach to the core end plates so as to de-couple the end windings from the core and to improve the end winding to radial brace attachment. The brace provides for dynamic isolation between the coils and core to permit detuning of the end winding natural frequency well below 100 Hz, the exciting frequency.
1

There are Fluoroelastomer rubber layers with good physical and dielectric properties placed between the insulating clamp plates and coils for protecting coil from wear of insulation, as well as for damping coil vibration. This end-winding bracing system has effectively controlled the forces which result from both steady and short circuit conditions and also allows axial motion for thermal expansion as proved by long operation practice.
DOCUMENT NO.: 50-F248C-D01-01 Page 10

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

This bracing design is found in the fact that, by isolating the stiffness of the core from the end winding support, the end winding dynamics can be favorably changed. 4 Main leads Stator parallel rings, phase leads and main lead bushings are directly cooled by the water. The main lead bushings are assembled in a gas-tight main lead box located underneath the frame at the exciter end. Bushings can be replaced without removing the generator rotor. The six main lead bushings extend from the lead box, three of which are used for the main leads connecting to the main transformer and three of which are used to form the neutral tie. Each bushing can be provided with up to four bushing mounted current transformers. Current transformers are suitable for metering, relaying, or voltage regulator service. The current transformers have a secondary current level of five amperes. 2.1.2.5. Generator rotor
1

The cylindrical type rotor forging is made from chromium, nickel, molybdenum, vanadium alloy steel and is poured with the vacuum degassing process. Forging materials are ultrasonically tested for compliance with rigid quality assurance specifications. A bore hole is provided to remove centerline indications. The bore hole may then be used in later years for examination of forging integrity. Two pole rotors have their pole faces slotted so as to equalize flexibility and to reduce double-frequency vibration. Rotor winding components are subjected to stresses both from rotation and from thermal expansion and contraction. It is essential that these stresses be accounted for and limited in the rotor design. During startups, shutdowns, and load changes the rotor winding will move relative to the rotor structural parts. Built-in clearances and slip layers allow for this motion while reducing the frictional forces which could cause distress or shaft vibration. Hard-drawn,
DOCUMENT NO.: 50-F248C-D01-01 Page 11

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

creep resistant, silver-bearing copper and glass-laminate turn-to-turn insulation reduces the chance of permanent winding deformation or shorted rotor turns. The winding is held firmly against rotational forces by nonmagnetic retaining rings and high-strength rotor slot wedges. In the rotor end turn area, customarily fitted glass epoxy blocking and spacers maintain alignment of the winding components. The end winding curved sections potentially high stress areas are arranged with brazed connections located well away from the curves. Axial expansion is controlled by allowing for expansion to occur and by including teflon slip layers in the rotor slots and under the retaining ring, to limit the friction that opposes axial motion. The field winding is manufactured from high-strength alloy copper. This silver-bearing alloy copper contains the necessary metallurgical creepresistant properties to minimize distortion during operation. The individual turns of the rotor winding are made up of two conductors. On the end turns each consisting of two copper channel sections, which form a gas passage for the hydrogen. For turns inside slots, there are two parallel rows of slim vent ducts evenly distributed along the winding slots to form radial vent holes over the sub-slots. The field winding insulation is provided with extra creepage distance on the top turns. The windings are placed in rectangular slots which are lined with one piece, molded insulating slot cells. The slot cells are teflon lined on the inner surface to permit the rotor copper to move axially due to thermal expansion and contraction. The insulation between turns consists of glass laminate bonded to the copper. The glass laminate exhibits excellent wear characteristics and has a high coefficient of friction, which reduces relative slippage between coil turns that causes wear and copper dusting. Instead, the entire coil slot structure acts as a unit rather than individual turns. After the rotor is pressed and cured, fitted, high-strength slot wedges are driven into the top of the slots.
1

The rotor end turns are supported radially against rotational forces by
DOCUMENT NO.: 50-F248C-D01-01 Page 12

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

18Mn18Cr nonmagnetic retaining rings shrunk onto the rotor body. This alloy is highly resistant to corrosion and stress corrosion cracking in the presence of moisture and other corrodents. These retaining rings are nonmagnetic steel forgings. These floating-type retaining rings, with teflon surfaced insulating liners, prevent distortion of the rotor copper and abrasion of the rotor coil insulation. The rings are shrunk and keyed onto machined sections at the ends of the rotor body with a firm fit at overspeed and rated temperature. The heavy shrink fit provides a low-resistance electrical path for induced rotor surface currents, thereby reducing heating due to rotor surface currents. A circumferential locking ring is provided to prevent axial movement of the retaining ring. This method of support permits the shaft to flex without causing fretting at the joint or overstressing the rotor winding and is used to eliminate the effect of shaft deflection on the rotor end winding assembly.
1

An amortisseur winding is provided which uses copper damper bars in each rotor slot connected at the ends by beryllium copper wedges to the retaining rings. This design meets the requirements of the industry standards for negative-phase-sequence current capability. This machine has two single stage blowers, mounted on the rotor shaft at both ends. The outside diameter of the blower blades is smaller than that of the retaining ring. The blower hub outside diameter is designed to be small enough to allow removal of the retaining ring over it, if necessary, for winding inspection. After unshrunk from the retaining ring, the end plate can be slided ver the spacer ring and attached to the blower hub during repairing. The completed rotor is dynamically balanced. It is carefully baked and seasoned at running speed to promote lasting stability of the rotor winding components. Standard equality control tests are made on every rotor before and after over-speed tests to verify that no shorted rotor turns have developed. It is performed by means of a continuous impedance test as the rotor speed is increased from rest up to rated speed and back to rest. The rotor is then
DOCUMENT NO.: 50-F248C-D01-01 Page 13

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

carefully inspected and a final high-potential test is performed. 2.1.2.6 Bracing gland seal and bearing brackets The bearings, supported in rugged fabricated bearing brackets, are insulated and may be removed without removing the hydrogen seals from the machine. Bearing and gland seal insulation is provided at the following places on both ends of the generator to prevent shaft currents from flowing through the bearings: between the bearing pad and the bearing seat; between the gland seals and the brackets; between the bearing oil seals and the brackets; and at the stop dowel and bearing key. In addition, the pieces on the exciter end are "double insulated" with terminals for checking the insulation resistance of the bearing and gland seal insulation during operation. Only the exciter end bearing is "double insulated". Since the combination of insulation and the shaft grounding brushes, which are located on the turning gear pedestal, is considered satisfactory for preventing bearing currents in the turbine end bearing of the generator. The ring type gland seals are also housed in the bearing brackets to maintain a gas-tight shaft seal. The shaft seals are of double oil flow construction with separate air and hydrogen side oil supplies to reduce hydrogen consumption. Vibration detector probes are provided at each bearing. The bearings are forced lubricated and visual oil flow gauges are supplied in the bearing bracket oil piping. 2.1.2.7Lubricating supply system The generator shares a common lubrication system with the turbine. Fewer subsystems mean less complexity and reduced installation costs. 2.1.2.8Seal oil system
1

The function of the seal oil system is to lubricate the seals and prevent hydrogen escaping from the generator, without introducing air and moisture
DOCUMENT NO.: 50-F248C-D01-01 Page 14

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

into the generator. The same oil is used in the turbine and generator bearing lubrication oil system and the gland seal oil system. Under normal operating conditions the seal oil is completely separated from the lubrication oil. Independent seal oil systems for air-side and gas-side oil eliminate the need for an oil vacuum treating unit and reduce hydrogen consumption by preventing the air-side oil which contains moisture from contacting the hydrogen gas in the generator. Part of the reliability of the system is the back-ups provided. Emergency seal oil back-up pumps, interconnected with the lubrication oil system, automatically provide continuous operation of the seal oil supply in the event that the main air side oil fails. 2.1.2.9 Hydrogen gas system Hydrogen pressure is maintained at the design pressure by a pressure regulator located in the hydrogen system. Continuous circulation of the hydrogen is maintained by the shaft-mounted axial blowers. The hydrogen gas system is designed for the following functions: To provide means of safely putting hydrogen in and taking hydrogen out of the generator, using carbon dioxide as a scavenging medium. To maintain the gas pressure in the generator at the desired level. To continuously monitor the condition of the machine with regard to gas pressure, temperature, and purity, and to provide alarm signals in the event of abnormal conditions in the gas system. The pressence of liquid in the machine is also indicated by an alarm. To dry the gas and remove any water vapor which might get into the machine from the seal oil system or other sources. To provide control to secure the system in the event of an abnormal condition. Gas dryer A gas dryer is connected across the generator fan so that gas is
DOCUMENT NO.: 50-F248C-D01-01 Page 15

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

circulated thru the dryer whenever the machine is running. Liquid detectors Float operated switches in small housings are provided under the generator frame and under the main lead box to indicate the presence of any liquid in the generator which might be due to leakage or condensation from the cooler. Openings are provided in each frame ring at the bottom of the frame so that any liquid collected will drain to these water detectors. Each detector is provided with a vent return line to the generator frame so that the drain line from the generator frame will not become air bound. Isolating valves are provided in both the vent and drain lines so that the switches can be inspected at anytime, and a drain valve is provided for the removal of any accumulated liquid. Hydrogen purity monitoring equipment The purity of the gas in the generator is determined by the use of the purity blower, the hydrogen purity electronic differential pressure transmitter, the hydrogen pressure electronic transmitter, and the hydrogen gas instrumentation package. An induction motor, loaded very lightly so as to run at practically constant speed, drives the purity blower and circulates the gas drawn from the generator housing. Thus, the pressure developed by the purity blower varies directly with the density of the sampled gas. The hydrogen purity differential pressure transmitter measures the pressure developed by the purity blower. Gas density is dependent upon the ambient pressure and temperature as well as the purity.
1

The hydrogen monitoring system combines the purity blower differential pressure and the machine gas pressure signals to provide a compensated density signal, which is a true reading of machine gas purity. The purity indicator scale is divided into three sections. Near the center of
DOCUMENT NO.: 50-F248C-D01-01 Page 16

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

the scale is a point marked "100% Air". This point provides a means of calibrating the indicator without removing the gas from the generator. The upper end of the dial consists of a scale showing the percentage of carbon dioxide present in a mixture of carbon dioxide and air. This portion of the scale is used during scavenging operation when carbon dioxide is being introduced into the generator. The lower end of the dial consists of a scale indicating the percentage of hydrogen present in a mixture of hydrogen and air. It is this portion of the scale which is used during normal opration of the machine to determine the purity of the hydrogen in the generator housing. The hydrogen purity signal, an electrical output signal, may be carried to a remotely located receiver provided with a dial similar to the purity indicator on the generator auxiliaries control enclosure. Two switch assemblies are provided with the hydrogen monitoring system which are set to produce a "hydrogen purity high or low" alarm when the purity signal falls below exceeds predetermined limits. Generator fan differential pressure monitoring equipment An electronic differential pressure transmitter is connected directly to the generator housing and senses the pressure developed by the fan mounted on the generator rotor. The hydrogen monitoring system transmits the generator fan differential pressure signal to an indicator in the generator auxiliaries control enclosure. This pressure can be used as a check on the purity indicator or can be used to indicate the hydrogen purity if the purity indicator is taken out of service while the generator is running. Hydrogen pressure monitoring equipment
1

The electronic hydrogen pressure transmitter is connected directly to generator housing an senses the pressure within the generator. The transmitted pressure signal is used by the hydrogen monitoring system, not
DOCUMENT NO.: 50-F248C-D01-01 Page 17

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

only to compensate the density for purity as mentioned above, but also to supply the electrical signals for the following: The hydrogen pressure indicator in the generator auxiliaries control enclosure. A remotely located indicator with dial similar to the previous indicator High and low pressure alarm switches located in the generator auxiliaries control enclosure. The high and low pressure alarm switches provide an indication when the gas pressure in the machine exceeds or goes below predetermined limits. Hydrogen temperature alarm A hydrogen cold gas thermostat is located in the generator to provide a source of alarm in case the temperature of the hydrogen in the generator becomes excessive. Supply pressure switch and gauges
1

All generators are equipped with a hydrogen pressure control, which has a supply pressure switch and two pressure gauges. The top gauge indicated the machine gas pressure and also the setting of the regulator on the hydrogen pressure control. The bottom gauge gives an indication of the amount of pressure available from the hydrogen supply system. A pressure switch is located on the supply side of the hydrogen pressure control manifold and gives and alarm when the supply pressure is low. A drop in pressure at this point would mean that the available pressure from the hydrogen supply was to low, or that the regulators in the hydrogen supply are set at too low a pressure. 2.1.2.10. Stator coil water system The stator coil water system is a closed loop system having the following
DOCUMENT NO.: 50-F248C-D01-01 Page 18

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

features: -Circulation of high purity water thru the stator coil hollow conductors for removal of heat due to the stator coil losses. -Dissipation of heat from the high purity water. -Filtering of water to remove foreign material. -Demineralization of the water to control its electrical conductivity. -Instrumentation and alarms to continuously monitor and advise conditions of conductivity, flow, pressure, and temperature of water. -All piping and components are made of corrosion resistant materials. Cold water is piped thru the generator shell into a circumferential manifold in the exciter end of the generator. The cold water inlet piping is e quipped with a temperature detector for temperature monitoring and a thermostat for alarm purposes. An inline strainer is installed for startup to prevent admission of dirt into the hollow stator conductors. Inside the generator, water flows from the inlet manifold into the coil ends thru teflon insulating tubes. Water discharging from the stator coil at the other end, is collected by teflon hoses and a discharge manifold, and then returns to the water tank. The two inlet and discharge manifolds are interconnected at the high point with a vent line which also serves as an anti-siphoning line. This vent is continued to the water tank. The two manifolds are connected to a differential pressure gauge to indicate pressure drop across the stator coils. They are also connected to differential pressure switches for alarms for abnormal pressure drops across the stator coils. The inlet end of the water manifold is also connected to an inlet water pressure gauge and to the low pressure side of a differential pressure switch. The high pressure side of this switch is connected to the generator (gas pressure). When the generator gas pressure drops to 0.35 bar above the inlet water pressure, an alarm is actuated.

1
DOCUMENT NO.: 50-F248C-D01-01 Page 19

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

2.1.2.11 Auxiliary alarms An alarm signal system is associated with the seal oil, stator coil water and hydrogen gas systems to indicate abnormal operating conditions. A Generator Auxiliary Control Enclosure has been supplied to indicate these alarms. A recent improvement has been made to supply the alarm signals dependent upon whether or not DEH is supplied and on the level of DEH supplied standard option. The traditionally supplied Generator Auxiliary Control Enclosure with local panel/announciator with limited contacts for Customer's use in addition to contact and analog signals going to DEH. DEH makes all calculations and displays on CRT under appropriate conditions. 2.1.2.12 Hydrogen coolers
1

Each hydrogen cooler consists of a number of finned tubes arranged within a suitable open frame structure, thus providing a layer heat transfer surface for cooling the hydrogen gas circulating within the generator. Technically a hydrogen cooler is classified as 1-2 cross flow heat exchanger. That is the hydrogen gas makes a single pass through the cooler on finned side of tubing and the cooling water makes two passes on the tubes. Generally hydrogen coolers are divided into 2 "sections", each section being an independent heat exchanger. The sections are arranged in tandem such that the hydrogen gas makes a single pass through all the tandem sections, whereas the cooling water flows in parallel in each section and makes two passes in each. There are generally two arrangements of hydrogen coolers used in generators: one is with coolers vertically mounted; and the other is with cooler horizontally mounted. This design uses the vertical arrangement. In the vertical arrangement, there are four hydrogen coolers, mounted in the frame of the generator at four corners. Each cooler consists of two separate, tandem sections, making a total of eight sections, each of which can
DOCUMENT NO.: 50-F248C-D01-01 Page 20

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

be isolated by valving. Each cooler is attached to the generator frame at one end only to permit expansion and contraction within the generator. The inlet water chamber, which extends beyond the generator frame, is bolted to the generator frame. A thin steel diaphragm is secured to the cooler and to the generator frame at the opposite end of the cooler. This diaphragm allows relative thermal expansion between the generator frame and the hydrogen cooler without allowing hydrogen gas to escape. The water makes two passes through each section in a counter flow manner by means of a reversing chamber at one end. The heat is transferred from the gas to the cooling water flowing through the finned tubes of the cooler. Temporary operation at reduced load is permitted with one or two of the eight cooler sections out of service. The permitted load can be seen from the generator instruction book in detail.
1

2.2 Generator surge protection system The surge arrestors and capacitors for each phase protect the generator and 3 sets of potential transformers from voltage surges. This system also senses voltage for metering, relaying, and automatic voltage regulation. The system includes the following major components: a) Surge capacitors for each phase. b) Surge arresters for each phase. c) Three sets potential transformers for each phase. Three separate compartments, one for each phase and each separated from
DOCUMENT NO.: 50-F248C-D01-01 Page 21

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

the other by grounded metal barriers to maintain the integrity of the isolated phase bus duct, shall be provided. Capacitors, surge arresters, and potential transformers will be connected phase-to-ground. Potential transformers will be fused on both the primary and secondary sides. The surge capacitors, surge arresters, and potential transformers that connect to the main isolated phase bus duct are enclosed in the surge arrester and potential transformer cabinet, the PT installed in the cabinet shall be draw out type. The cabinets located on the 6.3m floor of turbine house near the main isolated phase bus duct.. The Generator Surge Protection System will be designed for maximum generator output at any voltage from 95 to 105 percent of rated voltage and a phase-to-ground fault on the connected equipment. Please refer to single line diagram for generator protection metering, drg.no.50-F248C-D01-02 for connection of potential transformers. 2.3 Generator neutral grounding system The neutral grounding system provides a high resistance path between the generator neutral and ground to limit the overvoltage within approximate 2.6 p.u. under phase to ground fault, and also provides a means for detecting phase-to-ground fault currents. The system includes the following major components: a) Dry type neutral grounding transformer (NGT). b) Resistor connected to secondary winding of NGT. c) Current transformers on both side of NGT.
DOCUMENT NO.: 50-F248C-D01-01 Page 22

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

The maximum normal design conditions will be maximum generator output at any voltage from 95 to 105 percent of rated voltage. The emergency design condition is a phase-to-ground fault on the connected equipment. The high resistance neutral grounding unit shall consist of a neutral grounding transformer rated for short time overload and a secondary resistor of chromium, aluminum and iron alloy rated for 10 Sec short time loading. The primary winding of the distribution transformer will be connected between the generator neutral connection and ground while the secondary winding will be connected to the secondary resistor. A protective relay with a harmonic filter will be connected to the secondary winding to sense ground current flow and will initiate a unit trip through the Unit Protection System. The rated primary voltage of the NGT is rated phase to phase voltage of the generator. The kVA rating of the NGT will be based on a 5 minute duty. The NGT will be so chosen that the capacity of it shall be more than the energy loss in the resistance. Please refer to annexure I: Sizing calculation for generator neutral grounding system. The value of secondary resistance is so chosen that the energy loss in the resistor is equal to or more than the capacitive kVA of the generator windings and the equipments connected with generator. The NGT cabinet is located on the 6.3m floor of turbine house near the neutral point terminal of generator. 2.4 Generator Metering

DOCUMENT NO.: 50-F248C-D01-01

Page 23

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

The current, voltage, watt, var, frequency, power factor of the generator and exciter field current and voltage will be measured by discrete type static meters with DCS connectivity. Generator metering will be achieved through micro processor based Energy meter (kWH & VARH meter) with DCS interface facility. The energy meter as well as the discrete meters will housed in a stand alone type Generator metering panel and shall be located in Unit Control Room.(Please refer the Generator metering disposal diagram shown on drawing No. 50-F248C-D0102)

2.5 Synchronization Auto synchronization of GT 220kV circuit breaker will be performed through DCS . Back-up manual synchronization through sync check relay is provided across GT 220 kV circuit breaker.
1

3 Equipment description 3.1 Generator system 3.1.1 Type & cooling method Manufacture: Shanghai Turbine Generator Co, ltd Type: QFSN-300-2 Cool method: stator winding and terminal bushing is water inner-cooled, the rotor winding is hydrogen inner-cooled and stator core hydrogen cooled. Excitation type: brushless excitation system with permanent magnet pilot exciter

DOCUMENT NO.: 50-F248C-D01-01

Page 24

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

3.1.2 Main technical data Rated capacity:353 MVA Rated active power: 300MW Output under VWO condition: 315MW Rated voltage: 20kV Rated current: 10189A Frequency: 50Hz Power-factor:0.85(lag) Rated speed: 3000r/min Efficiency: 98.8%(guaranteed value with no negative tolerance.) 98.93%(designed value) Excitation system ceiling voltage:2 times Rated field current: 2510A Rated field voltage: 302V Gen. no load field current: 987A
DOCUMENT NO.: 50-F248C-D01-01 Page 25

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Gen. no load field voltage (75):113V

Stator winding resistance(15) : 0.00212

Rotor winding resistance(15) : 0.0923

Stator winding capacitance to ground per each phase: 0.209F

Xd (Sub-transient reactance (direct axis saturated)): 0.16 Xd (Transient reactance (direct axis saturated)): 0.202 Rotor rotating direction: clockwise direction (from turbine side to generator side) Terminal Phase physical location: CBA(Viewing from the exciter side to generator side ,and from left side to right side) The other data for generator refers to annexure II Date sheet for generator 3.2 Generator surge protection system 3.2.1 Surge capacitors for each phase: capacitance0.25f

3.2.2 Surge arresters for each phase


DOCUMENT NO.: 50-F248C-D01-01 Page 26

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Rated voltage: 24kV Normal discharge current: 5kA Residual voltage:56.2 kV 3.2.3 Potential transformers for each phase

fuse:5Arupturing capacity:5500MVA3set

PTs:

20 0.11 0.11 0.11 / / / kV ,1set 3 3 3 3

PTs:

20 0.11 0.11 0.11 / / / kV ,1set 3 3 3 3

PTs:

20 0.11 0.11 0.11 / / / kV ,1set 3 3 3 3

3.3 Generator neutral grounding system 3.3.1 Dry type neutral grounding transformer (NGT). Type: dry type, single phase Capacity: 50kVA for 5 minutes
DOCUMENT NO.: 50-F248C-D01-01 Page 27

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Ratio: 20/0.24kV 3.3.2 Secondary resistor. Resistance: 0.274 Tap voltage: 110V 3.3.3 Current transformers on primary side of NGT. Class: 0.5 Ratio: 10/5A 3.3.4 Single phase disconnector: Rate voltage: 20 kV Rate current: 400A 3.4 Excitation system

Excitation system will be brushless rotating diode wheel with a permanent magnet generator (PMG) excitation system. The exciter will be capable of maintaining field current for a 30 percent voltage depression on the machine terminals. The system shall be capable of providing 1.4 times nominal field voltage when the machine terminal voltage is 70 percent rated voltage. The excitation system will reach 95% of the difference between ceiling voltage and rated excitation voltage within 0.1 second. The ceiling voltage shall be maintained for a minimum of 10 seconds. The
DOCUMENT NO.: 50-F248C-D01-01 Page 28

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

excitation system response ratio shall not be less than 2.0 per second. The generator and its excitation system shall be provided with class F insulation with temperature rise limited to class B insulation limits. The proposed BLE excitation system was Westinghouse technology which is fully transferred to STGC. The features of brushless excitation system:
1

- The electric power source of excitation comes from the directly driven AC exciter and permanent magnet pilot exciter to avoid system interference. - Slip ring and brushes are no longer used. Thus pollution caused by carbon dust is eliminated, noise level lowered, and maintenance becomes easier. - The modular structure of rectifier, fuse and etc, is easy for maintenance. -Enough back up capacities are available for critical components such as the rotating diodes, firing circuit, power amplifying circuit and stable voltage source to ensure the safe operation. -With better protection devices (such as over excitation, low excitation and low frequency protection) the generator can be operated at the maximum output. -Internal connection: Rotating elements are solidly connected together. No outer connection is needed between the generator field and the exciter, the only outer connection being those between the stator of the AC exciter, the stator of the pilot exciter and the control circuit. -The field current of generator can be indirectly measured. - De-excitation is realized by field inversion of the AC exciter and then open of its field connection to PMG. The following protective and limit circuits will be provided for the system stability and protecting the interconnected components: volts/hertz regulator,
DOCUMENT NO.: 50-F248C-D01-01 Page 29

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

reactive current compensator, over excitation/ under excitation limiters and power system stabilizer (PSS), etc. The excitation system will include exciter, permanent magnet pilot exciter, regulator panel, converter suppression panel, field grounding detector panel, manual excitation control panel. All the panels will be IP54 degree of protection and housed in Electrical Relay Room (ERR). The above panels will be fabricated from steel structural sections or pressed and shaped cold-rolled sheet steel of thickness not less than 2mm, the panel size will be 2260(H)x800(W)x800(D).The protection degree for generator protection panel will be IP52. 3.5 Generator Protection Relay For each unit, one (1) set of doubly numerical multi-function Generator protection systems will be provided. The relay will be equipped in two (2) pieces of Generator protection panel and housed in ERR. Protection relay will provide detection and corrective/isolation action as required for the following faults and malfunctions: (The Generator protection disposal diagram is shown on drawing No. 50-F248C-D0102) 1) Generator Differential (87G) 2) Stator Inter-turn fault (95) 3) Stator earth fault 95 % and 100 % (64G) 4) Loss of excitation (40)

DOCUMENT NO.: 50-F248C-D01-01

Page 30

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

5) Negative phase sequence current (46) 6) Reverse power (32G1 / G2) 7) Low forward protection (37G) 8) Over current (51V) 9) Rotor earth fault (detect) (64R) - only feature 10) Over-voltage (59) 11) Under-voltage (27) 12) Generator pole slipping (90) 13) Under/over frequency (81U / O) 14) Voltage balance (60) 15) Over flux (99) 16) Overload (49) 17) Generator Backup impedance (21G) 18) Generator cooling water-loss (30G) 19) Stator winding temp high
DOCUMENT NO.: 50-F248C-D01-01 Page 31

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

20) Rotor winding temp high 21) Dead machine protection (96) 22) VT and CT supervision (98) 23) Startup/Shutdown protection (64SS) Start up/Shut down Protection is a protection which is used to react the stator earth fault and the interphase fault under low frequency or low speed conditions. Start up CBF is a protection which is used when the circuit breaker rejects tripping.
1

A micro-processor based rotor current supervision and overheat protective device (WZFD) will be provide for rotor winding temperature high protection. Voltages and currents of stator winding are sampled; Take the generators electrical-magnetic parameters and characteristic curve into consideration, the rotors current and negative sequence current can be calculated through the patent algorithm. The rotor winding temperature high alarm (or trip) signal can be issued if rotor current or negative sequence current reaches their settings respectively. Multiple generator lockout relays shall be used to receive signal inputs from protective relays and to provide the contacts needed to initiate protective action and alarms. Protective relays shall trip lockout relays based on functional redundancy. All lockout relays shall have a manual reset feature which shall request the operator to manually reset the lockout relay prior to
DOCUMENT NO.: 50-F248C-D01-01 Page 32

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

returning the affected equipment to service. Protective trip status/alarm will be displayed in DCS (DCS) CRT. Time synchronization will be supplied with the master clock/ GPS. Events Records, Fault Record and Data Logging will have sufficient storage capacity. The complete software of the protection scheme will be supplied in a laptop for each unit.
1

The Generator protection panel will be fabricated from steel structural sections or pressed and shaped cold-rolled sheet steel of thickness not less than 2mm, the panel size will be 2260(H)x800(W)x600(D).The protection degree for generator protection panel will be IP52. 3.6 Generator metering panel Generator metering panel will be provided and housed in CCR to install the meters of Generator. Generator metering panel will be fabricated from steel structural sections or pressed and shaped cold-rolled sheet steel of thickness not less than 2mm, the panel size will be 2260(H)x800(W)x600(D). The protection degree for generator metering panel will be IP52. 3.7 Generator fault recorder panel One (1) piece of Generator Fault Recorder Panel will be provided and housed in ERR to recorder electrical parameter of Generator when Generator fault and malfunctions for each unit. Generator Fault Recorder Panel will be fabricated from steel structural
DOCUMENT NO.: 50-F248C-D01-01 Page 33

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

sections or pressed and shaped cold-rolled sheet steel of thickness not less than 2mm, the panel size will be 2260(H)x800(W)x600(D). The protection degree for generator Fault Recorder panel will be IP52. 4 Generator control & operation philosophy records The Generator will be controlled from Power House Central Control Room (CCR) through DCS. The DCS will be utilized to perform control, interlock, indication, metering and annunciation related to the above equipment including equipment pertaining to Generator auxiliary system. All controls as supplementary to the proprietary system of BTG including auto synchronization of generator with 220kV grid will also be performed form DCS. 6.6 kV / 415V Electrical Breakers of Main Power house & ESP PMCC and Emergency DG set shall be operated from DCS. Balance of plant Electrical system will be operated from localized Electrical Control Panel (ECP). Detailed control and Operation philosophy shall be in line with DESIGN BASIS REPORT FOR ELECTRICAL CONTROL & OPERATION PHILOSOPHY _ doc no..:REL-DCRTP-CEE-299-R-517. 5 Main Equipments list

DOCUMENT NO.: 50-F248C-D01-01

Page 34

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Quantity

No.

Name

Type & specification

Unit 1 2 total

Remark

1. 1.1

Generator system Generator equipment(electrical part Bushing CT Supplied by generator manufacturer

1.1.1

12000/5A 5P20 60VA 12000/5A 0.2 60 VA 12000/5A 0.2S 60VA

set set set

15 3 6

15 3 6

30 6 12

1.1.2

Terminal box for connection the IPBD to generator Rotating brushless excitation system PT & LA cabinet

set

Supplied by REL

1.2 1.3

set

2 1(2)0AAA01~03

DOCUMENT NO.: 50-F248C-D01-01

Page 35

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Quantity

No.

Name

Type & specification

Unit 1 2 total

Remark

includingFuseRN4200.5ARupturing capacity:5500MVA PTJDZJ20

set

18

20 0.11 0.11 0.11 / / / kV 3 3 3 3 20 0.11 0.11 0.11 / / / kV 3 3 3 3 20 0.11 0.11 0.11 / / / kV 3 3 3 3

set

PTJDZJ20

set

PTJDZJ20

set set set set

3 3 3 1

3 3 3 1

6 6 6 2 1(2)0MK01

LAY5W124/56.2 Capacitor0.25f 1.4 Neutral point grounding transformer cabinet including dye-type single phase transformer: 50kVA 20/0.24Kv Secondary side resistance :0.274tap voltage:110V

DOCUMENT NO.: 50-F248C-D01-01

Page 36

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Quantity

No.

Name

Type & specification

Unit 1 2 total

Remark

CT 0.5 10/5A Single phase disconnectorGN220/400 400A 2 2.1 2.2 2.3 2.4 Excitation system Exciter Permanent exciter magnet pilot
1650kW, 475V, 3474A, exciter efficiency:90% 33.24Kva/31.6kW, 95V, 202A, 3000rpm, 350Hz

set set set piece piece

1 1 1 1 1

1 1 1 1 1

2 2 2 2 2

Regulator panel Converter and suppression panel Field grounding panel detector

Size: 2260(H)x800(W)x800(W) Size: 2260(H)x800(W)x800(W)

2.5

Size: 2260(H)x800(W)x800(W)

piece

2.6 2.7

Manual excitation control panel


Manual excitation adjust panel

Size: 2360(H)x800(W)x800(W)

piece
piece

1
1

1
1

2
2

Size: 2360(H)x800(W)x800(W)

DOCUMENT NO.: 50-F248C-D01-01

Page 37

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Quantity

No.

Name

Type & specification

Unit 1 2 1 total 2

Remark

2.8 3 4 5

AVR test panel

Size: 2200(H)x800(W)x640(W)

piece

Generator protection panel Generator metering panel Generator panel fault recorder

220V DC, 240V AC, CT:5A, PT:110VSize: 2260(H)x800(W)x600(W) 220V DC, 240V AC, CT:5A, PT:110VSize: 2260(H)x800(W)x600(W) 220V DC, 240V AC, CT:5A, PT:110VSize: 2260(H)x800(W)x600(W)

piece piece piece

2 2 1

2 2 1

4 4 2

6 7 8 9

Generator synchronization panel Terminal box


DC drive & control box

220V DC, 240V AC, CT:5A, PT:110VSize: 2260(H)x800(W)x600(W)

piece piece piece

1 2 5 5

1 2 5 5

2 4 10 10

1
Size: 1600(H)x800(W)x600(W)

Control cable

km

DOCUMENT NO.: 50-F248C-D01-01

Page 38

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Annexure I: Sizing calculation for generator neutral grounding system 1 Base data 1Capacitance of generator:
C1 = 0.209 f / phase

2 Capacitance of main transformers LV side (according to the data provided by REL):


C2 = 0.036 f / phase

3Capacitance of auxiliary transformers HV side (reference value): C3 = 0.005f / phase

4Capacitance of IPBD (according to the data provided by REL):


C4 = 0.002 f / phase

5Capacitance of Surge capacitor

C 5 = 0 . 25 f / phase
2 Sizing calculation Each phase total capacitance of the generator and the equipments connected

DOCUMENT NO.: 50-F248C-D01-01

Page 39

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

with the generator Cn = 0.25 + 0.209 + 0.036 + 0.005 2 + 0.002 = 0.507 f / phase

1 1 = 2093.83 Three phase capacitance to ground: X cg = 3 2f Cn

The generator neutral point resistance should be equal to or less than Xcg
1

2093.83 = = 1903.48 R' = 1.1 1.1


Basis for the factor 1.1:The safety Electrical Design reference book. Ratio of neutral ground transformer N = factor is according to the Chinese
1

X cg

20 10 = 83.33 240
3

The resistance of the neutral grounding transformer secondary side:

R=

R ' 1903.48 = = 0.274 N 2 83.332

The current of neutral grounding transformer secondary side:

Ir =

U2 240 = = 506 A 3R 3 0.274

The rating of the resistance:

DOCUMENT NO.: 50-F248C-D01-01

Page 40

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Pr =

2 240 2 U2 = 10 3 = 70.07kW 3R 3 0.274

NGT capacity:
S P r

Base on the 5 minutes overload capacity of dye type transformers, over load factor is 1.6: Basis for the factor 1.6 :the over load factor is according to the Electrical Design reference handbook for China Power plant The over load factor of the dry type transformer can be changed as follow: Overload time: 5 minutes 18 minutes 32 minutes 45 minutes 60 minutes NGT capacity S = over load factor: 1.6 1.5 1.4 1.3 1.2
1

70.07 = 43.80kVA 1.6

Rating50 kVA

3 Calculation for generator neutral fault current: Generator fault capacitive current:

DOCUMENT NO.: 50-F248C-D01-01

Page 41

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

I c = 3U ec 10 3 = 3 20 314 0.507 10 3 = 5.52 A

Generator fault current

I 2 I c = 2 5.52 = 7.78 A

ANNEXURE II Date sheet for generator


DOCUMENT NO.: 50-F248C-D01-01 Page 42

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.0

ELECTRICAL

21.1

GENERATOR MAIN

PARAMETERS

21.1.1 Manufacturers Name:

a) Make of Generator

Shanghai Turbine Generator Co, Limited

b) Type/Model No.

Water-Hydrogen lnner-cooled/ QFSN-300-2

c) AppIicable standards

lEC34-1,IEC34-3,IEC34 GB/T7064,GB755

21.1.2 Maximum continuous output(MCR)at rated hydrogen pressure and specified cooling water temperature

:(MVA)

370.5
1

21.1.3 Rated stator voltage

:(kV)

20

21.1.4 Rated stator current

:(Amps)

10189

DOCUMENT NO.: 50-F248C-D01-01

Page 43

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.1.5 Rated frequency and speed

:(Hz),(RPM)

503000

21.1.6 Rated power factor

:(Lag)

0.85

21.1.7 Field current at MCR

:(Amps)

2601

21.0.8 Field voltage at MCR

:(Volts)

312

21.1.9 Maximum continuous

permissible variation range in: a) Rated stator voltage :(%) 5

b) Rated frequency

:(%)

-5 to +3

c) Combined permissible variation of voltage and frequency

:(%)

As per IEC34-1 section 6.3

21.1.10 Number of: a) phases 3

DOCUMENT NO.: 50-F248C-D01-01

Page 44

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

b) parallel paths/phase

c) Line side terminals brought out d) Neutral side terminals brought out

21.1.11 Maximum temperature :( ) of a) Stator winding by RTD : 85

b) Rotor windings

110

21.1.12 Generator efficiency at :(%) rated power and power factor

98.8%(guaranteed value with no negative tolerance) 98.93%(designed value)

21.1.13 Short circuit ratio(SCR) : corresponding to maximum capability

0.6

21.1.14 Permissible tolerance :(%) in SCR


DOCUMENT NO.: 50-F248C-D01-01

According to IEC 60034-3 (+/-15%)

Page 45

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.1.15 Regulation at a) Unity power factor b) 0.85 power factor lagging 21.1.16 pressure 21.1.17 lnsulation class a) Stator winding b) Rotor winding : Rated hydrogen :(kg/cm2) : (kPa) : F F
1.25 2 (2U N + 1) = 72.5kV

Shall be provided during detailed engineering Shall be provided during detailed engineering

1
3.16/(310)

21.1.18 Basic impulse insulation :(kV peak) withstand voltage of stator winding with respect to earth (for standard wave shape of 1.2/50 micro sec.) 21.1.19 short Symmetrical circuit current r.m.s with : a) 3-phase (kA)

Initial value Sustained value

generator isolated:

69

15.5

DOCUMENT NO.: 50-F248C-D01-01

Page 46

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

b) Single phase to earth

:(kA)

80

21.0.20 3-phase short circuit Withstand time 21.1.21 permissible unbalanced load capability subject to rated current not being exceeded in any phase: a) Maximum continuous negative sequence current l b) Minimum value of l2t for transient operation under system fault conditions(wheres in seconds) 21.1.22 Maximum permissible inductive zero PF loading at
2

:(sec.)

2.5

:(p.u.)

10%

:(sec.)

10

:(MVAR)

270

1
21.1.23 Maximum permissible capacitive loading for stability at rated voltage and zero power factor :(MVAR) 154

DOCUMENT NO.: 50-F248C-D01-01

Page 47

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.1.24 Generator parameters : at rated kV and MVA a) Direct axis synchronous reactance Xd b) Direct axis transient reactance Xd c) Direct axis subtransient reactance Xd d) Effective winding capacitance to earth: i) Per phase ii) All phases connected together e) Effective surge I impedance to neutral per phase 21.1.25 Maximum temperature of H2 With the secondary cooling water inlet temperature as specified 21.1.26 Generator losses, :() :(Ohms) :(Microfarad) :(Microfarad) :(p.u.) : (p.u.) :(p.u.)

Unsaturated

Saturated

180%

22.9%

20.2%

17.4%

16%

0.209 0.627

Shall be provide during detailed engineering

46

DOCUMENT NO.: 50-F248C-D01-01

Page 48

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

also indicate where one loss component is included in the another one give curves various losses Vs. Load as above at different hydrogen pressures a) Stator core loss b) Rotor copper loss at load(including excitor) c) Stator copper loss at full :(kW) load d) Stray load loss e) Friction and windage loss f) Mechanical losses included bearing losses g) tolerance on above losses 21.1.27 temperature points in: a) stator core b) stator winding
DOCUMENT NO.: 50-F248C-D01-01

:(kW) full :(kW)

435 904

816

:(kW) :(kW) :(kW)

425 205 407

:(+%),(-%) of

+10%

number

Monitoring

: :

10(yoke)+10(teeth) 54
Page 49

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

c) generator bearings and excitor 21.2 ADDLTLONAL DATA 21.2.1Permissible overload and duration 21.2.2 Surge capacitor :(f) :(p.u)& (sec.)

2+1

1.05(long duration)

0.25

requirement for the generator 21.2.3 Complete description of stator core monitoring system for the generator enclosed 21.2.4 permissible volts/Hz Vs time characteristic of the generator enclosed 21.2.5 a) system b) Detailed write-up/ literature for the excitation system, enclosed :(Yes/No) Yes Type of excitation Brushless excitor :(Yes/No) : (Yes/No) Shall be provided during detailed engineering

1
Yes

1
c) Block schematic diagram of excitation system enclosed
DOCUMENT NO.: 50-F248C-D01-01 Page 50

:(Yes/No)

Shall be provided during detailed engineering

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.2.6 a)Type of voltage regulator b) Description of voltage regulator

:(Yes/No) :(Yes/No) :

DAVR microprocessor-based, with dual channel, mutually redundant, automatic following and automatic changeovers, digital type voltage regulator

21.2.7 Type of cooling for a) Stator winding b) Stator core c) Rotor 21.2.8 Transient rise of voltage on sudden rejection of full load at rated power factor a) with AVR b)without AVR 21.2.9 Acceleration time 21.2.10 lnertia constant H a) Generator& Exciter b) Complete turbine
DOCUMENT NO.: 50-F248C-D01-01

:(Yes/No) : :

Water Hydrogen Hydrogen

: (p.u) : (p.u) : (sec) : (kW-sec/kVA) :

1.1 1.31 Shall be provided during detailed engineering

1.14

Shall be provided during


Page 51

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

generator unit 21.2.11 Fly wheel moment of inertia of generator + exciter 21.2.12 Hydrogen coolers: a) Number of cooler section : (Kg-)

detailed engineering 32700

8 (4 coolers with 8 sections)

1
b) Maximum continuous rating of generatlr with one section cooler out of operation c) Material of i) Tubes ii) Fins iii) Tube plate iv) Water boxes d) Quantity of cooling water required/cooler : e) Rated cooling water pressure f) Pressure drop
DOCUMENT NO.: 50-F248C-D01-01

: (MVA)

90% (with one section of 8 out of service)

: : : : : :(m3 /hr) Bfe10-1-1 copper Bronze Steel 440 (110 per cooler)

(kPa)

600(max)

: (m.w.c)

56kPa

1
Page 52

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

across cooler on water side g) Rated cooling water temperature at cooler inlet 21.2.13 Degree of protection as per IEC 34-5 21.3.4 Current Transformers a) Make & Country of the manufacturer b) Type c) Reference standard d) Class of insulation e) Rated short time thermal current for three(3)sec f) Momentary current : (kA) exciter : (kAp)
DOCUMENT NO.: 50-F248C-D01-01 Page 53

: ()

38

IP-54

: :

Yes Shanghai instrument transformer works

: : :

Bushing CT

1
GB1208-997(epv IEC44-1,1996) Insulation class F, Temperature rise limited to class B Shall be provided during detailed engineering

1 1

Shall be provided during detailed engineering

21.3

Brushless

technical data

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

21.3.1Exciter DC Rating rated capacity rated voltage rated current efficiency 21.3.2Exciter AC Rating rated capacity rated power factor rated frequency rated voltage rated current parallel No. phase No. rated speed Pole No. Cooling air temp.
DOCUMENT NO.: 50-F248C-D01-01 Page 54

: (kW) : (V) : (A)

1650 475 3474 90%

: (kVA/kW)

1883/1695 0.9

: (Hz) : (V) : (A)

250 403 2698 5Y 3

: (r/min)

3000 10

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Rated/Max Air cooler capacity 21.3.3Exciter Parameter 1.Resistance Armature resistance(75) Field winding resistance(75) 2.Field winding inductance 3.Reactance(Unsaturated) Direct axis Xd sub-transient

: (/) kW)

45/50 2x125

winding : (/ph)

0.35x10-3

: ( ) : (H)

0.0657 0.108

13.6% 13.6% 60.3% 35.7% 35.7% 35.7% 16.6%


Page 55

reactance Xd Direct

Direct axis transient reactance

axis

synchronous

reactance Xd Quadrature axis sub-transient reactance Xq Quadrature reactance Xq Quadrature axis synchronous reactance Xq Negative phase-sequence axis transient

DOCUMENT NO.: 50-F248C-D01-01

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

reactance X2 Zero reactance X0 4.Time constant Transient circuit T do Transient circuit T d 5.High initial voltage response 6.Ceiling voltage 7.Critical speed 1st 2nd 8.Rotor flywheel moment GD2 21.3.4 Rectifier circuit Type : (r/min) : (r/min) : (t-m2) 2450 5200 1.1 Single wheel 3-phase full wave rectifier design ,A 3-phase bridge with 8 diodes connected in parallel each phase Model of diode Rating of diode : (A) R6L-40 disk type 400 0.1s 2 times

phase-sequence

7.35%

direct direct

axis axis

open : (s) short : (s)

1.64s 0.37s

DOCUMENT NO.: 50-F248C-D01-01

Page 56

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Diode reverse voltage Fuse rated current Fuse rated voltage Fuse resistance(25) Capacitor rating Capacitor fuse rated current 21.3.5 Permanent magnet pilot exciter Rated capacity Rated power factor Rated frequency Rated voltage Rated current Parallel Phase No. Rated speed
DOCUMENT NO.: 50-F248C-D01-01

: (V) : (A) : (V) : () : (F) : (A)

2000 670 750 (0.102~0.119)X10-3 0.3 15

: (kVA/kW)

33.24/31.6 0.95 350 95 202 2Y 3 3000


Page 57

: (Hz) : (V) : (A)

: (r/min)

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

Pole No. Permanent magnet material 21.3.6Air cooler Exciter cooling air flow Total water flow required : (m3/s) : (t/h)

14 AINiCo5-7

2x4.6 2x45 35

Max. inlet water temp. of air : () cooler 21.3.7Bearing Bearing type Bearing diameter Bearing length Bearing oil flow required : (mm) : (mm) : (l/min)

Tilt-pad 228.8 102 25

DOCUMENT NO.: 50-F248C-D01-01

Page 58

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

ANNEXURE III Generator capability curve

DOCUMENT NO.: 50-F248C-D01-01

Page 59

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

ANNEXURE IV Generator overfluxing capability curve

DOCUMENT NO.: 50-F248C-D01-01

Page 60

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

ANNEXURE V Generator saturation curve Line Voltage (kV)

Line Current (A)


DOCUMENT NO.: 50-F248C-D01-01 Page 61

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

ANNEXURE VI Generator vee curve

Leading Lagging

DOCUMENT NO.: 50-F248C-D01-01

Page 62

Design Basis Report for BTG Electrical System

HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamunanagar

ANNEXURE VII Exciter characteristic curve

DOCUMENT NO.: 50-F248C-D01-01

Page 63

Das könnte Ihnen auch gefallen