GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10. Connection of MELSEC-QnA Series PLC
This chapter explains connection of the GOT-F900 Series display unit to the QnA Series PLC. Connection Procedure
Introduction

2
Outline

This section introduces the procedure to connect the GOT-F900 to the QnA Series PLC.

1. Preparation
Item name System Condition System Configuration Description You can learn the connection availability as well as the version of the GOT-F900 OS and the screen creation software. You can select the configuration between the GOT and the QnA Series PLC/computer link unit as well as proper cables. Reference 10.1 10.2

3
Specifications

2. Setting
Item name QnACPU Selection in Direct Connection Description In the QnA computer link, the following setting is required. When QnA connection is selected, the GOT-F900 is automatically set to fixed values. No setting is required in the QnA Series PLC. You can learn the communication specifications and the setting. Setting in QnA Computer Link Connection Setting of QnA The contents of setting of computer link computer link Setting examples Switch setting in each computer link 10.3.1 10.3.2 Reference 10.3

4
installation and Wiring of F940GOT

5
installation and Wiring of Handy GOT

Setting of Connected Equipment for GOT

Set the PLC type using the GOT or the screen creation software.

10.5

3. Others
Item name Cable Diagram Troubleshooting Description Cable diagrams for QnA Series PLC/GOT connection Description of errors and how to fix them Reference 10.6 10.7

10-1

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

Connection of Peripheral Equipment

Caution on Use of MELSEC-QnA Series PLC

You can learn the restrictions in connecting the GOT to the QnA Series PLC.

10.4

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

10.1

System Condition
When connecting the QnA Series PLC, check the COM port designation, the OS version of the GOTF900, and the applicable version of the screen creation software. Compatibility when connecting QnA Series PLC
GOT-F900 Series F920GOT-K(5V) F920GOT-K(24V) F930GOT F930GOT-K F940GOT F940WGOT F940 Handy GOT F943 Handy GOT COM port RS-422 % $ $ $ $ $ $ RS-232C $ $ $ $ $ $ Version of screen creation software OS version of GOT-F900 Two or more GT GT 1:1 DU/WIN GOT units Designer2 Designer Connection type $ $ $ $ $ $ $ $ $ $ $ $ *1 *1 1.00 1.20 2.00 4.60 3.00 1.00 3.00 3.00 SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW5-26C SW2-A SW5-26C SW2-A SW5-F SW2-A SW2-A 2.70 2.30 2.70 2.30 2.50 2.30 2.30

- "%" in this table indicates that only connection via the programming connector of the QnA CPU is available, and computer link connection and connection to a serial communication unit are not available. - Connection of two or more GOT units is possible only in QnACPU direct connection and QnA computer link connection. It is not possible in A computer link connection. - The screen creation software version corresponds to the model of the GOT-F900 Series. Refer to section 3.2. *1 The RS-232C port for the Handy type GOT is provided inside the rear cover. As a result, environmental protection is lost when using this port and such a connection is not practical. (The Handy GOT can be connected as the final unit in a string of two or more GOTs.)

10.1.1

Restriction When Computer Link Unit for A Series is Used


When the computer link unit for the A Series shown in the table below is attached to the QnA Series CPU, then the GOT-F900 Series display unit is connected to the QnA Series CPU, there is restriction in the available device range. - Refer to the description on the MELSEC-QnA Series in section 3.3.
Computer link unit (There is restriction.) AJ71UC24 A1SJ71UC24-R4 Serial data communication unit (There is no restriction.) AJ71QC24 AJ71QC24-R4

10-2

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10.2 System Configuration
The QnA Series PLC can be connected to the GOT through a computer link connection (RS-422 or RS232C) or directly via RS-422. This section explains the cables and options required in such a system.
Introduction

10.2.1

Configuration for Direct Connection (RS-422)


Connect the GOT-F900 to the programming port of the QnA Series PLC. Program transfer and monitoring are available in the GOT-F900 Series using the built-in two-port interface function through connection of a personal computer to the RS-232C port. (excluding the F920GOT-K) 1) F920GOT-K/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-422 cable
F930GOT

2
Outline

3
Specifications

a) QnA Series PLC QnACPU direct connection

4
installation and Wiring of F940GOT

Not enabled with F920GOT-K


F940GOT

Connection of two or more GOT units ...

5
installation and Wiring of Handy GOT

F920GOT-K (5V type)


a) QnA Series PLC QnACPU direct connection (25-pin D-Sub) b) RS-422 cable Prepared by the user. Remarks Make sure the total cable extension distance is 3m (9 10) or less.

6
Connection of Peripheral Equipment

F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT


a) QnA Series PLC QnACPU direct connection (25-pin D-Sub) b) RS-422 cable FX-40DU-CAB FX-40DU-CAB-""M FX-50DU-CABL Remarks """" in "FX-40DU-CAB-""M" indicates the cable length.

7
Connection of Two or More GOT Units

10-3

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

- Only one of the cables listed in column b) is required for connection. - In the F930GOT and the F930GOT-K, the FX-50DU-CABL right-angle type (L type) cable can not be used.

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

2) F940 Handy GOT


GOT-F900 b) RS-422 cable (A) (B) a) QnA Series PLC QnACPU direct connection

Handy GOT (RS-422)

(A)

(C)

To power supply and operation switches

Use the RS-422 port on the rear face. (E)

(D)
To power supply and operation switches

To RS-422, power supply and operation switches

Total extension distance: 11.5m (37' 9") or less Connection of two or more GOT units

...

a) QnA Series PLC

b) RS-422 cable (A) F9GT-HCAB-""M (B) F9GT-HCAB3-150

Remarks

QnACPU direct connection (25-pin D-Sub)

(C) FX-40DU-CAB (D) F9GT-HCNB (E) F9GT-HCAB1-""M

- Make sure that the total cable extension distance "(A) + (B)" or (E) is 11.5m (37' 9") or less.

10-4

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10.2.2 Configuration for QnA Computer Link Connection (RS-422)
The GOT-F900 and the computer link unit can be connected on the "1:1" basis. Because the programming port of the PLC is not occupied, peripheral programming equipment (dedicated equipment) for PLC can be connected for monitoring and transfer of sequence programs. 1) F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-422 cable a) QnA Series PLC QnA computer link
Outline Introduction

Connection of two or more GOT units


F940GOT

4
installation and Wiring of F940GOT

...

a) QnA Series PLC AJ71QC24-R4 AJ71QC24 A1SJ71QC24 AJ71UC24 A1SJ71UC24-R4 Terminal block Terminal block 25-pin D-Sub

b) RS-422 cable

Remarks Make sure the total cable extension distance is 30m (98 5) or less. Make sure the total cable extension distance is 30m (98 5) or less. Connection of two or more GOT units is not possible. Make sure the total cable extension distance is 30m (98 5) or less.

5
installation and Wiring of Handy GOT

Prepared by the user.

6
Connection of Peripheral Equipment

- Applicable QnA Series PLC products in the column a) are computer link units equipped with built-in RS-422 interface.

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

9
Connection of MELSEC-A Series PLC

10
Connection of MELSEC-QnA Series PLC

10-5

Specifications

F930GOT

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

2) F940 Handy GOT


GOT-F900 b) RS-422 cable (A) (B) a) QnA Series PLC QnA computer link

(A)

(C)

To RS-422 To power supply and operation switches

To RS-422
Handy GOT (RS-422)

(D)
To power supply and operation switches

(E)

Use the RS-422 port on the rear face.

To RS-422, power supply and operation switches

Total extension distance: 11.5m (37' 9") or less Connection of two or more GOT units

...

a) QnA Series PLC AJ71QC24-R4 AJ71QC24 A1SJ71QC24 AJ71UC24 A1SJ71UC24-R4 25-pin D-Sub Terminal block Terminal block

b) RS-422 cable (A) F9GT-HCAB-""M (B) Prepared by the user. (C) Prepared by the user. (D) F9GT-HCNB (E) F9GT-HCAB1-""M

Remarks

Connection of two or more GOT units is not possible.

- Applicable QnA Series PLC products in the column a) are computer link units equipped with built-in RS-422 interface. - Make sure that the total cable extension distance "(A) + (B)" or (E) is 11.5m (37' 9") or less.

10-6

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10.2.3 Configuration for QnA Computer Link Connection (RS-232C)
The GOT-F900 and the computer link unit can be connected on the "1:1" basis. Because the programming port of the PLC is not occupied, peripheral programming equipment (dedicated equipment) for PLC can be connected for monitoring and transfer of sequence programs. 1) F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-232C cable
F930GOT
Introduction

2
Outline

a) QnA Series PLC QnA computer link

3
Specifications

Connection of two or more GOT units


F940GOT

4
installation and Wiring of F940GOT

...

a) QnA Series PLC AJ71QC24 AJ71QC24-R2 A1SJ71QC24 A1SJ71QC24-R2 A1SJ71UC24-R2 AJ71UC24 25-pin D-Sub 9-pin D-Sub 25-pin D-Sub

b) RS-232C cable F2-232CAB-1

Remarks

5
installation and Wiring of Handy GOT

Prepared by the user.

Make sure the total cable extension distance is 15m (49 3) or less. Make sure the total cable extension distance is 15m (49 3) or less.

6
Connection of Peripheral Equipment

F2-232CAB-1

- Applicable QnA Series PLC products in the column a) are computer link units equipped with built-in RS232C interface.

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

9
Connection of MELSEC-A Series PLC

10
Connection of MELSEC-QnA Series PLC

10-7

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

2) F943 Handy GOT


GOT-F900 b) RS-232C cable (A) (B) a) QnA Series PLC QnA couputer link

(C)
Handy GOT (RS-232C)

To power supply and operation switches

To RS-232C, power supply and operation switches

Total extension distance: 6m (19' 8") or less Connection of two or more GOT units

...

a) QnA Series PLC AJ71QC24 AJ71QC24-R2 A1SJ71QC24 A1SJ71QC24-R2 A1SJ71UC24-R2 AJ71UC24 25-pin D-Sub 9-pin D-Sub 25-pin D-Sub

b) RS-232C cable (A) F9GT-HCAB-3M (B) Prepared by the user. (C) F9GT-HCAB1-3M

Remarks

Connection of two or more GOT units is not possible.

- In the (C)F9GT-HCAB1-3M shown in the column "b) RS-232C cable", the end on the PLC side is loose wires. - Make sure that the total cable extension distance "(A) + (B)" or (C) is 6m (19' 8") or less.

10-8

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10.3 Setting in QnA Computer Link Connection
In QnA computer link connection, the switches in the computer link unit (shown in the following page) should be set as described below.
Connected equipment [classification in manual] [QnACPU direct connection] Port of QnA CPU, QnAS CPU [QnA computer link] AJ71QC24(RS-422/RS-232C) AJ71QC24-R4(RS-422) AJ71QC24-R2(RS-232C) A1SJ71QC24(RS-422/RS-232C) A1SJ71QC24-R2(RS-232C) [A computer link] AJ71UC24(RS-422/RS-232C) A1J71UC24-R4(RS-422) A1J71UC24-R2(RS-232C) AJ71UC24(RS-232C) Refer to the following setting method. Remarks
Introduction

2
Outline

3
Specifications

Refer to Chapter 9.

4
installation and Wiring of F940GOT

10.3.1

Communication Setting Specifications


1) Setting the mode selector switch Set the mode so that the COM port of the computer link unit connected to the GOT-F900 is set to the dedicated (MC) protocol format 5.
COM port RS-422 RS-232C Set value 5 5 Remarks

5
installation and Wiring of Handy GOT

6
2) Setting the transmission specifications setting switches Set the transmission specifications setting switches of the computer link unit to realize the transmission specifications shown in the table below. For the switch setting method, refer to the manual of each computer link unit.
Item Transmission speed Data bit Data format Parity bit Stop bit Sum check Write in RUN mode Set value 19,200 bps 8 bits Provided (odd) 1 bit Provided Possible The setting is different from A computer link (7 bits). The setting is different from A computer link (provided, even). Remarks
Connection of Peripheral Equipment

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

- The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be changed.

Match the switches to 0H both in the GOT-F900 and in the computer link unit. 4) Turning on the power again After setting the QnA computer link, make sure to turn off the power once, then turn it on again. (Even if the RESET switch in the QnA Series PLC is pressed, the changed setting does not become valid.)

10-9

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

3) Setting the station number setting switches

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

10.3.2

Setting Examples
5) RS-422 connection a) When the AJ71QC24(N)(-R4) is connected
AJ71QC24-R4
RUN CPUR/W CH1.ERR. CH2.ERR.

CH1
456 456
789
A

CH2
789
CH.1

NEU ACK NAK C/N P/S PRO SIO

NEU ACK NAK C/N P/S PRO SIO

CH.2

AB

SD.WAIT SD RD

SD.WAIT SD RD

BCDE
ERR. X10
4

CD E

23

23

~10
4
2 3
5 6

~1
4
2 3
5 6 STATION No.

CH1

CH2
789 3 4 56

SW
01 02 03 04 05 06 07 08

4 5 6

10 11 12

01 02 03 04 05 06 07 08 09 10 11 12

CH1
RS-232C

CH2
RS422 RS485

SDA RDA SDB RDB NC SG FG

Important Point Set the mode selector switch for the unused channel to any value other than "0 (interlocking operation)". b) When the A1SJ71QC24(N) is connected
A1SJ71QC24
RUN ERR. C/N P/S PRO SIO C.R/W NEU ACK NAK SD.W. SD RD CH1 ERROR SW.E NEU ACK NAK SD.W. SD CH2 RD ERR. C/N P/S PRO SIO

CH2 45 6
789
A

DISPLAY
STS X1
4

AB

5 6
2 3 7 8
9

5 6
7 8
9

STATION NO.

2 3

CH1 4 56 4 56
789

CH2
7 89

23

CH1/2
1 2 3 4 SW 5 6 7 8 9 10 11 12

ON

CH2 RS-422/RS-485

SDA SG SDB FG RDA NC RDB

CH1 RS-232-C

A1SJ71QC24

F01

23

MODE

Mode selector switches (for CH2) Transmission specifications setting switches (for CH2)

When the transmission speed is set to "19,200 bps"

F0 1

23

10-10

2 3

2 3

When the transmission speed is set to "19,200 bps" SW ON

Transmission specifications setting switches (for CH1/CH2)

09

4 5 6

F0 1

F01

Mode selector switches (for CH1/CH2)

7 89 3 4 56

0 1
B C DE

0 1

F01

0 1

0 1

F01

F01

MODE

Station number setting switches

7 8

7 8

10
7 8

1
7 8

A
B C DE

9 0 1

9 0 1

BCD E

CDE AB

CD AB E

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
6) RS-232C connection a) When the AJ71QC24(-R2) is connected
AJ71QC24
RUN CPUR/W CH1.ERR. CH2.ERR.

CH.1

NEU ACK NAK C/N P/S PRO SIO

NEU ACK NAK C/N P/S PRO SIO

CH1
CH.2

2
CDE

SD.WAIT SD RD

SD.WAIT SD RD

23

456

789

~10
4 5 6
7 8 2 3 2 3

~1
4 5 6
7 8
STATION No.

CH1
789 3 4 56 3 4 56

CH2
78 9

MODE

SW
01 02 03 04 05 06 07 08

09 10 11 12

CH1
RS-232C

CH2
RS422 RS485

SDA RDA SDB RDB NC SG FG

09 10 11 12

b) When the A1SJ71QC24(N)(-R2) is connected


A1SJ71QC24
RUN ERR. C/N P/S PRO SIO C.R/W NEU ACK NAK SD.W. SD RD CH1 ERROR SW.E NEU ACK NAK SD.W. SD CH2 RD ERR. C/N P/S PRO SIO

456

789

DISPLAY
STS ERR. X10
4

AB

5 6
2 3 7 8
9

5 6
7 8
9

STATION NO.

2 3

3 45 6

CH1/2
1 2 3 4 SW 5 6 7 8 9 10 11 12

ON

CH2 RS-422/RS-485

SDA SG SDB FG RDA NC RDB

CH1 RS-232-C

A1SJ71QC24

10-11

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

F01

23

MODE

F01

45 6

789

7 89

Transmission specifications setting switches

When the transmission speed is set to "19,200 bps"

Connection of Peripheral Equipment

CH1 CDE AB

CH2 CD AB E

Mode selector switches

F0 1

X1

23

installation and Wiring of Handy GOT

installation and Wiring of F940GOT

01 02 03 04 05 06 07 08

10

Specifications

Mode selector switches (for CH1) Transmission specifications setting switches (for CH1)

When the transmission speed is set to "19,200 bps" ON SW

Outline
A

0 1

0 1

F01

Introduction
AB

F0 1

9 0 1

9 0 1

A
B C DE

A
B C DE

F 01

BCD E

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

10.4

Caution on Use of MELSEC-QnA Series PLC


When using the GOT-F900 connected to the QnA Series PLC, observe the following caution on use.

10.4.1

Caution when the GOT is connected to the serial communication unit


1) Simultaneous use of 2 ports When the GOT is connected, the CH1 and the CH2 of the serial communication unit cannot be used at the same time. Accordingly, have in mind that connecting both of GOT unit and peripheral equipment for the GPP function or two GOT units to one serial communication unit is not allowed.
Personal computer GOT-F900

Either one CPU Personal computer Serial communication unit

GOT-F900

GOT-F900

CPU

GOT-F900 Serial communication unit

However, a GOT unit or a personal computer can be connected to the RS-422 port of the QnACPU while the computer link unit has one GOT unit. 2) Compatible OS version of QnACPU When connecting a GOT unit to a serial communication unit or A Series computer link unit, the OS version of QnACPU needs to be later than the version indicated below. (Programming port of CPU is compatible with any version.)
QnACPU Q2A,Q3A,Q4A Q2AS H/W version D A S/W version A L Production date Earlier than March, 1997 Earlier than March, 1997

10.4.2

Caution when the GOT is connected to the computer link for the A Series PLC
When connecting the GOT-F900 to the A computer link attached to the QnACPU, select A SERIES for PLC TYPE. For setting method for the A computer link or screen creation software, refer to Chapter 9.

10-12

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
10.5 Setting of Connected Equipment for GOT
The setting for connection to the QnA Series PLC can be executed using the GOT-F900 and the screen creation software (GT Designer2, GT Designer or DU/WIN). Setting the Connection Type Set the connection type in accordance with the connected equipment as shown in the table below. When using the computer link unit for the A Series PLC, select A SERIES for PLC TYPE. (Refer to Chapter 9 for details.) Have in mind that the computer link unit for the QnA requires CPU direct connection.
Connected equipment [classification in manual] [QnACPU direct connection] Port of QnA CPU, QnAS CPU [QnA computer link] AJ71QC24(RS-422/RS-232C) AJ71QC24-R4(RS-422) AJ71QC24-R2(RS-232C) A1SJ71QC24(RS-422/RS-232C) A1SJ71QC24-R2(RS-232C) [A computer link] AJ71UC24(RS-422/RS-232C) A1J71UC24-R4(RS-422) AJ71UC24(RS-422/RS-232C) A1SJ71C24-R4(RS-422) A1SJ71C24-R2(RS-232C) A1SJ71UC24-R4(RS-422) A1SJ71UC24-R2(RS-232C) A1J71UC24-R2(RS-232C) AJ71UC24(RS-232C) GOT-F900 CONNECTION Screen creation software Type Programming port Refer to the following setting method. Remarks
Introduction

2
Outline

3
Specifications

CPU direct connection (RS-422)

4
installation and Wiring of F940GOT

CPU direct connection (RS-422) or CPU direct connection (RS-232C)

Communicates as programming port Refer to the following setting method.

5
Link connection (RS-422) or link connection (RS-232C) Communicates as computer link. Select A SERIES for PLC TYPE Refer to Chapter 9.
installation and Wiring of Handy GOT

6
Connection of Peripheral Equipment

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

9
Connection of MELSEC-A Series PLC

10
Connection of MELSEC-QnA Series PLC

10-13

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1) GOT-F900 Series When the main menu screen change operation is disabled.
Operation Display (screen name) a)While pressing and holding the upper left corner of the screen, The "LANGUAGE" screen appears. turn on the power. Keep holding the upper left corner for about 25 seconds more. Then, press "END" at the upper right corner. The "SET-UP MODE" screen appears. b)Press "PLC TYPE". c) Set the following. PLC TYPE: QnA, Q SERIES (QnA CPU, QnA computer link) A SERIES (A computer link) CONNECTION:CPU PORT (RS-422) CPU PORT (RS-232C) LINK PORT (RS-422) LINK PORT (RS-232C) DST STATION # (STATION #) : 00 to 15 GOT STATION # () : Connection destination QnACPU direct connection QnA computer link unit PLC TYPE QnA, Q Series CONNECTION STATION # CPU PORT (RS-422) 0 The "PLC TYPE" screen appears.

CPU PORT (RS-422) QnA, Q Series CPU PORT (RS-232C)

LINK PORT (RS-422) A computer link A Series or QnA, Q Series LINK PORT unit (RS-232C)

0 to 15

10-14

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
When the main menu screen change operation is enabled.
Operation a)Press the upper left corner of the screen. (The position to be pressed can be changed in the GOT and the screen creation software.) b)Press "OTHER MODE" on the menu. c) Press "SET-UP MODE" on the menu. d)Press "PLC TYPE". e)Set the following. PLC TYPE: QnA, Q SERIES (QnA CPU, QnA computer link) A SERIES (A computer link) CONNECTION:CPU PORT (RS-422) CPU PORT (RS-232C) LINK PORT (RS-422) LINK PORT (RS-232C) DST STATION # (STATION #) : 00 to 15 GOT STATION # () : Connection destination QnACPU direct connection QnA computer link unit PLC TYPE QnA, Q Series CONNECTION STATION # CPU PORT (RS-422) 0 Display (screen name) The "SELECT MODE" screen appears.
Introduction

2
The "OTHER MODE" screen appears. The "PLC TYPE" screen appears.
Outline

The "SET-UP MODE" screen appears.

3
Specifications

4
installation and Wiring of F940GOT

LINK PORT A computer link A Series or A, (RS-422) unit QnA Series LINK PORT (RS-232C)

0 to 15

- When the screen data is transferred to the GOT-F900, the old data including the PLC type, connection type, and station number are overwritten. - The "PLC type" selection item display varies depending on the OS version as follows.
"PLC TYPE" selection item display in GOT GOT-F900 A SERIES 1.00 or later 1.00 or later Not available (A computer link connection is available.) A, QnA SERIES 3.00 or later 2.00 or later Available A SERIES *1 QnA, Q SERIES 1.00 or later 4.10 or later 4.60 or later 2.20 or later 1.00 or later Available (Select "QnA, Q SERIES".) A SERIES *1 QnA, Q SERIES Q (Multi) SERIES 1.30 or later 6.30 or later 4.60 or later 4.30 or later 1.00 or later Available (Select "QnA, Q SERIES".)

F940WGOT F940GOT, Handy GOT OS version F930GOT-K F930GOT F920GOT-K Connection setting availability

10-15

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

*1 Note that the selection item on the menu is changed from "A, QnA SERIES" to "A SERIES" and "QnA, Q SERIES".

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

Connection of Peripheral Equipment

installation and Wiring of Handy GOT

CPU PORT (RS-422) QnA, Q Series CPU PORT (RS-232C)

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

2) GT Designer2
Operation [Creation] a)Open GT Designer2. b)Click the [NEW] button. The dialog box shown below is displayed. If it is not displayed, click "System Environment" in the tree displayed in the project work space, then click "System settings" in the tree. Display (screen name) The "Select Project" dialog box appears. The "System Environment" dialog box appears.

c)Set the following. GOT type: F940WGOT (480 234) F94*GOT (320 240) F93*GOT (240 80) F920GOT (128 64) PLC type:MELSEC-QnA, Q (QnA CPU, QnA computer link) MELSEC-A (A computer link) Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) F920GOT(12864) Click [OK]. Model name (name) F940WGOT F940GOT Handy GOT F930GOT F930GOT-K F920GOT-K

10-16

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
Operation d)Setting the port (RS-422 or RS-232C) of the GOT-F900 Click "Auxiliary Settings" in the tree of the system environment menu. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). Display (screen name) The "Auxiliary Settings" dialog box appears.
Introduction

2
Outline

3
Click "Got Setup" in the tree of the system environment menu.
Specifications

4
installation and Wiring of F940GOT

5
e)Set the following. Port : RS-422 RS-232C Type : CPU LINK Station No. : 00 to 15 GOT Station No. : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination QnA CPU direct connection A computer link unit QnA computer link unit A computer link unit QnA computer link unit RS-232C RS-422 Port Type CPU LINK CPU LINK CPU The "Select Project" dialog box appears.
installation and Wiring of Handy GOT

6
Connection of Peripheral Equipment

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

[Change method] Change the connection type of the already created data as follows. a)Open GT Designer2. b)Click the [Project]-[Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"System Environment". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 or the RS-232C on the QnA Series PLCs, refer to e) of [Creation] above.

10-17

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

The "System Environment" dialog box appears.

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

3) GT Designer
Operation [Creation] a)Open the GT Designer. b)Click the [New] button. Display (screen name) The "Select Project" dialog box appears. The "GOT/PLC Type" dialog box appears.

c)Set the following. GOT type: F940WGOT (480 234) <WIDE> F94*GOT (320 240) F93*GOT (240 80) F920GOT (128 64) PLC type: MELSEC-QnA, Q (QnA CPU, QnA computer link) MELSEC-A (A computer link) Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) F920GOT(12864) Click [OK]. d)Set CPU direct connection (RS-422/RS-232C)/link connection (RS-422/RS-232C) of the GOT-F900. This setting is enabled in the SW4D5C-GOTR-PACKE version A or later. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). The "Project Auxiliary Settings" dialog box appears. Model name F940WGOT F940GOT Handy GOT F930GOT-K F930GOT F920GOT-K

Click the "Setup" tab.

10-18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
Operation In the case of SW4D5C-GOTR-PACKE earlier than version A, perform the setting in the GOT-F900. (Set the connection in "CONNECTION" in the GOT-F900.) For the setting method, refer to "1) GOT-F900 Series" on the previous page. e)Set the following. Port : RS-422 RS-232C Type : CPU LINK DST Station No. (Station No.) : 00 to 15 GOT Station No. () : In the case of and F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination QnA CPU direct connection A computer link unit QnA computer link unit A computer link unit QnA computer link unit RS-232C RS-422 Port Type CPU LINK CPU LINK CPU The "Select Project" dialog box appears. Display (screen name)
Introduction

2
Outline

3
Specifications

4
installation and Wiring of F940GOT

5
installation and Wiring of Handy GOT

[Change method] Change the connection type of the already created data as follows. a)Open the GT Designer. b)Click the [Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"GOT/PLC Type". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 or the RS-232C on the QnA Series PLCs, refer to e) of [Creation] above.

- The "PLC type" selection item display varies depending on the software version as follows.
"PLC type" selection item display in GT Designer GT Designer MELSEC-A MELSEC-A MELSEC-A MELSEC-A,QnA MELSEC-QnA,Q MELSEC-QnA,Q MELSEC-Q(Multi)
*1

Version Connection setting availability

SW1-A or later Not available (A computer link connection is available.)

SW2-A or later

SW4-F or later Available (Select "MELSECQnA,Q".)

SW5-P or later (5.13P) Available (Select "MELSECQnA,Q".)

Available

*1 Note that the selection item display is changed from "MELSEC-A, QnA" to "MELSEC-A" and "MELSECQnA, Q".

10-19

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

Connection of Peripheral Equipment

The "GOT/PLC Type" dialog box appears.

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

4) DU/WIN
Operation [Creation] a)Open the DU/WIN. b)On the menu, select "File"-"New". Display (screen name) The "Project settings" dialog box appears.

c)Set the following. Terminal: F940WGOT-TWD (V) (H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V) (H) F920GOT-BBD5-K PLC System: MELSEC-QnA, Q (QnA CPU, QnA computer link) MELSEC-A (A computer link) Select "Terminal" in accordance with the LC display color. Terminal F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) F920GOT-BBD5-K Model name F940WGOT (color) F940GOT (black and white) Handy GOT (black and white) F940GOT (color) Handy GOT (color) F930GOT-K (blue) F930GOT (blue) F920GOT-K (blue) The "Setup Data" dialog box appears.

d)Set CPU direct connection (RS-422/RS-232C)/link connection (RS-422/RS-232C) of the GOT-F900. On the menu, select "View/Project"-"System Settings"-"Setup Data".

10-20

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
Operation e)Set the following. Port: RS-422 RS-232C Type: CPU LINK DST Station No. (Station No.) : 0 to 15 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination QnA CPU direct connection A computer link unit QnA computer link unit A computer link unit QnA computer link unit RS-232C RS-422 Port Type Station number CPU LINK CPU LINK CPU 0 0 to 15 0 0 to 15 0 Display (screen name)
Introduction

2
Outline

3
Specifications

4
installation and Wiring of F940GOT

[Change method] Change the connection type of the already created data as follows. a)Open the DU/WIN. b)On the menu, select "File"-"Open". c)Select and open (read) the file of the screen data to be changed. d)When changing "Terminal" (GOT-F900), select "View/Project""System Settings"-"Project settings" on the menu. - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 or the RS-232C on the QnA Series PLCs, refer to e) of [Creation] above. The "Open" dialog box appears. The "Project settings" dialog box appears.

5
installation and Wiring of Handy GOT

"PLC System" selection item display in DU/WIN DU/WIN Version Connection setting availability MELSEC-A 2.00 or later Not available (A computer link connection is available.) MELSEC-A,QnA 2.30 or later Available MELSEC-A *1 MELSEC-QnA, Q 2.40 or later Available (Select "MELSEC-QnA,Q".)

*1 Note that the selection item display is changed from "MELSEC-A, QnA" to "MELSEC-A" and "MELSECQnA, Q".

10-21

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

Connection of Peripheral Equipment

- The "PLC" selection item display varies depending on the software version as follows.

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

10.6

Cable Diagram
This section explains cable diagrams to connect the GOT-F900 and the QnA Series PLC. 1) Cable for the GOT and the QnA Series PLC F920GOT-K (5V type)
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram
(1) (2) (3) (4) (5) (6) (7) (8) (9) (2) (3) (4) (20) (7) (15) (16) (17) (12) (8) (21)

Application

GOT-F900
1 5

QnA CPU direct connection Prepared by the user a) (Cable length 3m (9'10") or less)
Resistance per wire: 0.67 or less (Approximately AWG 28 or thicker)

QnA Series
1 13

9-pin D-Sub, male

14

25

25-pin D-Sub, male

10-22

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
: Female type : Male type The connector figure shows the engagement face. Introduction

No.

Model name RS-422 connection

Application

Connection diagram
(1) (2) (3) (4) (5) (6) (7) (8) (9) (2) (3) (4) (5) (7) (15) (16) (17) (18) (8) (21)

Application

2
13
Outline

QnACPU direct connection FX-40DU-CAB a) FX-40DU-CAB-10M FX-40DU-CAB-20M FX-40DU-CAB-30M FX-50DU-CABL

GOT-F900
1 5

QnA Series
1

9-pin D-Sub, male

14

25

25-pin D-Sub, male

3
Specifications

RS-422 connection

b)

A computer link

9-pin D-Sub, male


(1) (2) (3) (7) (8) (6) (5)

RS-232C connection

GOT-F900
5 1

c)

9-pin D-Sub, female (4)

RS-232C connection

A, QnA computer link Prepared by user If proper monitoring is not executed due to external noise d) when connecting A1SJ71QC24 (-R2), connect all signals in pair with SG (except SG and FG).
RD SD DTR DSR SG

SD RD DSR DTR SG

When the computer link unit for the QnA Series is equipped with the 25-pin D-Sub port, the connection diagram is as follows. (The AJ71QC24-R4 is available).
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram

Application

FG GOT-F900 (Grounding) 1 5 (1) (6) (2) (7) (5)

QnA computer link e) Prepared by the user

10-23

Connection of MELSEC-QnA Series PLC

9-pin D-Sub, male

Computer link FG (Grounding) unit side (PLC side) (2) 1 13 (15) (3) (16) 14 25 (8) (21) 25-pin D-Sub, male

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

(1) (2) (3) 5 1 (4) (5) (6) 9 6 9-pin D-Sub, female (7) (8)

GOT-F900

FG (Grounding) (1) CD(DCD) Computer link unit side (2) RD(RXD) (PLC side) (3) SD(TXD) (4) DR(DTR) 1 5 (5) SG(GND) (6) DR(DSR) (7) RS(RTS) 6 9 (8) CS(CTS) 9-pin D-Sub, male Signal name of computer link

Connection of Peripheral Equipment

installation and Wiring of Handy GOT

A computer link F2-232CAB-1 (The connection diagram is partially different)

(1)FG (2)SD(TXD) Computer link unit side (3)RD(RXD) (PLC side) (4)RS(RTS) (5)CS(CTS) 1 13 (6)DR(DSR) (7)SG(GND) (8)CD(DCD) 14 25 (20)ER(DTR) 25-pin D-Sub, male Signal name of computer link

installation and Wiring of F940GOT

FG (Grounding) (1) GOT-F900 (6) 1 5 (2) (7) (5) 6 9

FG (Grounding) Computer RXD+(RDA) Terminal link unit side RXD-(RDB) block TXD+(SDA) (PLC side) TXD-(SDB) SG(GND) Signal name of computer link

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

2) Cable for the Handy GOT and the QnA Series PLC When using the Handy GOT RH model, refer to the cable diagrams below for the RS-422/RS-232C connector, but not the wiring for the power supply, the operation switches, and the emergency stop switch because it is different. For details, refer to Section 5.18.
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram

Application
To F9GT-HCAB3-150

F9GT-HCAB-3M a) F9GT-HCAB-10M

RS-232C connection

Dedicated connector on Handy GOT side

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.

13

14

25

25-pin D-Sub, male

F9GT-HCAB1-3M b) F9GT-HCAB1-10M

RS-422 connection RS-232C connection RS-422 connection


Dedicated connector on Handy GOT side

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.
F9GT-HCAB-""M FG(Grounding) (2) (15) (4) (17) (3) (16) (5) (18) (7) (8) (21)

Loose wires (no connector)

F9GT-HCAB3-150 c)
The diagram on the right shows the wiring of the RS422 signals. For wiring of the operation switches and the power supply, refer to chapter 5.

Drain wire (1) BK(2) W(3) R(4) To cable F9GT-HCAB GR(5) on Handy GOT side Y(6) 1 13 BR(7) BL(8) GY(9) 25 14 10) O( 25-pin D-Sub, female

QnA Series
1 13

14

25

25-pin D-sub, male

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25) F9GT-HCAB1-""M

DC24VG DC24VG SW common SW1 SW2 SW3 SW4 ES1 ES1 DC24V+ DC24V+

Wire the power supply, the operation switches and the emergency stop switch.

RS-422 connection

Drain wire (1) BK(2) W(3) To cable F9GT-HCAB or Y(6) BR(7) F9GT-HCAB1 O(10)

F9GT-HCAB-""M FG(Grounding) RXD+(RDA) RXD-(RDB) Terminal Computer TXD+(SDA) block link unit side (PLC side) TXD-(SDB) SG(GND) Signal name of computer link DC24VG DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

A computer link d) Prepared by the user

on Handy GOT side

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

F9GT-HCAB1-""M

10-24

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram
F9GT-HCAB-""M FG(Grounding) (2) (15) (3) (16) (8) (21) DC24VG DC24VG SW common SW1 SW2 SW3 SW4 ES1 ES1 DC24V+ DC24V+ 1

Application
Computer link unit side (PLC side)
13

14 25 25-pin D-Sub, male

e)

Wire the power supply, the operation switches and the emergency stop switch.

4
installation and Wiring of F940GOT

F9GT-HCAB1-""M

RS-232C connection

f)

A computer link Prepared by the user

F9GT-HCAB1-""M

RS-232C connection

g)

If proper monitoring is not executed due to external noise when connecting A1SJ71QC24 (-R2), connect all signals in pair with SG (except SG and FG).
RD SD DTR DSR SG

SD RD DSR DTR SG

F9GT-HCAB1-""M

10-25

Connection of MELSEC-QnA Series PLC

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

A, QnA computer link Prepared by user

Drain wire (1) R(4) To cable BK(2) W(3) F9GT-HCAB or O (10) F9GT-HCAB1 GR(5) on Handy GOT Y(6) BR(7) side

F9GT-HCAB-""M FG(Grounding) (1) CD(DCD) (2) RD(RXD) (3) SD(TXD) Computer link (4) DR(DTR) unit side (5) SG(GND) (PLC side) (6) DR(DSR) (7) RS(RTS) 1 5 (8) CS(CTS) Signal name of computer link 6 9 DC24VG 9-pin D-Sub, male DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

Connection of Two or More GOT Units

F9GT-HCAB-""M FG(Grounding) (1) FG Drain wire (2) SD(TXD) Computer link (3) RD(RXD) unit side (4) RS(RTS) (PLC side) (5) CS(CTS) 1 13 (6) DR(DSR) (7) SG(GND) (8) CD(DCD) 14 25 (20)ER(DTR) W(3) 25-pin D-Sub, male Signal name of To cable computer link F9GT-HCAB or PL (12) DC24VG F9GT-HCAB1 on PK (13) DC24VG Handy GOT side SW FGR (14) common Wire the power SB (15) SW1 supply, the BK/W (16) SW2 operation switches and R/W (17) SW3 the emergency GR/W (18) SW4 stop BR/W (21 ) ES1 switch. Y/W(22) ES1 BL/W(24) DC24V+ GY/W(25) DC24V+ Drain wire (1) R(4) BK(2) Y(6) BR(7) GR(5) O (10)

5
installation and Wiring of Handy GOT

6
Connection of Peripheral Equipment

10

Specifications

QnA computer link Prepared by the user

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21 ) Y/W(22) BL/W(24) GY/W(25)

Outline

Drain wire (1) To cable BK(2) F9GT-HCAB or W(3) F9GT-HCAB1 on Y(6) Handy GOT side BR(7) O(10)

Introduction

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

10.7

Troubleshooting
For reference, this section summarizes frequently asked questions about connection of the GOT-F900 to the QnA Series PLC. The slightly different messages may be displayed on the F920GOT-K. 1) GOT-F900
Contents of trouble Check points and countermeasures The power of the QnA Series PLC is turned off. "COMMUNICATION ERROR OCCURS" is displayed when a screen changeover or numeric data input is performed on the GOT-F900 screen by a touch key *1. *1 No touch key is available on the F920GOT-K. Cause Communication is disabled because the power of the QnA Series PLC is turned off. Countermeasures Turn on the power. Something is wrong with the cable between the GOTF900 and the QnA Series PLC. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. Changeover to a nonexistent screen by a touch key or the QnA Series PLC was tried. "DISPLAY SCREEN IS NOT AVAILABLE." Cause The changeover destination screen has not been is displayed on the created yet. GOT-F900 screen. Countermeasures Create the screen. "DISPLAY SCREEN IS NOT AVAILABLE. (NO. ####)" is displayed on the GOT-F900 screen. A nonexistent screen was tried to be displayed. Cause The screen No. #### has not been created yet. Countermeasures Create the screen. From From 6.00 or 4.00 or first first later later product product Earlier than 6.00 Earlier than 4.00 OS version F940W F940 F930 F920

From From From From first first first first product product product product

10-26

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
Contents of trouble Check points and countermeasures A device that does not exist in the QnA Series PLC was referenced. (Example: While an QnA Series PLC is connected, a device exists only in the Q Series PLC is specified for numeric input.) Cause On the changeover destination screen (excluding the head screen), a nonexistent device in the connected QnA Series PLC is specified. Countermeasures Check the devices used on the head screen. When a PLC is not connected, the GOT defaults to the QnA mode. Earlier than 6.00 Earlier than 4.00 OS version F940W F940 F930 F920
Introduction

2
Outline

3
Specifications

There is an error on the screen to be displayed. Cause One of the screen objects is placed outside the available screen area. Countermeasures Check the placement of screen objects. The display screen contains an error. "DISPLAY SCREEN IS NOT AVAILABLE. (NO. ####)" is displayed on the GOT-F900 screen. Causes A device that does not exist in the connected PLC is referenced on the screen No. ####, or one of the screen objects is placed outside the available screen area. Countermeasures Check the devices used and placement of screen objects.

10-27

Connection of MELSEC-QnA Series PLC

Connection of MELSEC-A Series PLC

Connection of MELSEC-F FX Series PLC

Connection of Two or More GOT Units

From From 6.00 or 4.00 or first first later later product product

Connection of Peripheral Equipment

installation and Wiring of Handy GOT

"DISPLAY SCREEN IS NOT AVAILABLE." Cause is displayed on the Check for the A or QnA Series was executed, the GOT-F900 screen. connection mode was automatically changed over, then the device range was checked. This error occurs when the device range set on the changeover destination screen (excluding the head screen) is beyond the range for the A Series. Countermeasures Connect the PLC.

4
installation and Wiring of F940GOT

10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

Contents of trouble

Check points and countermeasures There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. A device that does not exist in the QnA Series PLC was referenced. (Example: While the QnA Series PLC was connected, a device provided only in the Q Series PLC was specified for numeric input.) Cause On the head screen, a nonexistent device in the connected QnA Series PLC is specified. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Check the devices used on the head screen. While the QnA Series PLC is not connected, the connection mode for the FX2 Series PLC is selected. Cause Check for the A or QnA Series was executed, the connection mode was automatically changed over, then the device range was checked. This error occurs when the device range set on the head screen is beyond the range for the A Series. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Connect the PLC. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software.

OS version F940W F940 F930 F920

Earlier than 6.00

Earlier than 4.00

"DATA IS NOT FOUND." is displayed on the GOT-F900 screen.

From From 6.00 or 4.00 or first first later later product product

"CAN NOT WRITE TO PLC MEMORY." is displayed on the GOT-F900 screen. "CAN NOT WRITE." is displayed on the GOT-F900 screen.

This error is not displayed.

Earlier than 1.10

Earlier than 6.10

Earlier than 4.10

From first product

This error is not displayed.

1.10 or 6.10 or 4.10 or later later later

"CAN NOT USE THE FUNCTION WHILE PROTECTED." is This error is not displayed. displayed on the GOT-F900 screen. "PLC IS RUNNING." is displayed on the GOT-F900 screen. This error is not displayed.

From From From From first first first first product product product product From From From From first first first first product product product product

10-28

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

1
2) Software
Contents of trouble Check points and countermeasures QnA PLC, bar code reader or printer is connected. Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures For monitoring or transferring sequence programs, set a bar code reader to invalid and a printer to "DON'T USE". If the PLC is connected, select the GOT-F900 equipped with two built-in RS-232C channels. Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. QnA computer link, bar code reader or printer is connected. Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures In the GOT-F900, select by hand "SELECT MODE"-"OTHER MODE"-"DATA TRANSFER". Or set a bar code reader to invalid and a printer to "DON'T USE". Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The connected cable is not proper. Or cable connection is not correct. Countermeasures Check the cable.
Introduction

2
Outline

4
installation and Wiring of F940GOT

5
installation and Wiring of Handy GOT

Screen creation software

Communication with the screen creation software and screen data cannot be transferred.

6
Connection of Peripheral Equipment

7
Connection of Two or More GOT Units

8
Connection of MELSEC-F FX Series PLC

9
Connection of MELSEC-A Series PLC

10
Connection of MELSEC-QnA Series PLC

10-29

Specifications

In the personal computer connected to the GOT-F900, sequence Software programs cannot be monitored or such as GX transferred. Developer Communication with the sequence and FX/WIN software is disabled. An error message is displayed (only in QnA CPU direct connection).

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-QnA Series PLC 10

MEMO

10-30

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11. Connection of MELSEC-Q Series PLC
This chapter explains connection of the GOT-F900 Series display unit to the Q Series PLC (Q mode). When connecting the Q Series PLC in the A mode or in the computer link for A, refer to chapter 9. Connection Procedure This section introduces the procedure to connect the GOT-F900 to the Q Series PLC.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

1. Preparation
Item name System Condition System Configuration Description You can learn the connection availability as well as the version of the GOT-F900 OS and the screen creation software. You can select the configuration between the GOT and the Q Series PLC/computer link unit as well as proper cables. Reference 11.1 11.2

13
Connection of FREQROL Inverter

Item name

Description

Reference 11.3 11.3.1

In the Q computer link unit, the following setting is required. QCPU Selection in Direct When Q connection is selected, the GOT-F900 is automatically set to Connection fixed values. No setting is required in the Q Series PLC. You can learn the communication specifications and the setting. Communicati The contents of setting of computer link on Setting Specifications Setting in Q Serial Communication Unit Setting by GPPW Used Connectors and Connector Covers Setting in Q Multi PLC System Caution on Use of MELSEC-Q Series PLC Setting of Connected Equipment for GOT

How to set the switches in the computer link unit 11.3.2 using the software GX Developer The model names and the manufacturer of the connectors used in the GOT-F900 and the serial 11.3.3 communication unit

You can learn the restrictions in connecting the GOT to the Q Series PLC. Set the PLC type using the GOT or the screen creation software.

11.5 11.6

Item name Cable Diagram Troubleshooting

Description Cable diagrams for Q Series PLC/GOT connection Description of errors and how to fix them

Reference 11.7 11.8

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-1

Connection of FP Series PLC

3. Others

Connection of Machine Controller

You can learn the connection of GOT-F900, setting in screen creation software, and PLC number.

11.4

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

2. Setting

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.1

System Condition
When connecting the Q Series PLC, check the COM port designation, the OS version of the GOT-F900, and the applicable version of the screen creation software. Compatibility when connecting Q Series PLC
GOT-F900 Series F920GOT-K(5V) F920GOT-K(24V) F930GOT F930GOT-K F940GOT F940WGOT F940 Handy GOT F943 Handy GOT COM port RS-422 $ $ $ $ $ $ RS-232C $ $ $ $ $ $ $ Version of screen creation software OS version of GOT-F900 Two or more GT GT 1:1 DU/WIN GOT units Designer2 Designer Connection type $ $ $ $ $ $ $ $ $ $ $ $ *1 *1 1.00 1.20 2.20 4.60 4.10 1.00 4.10 4.10 SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW1-C SW4-26C SW4-F SW4-26C SW4-F SW5-F SW4-F 2.70 2.40 2.70 2.40 2.50 2.40

The following versions or later are compatible with Q00JCPU/Q00CPU/Q01CPU and Q multi PLC system.
Compatible with Q00JCPU, Q00CPU, Q01CPU Q multiple PLC system F920GOT F930GOT F940W F930GOT F940GOT -K -K GOT F94* handy GOT Version of screen creation software GT Designer DU/WIN

Same as above 1.00 4.30 4.60 6.30 1.30 6.30 SW5-P (V. 5.13P)

- "%" in this table indicates that only connection via the programming port of the Q CPU is available, and connection to a serial communication unit is not available. - The screen creation software version corresponds to the model of the GOT-F900 Series. Refer to section 3.2. *1 The RS-232C port for the Handy type GOT is provided inside the rear cover. As a result, environmental protection is lost when using this port and such a connection is not practical. (The Handy GOT can be connected as the final unit in a string of two or more GOTs.)

11-2

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.2 System Configuration
The Q Series PLC can be connected to the GOT through a serial communication unit connection (RS422 or RS-232C) or directly via RS-232C. This section explains the cables and options required in such a system.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

11.2.1

Configuration for Direct Connection (RS-232C)


Connect the GOT-F900 to the programming port of the Q Series PLC. 1) F920GOT-K/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-232C cable
F930GOT

F940GOT

Not enabled with F920GOT-K Connection of two or more GOT units

...

F920GOT-K (5V type)


a) Q Series PLC QCPU direct connection (6-pin MINI DIN) b) RS-232C cable Prepared by the user. Remarks Make sure the total cable extension distance is 3m (9 10) or less.

F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT


a) Q Series PLC QCPU direct connection (6-pin MINI DIN) QC30R2 b) RS-232C cable Remarks

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-3

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

a) Q Series PLC QCPU direct connection

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

2) F943 Handy GOT


GOT-F900 b) RS-232C cable (A) (B) a) Q Series PLC QCPU direct connection

Handy GOT (RS-232C)

(C)

To power supply and operation switches

Use the RS-232C port on the rear face. Connection of two or more GOT units

To RS-232C, power supply and operation switches

Total extension distance: 6m (19' 8") or less

...

a) Q Series PLC QCPU (6-pin MINI DIN)

b) RS-232C cable (A) F9GT-HCAB-""M (B) F9GT-HCAB5-150 (C) F9GT-HCAB1-""M

Remarks

- Make sure that the total cable extension distance "(A) + (B)" or (C) is 6m (19' 8") or less.

11-4

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.2.2 Configuration for Q Computer Link Connection (RS-422)
The GOT-F900 and the serial communication unit can be connected on the "1:1" basis. By connecting the GOT-F900 to a serial communication unit attached to the Q Series PLC, two or more GOT units can be connected. 1) F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-422 cable
F930GOT
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

a) Q Series PLC Q computer link

13
Connection of FREQROL Inverter

14
F940GOT

Connection of two or more GOT units

...

a) Q Series PLC QJ71C24

b) RS-422 cable

Remarks Make sure the total cable extension distance is 30m (98 5) or less.

Two-piece terminal block Prepared by the user. (CH2)

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-5

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

- Applicable Q Series PLC products in the column a) are computer link units equipped with built-in RS-422 interface.

Connection of SYSMAC C Series PLC

Connection of Microcomputer

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

2) F940 Handy GOT


GOT-F900 b) RS-422 cable (A) (B) a) Q Series PLC Q computer link

(A)
Handy GOT (RS-422)

(C)

To RS-422 To power supply and operation switches

To RS-422

(D)
To power supply and operation switches

(E) Use the RS-422 port on the rear face.

To RS-422, power supply and operation switches

Total extension distance: 11.5m (37' 9") or less Connection of two or more GOT units

...

a) Q Series PLC

b) RS-422 cable (A) F9GT-HCAB-""M

Remarks

QJ71C24

(B) Prepared by the user. Two-piece terminal block (C) Prepared by the user. (CH2) (D) F9GT-HCNB (E) F9GT-HCAB1-""M

- Applicable Q Series PLC products in the column a) are computer link units equipped with built-in RS-422 interface. - Make sure that the total cable extension distance "(A) + (B)" or (E) is 11.5m (37' 9") or less.

11-6

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.2.3 Configuration for Q Computer Link Connection (RS-232C)
The GOT-F900 and the serial communication unit can be connected on the "1:1" basis. By connecting the GOT-F900 to a serial communication unit attached to the Q Series PLC, two or more GOT units can be connected. 1) F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-232C cable
F930GOT
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

a) Q Series PLC Q computer link

13
Connection of FREQROL Inverter

Connection of two or more GOT units


F940GOT

14
Connection of Microcomputer

...

a) Q Series PLC AJ71QC24 9-pin D-Sub (CH1)

b) RS-232C cable Prepared by the user.

Remarks Make sure the total cable extension distance is 15m (49 3) or less. Make sure the total cable extension distance is 15m (49 3) or less.

15
Connection of SYSMAC C Series PLC

AJ71QC24-R2

9-pin D-Sub Prepared by the user. (CH1 or CH2)

16
Connection of FLEX-PC N Series PLC

- Applicable Q Series PLC products in the column a) are computer link units equipped with built-in RS-232C interface.

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-7

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

2) F943 Handy GOT


GOT-F900 b) RS-232C cable (A) (B) a) QnA Series PLC Q computer link

(C)
Handy GOT (RS-232C)

To power supply and operation switches

To RS-232C, power supply and operation switches

Total extension distance: 6m (19' 8") or less Use the RS-232C port on the rear face. Connection of two or more GOT units

...

a) Q Series PLC QJ71C24 QJ71C24-R2 9-pin D-Sub (CH1)

b) RS-232C cable (A) F9GT-HCAB-3M (B) Prepared by the user.

Remarks

9-pin D-Sub (C) F9GT-HCAB1-3M (CH1 or CH2)

- In the (C)F9GT-HCAB1-3M shown in the column "b) RS-232C cable", the end on the PLC side is loose wires. - Make sure that the total cable extension distance "(A) + (B)" or (C) is 6 m or less.

11-8

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.3 Setting in Q Serial Communication Unit
In Q computer link connection, the switches in the serial communication unit should be set as described below. When setting the switches for communication with the GOT-F900, use the GX Developer (as described in the next page).
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

11.3.1

Communication Setting Specifications


This section explains the communication specifications. 1) Setting the communication protocol Set the communication protocol so that the COM port of the serial communication unit connected to the GOT-F900 is set to the dedicated (MC) protocol format 5.
Serial communication unit QJ71C24 QJ71C24-R2 COM port CH1(RS-232C) CH2(RS-422) CH1(RS-232C) CH2(RS-232C) Switch Switch 2 Switch 4 Switch 2 Switch 4 5H For communication using binary codes of QnA compatible 4C frame Set value Remarks

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

2) Setting the transmission specifications setting switches Set the transmission specifications setting switches of the serial communication unit to realize the transmission specifications shown in the table below. For the switch setting method, refer to the manual of the serial communication unit.
Item Transmission speed Data bit Data format Parity bit Stop bit Sum check Write in RUN mode Specifications 38400 bps 8 bits Provided (odd) 1 bit Provided Possible 66H (CH1 side: Switch 1 (lower)) (CH2 side: Switch 3 (lower)) Set value 09H Switch CH1 CH2 (CH1 side: Switch 1 (upper)) (CH2 side: Switch 3 (upper))

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

- The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be changed.
b7 b6 b5 b4 b3 b2 b1 b0 CH1 side: Switch 1 (lower) CH2 side: Switch 3 (lower) Bit Description OFF (0) OFF (1) Remarks Make sure to set the CH1 side to OFF. The parity bit is excluded. Vertical parity Valid only when the parity bit is set to "odd" or "even".

17
Connection of Machine Controller

b0 Operation setting Independent Interlocking b1 b2 b3 b4 b5 b7 Data bit Parity bit Odd/even parity Stop bit Sum check code Setting change 7 Not provided Odd 1 Odd Forbidden 8 Provided Even 2 Provided Permitted Permitted

18
Connection of FP Series PLC

b6 Write in RUN mode Forbidden

19
Connection of SLC500 Series PLC

3) Setting the station number setting switch Set to 00H in both the GOT-F900 and the serial communication unit (switch 5). 4) Turning on the power again After setting the QnA computer link, make sure to turn off the power once, then turn it on again. (Even if the RESET switch in the QnA Series PLC is pressed, the changed setting does not become valid.)
11-9

20
Connection of SIMATIC S7 Series PLC

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.3.2

Setting by GPPW
Set the switches in the QJ71C24(-R2) using "I/O assignment" of the GX Developer. For details of the setting, refer to the GX Developer OPERATING MANUAL. 1) I/O assignment Set the type of the unit attached on the base unit and the switches in the QJ71C24(-R2). [Open procedure] "GX Developer" "PLC Parameter" "I/O assignment" [Display contents] a) Type Set "Intelli". b) Model name Set the model name of the attached unit (QJ71C24 or QJ71C24-R2). c) Points Set "32". d) Start XY Set the head I/O signal number (hexadecimal) of the target unit. 2) Switch setting for the I/O unit/intelligent function unit Set the transmission specifications, the communication protocol, etc. between the GOT and connected equipment. [Open procedure] "GX Developer" "PLC Parameter" "I/O assignment" "Switch setting" The contents of setting vary depending on the CH (interface number) of the serial communication unit connected to the GOT. Set the following in accordance with the connected CH.
CH connected to GOT Contents of setting

CH1

CH2

11-10

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.3.3 Used Connectors and Connector Covers
1) Connector on the GOT side For the shape of the connector of the GOT (excluding the Handy GOT), refer to chapter 4 For the shape of the connector of the cable dedicated to the Handy GOT, refer to chapter 5.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

2) Connector on the serial communication unit side The serial communication unit is equipped with the connector having the following model name. Use a suitable counterpart connector. Manufacturer: DDK Ltd.Japan 17L-10090-27-D9AC

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-11

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.4

Setting in Q Multi PLC System (Function version -B or later)


QCPU of function version -B or later (except Q00JCPU, Q00CPU, or Q01CPU) is compatible with the multiple PLC system with 4 GOT units maximum. If the OS version of the GOT-F900 and the screen creation software is compatible with Q multiple PLC system, the screen creation software can specify the monitoring of other GOT through the connected GOT and the CPU.

11.4.1

Direct connection to QCPU


The required setting and PLC numbers for connecting the GOT-F900 to the programming port of QCPU (RS-232C) are shown below. 1) GOT-F900 connection Each QCPU can be connected to the GOT-F900. Connection of two or more GOT units can be performed and 2-port interface function (Program transfer and monitor using GX Developer) is available.
Multiple PLC system

GX Developer

2) Setting in the screen creation software a) GT Designer2 - Select "Common"-"System Environment", then set "PLC Type" to "MELSEC-Q (Multi)". - Click "Auxiliary Setting" in the "System Environment" tree, then give a check mark ($) to "Use Serial Port, Setup, Language, Menu Key." - Click "GOT Setup" in the "System Environment" tree. In "Connection", set "Port" to "RS-422" or "RS-232C", "Type" to "CPU", and "Station No." to "0". b) GT Designer - Select MELSEC-Q (Multi) in the "GOT/PLC Type" dialog box. - Specify RS-422 or RS-232C for Port, CPU for Type, and 0 for Station No. in the "Project Auxiliary Setting" dialog box. c) DU/WIN - The setting is not available.

11-12

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
3) PLC numbers when appointing device PLC numbers from 1 to 4 are allocated (smaller number for the unit closer to the power card). Specify the target PLC number and device number when creating screen data. When using QCPU with GOT-F900 connected, number 0 (own station) can also be specified.
PLC number of CPU 1 2 3 4
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Example: Specify 1 to monitor the unit with PLC number 1. Specify 0 or 3 to monitor the unit with PLC number 3.
Connection of FREQROL Inverter

11.4.2

Connection to serial communication


The required setting and PLC numbers for connecting the GOT-F900 to the serial communication unit attached to the Q multiple PLC system are shown below. Note that there are restrictions on use of the serial communication unit not compatible with the multiple PLC system. See below for its setting. 1) GOT-F900 connection GOT-F900 can be connected to RS-232C or RS-422 port on the serial communication unit. Connection of two or more GOT units can be performed and 2-port interface function (Program transfer and monitor using GX Developer) is available. 2) Serial communication unit compatible with the Q multiple PLC system (Version B or later) a) Setting in the screen creation software GT Designer Select MELSEC-Q (Multi) in the "GOT/PLC Type" dialog box. Specify RS-422 or RS-232C for Port, CPU for Type, and 0 for Station No. in the "Project Auxiliary Setting" dialog box. DU/WIN The setting is not available. b) PLC numbers when appointing device When the PLC No. is set to "0", the control CPU (No.2 in the example shown below) can be monitored. If one of the PLC numbers 1 through 4 is specified, the unit with the corresponding PLC number can be monitored.
Serial communication unit (Function version -B or later) 1 2 3 4 Each CPU can be monitored by specifying PLC number 0 to 4.

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

Set as control PLC (for example)

Version B or later is required for connecting the GOT-F900 to the serial communication unit attached to the Q multiple PLC system (Version B). 4) Control PLC Control PLC is the unit with the number specified under "PLC Parameter" - "I/O assignment" in the GX Developer. (No setting is available in the version of GX Developer not compatible with multiple PLC system.)
11-13

Connection of SIMATIC S7 Series PLC

Connection of SLC500 Series PLC

3) Serial communication unit not compatible with the Q multiple PLC system (Earlier than Version B)

19

20

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.5

Caution on Use of MELSEC-Q Series PLC


When using the GOT-F900 connected to the Q Series PLC, observe the following caution on use.

11.5.1

Restriction in device specification


Word specification of bit devices and bit specification of word devices are not supported in the GOTF900.

11.5.2

Caution when the GOT is connected to the serial communication unit


When the GOT is connected, the CH1 and the CH2 of the serial communication unit cannot be used at the same time. (The setting "CH1: dedicated protocol format 5, CH2: non-procedural protocol" is available.) Accordingly, have in mind that connecting both GOT unit and peripheral equipment for the GPP function or two GOT units to one serial communication unit is not allowed.
Personal computer GOT-F900

Either one CPU Serial communication unit

Personal computer

GOT-F900

GOT-F900

CPU

GOT-F900 Serial communication unit

However, a GOT unit (RS-232C) or a personal computer (USB port) can be connected to the QCPU while the computer link unit has one GOT unit.

11.5.3

Caution when connecting to Q multiple CPU system


1) Restriction in Device Monitor Function of GOT-F900 The PLC number cannot be specified on the screens for device monitor or sampling in HPP mode on the system screen. Hence, GOT-F900 monitors only the connected CPU. When a GOT is connected to the serial communication unit, the GOT monitors only the control PLC. 2) Restriction in Monitored CPU The GOT-F900 should be connected only when the system is configured with QCPU. If the system includes a motion control or CPU of personal computer, GOT-F900 should not be connected because monitoring cannot be performed properly even if it is connected to the QCPU.
GOT-F900

QCPU

CPU of personal computer Motion control

11-14

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
11.5.4 Caution when setting screen creation software
QCPU of function version -B or later (except Q00JCPU, Q00CPU, or Q01CPU) is compatible with the multiple PLC system with 4 GOT units maximum. When two or more QCPU are attached to the main unit, the configuration is called a multiple PLC system, and monitoring of other CPU (number specified) from the CPU connected with the GOT-F900 is enabled. According to the PLC type specified in the screen creation software, the CPU which can be monitored is determined as follows 1) In one unit CPU configuration In the screen creation software, select MELSEC-QnA, A for PLC type.
PLC type in screen creation software and GOT MELSEC-QnA, Q MELSEC-Q (Multi) CPU connected with GOT-F900 $ Other CPU Serial communication unit Only control PLC monitored
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

2) In multiple PLC system In the screen creation software, select MELSEC-Q (Multi) for PLC type.
PLC type in screen creation software and GOT MELSEC-QnA, Q MELSEC-Q (Multi) CPU connected with GOT-F900 $ $ Other CPU $ Serial communication unit Only control PLC monitored $

15
Connection of SYSMAC C Series PLC

PLC number of CPU 1 2 3 4

GOT-F900

16
Connection of FLEX-PC N Series PLC

QCPU 4 units

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-15

Connection of FP Series PLC

Connection of Machine Controller

Other CPU Control PLC

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.6

Setting of Connected Equipment for GOT


The setting for connection to the Q Series PLC can be executed using the GOT-F900 and the screen creation software (GT Designer2, GT Designer or DU/WIN). Setting the Connection Type Set the connection type in accordance with the connected equipment as shown in the table below. Have in mind that computer link for Q (serial communication unit) and Q multiple PLC system requires CPU direct connection.
Connected equipment [classification in manual] [QCPU direct connection] RS-232C port of QCPU card [Q computer link] QJ71C24 (RS-422/RS-232C) QJ71C24-R2 (RS-232C) GOT-F900 CONNECTION Screen creation software Type Programming port Remarks

CPU direct connection (RS-232C) CPU direct connection (RS-422) or CPU direct connection (RS-232C)

Communicates as programming port

1) GOT-F900 Series When the main menu screen change operation is disabled.
Operation Display (screen name) a)While pressing and holding the upper left corner of the screen, The "LANGUAGE" screen appears. turn on the power. Keep holding the upper left corner for about 25 seconds more. Then, press "END" at the upper right corner. The "SET-UP MODE" screen appears. b)Press "PLC TYPE". The "PLC TYPE" screen appears. c) Set the following. PLC TYPE:When monitoring only the connected CPU QnA, Q SERIES When monitoring other CPU via Q multiple PLC system Q (MULTI) SERIES CONNECTION:CPU PORT (RS-422) CPU PORT (RS-232C) DST STATION # (STATION #) : 00 GOT STATION # () :

When the main menu screen change operation is enabled.


Operation a)Press the upper left corner of the screen. (The position to be pressed can be changed in the GOT and the screen creation software.) b)Press "OTHER MODE" on the menu. c) Press "SET-UP MODE" on the menu. Display (screen name) The "SELECT MODE" screen appears.

The "OTHER MODE" screen appears. The "SET-UP MODE" screen appears.

d)Press "PLC TYPE". The "PLC TYPE" screen appears. e)Set the following. PLC TYPE:When monitoring only the connected CPU QnA, Q SERIES When monitoring other CPU via Q multiple PLC system Q (MULTI) SERIES CONNECTION:CPU PORT (RS-422) CPU PORT (RS-232C) DST STATION # (STATION #) : 00 GOT STATION # () :

11-16

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
- When the screen data is transferred to the GOT-F900, the old data including the PLC type, connection type, and station number are overwritten. - The "PLC type" selection item display varies depending on the OS version as follows.
"PLC TYPE" selection item display in GOT GOT-F900 A SERIES 1.00 or later Not available A, QnA SERIES 3.00 or later 2.00 or later Not available A SERIES *1 QnA, Q SERIES 1.00 or later 4.10 or later 4.60 or later 2.20 or later 1.00 or later Available (Select "QnA, Q SERIES".) A SERIES QnA, Q SERIES Q (Multi) SERIES 1.30 or later 6.30 or later 4.60 or later 4.30 or later 1.00 or later Available (Select "QnA, Q SERIES" or "Q (MULTI) SERIES".)
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

F940WGOT OS F930GOT-K version F930GOT F920GOT-K Connection setting availability

F940GOT, Handy GOT 1.00 or later

13
Connection of FREQROL Inverter

*1 Available choices on the menu are changed to "A SERIES" and "QnA, Q SERIES".

14
Display (screen name)
Connection of Microcomputer

2) GT Designer2
Operation [Creation] a)Open GT Designer2. b)Click the [NEW] button. The dialog box shown below is displayed. If it is not displayed, click "System Environment" in the tree displayed in the project work space, then click "System settings" in the tree. The "Select Project" dialog box appears. The "System Environment" dialog box appears.

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
c)Set the following. GOT type: F940WGOT (480 234) F94*GOT (320 240) F93*GOT (240 80) F920GOT (128 64) PLC type: When monitoring only the connected CPU: MELSEC-QnA, Q When monitoring other CPU connected using Q Multi system: MELSEC-Q (Multi) Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F930GOT(24080) F920GOT(12864) Click [OK]. Model name (name) F940WGOT F940GOT Handy GOT F930GOT F930GOT-K F920GOT-K
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-17

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

Operation d)Setting the port (RS-422 or RS-232C) of the GOT-F900 Click "Auxiliary Setting" in the tree of the system environment menu. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($).

Display (screen name) The "Auxiliary Settings" dialog box appears.

Click "GOT Setup" in the tree of the system environment menu.

e)Set the following. Port : RS-422 RS-232C Type : CPU Station No. : 00 GOT Station No. : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination Direct connection to Q CPU Computer link unit for Q Computer link unit for Q Port RS-232C RS-422 The "Select Project" dialog box appears. Type CPU

[Change method] Change the connection type of the already created data as follows. a)Open GT Designer2. b)Click the [Project]-[Open] button. c)Open (read) the screen data to be changed.

The "System d)On the menu, select "Common"-"System Environment". Environment" dialog box - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 on the Q Series PLCs, refer to e) of appears. [Creation] above.

11-18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
3) GT Designer
Operation [Creation] a)Open GT Designer. b)Click the [New] button. Display (screen name) The "Select Project" dialog box appears. The "GOT/PLC Type" dialog box appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
c)Set the following. GOT type: F940WGOT (480 234) <WIDE> F94*GOT (320 240) F93*GOT (240 80) F920GOT (128 64) PLC type: When monitoring only the connected CPU: MELSEC-QnA, Q When monitoring other CPU connected using Q Multi system: MELSEC-Q (Multi) Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) F920GOT(12864) Click [OK]. d)Set CPU direct connection (RS-422/RS-232C) of the GOT-F900. This setting is enabled in the SW4D5C-GOTR-PACKE version A or later. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). The "Project Auxiliary Settings" dialog box appears. Model name F940WGOT F940GOT Handy GOT F930GOT-K F930GOT F920GOT-K
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Click the "Setup" tab.
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-19

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

Operation In the case of SW4D5C-GOTR-PACKE earlier than version A, perform the setting in the GOT-F900. (Set the connection in "CONNECTION" in the GOT-F900.) For the setting method, refer to "1) GOT-F900 Series" on the previous page. e)Set the following. Port : RS-422 RS-232C Type : CPU DST Station No. (Station No.) : 0 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination Direct connection to Q CPU Computer link unit for Q Computer link unit for Q Port RS-232C RS-422 Type CPU

Display (screen name)

[Change method] Change the connection type of the already created data as follows. a)Open GT Designer. b)Click the [Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"GOT/PLC Type". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 or the RS-232C on the Q Series PLCs, refer to e) of [Creation] above.

The "Select Project" dialog box appears.

The "GOT/PLC Type" dialog box appears.

- The "PLC type" selection item display varies depending on the software version as follows.
"PLC type" selection item display in GT Designer GT Designer MELSEC-A SW1-A or later Not available MELSEC-A, QnA SW2-A or later Not available MELSEC-A *1 MELSEC-QnA, Q SW4-F or later MELSEC-A MELSEC-QnA, Q MELSEC-Q (Multi) SW5-P or later (5.13P)

Version Connection setting availability

Available Available (Select "QnA, Q SERIES" (Select "MELSEC-QnA,Q".) or "Q (MULTI) SERIES".)

*1 Available choices on the menu are changed to "A SERIES" and "QnA, Q SERIES".

11-20

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
4) DU/WIN
Operation [Creation] a)Open DU/WIN. b)On the menu, select "File"-"New". Display (screen name) The "Project settings" dialog box appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
c)Set the following. Terminal: F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) F920GOT-BBD5-K PLC System: MELSEC-QnA, Q Select "Terminal" in accordance with the LC display color. Terminal F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) F920GOT-BBD5-K Model name F940WGOT (color) F940GOT (black and white) Handy GOT (black and white) F940GOT (color) Handy GOT (color) F930GOT-K (blue) F930GOT (blue) F920GOT-K (blue) The "Setup Data" dialog box appears.
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

d)Set CPU direct connection (RS-422/RS-232C) of the GOT-F900. On the menu, select "View/Project"-"System Settings"-"Setup Data".

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-21

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

Operation e)Set the following. Port: RS-422 RS-232C Type: CPU DST Station No. (Station No.) : 0 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. Combinations of "Port" and "Type" are as follows. Connection destination Direct connection to Q CPU Computer link unit for Q Computer link unit for Q Port RS-422 RS-232C Type CPU

Display (screen name)

11-22

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
Operation [Change method] Change the connection type of the already created data as follows. a)Open DU/WIN. b)On the menu, select "File"-"Open". c)Select and open (read) the file of the screen data to be changed. d)When changing "Terminal" (GOT-F900), select "View/Project""System Settings"-"Project settings" on the menu. - For the contents of setting, refer to c) of [Creation] above. The "Open" dialog box appears. The "Project settings" dialog box appears. Display (screen name)
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

- The "PLC" selection item display varies depending on the software version as follows.
"PLC System" selection item display in DU/WIN DU/WIN Version Connection setting availability MELSEC-A 2.00 or later Not available MELSEC-A, QnA 2.30 or later Not available MELSEC-A *1 MELSEC-QnA, Q 2.40 or later Available(Select "MELSEC-QnA, Q".)

13
Connection of FREQROL Inverter

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-23

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

*1 Note that the selection item display is changed from "MELSEC-A, QnA" to "MELSEC-A" and "MELSECQnA, Q".

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.7

Cable Diagram
This section explains cable diagrams to connect the GOT-F900 and the Q Series PLC. 1) Cable for the GOT and the Q Series PLC F920GOT-K (5V type) When connecting the F920GOT-K directly to the Q Series PLC, the below cable is required to transfer screen data. For caution on use, refer to section 6.4. Composition of Q Series PLC connection When connecting GOT-F900 to the Q series PLC directly, connects by the following cable.

RS-232C Q CPU direct connection Q Series PLC


: Female type

F920GOT-K
: Male type The connector figure shows the engagement face.

No.

Model name RS-232C

Application
FG

Connection diagram

Application

Q CPU direct connection connection a) Prepared by the user. (Cable length 3m (9'10") or less)

GOT-F900 (Grounding)
5 1 (2) (3) (4) (5) (6) (8) (9)

Resistance per wire: 0.67 or less 9-pin D-Sub, female (Approximately AWG 28 or thicker)

FG (Grounding) Q Series (2) 3 5 (1) (5) 1 (3) 2 (6) 6 4 (4) 6-pin MINI DIN, male

Compoisition for translating screen data to GOT When downloading/uploading the screen data to/from the F920GOT-K(5V type), the following power cable is nessary for supplying 5V DC from the Q series PLC.

RS-422 Power cable Q Series PLC

RS-232C The cable for screen data transmission. Personal computer F920GOT-K
: Female type : Male type The connector figure shows the engagement face.

No.

Model name Power connection

Application
F920GOT-K
1 5

Connection diagram

Application
Q Series
3

GOT power cable Prepared by the user. b) (Cable length 3m (9'10") or less)
Resistance per wire: 0.67 or less (Approximately AWG 28 or thicker)

(5) (9)

(3) (4)

5 1 2 6

9 4

9-pin D-Sub, male

6-pin MINI DIN, male

11-24

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
F920GOT-K (24V type)/F930GOT/F930GOT-K/F940GOT/F940WGOT
: Female type : Male type The connector figure shows the engagement face. Connection of MELSEC-Q Series PLC

No.

Model name RS-232C connection

Application
GOT-F900
5 1

Connection diagram

Application
Q Series
3 5 1 2

12
Connection of FX Series Positioning

Q CPU direct connection a) QC30R2

6 4

9-pin D-Sub, female


FG (Grounding) (1) GOT-F900 (6) 1 5 (2) (7) (5) 6 9

6-pin MINI DIN, male

13
Connection of FREQROL Inverter

RS-422 connection

b)

Q computer link

9-pin D-Sub, male

FG (Grounding) RXD+(RDA) Serial RXD-(RDB) TXD+(SDA) Terminal communication unit side TXD-(SDB) block (PLC side) SG(GND) Signal name of computer link FG (Grounding) (1)CD(DCD) (2)RD(RXD) (3)SD(TXD) (4)DR(DTR) (5)SG(GND) (6)DR(DSR) (7)RS(RTS) (8)CS(CTS) Signal name of computer link

14
Connection of Microcomputer

RS-232C connection

c)

Q computer link Prepared by the user.

9-pin D-Sub, male

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-25

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

(1) GOT-F900 (2) (3) 5 1 (4) (5) (6) 9 6 (7) 9-pin D-Sub, female (8)

Serial communication unit side (PLC side)


1 5

15
6 9

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

2) Cable for the Handy GOT and the Q Series PLC When using the Handy GOT RH model, refer to the cable diagrams below for the RS-422/RS-232C connector, but not the wiring for the power supply, the operation switches, and the emergency stop switch because it is different. For details, refer to Section 5.18.
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram

Application
To F9GT-HCAB3-150

a) F9GT-HCAB-3M F9GT-HCAB-10M

RS-232C connection

Dedicated connector

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.

13

14

25

25-pin D-Sub, male

b)

F9GT-HCAB1-3M F9GT-HCAB1-10M

RS-422 connection RS-232C connection RS-232C connection


Dedicated connector

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.
F9GT-HCAB-""M FG(Grounding) (1) (5)

Loose wires (no connector)

Drain wire (1) BK (2) W (3) GR (5) BR (7) R (4) O (10)

Q Series
3 5 1

F9GT-HCAB

c)

F9GT-HCAB5-150

PL (12) PK (13) FGR (14) SB (15) 25 14 25-pin D-Sub, female BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25) 13 1 F9GT-HCAB1-""M

2 (6) 6 (2) 4 (3) 6-pin MINI DIN, male SHELL DC24VG DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

RS-422 connection

Drain wire (1) BK(2) W(3) Y(6) BR(7) O(10) PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

F9GT-HCAB-""M FG(Grounding) RXD+(RDA) Computer RXD-(RDB) Terminal TXD+(SDA) block link unit side (PLC side) TXD-(SDB) SG(GND) Signal name of computer link DC24VG DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

Q computer link d) Prepared by the user

F9GT-HCAB1-""M

11-26

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
: Female type : Male type The connector figure shows the engagement face. Connection of MELSEC-Q Series PLC

No.

Model name RS-232C connection

Application
Drain wire (1) R(4) BK(2) W(3) O (10) To cable F9GT- GR(5) Y(6) HCAB or F9GTBR(7) PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

Connection diagram

Application

e) Prepared by the user

F9GT-HCAB1-""M

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-27

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

HCAB1 on Handy GOT side

F9GT-HCAB-""M FG(Grounding) (1) CD(DCD) (2) RD(RXD) (3) SD(TXD) Computer link (4) DR(DTR) unit side (5) SG(GND) (PLC side) (6) DR(DSR) (7) RS(RTS) 1 5 (8) CS(CTS) Signal name of computer link 6 9 DC24VG 9-pin D-Sub, male DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

12
Connection of FX Series Positioning

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11.8

Troubleshooting
For reference, this section summarizes frequently asked questions about connection of the GOT-F900 to the Q Series PLC. 1) GOT-F900
Contents of trouble Check points and countermeasures The power of the Q Series PLC is turned off. "COMMUNICATION ERROR OCCURS" is displayed when a screen changeover or numeric data input is performed on the GOT-F900 screen by a touch key *1. *1 No touch key is available on the F920GOT-K. Cause Communication is disabled because the power of the Q Series PLC is turned off. Countermeasures Turn on the power. Something is wrong with the cable between the GOTF900 and the Q Series PLC. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. Changeover to a nonexistent screen by a touch key or the Q Series PLC was tried. "DISPLAY SCREEN IS NOT AVAILABLE." Cause The changeover destination screen has not been is displayed on the created yet. GOT-F900 screen. Countermeasures Create the screen. "DISPLAY SCREEN IS NOT AVAILABLE. (NO. ####)" is displayed on the GOT-F900 screen. A nonexistent screen was tried to be displayed. Cause The screen No. #### has not been created yet. Countermeasures Create the screen. From From 6.00 or 4.00 or first first later later product product Earlier than 6.00 Earlier than 4.00 OS version F940W F940 F930 F920

From From From From first first first first product product product product

11-28

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
Contents of trouble Check points and countermeasures A device that does not exist in the Q Series PLC was referenced. Cause On the changeover destination screen (excluding the head screen), a nonexistent device in the connected Q Series PLC is specified. Countermeasures Check the devices used on the head screen. When a PLC is not connected, the GOT defaults to the A mode. "DISPLAY SCREEN Cause IS NOT AVAILABLE." Check for the A or Q Series was executed, the is displayed on the connection mode was automatically changed over, GOT-F900 screen. then the device range was checked. This error occurs when the device range set on the changeover destination screen (excluding the head screen) is beyond the range for the A Series. Countermeasures Connect the PLC. There is an error on the screen to be displayed. Cause One of the screen objects is placed outside the available screen area. Countermeasures Check the placement of screen objects. The display screen contains an error. "DISPLAY SCREEN IS NOT AVAILABLE. (NO. ####)" is displayed on the GOT-F900 screen. Causes A device that does not exist in the connected PLC is referenced on the screen No. ####, or one of the screen objects is placed outside the available screen area. Countermeasures Check the devices used and placement of screen objects. Earlier than 6.00 Earlier than 4.00 OS version F940W F940 F930 F920
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
From From 6.00 or 4.00 or first first later later product product
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-29

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

Contents of trouble

Check points and countermeasures There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. A device that does not exist in the Q Series PLC was referenced. Cause On the head screen, a nonexistent device in the connected Q Series PLC is specified. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Check the devices used on the head screen. While the Q Series PLC is not connected, the connection mode for the A Series PLC is selected. Cause Check for the A or Q Series was executed, the connection mode was automatically changed over, then the device range was checked. This error occurs when the device range set on the head screen is beyond the range for the Q Series. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Connect the PLC. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software.

OS version F940W F940 F930 F920

Earlier than 6.00

Earlier than 4.00

"DATA IS NOT FOUND." is displayed on the GOT-F900 screen.

From From 6.00 or 4.00 or first first later later product product

"CAN NOT WRITE TO PLC MEMORY." is displayed on the GOT-F900 screen. "CAN NOT WRITE." is displayed on the GOT-F900 screen.

This error is not displayed.

Earlier than 1.10

Earlier than 6.10

Earlier than 4.10

From first product

This error is not displayed.

1.10 or 6.10 or 4.10 or later later later

"CAN NOT USE THE FUNCTION WHILE PROTECTED." is This error is not displayed. displayed on the GOT-F900 screen. "PLC IS RUNNING." is displayed on the GOT-F900 screen. This error is not displayed.

From From From From first first first first product product product product From From From From first first first first product product product product

11-30

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

11
2) Software
Contents of trouble Check points and countermeasures PLC, bar code reader or printer is connected. Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures For monitoring or transferring sequence programs, set a bar code reader to invalid and a printer to "DON'T USE". If the PLC is connected, select the GOT-F900 equipped with two built-in RS-232C channels. Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. Q computer link, bar code reader or printer is connected. Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures In the GOT-F900, select by hand "SELECT MODE"-"OTHER MODE"-"DATA TRANSFER". Or set a bar code reader to invalid and a printer to "DON'T USE". Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The connected cable is not proper. Or cable connection is not correct. Countermeasures Check the cable.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

Screen creation software

Communication with the screen creation software and screen data cannot be transferred.

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

11-31

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

In the personal computer connected to the GOT-F900, sequence Software programs cannot be monitored or such as GX transferred. Developer Communication with the sequence and FX/WIN software is disabled. An error message is displayed.

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of MELSEC-Q Series PLC 11

MEMO

11-32

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
12. Connection of FX Series Positioning Unit (FX(2N)-10/20GM)
This chapter explains connection of the GOT-F900 Series display unit to some FX Series positioning units. Connection Procedure This section introduces the procedure to connect the GOT-F900 to the FX Series positioning unit.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

1. Preparation
Item name System Condition System Configuration Description You can learn the connection availability as well as the version of the GOT-F900 OS and the screen creation software. You can select the configuration between the GOT and the FX Series positioning unit and proper cables. Reference 12.1 12.2

13
Connection of FREQROL Inverter

Item name FX Positioning Unit Selection Cautions Setting of Connected Equipment for GOT

Description When GMCPU connection is selected, the GOT-F900 is automatically set to fixed values. No setting is required in the FX Positioning unit. You can learn the restrictions in connecting the GOT to the FX Series positioning unit. Set the PLC type using the GOT or the screen creation software.

Reference 12.3

12.4

3. Others
Item name Cable Diagram Troubleshooting Description Cable diagrams for FX Series positioning unit/GOT connection Description of errors and how to fix them Reference 12.5 12.6

12.1

System Condition
When connecting the FX Series positioning unit, check the COM port designation, the OS version of the GOT-F900, and the applicable version of the screen creation software. Compatibility when connecting FX Series positioning unit
GOT-F900 Series F920GOT-K F930GOT F930GOT-K F940GOT F940WGOT F940 Handy GOT F943 Handy GOT COM port RS-422 $ $ $ $ $ RS-232C Version of screen creation software OS version Two or more of GOT-F900 GT GT 1:1 DU/WIN GOT units Designer2 Designer Connection type $ $ $ $ $ 4.10 4.60 6.10 1.10 6.10 SW1-C SW1-C SW1-C SW1-C SW1-C SW5-K SW5-26C SW5-K SW5-K SW5-K 2.50 2.70 2.50 2.50 2.50

19
Connection of SLC500 Series PLC

It cannot be connected. Select the F940 handy GOT.

- The screen creation software version corresponds to the model of the GOT-F900 Series. Refer to section 3.2.

20
Connection of SIMATIC S7 Series PLC

12-1

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

2. Setting

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

12.2

System Configuration
This section explains the cables required to connect the FX Series positioning unit (GMCPU connection) via RS-422. (It does not mean connection to the FX Series PLC CPU.)

12.2.1

Configuration for GMCPU direct connection (RS-422)


The FX Series positioning unit is equipped with a built-in RS-422 interface for positioning program. The GOT-F900 can be connected directly to this interface. 1) F930GOT/F930GOT-K/F940GOT/F940WGOT
GOT-F900 b) RS-422 cable
F930GOT

a) FX Series positioning unit GM direct connection

F940GOT

a) GM CPU FX2N-10GM FX2N-20GM FX-10GM FX-20GM E-20GM 20-pin D-Sub 8-pin MINI DIN

b) RS-422 cable FX-50DU-CAB0 FX-50DU-CAB0L FX-30DU-GM-CAB

Remarks Equivalent to the 8-pin MINI DIN port of the FX Series PLC

- The L type cable, FX-50DU-CAB0L (cable with a right angle connector), cannot be used for F930GOT or F930GOT-K.

12-2

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
2) F940 Handy GOT
GOT-F900 b) RS-422 cable (A) (B) a) FX Series positioning unit
Connection of MELSEC-Q Series PLC

12
To power supply and operation switches
Connection of FX Series Positioning

(A)

(C)

13
(A) (E)
To power supply and operation switches
Connection of FREQROL Inverter
Handy GOT (RS-422)

14
(D)
To power supply and operation switches
Connection of Microcomputer

(F)

To RS-422, power supply and operation switches

Total extension distance: 11.5m (37' 9") or less a) GM CPU FX2N-10GM FX2N-20GM 8-pin MINI DIN b) RS-422 cable (A) F9GT-HCAB-""M (B) F9GT-HCAB2-150 (D) F9GT-HCNB (E) FX-50DU-CAB0 or FX-50DU-CAB0-1M (G) F9GT-HCAB1-""M FX-10GM FX-20GM E-20GM 20-pin D-Sub (A) F9GT-HCAB-""M (C) Prepared by the user. (D) F9GT-HCNB (F) FX-30DU-GM-CAB (G) F9GT-HCAB1-""M Equivalent to the 8-pin MINI DIN connector of the FX Series PLC Remarks

- Make sure that the total cable extension distance (A) + "(B) or (C)" is 11.5m (37' 9") or less.

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-3

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Use the RS-422 port on the rear face.

(G)

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

12.3

Cautions on use of FX Series positioning unit


When using the GOT-F900 connected to the FX Series positioning unit, observe the following cautions on use.

12.3.1

Device specification
The device range specifications vary depending on the model of the FX Series positioning unit as shown in the table below.
Device name and Nos. which can be monitored in GOT Input relay (X) *1 X000~X377 Output relay (Y) Y0~Y67 Auxiliary relay (M) M0~M511 Special auxiliary relay (M) M9000~M9175 Data register (D) D0~D3999 File register (D) D4000~D6999 Special data register (D) D9000~D9599 Index register (V, Z) *2 V0~V7 Z0~Z7(32 bits) FX2N-10GM FX-10GM X000~X003 X375~X377 Y00~Y05 M0~M511 M9000~M9175 D0~D1999 D4000~D6999 D9000~D9313 V0~V7 Z0~Z7(32 bits) FX2N-20GM FX-20GM E-20GM X000~X007 X010~X067(when I/Os are extended) X372~X377 Y00~Y67 M0~M511 M9000~M9175 D0~D3999 D4000~D6999 D9000~D9599 V0~V7 Z0~Z7(32 bits)

*1 Input relays (X) X000 to X377 can be read only. *2 When a screen is created using the DU/WIN, only V and Z are available as index registers.

12.3.2

Devices which can be monitored


Among bit devices, specify the device number of input relays (X) and output relays (Y) in octal (1, 2, 3 . . . 7, 10, 11. . . 17, 20). Specify the device number of other bit devices in decimal. When specifying word devices, use the zero suppression function. Only devices described in chapter 3.3 can be specified.

12.3.3

Caution on connection of a programming tool to the FX Series positioning unit


When programming the positioning unit, the GOT-F900 should be disconnected from the programming port of the GMCPU. (Positioning programs cannot be transferred or monitored from a personal computer connected to the GOT-F900.)

12-4

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
12.4 Setting of Connected Equipment for GOT
The setting for connection to the FX Series positioning unit can be executed using the GOT-F900 and the screen creation software (GT Designer2, GT Designer or DU/WIN). 1) GOT-F900 Series When the main menu screen change operation is disabled.
Operation Display (screen name) a)While pressing and holding the upper left corner of the screen, The "LANGUAGE" screen appears. turn on the power. Keep holding the upper left corner for about 25 seconds more. Then, press "END" at the upper right corner. The "SET-UP MODE" screen appears. b)Press "PLC TYPE". c) Set the following. PLC TYPE:FX-GM SERIES CONNECTION:CPU PORT (RS-422) DST STATION # (STATION #) : 00 GOT STATION # () : The "PLC TYPE" screen appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Display (screen name) The "SELECT MODE" screen appears.
Connection of Microcomputer

When the main menu screen change operation is enabled.


Operation a)Press the upper left corner of the screen. (The position to be pressed can be changed in the GOT and the screen creation software.) b)Press "OTHER MODE" on the menu. c) Press "SET-UP MODE" on the menu. d)Press "PLC TYPE". e)Set the following. PLC TYPE: FX-GM SERIES CONNECTION:CPU PORT (RS-422) DST STATION # (STATION #) : 00 GOT STATION # () :

15
The "SET-UP MODE" screen appears. The "PLC TYPE" screen appears.
Connection of SYSMAC C Series PLC

The "OTHER MODE" screen appears.

16
Connection of FLEX-PC N Series PLC

- When the screen data is transferred to the GOT-F900, the old data including the PLC type, connection type, and station number are overwritten.

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-5

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

2) GT Designer2
Operation [Creation] a)Open GT Designer2. b)Click the [NEW] button. The dialog box shown below is displayed. If it is not displayed, click "System Environment" in the tree displayed in the project work space, then click "System settings" in the tree. Display (screen name) The "Select Project" dialog box appears. The "System Environment" dialog box appears.

c)Set the following. GOT type: F940WGOT (480 234) <WIDE> F94*GOT (320 240) F93*GOT (240 80) PLC type: FX(2N)-10GM/20GM Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) Click [OK]. d)Setting the port (RS-422) of the GOT-F900 Click "Auxiliary Setting" in the tree of the system environment menu. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). The "Auxiliary Settings" dialog box appears. Model name (name) F940WGOT F940GOT Handy GOT F930GOT F930GOT-K

Click "Got setup" in the tree of the system environment menu.

12-6

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
Operation e)Set the following. Port : RS-422 Type : CPU Station No. : 00 GOT Station No. : [Change method] Change the connection type of the already created data as follows. a)Open GT Designer2. b)Click the [Project]-[Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"System Environment". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 on the FX Series positioning unit, refer to e) of [Creation] above. The "System Environment" dialog box appears. The "Select Project" dialog box appears. Display (screen name)
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-7

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

3) GT Designer
Operation [Creation] a)Open GT Designer. b)Click the [New] button. Display (screen name) The "Select Project" dialog box appears. The "GOT/PLC Type" dialog box appears.

c)Set the following. GOT type: F940WGOT (480 234) <WIDE> F94*GOT (320 240) F93*GOT (240 80) PLC type: FX(2N)-10GM/20GM Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) Click [OK]. d)Set CPU direct connection (RS-422) of the GOT-F900. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). The "Project Auxiliary Settings" dialog box appears. Model name F940WGOT F940GOT Handy GOT F930GOT-K F930GOT

Click the "Setup" tab.

e)Set the following. Port : RS-422 Type : CPU DST Station No. (Station No.) : 00 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection.

12-8

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
Operation [Change method] Change the connection type of the already created data as follows. a)Open GT Designer. b)Click the [Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"GOT/PLC Type". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 on the FX Series positioning unit, refer to e) of [Creation] above. The "GOT/PLC Type" dialog box appears. Display (screen name) The "Select Project" dialog box appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-9

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

4) DU/WIN
Operation [Creation] a)Open DU/WIN. b)On the menu, select "File"-"New". Display (screen name) The "Project settings" dialog box appears.

c)Set the following. Terminal: F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) PLC System: FX-GM Select "Terminal" in accordance with the LC display color. Terminal F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) Model name F940WGOT (color) F940GOT (black and white) Handy GOT (black and white) F940GOT (color) Handy GOT (color) F930GOT-K (blue) F930GOT (blue)

The "Setup Data" dialog d)Set RS-422 of the GOT-F900. On the menu, select "View/Project"-"System Settings"-"Setup Data". box appears.

e)Set the following. Port: RS-422 Type: CPU DST Station No. (Station No.) : 00 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. [Change method] Change the connection type of the already created data as follows. a)Open DU/WIN. b)On the menu, select "File"-"Open". c)Select and open (read) the file of the screen data to be changed. d)When changing "Terminal" (GOT-F900), select "View/Project""System Settings"-"Project settings" on the menu. For the contents of setting, refer to c) in [Creation] above. For setting of RS-232C/RS-422 of the FX Series positioning unit, refer to e) in [Creation] above. The "Open" dialog box appears. The "Project settings" dialog box appears.

12-10

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
12.5 Cable Diagram
This section explains cable diagrams to connect the GOT-F900 and the FX Series positioning unit 1) Cable for the GOT and the FX Series positioning unit
: Female type : Male type The connector figure shows the engagement face. Connection of MELSEC-Q Series PLC

12
Connection diagram
(1) (2) (4) (5) (6) (7) (9) (2) (7) (6) (3) (1) (4) (5)

No.

Model name

Application
GOT-F900
1 5

Application
FX2N-10GM FX2N-20GM
3 4 1 2 5 8 6 7

9-pin D-Sub, male

8-pin MINI DIN, male


(1) (2) (3) (4) (5) (6) (7) (8) (9) (2) (3) (4) (5) (7) (12) (13) (14) (15) (10) (20)

RS-422 connection

GOT-F900
1 5

FX Series positioning unit b) connection FX-30DU-GM-CAB

10

9-pin D-Sub, male

11

20

20-pin D-Sub, male

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-11

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

FX-10GM E-20GM FX-20GM

Connection of FREQROL Inverter

RS-422 FX Series connection positioning unit connection a) FX-50DU-CAB0 FX-50DU-CAB0/EN FX-50DU-CAB0-1M FX-50DU-CAB0L

Connection of FX Series Positioning

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

2) Cable for the Handy GOT and the FX Series positioning unit When using the Handy GOT RH model, refer to the cable diagrams below for the RS-422/RS-232C connector, but not the wiring for the power supply, the operation switches, and the emergency stop switch because it is different. For details, refer to Sevtion 5.18.
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram

Application
To F9GT-HCAB2-150 or F9GT-HCAB3-150 1 13

a)

F9GT-HCAB-3M F9GT-HCAB-10M

RS-232C connection

Dedicated connector

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user. The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.
F9GT-HCAB-""M FG(Grounding)

14 25 25-pin D-Sub, male

b)

F9GT-HCAB1-3M connection F9GT-HCAB1-10M RS-232C


connection RS-422 connection

RS-422

Dedicated connector

Loose wires (no connector)

F9GT-HCAB2-150 c)
The diagram on the right shows the wiring of the RS-422 signals. For wiring of the operation switches and the power supply, refer to chapter 5.

Drain wire (1) To cable F9GT-HCAB BK (2) on Handy GOT side W (3) 1 13 Y (6) BR(7) BL (8) 25 14 GR(9) 25-pin D-Sub, female O (10) PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

FX2N-10GM FX2N-20GM 3 4 (2) 6 (1) 1 (7) 7 2 (4) 8 (6) 5 (5) (3) 8-pin MINI DIN, male SHELL DC24VG DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

F9GT-HCAB1-""M

RS-422 connection

Prepared by the user d)


The diagram on the right shows the wiring of the RS-422 signals. For wiring of the operation switches and the power supply, refer to chapter 5.

Drain wire (1) BK (2) W (3) R (4) To cable F9GT-HCAB GR(5) Y (6) on Handy GOT side BR(7) 1 13 BL (8) GR(9) O (10) 25 14 25-pin D-Sub, female

F9GT-HCAB-""M FG(Grounding) (2) (12) (4) FX-10GM (5) E-20GM (3) FX-20GM 10 (13) 1 (14) (15) (7) 11 20 (10) 20-pin D-Sub, male (20) (8) (21) Hood DC24VG DC24VG SW common Wire the power SW1 supply, the SW2 operation switches and SW3 the emergency SW4 stop ES1 switch. ES1 DC24V+ DC24V+

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25) F9GT-HCAB1-""M

12-12

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
12.6 Troubleshooting
For reference, this section summarizes frequently asked questions about connection of the GOT-F900 to the FX Series positioning unit. 1) GOT-F900
Contents of trouble Check points and countermeasures The power of the FX Series positioning unit is turned off. Cause Communication is disabled because the power of the FX "COMMUNICATION Series positioning unit is turned off. ERROR OCCURS" is Countermeasures displayed when a From From From Turn on the power. screen changeover or first first first numeric data input is Something is wrong with the cable between the GOT-F900 and product product product the FX Series positioning unit. performed on the GOT-F900 screen. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. Changeover to a nonexistent screen by a touch key or the FX Series positioning unit was tried. OS version F940W F940 F930
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

12-13

Connection of SIMATIC S7 Series PLC

Connection of SLC500 Series PLC

Cause One of the screen objects is placed outside the available screen area. Countermeasures Check the placement of screen objects.

19

20

Connection of FP Series PLC

Cause On the changeover destination screen (excluding the head screen), a nonexistent device in the connected FX Series "DISPLAY SCREEN positioning unit is specified. IS NOT AVAILABLE." Countermeasures is displayed on the Check the devices used on the head screen. GOT-F900 screen. There is an error on the screen to be displayed.

Earlier than 6.00

Earlier than 4.00

Connection of Machine Controller

A device that does not exist in the FX Series positioning unit was referenced. (Example: While the FX2N-10GM was connected, a device provided only in the FX2N-20GM was specified for numeric input.)

Connection of FLEX-PC N Series PLC

A nonexistent screen was tried to be displayed. "DISPLAY SCREEN IS NOT AVAILABLE. Cause (NO. ####)" is The screen No. #### has not been created yet. displayed on the GOT Countermeasures F900 screen. Create the screen.

From 6.00 or 4.00 or first later later product

Connection of SYSMAC C Series PLC

"DISPLAY SCREEN IS NOT AVAILABLE." Cause is displayed on the The changeover destination screen has not been created yet. GOT-F900 screen. Countermeasures Create the screen.

Earlier than 6.00

Earlier than 4.00

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

Contents of trouble

Check points and countermeasures The display screen contains an error.

OS version F940W F940 F930

"DISPLAY SCREEN Causes IS NOT AVAILABLE. A device that does not exist in the connected PLC is (NO. ####)" is referenced on the screen No. ####, or one of the screen displayed on the GOTobjects is placed outside the available screen area. F900 screen. Countermeasures Check the devices used and placement of screen objects. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. A device that does not exist in the FX Series positioning unit was referenced. (Example: While the FX2N-10GM was connected, a device provided only in the FX2N-20GM was specified for numeric input.) "DATA IS NOT FOUND." is displayed Cause On the head screen, a nonexistent device in the connected on the GOT-F900 FX Series positioning unit is specified. screen. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Check the devices used on the head screen. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. "CAN NOT WRITE TO PLC MEMORY." is This error is not displayed. displayed on the GOTF900 screen. "CAN NOT WRITE." is displayed on the GOT-F900 screen. This error is not displayed.

From 6.00 or 4.00 or first later later product

Earlier than 6.00

Earlier than 4.00

From 6.00 or 4.00 or first later later product

Earlier than 1.10

Earlier than 6.10

Earlier than 4.10

1.10 or 6.10 or 4.10 or later later later

"CAN NOT USE THE FUNCTION WHILE PROTECTED." is This error is not displayed. displayed on the GOTF900 screen. "PLC IS RUNNING." is displayed on the GOT-F900 screen. This error is not displayed.

From From From first first first product product product From From From first first first product product product

12-14

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

11
2) Software
Contents of trouble Check points and countermeasures An FX Series positioning unit, bar code reader or printer is connected. Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures In the GOT-F900, select by hand "SELECT MODE"-"OTHER MODE"-"DATA TRANSFER". Or set a bar code reader to invalid and a printer to "DON'T USE". Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The connected cable is not proper. Or cable connection is not correct. Countermeasures Check the cable.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

12-15

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

Screen creation software

Communication with the screen creation software and screen data cannot be transferred.

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FX Series Positioning Unit (FX(2N)-10/20GM) 12

MEMO

12-16

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13. Connection of FREQROL (S500/E500/A500) Inverter
This chapter explains the procedure to connect the GOT-F900 Series display unit to the FREQROL Series (S500/E500/A500) inverter. Connection Procedure This section introduces the procedure to connect the GOT-F900 to the FREQROL Series inverter.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

1. Preparation
Item name System Condition System Configuration Description You can learn the connection availability as well as the version of the GOT-F900 OS and the screen creation software. You can select the configuration between the GOT and the FREQROL inverter and proper cables. Reference 13.1 13.2

13
Connection of FREQROL Inverter

Item name Setting in FREQROL Inverter Cautions on Use of FREQROL Series Inverter Correspondence between GOT Devices and Parameters FREQROL Inverter Parameter List Setting of Connected Equipment for GOT

Description When INVCPU connection is selected, the GOT-F900 is automatically set to fixed values. No setting is required in the FRQROL inverter. You can learn the restrictions in connecting the GOT to the FREQROL inverter. You can learn correspondence between GOT devices and parameters as well as communication. You can compare parameters of the A500, the E500 and the S500. Set the PLC type using the GOT or the screen creation software.

Reference 13.3

13.4

13.5

13.6 13.7

3. Others
Item name Cable Diagram Troubleshooting Description Cable diagrams for FREQROL inverter/GOT connection Description of errors and how to fix them Reference 13.8 13.9

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-1

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

2. Setting

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.1

System Condition
When connecting the FREQROL Series inverter, check the COM port designation, the OS version of the GOT-F900, and the applicable versions of the screen creation software. Compatibility when connecting FREQROL (S500/E500/A500) Inverter
GOT-F900 Series F920GOT-K F930GOT F930GOT-K F940GOT F940WGOT F940 Handy GOT F943 Handy GOT COM port RS-422 $ $ $ $ $ RS-232C OS version Two or more of GOT-F900 GT 1:1 GOT units Designer2 $ $ $ $ $ 4.10 4.60 6.10 1.10 6.10 SW1-C SW1-C SW1-C SW1-C SW1-C Connection type Version of screen creation software GT Designer SW5-K SW5-26C SW5-K SW5-K SW5-K DU/WIN 2.50 2.70 2.50 2.50 2.50

It cannot be connected. Select the F940 handy GOT.

- The screen creation software version corresponds to the model of the GOT-F900 Series. Refer to section 3.2.

13.2

System Configuration
This section explains the cables required to connect the FREQROL Series inverter through INV direct connection (RS-422). (Up to 10 FREQROL Series inverters can be connected to one GOT-F900 unit.)

13.2.1

Configuration for CPU Direct Connection (RS-422)


The GOT-F900 can be connected to the FREQROL Series inverter equipped with built-in PU port (A500/ E500 Series), the FR-A5NR computer link option (A500 Series) or the S500 Series equipped with the RS-485 communication function. The GOT-F900 can be directly connected to the interface to control two or more inverters. 1) F930GOT/F930GOT-K/F940GOT/F940WGOT a) When one inverter is connected
GOT-F900 c) RS-422 cable (cable 10BASE-T)
F930GOT

a) FREQROL inverter INV direct connection

b) Option c) RS-422 cable (twisted pair cable) FR-A5NR

F940GOT

13-2

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
b) When two or more inverters are connected UP to 10 inverters can be connected through RS-422.
GOT-F900 Station number 0 Station number 1 Inverter Inverter Station number 9 Inverter
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

..... The FR-A5NR can be used in the A500 Series. Terminal resistor

13
Connection of FREQROL Inverter

PU port Distributor

PU port

PU port

Prepared by the user. Cable 10BASE-T (twisted pair cable for the FR-A5NR)

14
Connection of Microcomputer

a) INV S500 E500 A500 A500 PU port

b) Option

c) RS-422 cable Prepared by the user. (cable 10BASE-T)

Remarks It is called "RS-485 communication port".

FR-A5NR

Prepared by the user. (twisted pair cable)

Option for computer link connection is required.

c) Attaching a terminal resistor Communication may be affected by reflection depending on the transmission speed and the transmission distance. If communication is hindered by this reflection, provide a terminal resistor. - When the PU port or the RS-485 port is used for connection Attach a terminal resistor between the pin number 3 (RDA) and the pin number 6 (RDB). Because the terminal resistor cannot be attached, use the distributor. Attach the terminal resistor only to the inverter located farthest from the GOT-F900. (terminal resistor: 100,1/2W) - When the FR-A5NR is used for connection Attach a terminal resistor chip (included with the FR-A5NR) between the terminals RDB and RDR of the last inverter.

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-3

Connection of FP Series PLC

Connection of Machine Controller

The A500 Series can be connected using the PU port or the option for computer link connection. Though the port of the S500 Series is the RS-485 communication port, it is called "PU port" in this manual.

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

For connection between the GOT-F900 and the distributor, refer to a) on the previous page. For connection between the distributors, prepare connectors and cables while referring to section 13.8 later. Do not use the commercial straight connection type Ethernet 10BASE-T cable (Category 3 or 5). (If this cable is used, inverters will have a short circuit because the pins number 2 and 8 are connected to power supply.) Sample products (connector, cable, and distributor) are introduced in Cable Diagram in this chapter.

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

2) F940 Handy GOT (RS-422) a) When one inverter is connected


GOT-F900 c) RS-422 cable (A) (B) a) Inverter INV direct connection

25pin D-Sub (A) (C)

To power supply and operation switches

Handy GOT (RS-422)

25pin D-Sub (A) (E)

To power supply and operation switches

Use the RS-422 port on the rear face.

9pin D-Sub

(D)

To power supply and operation switches

(F)

(G)

+
b) Option
To RS-422, power supply and operation switches

Total extension distance: 11.5m (37' 9") or less

FR-A5NR

13-4

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
b) When two or more inverters are connected Up to 10 inverters can be connected through RS-422.
GOT-F900
Handy GOT (RS-422)

Station number 0 Station number 1 Inverter Inverter

Station number 9 Inverter

..... The FR-A5NR can be used in the A500 Series. Terminal resistor

Distributor Prepared by the user. Cable 10BASE-T (twisted pair cable for the FR-A5NR) Total extension distance: 11.5m (37' 9") or less

a) INV S500 E500 A500 PU port

b) Option

c) RS-422 cable (A) F9GT-HCAB-""M (B) Prepared by the user. (cable 10BASE-T) (D) F9GT-HCNB (E) Prepared by the user. (cable 10BASE-T) (G) F9GT-HCAB1-""M

Remarks It is called "RS-485 communication port".

A500

FR-A5NR

(A) F9GT-HCAB-""M (C) Prepared by the user. (twisted pair cable) (F) Prepared by the user. (twisted pair cable) (G) F9GT-HCAB1-""M

Option for computer link connection is required.

The A500 Series can be connected using the PU port or the option for computer link connection. Though the port of the S500 Series is the RS-485 communication port, it is called "PU port" in this manual. c) Attaching a terminal resistor Communication may be affected by reflection depending on the transmission speed and the transmission distance. If communication is hindered by this reflection, provide a terminal resistor. - When the PU port or the RS-485 port is used for connection Attach a terminal resistor between the pin number 3 (RDA) and the pin number 6 (RDB). Because the terminal resistor cannot be attached, use the distributor. Attach the terminal resistor only to the inverter located farthest from the GOT-F900. (terminal resistor: 100 1/2W) - When the FR-A5NR is used for connection Attach a terminal resistor chip (included with the FR-A5NR) between the terminals RDB and RDR of the last inverter.

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-5

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

For connection between the GOT-F900 and the distributor, refer to a) on the previous page. For connection between the distributors, prepare connectors and cables while referring to section 13.8 later. Do not use the commercial straight connection type Ethernet 10BASE-T cable (Category 3 or 5). (if this cable is used, inverters will have a short circuit because the pins number 2 and 8 are connected to power supply.) Sample products (connector, cable, and distributor) are introduced in Cable Diagram in this chapter.

Connection of Microcomputer

Connection of FREQROL Inverter

PU port

PU port

PU port

Connection of FX Series Positioning

Connection of MELSEC-Q Series PLC

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.3

Setting in FREQROL Inverter


When connecting the FREQROL Series inverter, the parameter should be set as described below.

13.3.1

Communication Setting Specifications


This section explains the contents to be set in the FREQROL Series inverter. 1) Setting the transmission specifications Set the transmission specifications of the inverter to realize the transmission specifications shown in the table below. For the setting method, refer to the manual of the inverter. For the communication setting parameters, refer to the next section.
Item Communication speed Control protocol Communication method Character system Data bit Terminator Data format Check system Parity check Sum check RS-422 19200 bps Asynchronous system Half-duplex method ASCII (7 bits) 7 bits CR: Provided, CF: Not provided Provided (odd) Provided Not provided 1 bit

Waiting time setting Stop bit length

The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be changed.

2) Setting the station number For the communication setting parameters, refer to the next section. Setting in the Inverter Set each station number in the range from 00 to 31 while making sure that one station number is used only once. In the case of RS-422 connection, 10 inverters can be connected at maximum. The station number can be set without regard to the inverter connection order. No problem is expected even if station numbers are not consecutive.
Station number 3 Station number 0 Station number 1 Station number 21 Station number 6

GOT-F900

Example of station number setting

Setting in the GOT-F900 Leave the station number setting in "00".

13-6

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.3.2 Setting Examples
1) Communication port and corresponding parameters When connecting the GOT-F900 to the inverter, parameters corresponding to the communication port should be set. S500 Series Remove the front cover. E500 Series Remove the operation panel. A500 Series Remove the operation panel.
PU port
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
PU port RS-485 port (PU port) Model Communication port GOT connection destination PU port PU port RS-485 port Parameters corresponding to inverter Pr117 to Pr124 Pr117 to Pr124 n1 to n12 (Remove the front cover.)
Connection of FREQROL Inverter

FR-A5NR

14
Connection of Microcomputer

A500 Series Built in inverter Option E500 Series Built in inverter S500 Series Built in inverter (only in certain models)

FR-A5NR computer link option Pr331 to Pr342

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-7

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

2) Communication setting in inverter Set the following parameters using the PU (parameter unit) to realize the communication specifications of the GOT-F900. Though these parameters can be monitored from the GOT-F900, do not change them. If they are changed, communication with the GOT-F900 is disabled.
Parameter number S500 (RS-485) n1 n2 n3 A500 (PU) Pr. 117 Pr. 118 Pr. 119 A500 (FR-A5NR) Pr. 331 Pr. 332 Pr. 333 E500 (PU) Pr. 117 Pr. 118 Pr. 119 Communication parameter Inverter station number Communication speed Stop bit length Setting Set value 00~31 192 10 Contents of setting 10 inverters can be connected at maximum. 19200 bps Data length: 7 bits Stop bit: 1 bit 0: No parity check 1: Odd parity 2: Even parity

n4

Pr. 120

Pr. 334

Pr. 120

Parity check yes/no

n5

Pr. 121

Pr. 335

Pr. 121

Communication retry count Communication check time interval Waiting time setting CRE LF yes/no selection Operation mode Link start mode selection E2PROM write selection Frequency setting command selection

S500: A500:9999 No abnormal stop E500:9999 S500:999 A500:999 E500:999 0 1 0 1 0 999 Communication check stop 0ms CR: Provided, LF: Not provided External operation mode at power ON Computer link Write to RAM and EEPROM Volume disabled

n6 n7 n11 Pr.79 n10 n12

Pr. 122 Pr. 123 Pr. 124 Pr. 79 Pr. 342

Pr. 336 Pr. 337 Pr. 341 Pr. 79 Pr. 340 Pr. 342

Pr. 122 Pr. 123 Pr. 124 Pr. 79 Pr. 146

a) S500 Series - Parameters n1 to n7 and n10 to n12 are set in the built-in parameter unit. - When parameters are monitored from the GOT-F900, they correspond to parameters Pr. 331 to Pr. 337 and Pr340 to Pr. 342 respectively.

13-8

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.3.3 Inverter Connector Specifications
1) Pin layout in the PU port
Pin number 1 2 3 4 5 6 7 8 Signal name GND (SG) (P5S) RXD+ (RDA) TXD- (SDB) TXD+ (SDA) RXD- (RDB) GND (SG) (P5S) Not used (1) Not used Remarks
Connection of MELSEC-Q Series PLC

When seen from the front of the inverter (receptacle side)


(8)

12
Connection of FX Series Positioning

Modular jack

13
Connection of FREQROL Inverter

The contents inside ( ) indicate symbols described in the inverter manual. The pins number 2 and 8 (P5S) are connected to the power supply for an operation panel or a parameter unit. Do not use them in RS-422 communication. 2) Terminal block layout in the FR-A5NR computer link option Attach this option to the A500 Series.

14
Connection of Microcomputer

15
Terminal block Screw size: M3
SDA SDB RDA RDB RDR SG

Terminal symbol

Connected to the GOT-F900.

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-9

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.3.4

Specification of Station Number in Creating Screen


An inverter can be selected out of multiple units concurrently used by setting the station number under numerical setting in screen creation for GOT-F900. The station number specified in the screen creation software corresponds to the station number specified for the parameter in an inverter. There are a direct and an indirect methods to specify the station number when creating a screen. If an individual screen is created for each inverter, it is a direct specification. Only one number corresponding to the inverter can be selected on one screen in order to edit its numerical value. If one screen is created for selecting an unit out of multiple inverters to edit its value, it is an indirect specification. It is more effective in screen creation because the inverter of which the numerical value is to be changed can be selected on one screen using the GOT-F900 internal data register (GD). 1) Direct specification When setting the device, specify the station number of the inverter of which data is to be changed. Setting range: 0 to 31 2) Indirect specification When setting the device, indirectly specify the station number of the inverter of which data is to be changed using the 16-bit GOT internal data register (GD100 to GD115). Setting range: 100 to 115 (Corresponds to each devive from GD100 to GD115) Setting example
Screen on GOT-F900 STATION NUMBER ### Numbers are specified where ### are indicated. When setting GD100

PROGRAM OPERATION ### PARAMETER DISPLAY ###

PG0:100 Pr0:100

Indicate GD100

a) Set the GOT internal data register (GD100) as the station number under numerical setting in the screen creation software. (Upper) b) Specify the device of the parameter in the inverter of which numerical value is to be displayed or edited as follows: PG0 (parameter) for Device, 100 for Station number (Middle) Pr0 (parameter) for Device, 100 for Station number (Lower) c) The parameter (PG0 and Pr0) of the inverter with the station number corresponding to GD100 is displayed.

13-10

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.4 Cautions on Use of FREQROL Series Inverter
When using the GOT-F900 connected to the FREQROL Series inverter, observe the following cautions on use.
Connection of MELSEC-Q Series PLC

Devices correspond to parameters of the FREQROL Series inverter. Accordingly, the device range specifications vary depending on the model. For the details of parameters, refer to section 13.6.
Device names and devices which can be monitored in GOT Control status (S) GOT internal bit register (GB) Alarm code (A) Parameter (Pr) Program operation (PG) Special parameter (SP) GOT internal data register (GD) a) Unsigned 16-bit $ $ $ $ $ b) Screen changeover $ c) System information/ control device $ $ d) Status monitor % $ $ $ $ e) Time switch f) Others $ $ $ $ $ $

In screen changeover, GOT internal data registers (GD) can be specified. Only GOT internal data registers (GD) can be specified for the system information of the GT Designer. GOT internal bit registers (GB) and GOT internal data registers (GD) only can be specified for control devices of the DU/WIN. In the status monitoring function, the alarm code (A) device cannot be specified as the operation device (word SET). In the control status (S) device, only one operation (bit) device can be specified. Because the time switch cannot use the bit device control status (S), this function is not available. The alarm code (A) device cannot be specified in the following devices. Recipe function Write device of operation panel (word SET) Bar code Numeric input ASCII input Operation device of touch key (word SET) Device for storing number of histories of alarm history Device for storing number of occurrences of alarm list

13.4.2

Changeover from the GOT (communication) to the PU operation mode


Not available in the S500 Series. Available in the E500 Series. Not available in the A500 Series if the GOT is connected to the communication board FR-A5NR.

13.4.3

When "8888" or "9999" is set to a parameter (Pr) of the inverter


Numbers "8888" and "9999" have special meaning respectively. When specifying such numbers from the GOT-F900, specify them as follows.
Set value on inverter side 8888 9999 Value to be specified in GOT-F900 65520 65535

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-11

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Among word devices, only unsigned 16-bit numeric values can be used. GOT internal data registers (GD) are excluded.

Connection of Microcomputer

Connection of FREQROL Inverter

Connection of FX Series Positioning

13.4.1

Device specification

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.4.4

Specification of the program operation (PG) devices


When setting the start time (PG10 to PG19, PG40 to PG49, PG70 to PG79), specify the hour or the minute to the upper 8 bits, and specify the minute or the second to the lower 8 bits. Example: When setting "13:35"
Time to be specified Convert the hour and the minute to hexadecimal number respectively. Add the upper bits and the lower bits. 13 (hour) H0D 35 (minute) H23 Remarks Hexadecimal (HEX)

Input "H0D23" or "3363".

13.4.5

Caution on setting of the calibration parameters (Pr900 to Pr905)


When setting the calibration parameters (Pr900 to Pr905), the following value should be written to the second extension parameter (SP108) depending on the used device number and inverter model.
Value to be written to second extension parameter (SP108) H00 H01 H02 Offset/gain Analog Analog value of terminal Description

13.4.6

Restriction in simultaneous specification of PG and Pr devices on one screen


When creating a screen of the GOT-F900, specify either program operation (PG) device or parameter (Pr. 900 to Pr. 905) device. Do not specify both on one screen.

13.4.7

Caution on connecting to the PU port (only in the E500 and the A500)
When the power of the inverter is turned on, the external operation mode is automatically selected. In order to rewrite values of parameters, etc. in the GOT-F900, changing operation mode to "PU operation" in advance is required. To change the operation mode, write "2" to the special parameter SP123.

13-12

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.5 Correspondence Between Devices of GOT and Parameters
The devices of the GOT-F900 correspond to the parameters and the communication data of the inverter as shown in the following table. For the device range, refer to section 3.3.
Device name in GOT-F900 Function of inverter When the inverter status monitor (read) and the operation command (write) of the inverter are changed over by instruction codes, b0 to b7 correspond to devices S0 to S7 and can be read/written. [RD]: Read enabled [WR]: Write enabled [RD/WR]: Read and write enabled Item Instruction code Contents of data H00 to HFF: Operation command operation b7 b0 00000 010 (In the case of example 1) The examples below show cases in the A500 Series. Example 1: H02 : During forward rotation Example 2: H80 : Stop due to alarm b0: Inverter running (RUN)* b1: Forward rotation (STF) b2: Reverse rotation (STR) b3: Up to frequency (SU)* b4: Overload (OL)* b5: Momentary stop (IPF)* b6: Frequency detection (FU)* b7: Alarm occurrence* As to the signals marked with "*", the output signal varies depending on the setting of Pr. 190 to Pr. 195 (output terminal function selection). H00 to HFF: Operation command operation b15 b7 b0 0000000000000 010 (In the case of example 1) The examples below show cases in the A500 Series. Example 1: H02 : Forward rotation Example 2: H80 : Output stop b0: Current input selection (AU)* b1: Forward rotation (STF) b2: Reverse rotation (STR) b3: Low speed (RL)* b4: Middle speed (RM)* b5: High speed (RH)* b6: Second acceleration/deceleration (RT)* b7: Output stop (MRS) As to the signals marked with "*", the input signal varies depending on the setting of Pr. 180 to Pr. 186 (input terminal function selection).
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

Control status (S)

Operation command (WR)

HFA

19
Connection of SLC500 Series PLC

When the operation command "b7: Output stop (MRS)" is executed by a touch key on the display unit:. Set a device for the switch S7 to a touch switch. Instruction code HFA

20
Connection of SIMATIC S7 Series PLC

13-13

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Inverter status monitor (RD)

H7A

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Device name in GOT-F900

Function of inverter The contents of abnormalities number 1 to 8 in the inverter correspond to devices A0 to A7 in the GOT. (From the GOT-F900, only "Most recent No.1, No.2/alarm display clear" can be executed.) In the GOT-F900, abnormalities can be read only. Item Instruction code Contents of data H0000 to HFFFF: Contents of two previous abnormalities Example of abnormality contents display (when the instruction code is "H74") Example: When the read data is "H30A0" b15 b8 b7 b0 00 11000010100000 Previous abnormality Current abnormality Data (H30) = Contents (THT) Data (HA0) = Contents (OPT) Contents of abnormality Contents of abnormality (Nos. 1, 3, 5, 7) (Nos. 2, 4, 6, 8) Abnormality data correspondence table Data H00 H10 H11 Contents of abnormality (RD) H74 to H77 H12 H20 H21 H22 H30 H31 H40 H41 H50 H51 H60 H70 H80 H81 H90 Contents No abnormality 0C1 0C2 0C3 0V1 0V2 0V3 THT THM FIN IPF UVT OLT BE GF LF OHT Data HA0 HB0 HB1 HB2 HC0 HC1 HC2 HD5 HD6 HD7 HD8 HD9 HDA HDB HA1 HA2 HA3 Contents OPT PE PUE RET CPU CTE P24 MB1 MB2 MB3 MB4 MB5 MB6 MB7 OP1 OP2 OP3

Alarm code (A)

Parameter devices in the GOT-F900 correspond to parameters in the inverter respectively. For the details of each parameter, refer to the manual of the inverter. Caution Some parameters cannot be written or read. Parameter (Pr) 1) In the case of S500 Series - Pr. 37 cannot be read or written from the GOT. - When monitoring Pr. 10 or later, write "1" to Pr. 30. 2) Parameter device range The ranges of Pr. 288 to Pr. 299, Pr. 343 to Pr. 899, Pr. 906 to Pr. 921 and Pr. 942 to Pr. 989 cannot be monitored from the GOT-F900.

13-14

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
Device name in GOT-F900 Function of inverter (Only in the A500 Series) Parameters Pr. 201 to Pr. 230 in the inverter correspond to devices PG0 to PG89. 1. Preparation When using the program operation function, set Pr. 79 in the inverter to "5". Confirm "4. Related parameters" below in accordance with the contents of operation. 2. Explanation In the inverter, 30 parameters Pr. 201 to Pr. 230 are classified into 3 groups each of which consists of 10 parameters. The three types of contents, the time, the operation frequency and the rotation direction, are set to each parameter. In the GOT-F900, by monitoring PG0 to PG89, the contents of setting in Pr201 to Pr230 can be easily used without considering the instruction codes of the inverter (described below). Setting point No.1 2 3 4 . . . 10 No.11 . . . 20 No.21 . . . 30 Rotation direction, frequency, start time Pr.201 Pr.202 Pr.203 Pr.204 . . . Pr.210 Pr.211 . . . Pr.220 Pr.221 . . . Pr.230
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

Program operation (PG)

Group 2

Correspond to PG30 to PG59.

Group 3

Correspond to PG60 to PG89.

Parameter number for inverter Pr. 201 to Pr. 210 (Group 1) Pr. 211 to Pr. 220 (Group 2) Pr. 221 to Pr. 230 (Group 3)

Device in GOT-F900 Operation frequency PG0 to PG9 PG30 to PG39 PG60 to PG69 Start time PG10 to PG19 PG40 to PG49 PG70 to PG79 Rotation direction PG20 to PG29 PG50 to PG59 PG80 to PG89

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-15

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

3. Correspondence table between device PG and set value of each parameter

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Group 1

Correspond to PG0 to PG29.

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Device name in GOT-F900

Function of inverter 4. Contents of communication in the GOT-F900 (reference) When the PG device is monitored in the GOT-F900, the instruction codes are issued and communication is executed. The instruction codes are automatically issued in the following procedure, and the user does not have to consider it. Procedure for communication with inverter PG0 is read. Instruction codes (1)FF (2)6C (3)3D PG0 is set in numeric display. (1) Writes the link parameter extension setting (H01) to SP127 by communication ENQ Station Instruction codes Data H5 HFF H01 Sum CR check Station number 5

Program operation (PG)

(2) Writes the second parameter changeover (H02) to SP108 (changeover to the rotation direction), then transfers it. ENQ Station Instruction codes Data H5 H6C H02 Sum check CR

(3) Pr201 is read. ENQ Station Instruction codes Data Sum CR H5 H3D H01 check The link parameter extension setting and the second parameter changeover are instruction codes in communication. 5. Related parameters Set the following parameters to desired values. Pr. 200: Time unit in program (Select "minute and second" or "hour and minute.) Pr. 231: Time setting (Set the time used as the reference of program operation.)

13-16

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
Device name in GOT-F900 Function of inverter This communication function of the inverter can be executed using the instruction code number When an instruction code is written to the special parameter (SP) device in the GOT-F900, communication with the inverter is executed. Device in Instruction code GOT Read Write SP108 SP109 SP110 SP111 SP112 SP113 SP114 Special parameter (SP) SP115 SP116 SP117 SP118 SP119 SP122 SP123 SP124 SP125 SP127 6C 6D 6E 6F 70 71 72 73 74 75 76 77 7A 7B 7F EC ED EE F3 F4 FA FB FC FD FF Description Second parameter changeover switch-over Running frequency (RAM) Running frequency (E2PROM) Frequency monitor Output current monitor Output voltage monitor Special monitor Special monitor selection No. Most recent No.1, No.2/alarm display clear Most recent No.3, No.4/alarm display clear Most recent No.5, No.6/alarm display clear Most recent No.7, No.8/alarm display clear Inverter status monitor/run command Operation mode acquisition All clear Inverter reset Link parameter extension setting S,A,PG,PR A A A A S Corresponding device in GOT PG,Pr
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

Caution In the case of E500/S500 Series: When SP127 is 1 and Pr37 is not 0, SP109 to SP111 cannot execute monitoring (write/read).

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-17

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

SP124 and SP125 can execute write only. SP111 to SP114 can execute monitoring only.

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.6

FREQROL Inverter Parameter List


This section describes, for reference, the list of comparison of parameters in the FREQROL Series inverters S500, E500 and A500. For the details of each function, refer to the manual of the inverter respectively.

13.6.1

Parameters
The inverter is equipped with the following parameters. (For the details, make sure to refer to the manual of the inverter.)
Function A500 Pr 0 1 2 Basic functions 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Standard operation functions 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Output terminal functions 41 42 43 Torque boost Maximum frequency Minimum frequency Base frequency Multi-speed setting (high speed) Multi-speed setting (middle speed) Multi-speed setting (low speed) Acceleration time Deceleration time Electronic thermal O/L relay DC injection brake operation frequency DC injection brake operation time DC injection brake voltage Starting frequency Load pattern selection Jog frequency Jog acceleration/deceleration time MRS input selection High-speed maximum frequency Base frequency voltage Acceleration/deceleration reference frequency Acceleration/deceleration time increments Stall prevention operation level Stall prevention operation level compensation factor at double speed Multi-speed setting (speed 4) Multi-speed setting (speed 5) Multi-speed setting (speed 6) Multi-speed setting (speed 7) Multi-speed input compensation Acceleration/deceleration pattern Regenerative function selection Frequency jump 1A Frequency jump 1B Frequency jump 2A Frequency jump 2B Frequency jump 3A Frequency jump 3B Speed display Up-to-frequency sensitivity Output frequency detection Output frequency detection for reverse rotation Name Pr 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 24 25 26 27 29 30 31 32 33 34 35 36 37 38 39 41 42 43 Torque boost Maximum frequency Minimum frequency Base frequency Multi-speed setting (high speed) Multi-speed setting (middle speed) Multi-speed setting (low speed) Acceleration time Deceleration time Electronic thermal O/L relay DC injection brake operation frequency DC injection brake operation time DC injection brake voltage Starting frequency Load pattern selection Jog frequency Jog acceleration/deceleration time High-speed maximum frequency Base frequency voltage Acceleration/deceleration reference frequency Acceleration/deceleration time increments Stall prevention operation level Stall prevention operation level compensation factor at double speed Multi-speed setting (speed 4) Multi-speed setting (speed 5) Multi-speed setting (speed 6) Multi-speed setting (speed 7) Acceleration/deceleration pattern Regenerative function selection Frequency jump 1A Frequency jump 1B Frequency jump 2A Frequency jump 2B Frequency jump 3A Frequency jump 3B Speed display Frequency at 5V (10V) input Frequency at 20mA input Up-to-frequency sensitivity Output frequency detection Output frequency detection for reverse rotation E500 Name Pr 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Torque boost Maximum frequency Minimum frequency Base frequency Multi-speed setting (high speed) Multi-speed setting (middle speed) Multi-speed setting (low speed) Acceleration time Deceleration time Electronic thermal O/L relay DC injection brake operation frequency DC injection brake operation time DC injection brake voltage Starting frequency Load pattern selection Jog frequency Jog acceleration/deceleration time RUN key rotation direction selection Base frequency voltage Acceleration/deceleration reference frequency Acceleration/deceleration time increments Stall prevention operation level Stall prevention operation level compensation factor at double speed Multi-speed setting (speed 4) Multi-speed setting (speed 5) Multi-speed setting (speed 6) Multi-speed setting (speed 7) Stall prevention operation reduction starting frequency Acceleration/deceleration pattern Regenerative function selection Frequency jump 1A Frequency jump 1B Frequency jump 2A Frequency jump 2B Frequency jump 3A Frequency jump 3B Speed display Frequency setting voltage gain frequency Frequency setting current gain frequency Start-time ground fault detection selection Up-to-frequency sensitivity Output frequency detection Output frequency detection for reverse rotation S500 Name

13-18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
Function A500 Pr 44 Second functions 45 46 47 48 49 50 52 Display functions 53 54 55 56 Additional Rated output function current 57 58 Name Second acceleration/deceleration time Second deceleration time Second torque boost Second V/F (base frequency) Second stall prevention operation current Second stall prevention operation frequency Second output frequency detection DU/PU main display data selection PU level display data selection FM terminal function selection Frequency monitoring reference Current monitoring reference Restart coasting time Restart cushion time Pr 44 45 46 47 48 52 54 55 56 57 58 E500 Name Second acceleration/deceleration time Second deceleration time Second torque boost Second V/F (base frequency) Second stall prevention operation current Control panel/PU main display data selection 34 B4 0 FM terminal function selection Frequency monitoring reference Current monitoring reference Restart coasting time Restart cushion time Pr 44 45 46 47 52 53 54 55 56 57 58 S500 Name Second acceleration/deceleration time Second deceleration time Second torque boost Second V/F(base frequency) Control panel display data selection Frequency setting operation selection FM terminal function selection Frequency monitoring reference Current monitoring reference Restart coasting time Restart cushion time

59

Remote setting function selection

59

Remote setting function selection

59

Remote setting function selection

60 61 62 63 64 65 Operation selection functions 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 Advanced magnetic flux vectorcontrol 84 89 90 91 92 93 94 95 96

Intelligent mode selection Reference I for intelligent mode Ref. I for intelligent mode accel Ref. I for intelligent mode decel Starting frequency for elevator mode Retry selection Stall prevention operation level reduction starting frequency Number of retries at alarm occurrence Retry waiting time Retry count display erasure Special regenerative brake duty Applied motor PWM frequency selection 0-5V/0-10V selection Filter time constant Reset selection/disconnected PU detection/PU stop selection Alarm code output selection Parameter write disable selection Reverse rotation prevention selection Operation mode selection Motor capacity Number of motor poles Motor exciting current Rated motor voltage Rated motor frequency Speed control gain Motor constant (R1) Motor constant (R2) Motor constant (L1) Motor constant (L2) Motor constant (X) Online auto tuning selection Auto-tuning setting/status

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 90 96

Shortest acceleration/deceleration mode 3C BC 0 Reference I for intelligent mode Ref. I for intelligent mode accel Ref. I for intelligent mode decel Starting frequency for elevator mode Retry selection Stall prevention operation level reduction starting frequency Number of retries at alarm occurrence Retry waiting time Retry count display erasure Special regenerative brake duty Applied motor PWM frequency selection 0-5V/0-10V selection Filter time constant Reset selection/disconnected PU detection/PU stop selection Alarm code output selection Parameter write disable selection Reverse rotation prevention selection Operation mode selection Motor capacity Number of motor poles Motor exciting current Rated motor voltage Rated motor frequency Motor constant (R1) Auto-tuning setting/status

66 67 68 69 71 72 73 74 75 76 77 78 79 Applied motor Retry selection

Number of retries at alarm occurrence Retry waiting time Retry count display erasure

PWM frequency selection 0-5V/0-10V selection Input filter time constant Reset selection/PU stop selection Cooling fan operation selection Parameter write disable selection Reverse rotation prevention selection Operation mode selection

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-19

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

Connection of FX Series Positioning

Connection of MELSEC-Q Series PLC

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Function

A500 Pr 100 101 102 Name V/F1 (first frequency) V/F1 (first frequency voltage) V/F2 (second frequency) V/F2 (second frequency voltage) V/F3 (third frequency) V/F3 (third frequency voltage) V/F4 (fourth frequency) V/F4 (fourth frequency voltage) V/F5 (fifth frequency) V/F5 (fifth frequency voltage) Third acceleration/deceleration time Third deceleration time Third torque boost Third V/F (base frequency) Third stall prevention operation current Third stall prevention operation frequency Third output frequency detection Station number Communication speed Stop bit length Parity check presence/absence Number of communication retries Communication check time interval Waiting time setting CR, LF presence/absence selection PID action selection PID proportional band PID integral time Upper limit Lower limit PID action set point for PU operation PID differential time Commercial power supply-inverter switchover sequence output terminal selection MC switch-over interlock time Start waiting time Commercial power supply-inverter switchover selection at alarm occurrence Automatic inverter-commercial power supply switch-over frequency Backlash acceleration stopping frequency Backlash acceleration stopping time Backlash deceleration stopping frequency Backlash deceleration stopping time Speed setting switch-over Parameter unit language switch-over Stall prevention operation level at 0V input Stall prevention operation level at 10V input Output current detection level Output current detection period Zero current detection time Zero current detection period Pr

E500 Name Pr 88 89 90 91 92 93 94 48 49 50 51

S500 Name PID action selection PID proportional band PID integral time Upper limit Lower limit PID action set point for PU operation PID differential time Output current detection level Output current detection period Zero current detection time Zero current detection period

5-point flexible V/F characteristics Third functions

103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118

117 Station number 118 Communication speed 119 Stop bit length 120 Parity check presence/absence 121 Number of communication retries 122 Communication check time interval 123 Waiting time setting 124 CR, LF presence/absence selection 128 PID action selection 129 PID proportional band 130 PID integral time 131 Upper limit 132 Lower limit 133 PID action set point for PU operation 134 PID differential time

Communication functions PID control Commercial power supply- inverter switch- over Backlash AdditDisplay ional functions

119 120 121 122 123 124 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 148 149 150

145 Parameter unit language switch-over 146 Frequency setting command selection

150 Output current detection level 151 Output current detection period 152 Zero current detection time 153 Zero current detection period

Current detection

151 152 153

13-20

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
Function A500 Pr 154 Sub functions 155 156 157 158 Additional function Name Voltage reduction selection during stall prevention operation RT signal activated condition Stall prevention operation selection OL signal waiting time AM terminal function selection Pr E500 Name Pr S500 Name

156 Stall prevention operation selection

160

User group read selection

160 User group read selection

Restart after instantaneous power failure

162 163 164 165 170 171 173 174 175 176 180 181 182

First cushion time for restart First cushion voltage for restart Restart stall prevention operation level Watt-hour meter clear Actual operation hour meter clear User group 1 registration User group 1 deletion User group 2 registration User group 2 deletion RL terminal function selection RM terminal function selection RH terminal function selection RT terminal function selection AU terminal function selection JOG terminal function selection CS terminal function selection RUN terminal function selection SU terminal function selection IPF terminal function selection OL terminal function selection FU terminal function selection A, B, C terminal function selection

60 61 62 63 64 65

RL terminal function selection RM terminal function selection RH terminal function selection SRT terminal function selection RUN terminal function selection A, B, C terminal function selection

Initial monitor

171 Actual operation hour meter clear 173 User group 1 registration 174 User group 1 deletion 175 User group 2 registration 176 User group 2 deletion 180 RL terminal function selection 181 RM terminal function selection 182 RH terminal function selection 183 MRS terminal function selection

User functions

Terminal assignment functions

183 184 185 186 190 191 192 193 194 195

190 RUN terminal function selection 191 SU terminal function selection 192 A, B, C terminal function selection

Additional function

199

User's initial value setting

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-21

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

Automatic restart after instantaneous power failure selection

Connection of FX Series Positioning

Connection of MELSEC-Q Series PLC

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Function

A500 Pr 200 201 202 203 204 205 206 207 208 209 210 211 212 Name Programmed operation minute/second selection Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 1 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 2 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Program setting 3 Timer setting Multi-speed setting (speed 8) Multi-speed setting (speed 9) Multi-speed setting (speed 10) Multi-speed setting (speed 11) Multi-speed setting (speed 12) Multi-speed setting (speed 13) Multi-speed setting (speed 14) Multi-speed setting (speed 15) Soft-PWM setting Cooling fan operation selection Stop selection Output phase failure protection selection Override bias Override gain Pr

E500 Name Pr 80 81 82 83 84 85 86 87 70 95 96 97 98 99

S500 Name Multi-speed setting (speed 8) Multi-speed setting (speed 9) Multi-speed setting (speed 10) Multi-speed setting (speed 11) Multi-speed setting (speed 12) Multi-speed setting (speed 13) Multi-speed setting (speed 14) Multi-speed setting (speed 15) Soft-PWM setting Rated motor slip Slip compensation time constant Constant-output region slip compensation selection Automatic torque boost selection (Motor capacity) Motor primary resistance

Programmed operation

213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232

232 Multi-speed setting (speed 8) 233 Multi-speed setting (speed 9) 234 Multi-speed setting (speed 10) 235 Multi-speed setting (speed 11) 236 Multi-speed setting (speed 12) 237 Multi-speed setting (speed 13) 238 Multi-speed setting (speed 14) 239 Multi-speed setting (speed 15) 240 Soft-PWM setting 244 Cooling fan operation selection 245 Rated motor slip 246 Slip compensation time constant Constant-output region slip compensation 247 selection

Multi- speed operation

233 234 235 236 237 238 239 240 244

Sub functions

249 Motor primary resistance 250 Stop selection 251 Output phase failure protection selection

Stop Additional function selection function

250 251 252 253

13-22

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
Function A500 Pr 261 Power failure stop functions 262 263 264 265 266 Function selection Name Power failure stop selection Subtracted frequency at deceleration start Subtraction starting frequency Power-failure deceleration time 1 Power-failure deceleration time 2 Power-failure deceleration time switchover frequency Stop-on-contact/load torque high-speed frequency control selection High-speed setting maximum current Mid-speed setting minimum current Current averaging range Current averaging filter constant Stop-on-contact exciting current lowspeed multiplying factor Stop-on-contact PWM carrier frequency Brake opening frequency Brake opening current Brake opening current detection time Brake operation time at start Brake operation frequency Brake operation time at stop Deceleration detection function selection Overspeed detection frequency Droop gain Droop filter constant Pr E500 Name Pr S500 Name

270 271 272 273 274 275 276 278

n12 342 C1 900 C2 902 C3 902 C4 903 C6 904 C7 905 n14 990 n15 991

E 2 PROM write selection

Stop on contact

Brake sequence functions

279 280 281 282 283 284 285

Additional Droop function control

286 287

342

E 2 PROM write selection

342 E 2 PROM write selection

900 901

FM (AM) terminal calibration AM terminal calibration

900 FM (AM) terminal calibration

FM (AM) terminal calibration Frequency setting voltage bias frequency Frequency setting voltage bias Frequency setting voltage gain Frequency setting current bias frequency Frequency setting current bias Parameter set by manufacturer. Do not set. PU buzzer sound control PU contrast adjustment Parameter clear

902 Calibration functions

Frequency setting voltage bias

902 Frequency setting voltage bias

903 904 905

Frequency setting voltage gain Frequency setting current bias Frequency setting current gain Built-in frequency setting Buzzer control LCD contrast

903 Frequency setting voltage gain 904 Frequency setting current bias 905 Frequency setting current gain 922 923 Built-in frequency setting potentiometer bias Built-in frequency setting potentiometer gain

Additional function

990 991

990 Buzzer control 991 LCD contrast

19
Connection of SLC500 Series PLC

Clear parameters

CLr

ECL Alarm history clear

20
Connection of SIMATIC S7 Series PLC

13-23

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

High speed frequency control

Connection of FX Series Positioning

Connection of MELSEC-Q Series PLC

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

In the column for S500, the numbers starting with 'c' or 'n' are the parameters displayed on the in-built operation panel, and the numbers below are the parameters for FR-PU04. Note: 1. Indicates the parameter settings which are ignored when the advanced magnetic flux vector control mode is selected. 2. Can be set when Pr. 80, Pr. 81 9999, Pr. 60 = 7 or 8. 3. Can be accessed when Pr. 80, Pr. 81 9999, Pr. 77 = 801. 4. Can be accessed when Pr. 29 = 3.

13-24

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.6.2 Communication Parameters
The parameters shown in the table below correspond to the following communication ports respectively. In the A500 Series, the following parameters are communication parameters for the FR-A5NR computer link option. In the E500 Series, only the PU port is available. In the S500 Series, the following parameters are available if the RS-485 communication function is provided.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

If an inverter is connected to the PU port other than above, set the parameters using Pr. 117 to Pr. 124 shown in the previous page.)
Function A500 Pr 331 332 333 334 335 336 337 Computer link function 338 339 340 341 342 Name Inverter station number Communication speed Stop bit length Parity check yes/no Communication retry count Communication check time interval Waiting time setting Operation command right Speed command right Link start mode selection CRE LF yes/no selection E2PROM write selection Pr E500 Name Pr n1 331 n2 332 n3 333 n4 334 n5 335 n6 336 n7 337 n8 338 n9 339 n10 340 n11 341 n12 342 n13 145 n14 990 n15 991 n16 992 n17 993 S500 Name Inverter station number Communication speed Stop bit length Parity check yes/no Communication retry count Communication check time interval Waiting time setting Operation command right Speed command right Link start mode selection CRE LF yes/no selection E2PROM write selection PU display language PU buzzer sound control PU contrast adjustment PU main display screen data selection PU disconnection detection/PU setting lock

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-25

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.7

Setting of Connected Equipment for GOT


The setting for connection to the FREQROL Series inverter can be executed using the GOT-F900 and the screen creation software (GT Designer2, GT Designer or DU/WIN). 1) GOT-F900 Series When the main menu screen change operation is disabled.
Operation Display (screen name) a)While pressing and holding the upper left corner of the screen, The "LANGUAGE" screen appears. turn on the power. Keep holding the upper left corner for about 25 seconds more. Then, press "END" at the upper right corner. The "SET-UP MODE" screen appears. b)Press "PLC TYPE". c) Set the following. PLC TYPE:FREQROL CONNECTION:CPU PORT (RS-422) DST STATION # (STATION #) : 00 GOT STATION # () : The "PLC TYPE" screen appears.

When the main menu screen change operation is enabled.


Operation a)Press the upper left corner of the screen. (The position to be pressed can be changed in the GOT and the screen creation software.) b)Press "OTHER MODE" on the menu. c) Press "SET-UP MODE" on the menu. d)Press "PLC TYPE". e)Set the following. PLC TYPE: FREQROL CONNECTION:CPU PORT (RS-422) DST STATION # (STATION #) : 00 GOT STATION # () : Display (screen name) The "SELECT MODE" screen appears.

The "OTHER MODE" screen appears. The "SET-UP MODE" screen appears. The "PLC TYPE" screen appears.

- When the screen data is transferred to the GOT-F900, the old data including the PLC type, connection type, and station number are overwritten.

13-26

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
2) GT Designer2
Operation [Creation] a)Open GT Designer2. b)Click the [NEW] button. The dialog box shown below is displayed. If it is not displayed, click "System Environment" in the tree displayed in the project work space, then click "System settings" in the tree. Display (screen name) The "Select Project" dialog box appears. The "System Environment" dialog box appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
c)Set the following. GOT type: F940WGOT (480 234) F94*GOT (320 240) F93*GOT (240 80) PLC type: FREQROL Selection of "GOT type" GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) Click [OK]. Model name (name) F940WGOT F940GOT Handy GOT F930GOT F930GOT-K
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

17
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-27

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Operation d)Setting the port (RS-422) of the GOT-F900 Click "Auxiliary Setting" in the tree of the system environment menu. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($).

Display (screen name) The "Auxiliary Settings" dialog box appears.

Click "Got Setup" in the tree of the system environment menu.

e)Set the following. Port : RS-422 Type : CPU Station No. : 00 GOT Station No. : [Change method] Change the connection type of the already created data as follows. a)Open GT Designer. b)Click the [Project]-[Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"System Environment". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 on the FREQROL Series inverter, refer to e) of [Creation] above. The "System Environment" dialog box appears. The "Select Project" dialog box appears.

13-28

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
3) GT Designer
Operation [Creation] a)Open GT Designer. b)Click the [New] button. Display (screen name) The "Select Project" dialog box appears. The "GOT/PLC Type" dialog box appears.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

c)Set the following. GOT type: F940WGOT (480 234) F940GOT (320 240) F930GOT (240 80) PLC type: FREQROL Selection of "GOT type"
GOT type F940WGOT(480234)<WIDE> F94*GOT(320240) F93*GOT(24080) Model name F940WGOT F940GOT Handy GOT F930GOT-K F930GOT

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

Click [OK]. d)Set CPU direct connection (RS-422) of the GOT-F900. Click the check box of "Use Serial Port, Setup, Language, Menu Key" to give a check mark ($). The "Project Auxiliary Settings" dialog box appears.

15
Connection of SYSMAC C Series PLC

16
Connection of FLEX-PC N Series PLC

13-29

Connection of SIMATIC S7 Series PLC

Connection of SLC500 Series PLC

e)Set the following. Port : RS-422 Type : CPU DST Station No. (Station No.) : 00 GOT Station No. () :

19

20

Connection of FP Series PLC

Connection of Machine Controller

Click the "Setup" tab.

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Operation [Change method] Change the connection type of the already created data as follows. a)Open GT Designer. b)Click the [Open] button. c)Open (read) the screen data to be changed. d)On the menu, select "Common"-"GOT/PLC Type". - For the contents of setting, refer to c) of [Creation] above. - For selection of the RS-422 on the FREQROL Series inverter, refer to e) of [Creation] above.

Display (screen name) The "Select Project" dialog box appears.

The "GOT/PLC Type" dialog box appears.

13-30

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
4) DU/WIN
Operation [Creation] a)Open DU/WIN. b)On the menu, select "File"-"New". The "Project settings" dialog box appears. Display (screen name)
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

c)Set the following. Terminal: F940WGOT-TWD (V) (H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V) (H) PLC System: FREQROL Select "Terminal" in accordance with the LC display color. Terminal F940WGOT-TWD (V)(H) F940GOT-LWD F940GOT-SWD F930GOT-BWD (V)(H) In the case of RS-422 connection Model name F940WGOT (color) F940GOT (black and white) Handy GOT (black and white) F940GOT (color) Handy GOT (color) F930GOT-K (blue) F930GOT (blue)

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

15
Connection of SYSMAC C Series PLC

The "Setup Data" dialog d)Set RS-422 of the GOT-F900. On the menu, select "View/Project"-"System Settings"-"Setup Data". box appears.

16
Connection of FLEX-PC N Series PLC

17
e)Set the following. Port: RS-422 Type: CPU DST Station No. (Station No.) : 00 GOT Station No. () : In the case of F943 Handy GOT Without regard to the port setting (RS-422 or RS-232C), the COM0 side of the RS-232C is fixed for PLC connection. [Change method] Change the connection type of the already created data as follows. a)Open DU/WIN. b)On the menu, select "File"-"Open". c)Select and open (read) the file of the screen data to be changed. The "Open" dialog box appears.
Connection of Machine Controller

18
Connection of FP Series PLC

19
Connection of SLC500 Series PLC

13-31

Connection of SIMATIC S7 Series PLC

The "Project settings" d)When changing "Terminal" (GOT-F900), select "View/Project"dialog box appears. "System Settings"-"Project settings" on the menu. For the contents of setting, refer to c) in [Creation] above. For setting of RS-422 of the FREQROL Series inverter, refer to e) in [Creation] above.

20

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

13.8

Cable Diagram
This section explains cable diagrams to connect the GOT-F900 and the FREQROL Series inverter.
Signal name RDA RDB SDA SDB SG GOT-F900 Handy GOT 9pin F9GT- F9GTD-Sub HCAB HCAB1 Twisted pair cable 2 6 Yellow 7 7 Brown 1 2 Black 6 3 White 5 10 Orange

Distributor
5 4 3 6 1
5 4 3 6 1

Distributor
5 4 3 6 1 5 4 3 6 1
5 4 3 6 1

5 4 3 6 1

A
Terminal resistor

Connect a terminal resistor to the inverter located farthest from the GOT-F900. Connect the terminal resistor as follows in accordance with the model of the inverter located farthest. PU port (A500/E500), RS-485 (S500) Connect as shown in (A) in the diagram on the right. FR-A5NR Connect to (B) in the diagram on the right.

5 4 3 6 1 S S R R R S D D D D D G A B A B R Inverter Upper line: PU port Lower line: FR-A5NR

5 4 3 6 1 S S R R R S D D D D D G A B A B R

...

Inverter Upper line: PU port Lower line: FR-A5NR

B
Terminal resistor connection chip

Station number 0

Station number n

In cables connecting distributors, do not wire the pin number 2 and 8. Inverters may fail by such wiring. 1) Cable for the GOT and the FREQROL Series inverter
: Female type : Male type The connector figure shows the engagement face.

No.

Model name

Application
GOT-F900
1 5

Connection diagram
(1) (2) (5) (6) (7) (3) (5) (1) (6) (4)

Application
PU port

RS-422 INV CPU direct connection connection a) PU port of A500 Series, E500 Series or S500 Series RS-422 connection

9-pin D-Sub, male GOT-F900


1 5 (1) (2) (5) (6) (7) (1) (2) Do not connect. (3) (4) (5) (6) (7) (8) Do not connect. (1) (2) Do not connect. (3) (4) (5) (6) (7) (8) Do not connect. RDA SDA SG RDB SDB (1) (2) (3) (4) (5) (6) (7) (8) SG (2) RDA SDB SDA RDB (7) (8)

PJ-45 plug, male

INV CPU direct b) connection FR-A5NR of A500 Series

Terminal block of FR-A5NR

9-pin D-Sub, male

RS-422 connection

Distributor

Distributor

c)

INV direct connection Between distributor and distributor

PJ-45 plug, male

PJ-45 plug, male

RS-422 connection

Distributor

d) INV direct connection Between distributor and FR-A5NR of A500 Series

Terminal block of FR-A5NR

PJ-45 plug, male

13-32

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
2) Cable for the Handy GOT and the FREQROL Series inverter When using the Handy GOT RH model, refer to the cable diagrams below for the RS-422/RS-232C connector, but not the wiring for the power supply, the operation switches, and the emergency stop switch because it is different. For details, refer to Section 5.18.
: Female type : Male type The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application

Connection diagram

Application
To F9GT-HCAB2-150 or F9GT-HCAB3-150 1 13

a)

F9GT-HCAB-3M F9GT-HCAB-10M

RS-232C connection

Dedicated connector on Handy GOT side

b)

F9GT-HCAB1-3M connection F9GT-HCAB1-10M RS-232C


connection RS-422 connection

RS-422

Dedicated connector on Handy GOT side

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.
F9GT-HCAB-""M FG(Grounding) (3) (5) (1) (6) (4)

Untied cable (no connector)

Prepared by the user c)


The diagram on the right shows the wiring of the RS422 signals. For wiring of the operation switches and the power supply, refer to chapter 5.

F9GT-HCAB1-""M

RS-422 connection

Prepared by the user d)


The diagram on the right shows the wiring of the RS422 signals. For wiring of the operation switches and the power supply, refer to chapter 5.

Terminal block of FR-A5NR

25 14 25-pin D-Sub, female

PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25) F9GT-HCAB1-""M

DC24VG DC24VG SW common SW1 SW2 SW3 SW4 ES1 ES1 DC24V+ DC24V+

19
Distributor
Connection of SLC500 Series PLC

RS-422 connection

Distributor

Prepared by the user e) Between distributor and distributor


1 8

13-33

Connection of SIMATIC S7 Series PLC

PJ-45 plug, male

(1) (2) Do not connect. (3) (4) (5) (6) (7) (8) Do not connect.

(1) (2) (3) (4) (5) (6) (7) (8)

20

PJ-45 plug, male

Connection of FP Series PLC

Wire the power supply, the operation switches and the emergency stop switch.

Connection of Machine Controller

Drain wire (1) To cable F9GT-HCAB BK (2) Y (6) on Handy GOT side O (10) 1 13 W (3) BR(7)

F9GT-HCAB-""M FG(Grounding) RDA SDA SG RDB SDB

Connection of FLEX-PC N Series PLC

Drain wire (1) To cable F9GT-HCAB BK (2) on Handy GOT side Y (6) 1 13 O (10) W (3) BR(7) 25 14 25-pin D-Sub, female PL (12) PK (13) FGR (14) SB (15) BK/W (16) R/W (17) GR/W (18) BR/W (21) Y/W(22) BL/W(24) GY/W(25)

PJ-45 plug, male

DC24VG DC24VG SW common SW1 SW2 SW3 SW4 ES1 ES1 DC24V+ DC24V+

Wire the power supply, the operation switches and the emergency stop switch.

Connection of SYSMAC C Series PLC

Connection of Microcomputer

PU port

Connection of FREQROL Inverter

The connector on the leader side of the Handy GOT is dedicated, and cannot be prepared by the user.

14 25 25-pin D-Sub, male

Connection of FX Series Positioning

Connection of MELSEC-Q Series PLC

12

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

: Female type

: Male type

The connector figure shows the engagement face.

No.

Model name RS-422 connection

Application
Distributor

Connection diagram
(1) (2) Do not connect. (3) (4) (5) (6) (7) (8) Do not connect. SG (2) RDA SDB SDA RDB (7) (8)

Application

f)

INV direct connection Between distributor and FR-A5NR of A500 Series

Terminal block of FR-A5NR

PJ-45 plug, male

3) Connectors and connector covers to be used a) Connector on the GOT side For the connectors used in the GOT-F900 and the Handy GOT, refer to the description on corresponding dedicated wiring. b) Connector of cable between FREQROL Series inverters Use the commercial connectors and cables shown in the table below or the comparable products. (Refer to the manual for the inverter.) Introduced products (as of June, 2000)
Name Connector Model name 5-554720-3 Specifications RJ45 connector Manufacturer Tyco Electronics AMP K.K. HACHIKO ELECTRIC CO.,LTD. Telephone number: 03-3806-9171 Cable conforming to EIA568 (such as cable 10BASE-T) MITSUBISHI CABLE INDUSTRIES, LTD.

Modular ceiling BMJ-8 rossette Cable SGLPEV 0.5mm4P

The company name is changed. Conventional name: AMP Incorporated New name: Tyco Electronics AMP K.K.

13-34

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
13.9 Troubleshooting
For reference, this section summarizes frequently asked questions about connection of the GOT-F900 to the FREQROL Series inverter. 1) GOT-F900
Contents of trouble Check points and countermeasures The power of the FREQROL inverter is turned off. Cause Communication is disabled because the power of the "COMMUNICATION FREQROL inverter is turned off. ERROR OCCURS" is Countermeasures displayed when a From From From Turn on the power. screen changeover or first first first numeric data input is Something is wrong with the cable between the GOT-F900 and product product product the FREQROL. performed on the GOT-F900 screen. Causes The wrong cable is used or the connection is bad. Countermeasures Check the cable. OS version F940W F940 F930
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

13
Connection of FREQROL Inverter

14
Connection of Microcomputer

13-35

Connection of SIMATIC S7 Series PLC

Connection of SLC500 Series PLC

Cause One of the screen objects is placed outside the available screen area. Countermeasures Check the placement of screen objects.

19

20

Connection of FP Series PLC

Cause On the changeover destination screen (excluding the head screen), a nonexistent device in the connected FREQROL "DISPLAY SCREEN inverter is specified. IS NOT AVAILABLE." Countermeasures is displayed on the Check the devices used on the head screen. GOT-F900 screen. There is an error on the screen to be displayed.

Earlier than 6.00

Earlier than 4.00

Connection of Machine Controller

A device that does not exist in the FREQROL inverter was referenced. (Example: While an S500 Series is connected, a device exists only in the A500 Series is specified for numeric input.)

Connection of FLEX-PC N Series PLC

A nonexistent screen was tried to be displayed. "DISPLAY SCREEN IS NOT AVAILABLE. Cause (NO. ####)" is The screen No. #### has not been created yet. displayed on the GOT Countermeasures F900 screen. Create the screen.

From 6.00 or 4.00 or first later later product

Connection of SYSMAC C Series PLC

Changeover to a nonexistent screen was tried by a touch key. "DISPLAY SCREEN IS NOT AVAILABLE." Cause is displayed on the The changeover destination screen has not been created yet. GOT-F900 screen. Countermeasures Create the screen.

Earlier than 6.00

Earlier than 4.00

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

Contents of trouble

Check points and countermeasures The display screen contains an error.

OS version F940W F940 F930

"DISPLAY SCREEN Causes IS NOT AVAILABLE. A device that does not exist in the connected PLC is (NO. ####)" is referenced on the screen No. ####, or one of the screen displayed on the GOTobjects is placed outside the available screen area. F900 screen. Countermeasures Check the devices used and placement of screen objects. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. A device that does not exist in the FREQROL inverter was referenced. (Example: While an S500 Series is connected, a device exists only in the A500 Series is specified for numeric input.) "DATA IS NOT FOUND." is displayed Cause On the head screen, a nonexistent device in the connected on the GOT-F900 FREQROL inverter is specified. screen. (The head screen is the screen No. 1 in the GT Designer, and the screen No. 0 in the DU/WIN.) Countermeasures Check the devices used on the head screen. There is not data because the unit is new or the memory clear has been executed. Cause There is no screen data. Countermeasures Write the screen data using the screen creation software. "CAN NOT WRITE TO PLC MEMORY." is This error is not displayed. displayed on the GOTF900 screen. A parameter (Pr) in the FREQROL inverter was tried to be changed. "CAN NOT WRITE." is displayed on the GOT-F900 screen.

From 6.00 or 4.00 or first later later product

Earlier than 6.00

Earlier than 4.00

From 6.00 or 4.00 or first later later product

Earlier than 1.10

Earlier than 6.10

Earlier than 4.10

Cause 1.10 or 6.10 or 4.10 or The FREQROL inverter is not set to the computer link later later later operation mode or the inverter is running. Countermeasures In the manual of the FREQROL inverter, confirm the allowable write range in each operation mode. From From From first first first product product product From From From first first first product product product

"CAN NOT USE THE FUNCTION WHILE PROTECTED." is This error is not displayed. displayed on the GOTF900 screen. "PLC IS RUNNING." is displayed on the GOT-F900 screen. This error is not displayed.

13-36

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

11
2) Software
Contents of trouble Check points and countermeasures A bar code reader or printer is connected. (Such equipment cannot be connected to the FREQROL inverter.) Causes The RS-232C connector to which the personal computer is connected is set to be used for another piece of equipment. Countermeasures In the GOT-F900, select by hand "SELECT MODE"-"OTHER MODE"-"DATA TRANSFER". Or set a bar code reader to invalid and a printer" to "DON'T USE". Something is wrong with the cable between the GOT-F900 and the personal computer. Causes The connected cable is not proper. Or cable connection is not correct. Countermeasures Check the cable.
Connection of MELSEC-Q Series PLC

12
Connection of FX Series Positioning

19
Connection of SLC500 Series PLC

20
Connection of SIMATIC S7 Series PLC

13-37

Connection of FP Series PLC

Connection of Machine Controller

Connection of FLEX-PC N Series PLC

Connection of SYSMAC C Series PLC

Connection of Microcomputer

Connection of FREQROL Inverter

Screen creation software

Communication with the screen creation software and screen data cannot be transferred.

13

14

15

16

17

18

GOT-F900 SERIES (CONNECTION)

Connection of FREQROL (S500/E500/A500) Inverter 13

MEMO

13-38