GETCO / E / 2S - 141/ PP - 015 1A / R0 Dt.03.11.

2011

Control & Relay Protection Philosophy for 220KV SARTANPAR Sub Station
A) Bus Bar Configuration 220kV System : Two Main Bus 132kV System : Single Bus 66KV System : Two Main Bus Isolator system 220kV System: Three isolator configuration (Two Bus isolators and a Line isolator) Integrated in Hybrid switch gear module 132kV System: Two isolator configuration (One Bus and a Line isolator) Integrated in Hybrid switch gear module 66KV System: Three isolator configuration (Two Bus isolators and a Line isolator) Integrated in Hybrid switch gear module B) Control Voltage 220V DC C) Control & Relay panels Control & protection Panels for Hybrid Switchgear modules to be mounted in Yard Kiosk. D) PLCC panels PLCC Panels to be mounted in Control Room PLCC BCU panel to be mounted in Control Room for interface between Control & protection Panels and PLCC Panels, through GOOSE commands E) Nos. of 220 KV Bays & Bus Bar Protection Feeder Bays 6 Nos. 220/66KV Transformer Bays 2 Nos. 220/132KV Transformer Bays 2 Nos. (Includes one Hybrid switch gear module for future transformer ) Bus Coupler Bay 1 No. Total Nos of Bays in first phase 11 Nos. Future Bays 2 Nos. Total Nos of Bays planned 13 Nos. Bays connected to Bus Bar Protection in first phase - 11 Bus Bar Protection o Control Unit - 24 Bays o Bay Units (Peripheral Units) 11 Nos + 1 No. (To be kept as spare) F) Nos. of 132KV Bays Feeder Bay 2 Nos. 220/132KV Transformer LV Bays 2 Nos (Includes one Hybrid switch gear module for future transformer ) Total bays in the Sub Station will be 4 Nos. G) Nos. of 66KV Bays Feeder Bays 12 Nos.

Page 1 of 4

GETCO / E / 2S - 141/ PP - 015 1A / R0 Dt.03.11.2011

220/66KV Transformer LV Bays 2 Nos. Bus Coupler Bay 1 No. Total Nos of Bays planned 15 Nos.

Control Philosophy SARTANPAR Sub Station


System 220 KV Bay 132 KV Bay 66 KV Bay Controlling Device to be Adopted Bay Control Unit Bay Control Unit Bay Control Unit Type of Controlling Device BCU with IEC 61850 Protocol BCU with IEC 61850 Protocol BCU with IEC 61850 Protocol

Protection Philosophy SARTANPAR Sub Station


A) Feeder Protection Feeder 220 KV Feeders 1 Protection to be Adopted Type of Relay Two Distance Protection Numerical Relay with IEC [shall be of two different make 61850 Protocol (i.e. from different manufacturers) or of same make with two different platforms with same specifications] -Main-I Protection & -Main II Protection Two Stage Over Voltage Integrated in Main I & Protection Main II Protection - Stage I - Stage II Local Breaker Backup (LBB) Integrated in Main I Protection. Protection and Bus Bar protection Distance Protection Numerical Relay with IEC 61850 Protocol

132 KV Feeders

2 Directional O/C & E/F Protection Numerical Relay with IEC 61850 Protocol 3 Local Breaker Backup (LBB) Protection. 66 KV Feeders Integrated in Distance protection and Backup protection 1 Directional O/C & E/F Protection Numerical Relay with IEC 61850 Protocol 2 Local Breaker Backup (LBB) Integrated in Dir. O/C-E/F Protection. protection Protection to be Adopted 1 Differential Protection

B) Power Transformer Protection Equipment 220/132 KV Transformer Type of Relay Numerical Relay with 61850 Protocol 2 Restricted Earth Fault Protection Numerical Relays with 61850 Protocol 3 Directional O/C & E/F Protection Numerical Relay with (HV side) 61850 Protocol 4 Directional O/C & E/F Protection Numerical Relay with (LV side) 61850 Protocol IEC IEC IEC IEC

Page 2 of 4

GETCO / E / 2S - 141/ PP - 015 1A / R0 Dt.03.11.2011

5 Over Fluxing Protection 6 Local Breaker Backup (LBB) Protn. - 220 KV side

Integrated Protection

in

Differential

-Integrated in Differential protection and Bus Bar protection

10

11

12

13

220/66 KV Transformer

1 2 3 4 5 6

- Integrated in Dir. O/C-E/F protection Buchholz Relay Integrated in Transformer. Auxiliary relay in protection panel. Pressure Relief Device Integrated in Transformer. Auxiliary relay in protection panel. Oil & Wdg. Temp. Alarm & Integrated in Transformer. Tripping Auxiliary relay in protection panel. OLTC Oil Surge Relay Integrated in Transformer. Auxiliary relay in protection panel. Oil Level Low Alarm Integrated in Transformer. Auxiliary relay in protection panel. Transformer Cooling Trouble Integrated in Transformer. Auxiliary relay in protection panel. Fire Protection System Integrated in Transformer. Auxiliary relay in protection panel. Differential Protection Numerical Relay with IEC 61850 Protocol Restricted Earth Fault Protection Numerical Relays with IEC (on HV & LV side) 61850 Protocol Directional O/C & E/F Protection Numerical Relays with IEC (HV side) 61850 Protocol Directional O/C & E/F Protection Numerical Relays with IEC (LV side) 61850 Protocol Over Fluxing Protection Integrated in Differential Protection Local Breaker Backup (LBB) Protn. - 220 KV side -Integrated in Differential Protection and Bus Bar protection - 66 KV side - Integrated in Dir. O/C-E/F protection Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel.

- 132 KV side

7 Buchholz Relay

8 Pressure Relief Device

Page 3 of 4

GETCO / E / 2S - 141/ PP - 015 1A / R0 Dt.03.11.2011

9 Oil & Wdg. Temp. Alarm & Tripping 10 OLTC Oil Surge Relay

11 Oil Level Low Alarm

12 Transformer Cooling Trouble

13 Fire Protection System

Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Numerical Relay with IEC 61850 Protocol Integrated in Non Dir. O/C & E/F Protection and Bus Bar protection. Numerical Relay with IEC 61850 Protocol Integrated in Non Dir. O/C & E/F Protection.

C) Bus Coupler Protection 220 KV Bus coupler

1 Non Directional O/C & E/F Protection 2 Local Breaker Backup (LBB) Protection. 1 Non Directional O/C & E/F Protection 2 Local Breaker Backup (LBB) Protection.

66 KV Bus coupler

E) Bus Bar Protection 220 KV Bus bar

Numerical Relay with IEC 1 Bus Differential Protection (Single scheme) 61850 Protocol 11 Bays, Extendable up to 24 Bays (i. e. Control Unit - 24 Bays) F) Disturbance Recorder & Event Loggers Integrated feature of protective relays is used to provide the information about the Disturbance and to log the events. G) GPS based Time Synchronizing Equipment 220 KV Sub station is to be provided with IEC 61850 compatible Global Positioning System based Time Synchronizing Equipment to synchronize all the protections.

Page 4 of 4