TABLE OF CONTENTS
1.0
1.1 1.2
2.0
2.1 2.2
MODBUS COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Implementation Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Transmission Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 Modbus Remote Transmission Unit settings for Liebert IntelliSlot 485/IP interface card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Device Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Function Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Supported Modbus function codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Data Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Error Check Field. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3
2.4
RTU Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 4 Table 5 Query sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Response sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0
3.1
ii
3.2
3.3
iii
3.4
4.0
4.1
4.2
4.3
iv
Liebert Equipment Compatibility - Connectivity to Liebert IntelliSlot Using Modbus 485, Modbus IP or BACnet IP
1.0
1.1
1.2
Table 1
Product Supported
MODBUS 485 & MODBUS IP PROTOCOLS Precision Cooling Products Liebert Challenger 3000 6-8 Liebert Challenger ITR 6-8 Liebert CRV 9-11 Liebert CW 6-8 Liebert Deluxe System/3 6-8 Liebert DS 6-8 Liebert HPC (Chiller) 12-14 Liebert HPM 6-8 Liebert XDC 15-16 Liebert XDP 17-19 Liebert XDWP (XDP-W) 20-21 Liebert PeX 6-8 Liebert DS 22-23 Liebert PeX 22-23 Liebert XDF 24-25 Liebert Challenger 3000 26 Liebert Deluxe System/3 26 Liebert Himod 26 Liebert ICS 26 Liebert DataMate 27 Liebert Mini-Mate Plus 27 Liebert Mini-Mate2 27 Liebert DataMate 28 Liebert Mini-Mate2 28 Liebert Mini-Mate2 8 Ton 29 Liebert Atlas Air 30 Liebert Atlas PEC 30 Liebert LECS 15 30 Liebert Atlas Air 31 Liebert Atlas PEC 31 Liebert CEMS 100 31
Liebert iCOM v4
IS-485L
IS-IPBML
Liebert iCOM v3
OC485-LBDS
LAM
OC485-ADPT
IS-WEBADPT
OC485-ADPT
IS-WEBADPT
Table 1
Product Supported
MODBUS 485 & MODBUS IP PROTOCOLS (continued) Power Distribution & Power Conditioning Products Liebert Datawave 32 PMP, PM2 for Liebert FPC 32 Liebert FPC & Liebert PPC Liebert PPC 32 Liebert FPC, Liebert RDC, 34-36 v4 Liebert FDC, Liebert RX Liebert Datawave 33 PMP for Liebert FPC 33 Liebert FPC & Liebert PPC Liebert PPC 33 Liebert STS / Liebert STS/PDU 37 STS Liebert STS2 / Liebert STS2/PDU 38 STS2 UPS Systems Liebert APM 39-41 Liebert GXT2 42-43 Liebert GXT3 42-43 Liebert HiNet 44-45 Liebert Nfinity 46-47 Liebert NX 48-49 Liebert NXL (SA, SR, SN, MM, CD) 50-52 Liebert PowerSure Interactive 53-54 Liebert PowerSure Interactive 2 55-56 Liebert Series 300 UPS 57-58 Liebert Series 600 UPS 59-60 Liebert Series 610 SCC UPS 61-62 63 Liebert HiPulse SMM/SSM Liebert SICE 7200 63 Liebert SICE 7200 64 SSC Liebert NPower 65 IMP Battery Monitoring Products Liebert BDSU BACNET IP PROTOCOL Precision Cooling Products Liebert Challenger 3000 Liebert Challenger ITR Liebert CRV Liebert CW Liebert Deluxe System/3 Liebert DS Liebert HPC Liebert HPM Liebert PeX Liebert XDP Liebert XDWP (XDP-W) Liebert DataMate Liebert Mini-Mate2 Liebert Mini-Mate2 8 Ton Precision Cooling Products Liebert APM 66-67
OC485-ADPT IS-485S OC485-ADPT OC485-ADPT OC485-ADPT IS-485L OC-485 OC-485 OC-485 OC-485 OC-485 IS-485X OC-485 OC-485 OC485-ADPT OC485-ADPT OC485-ADPT OC485-ADPT OC485-ADPT OC485-ADPT IS-485X
IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT IS-WEBADPT
68-71 68-71 72-75 68-71 68-71 68-71 76-79 68-71 68-71 80-83 80-83 84 84 85 86-88
Liebert iCOM v4
IS-IPBML
MM2 L8T
IS-485L
2.0
2.1
MODBUS COMMUNICATIONS
Implementation Basics
Modbus protocol provides control and data acquisition, through query and response, between master and slave devices. This protocol comprises the rules for communication, controlling the message format between devices, how master and slave devices initiate communications, as well as unit identification, message-handling and error-checking. The Liebert IntelliSlot 485/IP card acts as a slave device on a network. This network can be a multidrop configuration over EIA-485, where multiple slaves reside on a common wire or loop.
2.2
Transmission Format
The Liebert IntelliSlot 485/IP interface card supports Modbus Remote Terminal Unit (RTU) transmission modes. See Table 2 below. Table 2 Modbus Remote Transmission Unit settings for Liebert IntelliSlot 485/IP interface card
Transmission Mode RTU Baud Rate 9600, 19200 or 38400 Data Bits 8 Parity Bits None Stop Bits 1 Start Bits 1 Physical Port EIA-485/422 2 wire
2.3
2.3.1
Device Address
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user-assigned address of the slave device that is to receive the message from the attached master device. Each slave must be assigned a unique address. Only the addressed slave will respond to a query that contains its address.
2.3.2
Function Code
The function code field tells the addressed slaves what function to perform. Function codes are designed to invoke a specific action by the slave device. The function code ranges from 1 to 127. Liebert IntelliSlot Modbus server supports the following Modbus function codes. Table 3
Code 01
02
03 04 05 06 15 16
Read Holding Registers Read Input Registers Write Single Coil Write Single Register Write Multiple Coils Write Multiple Registers
2.3.3
Data Fields
The data field length varies, depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to the response to a data request from the master device.
2.3.4
2.4
RTU Framing
The example below shows a typical query and response from a Liebert IntelliSlot interface card. The master device initiates a query asking Slave Device, with address 2, for holding registers starting at holding register 40051 (offset 50) and including next two registers (three total). Table 4
Slave Address 02
Query sample
Function Code 03 Starting Register Hi Byte 00 Lo Byte 32 Number of Registers Hi Byte 00 Lo Byte 03 E5 CRC16 Hi Byte Lo Byte FA
Table 5
Response sample
Register CRC16 40053 Data Hi 00 Lo 54 Hi Byte 1B Lo Byte 0D Count: Bytes of Data 6 40051 Data Hi 1 Lo 58 40052 Data Hi 00 Lo FA
Slave Address 02
Function Code 03
Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values: 40051 = 158 (hex) = 344 (decimal) 40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 84 (decimal)
3.0
3.1
Liebert Products
Available Points Data Description Ext Reheat Lockout Ext Humidifier Lockout Minimum Chilled Water Temp Set Point Enable Return Air Sensor Event Control Ext Air Sensor A Event Control Ext Compressor Lockout System On/Off Control Fan State Cooling State Free Cooling State Hot Water / Hot Gas State Electric Reheat State Humidifier State Dehumidifier State Main Fan Overload Loss of Air Flow Ext Loss of Flow Compressor High Head Pressure Compressor Low Suction Pressure Compressor Thermal Overload Compressor Pump Down Issue Compressor High Head Pressure 2 Compressor Low Suction Pressure 2 Compressor Thermal Overload 2 Compressor Pump Down Issue 2 Dig Scroll Comp Over Temp 1 Dig Scroll Comp Over Temp 2 Smoke Detected Water Under Floor Humidifier Issue Ext Standby Glycol Pump On Ext Standby Unit On Ext Condenser Pump High Water Return Air Sensor Issue Status 10009 10010 10013 10019 10020 10021 10025 10026 10027 10028 10029 10030 10031 10034 10035 10036 10037 10038 10039 10040 10041 10042 10043 10044 10045 10046 10047 10048 10049 10050 10051 10052 10053 Coil 13 19 20 25 Scale Notes / Units Active on Alarm Active on Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled Active on Alarm 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
Table 6
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Status and Coil (continued)
Controller Liebert iCOM v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert PeX Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Liebert Products
Available Points Data Description Ext Loss of Air Blower Humidifier Low Water Humidifier Over Current Ext Over Temperature Shutdown - Loss Of Power Supply Chilled Water Over Temp Return Air Over Temperature Return Air Under Temperature High Return Humidity Low Return Humidity Ext Air Sensor A Over Temperature Ext Air Sensor A Under Temperature Ext Air Sensor A High Humidity Ext Air Sensor A Low Humidity Supply Chilled Water Loss of Flow Clogged Air Filter Supply Air Sensor Issue Free Cooling Temp Sensor Issue Ext Air Sensor A Issue Fan Hours Exceeded Compressor Hours Exceeded 1 Compressor Hours Exceeded 2 Free Cooling Valve Hours Exceeded Electric Reheater Hours Exceeded 1 Electric Reheater Hours Exceeded 2 Electric Reheater Hours Exceeded 3 Hot Water / Hot Gas Valve Hours Exceeded Humidifier Hours Exceeded Dehumidifier Hours Exceeded Unit Communication Lost Master Unit Communication Lost Unit Code Missing Service Required Humidifier Control Board Not Detected Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Status 10055 10058 10059 10060 10061 10065 10067 10068 10069 10070 10071 10072 10073 10074 10075 10076 10077 10078 10079 10080 10081 10082 10083 10084 10085 10086 10087 10088 10089 10091 10092 10094 10098 10099 10104 10105 10106 10107 Coil Scale Notes / Units Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
Table 6
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Status and Coil (continued)
Controller Liebert iCOM v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert PeX Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Liebert Products
Available Points Data Description Dig Scroll Comp Discharge Temp Sensor Issue 1 Dig Scroll Comp Discharge Temp Sensor Issue 2 Supply Air Over Temperature Supply Air Under Temperature Ambient Air Sensor Issue Compressor Short Cycle 1 Compressor Short Cycle 2 Ext Free Cooling Lockout Reheater Over Temperature Humidifier Cylinder Worn Humidifier Under Current Fan Issue Condenser TVSS Issue Condenser VFD Issue Condenser Issue 1 Condenser Issue 2 BMS Communications Timeout Digital Output Board Not Detected 1 Digital Output Board Not Detected 2 Digital Output Board Not Detected 3 RAM Battery Issue Water Leakage Detector Sensor Issue External Fire Detected Chilled Water Control Valve Position 1 Chilled Water Control Valve Position 2 Unit Off Unit On Unit Partial Shutdown Unit Shutdown High Power Shutdown Unit Standby Maintenance Due Maintenance Completed Compressor Low Pressure Transducer Issue 1 Compressor Low Pressure Transducer Issue 2 Compressor High Pressure Transducer Issue 1 Compressor High Pressure Transducer Issue 2 Compressor Capacity Reduced Status 10108 10109 10209 10210 10211 10212 10213 10214 10215 10216 10217 10218 10219 10220 10221 10222 10223 10224 10225 10226 10227 10228 10229 10230 10231 10232 10233 10234 10235 10236 10237 10238 10239 10240 10241 10242 10243 10244 Coil Scale Notes / Units Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
Table 6
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Status and Coil (continued)
Controller Liebert iCOM v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert PeX Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Liebert Products
Available Points Data Description Ambient Air Sensor Issue Dew Point Over Temperature Dew Point Under Temperature Ext Dew Point Over Temperature Ext Dew Point Under Temperature Compressor Superheat Over Threshold 1 Compressor Superheat Over Threshold 2 Unspecified General Event Remote Sensor Average Over Temperature Remote Sensor Average Under Temperature Remote Sensor System Average Over Temperature Remote Sensor System Average Under Temperature Remote Sensor Over Temperature 1 Remote Sensor Over Temperature 2 Remote Sensor Over Temperature 3 Remote Sensor Over Temperature 4 Remote Sensor Over Temperature 5 Remote Sensor Over Temperature 6 Remote Sensor Over Temperature 7 Remote Sensor Over Temperature 8 Remote Sensor Over Temperature 9 Remote Sensor Over Temperature 10 Remote Sensor Under Temperature 1 Remote Sensor Under Temperature 2 Remote Sensor Under Temperature 3 Remote Sensor Under Temperature 4 Remote Sensor Under Temperature 5 Remote Sensor Under Temperature 6 Remote Sensor Under Temperature 7 Remote Sensor Under Temperature 8 Remote Sensor Under Temperature 9 Remote Sensor Under Temperature 10 Air Economizer Emergency Override Air Economizer Reduced Airflow Status 10344 10345 10346 10347 10348 10349 10350 10351 10352 10353 10354 10355 10356 10357 10358 10359 10360 10361 10362 10363 10364 10365 10366 10367 10368 10369 10370 10371 10372 10373 10374 10375 10376 10377 Coil Scale Notes / Units Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding
Controller Data Description Liebert iCOM v4 Input Register 30017 30018 30019 30020 30021 30022 30023 30024 30025 30026 30027 30028 30029 30030 30031 30033 30045 30050 30051 30052 30053 30054 30055 30056 30057 30070 30071 30072 30073 30074 30075 30076 30077 30078 30079 30100 Holding Register 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40033 40045 40050 40051 40052 40053 40054 40055 40056 40057 40070 40071 40072 40073 40074 40075 40076 40077 40078 40079 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Notes / Units 0 = Disabled 1 = Contact 2 = Temperature 3 = Set Point % deg C deg C deg C deg C deg C min % RH % RH min % RH sec 0 = Proportional 1 = Prop+Integral 3 = Intelligent min deg C deg C deg C deg C % RH % RH % RH % RH hr hr hr hr hr hr hr hr hr hr 0 = Off / 1 = On 2 = Standby 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation
Free Cooling Internal Control Mode This point does not exist in the FDM Fan Speed Maximum Set Point This point does not exist in the FDM Free Cooling Internal Temperature Delta Minimum Chilled Water Temp Set Point Air Temperature Set Point Air Temperature Proportional Band Air Temperature Dead Band Air Temperature Control Integration Time Humidity Set Point Humidity Proportional Band Humidity Proportional Control Integration Time Humidity Dead Band Auto Restart Delay Air Temperature Control Type BMS Timeout Period Return Air Over Temp Threshold Return Air Under Temp Threshold Ext Air Sensor A Over Temp Threshold Ext Air Sensor A Under Temp Threshold High Return Humidity Threshold Low Return Humidity Threshold Ext Air Sensor A High Humidity Threshold Ext Air Sensor A Low Humidity Threshold Fan Hours Threshold Compressor Hours Threshold 1 Compressor Hours Threshold 2 Humidifier Hours Threshold Dehumidifier Hours Threshold Free Cooling Valve Hours Threshold Electric Reheater Hours Threshold 1 Electric Reheater Hours Threshold 2 Electric Reheater Hours Threshold 3 Hot Water / Hot Gas Valve Hours Threshold System Operating State
System Status
30102
10
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30103 30104 30105 30106 30107 30108 30109 30110 30112 30113 30115 30116 30117 30118 30119 30120 30130 30132 30133 30134 30141 30142 30143 30144 30145 30146 30147 30148 30149 30150 30151 30153 30155 30157 30257 30258 30260 30262 30263 30264 30265 Holding Register 40262 40263 40264 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 2 Scale 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1 = UPS 2 = AIR 3 = PMP 4 = PDU deg C deg C deg C deg C deg C deg C % RH % RH % RH % RH hr hr hr hr hr hr hr hr hr hr deg C deg C % RH % RH Notes / Units % % % % % % 0 = Off 2 = On 3 = No Support deg C deg C
Fan Speed Compressor Utilization Free Cooling Valve Open Position Reheat Utilization Humidifier Utilization Dehumidifier Utilization Free Cooling Status Return Air Temperature Supply Air Temperature This point does not exist in the FDM Free Cooling Fluid Temperature Ext Air Sensor A Temperature Ext Air Sensor B Temperature Ext Air Sensor C Temperature Dig Scroll Comp Discharge Temp 1 Dig Scroll Comp Discharge Temp 2 Return Humidity Ext Air Sensor A Humidity Ext Air Sensor B Humidity Ext Air Sensor C Humidity Fan Hours Compressor Hours 1 Compressor Hours 2 Humidifier Hours Dehumidifier Hours Free Cooling Valve Hours Electric Reheater Hours 1 Electric Reheater Hours 2 Electric Reheater Hours 3 Hot Water / Hot Gas Valve Hours Todays High Air Temperature Todays Low Air Temperature Todays High Humidity Todays Low Humidity Server Class Todays High Air Temperature Time Todays Low Air Temperature Time This point does not exist in the FDM This point does not exist in the FDM This point does not exist in the FDM Todays High Humidity Time
11
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30267 30269 30270 30271 30272 30273 30274 30275 30276 30277 30278 Holding Register 40273 40274 # of Reg. 2 1 1 1 1 1 1 1 1 1 1 Scale 100 100 100 100 Notes / Units 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On 0 = Off / 1 = On % 0 0 0 0 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 0 = Internal (Auto) 1 = External (Manual) 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display % 0 0 % 0 = Off / 1 = On 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm
Todays Low Humidity Time Compressor State 1 Compressor State 2 Compressor Capacity Control State 1 Compressor Capacity Control State 2 Infrared Humidifier Flush Rate This point does not exist in the FDM Analog Input Reading 1 Analog Input Reading 2 Analog Input Reading 3 Analog Input Reading 4
System Status
30279
30280
30281
Maintenance Ramp Calculated Next Maintenance Month Calculated Next Maintenance Year Hot Water / Hot Gas Valve Open Position Maintenance Tracking State Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 2 - Event Control Customer Input 2 - Event Type Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 4 - Event Control Customer Input 4 - Event Type Ext Free Cooling Lockout - Event Control Ext Free Cooling Lockout - Event Type
30282 30283 30284 30285 30286 30287 30288 30289 30290 30291 30292 30293 30294 30295 30296
40287 40288 40289 40290 40291 40292 40293 40294 40295 40296
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
12
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30297 30298 30299 30300 30301 30302 30303 30304 30305 30306 30307 30308 30309 30310 30311 30312 30313 30314 30315 30316 30317 30318 30319 30320 30321 Holding Register 40297 40298 40299 40300 40301 40302 40303 40304 40305 40306 40307 40308 40309 40310 40311 40312 40313 40314 40315 40317 40318 40320 40321 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled
Ext Condenser Pump High Water - Event Control Ext Condenser Pump High Water - Event Type Ext Standby Glycol Pump On - Event Control Ext Standby Glycol Pump On - Event Type Ext Standby Unit On - Event Control Ext Standby Unit On - Event Type Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Loss of Flow - Event Control Ext Loss of Flow - Event Type Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type High Power Shutdown - Event Control High Power Shutdown - Event Type Humidifier Issue - Event Control Humidifier Issue - Event Type Master Unit Communication Lost - Event Control Master Unit Communication Lost - Event Type Service Required - Event Control Service Required - Event Type Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Smoke Detected - Event Control
13
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30322 30323 30324 30325 30326 30327 30328 30329 30330 30331 30332 30333 Holding Register 40322 40323 40324 40325 40326 40327 40328 40329 40330 40331 40332 40333 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled
Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Clogged Air Filter - Event Control Clogged Air Filter - Event Type Ext Loss of Air Blower - Event Control Ext Loss of Air Blower - Event Type Compressor High Head Pressure - Event Control 1 Compressor High Head Pressure - Event Control 2 Compressor High Head Pressure - Event Type 1 Compressor High Head Pressure - Event Type 2 Compressor Low Suction Pressure - Event Control 1 Compressor Low Suction Pressure - Event Control 2 Compressor Low Suction Pressure - Event Type 1 Compressor Low Suction Pressure - Event Type 2 Compressor Pump Down Issue - Event Control 1 Compressor Pump Down Issue - Event Control 2 Compressor Pump Down Issue - Event Type 1 Compressor Pump Down Issue - Event Type 2 Compressor Short Cycle - Event Control 1 Compressor Short Cycle - Event Control 2
1 1 1 1
1 1 1 1
1 1 1
14
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30345 Holding Register 40345 # of Reg. 1 Scale Notes / Units 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm
Compressor Short Cycle - Event Type 2 Compressor Thermal Overload - Event Control 1 Compressor Thermal Overload - Event Control 2 Compressor Thermal Overload - Event Type 1 Compressor Thermal Overload - Event Type 2 Dig Scroll Comp Discharge Over Temp Event Ctrl 1 Dig Scroll Comp Discharge Over Temp Event Ctrl 2 Dig Scroll Comp Discharge Over Temp Event Type 1 Dig Scroll Comp Discharge Over Temp Event Type 2 Ext Air Sensor A High Humidity - Event Control Ext Air Sensor A High Humidity - Event Type Ext Air Sensor A Low Humidity - Event Control Ext Air Sensor A Low Humidity - Event Type Ext Air Sensor A Over Temp - Event Control Ext Air Sensor A Over Temp - Event Type Ext Air Sensor A Under Temp - Event Control Ext Air Sensor A Under Temp - Event Type High Return Humidity - Event Control High Return Humidity - Event Type Low Return Humidity - Event Control Low Return Humidity - Event Type
1 1 1 1
1 1 1 1
30354 30355 30356 30357 30358 30359 30360 30361 30362 30363 30364 30365 30366
1 1 1 1 1 1 1 1 1 1 1 1 1
15
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30367 30368 30369 30370 30371 30372 30373 30374 30375 30376 30377 30378 30379 Holding Register 40367 40369 40371 40373 40374 40375 40376 40377 40378 40379 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Disabled / 1 = Enabled 0 = Disabled / 1 = Enabled 0 = Message 1 = Warning 2 = Alarm 0 = Message 1 = Warning 2 = Alarm 2 = Reset 4 = Acknowledge 0 = Supply 1 = Remote 2 = Return deg C deg C deg C 0 = Relative 1 = Compensated 2 = Predictive 3 = Dew Point deg C deg C deg C 0 = Disabled / 1 = Enabled 0 = Disabled 1 = Contact 2 = Temperature 3 = Set Point 0 = Valve 1 1 = Valve 2 0 = Disabled / 1 = Enabled
Return Air Over Temp - Event Control Return Air Over Temp - Event Type Return Air Under Temp - Event Control Return Air Under Temp - Event Type Fan Hours Exceeded - Event Control Fan Hours Exceeded - Event Type Fan Issue - Event Control Fan Issue - Event Type Main Fan Overload - Event Control Main Fan Overload - Event Type Condenser Issue - Event Control 1 Condenser Issue - Event Control 2 Condenser Issue - Event Type 1
Condenser Issue - Event Type 2 System Event Acknowledge/Reset Air Temperature Control Sensor Supply Air Over Temp Threshold Supply Air Under Temp Threshold Outside Air Temperature Humidity Proportional Control Type Ext Air Sensor A Dew Point Temp Ext Dew Point Over Temp Threshold Ext Dew Point Under Temp Threshold Compressor Lockout Free Cooling Internal Control Mode
30380 30481 30482 30483 30484 30485 30486 30487 30488 30489 30490
40380 40381 40481 40482 40483 40485 40487 40488 40489 40490
1 1 1 1 1 1 1 1 1 1 1 1
10 10 10 10 10 10 -
30491 30492
40491 40492
1 1
16
Table 7
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Data Description Liebert iCOM v4 Input Register 30493 30494 30495 30496 30497 30498 30499 30500 30501 30502 30503 30504 30505 30506 30507 30508 30509 30510 30551 30552 30553 30554 30555 30556 30557 30558 30559 30560 30561 30562 39998 Holding Register 40493 40494 40495 40496 40497 40498 40503 40504 40505 40506 40562 49998 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 Scale 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Notes / Units 0 = Disabled / 1 = Enabled 0 = Supply 1 = Remote 2 = Return 3 = Manual % % deg C 0 % RH deg C deg C % RH deg C 0 = Disabled / 1 = Enabled deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C 0 = Available 1 = Not Available 0 = Disabled 1 = Internal 2 = External -
Humidifier Lockout Fan Control Sensor Fan Speed Minimum Set Point BMS Fan Speed Setting Fan Speed Temperature Set Point Standby Units Adjusted Humidity Return Dew Point Actual Air Temperature Set Point Actual Humidity Set Point Dew Point Set Point Supply Air Over/Under Temperature - Event Control Remote Sensor Over Temp Threshold Remote Sensor Under Temp Threshold Remote Sensor Average Temperature Remote Sensor Maximum Temperature Remote Sensor System Average Temperature Remote Sensor System Maximum Temperature Remote Sensor Temperature 1 Remote Sensor Temperature 2 Remote Sensor Temperature 3 Remote Sensor Temperature 4 Remote Sensor Temperature 5 Remote Sensor Temperature 6 Remote Sensor Temperature 7 Remote Sensor Temperature 8 Remote Sensor Temperature 9 Remote Sensor Temperature 10 Air Economizer Availability Air Economizer Control Source System Date and Time
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
17
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary
Controller Data Description Liebert iCOM v4 Description The actual set point being used for air temperature control. This value may differ from [Air Temperature Set Point] if compensation is applied by the control. The actual set point being used for humidity control. This value may differ from [Humidity Set Point] if compensation is applied by the control. Humidity value being used for control. This value may differ from the actual measured [Return Humidity] based on several factors which may include, but are not limited to, selection of humidity control sensor and humidity control type. Indicates if the outside air conditions are appropriate for cooling with the air economizer. Source of control of the air economizer. Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. Air economizer filter is dirty and needs to be cleaned or replaced. Time value used when system is under integral air temperature control. Sensor from which air temperature measurements will be used for cooling and heating control. Type of algorithm used to control the systems output air temperature. Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Value that is divided evenly to form proportional temperature control bands above and below [Air Temperature Set Point]. Desired air temperature. Ambient air sensor is disconnected or the signal is out of range. Generic analog input reading (unitless). If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Building Management System (or external monitoring system) has not communicated with the system within the expected time frame. Fan speed setting when under the manual control of the Building Management System. Time frame within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled water valve out of position. Chilled water control valve position does not match expected value. Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Clogged Air Filter] event. Air filter is dirty and needs to be (cleaned or) replaced. Compressor capacity control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor capacity has been reduced. Enable/disable the activation of the [Compressor High Head Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor High Head Pressure] event. Compressor is shut down due to high head pressure.
Actual Air Temperature Set Point Actual Humidity Set Point Adjusted Humidity Air Economizer Availability Air Economizer Control Source Air Economizer Emergency Override Air Economizer Reduced Airflow Air Temperature Control Integration Time Air Temperature Control Sensor Air Temperature Control Type Air Temperature Dead Band Air Temperature Proportional Band Air Temperature Set Point Ambient Air Sensor Issue Analog Input Reading Auto Restart Delay BMS Communications Timeout BMS Fan Speed Setting BMS Timeout Period Calculated Next Maintenance Month Calculated Next Maintenance Year Chilled Water Control Valve Position Clogged Air Filter - Event Control Clogged Air Filter - Event Type Clogged Air Filter Compressor Capacity Control State Compressor Capacity Reduced Compressor High Head Pressure Event Control Compressor High Head Pressure Event Type Compressor High Head Pressure
18
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Liebert iCOM v4 Description Compressor high pressure transducer is disconnected or the signal is out of range. [Compressor Hours] has exceeded [Compressor Hours Threshold]. Threshold value used in the [Compressor Hours Exceeded] event. Operating hours for compressor since last reset of this value. Enable/disable the use of the compressor. Compressor low pressure transducer is disconnected or the signal is out of range. Enable/disable the activation of the [Compressor Low Suction Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Low Suction Pressure] event. Compressor is shut down due to low suction pressure. Enable/disable the activation of the [Compressor Pump Down Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Pump Down Issue] event. Unable to pump down suction-side pressure during compressor shutdown. Enable/disable the activation of the [Compressor Short Cycle] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Short Cycle] event. Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. Compressor operational state. Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. Enable/disable the activation of the [Compressor Thermal Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Thermal Overload] event. Compressor is shut down due to thermal overload. Present compressor utilization expressed as a percentage of the maximum rated capacity. Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Condenser Issue] event. Condenser is not operating within its operational parameters. The condenser Transient Voltage Surge Suppressor device has failed. The condenser fan Variable Frequency Drive is offline. Cooling operational state. Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 1] event. Customer Input 1. Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 2] event.
Controller Data Description Compressor High Pressure Transducer Issue Compressor Hours Exceeded Compressor Hours Threshold Compressor Hours Compressor Lockout Compressor Low Pressure Transducer Issue Compressor Low Suction Pressure - Event Control Compressor Low Suction Pressure - Event Type Compressor Low Suction Pressure Compressor Pump Down Issue Event Control Compressor Pump Down Issue Event Type Compressor Pump Down Issue Compressor Short Cycle - Event Control Compressor Short Cycle - Event Type Compressor Short Cycle Compressor State Compressor Superheat Over Threshold Compressor Thermal Overload Event Control Compressor Thermal Overload Event Type Compressor Thermal Overload Compressor Utilization Condenser Issue - Event Control Condenser Issue - Event Type Condenser Issue Condenser TVSS Issue Condenser VFD Issue Cooling State Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 1 Customer Input 2 - Event Control Customer Input 2 - Event Type
19
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Liebert iCOM v4 Description Customer Input 2. Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 3] event. Customer Input 3. Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 4] event. Customer Input 4. Operating hours for the dehumidifier have exceeded the threshold. Threshold value used in the [Dehumidifier Hours Exceeded] event. Operating hours for dehumidifier since last reset of this value. Dehumidifier operational state. Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Dew point temperature reading has exceeded the upper threshold. Desired dew point temperature. Dew point temperature reading has dropped below the lower threshold. Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event. The event type for the [Dig Scroll Comp Discharge Over Temp] event. Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. Digital scroll compressor discharge temperature. Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. Digital output board is required to be connected, but no signal is detected. Electric reheater operational state. [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. Threshold value used in the [Electric Reheater Hours Exceeded] event. Operating hours for electric reheater since last reset of this value. Dew point temperature as measured by external air sensor A. Enable/disable the activation of events related to measurements by the external air sensor A. Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A High Humidity] event. Threshold value used in the [External Air Sensor A High Humidity] event. [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. Relative humidity as measured by external air sensor A. The external air sensor A is disconnected or the signal is out of range. Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A Low Humidity] event.
Controller Data Description Customer Input 2 Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 3 Customer Input 4 - Event Control Customer Input 4 - Event Type Customer Input 4 Dehumidifier Hours Exceeded Dehumidifier Hours Threshold Dehumidifier Hours Dehumidifier State Dehumidifier Utilization Dew Point Over Temperature Dew Point Set Point Dew Point Under Temperature Dig Scroll Comp Discharge Over Temp - Event Ctrl Dig Scroll Comp Discharge Over Temp - Event Type Dig Scroll Comp Discharge Temp Sensor Issue Dig Scroll Comp Discharge Temp Dig Scroll Comp Over Temp Digital Output Board Not Detected Electric Reheat State Electric Reheater Hours Exceeded Electric Reheater Hours Threshold Electric Reheater Hours Ext Air Sensor A Dew Point Temp Ext Air Sensor A Event Control Ext Air Sensor A High Humidity Event Control Ext Air Sensor A High Humidity Event Type Ext Air Sensor A High Humidity Threshold Ext Air Sensor A High Humidity Ext Air Sensor A Humidity Ext Air Sensor A Issue Ext Air Sensor A Low Humidity Event Control Ext Air Sensor A Low Humidity Event Type
20
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Liebert iCOM v4 Description Threshold value used in the [External Air Sensor A Low Humidity] event. [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. Enable/disable the activation of the [External Air Sensor A Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [External Air Sensor A Over Temperature] event. Threshold value used in the [External Air Sensor A Over Temperature] event. [Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp Threshold]. Air temperature as measured by external air sensor A. Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A Under Temperature] event. Threshold value used in the [External Air Sensor A Under Temperature] event. [Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp Threshold]. Relative humidity as measured by external air sensor B. Air temperature as measured by external air sensor B. Relative humidity as measured by external air sensor C. Air temperature as measured by external air sensor C. Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Compressor Lockout] event. The compressor is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Condenser Pump High Water] event. High water is detected in the condenser, as indicated by an external input signal. Threshold value used in the [Ext Dew Point Over Temperature] event. At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. Threshold value used in the [Ext Dew Point Under Temperature] event. At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Free Cooling Lockout] event. Free cooling is disabled by an external input signal.
Controller Data Description Ext Air Sensor A Low Humidity Threshold Ext Air Sensor A Low Humidity Ext Air Sensor A Over Temp - Event Control Ext Air Sensor A Over Temp - Event Type Ext Air Sensor A Over Temp Threshold Ext Air Sensor A Over Temperature Ext Air Sensor A Temperature Ext Air Sensor A Under Temp Event Control Ext Air Sensor A Under Temp Event Type Ext Air Sensor A Under Temp Threshold Ext Air Sensor A Under Temperature Ext Air Sensor B Humidity Ext Air Sensor B Temperature Ext Air Sensor C Humidity Ext Air Sensor C Temperature Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Ext Compressor Lockout Ext Condenser Pump High Water Event Control Ext Condenser Pump High Water Event Type Ext Condenser Pump High Water Ext Dew Point Over Temp Threshold Ext Dew Point Over Temperature Ext Dew Point Under Temp Threshold Ext Dew Point Under Temperature Ext Free Cooling Lockout - Event Control Ext Free Cooling Lockout - Event Type Ext Free Cooling Lockout
21
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Controller Data Description Liebert iCOM v4 Description Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Humidifier Lockout] event. The humidifier is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Loss of Air Blower] event. Loss of air blower is detected, as indicated by an external input signal. Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Loss of Flow] event. Loss of flow is detected, as indicated by an external input signal. Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Over Temperature] event. A temperature has exceeded its threshold, as indicated by an external input signal. Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Reheat Lockout] event. The reheater is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Standby Glycol Pump On] event. The standby glycol pump is on, as indicated by an external input signal. Enable/disable the activation of the [Ext Standby Unit On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Standby Unit On] event. Standby unit is on, as indicated by an external input signal. Fire detected, as indicated by an external input signal. Sensor to be used for fan speed control. Enable/disable the activation of the [Fan Hours Exceeded] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Fan Hours Exceeded] event. Operating hours for the unit blower fan have exceeded the threshold. Threshold value used in the [Fan Hours Exceeded] event. Operating hours for fan since last reset of this value. Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Fan Issue] event. One or more fans are not operating within their operational parameters. Maximum fan speed. Minimum fan speed.
Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Humidifier Lockout Ext Loss of Air Blower - Event Control Ext Loss of Air Blower - Event Type Ext Loss of Air Blower Ext Loss of Flow - Event Control Ext Loss of Flow - Event Type Ext Loss of Flow Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Over Temperature Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type Ext Reheat Lockout Ext Standby Glycol Pump On Event Control Ext Standby Glycol Pump On Event Type Ext Standby Glycol Pump On Ext Standby Unit On - Event Control Ext Standby Unit On - Event Type Ext Standby Unit On External Fire Detected Fan Control Sensor Fan Hours Exceeded - Event Control Fan Hours Exceeded - Event Type Fan Hours Exceeded Fan Hours Threshold Fan Hours Fan Issue - Event Control Fan Issue - Event Type Fan Issue Fan Speed Maximum Set Point Fan Speed Minimum Set Point
22
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Controller Data Description Liebert iCOM v4 Description If fan is in decoupled mode and not under manual control, the fan speed will vary depending on the delta between the selected fan control sensor temperature and this set point. Fan speed expressed as a percentage of the maximum rated speed. Fan operational state. Free cooling fluid temperature. Free cooling internal control mode. Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling. Free cooling operational state. Free cooling status. The free cooling fluid temperature sensor is disconnected or the signal is out of range. [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. Threshold value used in the [Free Cooling Valve Hours Exceeded] event. Operating hours for free cooling valve since last reset of this value. Free cooling valve open position. Enable/disable the activation of the [High Power Shutdown] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [High Power Shutdown] event. Supply to high power components has been shutdown. Enable/disable the activation of the [High Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [High Return Humidity] event. Threshold value used in the [High Return Humidity] event. [Return Humidity] has exceeded [High Return Humidity Threshold]. Hot water / hot gas operational state. [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded] event. Operating hours for hot water / hot gas valve since last reset of this value. Hot water / hot gas valve open position. Humidifier control board is required to be connected, but no signal is detected. Humidifier cylinder is not operating properly and needs to be replaced. Operating hours for the humidifier have exceeded the threshold. Threshold value used in the [Humidifier Hours Exceeded] event. Operating hours for humidifier since last reset of this value. Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Humidifier Issue] event. Humidifier issue detected, causing it to be locked out. Enable/disable the use of the humidifier. The water level in the humidifier has dropped below its threshold. The electrical current to the humidifier has exceeded its upper threshold. Humidifier operational state. The electrical current to the humidifier has dropped below its lower threshold.
Fan Speed Temperature Set Point Fan Speed Fan State Free Cooling Fluid Temperature Free Cooling Internal Control Mode Free Cooling Internal Temperature Delta Free Cooling State Free Cooling Status Free Cooling Temp Sensor Issue Free Cooling Valve Hours Exceeded Free Cooling Valve Hours Threshold Free Cooling Valve Hours Free Cooling Valve Open Position High Power Shutdown - Event Control High Power Shutdown - Event Type High Power Shutdown High Return Humidity - Event Control High Return Humidity - Event Type High Return Humidity Threshold High Return Humidity Hot Water / Hot Gas State Hot Water / Hot Gas Valve Hours Exceeded Hot Water / Hot Gas Valve Hours Threshold Hot Water / Hot Gas Valve Hours Hot Water / Hot Gas Valve Open Position Humidifier Control Board Not Detected Humidifier Cylinder Worn Humidifier Hours Exceeded Humidifier Hours Threshold Humidifier Hours Humidifier Issue - Event Control Humidifier Issue - Event Type Humidifier Issue Humidifier Lockout Humidifier Low Water Humidifier Over Current Humidifier State Humidifier Under Current
23
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Controller Data Description Liebert iCOM v4 Description Present humidifier utilization expressed as a percentage of the maximum rated capacity. Value that is divided evenly to form a range above and below [Humidity Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. Value that is divided evenly to form proportional humidity control bands above and below [Humidity Set Point]. Time value used to add an integral term to proportional humidity control. If set to 0, time will not be a factor in the proportional control algorithm. Type of algorithm to use for proportional control of output humidity. Desired relative humidity. A multiple of an internal time constant that determines the flush duration of the infrared humidifier water pan. No air flow through the unit due to failure of all fans. Enable/disable the activation of the [Low Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Low Return Humidity] event. Threshold value used in the [Low Return Humidity] event. [Return Humidity] has dropped below [Low Return Humidity Threshold]. The primary valve in a dual valve chilled water system. Enable/disable the activation of the [Main Fan Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Main Fan Overload] event. Main fan is shut down due to thermal overload. Maintenance has been completed on the unit. The calculated maintenance date has been reached. The ratio of operations performed to the calculated operations available between maintenance intervals. Maintenance tracking operational state. Enable/disable the activation of the [Master Unit Communication Lost] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Master Unit Communication Lost] event. Communication with master unit has been lost. Enable/disable the activation of [Minimum Chilled Water Temp Set Point]. Minimum desired chilled water temperature. Ambient outside air temperature. RAM or RAM backup battery is not operating correctly. Present reheating utilization expressed as a percentage of the maximum rated capacity. Enable/disable the use of the reheater. The temperature of the reheater has exceeded its threshold. [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Average value of remote sensor temperature measurements. [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Maximum value of remote sensor temperature measurements.
Humidifier Utilization Humidity Dead Band Humidity Proportional Band Humidity Proportional Control Integration Time Humidity Proportional Control Type Humidity Set Point Infrared Humidifier Flush Rate Loss of Air Flow Low Return Humidity - Event Control Low Return Humidity - Event Type Low Return Humidity Threshold Low Return Humidity Main Chilled Water Valve Main Fan Overload - Event Control Main Fan Overload - Event Type Main Fan Overload Maintenance Completed Maintenance Due Maintenance Ramp Maintenance Tracking State Master Unit Communication Lost Event Control Master Unit Communication Lost Event Type Master Unit Communication Lost Minimum Chilled Water Temp Set Point Enable Minimum Chilled Water Temp Set Point Outside Air Temperature RAM Battery Issue Reheat Utilization Reheater Lockout Reheater Over Temperature Remote Sensor Average Over Temperature Remote Sensor Average Temperature Remote Sensor Average Under Temperature Remote Sensor Maximum Temperature
24
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Liebert iCOM v4 Description Threshold value used in the remote air sensor over temperature events. [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Average value of remote sensor temperature measurements among a group of interconnected units in a single system. Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Maximum value of remote sensor temperature measurements among a group of interconnected units in a single system. Air temperature as measured by remote sensor. Threshold value used in the remote air sensor under temperature events. [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Enable/disable the activation of the [Return Air Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Return Air Over Temperature] event. Threshold value used in the [Return Air Over Temperature] event. [Return Air Temperature] has exceeded [Return Air Over Temp Threshold]. Enable/disable the activation of events related to measurements by the return air sensor. The air sensor at the inlet of the unit is disconnected or the signal is out of range. The temperature of the inlet air. Enable/disable the activation of the [Return Air Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Return Air Under Temperature] event. Threshold value used in the [Return Air Under Temperature] event. [Return Air Temperature] has dropped below [Return Air Under Temp Threshold]. Dew point temperature measured at the inlet of the unit. Relative humidity measured at the inlet of the unit. The general classification for this system. Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Service Required] event. Unit requires servicing. Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Shutdown - Loss Of Power] event. System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Smoke Detected] event. Smoke detected.
Controller Data Description Remote Sensor Over Temp Threshold Remote Sensor Over Temperature Remote Sensor System Average Over Temperature Remote Sensor System Average Temperature Remote Sensor System Average Under Temperature Remote Sensor System Maximum Temperature Remote Sensor Temperature Remote Sensor Under Temp Threshold Remote Sensor Under Temperature Return Air Over Temp - Event Control Return Air Over Temp - Event Type Return Air Over Temp Threshold Return Air Over Temperature Return Air Sensor Event Control Return Air Sensor Issue Return Air Temperature Return Air Under Temp - Event Control Return Air Under Temp - Event Type Return Air Under Temp Threshold Return Air Under Temperature Return Dew Point Return Humidity Server Class Service Required - Event Control Service Required - Event Type Service Required Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Shutdown - Loss Of Power Smoke Detected - Event Control Smoke Detected - Event Type Smoke Detected
25
Table 8
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Liebert iCOM v4 Description The number of standby units. Threshold value used in the [Supply Air Over Temperature] event. [Supply Air Temperature] has exceeded [Supply Air Over Temp Threshold]. Enable/disable the activation of the [Supply Air Over Temperature] and [Supply Air Under Temperature] events. The air sensor at the outlet of the unit is disconnected or the signal is out of range. Air temperature measured at the outlet of the unit. Threshold value used in the [Supply Air Under Temperature] event. [Supply Air Temperature] has dropped below [Supply Air Under Temp Threshold]. Supply chilled water flow is too low. [Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over Temp Threshold]. System control mode. The system date and time. Reset and/or acknowledge all events. Turn system functionality on or off. The reason the system is in the current operating state. Current operating state of the system. The operating status for the system. This point does not exist in the FDM. [Todays High Air Temperature] was measured at this time. The highest external air temperature measured since midnight. [Todays High Humidity] was measured at this time. The highest external humidity measured since midnight. [Todays Low Air Temperature] was measured at this time. The lowest external air temperature measured since midnight. [Todays Low Humidity] was measured at this time. The lowest external humidity measured since midnight. Unit code has not been entered and saved. Master has lost communication with one or more networked units. Unit was turned off. Unit was turned on. An event has occurred requiring some system components to be shutdown and disabled. An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit was placed in standby mode. One or more unspecified events active. See local unit display for further details. The water leakage detector sensor is disconnected or the signal is out of range. Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Water Under Floor] event. Water under the floor is detected.
Controller Data Description Standby Units Supply Air Over Temp Threshold Supply Air Over Temperature Supply Air Over/Under Temperature - Event Control Supply Air Sensor Issue Supply Air Temperature Supply Air Under Temp Threshold Supply Air Under Temperature Supply Chilled Water Loss of Flow Supply Chilled Water Over Temp System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status This point does not exist in the FDM Todays High Air Temperature Time Todays High Air Temperature Todays High Humidity Time Todays High Humidity Todays Low Air Temperature Time Todays Low Air Temperature Todays Low Humidity Time Todays Low Humidity Unit Code Missing Unit Communication Lost Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Unspecified General Event Water Leakage Detector Sensor Issue Water Under Floor - Event Control Water Under Floor - Event Type Water Under Floor
26
Table 9
Supply Air Over Temperature Supply Air Under Temperature Return Air Over Temperature Supply Air Sensor Issue High Return Humidity Low Return Humidity Humidifier Hours Exceeded Dehumidifier Hours Exceeded Humidifier Under Current Humidifier Over Current Humidifier Low Water Humidifier Cylinder Worn Humidifier Issue Ext Humidifier Lockout Humidifier Control Board Not Detected Return Humidity Out Of Proportional Band Loss of Air Flow Fan Hours Exceeded Top Fan Issue Bottom Fan Issue Remote Sensor Issue Module Index 1 Remote Sensor Issue Module Index 2 Remote Sensor Issue Module Index 3 Remote Sensor Issue Module Index 4 Remote Sensor Issue Module Index 5 Remote Sensor Issue Module Index 6 Remote Sensor Issue Module Index 7 Remote Sensor Issue Module Index 8 Remote Sensor Issue Module Index 9 Remote Sensor Issue Module Index 10 Compressor 1 High Head Pressure Compressor 1 Low Suction Pressure Compressor 1 Hours Exceeded Dig Scroll Comp 1 Temp Sensor Issue Dig Scroll Comp 1 Over Temp Compressor 1 Low Pressure Transducer Issue Ext Compressor Lockout Compressor 1 Short Cycle Compressor 1 High Pressure Transducer Issue Compressor 1 Pump Down Issue Reheater Over Temperature Electric Reheater 1 Hours Exceeded
27
Table 9
Ext Reheat Lockout Condenser 1 Issue Condenser VFD Issue Condenser TVSS Issue Supply Chilled Water Over Temp Chilled Water Control Valve Position Supply Chilled Water Loss of Flow Supply Fluid Temp Sensor Issue Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Smoke Detected Water Under Floor Service Required Shutdown -Loss Of Power Ext Over Temperature Ext Loss of Flow Ext Condenser Pump High Water Ext Standby Glycol Pump On External Fire Detected Unit On Unit Off Unit Standby Unit Partial Shutdown Unit Shutdown Water Leakage Detector Sensor Issue BMS Communications Timeout Maintenance Due Maintenance Completed Clogged Air Filter RAM Battery Issue Master Unit Communication Lost High Power Shutdown Return Air Sensor Issue
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
28
Table 10
Supply Air Temperature Supply Air Temperature Return Air Temperature Return Air Temperature Return Dew Point Return Dew Point Remote Sensor Minimum Temperature Remote Sensor Minimum Temperature Remote Sensor Maximum Temperature Remote Sensor Maximum Temperature Remote Sensor Average Temperature Remote Sensor Average Temperature Air Temperature Set Point Air Temperature Set Point Cooling Proportional Band Cooling Proportional Band Heating Proportional Band Heating Proportional Band Air Temperature Dead Band Air Temperature Dead Band Supply Air Over Temp Threshold Supply Air Over Temp Threshold Supply Air Under Temp Threshold Supply Air Under Temp Threshold Return Air Over Temp Threshold Return Air Over Temp Threshold Supply Humidity Return Humidity Humidity Set Point Humidification Proportional Band Dehumidification Proportional Band Humidity Dead Band High Return Humidity Threshold Low Return Humidity Threshold Fan Speed Proportional Band Fan Speed Proportional Band Fan Speed Manual Set Point Fan Speed Maximum Set Point Fan Speed Minimum Set Point Remote Sensor Temperature Module Index 1 Remote Sensor Temperature Module Index 2 Remote Sensor Temperature Module Index 3 Remote Sensor Temperature Module Index 4 Remote Sensor Temperature Module Index 5 Remote Sensor Temperature Module Index 6
29
Table 10
Remote Sensor Temperature Module Index 7 Remote Sensor Temperature Module Index 8 Remote Sensor Temperature Module Index 9 Remote Sensor Temperature Module Index 10 Remote Sensor Temperature Module Index 1 Remote Sensor Temperature Module Index 2 Remote Sensor Temperature Module Index 3 Remote Sensor Temperature Module Index 4 Remote Sensor Temperature Module Index 5 Remote Sensor Temperature Module Index 6 Remote Sensor Temperature Module Index 7 Remote Sensor Temperature Module Index 8 Remote Sensor Temperature Module Index 9 Remote Sensor Temperature Module Index 10 Supply Chilled Water Temperature Supply Chilled Water Temperature Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Threshold BMS Timeout Period Auto Restart Delay Operating Efficiency Fan Speed Compressor Utilization Dehumidifier Utilization Reheat Utilization Humidifier Utilization Calculated Next Maintenance Month Calculated Next Maintenance Year Maintenance Ramp Server Class
Air Temperature Control Sensor Remote Sensor Temperature Calculation Fan Control Mode Fan Control Sensor
1 1 1 1
30464
40464
30
Table 10
30466
40466
30467
40467
30468
40468
30469
40469
30470
40470
30471
40471
30472
40472
30473
40473
System Status
30474
30475 30476
1 1
30477
30478
40478 40479
1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
31
Table 11
Supply Air Over Temperature Supply Air Under Temperature Return Air Over Temperature Supply Air Sensor Issue High Return Humidity Low Return Humidity Humidifier Hours Exceeded Dehumidifier Hours Exceeded Humidifier Under Current Humidifier Over Current Humidifier Low Water Humidifier Cylinder Worn Humidifier Issue Ext Humidifier Lockout Humidifier Control Board Not Detected Return Humidity Out Of Proportional Band Loss of Air Flow Fan Hours Exceeded Top Fan Issue Bottom Fan Issue Remote Sensor Issue 1 - 10 Compressor 1 High Head Pressure Compressor 1 Low Suction Pressure Compressor 1 Hours Exceeded Dig Scroll Comp 1 Temp Sensor Issue Dig Scroll Comp 1 Over Temp Compressor 1 Low Pressure Transducer Issue Ext Compressor Lockout Compressor 1 Short Cycle Compressor 1 High Pressure Transducer Issue Compressor 1 Pump Down Issue Reheater Over Temperature Electric Reheater Hours Exceeded Ext Reheat Lockout Condenser 1 Issue Condenser VFD Issue Condenser TVSS Issue
32
Table 11
Supply Chilled Water Over Temp Chilled Water Control Valve Position Supply Chilled Water Loss of Flow Supply Fluid Temp Sensor Issue Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Smoke Detected Water Under Floor Service Required Shutdown - Loss Of Power Ext Over Temperature Ext Loss of Flow Ext Condenser Pump High Water Ext Standby Glycol Pump On External Fire Detected Unit On Unit Off Unit Standby Unit Partial Shutdown Unit Shutdown Water Leakage Detector Sensor Issue BMS Communications Timeout Maintenance Due Maintenance Completed Clogged Air Filter RAM Battery Issue Master Unit Communication Lost High Power Shutdown Return Air Sensor Issue Supply Air Temperature Supply Air Temperature Return Air Temperature Return Air Temperature Return Dew Point Return Dew Point Remote Sensor Minimum Temperature
33
Table 11
Remote Sensor Minimum Temperature Remote Sensor Maximum Temperature Remote Sensor Maximum Temperature Remote Sensor Average Temperature Remote Sensor Average Temperature Air Temperature Set Point Air Temperature Set Point Cooling Proportional Band
Air Temperature Dead Band Supply Air Over Temp Threshold Supply Air Over Temp Threshold Supply Air Under Temp Threshold Supply Air Under Temp Threshold Return Air Over Temp Threshold Return Air Over Temp Threshold Supply Humidity Return Humidity Humidity Set Point Humidification Proportional Band Dehumidification Proportional Band Humidity Dead Band High Return Humidity Threshold Low Return Humidity Threshold Fan Speed Proportional Band
34
Table 11
Fan Speed Manual Set Point Fan Speed Maximum Set Point Fan Speed Minimum Set Point Remote Sensor Temperature 1 - 10 Remote Sensor Temperature 1 - 10 Supply Chilled Water Temperature Supply Chilled Water Temperature Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Threshold BMS Timeout Period Auto Restart Delay Operating Efficiency Fan Speed Compressor Utilization Dehumidifier Utilization Reheat Utilization Humidifier Utilization Calculated Next Maintenance Month Calculated Next Maintenance Year Maintenance Ramp Server Class Air Temperature Control Sensor Remote Sensor Temperature Calculation Fan Control Mode Fan Control Sensor Remote Sensor Function 1 - 10 System Status System Operating State System Control Mode System Operating State Reason System On/Off Control System Event Acknowledge/Reset System Date and Time
35
Table 12
Compressors Compressor Not Stopping Compressor 1 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Thermal Overload Compressor Low Oil Pressure Compressor Head Pressure Over Threshold Compressor Loss of Differential Pressure Compressor Capacity Reduced Compressor 2 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Thermal Overload Compressor Low Oil Pressure Compressor Head Pressure Over Threshold Compressor Loss of Differential Pressure Compressor Capacity Reduced Condensers 1 Condenser Fan Issue Low Condenser Refrigerant Pressure Condenser Max Fan Speed Override Condensers 1 Condenser Fan Issue Low Condenser Refrigerant Pressure Condenser Max Fan Speed Override Fluid Low Fluid Pressure Supply (Outlet) Fluid Supply Fluid Over Temp Supply Fluid Under Temp Supply Fluid Temp Sensor Issue Return (Inlet) Fluid Return Fluid Over Temp Return Fluid Under Temp Return Fluid Temp Sensor Issue Pumps 10094 10095 10096 1 1 1
36
Table 12
All Pumps Loss of Flow Pump 1 Loss of Flow Pump 2 Loss of Flow Pump 1 Pump Hours Exceeded Pump 2 Pump Hours Exceeded Free Cooling Free Cooling Valve Hours Exceeded Ambient Air Temperature Sensor Issue Evaporators Evaporator Inlet Temp Sensor Issue Evaporator Return Fluid Over Temp Evaporator Return Fluid Under Temp Evaporator 1 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required Supply Refrigerant Temp Sensor Issue Evaporator 2 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required Supply Refrigerant Temp Sensor Issue System Events Customer Input 1 Customer Input 2 Unit On Unit Off Master Unit Communication Lost Subgroup Event Occurred During Communication Loss Humidifier Control Board Not Detected RAM Battery Issue Unit Code Missing Unspecified General Event
37
Table 13
Data Label Server Class Compressors Compressor Shut Down - Ambient Air Low Temp Limit Compressor Shut Down - Ambient Air Low Temp Limit Compressor 1 Compressor State Compressor Capacity Control State Compressor Head Pressure Compressor Hours Compressor Hours Threshold Compressor 2 Compressor State Compressor Capacity Control State Compressor Head Pressure Compressor Hours Compressor Hours Threshold Condensers 1 Condenser Fan Speed Condensers 2 Condenser Fan Speed Fluid Fluid Pressure Fluid Cooling Proportional Band Fluid Cooling Proportional Band Supply (Outlet) Fluid Supply Fluid Temp Set Point 1 Supply Fluid Temp Set Point 1 Supply Fluid Temp Set Point 2 Supply Fluid Temp Set Point 2 Supply Fluid Over Temp Warning Threshold Supply Fluid Over Temp Warning Threshold Supply Fluid Over Temp Alarm Threshold Supply Fluid Over Temp Alarm Threshold
30389 30390
40389 40390
1 1
1 1 1 1 1 Scale : x / 10
0 = off 1 = on 0 = off 1 = on Units : bar Units : hr Units : hr 0 = off 1 = on 0 = off 1 = on Scale : x / 10 Units : bar Units : hr Units : hr Units : % Units : % Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Units : bar Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F
30402 30403 30404 30405 30406 30410 30414 30418 30419 30420 30424 30425 30426 30427 30428 30429 30430 30431 40419 40420 40424 40425 40426 40427 40428 40429 40430 40431 40405 40406
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
38
Table 13
Data Label Supply Fluid Under Temp Warning Threshold Supply Fluid Under Temp Warning Threshold Supply Fluid Under Temp Alarm Threshold Supply Fluid Under Temp Alarm Threshold Return (Inlet) Fluid Return Fluid Over Temp Warning Threshold Return Fluid Over Temp Warning Threshold Return Fluid Over Temp Alarm Threshold Return Fluid Over Temp Alarm Threshold Return Fluid Under Temp Warning Threshold Return Fluid Under Temp Warning Threshold Return Fluid Under Temp Alarm Threshold Return Fluid Under Temp Alarm Threshold Pump 1 Pump Hours Pump Hours Threshold Pump 2 Pump Hours Pump Hours Threshold Free Cooling Free Cooling External Temperature Delta Free Cooling External Temperature Delta Free Cooling Status Free Cooling Valve Open Position Free Cooling Valve Hours
30439
40439
Units : deg C Only supported in FDM Version 28 Units : deg F Only supported in FDM Version 28 Units : deg C Only supported in FDM Version 28 Units : deg F Only supported in FDM Version 28 Units : deg C Only supported in FDM Version 28 Units : deg F Only supported in FDM Version 28 Units : deg C Only supported in FDM Version 28 Units : deg F Only supported in FDM Version 28 Units : hr Units : hr Units : hr Units : hr
30440
40440
30441
40441
30442
40442
30443
40443
30444
40444
30445
40445
30446
40446
1 1 1 1
40460 40461
1 1 1 1
40464
39
Table 13
Data Label Free Cooling Valve Hours Threshold Evaporators Evaporator Return Fluid Temperature Evaporator Return Fluid Temperature Evaporator Return Fluid Over Temp Alarm Threshold Evaporator Return Fluid Over Temp Alarm Threshold Evaporator Return Fluid Over Temp Warning Threshold Evaporator Return Fluid Over Temp Warning Threshold Evaporator Return Fluid Under Temp Warning Threshold Evaporator Return Fluid Under Temp Warning Threshold Evaporator Return Fluid Under Temp Alarm Threshold Evaporator Return Fluid Under Temp Alarm Threshold Brine Supply Brine Temp Set Point Supply Brine Temp Set Point Standby Units Standby Units System Info
30469 30470 30615 30616 30617 30618 30619 30620 30621 30622 40615 40616 40617 40618 40619 40620 40621 40622
1 1 1 1 1 1 1 1 1 1
Scale : x / 10 Scale : x / 10
Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F Units : deg C Units : deg F
1 1 1
System Status
30483
1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 0 = off 1 = on 2 = standby 0 = Internal (Auto) 1 = External (Manual) 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display 0 = off 1 = on
30484 30485
1 1
30486
30487
40487
40
Table 13
Data Label System Operations Return Fluid Temperature Return Fluid Temperature Supply Fluid Temperature Supply Fluid Temperature Actual Supply Fluid Temp Set Point Actual Supply Fluid Temp Set Point Condenser Inlet Water Temperature Condenser Inlet Water Temperature Condenser Outlet Water Temperature Condenser Outlet Water Temperature Supply Heated Water Temp Set Point Supply Heated Water Temp Set Point Free Cooling Utilization Reheat Utilization Compressor Utilization Ambient Air Temperature Ambient Air Temperature Compressor Economizer Utilization Condenser Adiabatic Cooling Utilization Pump 1 State Pump 2 State System Events System Event Acknowledge/Reset Time System Date and Time
40515
39998
49998
41
Table 14
Data Label
Actual Supply Fluid Temp Set Point All Pumps Loss of Flow Ambient Air Temperature Sensor Issue Ambient Air Temperature Compressor Capacity Control State Compressor Capacity Reduced Compressor Economizer Utilization Compressor Head Pressure Over Threshold Compressor Head Pressure Compressor High Head Pressure Compressor Hours Exceeded Compressor Hours Threshold Compressor Hours Compressor Loss of Differential Pressure Compressor Low Oil Pressure Compressor Low Suction Pressure Compressor Not Stopping Compressor Shut Down - Ambient Air Low Temp Limit Compressor State Compressor Thermal Overload Compressor Utilization Condenser Adiabatic Cooling Utilization Condenser Fan Issue Condenser Fan Speed Condenser Inlet Water Temperature Condenser Max Fan Speed Override Condenser Outlet Water Temperature Customer Input 1 Customer Input 2 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required
42
Table 14
Data Label
Evaporator Inlet Temp Sensor Issue Evaporator Return Fluid Over Temp Alarm Threshold Evaporator Return Fluid Over Temp Warning Threshold Evaporator Return Fluid Over Temp Evaporator Return Fluid Temperature Evaporator Return Fluid Under Temp Alarm Threshold Evaporator Return Fluid Under Temp Warning Threshold Evaporator Return Fluid Under Temp Fluid Cooling Proportional Band Fluid Pressure Free Cooling External Temperature Delta Free Cooling Status Free Cooling Utilization Free Cooling Valve Hours Exceeded Free Cooling Valve Hours Threshold Free Cooling Valve Hours Free Cooling Valve Open Position Humidifier Control Board Not Detected Low Condenser Refrigerant Pressure Low Fluid Pressure Master Unit Communication Lost Pump 1 Loss of Flow Pump 1 State Pump 2 Loss of Flow Pump 2 State Pump Hours Exceeded Pump Hours Threshold Pump Hours RAM Battery Issue Reheat Utilization Return Fluid Over Temp Alarm Threshold
43
Table 14
Data Label
Return Fluid Over Temp Warning Threshold Return Fluid Over Temp Return Fluid Temp Sensor Issue Return Fluid Temperature Return Fluid Under Temp Alarm Threshold Return Fluid Under Temp Warning Threshold Return Fluid Under Temp Server Class Standby Units Subgroup Event Occurred During Communication Loss Supply Brine Temp Set Point Supply Fluid Over Temp Alarm Threshold Supply Fluid Over Temp Warning Threshold Supply Fluid Over Temp Supply Fluid Temp Sensor Issue Supply Fluid Temp Set Point 1 Supply Fluid Temp Set Point 2 Supply Fluid Temperature Supply Fluid Under Temp Alarm Threshold Supply Fluid Under Temp Warning Threshold Supply Fluid Under Temp Supply Heated Water Temp Set Point Supply Refrigerant Temp Sensor Issue System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status Unit Code Missing Unit Off Unit On Unspecified General Event
44
Table 15
Pump 1 Loss of Flow Pump 2 Loss of Flow Fan Issue System Condensation Detected Customer Input 1 Supply Refrigerant Over Temp Supply Refrigerant Under Temp Supply Refrigerant Temp Sensor Issue Ext Air Sensor A Over Temperature Ext Air Sensor A Under Temperature Ext Air Sensor A Issue Ext Air Sensor B Over Temperature Ext Air Sensor B Under Temperature Ext Air Sensor B Issue Ext Dew Point Over Temperature Pump Short Cycle Compressor 1A High Head Pressure Compressor 1B High Head Pressure Compressor 2A High Head Pressure Compressor 2B High Head Pressure Compressor 1A Short Cycle Compressor 1B Short Cycle Compressor 2A Short Cycle Compressor 2B Short Cycle Circuit 1 Low Suction Pressure Circuit 2 Low Suction Pressure Shutdown - Loss Of Power Smoke Detected Water Under Floor Service Required
45
Table 16
Pump 1 State Pump 2 State Supply Refrigerant Temperature Supply Refrigerant Temperature System Operating State Ext Air Sensor A Temperature Ext Air Sensor A Temperature Ext Air Sensor A Humidity Ext Air Sensor A Dew Point Temp Ext Air Sensor A Dew Point Temp Ext Air Sensor B Temperature Ext Air Sensor B Temperature Ext Air Sensor B Humidity Ext Air Sensor B Dew Point Temp Ext Air Sensor B Dew Point Temp Dew Point Temperature Dew Point Temperature Minimum Room Temperature Set Point Minimum Room Temperature Set Point Ext Air Over Temp Threshold Ext Air Over Temp Threshold Ext Air Under Temp Threshold Ext Air Under Temp Threshold Ext Dew Point Over Temp Threshold Ext Dew Point Over Temp Threshold Supply Refrig Over Temp Threshold Supply Refrig Over Temp Threshold Hot Gas Valve 1 Open Position Hot Gas Valve 2 Open Position Hot Gas Solenoid Valve 1 Position Hot Gas Solenoid Valve 2 Position Compressor 1A State Compressor 1B State Compressor 2A State Compressor 2B State Calculated Next Maintenance Month Calculated Next Maintenance Year
System Status
30422
30423 30424
1 1
46
Table 16
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
47
Table 17
Pumps Pump 1 Loss of Flow Pump 2 Loss of Flow Pump Short Cycle System Events Fan Issue System Condensation Detected Customer Input 1 Shutdown - Loss Of Power Water Under Floor Smoke Detected Service Required Unit Communication Lost RAM Battery Issue Master Unit Communication Lost Remote Shutdown Unit Code Missing Chilled Water Supply Chilled Water Over Temp Supply Chilled Water Temp Sensor Issue Chilled Water Control Valve Position Refrigerant Supply Refrigerant Over Temp Supply Refrigerant Under Temp Supply Refrigerant Temp Sensor Issue External Air Ext Air Sensor A Over Temperature Ext Air Sensor A Under Temperature Ext Air Sensor A Issue Ext Air Sensor B Over Temperature Ext Air Sensor B Under Temperature Ext Air Sensor B Issue Ext Dew Point Over Temperature Pump Hours 1 Pump Hours Exceeded Pump Hours 2 Pump Hours Exceeded XD System 1 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown
48
Table 17
Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range XD System 2 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range XD System 20 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range Messages Unit On Unit Off Unit Standby Unit Partial Shutdown Unit Shutdown Maintenance Due Maintenance Completed SFA Report SFA Reserved Event 1 SFA Reserved Event 2 SFA Reserved Event 3 SFA Reserved Event 4 SFA Reserved Event 5 SFA Reserved Event 6 SFA Reserved Event 7 SFA Reserved Event 8 SFA Reserved Event 9 SFA Reserved Event 10 SFA Reserved Event 11 SFA Reserved Event 12 SFA Reserved Event 13 SFA Reserved Event 14 SFA Reserved Event 15 SFA Reserved Event 16 SFA Reserved Event 17
49
Table 17
SFA Reserved Event 18 SFA Reserved Event 19 SFA Reserved Event 20 SFA Reserved Event 21 SFA Reserved Event 22 SFA Reserved Event 23 SFA Reserved Event 24 SFA Reserved Event 25
50
Table 18
Pumps
Pump 1 State Pump 2 State Refrigerant Supply Refrigerant Temperature Supply Refrigerant Temperature Supply Refrig Over Temp Threshold Supply Refrig Over Temp Threshold Chilled Water Supply Chilled Water Temperature Supply Chilled Water Temperature Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Threshold Chilled Water Valve Open Position System Information
30385 30386
1 1
30387 30388 30411 30412 30389 30390 30413 30414 31710 40413 40414 40411 40412
1 1 1 1 1 1 1 1 1
System Status
30391
1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 0 = off 1 = on 2 = standby Units : sec 0 = Internal (Auto) 1 = External (Manual) Units : %
System Operating State Auto Restart Delay System Control Mode Maintenance Ramp Calculated Next Maintenance Month Calculated Next Maintenance Year System On/Off Control
1 1 1 1 1 1 1
0 = off 1 = on 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Scale : x / 10 Units : deg C Units : deg F Units : % RH Units : deg C Units : deg F Units : deg C Units : deg F Units : % RH
31704
External Air Ext Air Sensor A Temperature Ext Air Sensor A Temperature Ext Air Sensor A Humidity Ext Air Sensor A Dew Point Temp Ext Air Sensor A Dew Point Temp Ext Air Sensor B Temperature Ext Air Sensor B Temperature Ext Air Sensor B Humidity 30393 30394 30395 30396 30397 30398 30399 30400 1 1 1 1 1 1 1 1
51
Table 18
Ext Air Sensor B Dew Point Temp Ext Air Sensor B Dew Point Temp Minimum Room Temperature Set Point Minimum Room Temperature Set Point Ext Air Over Temp Threshold Ext Air Over Temp Threshold Ext Air Under Temp Threshold Ext Air Under Temp Threshold Ext Dew Point Over Temp Threshold Ext Dew Point Over Temp Threshold Dew Point Temperature Dew Point Temperature Time System Date and Time Pump Hours 1 Pump Hours Pump Hours Threshold Pump Hours 2 Pump Hours Pump Hours Threshold XD System 1 Communication Status Fan On/Off Control Primary Fan Group State Fan Button Control Visual ID Control Cooling Capacity Cooling Capacity Ext System Condensation Detected - Event Control Ext System Condensation Detected - Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control
30444 30445 30446 30447 30448 30449 30450 30451 30452 30453 30454 30455 40451 40452 40453 40454 40455 40447 40448 40445
1 1 1 1 1 1 1 1 1 1 1 1
52
Table 18
Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type Hot Aisle Over Temp Threshold Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold Cold Aisle Under Temp Threshold XD System 2 Communication Status Fan On/Off Control Primary Fan Group State Fan Button Control Visual ID Control Cooling Capacity Cooling Capacity Ext System Condensation Detected - Event Control Ext System Condensation Detected - Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type Hot Aisle Over Temp Threshold
30472 30473 30474 30475 30476 30477 30478 30479 30480 30481 30482 30483 30484 30485 30486 30487 40479 40480 40481 40482 40483 40484 40485 40486 40487 40475 40476 40473
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
53
Table 18
Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold Cold Aisle Under Temp Threshold XD System 20 Communication Status Fan On/Off Control Primary Fan Group State Fan Button Control Visual ID Control Cooling Capacity Cooling Capacity Ext System Condensation Detected - Event Control Ext System Condensation Detected - Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type Hot Aisle Over Temp Threshold Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold Cold Aisle Under Temp Threshold
30976 30977 30978 30979 30980 30981 30982 30983 30984 30985 30986 30987 30988 30989 30990 30991 30992 30993 30994 30995 30996 30997 30998 40983 40984 40985 40986 40987 40988 40989 40990 40991 40992 40993 40994 40995 40996 40997 40998 40979 40980 40977
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
54
Table 18
XD System 1 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 1 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 1 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 1 Secondary Fans Fan State 31032 1
Fan Economy Mode XD System 2 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 2 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 2 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 2 Secondary Fans Fan State
31033
41033
1 1 1 1 1 1
31067
Fan Economy Mode XD System 3 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 3 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 3 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 3 Secondary Fans Fan State
31068
41068
1 1 1 1 1 1
31102
55
Table 18
Fan Economy Mode XD System 4 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 4 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 4 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 4 Secondary Fans Fan State
1 1 1 1 1 1
31137
Fan Economy Mode XD System 5 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 5 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 5 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 5 Secondary Fans Fan State
31138
41138
1 1 1 1 1 1
31172
Fan Economy Mode XD System 6 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 6 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 6 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 6 Secondary Fans
31173
41173
1 1 1 1 1 1
56
Table 18
Fan State
Fan Economy Mode XD System 7 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 7 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 7 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 7 Secondary Fans Fan State
31208
41208
1 1 1 1 1 1
31242
Fan Economy Mode XD System 8 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 8 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 8 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 8 Secondary Fans Fan State
31243
41243
1 1 1 1 1 1
31277
Fan Economy Mode XD System 9 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 9 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 9 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature
31278
41278
1 1 1 1 1 1
57
Table 18
Fan Economy Mode XD System 10 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 10 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 10 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 10 Secondary Fans Fan State
31313
41313
1 1 1 1 1 1
31347
Fan Economy Mode XD System 11 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 11 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 11 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 11 Secondary Fans Fan State
31348
41348
1 1 1 1 1 1
31382
Fan Economy Mode XD System 12 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 12 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 12 Temperature Sensor 4 Remote Sensor Temperature
31383
41383
1 1 1 1 1
58
Table 18
31417
Fan Economy Mode XD System 13 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 13 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 13 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 13 Secondary Fans Fan State
31418
41418
1 1 1 1 1 1
31452
Fan Economy Mode XD System 14 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 14 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 14 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 14 Secondary Fans Fan State
31453
41453
1 1 1 1 1 1
31487
Fan Economy Mode XD System 15 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 15 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 15 Temperature Sensor 4
31488
41488
1 1 1 1
59
Table 18
Remote Sensor Temperature Remote Sensor Temperature XD System 15 Secondary Fans Fan State
31522
Fan Economy Mode XD System 16 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 16 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 16 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 16 Secondary Fans Fan State
31523
41523
1 1 1 1 1 1
31557
Fan Economy Mode XD System 17 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 17 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 17 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 17 Secondary Fans Fan State
31558
41558
1 1 1 1 1 1
31592
Fan Economy Mode XD System 18 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 18 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature
31593
41593
1 1 1 1
60
Table 18
XD System 18 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 18 Secondary Fans Fan State 31627 1
Fan Economy Mode XD System 19 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 19 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 19 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 19 Secondary Fans Fan State
31628
41628
1 1 1 1 1 1
31662
Fan Economy Mode XD System 20 Temperature Sensor 1 Remote Sensor Temperature Remote Sensor Temperature XD System 20 Temperature Sensor 2 Remote Sensor Temperature Remote Sensor Temperature XD System 20 Temperature Sensor 4 Remote Sensor Temperature Remote Sensor Temperature XD System 20 Secondary Fans Fan State
31663
41663
1 1 1 1 1 1
31697
Fan Economy Mode SFA Report SFA ID Number SFA 16bit Read Only Value 1 SFA 16bit Read Only Value 2 SFA 16bit Read Only Value 3
31698
41698
2 1 1 1
61
Table 18
SFA 16bit Read Only Value 4 SFA 16bit Read Only Value 5 SFA 16bit Read Only Value 6 SFA 16bit Read Only Value 7 SFA 16bit Read Only Value 8 SFA 16bit Read Only Value 9 SFA 16bit Read Only Value 10 SFA 32bit Read Only Value 1 SFA 32bit Read Only Value 2 SFA 32bit Read Only Value 3 SFA 32bit Read Only Value 4 SFA 32bit Read Only Value 5 SFA 32bit Read Only Value 6 SFA 32bit Read Only Value 7 SFA 32bit Read Only Value 8 SFA 32bit Read Only Value 9 SFA 32bit Read Only Value 10 SFA 16bit Writable Value 1 SFA 16bit Writable Value 2 SFA 16bit Writable Value 3 SFA 16bit Writable Value 4 SFA 16bit Writable Value 5 SFA 16bit Writable Value 6 SFA 16bit Writable Value 7 SFA 16bit Writable Value 8 SFA 16bit Writable Value 9 SFA 16bit Writable Value 10 SFA 32bit Writable Value 1 SFA 32bit Writable Value 2 SFA 32bit Writable Value 3 SFA 32bit Writable Value 4 SFA 32bit Writable Value 5 SFA 32bit Writable Value 6 SFA 32bit Writable Value 7 SFA 32bit Writable Value 8 SFA 32bit Writable Value 9 SFA 32bit Writable Value 10
62
Table 19
Auto Restart Delay Calculated Next Maintenance Month Calculated Next Maintenance Year Chilled Water Control Valve Failure Chilled Water Valve Open Position Cold Aisle Over Temp Threshold Cold Aisle Temp Out of Range Cold Aisle Under Temp Threshold Communication Status Cooling Capacity Cooling Capacity Customer Input 1 Dew Point Temperature Ext Air Over Temp Threshold Ext Air Sensor A Dew Point Temp Ext Air Sensor A Humidity Ext Air Sensor A Issue Ext Air Sensor A Over Temperature Ext Air Sensor A Temperature Ext Air Sensor A Under Temperature Ext Air Sensor B Dew Point Temp Ext Air Sensor B Humidity Ext Air Sensor B Issue Ext Air Sensor B Over Temperature Ext Air Sensor B Temperature Ext Air Sensor B Under Temperature Ext Air Under Temp Threshold Ext Dew Point Over Temp Threshold Ext Dew Point Over Temperature
Ext Fan Issue - Event Control Ext Fan Issue - Event Type Ext Fan Issue
63
Table 19
Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type Ext Remote Shutdown Ext System Condensation Detected Event Control Ext System Condensation Detected Event Type Ext System Condensation Detected Fan Button Control Fan Economy Mode Fan Issue Fan On/Off Control Fan State Hot Aisle Over Temp Threshold Hot Aisle Temp Out of Range Hot Aisle Under Temp Threshold Maintenance Completed Maintenance Due Maintenance Ramp Master Unit Communication Lost Minimum Room Temperature Set Point Primary Fan Group State Pump 1 Loss of Flow Pump 1 State Pump 2 Loss of Flow Pump 2 State Pump Hours Exceeded Pump Hours Threshold Pump Hours Pump Short Cycle RAM Battery Issue Remote Shutdown Sensor Issue - Event Control Sensor Issue - Event Type Sensor Issue Sensor Temperature
64
Table 19
Service Required SFA 16bit Read Only Value 1 SFA 16bit Read Only Value 10 SFA 16bit Read Only Value 2 SFA 16bit Read Only Value 3 SFA 16bit Read Only Value 4 SFA 16bit Read Only Value 5 SFA 16bit Read Only Value 6 SFA 16bit Read Only Value 7 SFA 16bit Read Only Value 8 SFA 16bit Read Only Value 9 SFA 16bit Writable Value 1 SFA 16bit Writable Value 10 SFA 16bit Writable Value 2 SFA 16bit Writable Value 3 SFA 16bit Writable Value 4 SFA 16bit Writable Value 5 SFA 16bit Writable Value 6 SFA 16bit Writable Value 7 SFA 16bit Writable Value 8 SFA 16bit Writable Value 9 SFA 32bit Read Only Value 1 SFA 32bit Read Only Value 10 SFA 32bit Read Only Value 2 SFA 32bit Read Only Value 3 SFA 32bit Read Only Value 4 SFA 32bit Read Only Value 5 SFA 32bit Read Only Value 6 SFA 32bit Read Only Value 7 SFA 32bit Read Only Value 8 SFA 32bit Read Only Value 9 SFA 32bit Writable Value 1 SFA 32bit Writable Value 10 SFA 32bit Writable Value 2 SFA 32bit Writable Value 3 SFA 32bit Writable Value 4 SFA 32bit Writable Value 5 SFA 32bit Writable Value 6 SFA 32bit Writable Value 7 SFA 32bit Writable Value 8 SFA 32bit Writable Value 9 SFA ID Number SFA Reserved Event 1
65
Table 19
SFA Reserved Event 10 SFA Reserved Event 11 SFA Reserved Event 12 SFA Reserved Event 13 SFA Reserved Event 14 SFA Reserved Event 15 SFA Reserved Event 16 SFA Reserved Event 17 SFA Reserved Event 18 SFA Reserved Event 19 SFA Reserved Event 2 SFA Reserved Event 20 SFA Reserved Event 21 SFA Reserved Event 22 SFA Reserved Event 23 SFA Reserved Event 24 SFA Reserved Event 25 SFA Reserved Event 3 SFA Reserved Event 4 SFA Reserved Event 5 SFA Reserved Event 6 SFA Reserved Event 7 SFA Reserved Event 8 SFA Reserved Event 9 Shutdown - Loss Of Power Smoke Detected Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Supply Chilled Water Temp Sensor Issue Supply Chilled Water Temperature Supply Refrig Over Temp Threshold Supply Refrigerant Over Temp Supply Refrigerant Temp Sensor Issue Supply Refrigerant Temperature Supply Refrigerant Under Temp System Condensation Detected System Control Mode System Date and Time System On/Off Control
66
Table 19
System Operating State Reason System Operating State System Status Unit Code Missing Unit Communication Lost Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Visual ID Control Water Under Floor
67
Table 20
Pump 1 Loss of Flow Pump 2 Loss of Flow Fan Issue System Condensation Detected Customer Input 1 Supply Chilled Water Over Temp Supply Chilled Water Temp Sensor Issue Supply Fluid Over Temp Supply Fluid Under Temp Supply Fluid Temp Sensor Issue Ext Air Sensor A Over Temperature Ext Air Sensor A Under Temperature Ext Air Sensor A Issue Ext Air Sensor B Over Temperature Ext Air Sensor B Under Temperature Ext Air Sensor B Issue Ext Dew Point Over Temperature Chilled Water Control Valve Position Shutdown -Loss Of Power Pump Short Cycle Water Under Floor Smoke Detected Service Required
68
Table 21
Scale 10 10 10 10
Notes / Units 0 = Off / 1 = On 0 = Off / 1 = On deg C deg F deg C deg F 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 0 = Off / 1 = On 2 = Standby deg C deg F % RH deg C deg F deg C deg F % RH deg C deg F deg C deg F deg C deg F deg C deg F deg C deg F deg C deg F deg C deg F deg C deg F sec 0 = Internal (Auto) 1 = External (Manual) % 0 = Off / 1 = On 2 = Reset 4 = Acknowledge
Pump 1 State Pump 2 State Supply Fluid Temperature Supply Fluid Temperature Supply Chilled Water Temperature Supply Chilled Water Temperature
System Status
30391
System Operating State Ext Air Sensor A Temperature Ext Air Sensor A Temperature Ext Air Sensor A Humidity Ext Air Sensor A Dew Point Temp Ext Air Sensor A Dew Point Temp Ext Air Sensor B Temperature Ext Air Sensor B Temperature Ext Air Sensor B Humidity Ext Air Sensor B Dew Point Temp Ext Air Sensor B Dew Point Temp Minimum Room Temperature Set Point Minimum Room Temperature Set Point Ext Air Over Temp Threshold Ext Air Over Temp Threshold Ext Air Under Temp Threshold Ext Air Under Temp Threshold Ext Dew Point Over Temp Threshold Ext Dew Point Over Temp Threshold Supply Fluid Over Temp Threshold Supply Fluid Over Temp Threshold Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Threshold Dew Point Temperature Dew Point Temperature Auto Restart Delay System Control Mode Maintenance Ramp Calculated Next Maintenance Month Calculated Next Maintenance Year System On/Off Control System Event Acknowledge/Reset
30392 30393 30394 30395 30396 30397 30398 30399 30400 30401 30402 30403 30404 30405 30406 30407 30408 30409 30410 30411 30412 30413 30414 30415 30416 30417 30418 30419 30420 30421 30422
40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40417 40422 40423
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
10 10 10 10 10 10 10 10 10 10 10 10 -
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
69
Table 22
Sleep on Monday Sleep on Tuesday Sleep on Wednesday Sleep on Thursday Sleep on Friday Sleep on Saturday Sleep on Sunday Supply Limit Enable Reheat Lockout Humidifier Lockout Temperature Indication 1 Timer Mode Type Minimum Chilled Water Temp Enable Std. Sensor Alarms Enable Sensor A Alarms Enable Compressor Lockout VSD Fan speed Unit Control Reset Alarm Acknowledge Alarm Reset Total Run Hours Fan Motor Reset Comp1Run Hour Reset Comp2Run Hour Reset Humidifier Run Hour Reset Dehumidifier Run Hour Reset CW/FC Run Hour Reset E-Heater1RunHour Reset E-heater2RunHour Reset E-heater3 Run Hour Reset HG/HW Run Hour Fan On Cool On Free Cool On Hot Water On Electrical Heater On Humidification On Dehumidification On Audible Alarm On Reserved Main Fan Overload Loss of Airflow Loss of Flow Comp 1 High Pressure Comp 1 Low Pressure
70
Table 22
Comp 1 Overload Comp 1 Pumpdown Fail Comp 2 High Pressure Comp 2 Low Pressure Comp 2 Overload Comp 2 Pumpdown Fail Digital Scroll Compressor 1 High Temperature Digital Scroll Compressor 2 High Temperature Smoke Detected Water Under Floor Humidifier Problem Stby Glycol Pump On Standby Unit On Cond Pump-high Water Room Sensor Failure Loss Compressor Power Loss of Air Blower 1 Humidifier Low Water Humidifier High Amps High Temperature Loss of Power Unspecified Event(s) 1 High CW Temp Reserved High Room Temp Low Room Temp High Room Hum Low Room Hum High Temp Sensor A Low Temp Sensor A High Hum Sensor A Low Hum Sensor A Loss of CW Flow Clogged Filters Supply Sensor Failure Freecool Temp Sensor Sensor A Failure Unit Hrs Exceeded Comp 1 Hrs Exceeded Comp 2 Hrs Exceeded FC Hrs Exceeded El Heat1 Hrs Exceeded El Heat2 Hrs Exceeded El Heat3 Hrs Exceeded
71
Table 22
HW/HG Hrs Exceeded Hum Hrs Exceeded Dehum Hrs Exceeded Network Failure No Connection W/Unit Unit(s) Disconnected Unit Code Missing Unit Code Mismatch Call Service Low Memory 1 RAM / Battery Failure HCB not connected (Parallel Flash) Memory 1 Fail (Serial Flash) Memory 2 Fail Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Digital Scroll Compressor 1 Sensor Fail Digital Scroll Compressor 2 Sensor Fail Low Int Temperature High Ext Dewpoint Cabinet Temp Sensor Fail Cabinet Humidity Sensor Fail Ambient Temp Sensor Fail Comp 1 Short Cycle Comp 2 Short Cycle Reheat Lockout Humidifier Lockout Compressor(s) Lockout Fire Alarm Heaters Overheated Condenser 1 Failure Condenser 2 Failure Humidifier Cylinder Worn Heat Rej VFD Heat Rej TVSS Humidifier Low Amps FC Lockout Water Leak Sensor Fail
Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
72
Table 23
Holding Register 40001 40002 40003 40004 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40032 40033 40040 40041 40042 40043 40044 40045 40050 40051 40052 40053 40054 40055 40056 40057 40070 40071 40072 40073 40074 40075
# of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
Scale 10 10 10 10 10 10 10 10 10 10 10 -
Notes / Units % (HP) deg C deg C deg C deg C deg C deg C Minutes % % Minutes % Seconds % LSB:Min LSB:Min LSB:Min LSB:Min deg C deg C deg C deg C deg C % % % % Hours Hours Hours Hours Hours Hours
30017 30018 30019 30020 30021 30022 30023 30024 30025 30026 30027 30028 30029 30030 30031 30032 30033 30040 30041 30042 30043 30044 30045 30050 30051 30052 30053 30054 30055 30056 30057 30070 30071 30072 30073 30074 30075
Supply Temperature Limit DT between Room and FC Minimum CW Temperature Temperature Setpoint Temperature Proportional Band Temperature Deadband Temperature Integration Time Humidity Setpoint Humidity Proportional Band Humidity Integration Time Humidity Deadband Single Unit Auto-Restart Delay Infrared Flush Rate Temp Control Type
4
Sleep Interval 1 Start Time Hour: Minute Sleep Interval 1 End Time Hour: Minute Sleep Interval 2 Start Time Hour: Minute Sleep Interval 2 End Time Hour: Minute Timer Deadband Manual VSD Timer/Counter 5 High Temperature Low Temperature High Temperature Sensor A Low Temperature Sensor A High Humidity Low Humidity High Humidity Sensor A Low Humidity Sensor A Fan Run Hour Threshold Compressor 1 Run Hour Threshold Compressor 2 Run Hour Threshold Humidifier Run Hours Threshold Dehumidification Run Hours Threshold CW/FC Run Hours Threshold
73
Table 23
# of Reg. -
Scale 10 10 10 10 10 10 10 10 10 10 10 10
Notes / Units Hours Hours Hours Hours % % % % % % % deg C deg C deg C deg C deg C deg C deg C deg C deg C deg C % % % % % Hours Hours Hours Hours Hours Hours Hours Hours Hours Hours deg C Hh:mm deg C
Electrical Heaters #1 Run Hours Threshold Electrical Heaters #2 Run Hours Threshold Electrical Heaters #3 Run Hours Threshold Hot Water / Hot Gas Run Hours Threshold Operating State
6
Number of Active Events/Alarm Summary Alarm Status Fan Ramp Cooling Ramp Free Cooling Ramp Heating Ramp Humidification Ramp Dehumidifier Ramp FreeCooling Status Return Temperature Actual Temperature SP Supply Temperature Actual Supply Temperature SP FC Temperature Sensor A Temperature Sensor B Temperature Sensor C Temperature Digital Scroll Compressor 1 High Temperature Digital Scroll Compressor 2 High Temperature Return Humidity Actual Humidity SP Sensor A Humidity Sensor B Humidity Sensor C Humidity Fan Run Hour Compressor 1 Run Hour Compressor 2 Run Hour Humidifier Run Hours Dehumidification Run Hours Free cooling Run Hours Electrical Heaters #1 Run Hours Electrical Heaters #2 Run Hours Electrical Heaters #3 Run Hours Hot Water / Hot Gas Run Hours Daily High Temperature Daily High Temp Time Daily Low Temperature
30109 30110 30111 30112 30113 30115 30116 30117 30118 30119 30120 30130 30131 30132 30133 30134 30141 30142 30143 30144 30145 30146 30147 30148 30149 30150 30151 30152 30153
74
Table 23
Daily Low Temp Time Daily High Humidity Daily High Hum Time Daily Low Humidity Daily Low Hum Time
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Timer mode: 0 = no, 1 = yes 2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value 3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive 4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent 5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information. 6. Operating state: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby Bit 2-3: 00 auto, 01 manual Bit 4-7: 0000 none 0001 local user 0010 alarm 0011 schedule 0100 remote user 0101 external device 0110 local display 7. Alarm state bit map: Bit 0 = Reset state Bit 1 = Active state Bit 2 = Acknowledge state Bit 3-7 = Alarm Type 00000: Message 00001: Warning 00010: Alarm 8. Free-cool state: 0 = Off, 1 = Start, 2 = On
75
Table 24
Temperature Indication 1 Unit Control Reset Alarm Acknowledge Alarm Cabinet Sensor Alarm Enable Fan On Cool On Compressor 1 High Pressure Compressor 1 Low Pressure Cond Pump-High Water Loss Compressor Power Emergency Damper Fail High Internal Temperature Loss of Power Remote Shutdown Unspecified Event(s) 1 Unit Hrs Exceeded Comp 1 Hrs Exceeded Network Failure No Connection W/Unit 1 Unit(s) Disconnected Unit Code Missing Unit Code Mismatch Low Memory 1 Ram / Battery Failure (Parallel Flash) MEMORY 1 FAIL (Serial Flash) MEMORY 2 FAIL Front Door Open Rear Door Open Digital Scroll Compressor 1 Sensor Fail Low Int Temperature High Ext Dewpoint Cabinet Temp Sensor Fail Cabinet Humidity Sensor Fail Ambient Temp Sensor Fail Comp 1 Short Cycle Reheat Lockout Humidifier Lockout Compressor(s) Lockout Backup Ventilation Door Open Device Load Alarm Status
Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event.
76
Table 25
Vendor ID Device ID Version number UPS/Env/Pwr Temperature Setpoint Delay after safe Temp has been reached Allowable deviation between internal temp sensors High Cabinet Temperature Setpoint Low Cabinet Temperature Setpoint Fan Run Hour Threshold Compressor 1 Run Hour Threshold Service Ramp Operating State 6 Number of Active Events/Alarm Summary Alarm Status 7 Fan Ramp Cooling Ramp Digital Scroll Compressor 1 High Temperature Sensor 1 Temp Sensor 2 Temp Sensor 3 Temp Sensor 4 Temp Ambient Temp Ambient Humidity Dew Point Temp Adjusted Setpoint Temp Cabinet Temperature Service Due Year Service Due Month Device kW Load Fan Run Hour Compressor 1 Run Hour
Scale 10 10 10 10 10 10 10 10 10 10 10 -
Notes / Units deg C Minutes deg C deg C deg C Hours Hours % % % deg C deg C deg C deg C deg C deg C % deg C deg C deg C kW Hours Hours
NOTES If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Timer mode: 0 = no, 1 = yes 2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value 3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive 4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent 5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information. 6. Operating state: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby Bit 2-3: 00 auto, 01 manual Bit 4-7: 0000 none 0001 local user 0010 alarm 0011 schedule 0100 remote user 0101 external device 0110 local display 7. Alarm state bit map: Bit 0 = Reset state Bit 1 = Active state Bit 2 = Acknowledge state Bit 3-7 = Alarm Type 00000: Message 00001: Warning 00010: Alarm 8. Free-cool state: 0 = Off, 1 = Start, 2 = On
77
Table 26
Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS - Input and Holding - LAM
Controller Liebert Products Advanced Microprocessor - LAM Liebert Challenger 3000 Liebert Deluxe System/3 Liebert Himod (LNA version - Using Liebert Sitescan) Liebert ICS Available Points Input Register Holding Register 40001 40002 40003 40004 40005 40006 40007 40008 40009 40018 40023 40024 40025 40026 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off (R/W) A/D raw value w/ slope=1 and offset = 0 A/D raw value w/ slope=1 and offset = 0 A/D raw value w/ slope=1 and offset = 0 A/D raw value w/ slope=1 and offset = 0 Discrete alarm objects available; use autodiscover for this unit Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2
Data Description Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) Analog input 1 Analog input 2 Analog input 3 Analog input 4 Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Short Cycle Loss of Power
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40290 40290 40290 40290 40290 40291 40291 40291
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
78
Table 26
Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS - Input and Holding - LAM (continued)
Controller Liebert Products Advanced Microprocessor - LAM Liebert Challenger 3000 Liebert Deluxe System/3 Liebert Himod (LNA version - Using Liebert Sitescan) Liebert ICS Available Points Input Register Holding Register 40291 40291 40291 40291 40291 40291 40291 40291 40019 40020 40021 40022 40010 40011 40012 40013 40014 40015 40016 40017 40028 40029 40030 40031 40349 40350 40350 40351 40351 40349 40349 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale 1000 1000 Notes / Units Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 (R/W) (R/W) (R/W) (R/W) (R/W) (R/W) (R/W) (R/W) Minutes (R/W) % (R/W) Hours (R/W) 0.1 minute (R/W) Bit 0 On=unit Off; Bit 1 On=unit On Bit 2 On=RH Off; Bit 3 On=RH On Bit 4 On=HL Off; Bit 5 On=HL On -
Data Description Inverter on Bypass Standby Fan On Loss of Emergency Power Local Alarm 1 Local Alarm 2 Off by Remote Shutdown Local Alarm 3 Local Alarm 4 Compressor 1 Run Hours Compressor 2 Run Hours Fan Motor Run Hours Humidifier Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temp Alarm Setpoint Low Temp Alarm Setpoint High Humd Alarm Setpoint Low Humidity Alarm Setpoint Winter Start Delay Auto Flush Rate Chill Water Flush Rate Auto Restart Delay Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout Trendable Points (Set) Temperature Humidity Reports Trend Status
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
79
Table 27
Liebert DataMate, Liebert Mini-Mate Plus, Liebert Mini-Mate2 - Input and Holding - L0B
Controller Liebert Products Small Systems - L0B Liebert DataMate Liebert Mini-Mate Plus Liebert Mini-Mate2 Available Points Input Register Holding Register 40001 40002 40003 40004 40005 40006 40007 40008 40009 40289 40289 40289 40289 40289 40289 40289 40011 40349 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Data Description Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Alarm Points Communications Local Off Remote Off High Temperature Low Temperature High Humidity Low Humidity Setpoints (View) None Control Points (Set) Unit On/Off Remote On/Off Trendable Points (Set) Temperature Humidity Reports Trend Status
Scale -
Notes / Units 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 1=On / 0=Off (R/W) Bit 0 On=unit Off Bit 1 On=unit On (W) -
1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
80
Table 28
Data Description Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Alarm Points Communications Local Off Remote Off High Head Pressure 1 Loss of Airflow Standby Glycol Unit On Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Flow Standby Unit On Short Cycle Loss of Power Local Alarm 1 Local Alarm 2 Local Alarm 3 Local Alarm 4 Run Hours (View) Compressor 1 Fan Motor Humidifier
Scale -
Notes / Units 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off Bit 0 Bit 1 Bit 2 Bit 3 Bit 5 Bit 6 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 8 Bit 9 Bit 10 Bit 1 Bit 2 Bit 6 Bit 7 Bit 9 Bit 10 -
81
Table 28
Data Description Setpoints (View) Temperature Temp Tolerance Humidity Humidity Tolerance High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Chill Water Flush Rate Auto Restart Delay Control Points (Set) Unit On/Off Remote On/Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Trendable Points (Set) Temperature Humidity Reports Trend Status
Notes / Units Hours (R/W) 0.1 minute (R/W) 1=On / 0=Off (R/W) Bit 0 On=unit Off Bit 1 On=unit On (W) (W) Multiply desired value by 1000 (Modbus only) 0=No Change (W) (W) Multiply desired value by 1000 (Modbus only) 0=No Change (W) -
1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
82
Table 29
Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Analog input 1 Analog input 2 Analog input 3 Analog input 4 Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Not Used Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Standby Unit On Not Used Short Cycle Loss of Power Local Alarm 1 Local Alarm 2 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40291 40291 40291 40291 40291 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -
83
Table 29
EPO Shutdown Local Alarm 3 Local Alarm 4 Run Times (View) Compressor 1 Run Hours Compressor 2 Run Hours Glycol Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Reheat 2 Run Hours Reheat 3 Run Hours Chilled H2O Valve Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Alarm Setpoint Low Temp Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint Winter Start Delay Auto Flush Rate Chill Water Flush Rate Auto Restart Delay Control Points (Set) Unit Status (On / Off) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
84
Table 30
Liebert Atlas Air, Liebert Atlas PEC, Liebert LECS 15 - Input and Holding - C10 2-step
Controller Liebert Products C10 Liebert Atlas Air Liebert Atlas PEC Liebert LECS 15 Available Points Input Register Holding Register 40001 40002 40003 40004 40005 40007 40008 40009 40010 40011 40012 40013 40014 40015 40019 40020 40021 40024 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Data Description Status Points (View) Unit Number Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Fan Status Cool 1 Status Cool 2 Status Heat 1 Status Heat 2 Status Humidifier Status De-humidifier Status Cooling Capacity Heating Capacity Temperature Control Status Battery Voltage Level Remote Shutdown Status Temperature Control Select Alarm Points Communications Faulty Sensor High Temperature Low Temperature High Humidity Low Humidity Loss of Airflow Water Under Floor Cool 1 Low Pressure Alarm Cool 2 Low Pressure Alarm Cool 1 High Pressure Alarm Cool 2 High Pressure Alarm Cool Service Humidifier Service Filter Service Humidity Low Level Battery Level Low Loss of Power Local Alarm 1 Local Alarm 2
Scale 10 10 10 10 10 -
Notes / Units 1-99 deg C % deg C % 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off % % 0=Return / 1=Supply V 1=Enabled / 0=Disabled 0=Return / 1=Supply 2=Remote / 3=Auto Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40290 40290 40290
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
85
Table 30
Liebert Atlas Air, Liebert Atlas PEC, Liebert LECS 15 - Input and Holding - C10 2-step (continued)
Controller Liebert Products C10 Liebert Atlas Air Liebert Atlas PEC Liebert LECS 15 Available Points Input Register Holding Register 40016 40017 40018 40025 40026 40027 40028 40029 40006 40022 40023 40349 40350 40351 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Data Description Setpoints (View) Return Air Temperature Return Air Humidity Supply Air Temperature High Temp Alarm Low Temp Alarm High Hum Alarm Low Hum Alarm Restart Delay Control Points (Set) Activation Mode General Alarm Status Audible Alarm Status Return Air Temperature Return Air Humidity Supply Air Temperature
Scale 10 10 10 10 10 10 10 10 10 10
Notes / Units deg C (R/W) deg C (R/W) deg C (R/W) deg C (R/W) deg C (R/W) % (R/W) % (R/W) Seconds (R/W) 1=On / 0=Off (R/W) 1=On / 0=Off; write 0 to reset alarm 1=On / 0=Off; write 0 to ack alarm deg C (R/W) deg C (R/W) deg C (R/W)
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
86
Table 31
Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input and Holding - C100 4-step
Controller Liebert Products CEMS 100 Liebert Atlas Air Liebert Atlas PEC Liebert CEMS 100 Available Points Input Register Holding Register 40001 40002 40003 40004 40005 40007 40008:0 40009:0 40008:4 40009:4 40010 40011 40012 40013 40014 40015 40019 40020 40021 40024 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Data Description Status Points (View) Unit Number Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Fan Status Cool 1 Status Cool 2 Status Cool 3 Status Cool 4 Status Heat 1 Status Heat 2 Status Humidifier Status De-humidifier Status Cooling Capacity Heating Capacity Temperature Control Status Battery Voltage Level Remote Shutdown Status Temperature Control Select Alarm Points Communications Faulty Sensor High Temperature Low Temperature High Humidity Low Humidity Loss of Airflow Water Under Floor Cool 1 Low Pressure Alarm Cool 2 Low Pressure Alarm Cool 1 High Pressure Alarm Cool 2 High Pressure Alarm Cool Service Humidifier Service Filter Service
Scale 10 10 10 10 100 -
Notes / Units 1-99 deg C % deg C % 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off % % 0=Return / 1=Supply V 1=Enabled / 0=Disabled 0=Return / 1=Supply 2=Remote / 3=Auto Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
87
Table 31
Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input and Holding - C100 4-step (continued)
Controller Liebert Products CEMS 100 Liebert Atlas Air Liebert Atlas PEC Liebert CEMS 100 Available Points Input Register Holding Register 40290 40290 40290 40290 40290 40290 40290 40290 40290 40290 40016 40017 40018 40025 40026 40027 40028 40029 40006 40022 40023 40349 40350 40351 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Data Description Humidity Low Level Battery Level Low Loss of Power Local Alarm 1 Local Alarm 2 Cool 3 Low Pressure Cool 4 Low Pressure Cool 3 High Pressure Cool 4 High Pressure Air Flow 2 Loss Setpoints (View) Return Air Temperature Return Air Humidity Supply Air Temperature High Temp Alarm Low Temp Alarm High Hum Alarm Low Hum Alarm Restart Delay Control Points (Set) Activation Mode General Alarm Status Audible Alarm Status Return Air Temperature Return Air Humidity Supply Air Temperature
Scale 10 10 10 10 10 10 10 10 10 10
Notes / Units Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 deg C (R/W) deg C (R/W) deg C (R/W) deg C (R/W) deg C (R/W) % (R/W) % (R/W) Seconds (R/W) 1=On / 0=Off (R/W) 1=On / 0=Off; write 0 to reset alarm 1=On / 0=Off; write 0 to ack alarm deg C (R/W) deg C (R/W) deg C (R/W)
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
88
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
3.2
89
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 32
Liebert Datawave, Liebert FPC, Liebert PPC - Input and Holding - PMP, PM2 Options for Liebert FPC and Liebert PPC (continued)
Controller Liebert Products Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC Liebert Datawave Liebert FPC Liebert PPC Available Points Input Register Holding Register # of Reg.
Data Description Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm #1 Local Alarm #2 Output Voltage THD Custom Alarm #1 Custom Alarm #2 Setpoints (View) None Control Points (Set) None
Scale
Notes / Units Discrete alarm objects available; use auto-discover for this unit
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40290 40290 40290
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 -
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
90
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 33
Liebert Datawave, Liebert FPC, Liebert PPC - Input and Holding - PMP Option for Liebert FPC and Liebert PPC
Controller Liebert Products Power Monitoring Panel - PMP Option for Liebert FPC and Liebert PPC Liebert Datawave Liebert FPC Liebert PPC Available Points Input Holding # of Register Register Reg. Scale 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10 10 -
Data Description Status Points (View) Voltage In X-Y Voltage In Y-Z Voltage In Z-X Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C Ground Current Neutral Current kVA kW Frequency % Capacity A % Capacity B % Capacity C Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm Custom Alarm #1 Custom Alarm #2 Setpoints (View) None Control Points (Set) None
Notes / Units V V V V V V V V V A A A A A kVA kW Hz % % % Discrete alarm objects available; use auto-discover for this unit Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 -
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40290
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
91
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 34
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Status and Coil
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Status 10001 10002 10013 10014 10025 10026 10027 10028 10029 10030 10031 10032 10033 10034 10045 10046 10047 10048 10049 10050 10051 10052 10053 10054 10065 10066 10067 10068 10069 10070 10071 10082 10083 10084 10085 10086 10087 10088 Coil Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm
Data Description Input Power 1 Phase Loss Phase Rotation Error Input Power 2 Phase Loss Phase Rotation Error Output Power 1 Output Overvoltage Output Undervoltage Output Overcurrent Neutral Overcurrent Ground Overcurrent Output Voltage THD Frequency Deviation Transformer Overtemperature Power Off Transformer Overtemperature Transformer Temperature Sensor Fail Output Power 2 Output Overvoltage Output Undervoltage Output Overcurrent Neutral Overcurrent Ground Overcurrent Output Voltage THD Frequency Deviation Transformer Overtemperature Power Off Transformer Overtemperature Transformer Temperature Sensor Fail Panel 1 Panel Summary Alarm Panel Overvoltage Panel Undervoltage Panel Phase Overcurrent Panel Phase Overcurrent Panel Neutral Overcurrent Panel Ground Overcurrent Panel 2 Panel Summary Alarm Panel Overvoltage Panel Undervoltage Panel Phase Overcurrent Panel Phase Overcurrent Panel Neutral Overcurrent Panel Ground Overcurrent
92
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 34
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Status and Coil (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Status 10116 10117 10118 10119 10120 10121 10122 10133 10134 10135 10146 10147 10148 11212 11213 11214 11225 11226 11227 11238 11239 11240 12304 12305 12306 12317 12318 12319 12330 12331 12332 13396 13397 13398 Coil Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm
Data Description Panel 4 Panel Summary Alarm Panel Overvoltage Panel Undervoltage Panel Phase Overcurrent Panel Phase Overcurrent Panel Neutral Overcurrent Panel Ground Overcurrent Panel 1 Position 1 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 1 Position 2 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 1 Position 84 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 2 Position 1 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 2 Position 2 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 2 Position 84 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 3 Position 1 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 3 Position 2 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 3 Position 84 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning
93
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 34
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Status and Coil (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Status 13409 13410 13411 13422 13423 13424 14488 14489 14490 14501 14502 14503 14504 14515 14516 14517 14518 15383 15384 15385 15386 15397 15408 15496 15507 15508 15509 15510 15511 Coil Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Alarm Active on Warning Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
Data Description Panel 4 Position 1 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 4 Position 2 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Panel 4 Position 84 Branch Overcurrent Branch Overcurrent Branch Undercurrent Warning Subfeed 1 Subfeed Phase Overcurrent Subfeed Phase Overcurrent Subfeed Neutral Overcurrent Subfeed Ground Overcurrent Subfeed 2 Subfeed Phase Overcurrent Subfeed Phase Overcurrent Subfeed Neutral Overcurrent Subfeed Ground Overcurrent Subfeed 64 Subfeed Phase Overcurrent Subfeed Phase Overcurrent Subfeed Neutral Overcurrent Subfeed Ground Overcurrent Customer Events 1 Event State Customer Events 2 Event State Customer Events 10 Event State System System Shutdown - EPO System Shutdown - REPO Transformer Overtemperature Shutdown Transformer Overtemperature Equipment Temperature Sensor Fail
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
94
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 30385 30386 30387 30391 30392 30393 30397 30398 30399 30400 30401 30402 30403 30404 30405 30406 30407 30408 30409 30410 30411 30413 30414 30415 30416 30417 30418 30419 30420 30421 30422 30423 30424 30425 30426 Holding Register 40411 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale 10 100 10 10 10 10 10 10 10 10 10 10 10 10 Notes / Units VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC A AC A AC A AC A AC A AC Hz kVA kW kWH % % THD % THD % THD % THD % THD % THD -
Input Power 1 Input Voltage A-B Input Voltage B-C Input Voltage C-A Input Power 2 Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Power 1 Output Voltage X-Y Output Voltage Y-Z Output Voltage Z-X Output Voltage Vx Output Voltage Vy Output Voltage Vz Output Current Ix Output Current Iy Output Current Iz Output Neutral Current Ground Current Output Frequency Output Power (kVA) Output Power (kW) Output kW-Hrs Output Power Factor Output Percent Load Output Voltage Vx THD Output Voltage Vy THD Output Voltage Vz THD Output Current Ix THD Output Current Iy THD Output Current Iz THD Output Current Ix K-Factor Output Current Iy K-Factor Output Current Iz K-Factor Output Current Ix Crest Factor Output Current Iy Crest Factor Output Current Iz Crest Factor
95
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 30430 30431 30432 30433 30434 30435 30436 30437 30438 30439 30440 30441 30442 30443 30444 30446 30447 30448 30449 30450 30451 30452 30453 30454 30455 30456 30457 30458 30459 30463 30464 30465 30466 30467 30468 30469 30470 Holding Register 40444 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale 10 100 10 10 10 10 10 10 10 10 10 10 10 10 Notes / Units VAC VAC VAC VAC VAC VAC A AC A AC A AC A AC A AC Hz kVA kW kWH % % THD % THD % THD % THD % THD % THD VAC VAC VAC VAC VAC VAC
Output Power 2 Output Voltage X-Y Output Voltage Y-Z Output Voltage Z-X Output Voltage Vx Output Voltage Vy Output Voltage Vz Output Current Ix Output Current Iy Output Current Iz Output Neutral Current Ground Current Output Frequency Output Power (kVA) Output Power (kW) Output kW-Hrs Output Power Factor Output Percent Load Output Voltage Vx THD Output Voltage Vy THD Output Voltage Vz THD Output Current Ix THD Output Current Iy THD Output Current Iz THD Output Current Ix K-Factor Output Current Iy K-Factor Output Current Iz K-Factor Output Current Ix Crest Factor Output Current Iy Crest Factor Output Current Iz Crest Factor Panel 1 Columns of Breakers Number of Breakers Panel Main Voltage X-Y Panel Main Voltage Y-Z Panel Main Voltage Z-X Panel Main Voltage X-N Panel Main Voltage Y-N Panel Main Voltage Z-N
96
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 30471 30472 30473 30474 30475 30476 30477 30478 30480 30481 30482 30483 30484 30485 30486 30487 30488 30489 30490 30494 30495 30496 30497 30498 30499 30500 30501 30502 30503 30504 30505 30506 30507 30508 30509 30511 30512 30513 Holding Register 40478 40509 # of Reg. 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 Scale 10 10 100 10 10 10 10 10 10 10 10 10 10 10 100 10 Notes / Units A AC A AC A AC A AC A AC kVA kW kWH % % THD % THD % THD % THD % THD % THD VAC VAC VAC VAC VAC VAC A AC A AC A AC A AC A AC kVA kW kWH % % THD
Panel Main Current Ix Panel Main Current Iy Panel Main Current Iz Panel Main Neutral Current Panel Main Ground Current Panel Main Output Power (kVA) Panel Main Output Power (kW) Panel Main Output kW-Hrs Panel Main Output Power Factor Panel Main Output Percent Load Panel Main Voltage Vx THD Panel Main Voltage Vy THD Panel Main Voltage Vz THD Panel Main Current Ix THD Panel Main Current Iy THD Panel Main Current Iz THD Panel Main Current Ix Crest Factor Panel Main Current Iy Crest Factor Panel Main Current Iz Crest Factor Panel 2 Columns of Breakers Number of Breakers Panel Main Voltage X-Y Panel Main Voltage Y-Z Panel Main Voltage Z-X Panel Main Voltage X-N Panel Main Voltage Y-N Panel Main Voltage Z-N Panel Main Current Ix Panel Main Current Iy Panel Main Current Iz Panel Main Neutral Current Panel Main Ground Current Panel Main Output Power (kVA) Panel Main Output Power (kW) Panel Main Output kW-Hrs Panel Main Output Power Factor Panel Main Output Percent Load Panel Main Voltage Vx THD
97
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 30514 30515 30516 30517 30518 30519 30520 30521 30556 30557 30558 30559 30560 30561 30562 30563 30564 30565 30566 30567 30568 30569 30570 30571 30573 30574 30575 30576 30577 30578 30579 30580 30581 30582 30583 Holding Register 40571 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 Scale 10 10 10 10 10 10 10 10 10 10 100 10 10 10 10 10 10 10 10 10 Notes / Units % THD % THD % THD % THD % THD VAC VAC VAC VAC VAC VAC A AC A AC A AC A AC A AC kVA kW kWH % % THD % THD % THD % THD % THD % THD -
Panel Main Voltage Vy THD Panel Main Voltage Vz THD Panel Main Current Ix THD Panel Main Current Iy THD Panel Main Current Iz THD Panel Main Current Ix Crest Factor Panel Main Current Iy Crest Factor Panel Main Current Iz Crest Factor Panel 4 Columns of Breakers Number of Breakers Panel Main Voltage X-Y Panel Main Voltage Y-Z Panel Main Voltage Z-X Panel Main Voltage X-N Panel Main Voltage Y-N Panel Main Voltage Z-N Panel Main Current Ix Panel Main Current Iy Panel Main Current Iz Panel Main Neutral Current Panel Main Ground Current Panel Main Output Power (kVA) Panel Main Output Power (kW) Panel Main Output kW-Hrs Panel Main Output Power Factor Panel Main Output Percent Load Panel Main Voltage Vx THD Panel Main Voltage Vy THD Panel Main Voltage Vz THD Panel Main Current Ix THD Panel Main Current Iy THD Panel Main Current Iz THD Panel Main Current Ix Crest Factor Panel Main Current Iy Crest Factor Panel Main Current Iz Crest Factor
98
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 30587 30588 30589 30590 30591 30592 30594 30595 30599 30600 30601 30602 30603 30604 30606 30607 31583 31584 31585 31586 31587 31588 31590 31591 31595 31596 31597 31598 31599 31600 31602 31603 Holding Register # of Reg. 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 Scale 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 Notes / Units A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH %
Panel 1 Position 1 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 1 Position 2 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 1 Position 84 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 2 Position 1 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load
99
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 31607 31608 31609 31610 31611 31612 31614 31615 32591 32592 32593 32594 32595 32596 32598 32599 32603 32604 32605 32606 32607 32608 32610 32611 32615 32616 32617 32618 32619 32620 32622 32623 Holding Register # of Reg. 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 Scale 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 Notes / Units A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH %
Panel 2 Position 2 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 2 Position 84 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 3 Position 1 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 3 Position 2 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load
100
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 33599 33600 33601 33602 33603 33604 33606 33607 33611 33612 33613 33614 33615 33616 33618 33619 33623 33624 33625 33626 33627 33628 33630 33631 34607 34608 34609 34610 34611 34612 34614 34615 Holding Register # of Reg. 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 Scale 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 10 10 10 1000 1000 100 Notes / Units A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH % A AC A AC A AC kW kWH %
Panel 3 Position 84 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 4 Position 1 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 4 Position 2 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load Panel 4 Position 84 Breaker position Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Power (kW) Output kW-Hrs Branch Output Power Factor Branch Output Percent Load
101
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 34619 34620 34621 34622 34623 34624 34625 34626 34628 34629 34630 34631 34632 34633 34634 34635 34639 34640 34641 34642 34643 34644 34645 34646 34648 34649 34650 34651 34652 34653 34654 34655 Holding Register 44626 44646 # of Reg. 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 Scale 10 10 100 10 10 10 10 10 10 10 10 100 10 10 10 10 10 10 Notes / Units A AC A AC A AC A AC A AC kVA kW kWH % % % % A AC A AC A AC A AC A AC kVA kW kWH % % % % -
Subfeed 1 Subfeed Current Ix Subfeed Current Iy Subfeed Current Iz Subfeed Neutral Current Subfeed Ground Current Subfeed Output Power (kVA) Subfeed Output Power (kW) Subfeed Output kW-Hrs Subfeed Power Factor Subfeed Output Percent Load Subfeed Current Ix THD Subfeed Current Iy THD Subfeed Current Iz THD Subfeed Current Ix Crest Factor Subfeed Current Iy Crest Factor Subfeed Current Iz Crest Factor Subfeed 2 Subfeed Current Ix Subfeed Current Iy Subfeed Current Iz Subfeed Neutral Current Subfeed Ground Current Subfeed Output Power (kVA) Subfeed Output Power (kW) Subfeed Output kW-Hrs Subfeed Power Factor Subfeed Output Percent Load Subfeed Current Ix THD Subfeed Current Iy THD Subfeed Current Iz THD Subfeed Current Ix Crest Factor Subfeed Current Iy Crest Factor Subfeed Current Iz Crest Factor
102
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 35
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert Products Liebert iCOM v4 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX Available Points Data Description Input Register 35879 35880 35881 35882 35883 35884 35885 35886 35888 35889 35890 35891 35892 35893 35894 35895 Holding Register 45886 # of Reg. 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 Scale 10 10 100 10 10 10 10 10 10 Notes / Units A AC A AC A AC A AC A AC kVA kW kWH % % % % 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 2 = Reset 4 = Acknowledge -
Subfeed 64 Subfeed Current Ix Subfeed Current Iy Subfeed Current Iz Subfeed Neutral Current Subfeed Ground Current Subfeed Output Power (kVA) Subfeed Output Power (kW) Subfeed Output kW-Hrs Subfeed Power Factor Subfeed Output Percent Load Subfeed Current Ix THD Subfeed Current Iy THD Subfeed Current Iz THD Subfeed Current Ix Crest Factor Subfeed Current Iy Crest Factor Subfeed Current Iz Crest Factor System
System Status
35899
39998
45900 49998
1 2
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
103
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 36
Branch Current Phase 1 Branch Current Phase 2 Branch Current Phase 3 Branch Output Percent Load Branch Output Power (W) Branch Output Power Factor Branch Overcurrent Branch Undercurrent Warning Breaker position Columns of Breakers Equipment Temperature Sensor Fail Event State Frequency Deviation Ground Current Ground Overcurrent Input Voltage A-B Input Voltage B-C Input Voltage C-A Neutral Overcurrent Number of Breakers Output Current Ix Crest Factor Output Current Ix K-Factor Output Current Ix THD Output Current Ix Output Current Iy Crest Factor Output Current Iy K-Factor Output Current Iy THD Output Current Iy Output Current Iz Crest Factor Output Current Iz K-Factor Output Current Iz THD Output Current Iz Output Frequency Output kW-Hrs Output kW-Hrs Output Neutral Current Output Overcurrent Output Overvoltage Output Percent Load Output Power (kVA) Output Power (kW) Output Power Factor Output Undervoltage
104
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 36
Output Voltage THD Output Voltage Vx THD Output Voltage Vx Output Voltage Vy THD Output Voltage Vy Output Voltage Vz THD Output Voltage Vz Output Voltage X-Y Output Voltage Y-Z Output Voltage Z-X Panel Ground Overcurrent Panel Main Current Ix Crest Factor Panel Main Current Ix THD Panel Main Current Ix Panel Main Current Iy Crest Factor Panel Main Current Iy THD Panel Main Current Iy Panel Main Current Iz Crest Factor Panel Main Current Iz THD Panel Main Current Iz Panel Main Ground Current Panel Main Neutral Current Panel Main Output kW-Hrs Panel Main Output Percent Load Panel Main Output Power (kVA) Panel Main Output Power (kW) Panel Main Output Power Factor Panel Main Voltage Vx THD Panel Main Voltage Vy THD Panel Main Voltage Vz THD Panel Main Voltage X-N Panel Main Voltage X-Y Panel Main Voltage Y-N Panel Main Voltage Y-Z Panel Main Voltage Z-N Panel Main Voltage Z-X Panel Neutral Overcurrent Panel Overvoltage Panel Phase Overcurrent Panel Summary Alarm Panel Undervoltage Phase Loss
105
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 36
Phase Rotation Error Subfeed Current Ix Crest Factor Subfeed Current Ix THD Subfeed Current Ix Subfeed Current Iy Crest Factor Subfeed Current Iy THD Subfeed Current Iy Subfeed Current Iz Crest Factor Subfeed Current Iz THD Subfeed Current Iz Subfeed Ground Current Subfeed Ground Overcurrent Subfeed Neutral Current Subfeed Neutral Overcurrent Subfeed Output kW-Hrs Subfeed Output Percent Load Subfeed Output Power (kVA) Subfeed Output Power (kW) Subfeed Phase Overcurrent Subfeed Power Factor System Date and Time System Event Acknowledge/Reset System Shutdown - EPO System Shutdown - REPO System Status Transformer Overtemperature Power Off Transformer Overtemperature Shutdown Transformer Overtemperature Transformer Overtemperature Transformer Temperature Sensor Fail
106
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 37
Data Description Status Points (View) Transfer Count Preferred Source Load On Source Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency kW kVA Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Alarm Points Communications Logic Failure Equipment Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR1 Shorted SCR2 Open SCR1 Open SCR2 Fan Failure
Scale 10 10 10 -
Notes / Units 1=Source 1 / 2=Source 2 1=Source 1 / 2=Source 2 V V V A A A Hz V V V A A A Hz kW kVA Seconds V Degree Hz Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2
107
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 37
Data Description Source 2 Overload Power Supply 2 Fault Frequency Deviation Transfer Inhibit Auto Retransfer Primed Out of Synchronization Source 1 Failure Source 2 Failure Auto Retransfer Failed Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB1 Open Source 2 CB2 Open Output CB3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Custom Alarm 3 Custom Alarm 4 Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8
Scale -
Notes / Units Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
108
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 38
Data Description Status Points (View) Total Transfer Count Preferred Source Active Source Source 1 Volts A-B Source 1 Volts B-C Source 1 Volts C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Volts A-B Source 2 Volts B-C Source 2 Volts C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency Output kW Output kVA CB 1 Status CB 2 Status CB 3 Status CB 3A Status CB 4 Status CB 5 Status CB Spare 1 Status CB Spare 2 Status CB 7 Status CB 8 Status Auto Xfer Enabled Has Dual Out Breakers Has PDU Equipped Has 4 pole Switch Has Shunt Trip Has Wye Out Xfmr Has Rmt Sorce Sel Manual I peak Reset Auto Restart Enabled
Scale 10 10 -
Notes / Units 1=Source 1, 2=Source 2 1=Source 1, 2=Source 2 V V V A A A Hz V V V A A A Hz kW kVA Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8
109
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 38
Data Description LoadKVA % Source 1 Volts A-N Source 1 Volts B-N Source 1 Volts C-N Source 2 Volts A-N Source 2 Volts B-N Source 2 Volts C-N Source 1 Neutral Current Source 2 Neutral Current Setpoints (View) Retransfer Delay STS2 Voltage Rating Max Xfer Phase Angle Freq. Deviation Trip Point Source 1 Neutral Current Limit Source 2 Neutral Current Limit Alarm Points Communications Lost S1 SCR Short S2 SCR Short S1 SCR Open S2 SCR Open Primary Fan Fail Control Module Fail PWR Supply DC A Fail PWR Supply DC B Fail PWR Supply SRC 1 AC Fail PWR Supply SRC 2 AC Fail PWR Supply Logic Fail Output Voltage Sense Fail S1 Voltage Sense Fail S2 Voltage Sense Fail S1 SCR Sense Fail S2 SCR Sense Fail S1 Current Sense Fail S2 Current Sense Fail S1 Gate Drive Fail S2 Gate Drive Fail
Scale 10 -
Notes / Units % V (4 Pole only) V (4 Pole only) V (4 Pole only) V (4 Pole only) V (4 Pole only) V (4 Pole only) A (4 Pole only) A (4 Pole only) Seconds V Degree Hz A (4 Pole only) A (4 Pole only) Discrete alarm objects available; use auto-discover for this unit
40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4
110
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 38
Data Description Internal Comm Fail External Comm Fail CB1 Shunt Trip Fail CB2 Shunt Trip Fail CB6 Neutral Open Contactor Neutral Fail Heatsink Overtemp Equipment Overtemp Ambient Overtemp S1 Undervolts S1 Undervolts (RMS) S1 Overvolts S1 Over/Under Freq S1 Fail S2 Undervolts S2 Undervolts (RMS) S2 Overvolts S2 Over/Under Frequency S2 Fail S1 Overcurrent S2 Overcurrent S1 I-Peak S2 I-Peak Sources Out of Sync Load On Alternate Source Auto Retransfer Inhibit CB1 (S1) Open CB2 (S2) Open CB4 (S1 BYP) Closed CB5 (S2 BYP) Closed CB3 Output Bkr Open CB3A Output Bkr Open S1 Phase Rotation Error S2 Phase Rotation Error Transfer Inhibited Output Undervoltage History Logs Full Equipment Fan Fail Load Volt THD High
Scale -
Notes / Units Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 (N/A to 4P) Bit 10 (N/A to 4P) Bit 11 Bit 12 (N/A to 4P) Bit 13 (N/A to 4P) Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12
111
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Table 38
Data Description Load Over-current Ground Over-current Neutral Over-current Customer Alarm #1 Customer Alarm #2 Customer Alarm #3 Customer Alarm #4 Customer Alarm #5 Customer Alarm #6 Customer Alarm #7 Customer Alarm #8 Neutral Current 1 Over Limit Neutral Current 2 Over Limit Neutral Snubber Fail Neutral 1 SCR Short Neutral 2 SCR Short Neutral 1 SCR Open Neutral 2 SCR Open
Scale -
Notes / Units Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 13 (4P Only) Bit 14 (4P Only) Bit 15 (4P Only) Bit 0 (4P Only) Bit 1 (4P Only) Bit 2 (4P Only) Bit 3 (4P Only)
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
112
3.3
UPS Systems
Table 39 Liebert APM - Status and Coil
Data Description System Status Battery Auto Test In Progress Battery Equalize Battery Charging Inhibited On Generator System Events System Input Power Problem Rectifier Failure Inverter Failure Bypass Not Available Battery Low LBS Inhibited System Fan Failure Equipment Over Temperature System Shutdown - EPO Bypass Static Switch Unavailable Bypass - Excess Auto Retransfers Parallel Comm Warning Power Supply Failure Battery Over Temperature System Input Phs Rotation Error Fuse Failure Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C MMS Overload Inverter Shutdown - Overload System Output Fault Internal Communications Failure Battery Charging Error System Input Current Imbalance Main Battery Disconnect Open Inverter Static Switch SCR Short Battery Not Qualified Battery Terminals Reversed Battery Converter Failure Inverter SCR Open Load Sharing Fault DC Bus Abnormal Mains Input Neutral Lost Load Impact Transfer 10015 10016 10017 10018 10019 10020 10021 10022 10023 10024 10025 10026 10027 10028 10029 10030 10031 10032 10033 10034 10035 10036 10037 10038 10039 10040 10041 10042 10043 10044 10045 10046 10047 10048 10049 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm 10001 10002 10003 10004 1 1 1 1 Active on Alarm Active on Alarm Active on Alarm Active on Alarm Status Coil Number of Bits Scale Notes / Units
113
Table 39
User Operation Invalid Power Sub Module Fault Battery Discharging UPS Output on Bypass Output Load on Maint. Bypass Battery Capacity Low MMS On Battery
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
114
Table 40
Input System Input RMS A-B System Input RMS B-C System Input RMS C-A System Input RMS Current Phase A System Input RMS Current Phase B System Input RMS Current Phase C System Input Frequency System Input RMS A-N System Input RMS B-N System Input RMS C-N System Input Power Factor Phs A System Input Power Factor Phs B System Input Power Factor Phs C Bypass Bypass Input Voltage RMS A-N Bypass Input Voltage RMS B-N Bypass Input Voltage RMS C-N Bypass Input Frequency Battery Battery Time Remaining Battery Volts for Cabinet Battery Temperature for Cabinet Battery Temperature for Cabinet Inlet Air Temperature Inlet Air Temperature DC Bus Current UPS battery1 status Output System Output Voltage RMS A-N System Output Voltage RMS B-N System Output Voltage RMS C-N System Output RMS Current Phs A System Output RMS Current Phs B System Output RMS Current Phs C System Output Frequency System Output Voltage RMS A-B System Output Voltage RMS B-C System Output Voltage RMS C-A System Output Power Factor Phs A System Output Power Factor Phs B 30419 30420 30421 30422 30423 30424 30425 30426 30427 30428 30429 30430 1 1 1 1 1 1 1 1 1 1 1 1 10 100 100
115
Table 40
System Output Power Factor Phs C System Output Pct Power Phase A System Output Pct Power Phase B System Output Pct Power Phase C MMS Output Apparent Power MMS Output Power System Output Apparent Power System Output Power Output Current Crest Factor Phs A Output Current Crest Factor Phs B Output Current Crest Factor Phs C System Status Inverter On/Off State Maintenance Bypass Breaker (MBB)
30447
System Status
30448
System Configuration System Date and Time 39998 49998 2 If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
116
Table 41
Battery Auto Test In Progress Battery Capacity Low Battery Charging Error Battery Charging Inhibited Battery Converter Failure Battery Discharging Battery Equalize Battery Low Battery Not Qualified Battery Over Temperature Battery Temperature for Cabinet Battery Terminals Reversed Battery Time Remaining Battery Volts for Cabinet Bypass - Excess Auto Retransfers Bypass Input Frequency Bypass Input Voltage RMS A-N Bypass Input Voltage RMS B-N Bypass Input Voltage RMS C-N Bypass Not Available Bypass Static Switch Unavailable DC Bus Abnormal DC Bus Current Equipment Over Temperature Fuse Failure Inlet Air Temperature Internal Communications Failure Inverter Failure Inverter On/Off State Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C Inverter SCR Open Inverter Shutdown - Overload Inverter Static Switch SCR Short
117
Table 41
LBS Inhibited Load Impact Transfer Load Sharing Fault Main Battery Disconnect Open Mains Input Neutral Lost Maintenance Bypass Breaker (MBB) MMS On Battery MMS Output Apparent Power MMS Output Power MMS Overload On Generator Output Current Crest Factor Phs A Output Current Crest Factor Phs B Output Current Crest Factor Phs C Output Load on Maint. Bypass Parallel Comm Warning Power Sub Module Fault Power Supply Failure Rectifier Failure System Date and Time System Fan Failure System Input Current Imbalance System Input Frequency System Input Phs Rotation Error System Input Power Factor Phs A System Input Power Factor Phs B System Input Power Factor Phs C System Input Power Problem System Input RMS A-B System Input RMS A-N System Input RMS B-C System Input RMS B-N System Input RMS C-A System Input RMS C-N System Input RMS Current Phase A System Input RMS Current Phase B System Input RMS Current Phase C System Output Apparent Power System Output Fault System Output Frequency System Output Pct Power Phase A
118
Table 41
System Output Pct Power Phase B System Output Pct Power Phase C System Output Power Factor Phs A System Output Power Factor Phs B System Output Power Factor Phs C System Output Power System Output RMS Current Phs A System Output RMS Current Phs B System Output RMS Current Phs C System Output Voltage RMS A-B System Output Voltage RMS A-N System Output Voltage RMS B-C System Output Voltage RMS B-N System Output Voltage RMS C-A System Output Voltage RMS C-N System Shutdown - EPO System Status UPS battery1 status UPS Output on Bypass UPS Output Source User Operation Invalid
119
Table 42
Audible Alarm Enabled Automatic Battery Test Enabled DC-to-DC Converter On Battery Charge Compensation Inverter Ready Power Factor Correction State Load Circuit 1 State Load Circuit 2 State Load Circuit 3 State Load Circuit 4 State Load Circuit 5 State Load Circuit 6 State Load Circuit 7 State Load Circuit 8 State Load Circuit 9 State Load Circuit 10 State Load Circuit 11 State Load Circuit 12 State Load Circuit 13 State Load Circuit 14 State Load Circuit 15 State Load Circuit 16 State Load On Inverter Bypass Active Replace Battery Battery Under Test Shutdown Reason - Over Temperature Shutdown Reason - Overload Shutdown Reason - Link Over Voltage Shutdown Reason - Output Short Shutdown Reason - Line Neutral Swap Shutdown Reason - Low Battery Shutdown Reason - Remote Shutdown Shutdown Reason - Input Under Voltage Shutdown Reason - PFC Startup Shutdown Reason - Hardware Load on Battery Output Off Pending Low Battery - Shutdown Imminent Output Overload Over Temperature Warning Battery Over Temperature CB Trip Input Power Supply Fail Input Over Voltage Input Under Voltage Bad Input Frequency Bypass Input Voltage/Frequency Fault Output Under Voltage Output Over Voltage
120
Table 43
Number of Input Lines Number of Bypass Lines Number of Output Lines Number of SubModules
30013
40013
Battery Cabinet Type Battery Cabinet Number Battery AmpHour Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Device Low Battery Time Load (Apparent Power) Load (Real Power) Load / Capacity Input Frequency Output Frequency Bypass Frequency
30018 30019 30020 30021 30027 30028 30029 30030 30031 30032 30033 30034 30051 30053 30102 30104 30106 30107 30108 30109
40018 40019 40020 40021 40027 40028 40029 40030 40031 40032 40033 40034 40051 40053 -
2 1 1 2 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1
10 10 100 10 10 10
30112
Battery Voltage Battery Time Remaining Battery Charge Percentage Ambient Temperature
1 1 1 1
30130
30153 30159
1 1
121
Table 43
Output Voltage L1 Output Current L1 Input Maximum Voltage L1 Input Minimum Voltage L1 Output Maximum Voltage L1 Output Minimum Voltage L1 Black Out Count Brown Out Count
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
122
Table 44
DC-To-DC Converter On Load On Inverter Bypass Active Load On Battery Permanently On Bypass Bypass SCR Open Circuit Low Battery - Shutdown Imminent Output Overload Inverter Unsynchronized Input Power Supply Fail Bypass Input Voltage/Frequency Fault
123
Table 45
Number of Input Lines Number of Bypass Lines Number of Output Lines Number of SubModules Number of Battery Cells Load (Apparent Power) Load (Real Power) Input Frequency Output Frequency Battery Voltage Battery Current (Charge/Discharge) Battery Charge Percentage Ambient Temperature Input Voltage L1 Input Current L1 Output Voltage L1 Output Current L1 Input Voltage L2 Input Current L2 Input Voltage L3 Input Current L3
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
124
Table 46
Automatic Battery Test Enabled Battery Charger On Inverter Ready Power Factor Correction State Load on Inverter Bypass Active Replace Battery Battery Under Test Load on Battery Load on Bypass Load on Manual Bypass Load Transferred to Bypass Due to UPS Fault Transfer Inhibit Output Off Pending Low Battery - Shutdown Imminent Output Overload UPS Overload Output Off Check Air Filter - Replace Transformer Over Temperature Input Power Supply Fail Internal Device Communication Failure Device Active Alarm Main Control Warning Redundant Control Warning Control Module Failure Redundant Control Module Failed User Interface Module Failed UPS Power Not Redundant Power Module Failure Battery Module Failure Power Module Warning Battery Module Warning
125
Table 47
Data Description Number of Input Lines Number of Bypass Lines Number of Output Lines Number of Power Mod. Number of Battery Modules Installed Device Maximum Frame Capacity Device System Capacity Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Device Auto Restart Percent Setpt Device Low Battery Time Next Battery Auto Test Time Overload Alarm Limit Minimum Redundant Power Modules Load (Apparent Power) Load (Real Power) Load / Capacity Input Frequency Output Frequency Bypass Frequency
30112
Battery Voltage Battery Time Remaining Battery Charge Percentage Battery Temperature Transformer Temperature Redundant Power Modules Active Power Module Count Battery Module Active Count Battery Test Result Input Voltage L1 Input Current L1 Bypass Voltage L1 Bypass Current L1 Output Voltage L1 Output Current L1 Power Module Failure Count Battery Module Failure Count Power Module Warning Count Battery Module Warning Count
30113 30115 30116 30117 30121 30124 30126 30127 30130 30153 30154 30159 30160 30163 30164 30304 30305 30306 30307
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
126
Table 48
Economode DC-To-DC Converter On Battery Charge Compensation Inverter Ready Power Factor Correction State Battery Charge Mode Load On Inverter Bypass Active Battery Under Test Load On Battery Overload Transfer To Bypass Input Switch Open Generator Disconnected Bypass Transfer Count Block Static Bypass Switch Disabled Low Battery - Shutdown Imminent Output Overload UPS Load Joint Mode Output Off Inverter Unsynchronized Main Neutral Lost Fan Failure Ambient Over Temperature Rectifier Over Temperature Rectifier Inductor Over Temperature Inverter Over Temperature Inverter Inductor Over Temperature Battery Converter Over Temperature DC Bus Balancer Over Temperature Input Power Supply Fail Input BrownOut Bad Input Frequency Bypass Phase Rotation Error Bypass Phase Loss Bypass Input Voltage/Frequency Fault Output Fuse Blown Output Over Voltage Charger Failed Battery Fault Battery Contact Fail Battery Converter Over Current Battery Converter Fail DC Bus Balancer Over Current
127
Table 48
DC Bus Balancer Fault DC Bus 1 Power Supply Fail Rectifier Fuse Fail Rectifier Startup Failure Rectifier Fault Rectifier Current Limit Inverter DC Voltage Low Shutdown Inverter Fault Inverter DC Offset Overload Inverter Contactor Fail Inverter Current Limit Parallel Low Battery Warning Load Share Fault Parallel System Fault Parallel Connection Error Parallel System Overload Parallel Transfer To Static Bypass Switch Inverter Communication Fail Rectifier Communication Failure Parallel Communication Fault Operation Fault
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
128
Table 49
Number of Input Lines Number of Bypass Lines Number of Output Lines Number of SubModules Module Number Device Module Count Device Redundant Count Device Module Mode Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal DC Bus #1 Voltage Nominal DC Bus #2 Voltage Nominal Battery Float Voltage Load Bus Sync Mode Auto Restart Delay Device Low Battery Time Input Frequency Output Frequency Bypass Frequency
30112
Battery Voltage Battery Current (Charge/Discharge) Battery Time Remaining Battery Charge Percentage Battery Temperature Ambient Temperature Parallel Load Source Rotary Breaker
1 1 1 1 1 1 1 1
30130
30151 30153
1 1
129
Table 49
Input Current L1 Input Power Factor L1 Bypass Voltage L1 Output Voltage L1 Output Current L1 Output Load L1 Output Power Factor L1 Apparent Output Power L1 Reactive Output Power L1 Output Power L1 Output Current Crest Factor L1 Input Voltage L2-L3 Input Voltage L2 Input Current L2 Input Power Factor L2 Bypass Voltage L2 Output Voltage L2 Output Current L2 Output Load L2 Output Power Factor L2 Apparent Output Power L2 Reactive Output Power L2 Output Power L2 Output Current Crest Factor L2 Input Voltage L3-L1 Input Voltage L3 Input Current L3 Input Power Factor L3 Bypass Voltage L3 Output Voltage L3 Output Current L3 Output Load L3 Output Power Factor L3 Apparent Output Power L3 Reactive Output Power L3 Output Power L3 Output Current Crest Factor L3
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
130
Table 50
Battery Self Test Battery Low Shutdown System Shutdown - REPO UPS Output on Bypass Output Load on Maint. Bypass Main Battery Disconnect Open Bypass - Excess Auto Retransfers Battery Low System Shutdown - EPO System Output Off Battery Over Temperature Inlet Air Over Temperature System Input Current Imbalance System Input Phs Rotation Error Rectifier Failure Inverter Failure Main Controller Fault Bypass Not Available Bypass Overload Phase A Bypass Overload Phase B Bypass Overload Phase C Bypass Auto Retransfer Failed Bypass Static Switch Unavailable Bypass Static Switch Overload Bypass Excessive Pulse Parallel Bypass Auto Transfer Failed Bypass Frequency Error Bypass - Manual Rexfr Inhibited Bypass - Manual Xfr Inhibited Bypass Static Switch Off Extrnl Battery Charging Reduced-Extrnl Battery Capacity Low Battery Discharging Battery Temperature Imbalance Battery Temperature Sensor Fault Battery Charging Inhibited Battery Circuit Breaker 1 Open Battery Circuit Breaker 2 Open Battery Circuit Breaker 3 Open Battery Circuit Breaker 4 Open Battery Circuit Breaker 5 Open Battery Circuit Breaker 6 Open Battery Circuit Breaker 7 Open
131
Table 50
Liebert NXL SA, SR, SN, MM, CD - Status and Coil (continued)
Data Label Status 10347 10348 10349 10350 10351 10352 10353 10354 10355 10356 10357 10358 10359 10360 10361 10362 10363 10364 10365 10366 10367 10368 10369 10370 10371 10372 10373 10374 10375 10376 10377 10378 10379 10380 10381 10382 10383 10384 10385 10386 10387 10388 10389 Coil # of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Notes Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SMS SMS NXL Type N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS 1+N, 1+1, SMS 1+N, 1+1, SMS 1+N, 1+1, SMS 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS CE only CE only SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 8 Open Battery - External Monitor 1 Battery - External Monitor 2 Battery Over Temperature DC Bus Ground Fault - Positive DC Bus Ground Fault - Negative System Output Low Power Factor Leading Power Factor Output Amp Over User Limit-Phs A Output Amp Over User Limit-Phs B Output Amp Over User Limit-Phs C System Output Fault Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C Inverter Inhibit - External Inverter Shutdown - Overload Inverter Off - External Inverter Static Switch SCR Short Equipment Over Temperature Equipment Over Temperature Equipment Temperature Sensor Fail Input Contact 01 Input Contact 02 Input Contact 03 Input Contact 04 Input Contact 05 Input Contact 06 Input Contact 07 Input Contact 08 Input Contact 09 Input Contact 10 Input Contact 11 Input Contact 12 Input Contact 13 Input Contact 14 Input Contact 15 Input Contact 16 Rectifier Operation Inhibit-Ext System Fan Failure - Redundant Multiple Fan Failure Auto Restart In Progress Automatic Restart Failed
132
Table 50
Liebert NXL SA, SR, SN, MM, CD - Status and Coil (continued)
Data Label Status 10390 10391 10392 10393 10394 10396 10397 10398 10399 10400 10401 10402 10403 10404 10405 10407 10408 10409 10410 10510 10521 10522 10523 10524 10525 10526 10527 10528 10529 10530 10531 10532 Coil # of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Notes Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm SCC SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC SCC SCC, 1+N, 1+1 SCC, 1+N, 1+1 NXL Type SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1 SCC, N+1, 1+N, 1+1 SCC, 1+N, 1+1
Fuse Failure System Breaker(s) Open Failure System Breaker(s) Close Failure Input Filter Cycle Lock Service Code Active LBS Inhibited Controls Reset Required Battery Test Failed Auto Restart Inhibited - Ext Battery Test Inhibited Battery Equalize Backfeed Breaker Open On Generator Power Supply Failure Battery Ground Fault System Input Power Problem System Input Current Limit Internal Communications Failure System Controller Error Output Output Of/Uf MultiModule Parallel Comm Warning System Comm Fail Loss of Redundancy BPSS Startup Inhibit MMS Transfer Inhibit MMS Retransfer Inhibit MMS Loss of Sync Pulse MMS Overload MMS On Battery MMS Low Battery Warning MMS Module Alarm Active MMS Sharing Calib Active Intelligent Paralleling Module In Standby - Intelligent Paralleling ECO Mode ECO Mode Active ECO Mode Suspended Excess ECO Suspends System LBS Active - Master LBS Active - Slave
10543
Active on Alarm
1 1 1 1 1
Active on Alarm Active on Alarm Active on Alarm Active on Alarm Active on Alarm
SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
133
Table 51
30007
Output Apparent Power Rating System Input Nominal Voltage System Output Nominal Voltage Bypass Nominal Voltage System Input Nominal Frequency System Output Nominal Frequency System Output Apparent Power System Output Power System Input Frequency System Output Frequency Bypass Input Frequency Battery Volts at Main Disconnect Battery Time Remaining Battery Percentage Charge Inlet Air Temperature System Input RMS A-B System Input RMS Current Phase A Bypass Input Voltage RMS A-B System Output Voltage RMS A-B System Output Voltage RMS A-N System Output RMS Current Phs A
30021 30027 30028 30029 30031 30032 30102 30104 30107 30108 30109 30113 30115 30116 30119 30151 30154 30157 30161 30162 30164
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
x / 10 x / 10 x / 10 x / 10 x / 10 -
134
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30165 30166 30201 30204 30207 30211 30212 30214 30215 30216 30251 30254 30257 30261 30262 30264 30265 30266 30309 30310 Holding # of Register Regs 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale x / 100 x / 100 x / 100 sec AH 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High deg sec 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High VAC A AC VAC VAC VAC A AC % VAC A AC VAC VAC VAC A AC % Units / Notes % NXL Types N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
System Output Pct Power Phase A System Output Power Factor Phs A System Input RMS B-C System Input RMS Current Phase B Bypass Input Voltage RMS B-C System Output Voltage RMS B-C System Output Voltage RMS B-N System Output RMS Current Phs B System Output Pct Power Phase B System Output Power Factor Phs B System Input RMS C-A System Input RMS Current Phase C Bypass Input Voltage RMS C-A System Output Voltage RMS C-A System Output Voltage RMS C-N System Output RMS Current Phs C System Output Pct Power Phase C System Output Power Factor Phs C Battery Discharge Time Battery Amp-Hours Consumed This Discharge Input Qualification Status
30312
30313 30314
1 1
30315
135
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30316 30317 Holding # of Register Regs 1 1 Scale Units / Notes hr W Masks: Year 0xFFFF 0000 Mon 0x0000 FF00 Day 0x0000 00FF Masks: Hour 0xFF00 0000 Min 0x00FF 0000 Sec 0x0000 FF00 Masks: Year 0xFFFF 0000 Mon 0x0000 FF00 Day 0x0000 00FF Masks: Hour 0xFF00 0000 Min 0x00FF 0000 Sec 0x0000 FF00 VDC A DC 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High % % % 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High sec 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High hr 0 = 6 Pulse 1 = 12 Pulse 2 = 18 Pulse 3 = 24 Pulse 0 = Not Installed 1 = Installed 0 = Not Installed 1 = Installed NXL Types N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
30318
30320
30322
30324
N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
30326 30327
1 1
30328
System Output Pct Pwr (VA) Phs A System Output Pct Pwr (VA) Phs B System Output Pct Pwr (VA) Phs C
1 1 1
30332
30333
30334
30335
30337
30338 30339
1 1
136
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30340 30341 Holding # of Register Regs 1 1 Scale Units / Notes 0 = Not Installed 1 = Installed 0 = off 1 = on 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 0 = Single Module System 1 = Module (1 + 1) 2 = Module (1 + N) 3 = Module (N + 1) 4 = System Control Cabinet 5 = Main Static Switch 0 = Not Applicable 1 = Continuous Duty 2 = Momentary Duty 0 = None 1 = Utility (mains) 2 = Generator kW 0 = Not Installed 1 = Installed A AC 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3-phase, no neutral) 4 = Four Wire (3 phases + neutral) NXL Types N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
System Status
30342
30343
30344
SCC, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1
System Input Power Source Output Real Power Rating Input Isolation Transformer System Output Maximum Amp Rating
1 1 1 1
30353
30354 30355
1 1
137
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register Holding # of Register Regs Scale Units / Notes 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass 0 = off 1 = on VDC VDC VDC VDC VDC VDC VDC VDC deg C deg C deg C deg C deg C deg C deg C deg C 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed NXL Types SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS Depricated N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
30356
Static Bypass Switch Battery Volts for Cabinet 1 Battery Volts for Cabinet 2 Battery Volts for Cabinet 3 Battery Volts for Cabinet 4 Battery Volts for Cabinet 5 Battery Volts for Cabinet 6 Battery Volts for Cabinet 7 Battery Volts for Cabinet 8 Battery Temperature for Cabinet 1 Battery Temperature for Cabinet 2 Battery Temperature for Cabinet 3 Battery Temperature for Cabinet 4 Battery Temperature for Cabinet 5 Battery Temperature for Cabinet 6 Battery Temperature for Cabinet 7 Battery Temperature for Cabinet 8 Backfeed Breaker
30357 30358 30359 30360 30361 30362 30363 30364 30365 30366 30367 30368 30369 30370 30371 30372 30373 30374
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
30375
30376
30377
138
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30378 Holding # of Register Regs 1 Scale Units / Notes 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed AH sec 0 = off 1 = on 1 = Unknown 2 = Normal 3 = Low 4 = Depleted 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer NXL Types N+1, 1+N, 1+1, SMS Depricated 1+N, 1+1, SMS SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS LEU/LAP only SCC, 1+N, 1+1 N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
30379
30380
Rectifier Feed Breaker (RFB) Maintenance Bypass Breaker (MBB) Maintenance Isolation Breaker (MIB) Output Series Static Switch
30381
30382
30383
30384
Module Output Breaker (MOB) Battery Amp-Hours Consumed Auto Retransfer Time Remaining Inverter On/Off State
1 2 1 1
30390
30391
39998
49998
SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS
30491
39998
49998
139
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register Holding # of Register Regs Scale Units / Notes 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3 phase, no neutral) 4 = Four Wire (3 phases + neutral) 0 = Single Module System 33 1 = Single Module System 34 2 = Single Module System 44 3 = 1+1 33 4 = 1+1 34 5 = 1+1 44 6 = 1+N 33 7 = 1+N 34 8 = 1+N 44 9 = N+1 33 10 = N+1 34 11 = N+1 44 12 = SCC w/ Continuous Duty SS 33 13 = SCC w/ Continuous Duty SS 44 14 = SCC w/ Momentary Duty SS 15 = Main Static Switch NXL Types
30496
Configuration Description
30497
Ratings System UPS Module Count MultiModule Multi-module System Output Voltage RMS A-B Multi-module System Output Voltage RMS B-C Multi-module System Output Voltage RMS C-A Multi-module System Output Voltage RMS A-N Multi-module System Output Voltage RMS B-N Multi-module System Output Voltage RMS C-N 30505 30506 30507 30508 30509 30510 1 1 1 1 1 1 Units : VAC Units : VAC Units : VAC Units : VAC Units : VAC Units : VAC SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 30501 1 SCC, 1+N, 1+1, SMS
140
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30511 30512 30513 30514 30515 30516 30517 30518 30519 30520 30521 30522 30523 30524 30525 30526 30527 30528 30529 Holding # of Register Regs 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed Scale : x / 100 Scale : x / 100 Scale : x / 100 Units : % Units : % Units : % Units : % Units : % Units : % Scale : x / 10 Scale Units / Notes Units : A AC Units : A AC Units : A AC Units : Hz Units : kW Units : kVA NXL Types SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC SCC SCC SCC SCC SCC SCC, 1+N, 1+1 N+1, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1 SCC, 1+N, 1+1
Sum of MMS Output RMS Currents for Phase A Sum of MMS Output RMS Currents for Phase B Sum of MMS Output RMS Currents for Phase C MMS Output Frequency MMS Output Power MMS Output Apparent Power MMS Output Power Factor Phase A MMS Output Power Factor Phase B MMS Output Power Factor Phase C MMS Output Pct Power Phase A MMS Output Pct Power Phase B MMS Output Pct Power Phase C MMS Output Pct Apparent Pwr (kVA) Phase A MMS Output Pct Apparent Pwr (kVA) Phase B MMS Output Pct Apparent Pwr (kVA) Phase C Number of Redundant Modules MMS Module Number Number of Modules in an MMS Module Output Breaker for Module 1 (MOB1) Module Output Breaker for Module 2 (MOB2) Module Output Breaker for Module 3 (MOB3) Module Output Breaker for Module 4 (MOB4) Module Output Breaker for Module 5 (MOB5) Module Output Breaker for Module 6 (MOB6)
30530
30531
30532
30533
30534
141
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30535 Holding # of Register Regs 1 Scale Units / Notes 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = None 1 = Alarm 2 = Fault 1 = Unknown 2 = Normal 3 = Low 4 = Depleted 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer NXL Types SCC, 1+N, 1+1 SCC, 1+N, 1+1 1+N, 1+1
Module Output Breaker for Module 7 (MOB7) Module Output Breaker for Module 8 (MOB8) Bypass Isolation Breaker for Module 1 (BIB1) Bypass Isolation Breaker for Module 2 (BIB2) Bypass Isolation Breaker for Module 3 (BIB3) Bypass Isolation Breaker for Module 4 (BIB4) Bypass Isolation Breaker for Module 5 (BIB5) Bypass Isolation Breaker for Module 6 (BIB6) Bypass Isolation Breaker for Module 7 (BIB7) Bypass Isolation Breaker for Module 8 (BIB8) System Output Breaker (UOB)
30536
30537
30538
1+N, 1+1
30539
1+N, 1+1
30540
1+N, 1+1
30541
1+N, 1+1
30542
1+N, 1+1
30543
1+N, 1+1
30544
1+N, 1+1
30545
SCC
System Load Bank Breaker (LBB) System Isolation Output Breaker (IOB) SCC Event Summary
30546
SCC
30547
SCC
30548
SCC
30549
30550
ModuleList 1
142
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30554 30555 30556 Holding # of Register Regs 1 1 1 Scale Units / Notes 0 = Failed 1 = Normal 0 = None 1 = Alarm 2 = Fault 0 = off 1 = on 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass Units : kW Units : kVA Units : VDC Units : A DC Units : min NXL Types SCC, 1+N, 1+1 SCC, 1+N, 1+1 1+N, 1+1 SCC, 1+N, 1+1
MMS Inter-Module Comm Status MMS Event Summary MMS Module Inverter Status MMS Module Output Voltage Status
30557
30558
MMS Module Total kW Output MMS Module Total kVA Output MMS Module DC Bus Voltage MMS Module Battery Current MMS Module Battery Time Remaining ModuleList 2 MMS Inter-Module Comm Status MMS Event Summary MMS Module Inverter Status MMS Module Output Voltage Status
1 1 1 1 1
1 1 1 1
0 = Failed 1 = Normal 0 = None 1 = Alarm 2 = Fault 0 = off 1 = on 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass Units : kW Units : kVA Units : VDC Units : A DC Units : min
SCC, 1+N, 1+1 SCC, 1+N, 1+1 1+N, 1+1 SCC, 1+N, 1+1
30571
MMS Module Total kW Output MMS Module Total kVA Output MMS Module DC Bus Voltage MMS Module Battery Current MMS Module Battery Time Remaining ModuleList 8 MMS Inter-Module Comm Status MMS Event Summary MMS Module Inverter Status
1 1 1 1 1
1 1 1
143
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30648 Holding # of Register Regs 1 Scale Units / Notes 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass Units : kW Units : kVA Units : VDC Units : A DC Units : min NXL Types SCC, 1+N, 1+1
30649
MMS Module Total kW Output MMS Module Total kVA Output MMS Module DC Bus Voltage MMS Module Battery Current MMS Module Battery Time Remaining Intelligent Paralleling Intelligent Parallel Operation State Intelligent Parallel Mode Intelligent Paralleling Shutdown Delay Intelligent Parallel Minimum Redundancy Intelligent Parallel Maximum Time in Standby ECO Mode ECO Mode Operation State Continuous Operation - ECO Mode Maximum Auto Suspensions - ECO Mode Restart Delay - ECO Mode Time Remaining - ECO Mode EcoModeSchedule 1 Schedule Operation State - ECO Mode Schedule Action - ECO Mode
1 1 1 1 1
1 1 1 1 1
SCC, N+1, 1+N, 1+1 SCC, N+1, 1+N, 1+1 SCC, N+1, 1+N, 1+1 SCC, N+1, 1+N, 1+1
Units : day
SCC, N+1, 1+N, 1+1 SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
40666
1 1 1 1 1
SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
30674 30675
1 1
0 = disabled 1 = enabled 0 = stop 1 = start 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Units : hr
30676
30677
144
Table 51
Liebert NXL SA, SR, SN, MM, CD - Input and Holding (continued)
Data Label Input Register 30678 Holding # of Register Regs 1 Scale Units / Notes Units : min NXL Types SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
Schedule Minute - ECO Mode EcoModeSchedule 2 Schedule Operation State - ECO Mode Schedule Action - ECO Mode
30682 30683
1 1
0 = disabled 1 = enabled 0 = stop 1 = start 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Units : hr Units : min
30684
Schedule Hour - ECO Mode Schedule Minute - ECO Mode EcoModeSchedule 16 Schedule Operation State - ECO Mode Schedule Action - ECO Mode
30685 30686
1 1
SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS
30794 30795
1 1
0 = disabled 1 = enabled 0 = stop 1 = start 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Units : hr Units : min
30796
30797 30798
1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
145
Table 52
Data Label
Auto Restart In Progress Auto Restart Inhibited - Ext Automatic Restart Failed Backfeed Breaker Open Backfeed Breaker Battery - External Monitor 1 Battery - External Monitor 2 Battery Amp-Hours Consumed This Discharge Battery Amp-Hours Consumed Battery Automatic Test Inhibited Battery Capacity Low Battery Cell Count - Lead Acid Battery Cell Count-Nickel Cadmium Battery Charging Error Battery Charging Inhibited Battery Charging ReducedExtrnl Battery Circuit Breaker 1 Open Battery Circuit Breaker 2 Open Battery Circuit Breaker 3 Open Battery Circuit Breaker 4 Open Battery Circuit Breaker 5 Open Battery Circuit Breaker 6 Open Battery Circuit Breaker 7 Open Battery Circuit Breaker 8 Open Battery Commission Date Battery Discharge Power Battery Discharge Time Battery Discharging Battery Equalize Battery Ground Fault Battery Last Discharge Date Battery Low Shutdown Battery Low Battery Over Temperature Battery Percentage Charge Battery Self Test Battery Temperature for Cabinet Battery Temperature Imbalance Battery Temperature Sensor Fault Battery Test Failed Battery Time Remaining
146
Table 52
Data Label
Battery Total Discharge Time Battery Volts at Main Disconnect Battery Volts for Cabinet BPSS Startup Inhibit Bypass - Excess Auto Retransfers Bypass - Manual Rexfr Inhibited Bypass - Manual Xfr Inhibited Bypass Auto Retransfer Failed Bypass Auto Transfer Failed Bypass Excessive Pulse Parallel Bypass Frequency Error Bypass Input Frequency Bypass Input Voltage RMS A-B Bypass Input Voltage RMS B-C Bypass Input Voltage RMS C-A Bypass Input Wire Configuration Bypass Isolation Breaker (BIB) Bypass Isolation Breaker for Module 1 (BIB1) Bypass Isolation Breaker for Module 2 (BIB2) Bypass Isolation Breaker for Module 3 (BIB3) Bypass Isolation Breaker for Module 4 (BIB4) Bypass Isolation Breaker for Module 5 (BIB5) Bypass Isolation Breaker for Module 6 (BIB6) Bypass Isolation Breaker for Module 7 (BIB7) Bypass Isolation Breaker for Module 8 (BIB8) Bypass Nominal Voltage Bypass Not Available Bypass Overload Phase A Bypass Overload Phase B Bypass Overload Phase C Bypass Qualification Status Bypass Retransfer Time Remaining Bypass SS Overload Time Remain
147
Table 52
Data Label
Bypass Static Switch Off Extrnl Bypass Static Switch Overload Bypass Static Switch Unavailable Bypass Sync Phase Difference Configuration Description Continuous Operation - ECO Mode Controls Reset Required DC Bus Current DC Bus Ground Fault - Negative DC Bus Ground Fault - Positive DC Bus Qualification Status DC Bus Voltage ECO Mode Active ECO Mode Operation State ECO Mode Suspended Equipment Over Temperature Equipment Temperature Sensor Fail Excess ECO Suspends Fuse Failure Inlet Air Over Temperature Inlet Air Temperature Input Breaker (CB1/RIB) Input Contact 01 Input Contact 02 Input Contact 03 Input Contact 04 Input Contact 05 Input Contact 06 Input Contact 07 Input Contact 08 Input Contact 09 Input Contact 10 Input Contact 11 Input Contact 12 Input Contact 13 Input Contact 14 Input Contact 15 Input Contact 16 Input Filter Cycle Lock
148
Table 52
Data Label
Input Isolation Transformer Input Qualification Status Intelligent Parallel Maximum Time in Standby Intelligent Parallel Minimum Redundancy Intelligent Parallel Mode Intelligent Parallel Operation State Intelligent Paralleling Shutdown Delay Internal Bypass Breaker (CB3) Internal Communications Failure Inverter Failure Inverter Inhibit - External Inverter Off - External Inverter On/Off State Inverter Output Qualification Status Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C Inverter Overload Time Remaining Inverter Shutdown - Overload Inverter Static Switch SCR Short LBS Active - Master LBS Active - Slave LBS Active LBS Inhibited Leading Power Factor Loss of Redundancy Main Battery Disconnect Open Main Controller Fault Maintenance Bypass Breaker (MBB) Maintenance Isolation Breaker (MIB) Maximum Auto Suspensions ECO Mode
149
Table 52
Data Label
MMS Event Summary MMS Inter-Module Comm Status MMS Loss of Sync Pulse MMS Low Battery Warning MMS Module Alarm Active MMS Module Battery Current MMS Module Battery Time Remaining MMS Module DC Bus Voltage MMS Module Inverter Status MMS Module Number MMS Module Output Source MMS Module Output Voltage Status MMS Module Total kVA Output MMS Module Total kW Output MMS On Battery MMS Output Apparent Power MMS Output Frequency MMS Output Pct Apparent Pwr (kVA) Phase A MMS Output Pct Apparent Pwr (kVA) Phase B MMS Output Pct Apparent Pwr (kVA) Phase C MMS Output Pct Power Phase A MMS Output Pct Power Phase B MMS Output Pct Power Phase C MMS Output Power Factor Phase A MMS Output Power Factor Phase B MMS Output Power Factor Phase C MMS Output Power MMS Overload MMS Power Sharing MMS Retransfer Inhibit MMS Transfer Inhibit MMS UPS Battery Status MMS UPS Output Source
150
Table 52
Data Label
Module In Standby - Intelligent Paralleling Module Output Breaker (MOB) Module Output Breaker for Module 1 (MOB1) Module Output Breaker for Module 2 (MOB2) Module Output Breaker for Module 3 (MOB3) Module Output Breaker for Module 4 (MOB4) Module Output Breaker for Module 5 (MOB5) Module Output Breaker for Module 6 (MOB6) Module Output Breaker for Module 7 (MOB7) Module Output Breaker for Module 8 (MOB8) Multi-module System Output Voltage RMS A-B Multi-module System Output Voltage RMS A-N Multi-module System Output Voltage RMS B-C Multi-module System Output Voltage RMS B-N Multi-module System Output Voltage RMS C-A Multi-module System Output Voltage RMS C-N Multiple Fan Failure Number of Modules in a MMS Number of Redundant Modules On Generator Output Amp Over User LimitPhs A Output Amp Over User LimitPhs B Output Amp Over User LimitPhs C Output Apparent Power Rating Output Breaker (CB2/IOB) Output Load on Maint. Bypass Output Of/Uf Output Qualification Status Output Real Power Rating Output Series Static Switch Output Wire Configuration
151
Table 52
Data Label
Parallel Comm Warning Power Supply Failure Rectifier Active Filter Rectifier Failure Rectifier Feed Breaker (RFB) Rectifier Input Passive Filter Rectifier Operation Inhibit-Ext Rectifier Passive Filter Switch Rectifier Pulse Count Rectifier Status Restart Delay - ECO Mode SBS Load Disconnect SCC Event Summary Schedule Action - ECO Mode Schedule Day of Week - ECO Mode Schedule Hour - ECO Mode Schedule Minute - ECO Mode Schedule Operation State ECO Mode Service Code Active Static Bypass Switch Static Switch Type Sum of MMS Output RMS Currents for Phase A Sum of MMS Output RMS Currents for Phase B Sum of MMS Output RMS Currents for Phase C System Breaker(s) Close Failure System Breaker(s) Open Failure System Comm Fail System Controller Error System Date and Time System Date and Time System Fan Failure Redundant System Input Current Imbalance System Input Current Limit System Input Frequency System Input Nominal Frequency
152
Table 52
Data Label
System Input Nominal Voltage System Input Phs Rotation Error System Input Power Problem System Input Power Source System Input RMS A-B System Input RMS B-C System Input RMS C-A System Input RMS Current Phase A System Input RMS Current Phase B System Input RMS Current Phase C System Isolation Output Breaker (IOB) System Load Bank Breaker (LBB) System Output Apparent Power System Output Breaker (UOB) System Output Fault System Output Frequency System Output Low Power Factor System Output Maximum Amp Rating System Output Nominal Frequency System Output Nominal Voltage System Output Off System Output Pct Power Phase A System Output Pct Power Phase B System Output Pct Power Phase C System Output Pct Pwr (VA) Phs A System Output Pct Pwr (VA) Phs B System Output Pct Pwr (VA) Phs C System Output Power Factor Phs A System Output Power Factor Phs B System Output Power Factor Phs C System Output Power
153
Table 52
Data Label
System Output RMS Current Phs A System Output RMS Current Phs B System Output RMS Current Phs C System Output Voltage RMS AB System Output Voltage RMS AN System Output Voltage RMS BC System Output Voltage RMS BN System Output Voltage RMS CA System Output Voltage RMS CN System Shutdown - EPO System Shutdown - REPO System Status System UPS Module Count Time Remaining - ECO Mode Total kW Hours Saved Total System Operating Time Trap Filter Disconnect UPS Battery Status UPS Module Type UPS Output on Bypass UPS Output Source UPS System Output Source
154
Table 53
Audible Alarm Enabled Automatic Battery Test Enabled Battery Charge Compensation Inverter Ready Load Circuit 1 State Load Circuit 2 State Load Circuit 3 State Load Circuit 4 State Load Circuit 5 State Load Circuit 6 State Load Circuit 7 State Load Circuit 8 State Load Circuit 9 State Load Circuit 10 State Load Circuit 11 State Load Circuit 12 State Load Circuit 13 State Load Circuit 14 State Load Circuit 15 State Load Circuit 16 State Load On Inverter Boost Mode On Buck Mode On Battery Under Test Shutdown Reason - Over Temperature Shutdown Reason - Overload Shutdown - Output Short Shutdown Reason - Remote Shutdown Load On Battery Output Off Pending Low Battery - Shutdown Imminent Output Overload Over Temperature Warning Battery Over Temperature CB Trip Input Power Supply Fail Input Over Voltage Input Under Voltage Bad Input Frequency Output Under Voltage Output Over Voltage
155
Table 54
Data Description Number of Input Lines Number of Bypass Lines Number of Output Lines Number of SubModules
30013
40013
Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Device Low Battery Time Load (Apparent Power) Load / Capacity Input Frequency Output Frequency
30021 30027 30028 30030 30031 30032 30033 30034 30051 30053 30102 30106 30107 30108
40021 40027 40028 40030 40031 40032 40033 40034 40051 40053 -
2 1 1 1 1 1 1 1 1 1 2 1 1 1
10 10 100 10 10
30112
1 1 1
30130
Input Voltage L1 Output Voltage L1 Output Current L1 Input Maximum Voltage L1 Input Minimum Voltage L1 Output Maximum Voltage L1 Output Minimum Voltage L1 Black Out Count Brown Out Count
1 1 1 1 1 1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
156
Table 55
Data Description Audible Alarm Enabled Automatic Battery Test Enabled DC-To-DC Converter On Battery Charger On Load Circuit 1 State Load Circuit 2 State Load Circuit 3 State Load Circuit 4 State Load Circuit 5 State Load Circuit 6 State Load Circuit 7 State Load Circuit 9 State Load Circuit 10 State Load Circuit 11 State Load Circuit 12 State Load Circuit 13 State Load Circuit 14 State Load Circuit 15 State Load Circuit 16 State Load On Inverter Boost Mode On Buck Mode On Replace Battery Battery Under Test Shutdown Reason - Over Temperature Shutdown Reason - Overload Shutdown Reason - Output Short Shutdown Reason - Line Neutral Swap Shutdown Reason - Low Battery Shutdown Reason - Remote Shutdown Shutdown Reason - Input Under Voltage Shutdown Reason - Hardware Load On Battery Output Off Pending Low Battery - Shutdown Imminent Output Overload Over Temperature Warning Input Power Supply Fail Input Over Voltage Input Under Voltage Input BrownOut Bad Input Frequency Output Under Voltage Output Over Voltage Charger Failed Battery Under Voltage Battery Over Voltage
Status 10002 10003 10042 10044 10057 10058 10059 10060 10061 10062 10063 10065 10066 10067 10068 10069 10070 10071 10072 10073 10075 10076 10081 10082 10086 10087 10089 10090 10092 10093 10094 10096 10128 10151 10152 10154 10171 10186 10187 10188 10189 10190 10218 10219 10234 10241 10242
Coil 2 3 -
Number of Bits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Scale -
Notes / Units -
157
Table 56
Data Description Number of Input Lines Number of Output Lines Number of SubModules
# of Reg. 1 1 1
Scale -
Notes / Units Bits 12 - 15 Bits 8 - 11 There are 16 possible Load Circuits. Each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1, then the Load Circuit is supported. VA V V A Hz Hz V Minutes V Seconds Minutes deg C deg C VA W % Hz Hz 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging V Minutes % deg C V A V A V V V V -
30013
40013
Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Nominal Battery Capacity Nominal Battery Float Voltage Auto Restart Delay Device Low Battery Time Ambient Temperature Warning Point Over Temperature Limit Point Load (Apparent Power) Load (Real Power) Load / Capacity Input Frequency Output Frequency
30021 30027 30028 30030 30031 30032 30033 30034 30037 30038 30051 30053 30069 30072 30102 30104 30106 30107 30108
40021 40027 40028 40030 40031 40032 40033 40034 40037 40038 40051 40053 40069 40072 -
2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1
10 10 100 10 10
30112
Battery Voltage Battery Time Remaining Battery Charge Percentage Ambient Temperature Battery Test Result Input Voltage L1 Input Current L1 Output Voltage L1 Output Current L1 Input Maximum Voltage L1 Input Minimum Voltage L1 Output Maximum Voltage L1 Output Minimum Voltage L1 Black Out Count Brown Out Count
30113 30115 30116 30119 30130 30153 30154 30163 30164 30180 30181 30182 30183 30301 30302
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
158
Table 57
Automatic Restart Enabled Battery Charge Compensation Inverter Ready Load Circuit 1 State Load Circuit 2 State Load Circuit 3 State Load Circuit 4 State Load Circuit 5 State Load Circuit 6 State Load Circuit 7 State Load Circuit 8 State Load Circuit 9 State Load Circuit 10 State Load Circuit 11 State Load Circuit 12 State Load Circuit 13 State Load Circuit 14 State Load Circuit 15 State Load Circuit 16 State Load On Inverter Bypass Active Buck On Replace Battery Battery Under Test Load On Battery Low Battery - Shutdown Imminent Output Overload Over Temperature Warning Battery Over Temperature CB Trip Input Power Supply Fail Input Over Voltage Input Under Voltage Bad Input Frequency Bypass Input Voltage/Frequency Fault Output Under Voltage Output Over Voltage Battery Charger Fail
159
Table 58
Data Description Number of Input Lines Number of Bypass Lines Number of Output Lines Number of SubModules
30013
40013
Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Device Low Battery Time Load (Apparent Power) Load (Real Power) Load / Capacity Input Frequency Output Frequency Bypass Frequency Battery Charge Status Battery Voltage Battery Current Battery Time Remaining Battery Charge Percentage
30021 30027 30028 30029 30030 30031 30032 30033 30034 30053 30102 30104 30106 30107 30108 30109 30112 30113 30114 30115 30116
40021 40027 40028 40029 40030 40031 40032 40033 40034 40053 -
2 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1
10 10 100 10 10 10 -
30130
Input Voltage L1 Input Current Bypass Voltage L1 Bypass Current L1 Output Voltage L1 Output Current L1 Input Voltage L2 Input Current L2
1 1 1 1 1 1 1 1
160
Table 58
Data Description Bypass Voltage L2 Bypass Current L2 Output Voltage L2 Output Current L2 Input Voltage L3 Input Current L3 Bypass Voltage L3 Bypass Current L3 Output Voltage L3 Output Current L3 Black Out Count Brown Out Count Transient Count Silent Audible Alarm Battery Start Open UPS Output Switch Reboot UPS Output Switch Close UPS Output Switch Transfer Load to Bypass Transfer Load to Inverter Reset UPS Statistic data Turn UPS Outlets On Turn UPS Outlets Off
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
161
Table 59
Auto Retransfer Primed Load On Inverter Load On Bypass Battery data Buffer Full Shutdown Reason - Hardware Load On Battery Load On Bypass Manual Reset Transfer Emergency Transfer Battery Switch Open Input Switch Open Output Switch open SBS Unable Low Battery - Shutdown Imminent Output Frequency Off Output Overload System Emergency Off Reverse Power Fan Fail Over Temperature Warning Ambient Over Temperature Input Power Supply Fail Input Phase Rotation Error Bypass Input Voltage Fail Output Under Voltage Output Over Voltage DC Ground Fault DC Cap Fuse Blown Rectifier Fuse Blown Inverter Fuse Blown Customer Alarm 1 Customer Alarm 2 Customer Alarm 3 Customer Alarm 4 Customer Alarm 5 Customer Alarm 6 Customer Alarm 7 Customer Alarm 8
162
Table 60
Number of Input Lines Number of Bypass Lines Number of Output Lines Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Input Current Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Silence Alarm Load (Apparent Power) Load (Real Power) Load / Capacity Output Frequency Bypass Frequency Battery Charge Status Battery Voltage Battery Current Battery Time Remaining Battery Charge Percentage Input Voltage L1 Input Current L1 Bypass Voltage L1 Bypass Current L1 Output Voltage L1 Output Current L1 Input Voltage L2 Input Current L2 Bypass Voltage L2 Bypass Current L2 Output Voltage L2 Output Current L2 Input Voltage L3 Input Current L3 Bypass Voltage L3 Bypass Current L3 Output Voltage L3 Output Current L3 Battery Discharge Count Battery Discharge duration Battery Amp-Hour Battery Watt-Hour
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
163
Table 61
Auto Retransfer Primed Load On Inverter Load On Bypass Load On Bypass Manual Reset Transfer Emergency Transfer Output Switch open SBS Unable Output Frequency Off Output Overload System Emergency Off Input Power Supply Fail Input Phase Rotation Error Bypass Input Voltage Fail Output Under Voltage Output Over Voltage Module Alarm Active Customer Alarm 1 Customer Alarm 2 Customer Alarm 3 Customer Alarm 4 Customer Alarm 5 Customer Alarm 6 Customer Alarm 7 Customer Alarm 8
164
Table 62
Number of Input Lines Number of Bypass Lines Number of Output Lines Nominal Power Rating Nominal Input Voltage Nominal Output Voltage Nominal Static Bypass Switch Voltage Nominal Output Frequency Nominal Power Factor Silence Alarm Load (Apparent Power) Load (Real Power) Load / Capacity Output Frequency Bypass Frequency Input Voltage L1 Bypass Voltage L1 Bypass Current L1 Output Voltage L1 Output Current L1 Input Voltage L2 Bypass Voltage L2 Bypass Current L2 Output Voltage L2 Output Current L2 Input Voltage L3 Bypass Voltage L3 Bypass Current L3 Output Voltage L3 Output Current L3
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
165
Table 63
Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 % Battery Charge Battery Temperature Battery Time Remaining Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Byp Phase Rotation Error Bypass SCR Failure Bypass Off Bypass Off Load On Bypass Bypass Overtemperature Rectifier Under Voltage Rectifier Block
166
Table 63
Liebert HiPulse, Liebert SICE 7200- Input and Holding - SMM/SSM (continued)
Controller Liebert Products Multi Module Series - SMM Liebert HiPulse Liebert SICE 7200 Available Points Data Description Input Register Holding Register 40290 40290 40290 40290 40291 40291 40291 40291 40291 40291 40291 40291 40291 40291 40291 40292 40292 40292 40292 40292 40292 40292 40292 40292 40292 40292 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 # of Reg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Scale Notes / Units Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13
Rectifier Block Rectifier Current Limit Rectifier Overtemperature Rectifier Fuse Failure Inverter Voltage Fault Inverter Disable Inverter Disable Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage Inverter Fuse Failure Output Overvoltage Output Undervoltage Output Undervoltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Overvoltage DC Undervoltage Battery Fuse Failure DC Overvoltage Transfer Count Block Overload Shutdown Overtemperature SD Emergency Stop Overload Present Overload Shutdown TO Display Error Display Error Inverter Over Capacity Bypass ECO Mode Fan Failure
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
167
Table 64
Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Bypass Frequency Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 % Battery Charge Battery Temperature Battery Time Remaining Communications Bypass Switch Open Output Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Bypass Ph Rotation Error Bypass SCR Failure Bypass Off Bypass Off Load On Bypass Bypass Overtemperature Inverter Non Sync Output Overvoltage Output Undervoltage
168
Table 64
Output Undervoltage Output Waveform Error Transfer Count Block Overload Shutdown Overtemperature Shutdown Emergency Stop Overload Present Overload Shutdown TO Display Error Display Error Invewrter Over Capacity Parallel Bus Open Battery Ground Fault Bypass Backfeed Bypass Sync Inhibited Bypass ECO Mode Fan Failure
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
169
Table 65
Data Description Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Battery Voltage Battery Current Battery Temperature Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Current A Output Current B Output Current C Output kVA A Output kVA B Output kVA C Output kW A Output kW B Output kW C Output Frequency Rated kVA Percentage Rated kW Percentage Alarm Points Communications Loss Battery Fuse Fail Battery Low Transfer DC Over Voltage Transient Input Phase Rotation Error Rectifier/Trap Fuse Fail Bypass Frequency Error Bypass Overload Shutdown Bypass Phase Rotation Error Inverter Over Voltage Transfer Inverter Fuse Fail Output Over Voltage Transfer Output Under Voltage Transfer SBS SCR Open SBS SCR Short Inverter Over Current Transfer Equipment Over Temperature
170
Table 65
Data Description Battery Ground Fault CB Trip Power Supply Fail EPO Shutdown Rectifier Fail Inverter Fail Hardware Shutdown Battery Discharge Input Current Imbalance Input Line fail Input Under Voltage Input Over Voltage Input Over Current Battery CB Open Battery Sync Error Bypass Voltage Out of Tolerance Bypass Line Fail Inverter Over Current Output OF/UF Inverter Overload Excessive Auto Retransfer Equipment Over Temperature Warning
Fan Fail SBS Unable Inverter Off By User Battery low Warning Battery Test Fail User Shutdown Load On Bypass Input Contact Alarms Generic Alarms Bypass Overload
40291 40291 40291 40291 40291 40291 40291 40291 40291 40291
1 1 1 1 1 1 1 1 1 1
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
171
3.4
172
Table 66
Low Cell Temperature Cell 1 - 320 High Cell Temperature Cell 1 - 320 Low Internal Resistance Cell 1 - 320 High Internal Resistance Cell 1 - 320 High Intercell Resistance Cell 1 - 320 Discharge Low Cell Voltage Cell 1 - 320
If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
173
Table 67
System Status 1
30385
Battery Entity Battery Name Battery 1 - 32 Battery Time Remaining Battery 1 - 32 Battery Discharge Time Battery 1 - 32 Battery Rating Battery 1 - 32 Ordinal Position of Battery Battery 1 - 32 String Entity Battery String Name String 1 - 32 String Ambient Temperature 1 String 1 - 32 String Ambient Temperature 2 String 1 - 32 String Ambient Temperature 1 String 1 - 32 String Ambient Temperature 2 String 1 - 32 String Overall Voltage String 1 - 32 String Current String 1 - 32 Float Current String 1 - 32 Ripple Current String 1 - 32 Total Active Alarms on a Battery String String 1 - 32 Discharge State String 1 - 32 Battery String Time-To-Go String 1 - 32 Amp-Hours Remaining in Battery String String 1 - 32 Battery String Discharge Time String 1 - 32 Low Ambient Temperature Global Threshold String 1 - 32 3125031921 3192231953 3195431985 3198632017 3201832049 3205032081 3208232113 3211432145 3214632177 3217832209 3221032241 3224232305 3230632337 3233832401 3240232433 21 1 1 1 1 1 1 1 1 1 1 2 1 2 1 10 10 10 10 10 10 Each 16-bit register is a single Unicode character of a null terminated string deg C deg C deg F deg F VDC A DC mA DC A AC 0 = Not In Progress 1 = In Progress min AH sec deg C 3038631057 3105831121 3112231185 3118631217 3121831249 21 2 2 1 1 -
174
Table 67
Low Ambient Temperature Global Threshold String 1 - 32 High Ambient Temperature Global Threshold String 1 - 32 High Ambient Temperature Global Threshold String 1 - 32 Battery String Overall Voltage Low Threshold String 1 - 32 Battery String Overall Voltage High Threshold String 1 - 32 Battery String Current High Threshold String 1 - 32 Battery String Float Current Low Threshold String 1 - 32 Battery String Float Current High Threshold String 1 - 32 Battery String Ripple Current High Threshold String 1 - 32 Cell Voltage Low Global Threshold String 1 - 32 Cell Voltage High Global Threshold String 1 - 32 Cell Temperature Low Global Threshold String 1 - 32 Cell Temperature Low Global Threshold String 1 - 32 Cell Temperature High Global Threshold String 1 - 32 Cell Temperature High Global Threshold String 1 - 32 Internal Resistance Low Global Threshold String 1 - 32 Internal Resistance High Global Threshold String 1 - 32 Intercell Resistance High Global Threshold String 1 - 32 Intertier Resistance High Global Threshold String 1 - 32
10
deg C
10
deg F
10
VDC
1 1 1
10 -
VDC A DC mA DC
mA DC
1 1 1 1 1 1
1000 1000 10 10 10
10
deg F
microOhm
microOhm
microOhm
microOhm
175
Table 67
Cell to Cell Temperature Deviation Threshold String 1 - 32 Cell to Cell Temperature Deviation Threshold String 1 - 32 Cell to Ambient Temperature Deviation Threshold String 1 - 32 Cell to Ambient Temperature Deviation Threshold String 1 - 32 Installation Date String 1 - 32 Cell/Monobloc Rating String 1 - 32 Discharge Low Cell Voltage Threshold String 1 - 32 Discharge Low Overall Voltage Threshold String 1 - 32 Discharge Battery String Current High Threshold String 1 - 32 Discharge Maximum Time String 1 - 32 Startup Date String 1 - 32 Battery String Commissioned Status String 1 - 32 Battery String Alarm Reset or Acknowledge 1 String 1 - 32 Ordinal Position of String String 1 - 32 Index of Parent Battery String 1 - 32 Cell Entity Cell Voltage Cell 1 - 320 Cell Temperature Cell 1 - 320 Cell Temperature Cell 1 - 320 Internal Resistance Value Cell 1 - 320 Intercell Resistance Value Cell 1 - 320 Cell Voltage Low Threshold Cell 1 - 320 Cell Voltage High Threshold Cell 1 - 320
10
deg F
10
deg C
1 2 1 1 1
10 1000 10
4349043521 -
1 1 2 1 1 1 1
1 1 1 1 1 1 1
176
Table 67
Cell Temperature Low Threshold Cell 1 - 320 Cell Temperature Low Threshold Cell 1 - 320 Cell Temperature High Threshold Cell 1 - 320 Cell Temperature High Threshold Cell 1 - 320 Internal Resistance Low Threshold Cell 1 - 320 Internal Resistance High Threshold Cell 1 - 320 Intercell Resistance High Threshold Cell 1 - 320 Ordinal Position of Cell Cell 1 - 320 Index of Parent String Cell 1 - 320 Index of Parent Battery Cell 1 - 320 Device Status and Control
Group Status 1
39026
1 = Normal Operation 2 = Startup 4 = Unknown - No System Support for System Status 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 64 = Unknown Communication Failure -
Linker Device System Date and Time 39998 49998 2 If the Scale column has a value for a Data Description, multiply the Modbus value by the value in the Scale column.
177
4.0
4.1
BACNET COMMUNICATIONS
BACnet Protocol Implementation Conformance Statement
The Liebert IntelliSlot Web IS-IPBML card provides BACnet IP to Emerson Network Power devices via the BACnet protocol. Data descriptions of the managed device are mapped to BACnet objects that are automatically created in the card when the device is discovered. The connection is a 10/100BaseT Ethernet port that supports device data access using BACnet IP and supports card configuration and administration through HTTP and Telnet. A DB-9 RS-232 port provides Service Terminal access for card configuration and administration. Following is a listing of Services and Objects supported in this BACnet implementation.
4.1.1
Segmentation Capability
Not supported.
178
4.1.2
Supported Services
Service Alarm and Event Services AcknowledgeAlarm ConfirmedCOVNotification UnconfirmedCOVNotification ConfirmedEventNotification UnconfirmedEventNotification GetAlarmSummary GetEnrollmentSummary GetEventInformation LifeSafetyOperation SubscribeCOV SubscribeCOVProperty File Access Services AtomicReadFile AtomicWriteFile Object Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple WriteProperty WritePropertyMultiple ReadRange Remote Device Management Services DeviceCommunicationControl ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ReinitializeDevice ConfirmedTextMessage UnconfirmedTextMessage TimeSynchronization UTCTimeSynchronization Who-Has I-Have Who-Is I-Am Virtual Terminal Services VT-Open VT-Close VT-Data x x x (IP-BML only) x (IP-BML only) x x x x x x x x x Originate Respond
179
4.1.3
180
4.1.4
Object Properties
The following object properties are supported. NOTE All properties are read-only unless otherwise noted
Device Object
The Device object represents the agent (the card) rather than the managed device.
Device Object Property Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_Version Location Description Protocol_Version Protocol_Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported Local_Time Local_Date UTC_Offset Daylight_Savings_Status APDU_Timeout Number_Of_APDU_Retries Device_Address_Binding Database_Revision Active_COV_Subscriptions Writable. Range: 0-8. Default 3. Comments The card must be configured with a unique Device Instance Number to avoid interference with other cards on the same BACnet network. Writable. If the Device Object Name is changed from the default, the configured name must be unique to avoid interference with other cards on the same BACnet network. Writable. Range: 1-65,535 ms. Default 3000 ms.
181
Analog Object
Analog Object Property Object_Identifier Object_Name Object_Type Analog Analog Analog Input Output Value x x x x x x x x x Comments Writable if any of these conditions apply: Object is Analog Output Object is Analog Value and associated device Data Description is writable Out_Of_Service is True Writable. Values: True/False. Default: False. See Units below this table. Support for this property on Analog Value objects is device-dependent. Support for this property on Analog Value objects is device-dependent. The value is equal to the Present_Value so that if all entries in the Priority_Array are relinquished, the Present_Value does not change. Writable. Default: 0.5.
Present_Value
x x x x x x
x x x x x x x x
x x x x x x (x) (x) x
Units
Possible values of the Units property includes the BACnet Engineering Units defined in the BACnet standard, plus these additional proprietary units values:
Value 256 257 258 259 260 261 Units Ampere-Hours MilliHertz (.001 Hertz) GigaHertz (1,000,000,000 Hertz) PSI - Absolute Total Harmonic Distortion (%) Microhms (.000001 Ohms)
182
Present_Value
x x x x x x x -
x x x x x x x x
x x x x x x x (x)
Relinquish_Default
(x)
183
4.2
184
Table 68
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Binary Data (continued)
Controller Data Description Liebert iCOM v4 Object Type Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Instance 117 118 119 130 131 132 143 154 165 176 177 178 179 180 181 182 183 194 205 206 207 218 219 220 231 242 253 254 255 256 257 258 259 260 Object Name 5306_1 5361_1 5362_1 5365_1 5068_1 5070_1 5368_1_1 5368_1_2 5368_1_3 5037_1 5044_1 5045_1 5042_1 5043_1 5041_1 5040_1 5039_1 5038_1 5054_1 5376_1 4729_1 5073_1 5072_1 5106_1 5377_1_1 5377_1_2 4270_1 4271_1 4272_1 4273_1 5415_1 5105_1 5107_1 5115_1 Access RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD Notes -
Free Cooling Free Cooling Valve Hours Exceeded Ext Free Cooling Lockout Free Cooling Temp Sensor Issue Reheat Hot Water / Hot Gas Valve Hours Exceeded Reheater Over Temperature Ext Reheat Lockout Reheat - Electric Reheater 1 Electric Reheater Hours Exceeded Reheat - Electric Reheater 2 Electric Reheater Hours Exceeded Reheat - Electric Reheater 3 Electric Reheater Hours Exceeded Humidifier Humidifier Hours Exceeded Ext Humidifier Lockout Humidifier Control Board Not Detected Humidifier Cylinder Worn Humidifier Issue Humidifier Low Water Humidifier Over Current Humidifier Under Current Dehumidifier Dehumidifier Hours Exceeded Fan Fan Hours Exceeded Main Fan Overload Fan Issue Condensers Condenser TVSS Issue Condenser VFD Issue Ext Condenser Pump High Water Condensers - Condenser 1 Condenser Issue Condensers - Condenser 2 Condenser Issue System Events Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Ext Loss of Air Blower Ext Loss of Flow Ext Standby Glycol Pump On BMS Communications Timeout
185
Table 68
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Binary Data (continued)
Controller Data Description Liebert iCOM v4 Object Type Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Instance 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 288 299 310 311 312 313 314 315 316 327 338 349 Object Name 5416_1 5118_1 5053_1 4726_1 5120_1 5119_1 4714_1 5121_1 4720_1 4980_1 4626_1 5418_1 5419_1 5114_1 4723_1 5104_1 5108_1 4703_1_1 4703_1_2 5110_1_1 5109_1_1 5112_1_1 5113_1_1 5111_1_1 5116_1_1 5117_1_1 5417_1_1 5417_1_2 5417_1_3 Access RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD Notes -
Ext Standby Unit On Clogged Air Filter Loss of Air Flow Service Required Master Unit Communication Lost RAM Battery Issue Shutdown - Loss Of Power High Power Shutdown Smoke Detected Supply Chilled Water Loss of Flow Supply Chilled Water Over Temp Unit Code Missing Unit Communication Lost Water Leakage Detector Sensor Issue Water Under Floor Ext Over Temperature External Fire Detected System Events - Chilled Water Valve 1 Chilled Water Control Valve Position System Events - Chilled Water Valve 2 Chilled Water Control Valve Position System Events - Messages Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Maintenance Due Maintenance Completed System Events - iCOM DO Board 1 Digital Output Board Not Detected System Events - iCOM DO Board 2 Digital Output Board Not Detected System Events - iCOM DO Board 3 Digital Output Board Not Detected
186
Table 69
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Analog Data
Controller Data Description Liebert iCOM v4 Object Type Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Instance 1 2 3 4 5 6 7 8 19 20 31 32 33 34 45 46 47 48 49 60 61 62 63 64 65 66 67 68 69 70 71 82 83 84 85 86 Object Name 5008_1 5325_1 5011_1 5326_1 5327_1 5328_1 5329_1 5330_1 5002_1_1 5331_1_1 4291_1_1 5333_1_1 5022_1_1 5334_1_1 4594_1_1 4597_1_1 5336_1_1 5337_1_1 5338_1_1 5028_1 5029_1 5339_1 5341_1 5032_1 5342_1 5033_1 5035_1 5343_1 5344_1 5345_1 5346_1 4595_1_1 4598_1_1 5347_1_1 5348_1_1 5350_1_1 Access RW RW RW RW RD RD RD RD RD RW RD RW RW RW RD RD RD RW RW RD RW RW RW RW RW RW RW RD RD RD RD RD RD RD RW RW Notes -
Air Air Temperature Set Point Air Temperature Proportional Band Air Temperature Dead Band Air Temperature Control Integration Time Today's High Air Temperature Today's High Air Temperature Time Today's Low Air Temperature Today's Low Air Temperature Time Air - Supply Air Supply Air Temperature Supply Air Temperature Set Point Air - Return Air Return Air Temperature Return Air Temperature Set Point Return Air Over Temp Threshold Return Air Under Temp Threshold Air - External Sensors Ext Air Sensor A Temperature Ext Air Sensor B Temperature Ext Air Sensor C Temperature Ext Air Sensor A Over Temp Threshold Ext Air Sensor A Under Temp Threshold Humidity Return Humidity Humidity Set Point Return Humidity Set Point Humidity Proportional Band Humidity Dead Band Humidity Proportional Control Integration Time High Return Humidity Threshold Low Return Humidity Threshold Today's High Humidity Today's High Humidity Time Today's Low Humidity Today's Low Humidity Time Humidity - External Sensors Ext Air Sensor A Humidity Ext Air Sensor B Humidity Ext Air Sensor C Humidity Ext Air Sensor A High Humidity Threshold Ext Air Sensor A Low Humidity Threshold
187
Table 69
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Analog Data (continued)
Controller Data Description Liebert iCOM v4 Object Type Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Instance 97 98 99 110 111 112 123 124 125 126 127 138 139 150 151 162 163 174 175 186 187 188 199 200 211 212 213 224 235 Object Name 5267_1_1 5268_1_1 5353_1_1 5267_1_2 5268_1_2 5353_1_2 5356_1 5358_1 5360_1 5304_1 5305_1 5363_1 5364_1 5366_1_1 5367_1_1 5366_1_2 5367_1_2 5366_1_3 5367_1_3 5369_1 5370_1 5445_1 5371_1 5372_1 5050_1 5374_1 5375_1 5378_1 5378_2 Access RW RW RD RW RW RD RW RD RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RD RD Notes -
Compressors - Compressor 1 Compressor Hours Compressor Hours Threshold Dig Scroll Comp Discharge Temp Compressors - Compressor 2 Compressor Hours Compressor Hours Threshold Dig Scroll Comp Discharge Temp Free Cooling Free Cooling Internal Temperature Delta Free Cooling Fluid Temperature Minimum Chilled Water Temp Set Point Free Cooling Valve Hours Free Cooling Valve Hours Threshold Reheat Hot Water / Hot Gas Valve Hours Hot Water / Hot Gas Valve Hours Threshold Reheat - Electric Reheater 1 Electric Reheater Hours Electric Reheater Hours Threshold Reheat - Electric Reheater 2 Electric Reheater Hours Electric Reheater Hours Threshold Reheat - Electric Reheater 3 Electric Reheater Hours Electric Reheater Hours Threshold Humidifier Humidifier Hours Humidifier Hours Threshold Infrared Humidifier Flush Rate Dehumidifier Dehumidifier Hours Dehumidifier Hours Threshold Fan Fan Speed Maximum Set Point Fan Hours Fan Hours Threshold Analog Inputs 1 Analog Input Reading Analog Inputs 2 Analog Input Reading
188
Table 69
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Analog Data (continued)
Controller Data Description Liebert iCOM v4 Object Type Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Instance 246 257 268 269 280 281 282 283 284 285 286 287 288 289 300 Object Name 5378_3 5378_4 5075_1 4710_1 5077_1 5078_1 5379_1 4870_1 4868_1 4869_1 5380_1 5080_1 5081_1 5079_1 4293_1 Access RD RD RW RW RD RD RD RD RD RD RD RD RD RD RW Notes -
Analog Inputs 3 Analog Input Reading Analog Inputs 4 Analog Input Reading System Info BMS Timeout Period Auto Restart Delay System Operations Fan Speed Compressor Utilization Free Cooling Valve Open Position Maintenance Ramp Calculated Next Maintenance Month Calculated Next Maintenance Year Hot Water / Hot Gas Valve Open Position Reheat Utilization Humidifier Utilization Dehumidifier Utilization Time System Date and Time
189
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data
Controller Liebert iCOM v4 Data Description Object Type Instance Object Name Access 1 = UPS 2 = AIR 3 = PMP 4 = PDU 1 = Proportional 2 = Prop+Integral 3 = Intelligent 1 = Disabled 2 = Limit 3 = Control 4 = Temp Only 1 = Relative 2 = Compensated 3 = Predictive 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 3 = No Support 1 = Disabled 2 = Contact 3 = Value 1 = Disabled 2 = Enabled 1 = Auto 2 = Manual 3 = Economy 4 = Delta 1 = Normal Operation 2 = StartUp 3 = Normal with Warning 4 = Normal with Alarm 5 = Abnormal Operation 1 = Off / 2 = On 3 = Standby 1 = Internal (Auto) 2 = External (Manual) Notes
Protocol Server Class Air Air Temperature Control Type Air - Supply Air Supply Air Temperature Sensor Control Humidity Humidity Proportional Control Type Compressors - Compressor 1 Compressor State Compressor Capacity Control State Compressors - Compressor 2 Compressor State Compressor Capacity Control State Free Cooling Free Cooling Status Free Cooling Internal Control Mode Minimum Chilled Water Temp Set Point Enable Fan Fan Control Mode System Info Multistate_Value 82 5373_1 RW Multistate_Value Multistate_Value Multistate_Value 69 70 71 5302_1 5357_1 5359_1 RD RW RW Multistate_Value Multistate_Value 57 58 5264_1_2 5265_1_2 RD RD Multistate_Value Multistate_Value 45 46 5264_1_1 5265_1_1 RD RD Multistate_Value 34 5340_1 RW Multistate_Value 23 5332_1_1 RW Multistate_Value 12 5324_1 RW Multistate_Value 1 4553_1 RD
System Status
Multistate_Value
93
4123_1
RD
Multistate_Value Multistate_Value
94 95
4706_1 4707_1
RD RD
190
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Instance Object Name Access Notes 1 = Reason Unknown 2 = Network Display 3 = Alarm 4 = Schedule 5 = Remote System 6 = External Input 7 = Local Display 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Off / 2 = On 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Multistate_Value
96
5074_1
RD
System Operations Fan State Cooling State Free Cooling State Maintenance Tracking State Hot Water / Hot Gas State Electric Reheat State Dehumidifier State Humidifier State System On/Off Control System Event Configuration Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 2 - Event Control Customer Input 2 - Event Type Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 4 - Event Control Customer Input 4 - Event Type Ext Free Cooling Lockout - Event Control Ext Free Cooling Lockout - Event Type Ext Condenser Pump High Water Event Control Ext Condenser Pump High Water Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value 126 127 128 129 130 131 132 133 134 135 136 137 4718_1 4719_1 5098_1 5099_1 5100_1 5101_1 5102_1 5103_1 5389_1 5390_1 5122_1 5123_1 RW RW RW RW RW RW RW RW RW RW RW RW Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value 107 108 109 110 111 112 113 114 115 5381_1 5382_1 5383_1 5384_1 5385_1 5386_1 5387_1 5388_1 5143_1 RD RD RD RD RD RD RD RD RW
191
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Multistate_Value Multistate_Value Instance 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 Object Name 5129_1 5130_1 5391_1 5392_1 5086_1 5087_1 5082_1 5083_1 5090_1 5091_1 5084_1 5085_1 5141_1 5142_1 5131_1 5132_1 5133_1 5134_1 4727_1 4728_1 Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RD RW RW Notes 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Ext Standby Glycol Pump On Event Control Ext Standby Glycol Pump On Event Type
Ext Standby Unit On - Event Control Multistate_Value Ext Standby Unit On - Event Type Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Loss of Flow - Event Control Ext Loss of Flow - Event Type Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type High Power Shutdown - Event Control High Power Shutdown - Event Type Humidifier Issue - Event Control Humidifier Issue - Event Type Master Unit Communication Lost Event Control Master Unit Communication Lost Event Type Service Required - Event Control Service Required - Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
192
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Instance 158 159 160 161 162 163 164 165 166 167 168 169 Object Name 4715_1 4716_1 4721_1 4722_1 4724_1 4725_1 5088_1 5089_1 5135_1 5136_1 5393_1 5394_1 Access RD RW RW RW RW RW RW RW RW RW RW RW Notes 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Smoke Detected - Event Control Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Clogged Air Filter - Event Control Clogged Air Filter - Event Type Ext Loss of Air Blower - Event Control Ext Loss of Air Blower - Event Type System Event Configuration Compressor 1 Compressor High Head Pressure Event Control Compressor High Head Pressure Event Type Compressor Low Suction Pressure Event Control Compressor Low Suction Pressure Event Type Compressor Pump Down Issue Event Control Compressor Pump Down Issue Event Type Compressor Short Cycle - Event Control
RW RW RW RW RW RW RW
1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled
193
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Instance 187 188 189 190 191 Object Name 5398_1_1 5320_1_1 5321_1_1 5399_1_1 5400_1_1 Access RW RW RW RW RW Notes 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Compressor Short Cycle - Event Type Compressor Thermal Overload Event Control Compressor Thermal Overload Event Type Dig Scroll Comp Discharge Over Temp - Event Ctrl Dig Scroll Comp Discharge Over Temp - Event Type System Event Configuration Compressor 2 Compressor High Head Pressure Event Control Compressor High Head Pressure Event Type Compressor Low Suction Pressure Event Control Compressor Low Suction Pressure Event Type Compressor Pump Down Issue Event Control Compressor Pump Down Issue Event Type Compressor Short Cycle - Event Control Compressor Short Cycle - Event Type Compressor Thermal Overload Event Control Compressor Thermal Overload Event Type Dig Scroll Comp Discharge Over Temp - Event Ctrl Dig Scroll Comp Discharge Over Temp - Event Type System Event Configuration - Air Ext Air Sensor A Event Control Return Air Sensor Event Control
Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
202 203 204 205 206 207 208 209 210 211 212 213
5316_1_2 5317_1_2 5318_1_2 5319_1_2 5395_1_2 5396_1_2 5397_1_2 5398_1_2 5320_1_2 5321_1_2 5399_1_2 5400_1_2
RW RW RW RW RW RW RW RW RW RW RW RW
1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Disabled 2 = Enabled
Multistate_Value Multistate_Value
224 225
5401_1_1 5402_1_1
RW RW
194
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Instance 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 Object Name 5403_1_1 5404_1_1 5405_1_1 5406_1_1 4602_1_1 4603_1_1 4609_1_1 4610_1_1 5137_1_1 5138_1_1 5139_1_1 5140_1_1 5024_1_1 5025_1_1 5407_1_1 5408_1_1 Access RW RD RW RD RW RD RW RD RW RD RW RD RW RD RW RD Notes 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Ext Air Sensor A High Humidity Event Control Ext Air Sensor A High Humidity Event Type Ext Air Sensor A Low Humidity Event Control Ext Air Sensor A Low Humidity Event Type Ext Air Sensor A Over Temp - Event Control Ext Air Sensor A Over Temp - Event Type Ext Air Sensor A Under Temp Event Control Ext Air Sensor A Under Temp Event Type High Return Humidity - Event Control High Return Humidity - Event Type Low Return Humidity - Event Control Low Return Humidity - Event Type Return Air Over Temp - Event Control Return Air Over Temp - Event Type Return Air Under Temp - Event Control
Return Air Under Temp - Event Type Multistate_Value System Event Configuration - Fan Fan Hours Exceeded - Event Control Fan Hours Exceeded - Event Type Fan Issue - Event Control Fan Issue - Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value
RW RD RW RW
195
Table 70
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Multistate Data (continued)
Controller Liebert iCOM v4 Data Description Object Type Multistate_Value Multistate_Value Instance 256 257 Object Name 5411_1_1 5412_1_1 Access RW RW Notes 1 = Disabled 2 = Enabled 1 = Message 2 = Warning 3 = Alarm
Main Fan Overload - Event Control Main Fan Overload - Event Type System Event Configuration Condenser 1 Condenser Issue - Event Control Condenser Issue - Event Type System Event Configuration Condenser 2 Condenser Issue - Event Control Condenser Issue - Event Type System Events System Event Acknowledge/Reset
Multistate_Value Multistate_Value
268 269
5413_1_1 5414_1_1
RW RW
Multistate_Value Multistate_Value
280 281
5413_1_2 5414_1_2
RW RW
Multistate_Value
292
4717_1
WO
196
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary
Data Description Description Time value used when system is under integral air temperature control. Type of algorithm used to control the system's output air temperature. Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Value that is divided evenly to form proportional temperature control bands above and below [Air Temperature Set Point]. Desired air temperature. Ambient air sensor is disconnected or the signal is out of range. Generic analog input reading (unitless). If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Building Management System (or external monitoring system) has not communicated with the system within the expected time frame. Time frame within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled water valve out of position. Chilled water control valve position does not match expected value. Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Clogged Air Filter] event. Air filter is dirty and needs to be (cleaned or) replaced. Compressor capacity control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor capacity has been reduced. Enable/disable the activation of the [Compressor High Head Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor High Head Pressure] event. Compressor is shut down due to high head pressure. Compressor high pressure transducer is disconnected or the signal is out of range. [Compressor Hours] has exceeded [Compressor Hours Threshold]. Threshold value used in the [Compressor Hours Exceeded] event. Operating hours for compressor since last reset of this value. Compressor low pressure transducer is disconnected or the signal is out of range. Enable/disable the activation of the [Compressor Low Suction Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Low Suction Pressure] event.
Air Temperature Control Integration Time Air Temperature Control Type Air Temperature Dead Band Air Temperature Proportional Band Air Temperature Set Point Ambient Air Sensor Issue Analog Input Reading Auto Restart Delay BMS Communications Timeout BMS Timeout Period Calculated Next Maintenance Month Calculated Next Maintenance Year Chilled Water Control Valve Position Clogged Air Filter - Event Control Clogged Air Filter - Event Type Clogged Air Filter Compressor Capacity Control State Compressor Capacity Reduced Compressor High Head Pressure Event Control Compressor High Head Pressure Event Type Compressor High Head Pressure Compressor High Pressure Transducer Issue Compressor Hours Exceeded Compressor Hours Threshold Compressor Hours Compressor Low Pressure Transducer Issue Compressor Low Suction Pressure Event Control Compressor Low Suction Pressure Event Type
197
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description Compressor is shut down due to low suction pressure. Enable/disable the activation of the [Compressor Pump Down Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Pump Down Issue] event. Unable to pump down suction-side pressure during compressor shutdown. Enable/disable the activation of the [Compressor Short Cycle] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Short Cycle] event. Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. Compressor operational state. Enable/disable the activation of the [Compressor Thermal Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Compressor Thermal Overload] event. Compressor is shut down due to thermal overload. Present compressor utilization expressed as a percentage of the maximum rated capacity. Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Condenser Issue] event. Condenser is not operating within its operational parameters. The condenser Transient Voltage Surge Suppressor device has failed. The condenser fan Variable Frequency Drive is offline. Cooling operational state. Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 1] event. Customer Input 1. Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 2] event. Customer Input 2. Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 3] event. Customer Input 3. Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Customer Input 4] event.
Compressor Low Suction Pressure Compressor Pump Down Issue Event Control Compressor Pump Down Issue Event Type Compressor Pump Down Issue Compressor Short Cycle - Event Control Compressor Short Cycle - Event Type Compressor Short Cycle Compressor State Compressor Thermal Overload Event Control Compressor Thermal Overload Event Type Compressor Thermal Overload Compressor Utilization Condenser Issue - Event Control Condenser Issue - Event Type Condenser Issue Condenser TVSS Issue Condenser VFD Issue Cooling State Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 1 Customer Input 2 - Event Control Customer Input 2 - Event Type Customer Input 2 Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 3 Customer Input 4 - Event Control Customer Input 4 - Event Type
198
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description Customer Input 4. Operating hours for the dehumidifier have exceeded the threshold. Threshold value used in the [Dehumidifier Hours Exceeded] event. Operating hours for dehumidifier since last reset of this value. Dehumidifier operational state. Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event. The event type for the [Dig Scroll Comp Discharge Over Temp] event. Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. Digital scroll compressor discharge temperature. Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. Digital output board is required to be connected, but no signal is detected. Electric reheater operational state. [Electric Reheater Hours] has exceeded [Electric Reheater Hours Threshold]. Threshold value used in the [Electric Reheater Hours Exceeded] event. Operating hours for electric reheater since last reset of this value. Enable/disable the activation of events related to measurements by the external air sensor A. Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A High Humidity] event. Threshold value used in the [External Air Sensor A High Humidity] event. [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. Relative humidity as measured by external air sensor A. The external air sensor A is disconnected or the signal is out of range. Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A Low Humidity] event. Threshold value used in the [External Air Sensor A Low Humidity] event. [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. Enable/disable the activation of the [External Air Sensor A Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [External Air Sensor A Over Temperature] event.
Customer Input 4 Dehumidifier Hours Exceeded Dehumidifier Hours Threshold Dehumidifier Hours Dehumidifier State Dehumidifier Utilization Dig Scroll Comp Discharge Over Temp - Event Ctrl Dig Scroll Comp Discharge Over Temp - Event Type Dig Scroll Comp Discharge Temp Sensor Issue Dig Scroll Comp Discharge Temp Dig Scroll Comp Over Temp Digital Output Board Not Detected Electric Reheat State Electric Reheater Hours Exceeded Electric Reheater Hours Threshold Electric Reheater Hours Ext Air Sensor A Event Control Ext Air Sensor A High Humidity Event Control Ext Air Sensor A High Humidity Event Type Ext Air Sensor A High Humidity Threshold Ext Air Sensor A High Humidity Ext Air Sensor A Humidity Ext Air Sensor A Issue Ext Air Sensor A Low Humidity Event Control Ext Air Sensor A Low Humidity Event Type Ext Air Sensor A Low Humidity Threshold Ext Air Sensor A Low Humidity Ext Air Sensor A Over Temp - Event Control Ext Air Sensor A Over Temp - Event Type
199
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description Threshold value used in the [External Air Sensor A Over Temperature] event. [Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp Threshold]. Air temperature as measured by external air sensor A. Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Air Sensor A Under Temperature] event. Threshold value used in the [External Air Sensor A Under Temperature] event. [Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp Threshold]. Relative humidity as measured by external air sensor B. Air temperature as measured by external air sensor B. Relative humidity as measured by external air sensor C. Air temperature as measured by external air sensor C. Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Compressor Lockout] event. The compressor is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Condenser Pump High Water] event. High water is detected in the condenser, as indicated by an external input signal. Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Free Cooling Lockout] event. Free cooling is disabled by an external input signal. Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Humidifier Lockout] event. The humidifier is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Loss of Air Blower] event. Loss of air blower is detected, as indicated by an external input signal. Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list.
Ext Air Sensor A Over Temp Threshold Ext Air Sensor A Over Temperature Ext Air Sensor A Temperature Ext Air Sensor A Under Temp Event Control Ext Air Sensor A Under Temp Event Type Ext Air Sensor A Under Temp Threshold Ext Air Sensor A Under Temperature Ext Air Sensor B Humidity Ext Air Sensor B Temperature Ext Air Sensor C Humidity Ext Air Sensor C Temperature Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Ext Compressor Lockout Ext Condenser Pump High Water Event Control Ext Condenser Pump High Water Event Type Ext Condenser Pump High Water Ext Free Cooling Lockout - Event Control Ext Free Cooling Lockout - Event Type Ext Free Cooling Lockout Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Humidifier Lockout Ext Loss of Air Blower - Event Control Ext Loss of Air Blower - Event Type Ext Loss of Air Blower Ext Loss of Flow - Event Control
200
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description The event type for the [Ext Loss of Flow] event. Loss of flow is detected, as indicated by an external input signal. Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Over Temperature] event. A temperature has exceeded its threshold, as indicated by an external input signal. Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Reheat Lockout] event. The reheater is shut down and disabled by an external input signal. Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Standby Glycol Pump On] event. The standby glycol pump is on, as indicated by an external input signal. Enable/disable the activation of the [Ext Standby Unit On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Ext Standby Unit On] event. Standby unit is on, as indicated by an external input signal. Fire detected, as indicated by an external input signal. Fan control mode. Enable/disable the activation of the [Fan Hours Exceeded] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Fan Hours Exceeded] event. Operating hours for the unit blower fan have exceeded the threshold. Threshold value used in the [Fan Hours Exceeded] event. Operating hours for fan since last reset of this value. Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Fan Issue] event. One or more fans are not operating within their operational parameters. Maximum fan speed. Fan speed expressed as a percentage of the maximum rated speed. Fan operational state. Free cooling fluid temperature. Free cooling internal control mode. Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling. Free cooling operational state. Free cooling status. The free cooling fluid temperature sensor is disconnected or the signal is out of range.
Ext Loss of Flow - Event Type Ext Loss of Flow Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Over Temperature Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type Ext Reheat Lockout Ext Standby Glycol Pump On Event Control Ext Standby Glycol Pump On Event Type Ext Standby Glycol Pump On Ext Standby Unit On - Event Control Ext Standby Unit On - Event Type Ext Standby Unit On External Fire Detected Fan Control Mode Fan Hours Exceeded - Event Control Fan Hours Exceeded - Event Type Fan Hours Exceeded Fan Hours Threshold Fan Hours Fan Issue - Event Control Fan Issue - Event Type Fan Issue Fan Speed Maximum Set Point Fan Speed Fan State Free Cooling Fluid Temperature Free Cooling Internal Control Mode Free Cooling Internal Temperature Delta Free Cooling State Free Cooling Status Free Cooling Temp Sensor Issue
201
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. Threshold value used in the [Free Cooling Valve Hours Exceeded] event. Operating hours for free cooling valve since last reset of this value. Free cooling valve open position. Enable/disable the activation of the [High Power Shutdown] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [High Power Shutdown] event. Supply to high power components has been shutdown. Enable/disable the activation of the [High Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [High Return Humidity] event. Threshold value used in the [High Return Humidity] event. [Return Humidity] has exceeded [High Return Humidity Threshold]. Hot water / hot gas operational state. [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded] event. Operating hours for hot water / hot gas valve since last reset of this value. Hot water / hot gas valve open position. Humidifier control board is required to be connected, but no signal is detected. Humidifier cylinder is not operating properly and needs to be replaced. Operating hours for the humidifier have exceeded the threshold. Threshold value used in the [Humidifier Hours Exceeded] event. Operating hours for humidifier since last reset of this value. Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Humidifier Issue] event. Humidifier issue detected, causing it to be locked out. The water level in the humidifier has dropped below its threshold. The electrical current to the humidifier has exceeded its upper threshold. Humidifier operational state. The electrical current to the humidifier has dropped below its lower threshold. Present humidifier utilization expressed as a percentage of the maximum rated capacity. Value that is divided evenly to form a range above and below [Humidity Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. Value that is divided evenly to form proportional humidity control bands above and below [Humidity Set Point]. Time value used to add an integral term to proportional humidity control. If set to 0, time will not be a factor in the proportional control algorithm.
Free Cooling Valve Hours Exceeded Free Cooling Valve Hours Threshold Free Cooling Valve Hours Free Cooling Valve Open Position High Power Shutdown - Event Control High Power Shutdown - Event Type High Power Shutdown High Return Humidity - Event Control High Return Humidity - Event Type High Return Humidity Threshold High Return Humidity Hot Water / Hot Gas State Hot Water / Hot Gas Valve Hours Exceeded Hot Water / Hot Gas Valve Hours Threshold Hot Water / Hot Gas Valve Hours Hot Water / Hot Gas Valve Open Position Humidifier Control Board Not Detected Humidifier Cylinder Worn Humidifier Hours Exceeded Humidifier Hours Threshold Humidifier Hours Humidifier Issue - Event Control Humidifier Issue - Event Type Humidifier Issue Humidifier Low Water Humidifier Over Current Humidifier State Humidifier Under Current Humidifier Utilization Humidity Dead Band Humidity Proportional Band Humidity Proportional Control Integration Time
202
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description Type of algorithm to use for proportional control of output humidity. Desired relative humidity. A multiple of an internal time constant that determines the flush duration of the infrared humidifier water pan. No air flow through the unit due to failure of all fans. Enable/disable the activation of the [Low Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Low Return Humidity] event. Threshold value used in the [Low Return Humidity] event. [Return Humidity] has dropped below [Low Return Humidity Threshold]. Enable/disable the activation of the [Main Fan Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Main Fan Overload] event. Main fan is shut down due to thermal overload. Maintenance has been completed on the unit. The calculated maintenance date has been reached. The ratio of operations performed to the calculated operations available between maintenance intervals. Maintenance tracking operational state. Enable/disable the activation of the [Master Unit Communication Lost] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Master Unit Communication Lost] event. Communication with master unit has been lost. Enable/disable the activation of [Minimum Chilled Water Temp Set Point]. Minimum desired chilled water temperature. RAM or RAM backup battery is not operating correctly. Present reheating utilization expressed as a percentage of the maximum rated capacity. The temperature of the reheater has exceeded its threshold. Enable/disable the activation of the [Return Air Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Return Air Over Temperature] event. Threshold value used in the [Return Air Over Temperature] event. [Return Air Temperature] has exceeded [Return Air Over Temp Threshold]. Enable/disable the activation of events related to measurements by the return air sensor. The air sensor at the inlet of the unit is disconnected or the signal is out of range. Desired air temperature at the inlet of the unit. The temperature of the inlet air.
Humidity Proportional Control Type Humidity Set Point Infrared Humidifier Flush Rate Loss of Air Flow Low Return Humidity - Event Control Low Return Humidity - Event Type Low Return Humidity Threshold Low Return Humidity Main Fan Overload - Event Control Main Fan Overload - Event Type Main Fan Overload Maintenance Completed Maintenance Due Maintenance Ramp Maintenance Tracking State Master Unit Communication Lost Event Control Master Unit Communication Lost Event Type Master Unit Communication Lost Minimum Chilled Water Temp Set Point Enable Minimum Chilled Water Temp Set Point RAM Battery Issue Reheat Utilization Reheater Over Temperature Return Air Over Temp - Event Control Return Air Over Temp - Event Type Return Air Over Temp Threshold Return Air Over Temperature Return Air Sensor Event Control Return Air Sensor Issue Return Air Temperature Set Point Return Air Temperature
203
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description Enable/disable the activation of the [Return Air Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Return Air Under Temperature] event. Threshold value used in the [Return Air Under Temperature] event. [Return Air Temperature] has dropped below [Return Air Under Temp Threshold]. Desired relative humidity at the inlet of the unit. Relative humidity measured at the inlet of the unit. The general classification for this system. Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Service Required] event. Unit requires servicing. Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Shutdown - Loss Of Power] event. System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Smoke Detected] event. Smoke detected. [Supply Air Temperature] has exceeded [Supply Air Over Temp Threshold]. The air sensor at the outlet of the unit is disconnected or the signal is out of range. Control mode to be used with the supply air temperature sensor. Desired supply air temperature. Air temperature measured at the outlet of the unit. [Supply Air Temperature] has dropped below [Supply Air Under Temp Threshold]. Supply chilled water flow is too low. [Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over Temp Threshold]. System control mode. The system date and time. Reset and/or acknowledge all events. Turn system functionality on or off. The reason the system is in the current operating state. Current operating state of the system. The operating status for the system. [Today's High Air Temperature] was measured at this time. The highest external air temperature measured since midnight. [Today's High Humidity] was measured at this time.
Return Air Under Temp - Event Control Return Air Under Temp - Event Type Return Air Under Temp Threshold Return Air Under Temperature Return Humidity Set Point Return Humidity Server Class Service Required - Event Control Service Required - Event Type Service Required Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Shutdown - Loss Of Power Smoke Detected - Event Control Smoke Detected - Event Type Smoke Detected Supply Air Over Temperature Supply Air Sensor Issue Supply Air Temperature Sensor Control Supply Air Temperature Set Point Supply Air Temperature Supply Air Under Temperature Supply Chilled Water Loss of Flow Supply Chilled Water Over Temp System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status Today's High Air Temperature Time Today's High Air Temperature Today's High Humidity Time
204
Table 71
Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert HPM, Liebert PeX - Glossary (continued)
Data Description Description The highest external humidity measured since midnight. [Today's Low Air Temperature] was measured at this time. The lowest external air temperature measured since midnight. [Today's Low Humidity] was measured at this time. The lowest external humidity measured since midnight. Unit code has not been entered and saved. Master has lost communication with one or more networked units. Unit was turned off. Unit was turned on. An event has occurred requiring some system components to be shutdown and disabled. An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit was placed in standby mode. The water leakage detector sensor is disconnected or the signal is out of range. Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. The event type for the [Water Under Floor] event. Water under the floor is detected.
Today's High Humidity Today's Low Air Temperature Time Today's Low Air Temperature Today's Low Humidity Time Today's Low Humidity Unit Code Missing Unit Communication Lost Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Water Leakage Detector Sensor Issue Water Under Floor - Event Control Water Under Floor - Event Type Water Under Floor
205
Table 72
Air Temperature Supply Air Over Temperature Supply Air Under Temperature Return Air Over Temperature Supply Air Sensor Issue Return Air Sensor Issue Humidity High Return Humidity Low Return Humidity Humidifier Hours Exceeded Dehumidifier Hours Exceeded Humidifier Under Current Humidifier Over Current Humidifier Low Water Humidifier Cylinder Worn Humidifier Issue Ext Humidifier Lockout Humidifier Control Board Not Detected Return Humidity Out Of Proportional Band Fans Loss of Air Flow Fan Hours Exceeded Top Fan Issue Bottom Fan Issue Remote Sensors 1 Remote Sensor Issue Remote Sensors 2 Remote Sensor Issue Remote Sensors 3 Remote Sensor Issue Remote Sensors 4 Remote Sensor Issue Remote Sensors 5 Remote Sensor Issue Remote Sensors 6 Remote Sensor Issue Remote Sensors 7 Remote Sensor Issue Remote Sensors 8 Remote Sensor Issue Remote Sensors 9 Remote Sensor Issue
206
Table 72
Remote Sensors 10 Remote Sensor Issue Compressor Compressor 1 High Head Pressure Compressor 1 Low Suction Pressure Compressor 1 Hours Exceeded Dig Scroll Comp 1 Temp Sensor Issue Dig Scroll Comp 1 Over Temp Compressor 1 Low Pressure Transducer Issue Compressor 1 High Pressure Transducer Issue Ext Compressor Lockout Compressor 1 Short Cycle Compressor 1 Pump Down Issue Reheater Reheater Over Temperature Electric Reheater Hours Exceeded Ext Reheat Lockout Condenser Condenser 1 Issue Condenser VFD Issue Condenser TVSS Issue Chilled Water Supply Chilled Water Over Temp Chilled Water Control Valve Position Supply Chilled Water Loss of Flow System Events Customer Input 1 Customer Input 2 Customer Input 3 Customer Input 4 Smoke Detected Water Under Floor Service Required Shutdown - Loss Of Power Ext Over Temperature Ext Loss of Flow Ext Condenser Pump High Water Ext Standby Glycol Pump On External Fire Detected Unit On Unit Off Unit Standby
207
Table 72
Unit Partial Shutdown Unit Shutdown Water Leakage Detector Sensor Issue BMS Communications Timeout Maintenance Due Maintenance Completed Clogged Air Filter RAM Battery Issue Master Unit Communication Lost High Power Shutdown Supply Fluid Temp Sensor Issue
208
Table 73
Air Temperature Supply Air Temperature Return Air Temperature Return Dew Point Remote Sensor Minimum Temperature Remote Sensor Maximum Temperature Remote Sensor Average Temperature Air Temperature Set Point Cooling Proportional Band Heating Proportional Band Air Temperature Dead Band Supply Air Over Temp Threshold Supply Air Under Temp Threshold Return Air Over Temp Threshold Humidity Supply Humidity Return Humidity Humidity Set Point Humidification Proportional Band Dehumidification Proportional Band Humidity Dead Band High Return Humidity Threshold Low Return Humidity Threshold Fans Fan Speed Proportional Band Fan Speed Manual Set Point Fan Speed Maximum Set Point Fan Speed Minimum Set Point Remote Sensors 1 Remote Sensor Temperature Remote Sensors 2 Remote Sensor Temperature Remote Sensors 3 Remote Sensor Temperature Remote Sensors 4 Remote Sensor Temperature Remote Sensors 5 Remote Sensor Temperature Remote Sensors 6 Remote Sensor Temperature Remote Sensors 7 Remote Sensor Temperature
209
Table 73
Remote Sensors 8 Remote Sensor Temperature Remote Sensors 9 Remote Sensor Temperature Remote Sensors 10 Remote Sensor Temperature Chilled Water Supply Chilled Water Temperature Supply Chilled Water Over Temp Threshold System Info BMS Timeout Period Auto Restart Delay System Operations Operating Efficiency Fan Speed Compressor Utilization Dehumidifier Utilization Reheat Utilization Humidifier Utilization Calculated Next Maintenance Month Calculated Next Maintenance Year Maintenance Ramp Time System Date and Time
210
Table 74
Protocol Server Class Air Temperature Air Temperature Control Sensor Multistate_Value 12 13 5012_1 5013_1 RW RW Multistate_Value 1 4553_1 RD
Remote Sensor Temperature Calculation Multistate_Value Fans Fan Control Mode Fan Control Sensor Remote Sensors 1 Remote Sensor Function Remote Sensors 2 Remote Sensor Function Remote Sensors 3 Remote Sensor Function Remote Sensors 4 Remote Sensor Function Remote Sensors 5 Remote Sensor Function Remote Sensors 6 Remote Sensor Function Remote Sensors 7 Remote Sensor Function Remote Sensors 8 Remote Sensor Function Remote Sensors 9 Remote Sensor Function Remote Sensors 10 Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
24 25
5047_1 5052_1
RW RW
36
5058_1
RW
47
5058_2
RW
58
5058_3
RW
69
5058_4
RW
80
5058_5
RW
91
5058_6
RW
102
5058_7
RW
113
5058_8
RW
124
5058_9
RW
211
Table 74
System Status
Multistate_Value
146
4123_1
RD
Multistate_Value Multistate_Value
147 148
4706_1 4707_1
RD RD
Multistate_Value
149
5074_1
RD
System Operations System On/Off Control Event Configuration System Event Acknowledge/Reset Smoke Detected - Event Control Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 2 - Event Control Customer Input 2 - Event Type Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 4 - Event Control
Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
160 171 172 173 174 175 176 177 178 179 180 181 182
5143_1 4717_1 4721_1 4722_1 4724_1 4725_1 4718_1 4719_1 5098_1 5099_1 5100_1 5101_1 5102_1
RW WO RW RW RW RW RW RW RW RW RW RW RW
212
Table 74
Customer Input 4 - Event Type Service Required - Event Control Service Required - Event Type Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Ext Loss of Flow - Event Control Ext Loss of Flow - Event Type Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Ext Over Temperature - Event Control Ext Over Temperature - Event Type Condenser VFD Issue - Event Control Condenser VFD Issue - Event Type Condenser TVSS Issue - Event Control Condenser TVSS Issue - Event Type Condenser 1 Issue - Event Control Condenser 1 Issue - Event Type
213
Table 75
Air Temperature Control Sensor Air Temperature Dead Band Air Temperature Set Point Auto Restart Delay BMS Communications Timeout BMS Timeout Period Bottom Fan Issue Calculated Next Maintenance Month Calculated Next Maintenance Year Chilled Water Control Valve Position Clogged Air Filter Compressor 1 High Head Pressure Compressor 1 High Pressure Transducer Issue Compressor 1 Hours Exceeded Compressor 1 Low Pressure Transducer Issue Compressor 1 Low Suction Pressure Compressor 1 Pump Down Issue Compressor 1 Short Cycle Compressor Utilization Condenser 1 Issue - Event Control Condenser 1 Issue - Event Type Condenser 1 Issue Condenser TVSS Issue - Event Control Condenser TVSS Issue - Event Type Condenser TVSS Issue Condenser VFD Issue - Event Control Condenser VFD Issue - Event Type Condenser VFD Issue
214
Table 75
Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 1 Customer Input 2 - Event Control Customer Input 2 - Event Type Customer Input 2 Customer Input 3 - Event Control Customer Input 3 - Event Type Customer Input 3 Customer Input 4 - Event Control Customer Input 4 - Event Type Customer Input 4 Dehumidification Proportional Band Dehumidifier Hours Exceeded Dehumidifier Utilization Dig Scroll Comp 1 Over Temp Dig Scroll Comp 1 Temp Sensor Issue Electric Reheater Hours Exceeded Ext Compressor Lockout - Event Control Ext Compressor Lockout - Event Type Ext Compressor Lockout Ext Condenser Pump High Water Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Ext Humidifier Lockout Ext Loss of Flow - Event Control Ext Loss of Flow - Event Type Ext Loss of Flow
215
Table 75
Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Over Temperature Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type Ext Reheat Lockout Ext Standby Glycol Pump On External Fire Detected Fan Control Mode Fan Control Sensor Fan Hours Exceeded Fan Speed Manual Set Point Fan Speed Maximum Set Point Fan Speed Minimum Set Point Fan Speed Proportional Band Fan Speed Heating Proportional Band High Power Shutdown High Return Humidity Threshold High Return Humidity Humidification Proportional Band Humidifier Control Board Not Detected Humidifier Cylinder Worn Humidifier Hours Exceeded Humidifier Issue Humidifier Low Water Humidifier Over Current Humidifier Under Current Humidifier Utilization Humidity Dead Band Humidity Set Point Loss of Air Flow Low Return Humidity Threshold
216
Table 75
Low Return Humidity Maintenance Completed Maintenance Due Maintenance Ramp Master Unit Communication Lost Operating Efficiency RAM Battery Issue Reheat Utilization Reheater Over Temperature Remote Sensor Average Temperature Remote Sensor Function Remote Sensor Issue Remote Sensor Maximum Temperature Remote Sensor Minimum Temperature Remote Sensor Temperature Calculation Remote Sensor Temperature Return Air Over Temp Threshold Return Air Over Temperature Return Air Sensor Issue Return Air Temperature Return Dew Point Return Humidity Out Of Proportional Band Return Humidity Server Class Service Required - Event Control Service Required - Event Type Service Required Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Shutdown - Loss Of Power Smoke Detected - Event Control
217
Table 75
Smoke Detected - Event Type Smoke Detected Supply Air Over Temp Threshold Supply Air Over Temperature Supply Air Sensor Issue Supply Air Temperature Supply Air Under Temp Threshold Supply Air Under Temperature Supply Chilled Water Loss of Flow Supply Chilled Water Over Temp Threshold Supply Chilled Water Over Temp Supply Chilled Water Temperature Supply Fluid Temp Sensor Issue Supply Humidity System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status Top Fan Issue Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Water Leakage Detector Sensor Issue Water Under Floor - Event Control Water Under Floor - Event Type Water Under Floor
218
Table 76
Compressors Compressor Not Stopping Compressors - Compressor 1 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Thermal Overload Compressor Low Oil Pressure Compressor Loss of Differential Pressure Compressor Capacity Reduced Compressors - Compressor 2 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Thermal Overload Compressor Low Oil Pressure Compressor Loss of Differential Pressure Compressor Capacity Reduced Condensers 1 Condenser Fan Issue Low Condenser Refrigerant Pressure Condenser Max Fan Speed Override Condensers 2 Condenser Fan Issue Low Condenser Refrigerant Pressure Condenser Max Fan Speed Override Fluid Low Fluid Pressure Return Fluid Temp Sensor Issue Fluid - Supply (Outlet) Fluid Supply Fluid Over Temp Supply Fluid Under Temp Supply Fluid Temp Sensor Issue Pumps All Pumps Loss of Flow Pump 1 Loss of Flow Pump 2 Loss of Flow Pumps - Pump 1 Pump Hours Exceeded Pumps - Pump 2 Pump Hours Exceeded
219
Table 76
Free Cooling Free Cooling Valve Hours Exceeded Ambient Air Temperature Sensor Issue Evaporators Evaporator Inlet Temp Sensor Issue Evaporator Return Fluid Over Temp Evaporator Return Fluid Under Temp Evaporators - Evaporator 1 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required Supply Refrigerant Temp Sensor Issue Evaporators - Evaporator 2 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required Supply Refrigerant Temp Sensor Issue System Events Customer Input 1 Customer Input 2 Unit On Unit Off Master Unit Communication Lost Subgroup Event Occurred During Communication Loss Humidifier Control Board Not Detected RAM Battery Issue Unit Code Missing Unspecified General Event
220
Table 77
Compressors Compressor Shut Down - Ambient Air Low Temp Limit Compressors - Compressor 1 Compressor Head Pressure Compressor Hours Compressor Hours Threshold Compressors - Compressor 2 Compressor Head Pressure Compressor Hours Compressor Hours Threshold Condensers 1 Condenser Fan Speed Condensers 2 Condenser Fan Speed Fluid Fluid Pressure Fluid Cooling Proportional Band Fluid - Supply (Outlet) Fluid Supply Fluid Temp Set Point 1 Supply Fluid Temp Set Point 2 Supply Fluid Over Temp Warning Threshold Supply Fluid Over Temp Alarm Threshold Supply Fluid Under Temp Warning Threshold Supply Fluid Under Temp Alarm Threshold Pumps - Pump 1 Pump Hours Pump Hours Threshold Pumps - Pump 2 Pump Hours Pump Hours Threshold Free Cooling Free Cooling External Temperature Delta Free Cooling Valve Open Position Free Cooling Valve Hours Free Cooling Valve Hours Threshold Evaporators Evaporator Return Fluid Temperature Evaporator Return Fluid Over Temp Alarm Threshold Evaporator Return Fluid Over Temp Warning Threshold Evaporator Return Fluid Under Temp Warning Threshold Evaporator Return Fluid Under Temp Alarm Threshold
221
Table 77
Brine Supply Brine Temp Set Point Standby Units Standby Units System Operations Return Fluid Temperature Supply Fluid Temperature Actual Supply Fluid Temp Set Point Condenser Inlet Water Temperature Condenser Outlet Water Temperature Supply Heated Water Temp Set Point Free Cooling Utilization Reheat Utilization Compressor Utilization Ambient Air Temperature Compressor Economizer Utilization Condenser Adiabatic Cooling Utilization Time System Date and Time
222
Table 78
Protocol Server Class Compressors - Compressor 1 Compressor State Compressor Capacity Control State Compressors - Compressor 2 Compressor State Compressor Capacity Control State Free Cooling Free Cooling Status System Events System Event Acknowledge/Reset System Info Multistate_Value 47 4717_1 WO Multistate_Value 36 5302_1 RD Multistate_Value Multistate_Value 24 25 5264_1_2 5265_1_2 RD RD Multistate_Value Multistate_Value 12 13 5264_1_1 5265_1_1 RD RD Multistate_Value 1 4553_1 RD
System Status
Multistate_Value
58
4123_1
RD
Multistate_Value Multistate_Value
59 60
4706_1 4707_1
RD RD
Multistate_Value
61
5074_1
RD
62 73 74
RW RD RD
223
Table 79
Actual Supply Fluid Temp Set Point All Pumps Loss of Flow Ambient Air Temperature Sensor Issue Ambient Air Temperature Compressor Capacity Control State Compressor Capacity Reduced Compressor Economizer Utilization Compressor Head Pressure Compressor High Head Pressure Compressor Hours Exceeded Compressor Hours Threshold Compressor Hours Compressor Loss of Differential Pressure Compressor Low Oil Pressure Compressor Low Suction Pressure Compressor Not Stopping Compressor Shut Down - Ambient Air Low Temp Limit Compressor State Compressor Thermal Overload Compressor Utilization Condenser Adiabatic Cooling Utilization Condenser Fan Issue Condenser Fan Speed Condenser Inlet Water Temperature Condenser Max Fan Speed Override Condenser Outlet Water Temperature Customer Input 1 Customer Input 2 Evaporator Fluid Freeze - Auto Reset Evaporator Fluid Freeze - Manual Reset Required Evaporator Inlet Temp Sensor Issue
224
Table 79
Evaporator Return Fluid Over Temp Alarm Threshold Evaporator Return Fluid Over Temp Warning Threshold Evaporator Return Fluid Over Temp Evaporator Return Fluid Temperature Evaporator Return Fluid Under Temp Alarm Threshold Evaporator Return Fluid Under Temp Warning Threshold Evaporator Return Fluid Under Temp Fluid Cooling Proportional Band Fluid Pressure Free Cooling External Temperature Delta Free Cooling Status Free Cooling Utilization Free Cooling Valve Hours Exceeded Free Cooling Valve Hours Threshold Free Cooling Valve Hours Free Cooling Valve Open Position Humidifier Control Board Not Detected Low Condenser Refrigerant Pressure Low Fluid Pressure Master Unit Communication Lost Pump 1 Loss of Flow Pump 1 State Pump 2 Loss of Flow Pump 2 State Pump Hours Exceeded Pump Hours Threshold Pump Hours RAM Battery Issue Reheat Utilization Return Fluid Temp Sensor Issue Return Fluid Temperature Server Class
225
Table 79
Standby Units Subgroup Event Occurred During Communication Loss Supply Brine Temp Set Point Supply Fluid Over Temp Alarm Threshold Supply Fluid Over Temp Warning Threshold Supply Fluid Over Temp Supply Fluid Temp Sensor Issue Supply Fluid Temp Set Point 1 Supply Fluid Temp Set Point 2 Supply Fluid Temperature Supply Fluid Under Temp Alarm Threshold Supply Fluid Under Temp Warning Threshold Supply Fluid Under Temp Supply Heated Water Temp Set Point Supply Refrigerant Temp Sensor Issue System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status Unit Code Missing Unit Off Unit On Unspecified General Event
226
Table 80
External Air Ext Air Sensor A Over Temperature Ext Air Sensor B Over Temperature Ext Air Sensor A Under Temperature Ext Air Sensor B Under Temperature Ext Dew Point Over Temperature Ext Air Sensor A Issue Ext Air Sensor B Issue Chilled Water Supply Chilled Water Over Temp Supply Chilled Water Temp Sensor Issue Chilled Water Control Valve Position Refrigerant Supply Refrigerant Over Temp Supply Refrigerant Under Temp Supply Refrigerant Temp Sensor Issue Fluid Supply Fluid Over Temp Supply Fluid Under Temp Supply Fluid Temp Sensor Issue Pumps Pump 1 Loss of Flow Pump 2 Loss of Flow Pump Short Cycle Pumps - Pump Hours 1 Pump Hours Exceeded Pumps - Pump Hours 2 Pump Hours Exceeded Compressors Compressor 1A High Head Pressure Compressor 1B High Head Pressure Compressor 2A High Head Pressure Compressor 2B High Head Pressure Compressor 1A Short Cycle Compressor 1B Short Cycle Compressor 2A Short Cycle Compressor 2B Short Cycle Circuit 1 Low Suction Pressure Circuit 2 Low Suction Pressure
227
Table 80
XD System 1 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range XD System 2 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range XD System 20 Ext System Condensation Detected Ext Fan Issue Sensor Issue Ext Remote Shutdown Hot Aisle Temp Out of Range Cold Aisle Temp Out of Range System Events Customer Input 1 System Condensation Detected Shutdown - Loss Of Power Smoke Detected Water Under Floor Service Required Fan Issue Unit Communication Lost RAM Battery Issue Master Unit Communication Lost Remote Shutdown Unit Code Missing System Events - Messages Unit On Unit Off Unit Standby Unit Partial Shutdown Unit Shutdown Maintenance Due Maintenance Completed
228
Table 81
External Air Dew Point Temperature Minimum Room Temperature Set Point Ext Air Sensor A Temperature Ext Air Sensor A Humidity Ext Air Sensor A Dew Point Temp Ext Air Sensor B Temperature Ext Air Sensor B Humidity Ext Air Sensor B Dew Point Temp Ext Air Over Temp Threshold Ext Air Under Temp Threshold Ext Dew Point Over Temp Threshold Chilled Water Supply Chilled Water Temperature Supply Chilled Water Over Temp Threshold Refrigerant Supply Refrigerant Temperature Supply Refrig Over Temp Threshold Fluid Supply Fluid Temperature Supply Fluid Over Temp Threshold Pumps - Pump Hours 1 Pump Hours Pump Hours Threshold Pumps - Pump Hours 2 Pump Hours Pump Hours Threshold Hot Gas Hot Gas Valve 1 Open Position Hot Gas Valve 2 Open Position XD System 1 Cooling Capacity Cooling Capacity Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold XD System 1 Temperature Sensor 1 Remote Sensor Temperature XD System 1 Temperature Sensor 2 Remote Sensor Temperature
229
Table 81
XD System 1 Temperature Sensor 4 Remote Sensor Temperature XD System 2 Cooling Capacity Cooling Capacity Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold XD System 2 Temperature Sensor 1 Remote Sensor Temperature XD System 2 Temperature Sensor 2 Remote Sensor Temperature XD System 2 Temperature Sensor 3 Remote Sensor Temperature XD System 2 Temperature Sensor 4 Remote Sensor Temperature XD System 20 Cooling Capacity Cooling Capacity Hot Aisle Over Temp Threshold Hot Aisle Under Temp Threshold Cold Aisle Over Temp Threshold Cold Aisle Under Temp Threshold XD System 20 Temperature Sensor 1 Remote Sensor Temperature XD System 20 Temperature Sensor 2 Remote Sensor Temperature XD System 20 Temperature Sensor 3 Remote Sensor Temperature XD System 20 Temperature Sensor 4 Remote Sensor Temperature System Information Auto Restart Delay Maintenance Ramp Calculated Next Maintenance Month Calculated Next Maintenance Year Time System Date and Time
230
Table 82
External Air Ext Air Sensor A Over Temp - Event Control Multistate_Value 1 2 3 4 5 6 7 8 9 10 11 12 13 14 4602_1 4603_1 4605_1 4606_1 4609_1 4610_1 4612_1 4613_1 4616_1 4617_1 4619_1 4620_1 4622_1 4623_1 RW RW RW RW RW RW RW RW RW RW RD RW RD RW
Ext Air Sensor A Over Temp - Event Type Multistate_Value Ext Air Sensor B Over Temp - Event Control Multistate_Value
Ext Air Sensor B Over Temp - Event Type Multistate_Value Ext Air Sensor A Under Temp - Event Control Ext Air Sensor A Under Temp - Event Type Ext Air Sensor B Under Temp - Event Control Ext Air Sensor B Under Temp - Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value
Ext Dew Point Over Temp - Event Control Multistate_Value Ext Dew Point Over Temp - Event Type Ext Air Sensor A Issue - Event Control Ext Air Sensor A Issue - Event Type Ext Air Sensor B Issue - Event Control Ext Air Sensor B Issue - Event Type Chilled Water Supply CW Over Temp - Event Control Supply CW Over Temp - Event Type Supply CW Temp Sensor Issue - Event Control Supply CW Temp Sensor Issue - Event Type Chilled Water Cntrl Valve Pos - Event Control Chilled Water Cntrl Valve Pos - Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
25 26 27 28 29 30
RD RW RD RW RW RW
231
Table 82
Refrigerant Supply Refrig Over Temp - Event Control Multistate_Value Supply Refrig Over Temp - Event Type Supply Refrig Under Temp - Event Control Supply Refrig Under Temp - Event Type Multistate_Value Multistate_Value Multistate_Value 41 42 43 44 45 46 4635_1 4636_1 4638_1 4639_1 4641_1 4642_1 RD RW RD RW RD RW
Supply Refrig Temp Sensor Issue - Event Multistate_Value Control Supply Refrig Temp Sensor Issue - Event Multistate_Value Type Fluid Supply Fluid Over Temp - Event Control Supply Fluid Over Temp - Event Type Multistate_Value Multistate_Value
57 58 59 60 61 62
RD RW RD RW RD RW
Supply Fluid Under Temp - Event Control Multistate_Value Supply Fluid Under Temp - Event Type Supply Fluid Temp Sensor Issue - Event Control Supply Fluid Temp Sensor Issue - Event Type Pumps Pump 1 State Pump 2 State Pump 1 Loss of Flow - Event Control Pump 1 Loss of Flow - Event Type Pump 2 Loss of Flow - Event Control Pump 2 Loss of Flow - Event Type Pump Short Cycle - Event Control Pump Short Cycle - Event Type Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
73 74 75 76 77 78 79 80
RD RD RW RW RW RW RD RW
232
Table 82
Compressors Compressor 1A State Compressor 1B State Compressor 2A State Compressor 2B State Compressor 1A High Head Pressure Event Control Compressor 1A High Head Pressure Event Type Compressor 1B High Head Pressure Event Control Compressor 1B High Head Pressure Event Type Compressor 2A High Head Pressure Event Control Compressor 2A High Head Pressure Event Type Compressor 2B High Head Pressure Event Control Compressor 2B High Head Pressure Event Type Compressor 1A Short Cycle - Event Control
Compressor 1A Short Cycle - Event Type Multistate_Value Compressor 1B Short Cycle - Event Control Multistate_Value
Compressor 1B Short Cycle - Event Type Multistate_Value Compressor 2A Short Cycle - Event Control Multistate_Value
Compressor 2A Short Cycle - Event Type Multistate_Value Compressor 2B Short Cycle - Event Control Multistate_Value
Compressor 2B Short Cycle - Event Type Multistate_Value Circuit 1 Low Suction Pressure - Event Control Circuit 1 Low Suction Pressure - Event Type Circuit 2 Low Suction Pressure - Event Control Multistate_Value Multistate_Value Multistate_Value
233
Table 82
Circuit 2 Low Suction Pressure - Event Type Hot Gas Hot Gas Solenoid Valve 1 Position Hot Gas Solenoid Valve 2 Position XD System 1 Communication Status Fan On/Off Control Primary Fan Group State Fan Button Control Visual ID Control Ext System Condensation Detected Event Control Ext System Condensation Detected Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type XD System 1 Secondary Fans 1 Fan State Fan Economy Mode XD System 2 Communication Status Fan On/Off Control Primary Fan Group State
Multistate_Value Multistate_Value
125 126
4701_1 4702_1
RD RD
Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
137 138 139 140 141 142 143 144 145 146 147 148 149
5486_1 5487_1 5509_1 5488_1 5489_1 5493_1 5494_1 5496_1 5497_1 5498_1 5499_1 5501_1 5502_1
RD RW RD RW RW RW RW RW RW RW RW RW RW
Multistate_Value Multistate_Value
160 161
5510_1_1 5511_1_1
RD RW
RD RW RD
234
Table 82
Fan Button Control Visual ID Control Ext System Condensation Detected Event Control Ext System Condensation Detected Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type XD System 2 Secondary Fans 1 Fan State Fan Economy Mode XD System 20 Communication Status Fan On/Off Control Primary Fan Group State Fan Button Control Visual ID Control Ext System Condensation Detected Event Control Ext System Condensation Detected Event Type Ext Fan Issue - Event Control Ext Fan Issue - Event Type Sensor Issue - Event Control
Multistate_Value Multistate_Value
195 196
5510_2_1 5511_2_1
RD RW
Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value Multistate_Value
802 803 804 805 806 807 808 809 810 811
5486_20 5487_20 5509_20 5488_20 5489_20 5493_20 5494_20 5496_20 5497_20 5498_20
RD RW RD RW RW RW RW RW RW RW
235
Table 82
Sensor Issue - Event Type Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type XD System 20 Secondary Fans 1 Fan State Fan Economy Mode System Information
Multistate_Value Multistate_Value
825 826
5510_20_1 5511_20_1
RD RW
System Status
Multistate_Value
837
4123_1
RD
Multistate_Value Multistate_Value
838 839
4706_1 4707_1
RD RD
Multistate_Value
840
5074_1
RD
System On/Off Control System Event Configuration Customer Input 1 - Event Control Customer Input 1 - Event Type System Condensation Detected - Event Control System Condensation Detected - Event Type Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Smoke Detected - Event Control
Multistate_Value
841
5143_1
RW
RW RW RD RW RD RW RW
236
Table 82
Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type Service Required - Event Control Service Required - Event Type Fan Issue - Event Control Fan Issue - Event Type System Events System Event Acknowledge/Reset
Multistate_Value
876
4717_1
WO
237
Table 83
Auto Restart Delay Calculated Next Maintenance Month Calculated Next Maintenance Year Chilled Water Cntrl Valve Pos Event Control Chilled Water Cntrl Valve Pos Event Type Chilled Water Control Valve Position Circuit 1 Low Suction Pressure Event Control Circuit 1 Low Suction Pressure Event Type Circuit 1 Low Suction Pressure Circuit 2 Low Suction Pressure Event Control Circuit 2 Low Suction Pressure Event Type Circuit 2 Low Suction Pressure Cold Aisle Over Temp Threshold Cold Aisle Temp Out of Range Cold Aisle Under Temp Threshold Communication Status Compressor 1A High Head Pressure - Event Control Compressor 1A High Head Pressure - Event Type Compressor 1A High Head Pressure Compressor 1A Short Cycle - Event Control Compressor 1A Short Cycle - Event Type Compressor 1A Short Cycle Compressor 1A State Compressor 1B High Head Pressure - Event Control Compressor 1B High Head Pressure - Event Type
238
Table 83
Compressor 1B High Head Pressure Compressor 1B Short Cycle - Event Control Compressor 1B Short Cycle - Event Type Compressor 1B Short Cycle Compressor 1B State Compressor 2A High Head Pressure - Event Control Compressor 2A High Head Pressure - Event Type Compressor 2A High Head Pressure Compressor 2A Short Cycle - Event Control Compressor 2A Short Cycle - Event Type Compressor 2A Short Cycle Compressor 2A State Compressor 2B High Head Pressure - Event Control Compressor 2B High Head Pressure - Event Type Compressor 2B High Head Pressure Compressor 2B Short Cycle - Event Control Compressor 2B Short Cycle - Event Type Compressor 2B Short Cycle Compressor 2B State Cooling Capacity Cooling Capacity Customer Input 1 - Event Control Customer Input 1 - Event Type Customer Input 1 Dew Point Temperature Ext Air Over Temp Threshold Ext Air Sensor A Dew Point Temp
239
Table 83
Ext Air Sensor A Humidity Ext Air Sensor A Issue - Event Control Ext Air Sensor A Issue - Event Type Ext Air Sensor A Issue Ext Air Sensor A Over Temp - Event Control Ext Air Sensor A Over Temp - Event Type Ext Air Sensor A Over Temperature Ext Air Sensor A Temperature Ext Air Sensor A Under Temp Event Control Ext Air Sensor A Under Temp Event Type Ext Air Sensor A Under Temperature Ext Air Sensor B Dew Point Temp Ext Air Sensor B Humidity Ext Air Sensor B Issue - Event Control Ext Air Sensor B Issue - Event Type Ext Air Sensor B Issue Ext Air Sensor B Over Temp - Event Control Ext Air Sensor B Over Temp - Event Type Ext Air Sensor B Over Temperature Ext Air Sensor B Temperature Ext Air Sensor B Under Temp Event Control Ext Air Sensor B Under Temp Event Type Ext Air Sensor B Under Temperature Ext Air Under Temp Threshold Ext Dew Point Over Temp - Event Control
240
Table 83
Ext Dew Point Over Temp - Event Type Ext Dew Point Over Temp Threshold Ext Dew Point Over Temperature
Ext Fan Issue - Event Control Ext Fan Issue - Event Type Ext Fan Issue Ext Remote Shutdown - Event Control Ext Remote Shutdown - Event Type Ext Remote Shutdown Ext System Condensation Detected - Event Control Ext System Condensation Detected - Event Type Ext System Condensation Detected Fan Button Control Fan Economy Mode Fan Issue - Event Control Fan Issue - Event Type Fan Issue Fan On/Off Control Fan State Hot Aisle Over Temp Threshold Hot Aisle Temp Out of Range Hot Aisle Under Temp Threshold Hot Gas Solenoid Valve 1 Position Hot Gas Solenoid Valve 2 Position Hot Gas Valve 1 Open Position Hot Gas Valve 2 Open Position Maintenance Completed Maintenance Due Maintenance Ramp Master Unit Communication Lost Minimum Room Temperature Set Point Primary Fan Group State
241
Table 83
Pump 1 Loss of Flow - Event Control Pump 1 Loss of Flow - Event Type Pump 1 Loss of Flow Pump 1 State Pump 2 Loss of Flow - Event Control Pump 2 Loss of Flow - Event Type Pump 2 Loss of Flow Pump 2 State Pump Hours Exceeded Pump Hours Threshold Pump Hours Pump Short Cycle - Event Control Pump Short Cycle - Event Type Pump Short Cycle RAM Battery Issue Remote Sensor Temperature Remote Shutdown Sensor Issue - Event Control Sensor Issue - Event Type Sensor Issue Service Required - Event Control Service Required - Event Type Service Required Shutdown - Loss Of Power - Event Control Shutdown - Loss Of Power - Event Type Shutdown - Loss Of Power Smoke Detected - Event Control Smoke Detected - Event Type Smoke Detected Supply Chilled Water Over Temp Threshold
242
Table 83
Supply Chilled Water Over Temp Supply Chilled Water Temp Sensor Issue Supply Chilled Water Temperature Supply CW Over Temp - Event Control Supply CW Over Temp - Event Type Supply CW Temp Sensor Issue Event Control Supply CW Temp Sensor Issue Event Type Supply Fluid Over Temp - Event Control Supply Fluid Over Temp - Event Type Supply Fluid Over Temp Threshold Supply Fluid Over Temp Supply Fluid Temp Sensor Issue Event Control Supply Fluid Temp Sensor Issue Event Type Supply Fluid Temp Sensor Issue Supply Fluid Temperature Supply Fluid Under Temp - Event Control Supply Fluid Under Temp - Event Type Supply Fluid Under Temp Supply Refrig Over Temp - Event Control Supply Refrig Over Temp - Event Type Supply Refrig Over Temp Threshold Supply Refrig Temp Sensor Issue Event Control Supply Refrig Temp Sensor Issue Event Type
243
Table 83
Supply Refrig Under Temp Control Event Supply Refrig Under Temp - Event Type Supply Refrigerant Over Temp Supply Refrigerant Temp Sensor Issue Supply Refrigerant Temperature Supply Refrigerant Under Temp System Condensation Detected Event Control System Condensation Detected Event Type System Condensation Detected System Control Mode System Date and Time System Event Acknowledge/Reset System On/Off Control System Operating State Reason System Operating State System Status Unit Code Missing Unit Communication Lost Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Visual ID Control Water Under Floor - Event Control Water Under Floor - Event Type Water Under Floor
244
Table 84
Liebert Products Data Description Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Unit On/Off Alarm Points Communications Local Off Remote Off High Head Pressure 1 Loss of Airflow Standby Glycol Unit On Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Flow Standby Unit On Short Cycle Loss of Power Local Alarm 1 Local Alarm 2 High Water Local Alarm 4 Setpoints (View) Temperature Humidity Control Points (Set) Remote On/Off Temperature Setpoint Humidity Setpoint
245
Table 85
Data Description Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Standby Unit On Short Cycle Loss of Power Local Alarm 1 Local Alarm 2 High Water Humidifier Pan Setpoints (View) Temperature Setpoint Humidity Setpoint Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout
246
247
4.3
UPS Systems
Table 86 Liebert APM - Binary Data
Object Type Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Instance 1 2 3 4 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 Object Name 4172_1 4170_1 4200_1 4315_1 4122_1 4295_1 4233_1 4135_1 4162_1 4758_1 4311_1 4310_1 4213_1 4143_1 4139_1 4823_1 4314_1 4219_1 4146_1 4440_1 4234_1 4235_1 4236_1 4831_1 4290_1 4389_1 4300_1 4164_1 4382_1 4173_1 4391_1 5149_1 5150_1 5151_1 5152_1 5153_1 5154_1 5155_1 5156_1 Access RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD RD Notes -
Data Description System Status Battery Auto Test In Progress Battery Equalize Battery Charging Inhibited On Generator System Events System Input Power Problem Rectifier Failure Inverter Failure Bypass Not Available Battery Low LBS Inhibited System Fan Failure Equipment Over Temperature System Shutdown - EPO Bypass Static Switch Unavailable Bypass - Excess Auto Retransfers Parallel Comm Warning Power Supply Failure Battery Over Temperature System Input Phs Rotation Error Fuse Failure Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C MMS Overload Inverter Shutdown - Overload System Output Fault Internal Communications Failure Battery Charging Error System Input Current Imbalance Main Battery Disconnect Open Inverter Static Switch SCR Short Battery Not Qualified Battery Terminals Reversed Battery Converter Failure Inverter SCR Open Load Sharing Fault DC Bus Abnormal Mains Input Neutral Lost Load Impact Transfer
248
Table 86
Data Description User Operation Invalid Power Sub Module Fault Battery Discharging UPS Output on Bypass Output Load on Maint. Bypass Battery Capacity Low MMS On Battery
249
Table 87
Data Description Input System Input RMS A-B System Input RMS B-C System Input RMS C-A System Input RMS Current Phase A System Input RMS Current Phase B System Input RMS Current Phase C System Input Frequency System Input RMS A-N System Input RMS B-N System Input RMS C-N System Input Power Factor Phs A System Input Power Factor Phs B System Input Power Factor Phs C Bypass Bypass Input Voltage RMS A-N Bypass Input Voltage RMS B-N Bypass Input Voltage RMS C-N Bypass Input Frequency Battery Battery Time Remaining Battery Volts for Cabinet Battery Temperature for Cabinet Inlet Air Temperature DC Bus Current Output System Output Voltage RMS A-N System Output Voltage RMS B-N System Output Voltage RMS C-N System Output RMS Current Phs A System Output RMS Current Phs B System Output RMS Current Phs C System Output Frequency System Output Voltage RMS A-B System Output Voltage RMS B-C System Output Voltage RMS C-A System Output Power Factor Phs A System Output Power Factor Phs B System Output Power Factor Phs C System Output Pct Power Phase A System Output Pct Power Phase B System Output Pct Power Phase C
250
Table 87
Data Description MMS Output Apparent Power MMS Output Power System Output Apparent Power System Output Power Output Current Crest Factor Phs A Output Current Crest Factor Phs B Output Current Crest Factor Phs C System Configuraton System Date and Time
251
Table 88
Data Description Battery Auto Test In Progress Battery Capacity Low Battery Charging Error Battery Charging Inhibited Battery Converter Failure Battery Discharging Battery Equalize Battery Low Battery Not Qualified Battery Over Temperature Battery Temperature for Cabinet Battery Terminals Reversed Battery Time Remaining Battery Volts for Cabinet Bypass - Excess Auto Retransfers Bypass Input Frequency Bypass Input Voltage RMS A-N Bypass Input Voltage RMS B-N Bypass Input Voltage RMS C-N Bypass Not Available Bypass Static Switch Unavailable DC Bus Abnormal DC Bus Current Equipment Over Temperature Fuse Failure Inlet Air Temperature Internal Communications Failure Inverter Failure Inverter On/Off State Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C Inverter SCR Open Inverter Shutdown - Overload Inverter Static Switch SCR Short
252
Table 88
Data Description LBS Inhibited Load Impact Transfer Load Sharing Fault Main Battery Disconnect Open Mains Input Neutral Lost Maintenance Bypass Breaker (MBB) MMS On Battery MMS Output Apparent Power MMS Output Power MMS Overload On Generator Output Current Crest Factor Phs A Output Current Crest Factor Phs B Output Current Crest Factor Phs C Output Load on Maint. Bypass Parallel Comm Warning Power Sub Module Fault Power Supply Failure Rectifier Failure System Date and Time System Fan Failure System Input Current Imbalance System Input Frequency System Input Phs Rotation Error System Input Power Factor Phs A System Input Power Factor Phs B System Input Power Factor Phs C System Input Power Problem System Input RMS A-B System Input RMS A-N System Input RMS B-C System Input RMS B-N System Input RMS C-A System Input RMS C-N System Input RMS Current Phase A System Input RMS Current Phase B System Input RMS Current Phase C System Output Apparent Power System Output Fault System Output Frequency System Output Pct Power Phase A
253
Table 88
Data Description System Output Pct Power Phase B System Output Pct Power Phase C System Output Power Factor Phs A System Output Power Factor Phs B System Output Power Factor Phs C System Output Power System Output RMS Current Phs A System Output RMS Current Phs B System Output RMS Current Phs C System Output Voltage RMS A-B System Output Voltage RMS A-N System Output Voltage RMS B-C System Output Voltage RMS B-N System Output Voltage RMS C-A System Output Voltage RMS C-N System Shutdown - EPO System Status UPS battery1 status UPS Output on Bypass UPS Output Source User Operation Invalid
254
255
256
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Locations
United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2009 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-28170_REV8_03-12
Emerson Network Power. The global leader in enabling Business-Critical Continuity AC Power Connectivity DC Power Embedded Computing Embedded Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. 2009 Emerson Electric Co.