Logix5000 Controllers Messages

Programming Manual Catalog Numbers 1756-L1, 1756-L55, 1756-L61, 1756-L62, 1756-L63, 1769L31, 1769-L32C, 1769-L32E, 1769L35CR, 1769-L35E, 1789-L60, 1794-L34, PowerFlex 700S/SE

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hardwired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT ATTENTION

Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents
Preface
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 How to Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Chapter 1 Controller Messages


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Message Queue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Cache List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Unconnected Buffers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Get or Set the Number of Unconnected Buffers . . . . . . . . . . . . . . . . . 12 Get the Number of Unconnected Buffers . . . . . . . . . . . . . . . . . . . 12 Set the Number of Unconnected Buffers. . . . . . . . . . . . . . . . . . . . 13 Convert Between INTs and DINTs . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter 2 Manage Multiple Messages


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 How to Use this Example Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Message Manager Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Initialize the Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Restart the Sequence, If Required. . . . . . . . . . . . . . . . . . . . . . . . . . 18 Send the First Group of MSGs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Enable the Next Group of MSGs. . . . . . . . . . . . . . . . . . . . . . . . . . 19 Send the Next Group of MSGs . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Enable the Next Group of MSGs. . . . . . . . . . . . . . . . . . . . . . . . . . 20 Send the Next Group of MSGs . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Chapter 3 Send a Message to Multiple Controllers


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Set Up the I/O Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Define Your Source and Destination Elements . . . . . . . . . . . . . . . . . . 25 Create the MESSAGE_ CONFIGURATION Data Type . . . . . . . . . 26 Create the Configuration Array . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Get the Size of the Local Array . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Load the Message Properties for a Controller . . . . . . . . . . . . . . . . . . . 30 Configure the Message. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Step to the Next Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Restart the Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

3Publication 1756-PM012B-EN-P - July 2008

Publication 1756-PM012B-EN-P - July 2008

Preface

Purpose of this Manual

This manual shows how to program MSG instructions to and from Logix5000 controllers. This manual is one of a set of related manuals that show common procedures for programming and operating Logix5000 controllers. For a complete list of common procedures manuals, see the Logix 5000 Controllers Common Procedures Programming Manual, publication 1756-PM001. The term Logix5000 controller refers to any controller that is based on the Logix5000 operating system, such as: CompactLogix controllers ControlLogix controllers DriveLogix controllers FlexLogix controllers SoftLogix5800 controllers

How to Use this Manual


Text that is Italic courier Identifies

Some text is formatted differently from the rest of the text.


For example Means Right-click the item that is named User-Defined. You must identify the specific program in your application. Typically, it is a name or variable that you have defined. Press the Enter key.

the actual name of an item that you Right-click User-Defined see on your screen or in an example information that you must supply based on your application (a variable) Right-click name_of_program Press [Enter].

enclosed in brackets a keyboard key

5Publication 1756-PM012B-EN-P - July 2008

Preface

Notes:

Publication 1756-PM012B-EN-P - July 2008

Chapter

Controller Messages

Introduction
EXAMPLE

To transfer data between controllers (send or receive data), execute a Message (MSG) instruction. Execute a Message (MSG) Instruction

If count_send = 1 and count_msg.EN = 0 (MSG instruction is not already enabled), then execute a MSG instruction that sends data to another controller.

count_send

count_msg.en /

MSG Type - Unconfigured Message Controlcount_msg

...

EN DN ER

This diagram shows how the controller processes MSG instructions.


1 2

Message Queue

Cache List

Unconnected Buffers

MSG 16 total

Cached? Yes

No

destination device

Description
1

The controller scans the MSG instruction and its rung-condition-in goes true. The MSG instruction enters the message queue. The MSG instruction comes off the queue and is processed. If the MSG instruction Does not use a connection or the connection was not previously cached. Uses a connection and the connection is cached Communication occurs with the destination device. Then the MSG instruction uses an unconnected buffer to establish communication with the destination device does not use an unconnected buffer

2 3

7Publication 1756-PM012B-EN-P - July 2008

Chapter 1

Controller Messages

Message Queue

The message queue holds up to 16 MSG instructions, including those that you configure as a block-transfer read or block-transfer write. When the queue is full, an instruction tries to enter the queue on each subsequent scan of the instruction, as shown below:
rung-condition-in false true false

.EN bit

off

on

.EW bit

off

on

Description
1

The controller scans the MSG instruction. The rung-condition-in for the MSG instruction is true. The EN bit is set. The MSG instruction attempts to enter the queue but the queue is full (16 MSG instructions are already enabled). The EW bit remains cleared. The controller scans the MSG instruction. The rung-condition-in for the MSG instruction is false. The EN bit remains set. The MSG instruction attempts to enter the queue but the queue is full. The EW bit remains cleared. The controller scans the MSG instruction. The MSG instruction attempts to enter the queue. The queue has room so the instruction enters the queue. The EW bit is set.

2 & 3

Publication 1756-PM012B-EN-P - July 2008

Controller Messages

Chapter 1

Cache List

Depending on how you configure a MSG instruction, it may use a connection to send or receive data.
This type of message CIP data table read or write PLC2, PLC3, PLC5, or SLC (all types) CIP CIP with Source ID DH+ CIP generic block-transfer read or write
(1)

And this communication method: Uses a connection

your option (1)

You can connect CIP generic messages. But for most applications we recommend you leave CIP generic messages unconnected.

If a MSG instruction uses a connection, you have the option to leave the connection open (cache) or close the connection when the message is done transmitting.
If you Cache the connection Then The connection stays open after the MSG instruction is done. This optimizes execution time. Opening a connection each time the message executes increases execution time. The connection closes after the MSG instruction is done. This frees up that connection for other uses.

Do not cache the connection

The controller has these limits on the number of connections that you can cache:
If you have this software and firmware revision 11.x or earlier 12.x or later Then you can cache Block transfer messages for up to 16 connections Other types of messages for up to 16 connections Up to 32 connections

Publication 1756-PM012B-EN-P - July 2008

Chapter 1

Controller Messages

If several messages go to the same device, the messages may be able to share a connection.
If the MSG instructions are to Different devices Same device Enabled at the same time Not enabled at the same time And they are Then Each MSG instruction uses 1 connection. Each MSG instruction uses 1 connection. The MSG instructions share the connection. (For example, together they count as 1 connection.)

EXAMPLE

Share a Connection If the controller alternates between sending a block-transfer read message and a block-transfer write message to the same module, then together both messages count as 1 connection. Caching both messages counts as 1 on the cache list.

Unconnected Buffers
Term Unconnected buffer

To establish a connection or process unconnected messages, the controller uses an unconnected buffer.
Definition An allocation of memory that the controller uses to process unconnected communication. The controller performs unconnected communication when it: establishes a connection with a device, including an I/O module. executes a MSG instruction that does not use a connection. The controller can have 10 - 40 unconnected buffers. The default number is 10. To increase the number of unconnected buffers, execute a MSG instruction that reconfigures the number of unconnected buffers. Each unconnected buffers uses 1.1K bytes of memory. If all the unconnected buffers are in use when an instruction leaves the message queue, the instruction errors and data does not transfer.

If a MSG instruction uses a connection, the instruction uses an unconnected buffer when it first executes to establish a connection. If you configure the instruction to cache the connection, it no longer requires an unconnected buffer once the connection is established.

10

Publication 1756-PM012B-EN-P - July 2008

Controller Messages

Chapter 1

Guidelines
Guideline 1. For each MSG instruction, create a control tag.

As you plan and program your MSG instructions, follow these guidelines:
Details Each MSG instruction requires its own control tag. Data type = MESSAGE Scope = controller The tag cannot be part of an array or a user-defined data type.

2. Keep the source and/or destination data at the controller scope. 3. If your MSG is to a device that uses 16-bit integers, use a buffer of INTs in the MSG and DINTs throughout the project.

A MSG instruction can access only tags that are in the Controller Tags folder (controller scope). If your message is to a device that uses 16-bit integers, such as a PLC-5 or SLC 500 controller, and it transfers integers (not REALs), use a buffer of INTs in the message and DINTs throughout the project. This increases the efficiency of your project because Logix5000 controllers execute more efficiently and use less memory when working with 32-bit integers (DINTs). Refer to Convert Between INTs and DINTs on page 15.

4. Cache the connected MSGs that execute most frequently.

Cache the connection for those MSG instructions that execute most frequently, up to the maximum number permissible for your controller revision. This optimizes execution time because the controller does not have to open a connection each time the message executes.

5. If you want to enable more than 16 MSGs at If you enable more than 16 MSGs at one time, some MSG instructions may experience one time, use some type of management delays in entering the queue. To guarantee the execution of each message, use one of strategy. these options: Enable each message in sequence. Enable the messages in groups. Program a message to communicate with multiple devices. Program logic to coordinate the execution of messages. 6. Keep the number of unconnected and uncached MSGs less than the number of unconnected buffers. The controller can have 10 - 40 unconnected buffers. The default number is 10. If all the unconnected buffers are in use when an instruction leaves the message queue, the instruction errors and does not transfer the data. You can increase the number of unconnected buffers (40 max.), but continue to follow guideline 5. To increase the number of unconnected buffers, see page 12.

Publication 1756-PM012B-EN-P - July 2008

11

Chapter 1

Controller Messages

Get or Set the Number of Unconnected Buffers

To determine or change the number of unconnected buffers, use a MSG instruction. The range is 10 - 40 unconnected buffers. The default number is 10. Each unconnected buffers uses 1.1K bytes of memory.

Get the Number of Unconnected Buffers


To determine the number of unconnected buffers that the controller currently has available, configure a Message (MSG) instruction as follows:
On this tab Configuration For this item Message Type Service Type Service Code Class Instance Attribute Source Element Type or select CIP Generic Custom 3 304 1 0 source_array where data type = SINT[4] In this element source_array[0] source_array[1] source_array[2] source_array[3] Source Length (bytes) Destination Communication Path 4 (Write 4 SINTs.) destination_array where data type = SINT[10] (Leave all the values = 0.) destination_array[6] = current number of unconnected buffers 1, slot_number_of_controller Enter 1 0 17 0

12

Publication 1756-PM012B-EN-P - July 2008

Controller Messages

Chapter 1

Set the Number of Unconnected Buffers


As a starting value, set the number of unconnected buffers equal to the number of unconnected and uncached messages enabled at one time plus approximately 5. The additional 5 buffers provides a cushion in case you underestimate the number of messages that are enabled at one time. To change the number of unconnected buffers of the controller, configure a Message (MSG) instruction as follows:
On this tab Configuration For this item Message Type Service Type Service Code Class Instance Attribute Source Element Type or select CIP Generic Custom 4 304 1 0 source_array where data type = SINT[8] In this element source_array[0] source_array[1] source_array[2] source_array[3] source_array[4] source_array[5] source_array[6] source_array[7] Source Length (bytes) Destination Communication Path 8 (Write 8 SINTs.) destination_array where data type = SINT[6] (Leave all the values = 0.) 1, slot_number_of_controller Enter 1 0 17 0 Number of unconnected buffers that you want. 0 0 0

Publication 1756-PM012B-EN-P - July 2008

13

Chapter 1

Controller Messages

EXAMPLE

Set the Number of Unconnected Buffers

If S:FS = 1 (first scan), then set the number of unconnected buffers for the controller: Source_Array[0] = 1 Source_Array[1] = 0 Source_Array[2] = 17 Source_Array[3] = 0 Source_Array[4] = 12 (The number of unconnected buffers that you want. In this example, we want 12 buffers.) If UCB_Set.EN = 0 (MSG instruction is not already enabled) then: MSG instruction sets the number of unconnected buffers = Source_Array[4]

where:
Tag Name UCB_Set Source_Array Type MESSAGE SINT[8] Description Control tag for the MSG instruction. Source values for the MSG instruction, including the number of unconnected buffers that you want.

14

Publication 1756-PM012B-EN-P - July 2008

Controller Messages

Chapter 1

Convert Between INTs and DINTs

In the Logix5000 controller, use the DINT data type for integers whenever possible. Logix5000 controllers execute more efficiently and use less memory when working with 32-bit integers (DINTs). If your message is to a device that uses 16-bit integers, such as a PLC-5 or SLC 500 controller, and it transfers integers (not REALs), use a buffer of INTs in the message and DINTs throughout the project. This increases the efficiency of your project.
1 2 Buffer of INTs INT_Buffer[0] INT_Buffer[1] INT_Buffer[2] DINTs for use in the project DINT_Array[0] DINT_Array[1] DINT_Array[2]

Read 16-Bit Integers

Data from the device Word 1 Word 2 Word 3

1. The Message (MSG) instruction reads 16-bit integers (INTs) from the device and stores them in a temporary array of INTs. 2. An File Arith/Logical (FAL) instruction converts the INTs to DINTs for use by other instructions in your project.
1 Write 16-Bit Integers DINTs from the project DINT_Array[0] DINT_Array[1] DINT_Array[2] Buffer of INTs INT_Buffer[0] INT_Buffer[1] INT_Buffer[2] 2 Data for the device Word 1 Word 2 Word 3

1. An FAL instruction converts the DINTs from the Logix5000 controller to INTs. 2. The MSG instruction writes the INTs from the temporary array to the device. EXAMPLE Read integer values from a PLC-5 controller

If Condition_1 = 1 And Msg_1.EN = 0 (MSG instruction is not already enabled) then: Read 3 integers from the PLC-5 controller and store them in INT_Buffer (3 INTs)

Publication 1756-PM012B-EN-P - July 2008

15

Chapter 1

Controller Messages

If Msg_1.DN =1 (MSG instruction has read the data.) then Reset the FAL instruction. The FAL instruction sets DINT_Array = INT_Buffer. This converts the values to 32-bit integers (DINTs).

EXAMPLE

Write integer values to a PLC-5 controller

If Condition_2 = 1 then: Reset the FAL instruction. The FAL instruction sets INT_Buffer = DINT_Array. This converts the values to 16-bit integers (INTs).

If Control_2.DN = 1 (FAL instruction has converted the DINTs to INTs) And Msg_2.EN = 0 (MSG instruction is not already enabled) then: Write the integers in INT_Buffer (3 INTs) to the PLC-5 controller

16

Publication 1756-PM012B-EN-P - July 2008

Chapter

Manage Multiple Messages

Introduction

You can use ladder logic to send groups of Message (MSG) instructions in sequence. To be processed, each MSG instruction must enter the message queue. The queue holds 16 MSGs. If more than 16 MSGs are enabled at one time, there may not be room on the queue when a MSG is enabled. If this occurs, the MSG has to wait until there is room on the queue before the controller can process the MSG. On each subsequent scan of the MSG, it checks the queue to see if there is room. The message manager logic lets you control the number of MSGs that are enabled at one time and enable subsequent MSGs in sequence. In this way, MSGs enter and exit the queue in an ordered fashion and do not have to wait for room on the queue to become available.

How to Use this Example Logic

The message manager logic sends three groups of MSGs. To make the example easier to follow, each groups contains only 2 MSGs. In your project, use more MSGs in each group, such as 5. Use as many groups as needed to include all your MSGs. The Msg_Group tag controls the enabling of each MSG. The tag uses the DINT data type. Each bit of the tag corresponds to a group of MSGs. For example, Msg_Group.0 enables and disables the first group of MSGs (group 0).

17Publication 1756-PM012B-EN-P - July 2008

17

Chapter 2

Manage Multiple Messages

Message Manager Logic

Initialize the Logic

If S:FS = 1 (first scan), then initialize the MSGs: Msg_Group = 0, which disables all the MSGs. Msg_Group.0 =1, which enables the first group of MSGs.

Restart the Sequence, If Required


If the MSGs in group 2 (last group) are currently enabled (Msg_Group.2 = 1) And Msg_4 is done or errored And Msg_5 is done or errored Then restart the sequence of MSGs with the first group: Msg_Group.2 = 0. This disables the last group of MSGs. Msg_Group.0 = 1. This enables the first group of MSGs.

18

Publication 1756-PM012B-EN-P - July 2008

Manage Multiple Messages

Chapter 2

Send the First Group of MSGs


If Msg_Group.0 changes from 0 -> 1 then Send Msg_0. Send Msg_1. Because a MSG instruction is a transitional instruction, it executes only when its rung-condition-in changes from false to true.

Enable the Next Group of MSGs


If the MSGs in group 0 are currently enabled (Msg_Group.0 = 1) And Msg_0 is done or errored And Msg_1 is done or errored Then Msg_Group.0 = 0. This disables the current group of MSGs. Msg_Group.1 = 1. This enables the next group of MSGs.

Publication 1756-PM012B-EN-P - July 2008

19

Chapter 2

Manage Multiple Messages

Send the Next Group of MSGs


If Msg_Group.1 changes from 0 -> 1 then Send Msg_2. Send Msg_3.

Enable the Next Group of MSGs


If the MSGs in group 1 are currently enabled (Msg_Group.1 = 1) And Msg_2 is done or errored And Msg_3 is done or errored Then Msg_Group.1 = 0. This disables the current group of MSGs. Msg_Group.2 = 1. This enables the next group of MSGs.

20

Publication 1756-PM012B-EN-P - July 2008

Manage Multiple Messages

Chapter 2

Send the Next Group of MSGs


If Msg_Group.1 changes from 0 -> 1 then Send Msg_2. Send Msg_3.

Publication 1756-PM012B-EN-P - July 2008

21

Chapter 2

Manage Multiple Messages

Notes:

22

Publication 1756-PM012B-EN-P - July 2008

Chapter

Send a Message to Multiple Controllers

Introduction

You can program a single message instruction to communicate with multiple controllers. To reconfigure a MSG instruction during runtime, write new values to the members of the MESSAGE data type. In the MESSAGE data type, the RemoteElement member stores the tag name or address of the data in the controller that receives the message.
If the message Reads data Writes data Then the RemoteElement is the Source Element Destination Element

IMPORTANT

Tag Name

message + message.RemoteElement. + message.RemoteIndex. + message.LocalIndex.


43052

+ message.Channel. + message.Rack.
A B

+ message.Group. + message.Slot. + message.Path.

A. If you use an asterisk [*] to designate the element number of the array, the value in B provides the element number. B. The Index box is only available when you use an asterisk [*] in the Source Element or Destination Element. The instruction substitutes the value of Index for the asterisk [*]. To send a message to multiple controllers:
23Publication 1756-PM012B-EN-P - July 2008 23

Chapter 3

Send a Message to Multiple Controllers

TIP

Set Up the I/O Configuration Define Your Source and Destination Elements Create the MESSAGE_ CONFIGURATION Data Type Create the Configuration Array Get the Size of the Local Array Load the Message Properties for a Controller Configure the Message Step to the Next Controller Restart the Sequence

To copy the above components from a sample project, open the \RSLogix 5000\Projects\Samples folder.

MSG_to_Multiple_Controllers.ACD
43055

Open this project.

Set Up the I/O Configuration

Although not required, we recommend that you add the communication modules and remote controllers to the I/O configuration of the controller. This makes it easier to define the path to each remote controller. For example, once you add the local communication module, the remote communication module, and the destination controller, the Browse button lets you select the destination.
Message Path Browser Path: peer_controller

peer_controller

I/O Configuration

[0] 1756-CNB/x Local_CNB

2 [0] 1756-CNB/x chassis_b


[1] 1756-L55/x peer_controller

24

Publication 1756-PM012B-EN-P - July 2008

Send a Message to Multiple Controllers

Chapter 3

Define Your Source and Destination Elements

In this procedure, an array stores the data that is read from or written to each remote controller. Each element in the array corresponds to a different remote controller. 1. Use the following worksheet to organize the tag names in the local and remote controllers:

Name of the Remote Controller

Tag or Address of the Data in the Remote Controller

Tag in This Controller local_array[0] local_array[1] local_array[2] local_array[3]

2. Create the local_array tag, which stores the data in this controller.
Tag Name local_array Type data_type [length ] where: data_type is the data type of the data that the message sends or receives, such as DINT, REAL, or STRING. length is the number of elements in the local array.

Publication 1756-PM012B-EN-P - July 2008

25

Chapter 3

Send a Message to Multiple Controllers

Create the MESSAGE_ CONFIGURATION Data Type

In this procedure, you create a user-defined data type to store the configuration variables for the message to each controller. Some of the required members of the data type use a string data type. The default STRING data type stores 82 characters. If your paths or remote tag names or addresses use less than 82 characters, you have the option of creating a new string type that stores fewer characters. This lets you conserve memory. To create a new string type, choose File > New Component > String Type If you create a new string type, use it in place of the STRING data type in this procedure. To store the configuration variables for the message to each controller, create the following user-defined data type.
Data Type: MESSAGE_CONFIGURATION
Name Description Members Name Data Type STRING STRING Style Description MESSAGE_CONFIGURATION Configuration properties for a message to another controller

To create a new data type:

+ Controller Your_Project + Tasks + Motion Groups


Trends

Data Types User-Defined

+ Path + RemoteElement

Right-click and choose New Data Type.

Create the Configuration Array


Configuration Array

In this procedure, you store the configuration properties for each controller in an array. Before each execution of the MSG instruction, your logic loads new properties into the instruction. This sends the message to a different controller.
Message Properties first execution of the message

message_config message_config[0] + message_config[0].Path + message_config[0].RemoteElement message_config[1] + message_config[1].Path + message_config[1].RemoteElement


next execution of the message

message + message.Path. + message.RemoteElement.

Message Properties

message + message.Path. + message.RemoteElement.

26

Publication 1756-PM012B-EN-P - July 2008

Send a Message to Multiple Controllers

Chapter 3

1. To store the configuration properties for the message, create the following array:
Tag Name message_config Type MESSAGE_CONFIGURATION[number] Scope any

where: number is the number of controllers to which to send the message. 2. Into the message_config array, enter the path to the first controller that receives the message.
Tag Name Value {} {}
Right-click and choose Go to Message Path Editor.

message_config message_config[0] + message_config[0].Path + message_config[0].RemoteElement

Type the path to the remote controller. or Browse to the remote controller.

Message Path Browser Path: peer_controller I/O Configuration

Publication 1756-PM012B-EN-P - July 2008

27

Chapter 3

Send a Message to Multiple Controllers

3. Into the message_config array, enter the tag name or address of the data in the first controller to receive the message.
Tag Name Value {} {}

message_config message_config[0] + message_config[0].Path + message_config[0].RemoteElement message_config[1] + message_config[1].Path + message_config[1].RemoteElement


...

{}

Type the tag name or address of the data in the other controller.

4. Enter the path and remote element for each additional controller:
Tag Name Value {} {}

message_config message_config[0] + message_config[0].Path + message_config[0].RemoteElement message_config[1] + message_config[1].Path + message_config[1].RemoteElement

{}

28

Publication 1756-PM012B-EN-P - July 2008

Send a Message to Multiple Controllers

Chapter 3

Get the Size of the Local Array

43051

1. The SIZE instruction: counts the number of elements in local_array. counts the number of elements in Dimension 0 of the array. In this case, that is the only dimension. 2. Local_array_length (DINT) stores the size (number of elements) of local_array. This value tells a subsequent rung when the message has been sent to all the controllers and to start with the first controller again.

Load the Message Properties for a Controller


2.

3.

43051

1. The XIO instruction conditions the rung to continuously send the message. 2. The first COP instruction loads the path for the message. The value of index determines which element the instruction loads from message_config. The instruction loads 1 element from message_config.
Publication 1756-PM012B-EN-P - July 2008 29

Chapter 3

Send a Message to Multiple Controllers

3. The second COP instruction loads the tag name or address of the data in the controller that receives the message. The value of index determines which element the instruction loads from message_config. The instruction loads 1 element from message_config.

Configure the Message

Although the logic controls the remote element and path for the message, there is initial configuration.

IMPORTANT

43054

Clear the Cache Connection check box.

30

Publication 1756-PM012B-EN-P - July 2008

Send a Message to Multiple Controllers

Chapter 3

On this tab Configuration

If you want to Read (receive) data from the other controllers

For this item Message Type Source Element Number Of Elements Destination Tag Index

Type or select The read-type that corresponds to the other controllers Tag or address that contains the data in the first controller 1 local_array[*] 0 The write-type that corresponds to other controllers local_array[*] 0 1 Tag or address that contains the data in the first controller Path to the first controller Clear the Cache Connection check box. Since this procedure continuously changes the path of the message, it is more efficient to clear this check box.

Write (send) data to the other controllers

Message Type Source Tag Index Number Of Elements Destination Element

Communication

Path Cache Connections

Publication 1756-PM012B-EN-P - July 2008

31

Chapter 3

Send a Message to Multiple Controllers

Step to the Next Controller


1. 2.

43051

After the MSG instruction sends the message 1. The first ADD instruction increments index. This lets the logic load the configuration properties for the next controller into the MSG instruction. 2. The second ADD instruction increments the LocalIndex member of the MSG instruction. This lets the logic load the value from the next controller into the next element of local_array.

Restart the Sequence


1. 2.

43051

When index equal local_array_length, the controller has sent the message to all the other controllers. 1. The first CLR instruction sets index equal to 0. This lets the logic load the configuration properties for the first controller into the MSG instruction and start the sequence of messages again. 2. The second CLR instruction sets the LocalIndex member of the MSG instruction equal to 0. This lets the logic load the value from the first controller into the first element of local_array.

32

Publication 1756-PM012B-EN-P - July 2008

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States Outside United States 1.440.646.3434 Monday Friday, 8am 5pm EST Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process. Please contact your local Rockwell Automation representative for the return procedure.

Outside United States

Publication 1756-PM012B-EN-P - July 2008 38


Supersedes Publication 1756-PM012A-EN-P - July 2007 Copyright 2008 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.