Powerware Series

Eaton 5125 Tower UPS


10002200 VA
User's Guide

Requesting a Declaration of Conformity


Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S Harmonized Standards: IEC/EN 62040-1-1 and IEC/EN 62040-2
S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
Eaton, Powerware, ABM, LanSafe, and X-Slot are registered trademarks and ConnectUPS is a trademark of
Eaton Corporation or its subsidiaries and affiliates. Modbus is a registered trademark of Schneider Automation.
National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other
trademarks are property of their respective companies.
ECopyright 20012010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Eaton Corporation.
Class A EMC Statements
(10001500 VA Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing
Equipment Regulations ICES003.
Cet appareil numrique de la classe A respecte toutes les exigences du Reglement sur le matriel brouilleur du
Canada.
EN 50091-2
Some configurations are classified under EN 500912 as ClassA UPS for Unrestricted Sales Distribution. For
these configurations, the following applies:
WARNING This is a Class AUPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
VCCI Notice
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock
symbol.
CAUTION: REFER TO OPERATORS MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance instructions.
RJ-45 RECEPTACLE - For 230V models only: this receptacle provides network interface connections.
Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
product contains sealed, leadacid batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality i
Table of Contents
1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Safety Warnings 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Installation 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspecting the Equipment 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the UPS Internal Battery 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the UPS 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Rear Panels 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operation 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS On 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS on Battery 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS Off 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initiating the SelfTest 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Modes 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Mode 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Buck and Double Boost Mode 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Mode 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standby Mode 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Additional UPS Features 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X-Slot Cards 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single-Port Card 36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Transient Protector 38 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Segments 39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 UPS Maintenance 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS and Battery Care 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transporting the UPS 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the UPS and Batteries 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When to Replace Batteries 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing Batteries 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Replace Internal Batteries 43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Replace Extended Battery Modules 46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing New Batteries 46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recycling the Used Battery or UPS 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality ii
7 Specifications 49 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Troubleshooting 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Audible Alarms and UPS Conditions 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Silencing an Audible Alarm 54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service and Support 57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 Warranty 59 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two-Year Limited Warranty with Extension to Three-Year Limited Warranty (US and Canada) 59 . . . . . . . . . . . . . .
Load Protection Guarantee (US and Canada) 61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 1
Chapter 1 Introduction
Eaton

5125 uninterruptible power system (UPS) protects your sensitive


electronic equipment from basic power problems such as power
failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power
quality can be erratic. These power problems have the potential to
corrupt critical data, destroy unsaved work sessions, and damage
hardware causing hours of lost productivity and expensive repairs.
With the Eaton 5125, you can safely eliminate the effects of power
disturbances and guard the integrity of your equipment. The Eaton 5125
was designed for critical applications such as PCs, servers,
workstations, and telecommunications equipment.
Figure 1 shows the Eaton 5125 UPS with an optional Extended Battery
Module (EBM).
Figure 1. The Eaton 5125 UPS with Optional EBM
INTRODUCTION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 2
Providing outstanding performance and reliability, the Eaton 5125's
unique benefits include:
S Buck and Double Boost regulation that ensures consistent voltage to
your load by correcting voltage fluctuations without using battery
power.
S ABM

technology that uses advanced battery management to


increase battery service life, optimize recharge time, and provide a
warning before the end of useful battery life.
S Hours of extended runtime with up to four EBMs.
S Startonbattery capability for powering up the UPS even if utility
power is not available.
S Hotswappable batteries that simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
S Optional X-Slot

cards with enhanced communication capabilities for


network connectivity with monitoring and control.
S Network transient protector that guards your network
communications equipment from surges. Low voltage models can
also protect modems, fax machines, or other telecommunications
equipment.
S Advanced power management with the Software Suite CD for
graceful shutdowns and power monitoring.
S Sequential shutdown and load management through separate
receptacle groups, called load segments.
S Backed by worldwide agency approvals.
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 3
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
D A N G E R
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
W A R N I N G
S This UPS contains its own energy source (batteries). The output receptacles may carry
live voltage even when the UPS is not connected to an AC supply.
S For 230V models, the output receptacles may remain electrically live. If the input power
source in your application is wired line-to-neutral (as in most European applications), the
voltage to the output receptacles is 0V. With line-to-line input wiring, the voltage to the
output receptacles is 115V (measured from line-to-ground or line-to-neutral, depending
on the UPS wiring).
S Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40C (104F). Do not operate near water or excessive humidity (95%
maximum).
S To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than
1.5 milliamperes.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 4
C A U T I O N
S Batteries can present a risk of electrical shock or burn from high short-circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
Denne manual indeholder vigtige instruktioner, som skal flges under installation og
vedligeholdelse af UPS'en og batterierne. Ls venligst alle instruktioner inden betjening af
udstyret og gem denne manual mhp. fremtidige opslag.
F A R E
Denne UPS indeholder LIVSFARLIG HJSPNDING. Alle reparationer og vedligeholdelse br
kun udfres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS'ens indvendige dele kan
repareres af brugeren.
A D V A R S E L !
S Denne UPS indeholder sin egen energikilde (batterier). Udgangsstikkene kan endog vre
strmfrende, nr UPS'en ikke er koblet til en vekselstrmsforsyning.
S P 230V-modeller kan udgangsstikkene vre strmfrende. Hvis ledningsfringen til
indgangsstrmkilden p din enhed er fase-til-neutral (som p de fleste europiske
enheder), er spndingen til udgangsstikkene 0V. Med en fase-til-fase
indgangsledningsfring er spndingen til udgangsstikkene 115V (mlt fra fase-til-jord
eller fase-til-neutral, afhngig af UPS-ledningsfringen).
S Netledningen m ikke fjernes og stikket m ikke trkkes ud, mens UPS'en er tndt.
Dette fjerner sikkerhedsjorden fra UPS'en og fra det udstyr, der er sat til.
S Installr denne UPS i et temperatur- og fugtighedskontrolleret indendrsmilj, frit for
ledende forureningsstoffer for at formindske risikoen for brand og elektrisk std.
Rumtemperaturen m ikke overstige 40C. UPS'en br ikke betjenes nr vand eller hj
fugtighed (maksimalt 95%).
S I overensstemmelse med internationale normer og bestemmelser for el-installation m
det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en
jordafdelingsspnding p mere end 1,5 milliampere.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 5
A D V A R S E L
S Batterierne kan give risiko for elektrisk std eller brandsr forrsaget af hj
kortslutningsstrm. Overhold gldende forsigtighedsregler. Servicering skal udfres af
kvalificeret servicepersonale med kendskab til batterier og gldende forsigtighedsregler.
Hold uautoriseret personale vk fra batterierne.
S Korrekt bortskaffelse af batterier er pkrvet. Overhold gldende lokale regler for
bortskaffelsesprocedurer.
S Skaf dig aldrig af med batterierne ved at brnde dem. Batterierne kan eksplodere ved
ben ild.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZE INSTRUCTIES
Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en
het onderhoud van de UPS en de accu's. Lees alle instructies voordat u de apparatuur in
bedrijf neemt en bewaar deze handleiding als naslagwerk.
G E V A A R
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd.
Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden
GEREPAREERD.
W A A R S C H U W I N G
S Deze UPS bevat een eigen energiebron (batterijen). De uitgangscontactdoos kan onder
spanning staan, zelfs wanneer de UPS niet is aangesloten op de netspanning.
S Bij de modellen van 230V kan de uitgangscontactdoos onder spanning blijven staan. Als
de bedrading van de ingangsspanningsbron in uw systeem loopt van fase naar aarde
(zoals bij de meeste Europese systemen) dan bedraagt de spanning op de
uitgangscontactdozen 0 V. Als de ingangsbedrading loopt van fase naar fase dan
bedraagt de spanning op de uitgangscontactdozen 115V (gemeten tussen fase en aarde
of tussen fase en neutraal, afhankelijk van de UPS-bedrading).
S Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de
UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen
aardebeveiliging meer hebben.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 6
S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een
gebouw met temperatuur en vochtigheidregeling te worden genstalleerd, waar geen
geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40C niet
overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid
(max. 95%).
S Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele
apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van
meer dan 1,5 milliampre hebben.
O P G E L E T
S Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden
veroorzaken door een grote kortsluitstroom. Neem de juiste voorzorgsmaatregelen in
acht. Het onderhoud moet worden uitgevoerd door bevoegde onderhoudsmonteurs die
verstand hebben van accu's en op de hoogte zijn van de vereiste voorzorgsmaatregelen.
Houd onbevoegden uit de buurt van de accu's.
S De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
plaatselijke voorschriften.
S Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 7
Tarkeita turvaohjeita
TRKEIT TURVAOHJEITA - SUOMI
SILYT NM OHJEET
Tm kyttohje sislt trkeit ohjeita, joita on noudatettava UPS-virtalhteen ja akkujen
asennuksen ja huollon yhteydess. Lue kaikki ohjeet ennen laitteiston kytt ja silyt ohje
myhemp tarvetta varten.
V A A R A
Tm UPS sislt HENGENVAARALLISIA JNNITTEIT. Kaikki korjaukset ja huollot on
jtettv VAIN VALTUUTETUN HUOLTOHENKILN TOIMEKSI. UPS ei sisll MITN
KYTTJN HUOLLETTAVIA OSIA.
V A R O I T U S
S Tss UPS-virtalhteess on oma energianlhde (akut). Lhtvastakkeissa voi olla
jnnite, vaikka UPS-virtalhdett ei ole kytketty verkkovirtaan.
S 230V -malleissa lhtvastakkeissa voi sily jnnite. Jos sovelluksen tulovirtalhde on
johdotettu linjasta neutraaliin (kuten useimmissa eurooppalaisissa sovelluksissa)
lhtvastakkeiden jnnite on 0 V. Linjasta linjaan tulojohdotuksessa lhtvastakkeiden
jnnite on 115V (mitataan linjasta maahan tai linjasta neutraaliin, UPS-virtalhteen
johdotuksesta riippuen).
S l poista tai irrota sisntulojohtoa, kun UPS on kytkettyn. Tm poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetyst laitteistosta.
S Vhentksesi tulipalon ja shkiskun vaaraa asenna tm UPS sistiloihin,
joissa lmptila ja kosteus on sdettviss ja joissa ei ole virtaa johtavia
eppuhtauksia. Ympristn lmptila ei saa ylitt 40 C. l kyt lhell vett ja vlt
kosteita tiloja (95 % maksimi).
S Kansainvliset normit ja johdotusmrykset vaativat, ett kaikkien tmn UPS-laitteen
ulostulokytkentjen yhteinen maavuotovirta ei ylit 1,5 milliampeeria (mA).
V A R O
S Akut voivat aiheuttaa shkiskun tai palovammojen vaaran johtuen suuresta
oikosulkuvirrasta. Noudata kaikkia asianmukaisia varotoimia. Laitteen saa huoltaa vain
ammattitaitoinen huoltohenkilkunta, joka tuntee akut ja niihin liittyvt varotoimet. l
pst valtuuttamatonta henkilst lhelle akkuja.
S Akusto tytyy hvitt sdsten mukaisella tavalla. Noudata paikallisia mryksi.
S l koskaan heit akkuja tuleen. Ne voivat rjht.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 8
Consignes de scurit
CONSIGNES DE SCURIT IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous tes invit suivre lors de toute
procdure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter
entirement ces instructions avant de faire fonctionner l'quipement et conserver ce manuel
afin de pouvoir vous y reporter ultrieurement.
D A N G E R !
Cet onduleur contient des TENSIONS MORTELLES. Toute opration d'entretien et de
rparation doit tre EXCLUSIVEMENT CONFIE A UN PERSONNEL QUALIFI AGR.
AUCUNE PICE RPARABLE PAR L'UTILISATEUR ne se trouve dans l'onduleur.
A V E R T I S S E M E N T !
S Cette onduleur possde sa propre source d'alimentation (batteries). Il est possible que
les prises de sortie soient sous tension mme lorsque l'onduleur n'est pas connecte
une alimentation CA.
S En ce qui concerne les modles 230 V, il est possible que les prises de sortie restent
sous tension. Si la source d'alimentation de votre application est cble phase et neutre
(comme dans la majorit des applications europennes), la tension vers les prises de
sortie est de 0 V. Avec un cblage d'entre phase phase, la tension vers les prises de
sortie est de 115 V (mesure entre phase et terre ou phase et neutre suivant le cblage
de l'onduleur).
S Ne pas retirer le cordon d'alimentation lorsque l'onduleur est sous tension sous peine de
supprimer la mise la terre de l'onduleur et du matriel connect.
S Pour rduire les risques d'incendie et de dcharge lectrique, installer l'onduleur
uniquement l'intrieur, dans un lieu dpourvu de matriaux conducteurs, o la
temprature et l'humidit ambiantes sont contrles. La temprature ambiante ne doit
pas dpasser 40 C. Ne pas utiliser proximit d'eau ou dans une atmosphre
excessivement humide (95 % maximum).
S Afin d'tre conforme aux normes et rglements internationaux de cblage, le courant de
fuite la terre de la totalit du matriel branch sur la sortie de l'onduleur ne doit pas
dpasser 1,5 mA.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 9
A T T E N T I O N !
S Les batteries peuvent prsenter un risque de choc lectrique ou de brlure provenant
d'un courant de court-circuit haute intensit. Observez les prcautions appropries.
L'entretien doit tre ralis par du personnel qualifi connaissant bien les batteries et
les prcautions ncessaires. N'autorisez aucun personnel non qualifi manipuler les
batteries.
S Une mise au rebut rglementaire des batteries est obligatoire. Consulter les rglements
en vigueur dans votre localit.
S Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire
exploser.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN
AUFBEWAREN
Dieses Handbuch enthlt wichtige Anweisungen, die Sie whrend der Installation und
Wartung des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterien
befolgen mssen. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem
Gert arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.
W A R N U N G
Die USV fhrt lebensgefhrliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten
nur von Kundendienstfachleuten durchgefhrt werden. Die USV enthlt keine vom Benutzer
zu wartenden Komponenten.
A C H T U N G
S Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthlt eine eigene
Energiequelle (Batterien). Die Ausgangssteckdosen knnen Spannung fhren, auch wenn
das USV nicht an eine Wechselstromquelle angeschlossen ist.
S Bei Modellen mit 230 Volt knnen die Ausgangssteckverbinder stromfhrend bleiben.
Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist (wie in
den meisten europischen Anlagen), betrgt die Spannung an den
Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Auenleitern betrgt die
Spannung an den Ausgangssteckverbindern 115 Volt (gemessen von Leitung zu Masse
oder Leitung zu Masseleiter, abhngig von der USV-Verkabelung.
S Das Eingangskabel nicht entfernen oder abziehen, whrend die USV eingeschaltet ist,
weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen
Gerten entfernt wird.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 10
S Um die Brand oder Elektroschockgefahr zu verringern, diese USV nur in Gebuden mit
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40C nicht bersteigen.
Die USV nicht in der Nhe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)
betreiben.
S Um internationale Normen und Verdrahtungsvorschriften zu erfllen, drfen die an den
Ausgang dieser USV angeschlossenen Gerte zusammen einen Erdableitstrom von
insgesamt 1,5 Milliampere nicht berschreiten.
V O R S I C H T !
S Batterien knnen das Risiko eines elektrischen Schlags bergen oder durch hohen
Kurzschlussstrom in Brand geraten. Die richtigen Vorsichtsmanahmen beachten. Die
Wartung muss von qualifiziertem Wartungspersonal durchgefhrt werden, das im
Umgang mit Batterien gebt ist und ber gute Kenntnisse der erforderlichen
Vorsichtsmanahmen verfgt. Nicht autorisiertes Personal von Batterien fern halten.
S Die Batterien mssen ordnungsgem entsorgt werden. Hierbei sind die rtlichen
Bestimmungen zu beachten.
S Batterien niemals verbrennen, da sie explodieren knnen.
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA
CONSERVARE QUESTE ISTRUZIONI
Il presente manuale contiene importanti istruzioni da seguire durante l'installazione e la
manutenzione dell'UPS e delle batterie. Leggere integralmente le istruzioni prima di
utilizzare l'apparecchiatura e conservare il presente manuale per futuro riferimento.
P E R I C O L O
La TENSIONE contenuta in questo gruppo statico di continuit LETALE. Tutte le operazioni
di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA
PERSONALE TECNICO AUTORIZZATO. All'interno del gruppo statico di continuit NON vi
sono PARTI RIPARABILI DALL'UTENTE.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 11
A V V E R T E N Z A
S L'UPS contiene la propria fonte di energia (batterie). Le prese d'uscita possono essere
sotto tensione anche quando l'UPS non collegato all'alimentazione elettrica CA.
S Nei modelli da 230 V possibile che le prese d'uscita rimangano sotto tensione. Se la
fonte di alimentazione in entrata dell'installazione costituita da un collegamento
linea-neutro (come accade nella maggior parte delle installazioni europee), la tensione
delle prese d'uscita pari a 0 V. Con un cablaggio in entrata del tipo linea-linea, la
tensione sulle prese d'uscita 115 V (con misurazione effettuata da linea a terra o da
linea a neutro in base al cablaggio dell'UPS).
S Non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit
acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del
gruppo statico di continuit e dell'apparecchiatura ad esso collegata.
S Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di
continuit in un ambiente interno a temperatura ed umidit controllata, privo di agenti
contaminanti conduttivi. La temperatura ambiente non deve superare i 40C. Non
utilizzare l'unit in prossimit di acqua o in presenza di umidit eccessiva (95% max).
S Per conformit con gli standard internazionali e con le norme in merito al cablaggio, tutta
l'apparecchiatura collegata con l'uscita del gruppo statico di continuit non deve avere
una corrente di dispersione di terra superiore a 1,5 milliampere.
A T T E N Z I O N E
S Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a
un'elevata corrente di corto circuito. Osservare le dovute precauzioni. L'assistenza deve
essere eseguita da personale qualificato esperto di batterie e delle necessarie
precauzioni. Tenere il personale non autorizzato lontano dalle batterie.
S Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare
riferimento alle disposizioni locali.
S Non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle
fiamme.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 12
Viktig Sikkerhetsinformasion
VIKTIGE SIKKERHETSINSTRUKSJONER
GJEM DISSE INSTRUKSJONENE
Denne hndboken inneholder viktige instruksjoner som du br overholde ved montering og
vedlikehold av UPS-enheten og batteriene. Les alle instruksjoner fr utstyret tas i bruk, og
gjem hndboken til fremtidig referanse.
F A R L I G
Denne UPS'en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service m kun
utfres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFRE SERVICE P
NOEN AV DELENE i UPS'en.
F A R L I G
S UPS-enheten inneholder sin egen energikilde (batterier). Utgangsstikkene kan vre
strmfrende selv nr UPS-enheten ikke er koblet til et strmuttak.
S Utgangsstikkene kan vre strmfrende for 230V modellene. Spenningen til
utgangsstikkene vil vre 0 V dersom din enhets strmkilde er fase-til-nytral (som p de
fleste europeiske enheter). Med ledningsfrt fase-til-fase inngang vil spenningen til
utgangsstikkene vre 115V (mlt fra fase-til-jord eller fase-til-nytral, avhenging av
UPS-ledningsfringen).
S Strmforsyningskabelen m ikke fjernes eller trekkes ut nr UPS'en er p, slik at ikke
sikkerhetsjordingen fjernes fra UPS'en og det utstyret som er forbundet med den.
S For redusere fare for brann eller elektriske stt, br denne UPS'en installeres i et
innendrs milj med kontrollert temperatur og luftfuktighet som er fritt for ledende,
forurensende stoffer. Romtemperaturen m ikke overskride 40C. Den m ikke brukes i
nrheten av vann eller ved meget hy luftfuktighet (95% maks.).
S Alt utstyr som er forbundet med utgangen av denne UPS'en m ikke ha en sterkere total
lekkasjestrm enn 1,5 milliampere for vre i overensstemmelse med internasjonale
standarder og forkablingsbestemmelser.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 13
F O R S I K T I G
S Batterier kan utgjre en fare for elektrisk stt eller brannsr pga. hy kortsluttingsstrm.
Treff passende forholdsregler. Service br utfres av kvalifisert servicepersonale med
kjennskap til batterier og ndvendige forholdsregler. Hold uautorisert personale borte fra
batteriene.
S Batterier m fjernes p korrekt mte. Se lokale forskrifter vedrrende krav om fjerning av
batterier.
S Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for pen ild.
Regulamentos de Segurana
INSTRUES DE SEGURANA IMPORTANTES
GUARDE ESTAS INSTRUES
Este manual contm instrues importantes que devem ser seguidas durante a instalao e
manuteno do no-break e das baterias. Leia todas as instrues antes de operar o
equipamento e guarde este manual para consult-lo futuramente.
C U I D A D O
A UPS contm VOLTAGEM MORTAL. Todos os reparos e assistncia tcnica devem ser
executados SOMENTE POR PESSOAL DA ASSISTNCIA TCNICA AUTORIZADO. No h
nenhuma PEA QUE POSSA SER REPARADA PELO USURIO dentro da UPS.
A D V E R T N C I A
S Este no-break possui sua prpria fonte de energia (baterias). As tomadas de sada podem
estar energizadas mesmo que o no-break no esteja conectado a uma fonte de energia
eltrica.
S Nos modelos 230V, pode ser que as tomadas de sada permaneam energizadas. Se a
alimentao da sua aplicao for do tipo fase-neutro (como ocorre na maioria das
aplicaes na Europa), a tenso das tomadas de sada de 0 V. Com a alimentao
fase-fase, a tenso das tomadas de sada de 115V (medida como fase-terra ou
fase-neutro, dependendo da instalao eltrica do no-break).
S No remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
remover o aterramento de segurana da UPS e do equipamento conectado.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 14
S Para reduzir o risco de incndios ou choques eltricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutveis.
A temperatura ambiente no deve exceder 40C. No opere prximo a gua ou em
umidade excessiva (mx: 95%).
S Para estar de acordo com os padres internacionais e os regulamentos de fiao, o
equipamento total conectado sada desta UPS no deve ter uma corrente de fuga
terra maior que 1,5 miliampres.
P E R I G O
S As baterias podem oferecer risco de choque eltrico ou queimadura, ocasionados por
alta tenso com possibilidade de curto-circuito. Tome as precaues adequadas. A
manuteno deve ser realizada por pessoal qualificado, com conhecimento sobre
baterias e ciente das precaues exigidas. Mantenha o pessoal no autorizado afastado
das baterias.
S Siga as instrues apropriadas ao desfazerse das baterias. Consulte os cdigos do local
para maiores informaes sobre os regulamentos de descarte de produtos.
S Nunca jogue as baterias no fogo, porque h risco de exploso.
Mepm esonacuoc1u
BAXHbE YKA3AHHR HO MEPAM BE3OHACHOCTH
COXPAHHTE DTH YKA3AHHR

() .
.
.
O H A C H O
.

.
, .
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 15
H P E Y H P E X E H H E
S ().
,
.
S 230
.
- ( , ),
0 .
- 115 (
- -,
).
S
.
, .
S

,
.
40.
(. 95%).
S
,
, ,
1,5 .
O C T O P O X H O
S , ,
.
.

, .
.
S .

.
S .
.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 16
Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
GUARDE ESTAS INSTRUCCIONES
Este manual contiene instrucciones importantes que debe seguir durante la instalacin y el
mantenimiento del SIE y de las bateras. Por favor, lea todas las instrucciones antes de
poner en funcionamiento el equipo y guarde este manual para referencia en el futuro.
P E L I G R O
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio tcnico deben
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TCNICO AUTORIZADO. No hay
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
A D V E R T E N C I A
S Este SIE contiene su propia fuente de energa (bateras). Los receptculos de salida
pueden transportar voltaje activo aun cuando el SIE no est conectado con una fuente de
CA.
S Para los modelos 230V, es posible que los receptculos de salida permanezcan
elctricamente activos. Si la fuente de energa de entrada de su aplicacin est
cableada de lnea a neutro (como la mayora de las aplicaciones europeas), el voltaje a
los receptculos de salida es 0V. Con cableado de entrada de lnea a lnea, el voltaje
hacia los receptculos de salida es 115V (medido de lnea a tierra o de lnea a neutro, lo
que depender del cableado del SIE).
S No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto
suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
S Para reducir el riesgo de incendio o de choque elctrico, instale este SIE en un lugar
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.
La temperatura ambiente no debe exceder los 40C. No trabaje cerca del agua o con
humedad excesiva (95% mximo).
S Para cumplir con los estndares internacionales y las normas de instalacin, la totalidad
de los equipos conectados a la salida de este SIE no debe tener una intensidad de
prdida a tierra superior a los 1,5 miliamperios.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 17
P R E C A U C I N
S Las bateras pueden constituir un riesgo de descarga elctrica o quemaduras por
corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado de
servicio que conozca de bateras y est al tanto de las precauciones requeridas debe
darle servicio al equipo. Mantenga al personal no autorizado alejado de las bateras.
S Es necesario desechar las bateras de un modo adecuado. Consulte las normas locales
para conocer los requisitos pertinentes.
S Nunca deseche las bateras en el fuego. Las bateras pueden explotar si se las expone a
la llama.
Skerhetsfreskrifter
VIKTIGA SKERHETSFRESKRIFTER
SPARA DESSA FRESKRIFTER
Den hr anvisningen innehller viktiga instruktioner som du ska flja under installation och
underhll av UPS-enheten och batterierna. Ls alla instruktioner innan du anvnder
utrustningen och spara den hr anvisningen fr framtida referens.
F A R A
Denna UPS-enhet innehller LIVSFARLIG SPNNING. ENDAST AUKTORISERAD
SERVICEPERSONAL fr utfra reparationer eller service. Det finns inga delar som
ANVNDAREN KAN UTFRA SERVICE P inuti UPS-enheten.
V A R N I N G
S Den hr UPS-enheten innehller sin egen energiklla (batterier). Uttagen kan vara
spnningsfrande ven d UPS-enheten inte r ansluten till spnningsntet.
S P modellerna 230 V kan de utgende uttagen fortfarande vara strmfrande. Om den
ingende strmkllan i din applikation r kopplad ledare-till-nolla (det vanligaste i
Europa) r spnningen till de utgende uttagen 0 V. r den ingende strmkllan kopplad
ledare-till-ledare r spnningen i de utgende uttagen 115 V (uppmtt frn
ledare-till-jord eller ledare-till-nolla beroende p UPS:ens anslutning).
S Ta aldrig bort ntsladden nr UPS-enheten r pslagen. Detta tar bort skyddsjordningen
frn bde UPS-enheten och den anslutna utrustningen.
SAFETY WARNINGS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 18
S Minska risken fr brand eller elektriska sttar genom att installera denna UPS-enhet
inomhus, dr temperatur och luftfuktighet r kontrollerade och dr inga ledande
froreningar frekommer. Omgivande temperatur fr ej verstiga 40C. Anvnd inte
utrustningen nra vatten eller vid hg luftfuktighet (max 95 %).
S Fr att verensstmma med internationell standard och installationsfreskrifter fr inte
den totala utrustning som anslutits till uttagen p denna UPS-enhet ha lcksstrm som
verstiger 1,5 milliampere.
V I K T I G T
S Batterierna kan innebra en risk fr elektrisk stt eller brnnskada frn kortsluten
starkstrm. Iakttag lmpliga frsiktighetstgrder. Service ska utfras av utbildad
servicepersonal med kunskap om batterierna och ndvndiga frsiktighetstgrder. Hll
ej behrig personal borta frn batterierna.
S Batterierna mste avyttras enligt anvisningarna i lokal lagstiftning.
S Anvnda batterier fr aldrig brnnas upp. De kan explodera.
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 19
Chapter 3 Installation
This section explains:
S Equipment inspection
S UPS internal battery connection
S UPS installation
S UPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and file
a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has expired
and the batteries were never recharged, do not use the UPS. Contact your service
representative.
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 20
Connecting the UPS Internal Battery
To ensure proper battery operation:
1. Verify that the UPS is off and unplugged.
2. Remove the UPS front cover (see Figure 2).
Figure 2. Removing the UPS Front Cover
3. Slide up and remove the metal battery cover (see Figure 3).
1000 VA 1500 VA 2200 VA
Figure 3. Removing the Battery Cover
4. Remove the protective label from the internal battery connector
(see Figure 4).
1000 VA 1500 VA 2200 VA
Figure 4. Removing the Protective Label
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 21
NOTE A small amount of arcing may occur when connecting the batteries. This is normal
and does not damage the unit or present any safety concern.
5. Connect the internal battery connector(s) (see Figure 5).
1000 VA 1500 VA 2200 VA
Figure 5. Connecting the Internal Battery Connector(s)
6. Replace the metal battery cover.
7. Replace the UPS front cover.
8. Continue to the following section, Installing the UPS.
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 22
Installing the UPS
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
Figure 6 shows a typical installation only. See UPS Rear Panels on
page 24 for the rear panel of each model.
To install the UPS and optional Extended Battery Modules (EBMs):
1. If installing an optional EBM, continue to Step 2; otherwise,
proceed to Step 3.
2. Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 6. Up to four EBMs may be connected to the UPS.
UPS Battery
Connector
EBM Cable EBM Battery Connector
Output Receptacles
Communication Port
Power Cord
UPS EBM EBM
Figure 6. Typical UPS Installation with Two EBMs
3. If you plan to install power management software, connect your
computer to the UPS communication port using the supplied
communication cable. For more information about communication
options, see page 35.
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 23
4. Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 39 for more information on load segments).
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
5. For 208V/230V models only. Plug the detachable UPS power cord
into the input connector on the UPS rear panel.
6. Plug the UPS power cord into a power outlet.
The front panel indicators cycle through a startup sequence while
the UPS conducts a selftest. When the self-test is complete, the
indicator flashes, indicating the UPS is in Standby mode with
the equipment offline. If the alarm beeps or a UPS alarm indicator
stays on, see Table 9 on page 54.
7. Press and hold the On button until you hear the UPS beep
(approximately one second).
The indicator illuminates solid and the bar graph indicators
display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
NOTE If more than two EBMs are installed, an external battery charger is recommended
for faster recharge times.
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 24
UPS Rear Panels
This section shows the rear panels of the Eaton 5125 models.
X-Slot
Communication
Bay
6ft Power Cord
with 515 Plug
Battery
Connector
Network Transient
Protector
Six 5-15R
Receptacles
Communication
Port
Figure 7. PW5125 1000 and PW5125 1500 Rear Panel
6ft Power Cord
with 520 Plug
Battery
Connector
Network Transient
Protector
Six 5-15R
Receptacles
Two 5-20R
Receptacles
X-Slot
Communication
Bay
Communication Port
Figure 8. PW5125 2200 Rear Panel
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 25
10A, IEC320
Input Connector
Battery
Connector
Network Transient
Protector
Six 10A, IEC 320-C13
Receptacles
X-Slot
Communication
Bay
Communication
Port
Figure 9. PW5125 1000i and PW5125 1500i Rear Panel
10A, IEC320
Input Connector
Battery
Connector
Network Transient
Protector
Nine 10A, IEC 320-C13
Receptacles
X-Slot
Communication
Bay
Communication Port
Figure 10. PW5125 2200i Rear Panel
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 26
6ft Power Cord
with 515 Plug
Battery
Connector
Network Transient
Protector
Six 5-15R
Receptacles
X-Slot
Communication
Bay
Communication
Port
Figure 11. PW5125 1000j Rear Panel
Battery
Connector
Network Transient
Protector
Six 5-15R
Receptacles
6ft Power Cord
with 520 Plug
X-Slot
Communication
Bay
Communication
Port
Figure 12. PW5125 1500j Rear Panel
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 27
6-ft Power Cord
with L5-30 Plug
Battery
Connector
Network Transient
Protector
Six 5-15R
Receptacles
Two 5-20R
Receptacles
X-Slot
Communication
Bay
Communication Port
Figure 13. PW5125 2200j Rear Panel
Network Transient
Protector
15A, IEC320
Input Connector
Battery
Connector
Nine 10A, IEC 320-C13
Receptacles
X-Slot
Communication
Bay
Communication Port
Figure 14. PW5125 2200b Rear Panel
INSTALLATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 28
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 29
Chapter 4 Operation
This section describes:
S Turning the UPS on and off
S Starting the UPS on battery
S Initiating the selftest
S Operating modes
Turning the UPS On
After the UPS is connected to a power outlet, it conducts a selftest and
enters Standby mode.
To turn on the UPS, press and hold the On button until you hear the
UPS beep (approximately one second). The indicator illuminates
solid, and the bar graph indicators display the percentage of load being
applied to the UPS.
Starting the UPS on Battery
NOTE Before using this feature, the UPS must have been powered by utility power at least
once.
To turn on the UPS without using utility power, press and hold the
On button for at least four seconds. The UPS starts up in Battery mode
and supplies battery power to your equipment.
OPERATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 30
Turning the UPS Off
NOTE Pressing the Off button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1. Prepare your equipment for shutdown.
2. Press and hold the Off button until the long beep ceases
(approximately five seconds). The indicator begins to flash. The
UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
3. Unplug the UPS.
If you do not unplug the UPS, it remains in Standby mode.
Initiating the SelfTest
NOTE The batteries must be fully charged to perform the selftest.
Press and hold the button for three seconds to initiate the selftest.
During the test, individual indicators illuminate as various parts of the
UPS are checked. If the alarm beeps or a UPS alarm indicator stays on,
see Table 9 on page 54.
OPERATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 31
Operating Modes
The Eaton 5125 front panel indicates the UPS status through the UPS
indicators. Figure 15 shows the UPS front panel indicators and controls.
Normal Mode Indicator (solid green)
Standby Mode Indicator (flashing green)
Buck Mode Indicator (solid green, solid red)
Boost 1 Mode Indicator (solid green, flashing red)
Boost 2 Mode Indicator (flashing green, solid red)
Red
On Button
Off Button
Test/Alarm Reset Button
Bar Graph Indicators
Battery Mode Indicator
Flashing
Unlit
Green
Indicator Legend
Figure 15. UPS Front Panel
OPERATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 32
Normal Mode
During Normal mode, the indicator illuminates and the front panel
displays the percentage of UPS load capacity being used by the
protected equipment (see Figure 16). The UPS monitors and charges the
batteries as needed and provides power protection to your equipment.
>100%
76100%
5175%
2650%
025%
Figure 16. Load Level Indicators
When all of the bar graph indicators and the indicator are illuminated,
power requirements exceed UPS capacity; see page 56 for more
information.
Buck and Double Boost Mode
With the Buck and Double Boost feature, the UPS accepts a wide input
voltage range (-30/+20% of nominal) and provides consistent, clean
voltage to your equipment. The UPS operates normally from utility
power and alerts you of the voltage fluctuations. The indicator
alternates between green and red while in Buck, Single Boost, or Double
Boost mode as shown in Figure 17.
Buck Mode
Single Boost Mode
Double Boost Mode
Figure 17. Buck and Double Boost Indicators
OPERATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 33
Battery Mode
When the UPS is operating during a power outage, the alarm beeps
once every four seconds and the
+ -
indicator illuminates.
When utility power returns, the UPS transfers to Normal mode operation
while the battery recharges.
If battery capacity becomes low while in Battery mode, the indicator
flashes and the alarm beeps twice every two seconds. Immediately
complete and save your work to prevent data loss and similar difficulties.
When utility power is restored after the UPS shuts down, the UPS
automatically restarts.
Standby Mode
When the UPS is turned off and remains plugged into a power outlet,
the UPS is in Standby mode. The indicator flashes and the bar graph
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE For 230V models, the output receptacles may remain electrically live (up to 115V).
Unplug the UPS to ensure power is not available to the output receptacles.
OPERATION
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 34
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 35
Chapter 5 Additional UPS Features
This section describes:
S X-Slot cards
S Network transient protector
S Load segments
X-Slot Cards
X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The Eaton 5125 is
factory-installed with a Single-Port Card, which can be replaced with one
of the following X-Slot cards:
S ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities
as well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in
switching hub that allows three additional network devices to be
connected to the network without the requirement of additional
network drops. In addition, a Environmental Monitoring Probe can be
attached to obtain humidity, temperature, smoke alarm, and security
information.
S Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
S Modbus

Card - allows you to continuously and reliably monitor the


UPSs in your Building Management System (BMS).
S Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using LanSafe

Power Management Software (provided on the Software Suite CD).


S USB Card - connects to a USB port on your computer.
t
ADDITIONAL UPS FEATURES
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 36
Multi-Server Card
Relay Interface Card
USB Card
Modbus Card
ConnectUPS-X Web/SNMP Card
X-Slot Communication Bay
(Single-Port Card shown)
Figure 18. Optional X-Slot Cards
Single-Port Card
The Eaton 5125 is factory-installed with a Single-Port Card, enabling
connection to a PC for power management control or to the Expansion
Chassis for multiple communication options.
To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS
for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data
and an orderly shutdown of the equipment.
The cable pins are identified in Figure 19 and the pin functions are
described in Table 1.
3
8 7 9
1
6
2 4 5
Figure 19. Communication Port
ADDITIONAL UPS FEATURES
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 37
Table 1. Communication Port Pin Assignment
Pin Number Signal Name Function Direction from the UPS
1 Low Batt Low Battery relay contact; 20 mA, 30 Vdc contact rating Out
2 TxD Transmit to external device Out
3 RxD Receive from external device In
4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In
5 GND Signal common (tied to chassis)
6 DSR To external device (tied to Pin 4) Out
7 RTS PnP from external device In / Out
8 AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Out
9 Power Source +V (8 to 24 volts DC power) Out
ADDITIONAL UPS FEATURES
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 38
Network Transient Protector
The network transient protector, shown in Figure 20, is located on the
rear panel and has jacks labeled IN and OUT. This feature
accommodates a single RJ45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ11 telephone
connector that provides protection for modems, fax machines, or other
telecommunications equipment. As with most modem equipment, it is
not advisable to use this jack in digital PBX (Private Branch Exchange)
environments.
NOTE DO NOT connect any telephone or fax/modem equipment (RJ-11) to the 230V
models; only connect network cables (RJ-45) to the 230V models.
1. Connect the input connector of the equipment you are protecting to
the jack labeled IN.
2. Connect the network or telephone (low voltage models only) cable
to the jack labeled OUT.
OUT
IN
Figure 20. Network Transient Protector
ADDITIONAL UPS FEATURES
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 39
Load Segments
Load segments are sets of receptacles that can be controlled by power
management software, providing an orderly shutdown and startup of
your equipment. For example, during a power outage, you can keep key
pieces of equipment running while you turn off other equipment. This
feature allows you to save battery power. See your power management
software manual for details (refer to the Software Suite CD or
www.eaton.com/powerquality for the latest information).
NOTE If power management software is not used, the individual load segments cannot be
controlled.
Each UPS has two or three load segments as shown in Figure 21 and
Figure 22.
Load Segment 1
Load Segment 2
230V Models
Load Segment 1
Load Segment 2
100V/120V Models
Figure 21. 1000 VA and 1500 VA Load Segments
Load Segment 1
Load Segment 2
Load Segment 3
Load Segment 1
Load Segment 2
Load Segment 3
100V/120V Models 208V/230V Models
Figure 22. 2200 VA Load Segments
ADDITIONAL UPS FEATURES
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 40
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 41
Chapter 6 UPS Maintenance
This section explains how to:
S Care for the UPS and batteries
S Transport the UPS
S Store the UPS and batteries
S Replace the batteries
S Test new batteries
S Recycle used batteries or UPS
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dustfree. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25C (77F).
NOTE The batteries in the UPS are rated for a 35 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
Transporting the UPS
NOTE The internal UPS batteries MUST be disconnected.
If the UPS requires any type of transportation:
1. Verify that the UPS is unplugged and turned off.
2. Disconnect the UPS internal battery connector using the steps in
Connecting the UPS Internal Battery on page 20 in reverse order.
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 42
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every
6 months by plugging the UPS into a power outlet. The batteries charge
to 90% capacity in approximately 3 hours. However, it is recommended
that the batteries charge for 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has passed and the batteries were never recharged, do not use the UPS.
Contact your service representative.
When to Replace Batteries
When the indicator flashes and there is a continuous audible alarm,
the batteries may need replacing. Conduct a selftest by pressing and
holding the button for three seconds. If the indicator stays on,
contact your service representative to order new batteries.
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hotswappable battery feature, UPS batteries can be replaced
easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries, see
Turning the UPS Off on page 30.
Consider all warnings, cautions, and notes before replacing batteries.
W A R N I N G
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 43
How to Replace Internal Batteries
C A U T I O N
Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it
out of the UPS.
To replace the UPS internal batteries:
1. Remove the UPS front cover (see Figure 23).
Figure 23. Removing the UPS Front Cover
2. Slide up and remove the metal battery cover (see Figure 24).
1000 VA 1500 VA 2200 VA
Figure 24. Removing the Battery Cover
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 44
3. 1000 VA models. Disconnect the red battery cable on the front of
the battery (see Figure 25). Pull the battery out onto a flat, stable
surface.
Disconnect the black battery cable on the rear of the battery, then
on the front of the battery. Disconnect the red battery cable on the
rear of the battery.
See Recycling the Used Battery or UPS on page 47 for proper
disposal.
Black Battery Cable
Red Battery Cable
Figure 25. Battery Removal (1000 VA Models)
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 45
4. 1500 and 2200 VA models. Pull the battery out onto a flat, stable
surface (see Figure 26). Press on the black tab on the battery cable
connector to disconnect the battery.
See Recycling the Used Battery or UPS on page 47 for proper
disposal.
Figure 26. Battery Removal (1500 and 2200 VA Models)
5. Install the new batteries in the reverse order of removal.
6. Replace the metal battery cover.
7. Replace the UPS front cover.
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 46
How to Replace Extended Battery Modules
To replace the Extended Battery Modules (EBMs):
1. Unplug the EBM cable from the UPS.
If additional EBMs are installed, unplug the EBM cable from the
battery connector on each EBM.
2. Replace the EBM. See Recycling the Used Battery or UPS on
page 47 for proper disposal.
3. Plug the new EBM into the UPS as shown in Figure 27.
For additional EBMs, plug the EBM cable into the battery connector
on the adjacent EBM.
EBM
Battery
Connector
UPS Battery
Connector
EBM
Cable
Figure 27. EBM Connections (120V Model Shown)
Testing New Batteries
Press and hold the button for three seconds to initiate a selftest.
After the test is finished, the indicator should turn off. If the
indicator stays on, check the battery connections. Call your service
representative if the problem persists.
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 47
Recycling the Used Battery or UPS
Contact your local recycling or hazardous waste center for information
on proper disposal of the used battery or UPS.
W A R N I N G
S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
C A U T I O N
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
leadacid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.
C A U T I O N
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.
UPS MAINTENANCE
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 48
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 49
Chapter 7 Specifications
This section provides the following specifications:
S Model list
S Dimensions and weights
S Electrical input and output
S Environmental and safety
S Battery
Table 2. Model Specifications
Model Number
Power Levels
(Rated at Nominal Inputs)
Nominal Voltage Input Voltage Range
PW5125 1000 1000 VA, 700W 120V
77152V (-30/+20%)
PW5125 1500 1440 VA, 1050W 120V
PW5125 2200 1920 VA, 1600W 120V
PW5125 2200b 2080 VA, 1600W 208V 164250V (20%)
PW5125 1000i 1000 VA, 700W 230V
154288V (-30/+20%)
PW5125 1500i 1500 VA, 1050W 230V
PW5125 2200i 2200 VA, 1600W 230V
PW5125 1000j 1000 VA, 700W 100V
82120V (20%)
PW5125 1500j 1500 VA, 1050W 100V
PW5125 2200j 2200 VA, 1600W 100V
Table 3. Dimensions and Weights
Dimensions (WxDxH) Weight
1000 VA Models 16.240.124.0 cm (6.3815.799.45) 15 kg (34 lb)
1500 VA Models 16.246.725.0 cm (6.3818.399.84) 23 kg (50 lb)
2200 VA Models 20.549.325.0 cm (8.0719.419.84) 31 kg (68 lb)
Extended Battery Module
(EBM)
16.247.425.0 cm (6.3818.669.84) 27 kg (60 lb)
SPECIFICATIONS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 50
Table 4. Power Connections
Input Connection Output Receptacles
PW5125 1000 6-ft, 5-15P power cord (6) 5-15R
PW5125 1500 6-ft, 5-15P power cord (6) 5-15R
PW5125 2200 6-ft, 5-20P power cord (6) 5-15R (2) 5-20R
PW5125 2200b 15A, IEC-320 input connector (9) 10A, IEC 320-C13
PW5125 1000i 10A, IEC-320 input connector (6) 10A, IEC 320-C13
PW5125 1500i 10A, IEC-320 input connector (6) 10A, IEC 320-C13
PW5125 2200i 10A, IEC-320 input connector (9) 10A, IEC 320-C13
PW5125 1000j 6-ft, 5-15P power cord (6) 5-15R
PW5125 1500j 6-ft, 5-20P power cord (6) 5-15R
PW5125 2200j 6-ft, L5-30P power cord (6) 5-15R (2) 5-20R
Table 5. Technical Specifications
Operating Frequency 50/60 Hz, auto-sensing
Frequency Range 4665 Hz
Noise Filtering MOVs and line filter for normal and common mode noise
Regulation
(Normal Mode)
-10% to +6% of nominal voltage
Regulation
(Battery Mode)
Nominal output voltage 5%
Voltage Waveform Sine wave
SPECIFICATIONS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 51
Table 6. Environmental and Safety
Low Voltage Models High Voltage Models
Operating Temperature 10C to 40C (50F to 104F)
Optimal battery performance: 25C (77F)
Storage Temperature 0C to 25C (32F to 77F)
Transit Temperature -25C to 55C (-13F to 131F)
Relative Humidity 595% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 15,000 meters above sea level
Audible Noise Less than 40 dBA Normal mode, typical load
Less than 55 dBA Battery mode
Surge Suppression ANSI C62.41 Category B, IEC 61000-4-5
Safety Conformance UL 1778 4th Edition, UL 497A;
CSA C22.2, No. 107.3;
NOM-019-SCFI
UL 1778 4th Edition, UL 497A (data line only);
CSA C22.2, No. 107.3;
IEC/EN 62040-1-1 and IEC/EN 60950
Agency Markings cULus, cUL, NOM cULus and cUL; CE, C-Tick, LGA/GS, UL-GS
EMC (Class A) FCC Part 15, ICES-003, VCCI IEC/EN 62040-2, FCC Part 15, ICES-003
Table 7. Battery
UPS Configuration 1000 VA: (2) 24V, 9 Ah internal batteries
1500 VA: (4) 48V, 7 Ah internal batteries
2200 VA: (4) 48V, 12 Ah internal batteries
EBM Configuration PW5125 EBM-24: (8) 24V, 9 Ah batteries
PW5125 EBM-48: (8) 48V, 9 Ah batteries
Type Sealed, maintenancefree, valveregulated, leadacid
Charging Internal battery: approximately 3 hours to 90% usable capacity
at nominal line voltage after full load discharge
External battery: recharging at 80% load or less is recommended;
no more than 16x discharge time to 90% usable capacity at nominal line voltage after full
load discharge; an external battery charger is recommended for faster recharge times
when using more than two EBMs.
Monitoring Advanced monitoring for earlier failure detection and warning;
auto detection of additional EBMs
SPECIFICATIONS
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 52
Table 8. Battery Runtimes (in Minutes at Full/Half Load)
Model UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1000 VA 5/14 25/60 55/170 83/199 109/228
1500 VA 6/17 33/79 63/146 92/174 120/201
2200 VA 5/14 26/60 55/170 81/198 106/224
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 53
Chapter 8 Troubleshooting
This section explains:
S UPS alarms and conditions
S How to silence an alarm
S Service and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power
problems. Use Table 9 to determine and resolve the UPS alarms and
conditions.
Red
Flashing
Unlit
Green
Indicator Legend
On Button
Off Button
Test/Alarm Reset Button
Battery Service
Site Wiring Fault
On Battery
General Alarm
Power On
Figure 28. Alarm Indicators
TROUBLESHOOTING
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 54
Silencing an Audible Alarm
Before silencing an alarm, check the alarm condition and perform the
applicable action to resolve the condition (see Table 9).
To silence the alarm for an existing fault, press the button. If UPS
status changes, the alarm beeps, overriding the previous alarm silencing.
The alarm does not silence if there is a low battery condition.
Table 9. Troubleshooting Guide
Alarm or Condition Possible Cause Action
The indicator is not on;
the UPS does not start.
The UPS internal battery is not
connected.
See Connecting the UPS Internal Battery on
page 20.
The power cord is not connected
correctly.
Check the power cord connections.
The wall outlet is faulty. Have a qualified electrician test and repair
the outlet.
The indicator is flashing;
power is not available at the UPS
output receptacles.
The UPS is in Standby mode. Press the On | button to supply power to the
connected equipment.
The UPS operates normally, but
some or all of the protected
equipment is not on.
The equipment is not connected
to the UPS correctly.
Verify that the equipment is plugged into the
UPS receptacles.
For hardwired models, contact a qualified
electrician to check connections to the power
source.
One of the load segments has
been turned off through the
power management software.
Reactivate the segment with the software.
The UPS does not provide the
expected backup time.
The batteries need charging or
service.
Plug the UPS into a power outlet for 24 hours
to charge the battery. Press and hold the
button for 3 seconds.
If the indicator is still on, see Replacing
Batteries on page 42.
TROUBLESHOOTING
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 55
Table 9. Troubleshooting Guide (continued)
Action Possible Cause Alarm or Condition
1 beep every 4 seconds. The UPS is on battery (see
Battery Mode on page 33 for
more information).
The UPS is powering the equipment with
battery power. Prepare your equipment for
shutdown. During an extended power outage,
save your work and turn off your equipment to
conserve battery power.
2 beeps every 2 seconds.
The battery is running low. Three minutes or less of battery power
remains (depending on load configuration and
battery charge).
Save your work and turn off your equipment.
The alarm cannot be silenced.
The UPS is running on battery
power because the input voltage
is too high or too low.
Correct the input voltage, if possible. The UPS
continues to operate on battery until the
condition is corrected or the battery is
completely discharged.
If the condition persists, the input voltage in
your area may differ from the UPS nominal.
The utility line voltage and
frequency are out of
specification.
Have a qualified electrician check the wiring.
1 beep every 5 seconds.
The batteries may be fully
discharged.
Plug the UPS into a power outlet for 24 hours
to charge the battery. Press and hold the
button for 3 seconds.
If the indicator is still on, see Replacing
Batteries on page 42.
The battery is not connected
correctly.
Check the b attery connections. Call your
service representative if the problem persists.
TROUBLESHOOTING
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 56
Table 9. Troubleshooting Guide (continued)
Action Possible Cause Alarm or Condition
The self-test failed. Plug the UPS into a power outlet for at least
3 hours to charge the battery. Press and hold
the button for 3 seconds.
If the indicator is still on, shut down the
UPS and contact your service representative.
The UPS internal temperature is
too high.
Shutdown is imminent (10 seconds). Save
your work immediately and turn off your
equipment. Turn off the UPS.
Clear vents and remove any heat sources.
Ensure the airflow around the UPS is not
restricted. Wait at least 5 minutes and restart
the UPS. If the condition persists, contact
your service representative.
Ground wire connection does not
exist or the line and neutral wires
are reversed in the wall outlet.
Have a qualified electrician correct the
wiring.
Power requirements exceed UPS
capacity (101110% for 3 minutes
or 111150% for 10 cycles) or the
load is defective.
Turn off and unplug the UPS. Remove some of
the equipment from the UPS. Wait at least
5 seconds until all LEDs are off and restart the
UPS. You may need to obtain a larger
capacity UPS.
UPS fault condition. Save your work and turn off your equipment.
Turn off and unplug the UPS. Contact your
service representative. The alarm cannot be
silenced.
TROUBLESHOOTING
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 57
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
United States: 1-800-356-5737
Canada: 1-800-461-9166 ext 260
All other countries: Call your local service representative
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the package
and on the Bill Of Lading (if applicable). Use the original packaging or
request packaging from the Help Desk or distributor. Units damaged in
shipment as a result of improper packaging are not covered under
warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
Desk for the dealer or distributor nearest you.
TROUBLESHOOTING
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 58
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 59
Chapter 9 Warranty
Two-Year Limited Warranty with Extension to Three-Year Limited
Warranty (US and Canada)
Eaton UPS Models: 3105, 5110, 5115, 5125, and 5130
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, an Ohio Corporation
company (Company).
LIMITED WARRANTY: This limited warranty (this Warranty) applies only to the original End-User (the End-User)
of any Eaton 3105, 5110, 5115, 5125, and 5130 Products (individually and collectively, the Product) purchased on
or after August 19, 2009 and cannot be transferred. This Warranty applies even in the event that the Product is
initially sold by Company for resale to an End-User.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in
the fifty (50) United States, the District of Columbia, and Canada is twenty-four (24) months from the date of
purchase, or thirty (30) months from the date of shipment. For units which are registered online at
www.eaton.com/PQ/Register, the warranty is extended to thirty-six (36) months from the date of purchase, or
forty-two (42) months from the date of shipment.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and
collectively, the Warranted Items) are free from defects in material and workmanship. If, in the opinion of
Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company's sole
obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor,
as applicable), at the option of Company.
PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS: The Warranted Item will be repaired or
replaced at a Company site or such other location as determined by Company.
If the Warranted Item is to be replaced by Company, and the End-User supplies a credit card number or purchase
order for the value of the replacement Product, Company will use commercially reasonable business efforts to ship
(via standard ground shipment and at no cost to the End-User) the replacement Warranted Item to the End-User
within one (1) business day after Company receives notice of the warranty claim. In such case, the End-User must
return (at Company's expense) the defective Warranted Item to Company in the same packaging as the
replacement Warranted Item received by the End-User or as otherwise instructed by Company. If Company does
not receive the defective Warranted Item, Company will either charge the End-User's credit card, or send the
End-User an invoice (which the End-User agrees to pay), for the value of the replacement Product.
If the Warranted Item is to be replaced by Company, but the End-User is unwilling or unable to supply a credit card
number or purchase order for the value of the replacement Product, Company will use commercially reasonable
business efforts to ship (via standard ground shipment and at no cost to the End-User) the replacement Warranted
Item to the End-User within one (1) business day after Company receives the defective Product from the End-User.
In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for
return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are
replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by
Company shall become the property of Company.
WARRANTY
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 60
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product
under other than normal operating conditions or in a manner inconsistent with the Product's labels or instructions.
This Warranty is not valid if the Product's serial numbers have been removed or are illegible. Any Warranted Items
repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty
subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal, or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER'S WARRANTIES TO
END-USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN OPEN SOURCE MODEL OR IS DISTRIBUTED
PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,
NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY'S SOLE
LIABILITY AND END-USER'S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY
OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABILITY: The remedies of the End-User set forth herein are exclusive and are the sole remedies
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of
customers of the End-User, or any special, indirect, incidental, or consequential damages whatsoever. The total
cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort
(including negligence or strict liability), or otherwise, shall not exceed the price of the Product on which such liability
is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company's
reasonable control.
END-USER'S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Product
in a normal way; follow the Product's user's guide; and protect against further damage to the Product if there is a
covered defect.
OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any
overdue or unpaid amounts.
WARRANTY
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 61
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses, or labor of Company representatives outside the terms of this Warranty will be
borne by the End-User.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside
of the USA, call your local Eaton product sales or service representative. For comments or questions about this
Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616
USA.
Load Protection Guarantee (US and Canada)
Eaton UPS Models 3105, 5110, 5115, 5125, and 5130
GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Corporation, an Ohio
Corporation company (Company).
LIMITED GUARANTY: This load protection guaranty (this Guaranty) applies only to the original End-User (the
End-User) of any Eaton 3105, 5110, 5115, 5125, and 5130 Products (individually and collectively, the Product)
and cannot be transferred. This Guaranty applies even in the event that the Product is initially sold by Company for
resale to an End-User.
WHAT THIS GUARANTY COVERS: For the lifetime of the Product, Guarantor promises to repair or replace, at
Guarantor's option, the equipment (valued up to the limits shown below*) that is damaged by an AC power line
surge, spike, or other transient when properly connected to Guarantor's uninterruptible power system (UPS).
Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following
circumstances arise:
1. The UPS is plugged into properly grounded and wired outlets, using no extension cords, adapters, other ground
wires, or other electrical connectors;
2. The installation of the UPS complies with all applicable electrical and safety codes described by the National
Electrical Code

(NEC

);
3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and
4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.
*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:
S $25,000 for Eaton UPS Model 3105
S $150,000 for Eaton UPS Models 5110, 5115, 5125, and 5130
WARRANTY
Eaton 5125 Tower UPS (10002200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality 62
WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User's equipment does not
include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the
Product's labels or instructions.
This Guaranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card or
completes the registration form on www.eaton.com/PQ/Register within thirty (30) days of purchase; or (b) if the
Product's serial numbers have been removed or are illegible.
Company shall not be responsible for any charges for testing, checking, removal, or installation of any items.
LIMITATION OF LIABILITY: THE REMEDIES OF THE END-USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE
THE SOLE REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER.
EXCEPT AS OTHERWISE PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN
CONTRACT, IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE FOR DAMAGE TO
PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE,
LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF CAPITAL, CLAIMS OF CUSTOMERS OF THE END-USER
OR ANY SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES WHATSOEVER. THE TOTAL
CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT
(INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE, SHALL
NOT EXCEED THOSE SET FORTH ABOVE.
Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes
beyond Company's reasonable control.
END-USER'S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End-User must use the Product
in a normal way; follow the Product's user's guide; and protect against further damage to the Product if there is a
covered defect.
OTHER LIMITATIONS: Company's obligations under this Guaranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Guaranty.
COSTS NOT RELATED TO GUARANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses, or labor of Company representatives outside the terms of this Guaranty will be
borne by the End-User.
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA,
contact your local Eaton product sales or service representative. For comments or questions about this Load
Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North
Carolina 27616 USA.