Beruflich Dokumente
Kultur Dokumente
6xxx
5xxx
4xxx
3xxx
2xxx
1xxx
SA
FE T Y I
EGRITY NT
VE L LE
These units are in conformity with the provisions of: 1. The EMC Directive: 2004/108/EC. 0038 The units have been tested to 0344 EN 61326:1997 + A1 + A2. 2. Directive 94/9/EC for Equipment or protective system for use in potentially explosive atmospheres. EC-type examination certicate number ISSeP08ATEX021X (intrinsic safe units) or ISSeP08ATEX019 (EEx d units). The following harmonized standards have been applied: EN 60079-0:2006 / EN 60079-11:2007 / EN 6007926:2004 / EN 60079-27:2006 3. The PED directive 97/23/EC (pressure equipment directive). Safety accessories per category IV module H1. TOP MOUNTED UNITS After unpacking, inspect all components to see that no damage has occurred during shipment. Care should be taken not to bend the displacer stem or enclosing tube during unpacking or installation.
Unpack the instrument carefully. Make sure all components have been removed from the foam protection. Inspect all components for damage. Report any concealed damage to the carrier within 24 hours. Check the contents of the carton/crates against the packing slip and report any discrepancies to Magnetrol. Check the nameplate model number (Model number/approvals as per inserted separate sheet) to be sure it agrees with the packing slip and purchase order. Check and record the serial number for future reference when ordering parts.
UNPACKING
CHAMBERED UNITS A strap and wire assembly retains and protects the displacer within the chamber during shipment. This assembly must be removed through bottom chamber connection before startup. Inspect instrument as described for top mounting units. Caution: If re-shipping to another location, displacer must again be secured using same strap and wire assembly.
DENSITY Yet another capability of E3 Modulevel is to track the changing density of a liquid over a known density range and convert that into a stable output signal. As the density of the liquid changes, so does the mass of the liquid displaced by the specially designed displacer. The resulting change in buoyancy force on the displacer causes the movement of the LVDT core necessary to convert the density change to the output signal.
2
INTERFACE E3 Modulevel is capable of tracking the interface level of two immiscible liquids with different densities. Each unit is custom-made with a displacer specially designed for the users application. This allows it to detect the position of a clean interface or an emulsion layer and convert it into a stable output signal. Contact the factory for assistance in specifying an E3 for interface service. Note that for proper interface detection, the entire displacer must always be immersed in liquid.
LEVEL Liquid level change acts upon the range spring supported displacer causing vertical motion of a core within a linear variable differential transformer (LVDT). The enclosing tube acts as a static isolation barrier between the LVDT and the process media. As core position changes with liquid level, voltages are induced in the secondary windings of the LVDT. These signals are processed in the electronic circuitry and used to control the output signal.
PRINCIPLE OF OPERATION
Moving LVDT Core Electronics incl. digital display / 3 button key pad Enclosing tube Range spring
LVDT
External cage
MOUNTING
calibration vent is recommended Liquid level Shut-off valves are recommended Size 1/8" max 1 tolerance Always unlock for repositioning or removal of head assembly and always relock, after nal positioning
max 360
Transmitter
Slide the amplier over the enclosing tube. Make sure not to bend the enclosing tube. Bending causes permanent damage.
Enclosing tube
WIRING
CAUTION: power must be switched OFF before wiring the unit. Current loop test point
IS
Positive supply to (+) terminal/HART connection Negative supply to (-) terminal/HART connection min. 11 V DC required max 36 V DC
IS
Shield wire to green grounding screw (resistance to ground must be < 1 ). Use certied ameproof cable gland(s) and cable for Explosion proof area. Standard shielded twisted pair cable recommended.
0%
100 %
Ex
Non Ex
Ex
Galvanic Barrier: ATEX Intrinsically safe units: max 28,4 V DC @ 94 mA FM Intrinsically safe units: max 28,6 V DC @ 140 mA Not needed for General Purpose / explosion proof models. ANALOG I/O or DIGITAL I/O (only for units with HART)
Non Ex
Ex
Non Ex
IMPORTANT: The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the eld (at the transmitter side - as shown above) but connecting in the control room is also allowed. LOOP RESISTANCE
1200
1000
20.5 mA
400
200 0
24 VDC
11
10
20
30
40 VDC
NOTE: When connected to an approved barrier, the intrinsically safe electronics of the E3 Modulevel allow to remove the covers with power switched on even if the area is known to be hazardous
CONFIGURATION
2 line 8 characters LCD Default display cycles every 5 s through Status STATUS / Level LEVEL / % output % OUTPUT / Loop LOOP.
IMPORTANT: The E3 Modulevel amplier can be bench congured without displacer attached. Ignore the start up message No Level Signal / STATUS SecFltHi in this case.
Display
Comment
Press Press Press :
* Scroll through the choices or increase/decrease the values on the second line of the display by and pushbuttons. pushbutton. * Accept values/choices as selected by Scroll through the menu.
The last character on the rst line of the display changes to !. This sign conrms that the values/choices of the second line can be modied via the and push buttons.
PASSWORD
DISPLAY
ACTION
Display shows 0 Press and last character changes into ! Enter your personal password with and (any value between 1 and 255) Press to conrm
COMMENT
Factory default setting Data is not protected Setting password Changing password
Press and enter old password Press and last character changes into ! Enter your new password with and (any value between 1 and 255) Press to conrm
NOTE: Password protection is activated when after 5 minutes no keystrokes are sensed.
Display shows an encrypted value, enter your password or call Magnetrol for assistance to recoop your password if necessary
NOTE: For exchanging a new head or re-calibration of a unit with new spare parts, follow the User calibration procedure (see page 15).
IMPORTANT: Units are pre-calibrated at the factory with 4mA at the bottom of the displacer (free hanging position) and 20mA at the top of the displacer. If these settings match with the required settings, only enter - density @ operating temperature Proc SG and - operating temperature OperTemp. Wet calibration is recommended in case the correct 4-20 mA levels can be simulated. In this case, do not use the screens set 4mA and Set 20mA but proceed with the screens Capture 4mA and Capture 20mA
Screen
1
*Status* *Level* *%Output* *Loop*
Action
Comment
Run mode
Transmitter default values cycle every 5 seconds. Status Status, Level Level, % Output % Output, and Loop Loop. Transmitter displays level value in selected engineering units.
2 3 4 5
Level xx.x %Output xx.x% Loop xx.xx mA LvlUnits (select) Proc SG x.xxx sg OperTemp xxx C Set 4mA xxx.x Set 20mA xxx.x Lvl Ofst xxx.x
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA span. Transmitter displays Loop measurement (mA). cm cm, m m, inches inches or feet feet. Adjusts factory calibration for actual specic gravity. Adjusts factory calibration for actual temperature.
6 7
Conguration
8 9 10 11 12
Enter the process operating temperature. Enter the level value for the 4 mA point.
Distance in cm or inches from typically the end of the displacer up to the 4mA (0%) level. If an offset value is used refer to the drawing at the right page. Distance in cm or inches from typically the end of the displacer up to the 20mA (100%) level. If an offset value is used refer to the drawing at the right page.
When entering conguration values from the end of the displacer is cumbersome, an offset can be introduced to determine a new reference point. This reference point can be either below the displacer (positive offset) or at the displacer (negative offset).
Select 3.6 mA, 22 mA or hold last value HOLD. In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high. A Damping factor (1-45 seconds) may be added to smooth a noisy display and/or output due to turbulence.
Action
Poll Adr xx Trim Lvl xx.x Trim 4 xxxx Trim 20 xxxx Loop Tst xx.x mA Capture 4.00 mA
Comment
Select a HART poll address (0-15). Enter 0 for a single transmitter installation. Allows to compensate for a xed level deviation.
15 16 17 18
Attach a mA meter to the output. If the output does not equal 4.0 mA, adjust the value on the display to equal 4.00 mA. Attach a mA meter to the output. If the output does not equal 20.0 mA, adjust the value on the display to equal 20.00 mA. Set mA Output to any given value to perform loop test.
Conguration
19
Bring liquid level at desired 4 mA point. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 4 mA level.
Manual setting of 4 mA output signal: free hanging displacer or level at the lowest level. Level is ideally brought to match with 20 mA point. If this is not possible, bring level to the highest possible position (should correspond with min 8 mA). Attach a mA meter and adjust the loop current via the keypad (down & up arrows) to match with the calculated mA value of the current level.
Capture 20.00 mA
21 22
20
Note: in case of full span cannot be reached, adjust loop readout to current level (see at right).
Bring liquid level at highest possible point. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 20 mA level.
Use arrows to select desired value. Values between 0 and 255. Select English, Franais, Deutsch or Espagnol. Factory setting. Ver refers to software version. See page 15.
23
Advanced diagnostics.
OFFSET
100 % 75 cm 15 cm
20 mA = 75 cm
20 mA = 85 cm
20 mA = 60 cm
0%
4 mA = 15 cm
4 mA = 25 cm
4 mA = 0 cm
10 cm
NOTE: For exchanging a new head or re-calibration of a unit with new spare parts, follow the User calibration procedure (see page 15).
IMPORTANT: Units are pre-calibrated at the factory with 4mA at the bottom of the displacer (free hanging position) and 20mA at the top of the displacer. If these settings match with the required settings, only enter operating temperature OperTemp. The displacer is specically designed for the application and does not require any density setting. Wet calibration is recommended in case the correct 4-20 mA levels can be simulated. In this case, do not use the screens set 4mA and Set 20mA but proceed with the screens Capture 4mA and Capture 20mA. Correct output assumes that the displacer is at all times fully immerged in the liquid level (min. 50 mm (2")). See page 12 for proper guidelines.
Screen
1
*Status* *IfcLevel* *%Output* *Loop*
Action
Comment
Run mode
2 3 4 5
Transmitter default values cycle every 5 seconds. Status Status, Interface level IfcLevel, % Output % Output, and Loop Loop. Transmitter displays interface level in selected engineering units. Transmitter displays % Output measurement derived from 20 mA span. Transmitter displays Loop measurement (mA). cm cm, m m, inches inches or feet feet. Adjusts factory calibration for actual temperature.
IfcLevel xx.x %Output xx.x% Loop xx.xx mA LvlUnits (select) OperTemp xxx C Set 4mA xxx.x
Enter the process operating temperature. Enter the level value for the 4 mA point.
Conguration
8 9 10 11
Distance in cm or inches from typically the end of the displacer up to the 4mA (0%) level. If an offset value is used refer to the drawing at the right page. When entering conguration values from the end of the displacer is cumbersome, an offset can be introduced to determine a new reference point. This reference point can be either below the displacer (positive offset) or at the displacer (negative offset).
Select 3.6 mA, 22 mA or hold last value HOLD. In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high. A Damping factor (1-45 seconds) may be added to smooth a noisy display and/or output due to turbulence.
Distance in cm or inches from typically the end of the displacer up to the 20mA (100%) level. If an offset value is used refer to the drawing at the right page.
Action
Poll Adr xx Trim Lvl xx.x Trim 4 xxxx Trim 20 xxxx Loop Tst xx.x mA Capture 4.00 mA
Comment
Select a HART poll address (0-15). Enter 0 for a single transmitter installation. Allows to compensate for a xed level deviation.
14 15 16 17
Attach a mA meter to the output. If the output does not equal 4.0 mA, adjust the value on the display to equal 4.00 mA. Attach a mA meter to the output. If the output does not equal 20.0 mA, adjust the value on the display to equal 20.00 mA. Set mA Output to any given value to perform loop test.
Conguration
18
Bring interface level at desired 4 mA point, make sure that the displacer remains fully immerged in the upper liquid layer. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 4 mA interface level.
Capture 20.00 mA
Bring interface level at highest possible point, make sure that the displacer remains fully immerged in the upper liquid layer. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 20 mA interfacelevel. Note: in case of full span cannot be reached, adjust loop readout to current level (see at right). Enter new password. Select language.
Interface level is ideally brought to the level that matches with 20 mA point. If this is not possible, bring the interface level to the highest possible position (should correspond with min 8 mA). Attach a mA meter and adjust the loop current via the keypad (down & up arrows) to match with the calculated mA value of the current interface level.
20 21
19
Use arrows to select desired value. Values between 0 and 255. Select English, Franais, Deutsch or Espagnol. Factory setting. Ver refers to software version. See page 15.
22
Advanced diagnostics.
OFFSET
100 % 75 cm 15 cm
20 mA = 75 cm
20 mA = 85 cm
20 mA = 60 cm
0%
4 mA = 15 cm
4 mA = 25 cm
4 mA = 0 cm
10 cm
IMPORTANT: Units are pre-calibrated at the factory with 4mA at the bottom of the displacer (free hanging position) and 20mA at the top of the displacer. If these settings match with the required settings, only enter operating temperature OperTemp. The displacer is specically designed for the application and does not require any density setting. Wet calibration is recommended in case the correct 4-20 mA levels can be simulated. In this case, do not use the screens set 4mA and Set 20mA but proceed with the screens Capture 4mA and Capture 20mA. Correct output assumes no shift in level and the displacer at all times fully immerged in the liquid level (min. 50 mm (2")). See page 12 for proper guidelines.
NOTE: For exchanging a new head or re-calibration of a unit with new spare parts, follow the User calibration procedure (see page 15).
Screen
1
*Status* *SG* *%Output* *Loop*
Action
Comment
Run mode
2 3 4 5
SpecGrav x.xx sg %Output xx.x% Loop xx.xx mA OperTemp xxx C Set 4mA xxx.x Set 20mA xxx.x Damping xx sec Fault (Select)
Transmitter displays Interface volume or interface level in selected engineering units (depending selection in Loop control Loop Ctrl Transmitter displays % Output measurement derived from 20 mA span. Transmitter displays Loop measurement (mA). Adjusts factory calibration for actual temperature.
Transmitter default values cycle every 5 seconds. Status Status, Density SG, % Output % Output, and Loop Loop.
Conguration
Enter the process operating temperature. Enter the level value for the 4 mA point.
Transmitter Display
7 8 9
Select 3.6 mA, 22 mA or hold last value HOLD. In case of loop failure, error signal will follow the failing trend; meaning the unit will show 3.6 mA when the reviewed loop current by the device is found too low. The unit will show 22 mA in case the reviewed loop current is found too high.
10
Action
Poll Adr xx Trim SG xx.x Trim 4 xxxx Trim 20 xxxx Loop Tst xx.x mA Capture 4.00 mA
Comment
12 13 14 15
Enter SG value to adjust SG value reading. Fine tune the 4 mA point. (Trim 0-20) Enter a mA output value.
Select a HART poll address (0-15). Enter 0 for a single transmitter installation. Allows to compensate for a xed deviation.
Fine tune the 20 mA point. (Trim 4-4095) The immerged displacer is fully immerged in liquid at the min. S.G. value = 4 mA point. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 4 mA value.
Attach a mA meter to the output. If the output does not equal 4.0 mA, adjust the value on the display to equal 4.00 mA. Attach a mA meter to the output. If the output does not equal 20.0 mA, adjust the value on the display to equal 20.00 mA. Set mA Output to any given value to perform loop test.
Manual setting of 4 mA output signal. Displacer immerged in liquid with the min. S.G.
Conguration
16
Capture 20.00 mA
The immerged displacer is fully immerged in liquid at the max. S.G. value = 20 mA point. Press Enter to enter manual setting mode. Press up arrow + Enter (simultaneously) to conrm 20 mA value.
Liquid S.G. is ideally brought to match with 20 mA point. If this is not possible, bring S.G. to the highest possible value (should correspond with min 8 mA). Attach a mA meter and adjust the loop current via the keypad (down & up arrows) to match with the calculated mA value of the current S.G.
18 19
17
Note: in case the max. S.G. cannot be reached, adjust loop readout to current S.G. (see at right). Enter new password. Select language.
Use arrows to select desired value. Values between 0 and 255. Select English, Franais, Deutsch or Espagnol. Factory setting. Ver refers to software version. See page 15.
20
Advanced diagnostics.
min 50 mm (2")
Highest SG = 20 mA
lowest SG = 4 mA
11
Calibrate 4 mA/0 % level Bring level lower than displacer (free hanging) or to the lowest level. Press Enter = start calibration. Press Up + Enter = lock 4 mA value
Calibrate 20 mA/100 % level: Bring level to the highest possible position Attach a mA meter to the test points Adjust the loop current via Up and Down
Eg. 50 % level reads 10 mA. Toggle with the Up button, till the mA meter reads (20 mA - 4 mA) x 50 % + 4 mA = 12 mA
air/gases set 4 mA
process liquid
100 % = 20 mA
50 % = 12 mA
INTERFACE MEASUREMENT: using the process liquid Calibrate 4 mA/0 % level Bring interface at lowest level Press Enter = start calibration. Press Up + Enter = lock 4 mA value
Important: Displacer must remain always immerged for min. 50 mm (2") in the upper liquid.
Calibrate 20 mA/100 % level: Bring interface at highest level Press Enter = start calibration Press Up + Enter = lock 20 mA value
air/gases
set 20 mA
lower liquid
interface
lower liquid
12
INTERFACE MEASUREMENT: using water for calibration Lower liquid is water with S.G. = 1.0 kg/dm3 Upper liquid with S.G. = 0.80 kg/dm3
Calibrate 4 mA/0 % level Immerge displacer for 80 % in water Press Enter = start calibration. Press Up + Enter = lock 4 mA value.
NOTE: in case the liquid would be 0.78 kg/dm, immerge the displacer only for 78% instead of 80% as per below example. Calibrate 20 mA/100 % level: Immerge displacer for 100 % in water Press Enter = start calibration Press Up + Enter = lock 20 mA value.
air/gases
set 4 mA water
set 20 mA
water
Calibrate 4 mA/0 % level Immerge displacer for 80 % in water Press Enter = start calibration. Press Up + Enter = lock 4 mA value.
Lower liquid with S.G. = 1.2 kg/dm3 Upper liquid with S.G. = 0.80 kg/dm3
air/gases
=
set 4 mA
Calibrate 20 mA/100 % level: Immerge displacer for 100 % in water Press Enter = start calibration Press Up and/or Down = untill loop signal corresponds with, in our example, 12 mA Calculation: 100 x (1 - 0,8) 1.2 - 0,8 = 50 %
[(20 mA - 4 mA) x 50 %] + 4 mA = 12 mA
water
air/gases
set 18.5 mA
water
13
Hidden diagnostic screens. Do not access without assistance or having followed advanced training.
Action
DispFact Select History (current status) Run time xxxx.x h History Reset MeasType (select) Model (select) SpringSG (select) SprgRate x.x SprgMatl TempLimt xxx C Length xx.xx cm Diameter x.xxx cm Weight xx.x kg Lower SG x.xx Upper SG x.xx CalSelct (select) Factory Cal Menu User Cal Menu AdjSnrLo AdjSnrHi Conv Fct xxxx Scl Ofst xxx LVDT% xx.xx % Chan 0 Chan 1 NSP Value ElecTemp xxx C Max Temp xxx C Min Temp xxx C
Comment
3 4 5 6 7
A cumulative review of all diagnostic messages. Press the enter button twice to clear. Shows time in hours that unit is in operation since last power on. Select YES to clear History. Level, IfcLevel or Density.
Diagnostic display. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set. Factory set.
E31, E32, E33, E34, E35, E36. Model specic. Model specic. Model specic.
8 9
10 11 12 13
Model specic. Max process temperature for which unit is suitable. Model specic. Length of measuring range.
Model specic. Outside diameter of displacer. Model specic. Weight of displacer Only for interface units. Only for interface units.
Diagnostics
14 15 16
Select factory or user calibration. Depress enter to display the factory calibration sub-menu. Depress enter to display the factory calibration sub-menu. Diagnostic display. Diagnostic display.
Selects calibration parameters used to calculate the measured PV. CalSelct = factory submenu on page 15 CalSelct = user submenu on page 15
17 18 19 20 21 22
None, do not adjust. None, do not adjust. Diagnostic display. Diagnostic display. Diagnostic display. Diagnostic display.
23
24 25
26
27 28
Diagnostic display, shows maximum internal housing temperature recorded. Diagnostic display, shows minimum internal housing temperature recorded.
14
CalSelct allows to view either the factory settings Factory or the super user modied settings User. Spare heads will be congured per factory default values and will be different from the super user modied settings. The super user settings overrule the factory settings, whereby the factory settings can at all times be referenced to, to allow efcient troubleshooting.
Screen
2 1
Action
LVDT% xx.xx % Calib SG xx.xx sg DrySenr xx.xx % SnrCalLo xx.xx % LvlCalLo xx.xx lu Set 4mA xx.xx lu SnrCalHi xx.xx % LvlCalHi xx.xx lu Set 20mA xx.xx lu Escape
Comment
3 4 5 6 7
Factory calibration menu. Only used for units congured for liquid level applications.
Diagnostics
Enter or capture sensor output for Low Cal Point. Enter the level value for 4 mA set point.
Press up arrow + Enter (simultaneously) to capture current sensor output. Press up arrow + Enter (simultaneously) to capture current sensor output. Specify level at 4 mA (User Cal menu only).
Enter level value corresponding to SnrCalLo. Enter or capture sensor output for High Cal Point. Enter the level value for 20 mA set point.
8 9
Enter level value corresponding to SnrCalHi. Depress enter key to exit calibration sub-menu; returns to factory menu.
Press up arrow + Enter (simultaneously) to capture current sensor output. Specify level at 20 mA (User Cal menu only).
10
Capturing the 20mA value 5. Move liquid to desired 20mA value (high level / max. density) 6. Enter advanced conguration DispFact (see page 14) and scroll to the submenu CalSelct and select the super user menu User (see above). 7. Select SnrCalHi and capture this level. Press up arrow + Enter (simultaneously). NOTE: PACTware provides a user friendly way to remotely perform the identical procedure 8. Select LvlCalHi, default value is the displacer length, adjust with up and down for the desired level and press Enter.
Capturing the 4mA value 1. Move liquid to desired 4mA value (low level / min. density) 2. Enter advanced conguration DispFact (see page 14) and scroll to the submenu CalSelct and select the super user menu User (see above). 3. Select SnrCalLo and capture this level. Press up arrow + Enter (simultaneously). 4. Select LvlCalLo, default value is 0.00, adjust with up and down for the desired level and press Enter.
Use this procedure - for matching new E3 electronics with older generation EZ Modulevels - when replacing spare parts: Electronic module, LVDT assembly, range spring, stem assembly or displacer - for exchanging a complete electronics head on a E3 Model. NOTE: This procedure should be performed at normal operating conditions.
15
For more details about the use of PACTware and FDT technology, refer to instruction manual 59-601 WHAT IS FDT, PACTware AND DTM FDT (Field Device Tool) is a new interface code that describes the standardization between frame programs (e.g., PACTware) and DTMs (Device Type Manager). 1. Start a project Open Pactware and add the Hart modem key and then the Magnetrol instrument to your project. Select: Device add device select device (repeat for each device in your project) Important: Make sure that the COM port settings for your Hart modem key are correct; 2. Connect the devices Select in the left window the Magnetrol instrument. Select: Device connect (both modem and Magnetrol instrument are getting connected) 3. Congure the instrument Select: Device parameter Online parameterization Open + Main Menu and select + Device set up Calibration Parameters can be changed in the window at right, via the drop down boxes. ENTER conrms the change online. 4. Manually calibrate the 4-20mA output Select in Calibration - Set point Calib and Select Capture values. A warning message appears to remove the loop from DCS. Set the 4mA (see MENU pages) Capture 4mA Set the 20mA or 20 mA by % (see MENU pages) Capture 20mA, close the procedure by selecting End. 5. Diagnostics E3 Modulevel offers the ability to monitor output and LVDT position. Select: Device parameter Online parameterization Open + Main Menu and select + Device set up Diagnostics An overview is provided of all possible diagnostic values. A Print screen shot can, in case of eld problems, be sent for factory assistance. This screen also provides a loop test function: 4mA, 20mA or any random mA test value. Close the loop procedure by selecting End. QUICK START
DTM (Device Type Manager) is a device-specic software driver designed to operate within a FDT compatible frame program such as PACTware. It includes all special information needed to communicate with a specic device (e.g., Pulsar RX5). There are two basic categories of DTMsCommunication (HART, Fieldbus, Probus, etc.) and Field Device (e.g. Pulsar RX5 Radar transmitter). MINIMUM SYSTEM REQUIREMENTS
PACTware (Process Automation Conguration Tool) is a frame program. It is a device-independent software program that communicates with all approved DTMs.
Following are general requirements for proper operation of this program: 128 MB RAM. Pentium II 500 MHz processor. 120 MB free hard disk space.
Windows XP/2000 (Service Pack 1) / NT 4.0 (Service Pack 6). RS232 serial interface. Internet Explorer 5.0. Graphic Resolution 1024x768 (16-bit color).
RS232-HART or USB-HART serial interface for point-topoint connection or RS232-RS485 converter for connection to Hart Multiplexer. Transmitter with current HART revision. CONNECTIONS HART communication DTM.
The following diagram shows a typical hardware conguration. Observe all safety codes when attaching to instrument loops in hazardous areas or when measuring ammable media. Computers are not intrinsically safe devices.
24 V DC HART connections Power
Magnetrol recommends the VIATOR USB HART Interface from MACTek Corporation.
16
Connection of your Hart communicator: at power terminals (+) and (-) in wiring compartment at rst junction box between unit and control room.
CONNECTIONS
Junction
IMPORTANT: The digital HART communication is superimposed on the 4-20 mA loop and requires a min. load resistance of 250 and a max load resistance of 450 .
RL > 250
Before starting the HART conguration procedure check if your HART communicator is equipped with the proper E3 Modulevel Device Descriptors (DDs). I/O Select NO: Select 4: Select 5: Check manufacturer: start up the communicator go ofine utility simulation Magnetrol Model E3
CHECK HART
Power Supply
Current Meter
When the proper software version is not found, consult your local HART Service Center to load the correct E3 Modulevel DDs. HART MENU
I/O Start up the device 1 Enter Device Set Up DEVICE SET UP Press one of the following alphanumeric keys (if no key is sensed after 5 s, the unit will automatically jump to RUN mode and alternatively show Level/% Output and Loop signal 1 for entering Calibration CALIBRATION (see page 24 for additional information) 2 for entering Basic Set Up BASIC SET UP general HART 3 for Advanced Set Up ADVANCED SET UP (see page 24 for additional information) 4 for entering Diagnostics DIAGNOSTICS (see page 24 for additional information) 5 for entering Review REVIEW to review all settings.
17
1 2 3 4
2 Basic Setup
1 2 3 4 5 6 1 2 3 4
Tag Descriptor Date Message Poll Address Final asmbly num Trim Loop Current Enter Password Measurement Type Model Parameters
3 Advanced Setup
1 2 3 4 5 6 7
Model Number Spring SG Range Spring Rate Temperature Limit Displacer Length Displacer Diameter Displacer Weight
** Interface Parameters
5 Calibration Selected
IF FACTORY SELECTED:
4 Diagnostics
1 2 3 4 5 6 7 8 9 10 11
Loop Test LVDT % Channel 0 Channel 1 Adj Sensor Cal Lo Adj Sensor Cal Hi Conversion Factor Scale Offset Present Status
Status History Temp Information
1 2 3 4 5 6 7 8 9 10
Set Dry Point Set Low Calib Pts Set High Calib Pts LVDT % Calib SG Dry Sensor Value Sensor Cal Lo Level (or SG) Cal Lo Sensor Cal Hi Level (or SG) Cal Hi
8 Sensor Cal Hi 9 Level (or SG) Cal Hi 1 Faults 2 Warnings 1 View History 2 Reset History 1 2 3 4 Elec Temperature Max Temperature Min Temperature Reset Temperature Level Offset Process SG Operating Temp 4mA Set Point 20mA Set Point Damping System Fault State Trim Level (or SG) 4mA Trim Value 20mA Trim Value Measurement Type Calibration Selected Model Number
1 2 3 4 5 6 1 2 3 4 5 6
Default Params Loop Failure Primary Fault Core Drop Secondary Fault Hi Secondary Fault Lo Calib required Trim Required Hi Temperature Lo Temperature Cal Span Warning Initializing
5 Review
1 2 3 4 5 6 7 8 9 10 11 12 13
Model Manufacturer Magnetrol S/N Firmware Version Tag Descriptor Date Message Poll Address Final asmbly num Device ID PV is Level Units
14 15 16 17 18 19 20 21 22 23 24 25 26
27 28 29 30 31 32 33 34 35 36
Spring SG Range Spring Rate Temperature Limit Displacer Length Displacer Diameter Displacer Weight Universal rev Fld dev rev Software rev Num req preams
18
MAINTENANCE
Symptom
No loop current.
Problem
Power supply not turned on. Turn on power. Insufficient source voltage. Improperly wired or damaged wiring. Defective electronics.
Solution
E3 requires a minimum of 11 VDC at the wiring board. Verify supply voltage. Check wiring and connections. Replace PC board assembly or wiring board as required. Verify Level Offset values. If using factory calibration, verify that Process SG and Operating Temperature values are accurate. Verify/confirm that Model Parameters are accurate. Confirm set points are as expected.
Model incompatible with process liquid Possible damage to unit. Possible material buildup Displacer, spring or stem dragging on inside of chamber, e-tube.
Verify model in use is appropriate for process liquid SG. Check displacer, spring, stem and enclosing tube for damage. Replace all damaged parts. Check displacer, spring, stem, enclosing tube and displacer for buildup of process material. Clean any fouled parts. Verify proper and level installation (within 3 degrees of plumb in all directions). Set poll address to 0 if not using multi-drop.
Level reading on display Invalid poll address. is correct, but loop value is stuck at 4 mA. LEVEL, % OUTPUT and LOOP values fluctuate. Liquid turbulence. Power supply unstable. Electrical interference (RFI). HART device only: Handheld will only read Universal Commands Cannot set high level to 20 mA Loop current less than 4 mA 4 mA output does not match display Loop current exceeds 20 mA Most current Device Descriptors are not installed in handheld. Incorrect power supply. Excessive loop resistance Liquid level less than 0%. Supply voltage out of limits at transmitter. 4 mA may need to be trimmed. Liquid level greater than 100%. Supply voltage out of limits at transmitter. Wired incorrectly. 20 mA output does not match display Output jumps quickly over wide range Non-linear output. 20 mA may need to be trimmed.
Increase damping until output stabilizes or install stilling well. Repair or replace power supply. Consult factory for assistance. Contact local HART service center for the latest DDs.
Check power supply. Increase power supply voltage or decrease loop resistance (max 620 ohms @ 24 VDC). No action required. Adjust power supply or reduce loop resistance. Use Trim 4 mA to adjust output to match display. No action required. Adjust power supply or reduce loop resistance. Check power supply (+) and (-) for reverse wiring. Use Trim 20 mA to adjust output to match display.
Bent stem impeding smooth Review Status History for Surge event. Inspect stem and replace if damaged. core movement Excessive loop resistance. Displacer hanging up. Bent stem. Possible material buildup Increase power supply voltage or decrease loop resistance. Verify proper and level installation (within 3 degrees of plumb in all directions.) Check stem. Replace if damaged. Check displacer, spring, stem, enclosing tube and displacer for buildup of process material. Clean any fouled parts.
19
INFORMATION MESSAGES
MAINTENANCE
The lowest in the hierarchy of diagnostic conditions provides operational factors that are not critical to measurement. Further error information can be obtained by viewing the status history in the factory menu.
Display Message
System Warning Surge OK
Description
Absence of any warning or fault Unexpected system events No action required.
Solution
Readings from the LVDT secondary windings are Rate of level change is greater than expected. changing more rapidly than expected. Check for possible process surge or bent stem.
WARNING MESSAGES
A warning message identies the status of the instrument. A warning message does not necessarily require immediate action but may require close attention and/or follow up. The warning message will be displayed on the unit and/or selected on the PACTware screen while the output signal will remain normal.
Display Message
Initial
Description
Initializing, PV held at 4 mA set point while unit powers up. Should be transient. Span between Sensor Calibration Hi and Lo values is less than minimum span. Present temperature measured in electronics compartment is below -40 C (-40 F). No action required.
Solution
Recalibrate or reconfigure unit with longer span 1. Transmitter may need to be moved to ensure ambient temperature is within specification 2. Change to remote mount transmitter 3. Controlled external heat may be required to ensure that temperature inside housing is within specification
Hi Temp TrimReqd
1. Transmitter may need to be moved to ensure ambient temperature is within specification 2. Change to remote mount transmitter 3. Controlled external cooling may be required to ensure that temperature inside housing is within specification
Loop trim values are defaults; loop output may be inaccurate. Default calibration parameters in use, level reading inaccurate.
Cal Reqd
20
An error message identies a possible instrument failure and requires an action. The error message will be displayed on the unit and/or selected on the Pactware screen while the output signal will shift to the selected error output (3.6mA, 22mA or HOLD).
ERROR MESSAGES
MAINTENANCE
Display Message
SecFltHi SecFltLo CoreDrop PriFault LoopFail DfltParm
Description
Readings from LVDT secondary windings are above expected range. Readings from LVDT secondary windings are below expected range. Core too far out. LVDT Primary circuit open condition. Loop current differs from commanded value by more than 1.00 mA. Non-volatile parameters have been defaulted.
Solution
Check for missing displacer. Check for broken spring or leaking displacer. Check for lost or damaged LVDT core. Check LVDT winding resistance. Replace LVDT if values are out of range Consult factory. Consult factory.
Loop Output
Fault Warning Information 3.6/22/HOLD No Effect No Effect
Status Message
Yes Yes No
Status History
Yes Yes Yes
21
MAINTENANCE
CAUTION: BENDING THE ENCLOSING TUBE WILL PERMANENTLY DAMAGE THE UNIT.
2 Remove C-ring, use proper ring pliers 3 Remove LVDT top spacer 1 Remove the LVDT housing
() P2 ERROR SPAN
(+) P1 ZERO
TB1 +
UP DOWN ENTER
REFER TO MODULEVEL MANUAL, BULLETIN 48-615, FOR INSTALLATION AND OPERATION INSTRUCTIONS. TP1
www.magnetrol.com
AW3175
TP2
TB2
D1 +
J1 05-9123-001
L6
C6 C5
L5
JP1 D2
P2
L3
P1
C3
TB1
3 Unlock for repositioning or removal of head assembly and always relock, after nal positioning
Size 1/8"
1 Disconnect Power
NOTE: Remove transport enclosing tube before mounting For calibration, use only the calibration procedure, page 15.
L4
4 Loosen the set screws and remove the dummy encolsing tube
6 Ensure that the ame path adaptor is seated all the way down on the E-tube nut
C4
L2
C1
22
REPLACING LINEAR VARIABLE DIFFERENTIAL TRANSFORMER (LVDT) CAUTION: REMOVE POWER FIRST.
Enclosing tube
MAINTENANCE
2. Secondary winding (pins 2 and 5 or 3 and 6) should have approximately 70 to 100 . If not in this range, replace the LVDT.
1. Using a multimeter, check primary winding. Pins 1 and 4 should have approximately 75 to 105 .
1 Remove cover
2 Remove electronics
3 Remove LVDT
23
4a
Electronics module
Order code for spare E3 Modulevel head: 3 last digits of the selection data on pages 31, 32, 33 and 34
Z39-4101-
10
CAUTION: Follow the user calibration procedure (see page 15), when replacing the following spare parts: electronic module, LVDT assembly, stem, range spring or displacer Partn: E 3 Serial n: See nameplate, always provide complete partn and serial n when ordering spares. LVDT assembly kit (5) Replacement part 089-7827-007 089-7827-008 089-7827-009
Digit in partn:
X 1 2 3
Digit 8 H F
Housing cover (4a) Digit 10 Cast aluminium 5, 6, A, B, J or K 036-4410-001 1, 2, E or F 036-4410-003 Digit 10 Stainless steel 3, 4, 7, 8, C, D, G, H, L or M 036-4410-004 Housing cover (4b) Digit 10 Cast aluminium 5, 6, A, B, J or K 004-9193-003 1, 2, E or F 004-9193-002 Digit 10 Stainless steel 7, 8, C, D, L or M 004-9193-007 3, 4, G or H 004-9193-006
Wiring board (2) Digit 10 Replacement part all Z30-9151-001 5, 6, 7, 8, A, B, C, Z30-9151-004 D, J, K, L or M 1, 2, 3, 4, E, F, G or H Z30-9151-003
Digit 8 H F
4 5 6 7
8 9 10
Common parts for all units ITEM Replacement part (3) Housing O-ring kit 089-6562-002 (8) Enclosing tube gasket 012-1204-001
LVDT housing cover (6) Digit 10 Replacement part 1, 2, 5, 6, A, B, 089-7837-001 E, F, J or K (Cast aluminium) 3, 4, 7, 8, C, D, 089-7837-002 G, H, L or M (Stainless steel)
Digit 9 1 2 3
24
Stem assembly
11
Digit 4 A, J or M B, K or N C, L or P D E F B or N M E or N P
Cotter pins
1 2 3
12
13
Digit 6
Digit 7 A B C D E F G H I A B C D
3, 4, 5, A, C, F, G, H, D, E or K L, M or N Replacement part 089-5340-002 not applicable 089-5340-005 089-5340-010 089-5340-008 not applicable 089-5340-003 not applicable 089-5340-006 089-5340-010 089-5340-009 not applicable 089-5340-005 089-5340-010 089-5340-003 not applicable 089-5340-006 089-5340-010 089-5340-009 not applicable Digit 4
Displacer kit
14
3, 4, 5, A, C, D, E, F, K or L G, H, M or N
Digit 6
Temp. Ext. Gasket (9) Digit 4 Replacement part J, K or L not applicable all except J, K and L 012-1204-001 Digit 3 1 or 2 Chamber gasket / Ring joint (10) Digit 6 Replacement part all not applicable 3 or A 012-1301-017 4 or C 012-1301-018 5, D, E or K 012-1204-021 3 or 5 L 012-1904-002 F, G or M 012-1904-003 H or N 012-1904-011 3 or A 012-1301-017 4 or C 012-1301-018 5, D, E or K 012-1204-021 4 or 6 L 012-1906-002 F, G or M 012-1906-003 H or N 012-1906-011
Enclosing tube (7) Digit 10 Replacement part all except 032-6401-007 E, F, G and H E, F, G or H 032-6401-010 all 032-6401-010
3, 4, 5, A, C, D, E or K
F, G, H, L, M or N
E, F, G, H or I
all except C, F, L or P C, F, L and P Replacement part 089-6125-001 089-6126-001 089-6125-002 089-6126-002 089-6125-003 089-6126-003 089-6125-004 089-6126-004 089-6125-005 089-6126-005 089-6125-006 089-6126-006 089-6125-007 089-6126-007 089-6125-008 089-6126-008 089-6125-009 089-6126-009 089-6125-010 089-6125-011 089-6125-012 not 089-6125-013 applicable consult factory
Common parts for all units ITEM Replacement part (11) Stem assembly consult factory (13) Cotter pin (ordering qty: 2) 010-5203-001
Kit Definitions Stem assembly kit includes: stem assembly and LVDT core. Spring assembly kit includes: spring assembly, screws and lockwashers. Displacer kit includes: displacer and cotter pins (Qty of 2).
25
FUNCTIONAL/PHYSICAL
Description Power (at terminals) Signal Output Span Resolution
TRANSMITTER SPECIFICATIONS
Weatherproof / Intrinsically Safe: 11 to 28,4 V DC (ATEX) - 28,6 V DC (FM) ATEX Explosion Proof 11 to 36 V DC (ATEX-FM) FOUNDATION Fieldbus (FISCO Intrinsically Safe): 9 to 17,5 V DC FOUNDATION Fieldbus (Explosion proof): 9 to 32 V DC 4-20 mA with HART, 3,8 mA to 20,5 mA useable (meets NAMUR NE 43), FOUNDATION Fieldbus H1 (ITK Ver. 5) Analog: 0,01 mA Display: 0,1 cm (inch) from 356 mm up to 3048 mm (14" up to 120") - others at request Specication
Loop Resistance) Damping Diagnostic Alarm User Interface Display Menu Language Housing Material Approvals
620 @ 20,5 mA - 24 V DC Adjustable 0-45 s Adjustable 3,6 mA, 22 mA, HOLD HART communicator, AMS or PACTware, FOUNDATION Fieldbus and 3-button keypad 2-line x 8-character LCD English/Spanish/French/German (FOUNDATION Fieldbus: English) IP 66/Aluminium A356T6 (< 0.20 % copper) or stainless steel ATEX II 1 G Ex ia IIC T4, intrinsically safe ATEX II 1 G Ex ia IIC T4, FISCO intrinsically safe ATEX II 1 / 2 G Ex d IIC T6, explosion proof FM, Intrinsically Safe (FISCO) and explosion proof
Equivalent Data
Cast aluminium Stainless steel ITK Version H1 Device Class H1 Prole Class Function Blocks Execution time CFF les Quiescent current draw
Ci = 2,2 nF, Li = 3 H - ATEX Ci = 5,5 nF, Li = 9 H - FM Ci = 0,71 nF, Li = 3 H (FOUNDATION Fieldbus) ANSI/ISA-571.03 SA1 (Shock), ANSI/ISA-571.03 VC2 (Vibration) 3 kg (7 lbs) amplier only 8 kg (17 lbs) amplier only H 306 mm (12.05") x W 112 mm (4.41") x D 192 mm (7.56") 5.0 Link Master (LAS) selectable ON/OFF 31PS, 32L 17 mA 1 x AI and 1 x PID, 1 x RB, 1 x TB AI: 15 ms, PID 40 ms
Ui = 28,4 V, li = 94 mA, Pi = 0,67 W - ATEX Ui = 28,6 V, li = 140 mA, Pi = 1 W - FM Ui = 17,5 V, li = 380 mA, Pi = 5,32 W (FOUNDATION Fieldbus)
LRS Lloyds Register of Shipping (marine applications) ROSTECH/FSTS Russian Authorisation Standards Functional safety to SIL 2 as 1oo1 in accordance to 61508 SFF of 92,3 % full FMEDA report and declaration sheet available at request
FOUNDATION Fieldbus units are FISCO (intrinsically safe) and ATEX FM/CSA explosion proof approved
26
PERFORMANCE
Description Linearity
TRANSMITTER SPECIFICATIONS
Level Level Specication 0,50 % of full span 0,70 % of full span 0,05 % of full span 0,10 % of full span 0,05 % of full span -40 -20 -40 -40 < 1 second C C C C to to to to < 5 seconds +80 +70 +70 +85 C C C C (-40 F to +175 F) (-5 F to +160 F) (-40 F to +160 F) (-40 F to +185 F) electronics temperature range LCD temperature range for Ex ia and Ex d units
Interface/Density Interface/Density
Storage temperature
Ambient Temp. Effect Process Max Temp. Min Density Range Humidity
Max zero shift is 0,03 % / C (0,017 % / F) +260 C (+500 F) for steam / + 315 C (+600 F) for non steam 355 bar @ +40 C (5150 psi @ +100 F). from 0,23 kg/dm3 up to 2,20 kg/dm3 0-99 %, non-condensing
-29 C (-20 F) for carbon steel models / -196 C (-320 F) for stainless steel models
MECHANICAL SPECIFICATIONS
Description Cage materials Wetted parts carbon steel or 316/316L (1.4401/1.4404) (other materials at request) Inconel (other materials at request) 316/316L (1.4401/1.4404) or 316 (1.4401) Threaded: 1 1/2" NPT-F or 2" NPT-F or 1 1/2" Socket Weld or 2" Socket Weld Flanged: Various ANSI or EN/DIN anges From 356 mm (14") up to 3048 mm (120") - other lengths at request Specication
Spring Displacer
27
DIMENSIONS in mm (inches)
Transmitter Head
102 (4.02)
407 (16)
407 (16)
72 (2.81)
262 (10.32)
70
Level Range
133 (5.24)
407 (16)
407 (16)
407 (16)
133 (5.24)
Models E3x-M/N/P
Models E3x-D/E/F
509 (20)
610 (24)
712 (28)
28
Dimension A for all models 150 / 300 / 600 lbs PN 16 .. PN 100 2500 lbs PN 320 Cage rating
DIMENSIONS in mm (inches)
SG range 4 th digit J/A/M/D L/C/P/F K/B/N/E K/B/N/E Dimension A 236 (9.29) 186 (7.32) 186 (7.32) 245 (9.65)
320 (12.60)
Dimensions B and C for external cage models (E33/E34/E35/E36) Flanged process connections Flange size Flange rating Connection type B Dimensions C
1 1/2"
2"
DN 40
DN 50
150 / 300 / 600 lbs 600 lbs 900 lbs 1500 lbs 2500 lbs 150 / 300 / 600 lbs 600 lbs 900 lbs 1500 lbs 2500 lbs PN 16 / PN 25 / PN 40 PN 63 / PN 100 PN 160 PN 250 PN 320 PN 16 PN 25 / 40 PN 63 PN 100 PN 160 PN 250 PN 320 Cage rating
Slip on - ANSI RF Weldneck - ANSI RJ Weldneck - ANSI RJ Weldneck - ANSI RJ Weldneck - ANSI RJ Slip on - ANSI RF Weldneck - ANSI RJ Weldneck - ANSI RJ Weldneck - ANSI RJ Weldneck - ANSI RJ EN 1092-1 Type B1 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B1 EN 1092-1 Type B1 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B2 EN 1092-1 Type B2
180 (7.09) 180 (7.09) 193 (7.60) 185 (7.28) 228 (8.98) 185 (7.28) 185 (7.28) 214 (8.43) 211 (8.31) 249 (9.80) 180 (7.09) 200 (7.87) 143 (5.63) 177 (6.97) 197 (7.76) 185 (7.28) 188 (7.40) 202 (7.95) 208 (8.19) 159 (6.26) 186 (7.32) 214 (8.43)
268 (10.55) 268 (10.55) 283 (11.14) 283 (11.14) 313 (12.32) 273 (10.75) 273 (10.75) 303 (11.93) 303 (11.93) 328 (12.91) 268 (10.55) 288 (11.34) 288 (11.34) 303 (11.93) 313 (12.32) 273 (10.75) 278 (10.95) 293 (11.54) 298 (11.73) 303 (11.93) 313 (12.32) 328 (12.91)
Threaded / Socket weld process connections Size 150 / 300 / 600 / 900 lbs 1500 lbs 2500 lbs 150 / 300 / 600 / 900 lbs 1500 lbs 2500 lbs
1 1/2" 2"
Connection type
Dimensions
Not Applicable
29
The following charts lists combinations of process and ambient temperatures that should not be exceeded, with standard instruments
OPERATING TEMPERATURES
Non-steam applications
350 300 Process temperature C 250 200 150 100 50 0 30 35 40 45 50 55 Ambient temp. C 60 65 70 75
Digit 4 = A/B/C
Digit 4 = J/K/L
Digit 4 = D/E/F
Steam applications
350 Process temperature C 300 250 200 150 100 50 0 30 35 40 45 Digit 4 = K Digit 4 = N Ambient temp. C 50 55 60 65 70 75
Digit 4 = B
Digit 4 = E
MODEL IDENTIFICATION
30
2. Options: - Adjustable displacer hanger for top mounted units, cable length 2,5 m (8'). Order code 032-3110-004 required when distance between the top of the displacer and the ange face is > dimension A (see page 10 & 11) + 60 mm (2.36"). - Free of charge: Magnetrol master C.D. with E3 Modulevel DTM (PACTware). Order code: 090-BE59-200 (included in each order).
1. One order code for a complete standard E3 Modulevel transmitter. Order code for modied models/adders: put an "X" in front of the closest matching order code and specify the modication/adders separately. e.g: XE35-KQ3A-H1B X = material certication EN 10204-3.1
E 3 1 E 3 3 E 3 5
SPECIFIC GRAVITY AND PROCESS TEMPERATURE (consult factory for interface applications) Match temperature extensions with max. process temperature (digit 9) 230C M N P 290C D E F 315C M N P
150 lbs RF G3 H3 K3
150 lbs RF
E31/E32 - EN 1092-1 (DIN) Flange rating PN 16 PN 25/40 PN 63 PN 100 Size Type B1 Type B1 Type B2 Type B2 EA FA GA EC FC GC ED FD GD EE FE GE
DN 80 DN 100 DN 150
E33 ... E36 - ANSI Flange/Cage rating E33 ... E36 - EN 1092-1 (DIN) Flange rating 600 lbs 300 lbs PN 16 PN 25/40 PN 63 PN 100 Size Size RF Type B1 Type B1 Type B2 Type B2 RF RJ P3 P4 P5 PK 11/2" anged DN 40 Q3 Q4 Q5 QK 2" anged CA CC CD CE anged A3 A4 A5 11/2" NPT-F E3 E4 E5 2" NPT-F DN 50 R3 R4 R5 11/2" S.W. DA DC DD DE anged F3 F4 F5 2" S.W. 356 14 A LEVEL RANGE 813 32 B 1219 48 C 1524 60 D 1829 72 E 2134 84 F 2438 96 G 2743 108 H 3048 120 I mm inches code
H F
OUTPUT/COMMUNICATION
TRANSMITTER ELECTRONICS
1 3
MAX PROCESS TEMPERATURE Match max. process temperature with temperature extensions (digit 4)
4-20 mA with Hart communication incl. display / 3 button keypad FOUNDATION Fieldbus communication incl. display / 3 button keypad Process temp. up to +290 C (+550 F) digit 4: ALL Process temp. from +291 C (+551 F) up to +315 C (+600 F) digit 4: M, N or P Stainless Steel NPT M20 L M C D G H 7 8 3 4 Housing material Cable entry Approval Weatherproof ATEX and FISCO intrinsically safe ATEX (Hart and FF) Explosion proof FM and FISCO intrinsically safe FM (Hart and FF) Explosion proof
3/4"
E 3
31
E 3 1 E 3 3 E 3 5
SPECIFIC GRAVITY AND PROCESS TEMPERATURE (consult factory for interface applications) Match temperature extensions with max. process temperature (digit 9) 230C N E 260C
150 lbs RF G3 H3 K3
150 lbs RF
E31/E32 - EN 1092-1 (DIN) Flange rating PN 16 PN 25/40 PN 63 PN 100 Size Type B1 Type B1 Type B2 Type B2 EA FA GA EC FC GC ED FD GD EE FE GE
DN 80 DN 100 DN 150
E33 ... E36 - ANSI Flange/Cage rating E33 ... E36 - EN 1092-1 (DIN) Flange rating 600 lbs 300 lbs PN 16 PN 25/40 PN 63 PN 100 Size Size RF Type B1 Type B1 Type B2 Type B2 RF RJ P3 P4 P5 PK 11/2" anged DN 40 Q3 Q4 Q5 QK 2" anged CA CC CD CE anged A3 A4 A5 11/2" NPT-F E3 E4 E5 2" NPT-F DN 50 R3 R4 R5 11/2" S.W. DA DC DD DE anged F3 F4 F5 2" S.W. 356 14 A LEVEL RANGE 813 32 B 1219 48 C 1524 60 D 1829 72 E 2134 84 F 2438 96 G 2743 108 H 3048 120 I mm inches code
H F
1 2 3
MAX PROCESS TEMPERATURE Match max. process temperature with temperature extensions (digit 4)
4-20 mA with Hart communication incl. display / 3 button keypad FOUNDATION Fieldbus communication incl. display / 3 button keypad Process temp. up to +150 C (+300 F) digit 4: K Process temp. from +151 C (+301 F) up to +230 C (+450 F) digit 4: B or N Process temp. from +231 C (+451 F) up to +260 C (+500 F) digit 4: E Stainless Steel NPT M20 L M C D G H 7 8 3 4 Housing material Cable entry Approval Weatherproof ATEX and FISCO intrinsically safe ATEX (Hart and FF) Explosion proof FM and FISCO intrinsically safe FM (Hart and FF) Explosion proof
3/4"
32
E 3
E 3 1 E 3 3 E 3 5
MODEL IDENTIFICATION NON STEAM applications (from 900 lbs to 2500 lbs)
top mounted E3 Modulevel E3 Modulevel with side/bottom cage E3 Modulevel with side/side cage E 3 2 E 3 4 E 3 6 Stainless steel models top mounted E3 Modulevel E3 Modulevel with side/bottom cage E3 Modulevel with side/side cage
SPECIFIC GRAVITY AND PROCESS TEMPERATURE (consult factory for interface applications) Match temperature extensions with max. process temperature (digit 9) 150 C K 200 C B 230 C N 290C E 315 C N
E31/E32 - ANSI Flange rating 2500 lbs 900 lbs 1500 lbs RJ RJ RJ
E31/E32 - EN 1092-1 (DIN) Flange rating PN 160 PN 250 PN 320 Type B2 Type B2 Type B2 EF EG EH FF FG FH GF GG GH E33...E36 - EN 1092-1 (DIN) Flange rating PN 160 PN 250 PN 320 Type B2 Type B2 Type B2 CF DF CG DG CH DH
Size
E33...E36 - ANSI Flange/Cage rating 2500 lbs 900 lbs 1500 lbs RJ RJ RJ PL PM PN QL QM QN AL AM AN EL EM EN RL RM RN FL FM FN LEVEL RANGE A 813 32 B
1 1/2" anged 2" anged 1 1/2" NPT-F 2" NPT-F 1 1/2" S.W. 2" S.W.
Size
356 14
1219 48 C
1524 60 D
1829 72 E
2134 84 F
2438 96 G
2743 108 H
3048 120 I
mm inches code
H F
1 3
MAX PROCESS TEMPERATURE Match max. process temperature with temperature extensions (digit 4)
4-20 mA with Hart communication incl. display / 3 button keypad FOUNDATION Fieldbus communication incl. display / 3 button keypad Process temp. up to +290 C (+550 F) digit 4: ALL Process temp. from +291 C (+551 F) up to +315 C (+600 F) digit 4: N Stainless Steel NPT M20 L M C D G H 7 8 3 4 Housing material Cable entry Approval Weatherproof ATEX and FISCO intrinsically safe ATEX (Hart and FF) Explosion proof FM and FISCO intrinsically safe FM (Hart and FF) Explosion proof
3/4"
E 3
complete code for E3 Modulevel transmitter NON STEAM applications / high pressure
33
E 3 1 E 3 3 E 3 5
SPECIFIC GRAVITY AND PROCESS TEMPERATURE (consult factory for interface applications) Match temperature extensions with max. process temperature (digit 9) 150C K 200C B 230C N E 260C
E31/E32 - ANSI Flange rating 2500 lbs 900 lbs 1500 lbs RJ RJ RJ GL HL HM HN KL KM KN E33...E36 - ANSI Flange/Cage rating 2500 lbs 900 lbs 1500 lbs RJ RJ RJ PL PM PN QL QM QN AL AM AN EL EM EN RL RM RN FL FM FN LEVEL RANGE A 813 32 B
E31/E32 - EN 1092-1 (DIN) Flange rating PN 160 PN 250 PN 320 Type B2 Type B2 Type B2 EF EG EH FF FG FH GF GG GH E33...E36 - EN 1092-1 (DIN) Flange rating PN 160 PN 250 PN 320 Type B2 Type B2 Type B2 CF DF CG DG CH DH
Size
1 1/2" anged 2" anged 1 1/2" NPT-F 2" NPT-F 1 1/2" S.W. 2" S.W.
Size
356 14
1219 48 C
1524 60 D
1829 72 E
2134 84 F
2438 96 G
2743 108 H
3048 120 I
mm inches code
H F
OUTPUT/COMMUNICATION
TRANSMITTER ELECTRONICS
1 2 3
MAX PROCESS TEMPERATURE Match max. process temperature with temperature extensions (digit 4)
4 - 20 mA with Hart communication incl. display / 3 button keypad FOUNDATION Fieldbus communication incl. display / 3 button keypad Process temp. up to +150 C (+300 F) digit 4: K Process temp. from +151 C (+301 F) up to +230 C (+450 F) digit 4: B or N Process temp. from +231 C (+451 F) up to +260 C (+500 F) digit 4: E Stainless Steel NPT M20 L M C D G H 7 8 3 4 Housing material Cable entry Approval Weatherproof ATEX and FISCO intrinsically safe ATEX (Hart and FF) Explosion proof FM and FISCO intrinsically safe FM (Hart and FF) Explosion proof
3/4"
34
E 3
Copy blank page and store calibration data for future reference and troubleshooting. (data can also be printed from PACTware with function print online parameterisation)
Identication Vessel # Tag # Vessel name Process medium Electronics serial # Conguration Item Level Loop Level units
Screen
Value
Value
Level
Loop LvlUnits Proc SG OperTemp Set 4mA Set 20mA Lvl Ofst Damping Fault Trim Lvl Trim 4 Trim 20 MeasType Calselect Calib SG DrySensr SnsrCalLo LvlCalLo SnsrCalHi LvlCalHi LVDT% E3 ModHT
35
Process SG 4 mA point
Trim 20 mA
Calibration selected Dry sensor value Sensor cal low Level cal low
Firmware version
IMPORTANT
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to the purchaser, (or owner) other than transportation cost if: a. Returned within the warranty period; and, b. The factory inspection nds the cause of the malfunction to be defective material or workmanship.
SERVICE POLICY
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour and the parts required to rebuild or replace the equipment. In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of our warranty. No claims for misapplication, labour, direct or consequential damage will be allowed.
So that we may efciently process any materials that are returned, it is essential that a Return Material Authorisation (RMA) form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is available through Magnetrols local representative or by contacting the factory. Please supply the following information: 1. 2. 3. 4. 5. 6. Purchaser Name Description of Material Serial Number and Ref Number Desired Action Reason for Return Process details
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
Heikensstraat 6, 9240 Zele, Belgi -Belgique Tl. +32 (0)52.45.11.11 Fax. +32 (0)52.45.09.93 E-Mail: info@magnetrol.be Alte Ziegelei 2-4, D-51491 Overath Tel. +49 (0)2204 / 9536-0 Fax. +49 (0)2204 / 9536-53 E-Mail: vertrieb@magnetrol.de C-20 Community Centre, Janakpuri, New Delhi - 110 0058 Tel. +91 (11) 41661840 Fax +91 (11) 41661843 E-Mail: info@magnetrolindia.com Via Arese 12, I-20159 Milano Tel. +39 02 607.22.98 (R.A.) Fax. +39 02 668.66.52 E-Mail: mit.gen@magnetrol.it DAFZA Office 5EA 722 PO Box 293671 Dubai Tel. +971-4-6091735 Fax +971-4-6091736 E-Mail: info@magnetrol.ae Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL Tel. +44 (0)1444 871313 Fax +44 (0)1444 871317 E-Mail: sales@magnetrol.co.uk
www.magnetrol.com