Location

Area sqmt

Heigh (M)

Trickle Mode Supply ACH

2 3 4 5 6 7 8 9 10 11 11 12 13 14 15 16 17 4 Level Subgrade Total (m3/sec) Total/shaft (m3/sec) Air Velocity Area Required
25376.0 Qty

Basement-01

6050.0

4.1

3.0

Basement-02

6462.0

3.6

3.0

Basement-03

6664.0

3.6

3.0

Basement-04

6200.0

3.9

3.0

Total (m3/sec) Total/shaft (m3/sec) Air Velocity(m/s) Area Required(m2)

Note : Louver is designed based on maximum fire flow rate. Since maximum flow rate is 69.3 M3/S and it is divided into two shaft so the selection is

3.11 CAR PARKING DESIGN BUR


Trickle Mode Normal Mode Trickle Mode Rate (M3/S) Supply Rate (M3/S) ACH Fire Mode Supply ACH Fire Mode Rate (M3/S) Exhaust Air Riser Fresh Air Riser

20.8

6.0

41.6

10.0

69.3

19.4

6.0

38.9

10.0

64.8

19.9

6.0

39.7

10.0

66.2

20.1

6.0

40.1

10.0

66.9

80.16

160.32

69.32

176.4 88.18 3.5 25.19

158.7 79.36 3.5 22.67

shaft so the selection is based on 35 M3/S(approx) and velocity is given below

PARKING DESIGN BURO HOPPOLD

Type of Fan

Qty

Qty/Shaft

Arrangment

Smoke Rated Axial Flow(EA) Axial Flow Fan(FA) Impulse Fan Smoke Rated Axial Flow(EA) Axial Flow Fan(FA) Impulse Fan Smoke Rated Axial Flow(EA) Axial Flow Fan(FA) Impulse Fan Smoke Rated Axial Flow(EA) Axial Flow Fan(FA) Impulse Fan

6 4 22 6 4 24 6 4 24 6 4 20

3 2

D/D/S D/D D

3 2

D/D/S D/D D

3 2

D/D/S D/D D

3 2

D/D/S D/D D

Flow (M3/S) (As per Calcualtion) Low 10.40 5.20 High 17.33 8.67

Flow (M3/S) (As per Schedule) Low 11.276 4.26 0.97 High 18.70 8.52 1.9 19.547 11.57 1.9 17.985 10.9 1.9 17.1 10.93 1.9

9.72 4.86

16.20 8.10

11.78 5.79 0.97

9.93 4.96

16.54 8.27

10.79 5.45 0.97

10.04 5.02

16.73 8.36

10.268 5.47 0.97

VFD

Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High

Location

Area sqmt

Heigh (M)

Trickle Mode Supply ACH

2 3 4 5 6 7 8 9 10 11 11 12 13 14 15 16 17 4 Level Subgrade Total (m3/sec) Total/shaft (m3/sec) Air Velocity Area Required
25376.0 Qty

Basement-01

6050.0

4.1

3.0

Basement-02

6462.0

3.6

3.0

Basement-03

6664.0

3.6

3.0

Basement-04

6200.0

3.9

3.0

Total (m3/sec) Total/shaft (m3/sec) Air Velocity(m/s) Area Required(m2)

Note: Louver is designed based on maximum fire flow rate. Since maximum flow rate is 69.3 M3/S and it is dived into two shaft so the selection is based on 3

3.11 CAR PARKING DESIGN COLT ARABIA


Trickle Mode Normal Mode Trickle Mode Rate (M3/S) Supply Rate (M3/S) ACH Fire Mode Supply ACH Fire Mode Rate (M3/S) Exhaust Air Riser Fresh Air Riser

20.8

6.0

41.6

10.0

69.3

19.4

6.0

38.9

10.0

64.8

19.9

6.0

39.7

10.0

66.2

20.1

6.0

40.1

10.0

66.9

80.16

160.32

69.32

176.4 88.18 3.5 25.19

158.7 79.36 3.5 22.67

selection is based on 35 M3/S(approx) and velocity is 2.2 M/S

COLT ARABIA

Type of Fan

Qty

Qty/Shaft

Arrangment

Impulse Fan

14

Impulse Fan

14

Impulse Fan

14

Axial Smoke Extract Fan Axial Fresh Air Fan Impulse Fan

6 6 11

3 3

D/D/D D/D/D D

Flow (M3/S) (As per Calcualtion) VFD Low(50%) 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 13.36 12.02 0.9 High(100%) 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 26.72 24.05 1.8 Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High Low/High