DOC. No. : 0260-573-PVE-Y-233 (Rev.3) Vendor Doc. No. : HS-09A-C (Rev.

3)

CUSTOMER PROJECT

: NTPC TAMIL NADU ENERGY COMPANY LIMITED : NTECL Power Project (3X500MW) (VALLUR Thermal Power Project-3X500MW)

GUARANTEED TECHNICAL PARTICULARS


FOR

420kV 50kA Gas Insulated Switchgear

20 October, 2009

Digitally signed by TIKARAM Date: 2009.10.26 09:34:37 GMT+05:30 Reason: CAT I Location: NTPCEOC

Page 1

of 34

. GIS Module
1. 2. 3. 4. 5. 6. 7. 8. 9. Name of manufacturer & address Place of manufacture, inspection & testing Manufacturers type / designation Standard applicable Rated voltage (System voltage) System frequency Maximum (continuous) service rated voltage Single phase or three phase design Normal current rating i) ii) iii) iv) 10. 11. Generator Transformer feeder circuit Line feeder circuit Bus coupler circuit Bus bars Amp. Amp. Amp. Amp. kA kV Hz kV 1. 2. 3. 4. 5. 6. 7. 8. 9. i) 2000 ii) 2000 iii) 3150 iv) 3000 10. 11. kA kA kV(peak) kV(peak) kV(peak rms) deg C sec 12. 13. 14. 15. 16. 50 1425 1050 650 40 1 130 Hyosung, Korea Changwon, Korea 420 HGS 50 IEC 62271-203 400 (420) 50 420 Single phase

Rated peak withstand current Short time current rating 1 second rms 3 second rms

12. 13. 14. 15. 16.

Rated Lightning impulse withstand voltage Rated Switching impulse withstand voltage Rated one minute power frequency withstand voltage Maximum temperature rise over 50 deg. ambient Thermal rating of current carrying parts at 420 KV for the rated symmetrical short circuit current

17.

a)

Features adopted for preventing burn through in the various enclosures of SF6 GIS

17. a) Pressure relief device ms b) 500

b)

Time in m sec to withstand an internal flashover without burn through

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 2

of 34

18.

Design pressure of the enclosures for a) b) c) d) e) f) Circuit breakers Disconnectors Surge arresters etc GIS duct VT CT MPa.G MPa.G MPa.G MPa.G MPa.G MPa.G

18. a) 0.803 b) 0.674 c) To be submitted separately d) 0.674 e) To be submitted separately f) 0.674 19. a) 5~6 / Bay b) 5~6 / Bay c) 5~6 / Bay %/year kg 20. a) 0.5 max b) Depend on layout

19.

No of gas compartments a) b) c) Each line bay Each Generator bay Bus coupler bay Average leakage rate of SF6 gas Quantity of SF6 gas required to completely charge the 3-pole equipment including any tank storage system c) Quantity of SF6 gas required for largest gas compartment d) Operating pressure Circuit breaker Others CT VT Disconnector SA bar MPa.G MPa.G MPa.G MPa.G MPa.G MPa.G mm kW kg

20.

a) b)

c) 120 for CB compartment

d) 0.6 0.5 0.5 To be submitted separately 0.5 To be submitted separately 21. 14700 22. 2

21. 22.

Creepage distance adopted for GIS/AIS termination Heat generated in K.W. when the complete switchgear is operating at its rated capacity

23.

a) b)

Seismic level for which GIS is designed Noise level in (dB) at distance of (m) i) ii) iii) iv) 0 50 100 150

23. a) 0.3G b) i) 100 ii) 70 iii) 50 iv) 40

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 3

of 34

24.

Type and material of a) b) c) d) e) f) g) Breaker main contact Disconnecting switch contact Grounding switch contact Busbars Internal bus contact Enclosure Terminal pads

24. a) Copper with silver coated b) Copper with silver coated c) Copper with silver coated d) Aluminum e) Copper with silver coated f) Aluminum g) Tinned copper 25. mm mm mm mm a) 516 b) 10 c) 120 d) 6 26. To be filled at site

25.

Dimensions a) b) c) d) Bus enclosure outside diameter Bus enclosure wall thickness Internal bus, outside diameter Internal bus thickness

26.

Whether GIS are dispatched filled with SF6 or required to be filled at site

27. 28.

Capacity of EOT crane in GIS building Type and make of SF6 pipe coupling used

Ton

27.

28. Non return valve (BTX Korea or DILO Germany)

29.

Type and make of mandatory maintenance equipment to be supplied i) ii) iii) iv) v) SF6 gas filling and evacuation plant (portable) SF6 gas filtering, drying, storage and recycling plant Operation analyzer with DCRM KIT SF6 gas leak detector Gas analyzing equipments

29.

i) 3-001-2-R001,DILO Germany ii) B057R01,DILO Germany iii) EGIL, GE Energy iv) 3-033-R002, DILO Germany v) 3-032-R003,DILO Germany 30. Yes/No Yes/No Yes/No a) To be submitted separately b) To be submitted separately (0260-573-PVE-X-237) c) Already submitted during tender stage. d) Yes (As per civil scope) e) Yes (As per GIS Layout and civil scope)

30.

Whether the following are enclosed a) b) c) Type test reports Operation manual for equipments Leaflets & literature bringing out salient features of equipment offered d) e) The details of control room building The details of GIS building Yes/No Yes/No

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 4

of 34

31.

Details of equipments and procedure for conducting site test (including power frequency. test) of the bay module as per IEC

31. To be submitted separately It will be included in IOM manual. (Refer to 260-573-PVE-X-237) kg 32. 12000 (CB)

32.

Weight of the heaviest piece of equipment to be handled during installation on site.

33.

SF6 GAS a. Name of manufacturer & address

33. a. Allied Signal, USA / Solvay, Germany

b. 34.

Standard applicable Yes/No

b. IEC 60376 34. No (Same compartment with BUS disconnector and earthing switch) Yes/No 35. Yes

Whether the common point of bus disconnectors alongwith Earth Switch has been brought out in a separate compartment

35.

Whether provision exists for extension busbars on both ends

36.

Details of arrangement provided to account for thermal expansion for busbars enclosed

Yes/No

36. Yes (Refer to layout drawing)

37.

Details of earthing arrangement adopted for the GIS enclosed

Yes/No

37. Refer to already approved Foundation Drawing. (Dwg. No. 0260-573-PVE-F-204)

38.

Whether layout plan sections of each bay/equipment of GIS/AIS indicating the complete arrangement enclosed

Yes/No

38. Refer to already submitted Layout drawing. (Dwg, No. 0260-573-PVE-F-205)

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 5

of 34

. EQUIPMENTS INCLUDED IN GIS


A. Circuit Breaker 1. Name plate data a. b. Manufacturers name Type / designation 1. a. b. Hyosung, Korea Puffer, Dead Tank / 420 HCB 50 c. d. e. f. Standard applicable Rated frequency Rated voltage Rated current i) ii) g. h. i. Under normal condition Under site condition kA A kA A Hz kV c. d. e. f. i) 2000 / 3150 ii) 2000 / 3150 g. h. i. 3 C2-M1 1 IEC 62271-100 50 420

Number of poles per unit Class (indoors) Number of interrupting chambers per pole (No of breaks per pole)

j. k. l.

Whether 3 pole or single pole design Maximum Operating Voltage for guaranteed Breaking Capacity Duty cycle as per IEC M1/M2&C1/C2 kV Vdc

j.

Single phase

k. 242 l. M1-C2

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 6

of 34

. GUARANTEED RATINGS
A) Circuit Breaker 1. Making & Breaking a) Breaking Capacity Rated short circuit breaking Current KA(rms) Symmetrical component at highest system voltage DC Component (%) Asymmetrical breaking current at highest system voltage b) Rated breaking MVA (Symmetrical) Breaking time kA(rms) secs b) kA kA(rms) secs 2. Vdc Vdc 3. A kA kA kA kA (peak) 4. a) kV rms kV rms i) ii) 650 815 2000 / 3150 50 50 65.6 130 242 154 130 50 0.01 50 0.04 % kA 60 65.6 kA kA 1. a) 50 50

Making Capacity Rated making current Rated making MVA symmetrical Making time

2.

Operating voltages of closing/opening coil Maximum operating voltage Minimum operating voltage

3.

Current ratings Rated continuous current at 27 ambient temp. Rated interrupting current for 1s. Rated symmetrical interrupting current Rated asymmetrical interrupting current Rated short circuit making current

4.

Rated Insulation level a) One minute dry power frequency withstand voltage i) ii) Between live terminal and ground (kV rms) Between terminals with breaker contacts open (kV rms)

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 7

of 34

b)

1.2/50 micro second impulse withstand test voltage i) ii) Between live terminal and ground (kV peak) Between terminals with breaker contacts open (kV peak) kVp kVp

b) i) 1425 ii) 1425(+240)

c)

250/2500 micro second impulse switching surge withstand test voltage i) ii) Between live terminal and ground (kV peak) Between terminals with breaker contacts open (kV peak) kVp kVp

c)

i) 1050 ii) 900(+345)

d)

Line to ground power frequency withstand voltage at gas pressure equivalent to atmospheric pressure

kV

d) 420/ 3

e)

Minimum allowable moisture content in interrupting medium

ppm/vol.

e) 300

f)

Maximum total break time for any current upto rated breaking current (ms) i) ii) For Test duties 2,3 & 4 at rated values For other duties at limiting conditions of voltage and pressure ms ms

f)

i) 38 ii) 42

g) h)

Closing time Minimum opening time under any condition with limiting voltage and pressure (ms)

ms ms

g) Max.150 h) 15

i)

Maximum opening time under any condition with limiting voltage and pressure (ms)

ms

i) 18

j) 5.

First pole to clear factor

j) 1.3 5.

Maximum temperature rise above ambient at rated load and voltage for Contacts Hottest part K K

34 34 6.

6.

Operating data Rated operating duty cycle a) b) Line Breakers Generator Transformers, & Bus Coupler Breakers

a) O-0.3s-CO-3min-CO b)O-0.3s-CO(-3min-CO) * ( ) shall be related with system operation.

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 8

of 34

Reclosing duty cycle (Line Breakers) Permissible tripping delay Maximum arc duration at a) b) c) d) 10% rated breaking current 30% 60% do do ms ms ms ms ms ms sec

O-0.3s-CO-3min-CO 1

a) 17 b) 15.7 c) 20.7 d) 24 105

100% do

Closing time Total breaking time at a) b) c) d) e) 10% rated breaking current 30% 60% do do

ms ms ms ms

a) 34.3 b) 33.4 c) 38.7 d) 42.1 e) 42.1

100% do Arc duration from separation of arc at contact to instant of arc extinction for full rated interrupting capacity.

Longest time to interrupt current less than 25% of rated symmetrical short circuit current from energizing trip circuit

ms

40

Minimum time from arc extinction to contact remake for auto reclosing.

ms

80

Minimum dead time for a) b) 3 phase reclosing 1 phase reclosing ms ms ms a) 72 b) 72 N/A

Maximum difference of time at opening of series contacts within one pole

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 9

of 34

Maximum difference of time at opening between phases

ms

3.3

Maximum difference of time at closing between phases

ms

Details of the curve enclosed for maximum opening time vs. 3 phase fault current

N/A

Number of interruptions before scheduled maintenance is required

Every 10 in rated 40kA Every 30 operation in rated 25kA Every 100 operation in rated 15kA Every 2000 operation in rated currents 2000

Number of mechanical operations before scheduled maintenance is required

Number of interruptions at rated S.C. current with associated TRV without changing any parts.

10

Description and frequency of scheduled maintenance required

Recovery voltage rate of rise at a) Rated symmetrical interrupting current kV/ms kV/ s b) 60 percent of rated symmetrical interrupting current c) 30 percent of rated symmetrical interrupting current d) 10 percent of rated symmetrical interrupting current data for Restrike voltage kV/ms kV/ s kV/ms kV/ s kV/ms kV/ s

- Ordinary Inspection : Either every 500 operation or 3 years Conduct maintenance and inspection by utilizing service interruption without discharging SF6 gas - Detail inspection : Either every 2000 operation or 6 years Conduct maintenance and inspection discharging SF6 gas As per IEC62271-100 for the belows a) 2.0

b) 3.0

c) 5.0

d) 7.0

Amplitude factor Phase factor Natural frequency

(T100/T60/T30/T10)

1.4/1.5/1.54/0.9X1.7 1.3 Hz kV/ s 50 2/3/5/7 N/A N/A N/A

Rate of rise of restriking voltage (T100/T60/T30/T10) Devices used for controlling RRRV Devices used for uniform voltage distribution Distribution of voltage across breaks

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 10

of 34

Pre-insertion resistor (if applicable) i) ii) Value / pole (Ohms) / with tolerance Minimum and maximum duration of insertion per pole (ms) iii) Thermal rating for the C-1m-0-CO-2m-C-1m-O-CO for terminal fault considering maximum resistance and time setting iii) N/A i) N/A ii) N/A

Recovery voltage distribution between breaks in percent of rated voltage a) b) c) Single line to ground fault Interruption of short lines Switching off an unloaded transformer a) N/A b) N/A c) N/A 7. a) i) Hydraulic ii) Hydraulic b) W W i) 100 ii) 265 7.1 a) N/A b) i) N/A ii) N/A c) i) N/A ii) N/A
3

7.

Operating Mechanism a) Type of operating mechanism for i) ii) b) Closing Opening

Normal power consumption (w) at rated voltage of i) ii) Trip coil Closing coil

7.1

Pneumatic operating mechanism a) b) Rated operating pressure (kg/sq.cm) Rated of pressure for (kg/sq.cm) i) ii) c) Closing Opening

Air Consumption at rated pressure for i) ii) iii) Closing (m ) Opening (m ) Close -Open (m )
3 3

iii) N/A d) N/A e) N/A

d) e)

Pressure drop/metre length of piping Number and Capacity (m ) of breaker local air storage receivers
3

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 11

of 34

f)

No. of close operations for which sufficient air as available in local receiver

f) N/A

g)

Capacity of compressor (m /hr) and working pressure (kg/cm )


2

g) N/A

h)

Maximum time for which compressor can operate continuously (Minutes)

h) N/A

i)

Time to fill i) Air receiver after one C-O operation (Minutes) ii) For making up of losses occuring in 4 hours (Minutes)

i) i) N/A

ii) N/A

j)

Pressure at which compressor i) ii) Starts (kg/cm ) Stops (Kg/cm )


2 2

j) i) N/A ii) N/A k) N/A l) N/A m) N/A

k) l) m)

Material of compressed air piping Inner & outer dia of piping (mm) Whether time totaliser for the compressor provided

n) o)

Safety valve blow off at (kg/cm ) Alarm switch closes (kg/cm ) i) ii) iii) Closing Opening Auto reclose
2

n) N/A o) i) N/A ii) N/A iii) N/A 7.2 kg/cm


2

7.2

Hydraulic operating mechanism a) Rated pressure of oil in operating cylinder (kg/cm ) b) c) d) Limits of pressure (kg/cm ) Quantity of oil (litre) Details of monitoring arrangement for hydraulic pressure
2 2

a) 320

kg/cm

b) 275 (O Lock-out) c) 240 d) Due to pressure switch as indicated pressure settings

L/phase

e)

No. of close-open operation possible after loss of AC supply to drive motor

e) 2 CO

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 12
f) Pressure drop starting from lowest pressure at which motor starts for i) ii) iii) iv) v) g) C-operation O-operation CO-operation O-CO-operation 2CO-operation kg/cm kg/cm kg/cm kg/cm kg/cm
2 2 2 2 2

of 34

f)

i) 5 ii) 15 iii) 20 iv) 35 v) 40 g)

Time required to make up pressure upto loss of nitrogen pressure after i) ii) iii) iv) v) C-operation O-operation CO-operation O-CO-operation 2CO-operation sec sec sec sec sec year & %/year

i) 15 ii) 60 iii) 75 iv) 135 v) 150 h) 30 & 0.25

h)

Life expectancy & guaranteed leakage rate of nitrogen accumulators

7.3

Spring charged mechanism a) Number of close open operations possible after failure of AC supply to motor b) Time required for motor to charge the closing spring (minutes) c) Whether indication of spring charged condition provided in central control cabinet

7.3 a) N/A

b) N/A

c) N/A

8.

Motor Data a) b) c) d) Type Rating at site conditions (kW) Rated voltage (V) Full load current (A) kW V A

8. a) AC Motor b) 1.5 c) 415 d) 2.1

9.

SF6 gas system Normal operating pressure Normal operating density Weight of gas per breaker Lockout pressure bar g/cc kg bar 6 0.0462 (46.2Kg/m3) 65 5.5

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 13

of 34

Alarm pressure Whether breakers work at single pressure or dual pressure

bar

5.7 Single phase

Type of SF6 gas flow (axial or radial) Type of nozzles (single flow or double flow) Compression ratio for puffer action Quantity of compressed gas for puffer action Total volume of SF6 gas required per circuit breaker at operating pressure. kg m
3

Axial Single flow 4 time 4 4.3

10.

Control power requirement Tripping (3poles) current at rated supply voltage (220V DC) Closing (3 poles) current at rated supply voltage (220V DC) Tripping voltage range percent Closing voltage range percent % % A A

10. 19.8

6.3

85~110 70~110 11.

11.

Heaters Continuously current rating Thermostat power rating A A

1.7 1.7 12. i) 100 ii) 70 iii) 50 iv) 40 13. Multi finger type

12.

Noise level in (dB) at distance of (m) i) ii) iii) iv) 0 50 100 150

13.

Interrupters Type of main contacts, arcing contacts & Aux. contacts. Material of main contacts/arcing contacts, silver coated or not Contact pressure kg/sq mm Number of interrupters per pole Breaker length of an interrupter Length of contact travel mm mm kg/sq mm

Copper with silver coated

0.001 1 1255 260

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 14

of 34

14. 15. 16.

Rate of contact travel at tripping Rate of contact travel at closing

m/sec m/sec

15.2 105 14. Trip free

Whether fixed trip or trip free Details of anti pumping device Maximum line charging breaking current with temporary over voltage up to 1.4 p.u. (kA) kA A

15. Hydraulic operating mechanism has structurally anti-pumping capability 16. 600

17. 18.

Rated small capacitive breaking current Rated small inductive breaking current Generator transformer, Line & Bus coupler breakers

A A

17.

600

18. 50 as per requirement (To be submitted the calculation/ Test report separately) 19. Refer to the Annex I

19. 20.

Rated characteristics for short line fault a) Rated transient recovery voltage for terminal faults kV

20. a) 624

b)

Parameters as per IEC

parameters

b) As per table 5 of IEC62271-100

21. 22.

Rated value of phase making current Max. interrupting capacity under phase opposition conditions

kA(rms) kA

21. 22.

50 12.5

23.

Maximum breaking Capacity under Kilimeteric faults and rated TRV characteristic (kA peak)

kA

23.

50

24.

Maximum period between closing of first contact & last contact in a pole (ms)

ms

24.

3.3

25. 26. 27.

Maximum pole discrepancy (ms) Capacity for interrupting in-rush current of transformer Max. over voltage factor of the circuit breaker when switching off a) b) c) d) Unloaded transformer Loaded transformer Open circuited lines Synchronous system

ms A

25. 26. 27.

3.3 (open) 500

a) 1.2 b)1.2 c) 1.2 d) 2 28. mechanically numeric

28.

Details of operation counter

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 15
counter

of 34

29.

a)

Number of auxiliary contacts per pole provided i) ii) iii) NO NC Adjustable Vdc

29. a) i) 20 ii) 20 iii) N/A b) 220 c) A A pC microvolt kg i) 20 ii) 10 30. 31. 32. 5 Below 1000

b) c)

Rated voltage of auxiliary contacts (V) Current capacity of Aux. contacts i) ii) Continuous (Amps) DC breaking with 20 ms time constant (A)

30. 31. 32.

Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV (rms) Maximum impact loading on foundation during breaker operations under fault conditions. i) ii) Closed conditions Open conditions

ton ton

i) 4 ii) +15 33. i) 0.3G ii) 0.3G 34.

33.

Seismic withstand value i) ii) Vertical Horizontal

34.

Tests to be conducted by the supplier at works (whether enclosed) a) b) c) Type tests Routine tests Tests to be conducted at site Yes/No Yes/No Yes/No m kg

a) To be submitted separately b) To be submitted separately through ITP for factory test c) To be submitted separately through ITP for site test 35. 3.4X1.7X4.5 (CB 3phase) 36.

35. 36.

Overall dimensions (LxBxH) Weight of breaker complete with operating mechanism, bushing, frame work, a) b) with SF6 gas without SF6 gas

ton ton

a) 10.2 b) 10 37. Refer to 0260-573-PVE-B-219

37.

Descriptive bulletins and drawings of the circuit breakers giving general details of construction.

38. 39.

Out of phase switching capability of the circuit breaker Comments regarding the suitability of the circuit breaker transformer carrying

kA

38. 39.

12.5 Type tested by C2

for restrike free operation of power full load current.

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 16
40. Guaranteed time difference between the first pole and last pole operation timing. 41. Data on operating Coils (a) (b) 42. No. of trip coils/pole (No.) No. of close coils/pole (No.) 41. (a) 2 (b) 1 ms 40. 3.3

of 34

Details of the standard accessories to be supplied alongwith the breaker

42. GD, Manual handle

43.

No. of the enclosed drg. showing the control scheme of circuit breaker

43. Refer to 0260-573-PVE-L-234

44.

Details of the provision to be made on GIS to reduce H.V. transients to acceptable values.

44. N/A

45.

Guaranteed degraded values of B.I.L. switching surges and 50 Hz rated values during the life of equipment (Test data to support this guarantee to be enclosed by the bidder).

45. 80% of BIL voltage and the rated power Frequency for 30 years life time. 46. Yes/No Yes/No a) Yes b) To be submitted separately (0260-573-PVE-X-237)

46.

Whether the following are enclosed a) b) Type test reports Operation manual for breaker

c)

OGA drawing of breaker

Yes/No

c) To be submitted separately (GIS Dimension drawing)

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 17

of 34

B) Disconnectors / Grounding Switches B-I 1. 2. 3. 4. 5. 6. Disconnector Switches Manufacturers name & address Type & designation Standard applicable and duty M1/M2 Rated Frequency Whether all the 3 poles are gang operated Rated voltage i) ii) 7. Rated Max. permissible kV Hz 1. Hyosung, Korea 2. 420 SDSV, 420 SDSH 3. IEC 62271-102 4. 50 5. 3 poles grouped 6. i) 420 ii) 420 7.

Dielectric with-stand capacity of Completely assembled DS and earth switch a) One minute power frequency withstand test voltage (kV) rms i) against ground (kV peak) b) dry (kV rms) kV rms

a)

i) 650

1.2/50 micro second impulse withstand test voltage i) ii) against ground (kV peak) across open contacts (kV peak) kVp kVp

b) i) 1425 ii) 1425(+240) c)

c)

250/2500 micro second switching surge withstand test voltage (dry) i) ii) against ground (kV peak) across open contacts (kV peak) kVp kVp

i) 1050 ii) 900(+345) d) Below 1000

d)

Radio interference level at 1.1 x Um/ 3 (in micro volts) for frequency between 0.5 MHz to 2.0 MHz

8.

Rated normal current Generator Transformer module Line module Bus coupler module A A A kA A/V

8. 2000 2000 3150 9. 10. 50 1600A at 20V

9. 10.

Rated peak short circuit current Interruption of loop current

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 18

of 34

11.

a)

Rated short time current of DS i) ii) iii) for 1 sec. (kA rms) for 3 sec. (kA rms) Dynamic current kA rms kA rms kA

11. a) i) 50 ii) N/A iii) 130 b) i) <5 ii) <5 c) i) <5 ii) <5 d) <85

b)

Opening time of i) ii) DS (sec) Earth switch (sec)

c)

Closing time of i) ii) DS (sec) Earth switch (sec)

d)

Temperature rise over 50 ambient temperature corresponding to maximum continuous current ()

12. 13. 14. 15. 16. 17.

Rated peak withstand current Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Maximum temperature rise above ambient at rated current Contacts, Hottest part

kA (peak) A kV A kV

12. 13. 14. 15. 16. 17.

130 N/A N/A 0.5 N/A

Deg. C Deg. C

85 68 (enclosure) 18.

18.

Operating Mechanism a) b) c) d) Rated torque of the mechanism Type and rating (kW) of motor Rated voltage of motor Full load current (A) Vdc A kgf.m

a) 1.5 b) DC Motor / 260W

c) 220 d) <5 19.

19.

Interlockings a) Whether mechanical / constructional interlock between DS and Earth switch provided b) Details of electrical interlock enclosed for i) ii) DS Earth Switch Yes/No

a) No

b) Refer to the schematic provided by L&T i) CB: Open, ES: Open ii) DS: Open

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 19

of 34

c)

Arrangement provided to prevent electrical or manual operation unless interlock conditions are satisfied

c) Provision for padlocking both open & close position / Isolating control circuit using device for preventing manual handle from inserting

d) e) f) 20.

Whether interlock coil is continuously rated Rated D.C. control voltage and variation allowed Power consumption (watts) V and %

d) No e) 220 and 80~110 f) Almost zero 20. Vdc Vdc W a) 220 b) 176~242 c) <650 21. Yes/No a) Yes, under supervision

Controls a) b) c) Rated D.C. control voltage (Volts) Limits of voltage Power consumption of control coils (W)

21.

Constructional Features a) Whether position of earth switch can be interchanged at site to either side of pole b) Main contacts i) ii) iii) iv) v) Type of contacts Contact area (cm ) Material of contacts Contact pressure (kg/cm ) Maximum current density under normal current carrying capacity (Amp/cm ) vi) c) Thickness of silver plating microns
2 2 2

b) i) Multi finger cm
2

ii) 28.3 iii) Copper with silver plated

kg A/cm
2

iv) 1.2 / segment v) 1.1 Aluminum 2.0 Copper vi) 30 c) i) 36 ii) 18 iii)18 iv) N/A v) N/A

Auxiliary contacts on Disconnecting switch i) ii) iii) iv) v) vi) vii) viii) Total number NO NC Adjustable Make before break Rated voltage (volts) Rated continuous current (Amps) Rated DC breaking current with 20 ms time constant (A) Vdc A A

vi) 220 vii) 20 viii) 10

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 20

of 34

d)

Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) vii) Total number NO NC Adjustable Rated voltage (volts) Rated continuous current (Amps) Rated DC breaking current with 20 ms time constant (A) Vdc A A

d) i) 22 ii) 11 iii) 11 iv) N/A v) 220 vi) 20 vii) 10

e)

Whether counter balance spring provided for isolator and earth swtich

e) N/A

22.

Design data Type of contacts Contact area Contact pressure Surface treatment and thickness of surface coating / silver electrolytic plating. Overtravel distance after making of contacts Distance between the contacts in the fully open position Current density at the minimum cross section of switch blade Speed of break m/s pC secs. A/mm
2

22. Multi finger cm


2

28.3 1.2 / segment Silver plated by 25 m for main contacts

mm mm

12 160

0.7 (Silver coated copper) 0.1 23. 5 <5

23. 24.

Partial discharge level at 1.1 Un / 3 a) Total operating time of disconnector along with its operating mechanism b) Total operating time of disconnector after the command is given

24. a)

secs.

b)

<5

25.

No. of operations the switch can withstand without any need for inspection

25.

No load 1000 time

26. 27.

Type of mounting No. of poles per phase

26. 27.

Vertical type 1

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 21

of 34

28.

Safety factor taken into account while designing the disconnector.

28.

1.2

29. 30.

Type and material used for arcing contacts, if provided Weight of 3 pole isolating switch with earthing blades without earthing blades kg kg

29. 30.

Tungsten

200 (Include in GIS) N/A 31. Electrical interlock

31.

Type of interlock between main isolator and earthing switch

32.

Details of the type test reports enclosed and the standards as per which these tests have been carried out

32. As per IEC62271-102

33. 34. 35.

Rated maximum time duration of short circuit Rated mechanical terminal load. Rated supply voltage of operating devices and auxiliary circuits.

ms kg Vdc

33. 34. 35.

1000 30 220

36. 37.

Rated pressure of SF6 gas Minimum distance between poles with regard to insulation and forces caused by short circuit currents.

bar MPa.G mm

36. 37.

0.5 160

38.

Tests to be conducted at site Whether the following are enclosed: a) b) Type test reports OGA drawing for disconnecting switches with & without earth switches c) d) e) Operation manual Details of motor operating mechanism Leaflets & literature bringing out salient features of equipment offered f) Whether details of constructional interlock enclosed Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No

38.

a) To be submitted separately b) Refer to the Doc. No. 0260-573-PVE-B-214 c) To be submitted separately (0260-573-PVE-X-237) b) To be submitted separately (0260-573-PVE-X-237) e) Already submitted during tender stage f) No (N/A for constructional interlock)

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 22

of 34

B-II Safety Grounding Switches 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Manufacturers name & address Type / designation Standard applicable Maximum permissible operating voltage Maximum make and carry current for one sec. Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Operating Mechanism a) b) c) d) 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Rated torque of the mechanism Type and rating (KW) of motor Rated voltage of motor Full load current (A) Vdc A Vdc kV kg.f.m kV kA (peak) A kV A kV 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. a) 1.5 b) DC Motor / 260W c) 220 d) <5 11. 12. 13. mm mm 14. 15. 16. m/s pC microvolt 17. 18. 19. 176~242 / 220 6.6 Multi finger 12 160 6t x 100w 0.1 5 Below 1000 Hyosung, Korea 420 SESM IEC 62271-102 420 50 N/A N/A N/A N/A

Operating voltage range & rated voltage Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV (rms) Details of type test reports enclosed and the standards as per which these tests have been carried out

20. As per IEC62271-102

21.

Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) Total number NO NC Adjustable Rated voltage (volts) Rated continues current (Amps) Vdc A

21. i) 22 ii) 11 iii) 11 iv) N/A v) 220 vi) 20

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 23

of 34

22.

Whether the following are enclosed: a) b) Type test reports OGA drawing for disconnecting switches with & without earth switches

22. a) To be submitted separately c) Refer to the Doc. no. 0260-573-PVE-B-215

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 24

of 34

B-III High Speed Fault Making Grounding Switch 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Manufacturers name & address Type/ designation Standard applicable Maximum permissible operating voltage Maximum make and carry current for 1 sec. Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Operating Mechanism a) b) c) d) 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. Rated torque of the mechanism Type and rating (kW) of motor Rated voltage of motor Full load current (A) Vdc A kA A kA s kA s Vdc kV kgfm kV kA(peak) A kV A kV 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. a) 1.5 b) DC Motor / 260W c) 220 d) <5 11. 12. 13. 130 160 130 Hyosung, Korea 420 SESA IEC 62271-102 420 50 160 10 18 20

Making current Induced current switching capability Closing current Closing time Opening current Opening time Operating voltage range, rated voltage Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV Has equipment been type tested and to which standards?

14. <7 with actual contact making time of <200ms 15. 16. 17. 18. 19. 160 <8 176~242 / 220 6.6 Multi finger 12 160 6t x 100w 2.1 5 Below 1000 Yes

mm mm

20. 21. 22.

m/s pC microvolt

23. 24. 25. 26.

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 25

of 34

27.

Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) Total number NO NC Adjustable Rated voltage (volts) Rated continues current (Amps) s Vdc

27. i) 22 ii) 11 iii) 11 iv) N/A v) 220 vi) 20 28. <5

28.

Total operating time of switch alongwith its operating mechanism

29. 30.

Total operating time of switch after the command is given. Operating Mechanism a) b) c) d) Rated torque of the mechanism Type and rating (KW) of motor Rated voltage of motor Full load current (A)

29. 30.

<5

kgfm

a) 1.5 b) DC Motor / 260W

Vdc A

c) 220 d) <5

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 26

of 34

C) CURRENT TRANSFORMERS (Bidder to fill up date separately for each type of CT) 1. 2. 3. 4. 5. 6. Name of manufacturer Type Manufacturers type / designation Standard applicable Mounted inside/outside SF6 Gas enclosure Rated frequency Rated continuous normal current (A) 7. 8. 9. 10. 11. 12. 13. Short time current withstand for 1 sec. (kA) Dynamic current withstand (kA peak) Transformation Ratio Rated primary current Rated secondary current Numbers of cores. Number of secondary turns A A kA kAp 7. 8. 1. Hyosung, Korea 2. Ring type 3. 420 HGS 50 GIS type 4. IEC 60044-1 5. Inside 6. 2000 / 3000 50 130

9. 2000/1000/500:1, 3000/2000/1000:1 10. 2000 / 3000 11. 12. 1 5

13. 2000 / 3000

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 27

of 34

14.

Particulars of for each type of C.T. Refer to the Annex V 1 CORE 2 Rated output (VA) 3 Class of accuracy 4 Accuracy limit 5 Current error at rated primary current (%) 6 CORE Phase displacement at rated primary current (minutes) 7 Composite errors at cement rated accuracy limited it primary current. 10 CORE Secondary winding resistance (ohm) 11 Magnetising current (mA) at knee point voltage Refer to the next page Refer to the next page Refer to the next page 12 Instrument security factor As per IEC standard Refer to the next page Refer to the next page Refer to the next page 8 Knee point voltage (V) (Volts) 9 Secondary limiting voltage Refer to the next page Refer to the next page Refer to the next page As per IEC standard

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 28

of 34

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 29

of 34

15.

One second over current factor & corresponding value of current.

kA

15.

50

16. 17.

Rated dynamic current (peak value) in amps. Rated continuous thermal current temperature rise over ambient.

kA K

16. 17.

130 <60

18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28.

Partial discharge level at 1.1 Un/ 3 Radio Interference voltage at 266 kV (rms) Total weight Magnetisation curves of CT cores Mounting details Overall dimensions Temperature rise over an ambient temp. of 50 () Whether CT characteristic curves enclosed Type Test Reports enclosed OGA drawing enclosed Tests proposed to be conducted at site.

pC micro-volt kg

18. 19.

Below 5 Below 1000

20. As per design 21. To be submitted separately in test report 22. Refer to the Doc. No. 0260-573-PVE-B-216 23. Refer to the Doc. No. 0260-573-PVE-B-216

Yes/No Yes/No Yes/No Yes/No

24.

<85

25. To be submitted separately in test report 26. To be submitted separately 27. Refer to the Doc. No. 0260-573-PVE-B-216 28. To be submitted separately through ITP for site test

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 30

of 34

D) VOLTAGE TRANSFORMERS 1. Name of manufacturer 1. Nissin Japan, Trench Germany or equivalent 2. 3. Type designation Standard applicable 2. 3. IEC 60044-2 Wdg Wdg Wdg 4. 5. 6. 7. 8. 9. Rated primary voltage Rated secondary voltage Rated output per phase Rated burden Rated frequency Standard values of rated voltage factor kV V VA VA Hz 4. 5. 6. 7. 8. 9. 400/ 3 110/ 3 50 50 50 1.5Un-30sec. 1.2Un-continuous 10. 11. Limits of temperature rise One-minute power frequency withstand voltage K kV(rms) 10. 11. <60 <60 <60 110/ 3 50 50 110/ 3 50 50

650-Main circuit 3-Secondary circuit

12. 13.

1.2/50 microsecond lightning impulse withstand voltage 250/2500 micro second impulse switching surge withstand test voltage of capacitor (dry wet) (kV peak)

kV(peak)

12. 13.

1425 1050

14. 15. 16. 17. 18. 19. 20. 21.

Total weight and dimensions Limits of voltage error and phase displacement in % Phase angle error Voltage error Accuracy class at rated burden Voltage factor and rated time Total weight Details of the tests to be conducted by the manufacturer at works i) ii) Type tests Routine tests

kg

14. 15. 16. 17. 18. 19.

900kg/1.2x1.2x1.7m As per IEC60044-2 As per IEC60044-2 As per IEC60044-2

3P / 3P / 0.2
As per IEC60044-2 900

kg

20. 21.

i) ii) 22.

22.

Tests to be conducted at site

As per IEC Standard & Technical Specification As per Technical Specification As per Technical Specification

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 31

of 34

E) SURGE ARRESTORS 1. 2. 3. 4. 5. 6. Manufacturer Type designation Arrestor Class & Type Rated Voltage of Arrestor Normal Maximum continuous operating voltage (MCOV) i) Minimum discharge capability (kj/kV) reffered to rated voltage at minimum of discharge characteristics ii) 7. 8. 9. Line Discharge class, as per IEC kA kVp 9. ii) Class 4 7. 8. Maximum 0.5 microsecond discharge voltage Maximum residual voltage for 8/20 micro sec current wave i) ii) iii) 10. 11. at 50% nominal discharge current (kVp) at 100% nominal discharge current (kVp) at 200% nominal discharge current (kVp) kVp kVp kVp kV(peak) kVrms i) N/A ii) 898 at 10kA iii) 960 at 20kA 10. 790 at 2kA 20 1055 at 20kA Front steepness : 1 micro sec kV kV 1. Toshiba, Japan 2. RVLRF-390KY 3. Gapless (Metal oxide) 4. 5. 390 315

6. i) 8

Maximum discharge current (8/20 microsecond wave)

Maximum switching surge protective voltage a) One minute power frequency (dry) withstand voltage of arrester (kVrms) b) Impulse withstand test voltage of arrester housing with 1.2/50 micro sec wave, (kVp) c) Impulse current withstand i) High current short duration (4/10 micro sec. wave ) kAp ii) Low current short duration (A peak)

11. a) 630

kVp

b) 1425

c) kAp i) 100

Ap pC Microvolts kA

ii) 1200 12. 13. 14. 15. 5 N/A N/A 50kA / Class A

12. 13. 14. 15.

Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 KV (rms) High current short duration test value Short circuit capability & class of pressure relief device

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 32

of 34

16.

I)

Maximum internal ionization at 50 Hz voltage equal to i) ii) 1.05 COV 1.0 COV

16.

i) N/A ii) N/A 17. a) 592 at 3mA

17.

a)

Reference voltage and corresponding reference current of arrester

b)

Maximum internal leakage current at (mA) i) ii) iii) iv) COV 1.1 COV COV at 150 deg. C Reference voltage

b) i) Approx. 1.0mAp at 420kV / 3 X 2 ii) Approx. 1.1mAp at 420kV / 3 X 2 iii) To be submitted separately iv) 592 at 3mA c) Class A 18. kJ/kV 19. A 8

c) 18. 19. 20.

Pressure relief class

Protective level provided by surge arrestor Energy level Details of the type test reports enclosed and the standards as per these tests have been carried out

20. As per IEC60099-4

21.

Whether SF6 Gas insulated

Yes/No

21. Yes

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 33

of 34

F) SUPPORT & BARRIER INSULATORS (Details for each type of insulator used to be indicated separately) Support 1. 2. 3. 4. 5. 6. Manufacturer & address Type of insulators used One-minute power frequency dry withstand test voltage Dry flashover value Wet flashover value 1.2/50 microsecond lightning impulse withstand test voltage 7. 8. 9. Creepage distance Puncture value of insulator in SF6 gas Weight of insulators in the SF6 GIS enclosure. mm kV(rms) kg 7. 8. 9. N/A >650 10 N/A >650 50 kV(rms) kV(rms) kV(rms) kV(peak) 1. 2. 3. 4. 5. 6. Barrier

Hyosung, Korea Epoxy Resin 650 >715 N/A 1425 650 >715 N/A 1425

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

Page 34

of 34

G) GROUNDING CONNECTION a. b. c. Type of conductor Arrangement for connecting conductor to ground Type of painting, if any required to be carried out at end points of ground riser a. Tinned Copper band b. Refer to the Dwg. No. 0260-573-PVE-F-204 /205 c. Paint with black color

H) DESIGN CLEARANCE Minimum insulating clearances at nominal rated SF6 gas pressure and rated voltage/BIL voltage for the following : a) b) Main bus to ground Circuit breaker c) Contact to ground Across the contacts mm mm c) mm mm d) mm mm 120 160 120 160 mm a) 200 b) 100 190

Isolator switches Contact to ground Across the contacts

d)

Safety grounding switches Contact to ground Across the contacts

I) TOLERANCES 1. Tolerance (vertical & horizontal) and at interface of SF6 to Transformer oil bushing 2. Tolerance (vertical & horizontal) and at interface of SF6 to GIS bus Reactor bushing 2. N/A mm 1. 10

Project : VALLUR Thermal Power Project (GIS)

Guaranteed Technical Particulars

TECHNICAL CLARIFICATION
CUSTOMER : NTPC TAMIL NADU ENERGY COMPANY LIMITED PROJECT : NTECL Power Project (3X500MW) (VALLUR Thermal Power Project-3X500MW) Drawing No. : 0260-573-PVE-Y-233 (GUARANTEED TECHNICAL PARTICULARS) Spec. No.& Sl. Specification Requirement Hyosung Clarification No Clause
1 0260-573-PVE-Y- Page 16 of 34 233 41. No. of closing coils/pole(No.) We would like to clarify that No. of closing coil is 1 instead of 2. In revision 2, 2(No. of coil) is typographical errors.

Remark

: 2