. GIS Module
1. 2. 3. 4. 5. 6. 7. 8. 9. Name of manufacturer & address Place of manufacture, inspection & testing Manufacturers type / designation Standard applicable Rated voltage (System voltage) System frequency Maximum (continuous) service rated voltage Single phase or three phase design Normal current rating i) ii) iii) iv) 10. 11. Generator Transformer feeder circuit Line feeder circuit Bus coupler circuit Bus bars Amp. Amp. Amp. Amp. kA kV Hz kV 1. 2. 3. 4. 5. 6. 7. 8. 9. i) 2000 ii) 2000 iii) 3150 iv) 3000 10. 11. kA kA kV(peak) kV(peak) kV(peak rms) deg C sec 12. 13. 14. 15. 16. 50 1425 1050 650 40 1 130 Hyosung, Korea Changwon, Korea 420 HGS 50 IEC 62271-203 400 (420) 50 420 Single phase
Rated peak withstand current Short time current rating 1 second rms 3 second rms
Rated Lightning impulse withstand voltage Rated Switching impulse withstand voltage Rated one minute power frequency withstand voltage Maximum temperature rise over 50 deg. ambient Thermal rating of current carrying parts at 420 KV for the rated symmetrical short circuit current
17.
a)
Features adopted for preventing burn through in the various enclosures of SF6 GIS
b)
Page 2
of 34
18.
Design pressure of the enclosures for a) b) c) d) e) f) Circuit breakers Disconnectors Surge arresters etc GIS duct VT CT MPa.G MPa.G MPa.G MPa.G MPa.G MPa.G
18. a) 0.803 b) 0.674 c) To be submitted separately d) 0.674 e) To be submitted separately f) 0.674 19. a) 5~6 / Bay b) 5~6 / Bay c) 5~6 / Bay %/year kg 20. a) 0.5 max b) Depend on layout
19.
No of gas compartments a) b) c) Each line bay Each Generator bay Bus coupler bay Average leakage rate of SF6 gas Quantity of SF6 gas required to completely charge the 3-pole equipment including any tank storage system c) Quantity of SF6 gas required for largest gas compartment d) Operating pressure Circuit breaker Others CT VT Disconnector SA bar MPa.G MPa.G MPa.G MPa.G MPa.G MPa.G mm kW kg
20.
a) b)
d) 0.6 0.5 0.5 To be submitted separately 0.5 To be submitted separately 21. 14700 22. 2
21. 22.
Creepage distance adopted for GIS/AIS termination Heat generated in K.W. when the complete switchgear is operating at its rated capacity
23.
a) b)
Seismic level for which GIS is designed Noise level in (dB) at distance of (m) i) ii) iii) iv) 0 50 100 150
Page 3
of 34
24.
Type and material of a) b) c) d) e) f) g) Breaker main contact Disconnecting switch contact Grounding switch contact Busbars Internal bus contact Enclosure Terminal pads
24. a) Copper with silver coated b) Copper with silver coated c) Copper with silver coated d) Aluminum e) Copper with silver coated f) Aluminum g) Tinned copper 25. mm mm mm mm a) 516 b) 10 c) 120 d) 6 26. To be filled at site
25.
Dimensions a) b) c) d) Bus enclosure outside diameter Bus enclosure wall thickness Internal bus, outside diameter Internal bus thickness
26.
Whether GIS are dispatched filled with SF6 or required to be filled at site
27. 28.
Capacity of EOT crane in GIS building Type and make of SF6 pipe coupling used
Ton
27.
29.
Type and make of mandatory maintenance equipment to be supplied i) ii) iii) iv) v) SF6 gas filling and evacuation plant (portable) SF6 gas filtering, drying, storage and recycling plant Operation analyzer with DCRM KIT SF6 gas leak detector Gas analyzing equipments
29.
i) 3-001-2-R001,DILO Germany ii) B057R01,DILO Germany iii) EGIL, GE Energy iv) 3-033-R002, DILO Germany v) 3-032-R003,DILO Germany 30. Yes/No Yes/No Yes/No a) To be submitted separately b) To be submitted separately (0260-573-PVE-X-237) c) Already submitted during tender stage. d) Yes (As per civil scope) e) Yes (As per GIS Layout and civil scope)
30.
Whether the following are enclosed a) b) c) Type test reports Operation manual for equipments Leaflets & literature bringing out salient features of equipment offered d) e) The details of control room building The details of GIS building Yes/No Yes/No
Page 4
of 34
31.
Details of equipments and procedure for conducting site test (including power frequency. test) of the bay module as per IEC
31. To be submitted separately It will be included in IOM manual. (Refer to 260-573-PVE-X-237) kg 32. 12000 (CB)
32.
33.
b. 34.
b. IEC 60376 34. No (Same compartment with BUS disconnector and earthing switch) Yes/No 35. Yes
Whether the common point of bus disconnectors alongwith Earth Switch has been brought out in a separate compartment
35.
36.
Details of arrangement provided to account for thermal expansion for busbars enclosed
Yes/No
37.
Yes/No
38.
Whether layout plan sections of each bay/equipment of GIS/AIS indicating the complete arrangement enclosed
Yes/No
Page 5
of 34
Number of poles per unit Class (indoors) Number of interrupting chambers per pole (No of breaks per pole)
j. k. l.
Whether 3 pole or single pole design Maximum Operating Voltage for guaranteed Breaking Capacity Duty cycle as per IEC M1/M2&C1/C2 kV Vdc
j.
Single phase
k. 242 l. M1-C2
Page 6
of 34
. GUARANTEED RATINGS
A) Circuit Breaker 1. Making & Breaking a) Breaking Capacity Rated short circuit breaking Current KA(rms) Symmetrical component at highest system voltage DC Component (%) Asymmetrical breaking current at highest system voltage b) Rated breaking MVA (Symmetrical) Breaking time kA(rms) secs b) kA kA(rms) secs 2. Vdc Vdc 3. A kA kA kA kA (peak) 4. a) kV rms kV rms i) ii) 650 815 2000 / 3150 50 50 65.6 130 242 154 130 50 0.01 50 0.04 % kA 60 65.6 kA kA 1. a) 50 50
Making Capacity Rated making current Rated making MVA symmetrical Making time
2.
Operating voltages of closing/opening coil Maximum operating voltage Minimum operating voltage
3.
Current ratings Rated continuous current at 27 ambient temp. Rated interrupting current for 1s. Rated symmetrical interrupting current Rated asymmetrical interrupting current Rated short circuit making current
4.
Rated Insulation level a) One minute dry power frequency withstand voltage i) ii) Between live terminal and ground (kV rms) Between terminals with breaker contacts open (kV rms)
Page 7
of 34
b)
1.2/50 micro second impulse withstand test voltage i) ii) Between live terminal and ground (kV peak) Between terminals with breaker contacts open (kV peak) kVp kVp
c)
250/2500 micro second impulse switching surge withstand test voltage i) ii) Between live terminal and ground (kV peak) Between terminals with breaker contacts open (kV peak) kVp kVp
c)
d)
Line to ground power frequency withstand voltage at gas pressure equivalent to atmospheric pressure
kV
d) 420/ 3
e)
ppm/vol.
e) 300
f)
Maximum total break time for any current upto rated breaking current (ms) i) ii) For Test duties 2,3 & 4 at rated values For other duties at limiting conditions of voltage and pressure ms ms
f)
i) 38 ii) 42
g) h)
Closing time Minimum opening time under any condition with limiting voltage and pressure (ms)
ms ms
g) Max.150 h) 15
i)
Maximum opening time under any condition with limiting voltage and pressure (ms)
ms
i) 18
j) 5.
j) 1.3 5.
Maximum temperature rise above ambient at rated load and voltage for Contacts Hottest part K K
34 34 6.
6.
Operating data Rated operating duty cycle a) b) Line Breakers Generator Transformers, & Bus Coupler Breakers
Page 8
of 34
Reclosing duty cycle (Line Breakers) Permissible tripping delay Maximum arc duration at a) b) c) d) 10% rated breaking current 30% 60% do do ms ms ms ms ms ms sec
O-0.3s-CO-3min-CO 1
100% do
Closing time Total breaking time at a) b) c) d) e) 10% rated breaking current 30% 60% do do
ms ms ms ms
100% do Arc duration from separation of arc at contact to instant of arc extinction for full rated interrupting capacity.
Longest time to interrupt current less than 25% of rated symmetrical short circuit current from energizing trip circuit
ms
40
Minimum time from arc extinction to contact remake for auto reclosing.
ms
80
Page 9
of 34
ms
3.3
ms
Details of the curve enclosed for maximum opening time vs. 3 phase fault current
N/A
Every 10 in rated 40kA Every 30 operation in rated 25kA Every 100 operation in rated 15kA Every 2000 operation in rated currents 2000
Number of interruptions at rated S.C. current with associated TRV without changing any parts.
10
Recovery voltage rate of rise at a) Rated symmetrical interrupting current kV/ms kV/ s b) 60 percent of rated symmetrical interrupting current c) 30 percent of rated symmetrical interrupting current d) 10 percent of rated symmetrical interrupting current data for Restrike voltage kV/ms kV/ s kV/ms kV/ s kV/ms kV/ s
- Ordinary Inspection : Either every 500 operation or 3 years Conduct maintenance and inspection by utilizing service interruption without discharging SF6 gas - Detail inspection : Either every 2000 operation or 6 years Conduct maintenance and inspection discharging SF6 gas As per IEC62271-100 for the belows a) 2.0
b) 3.0
c) 5.0
d) 7.0
(T100/T60/T30/T10)
Rate of rise of restriking voltage (T100/T60/T30/T10) Devices used for controlling RRRV Devices used for uniform voltage distribution Distribution of voltage across breaks
Page 10
of 34
Pre-insertion resistor (if applicable) i) ii) Value / pole (Ohms) / with tolerance Minimum and maximum duration of insertion per pole (ms) iii) Thermal rating for the C-1m-0-CO-2m-C-1m-O-CO for terminal fault considering maximum resistance and time setting iii) N/A i) N/A ii) N/A
Recovery voltage distribution between breaks in percent of rated voltage a) b) c) Single line to ground fault Interruption of short lines Switching off an unloaded transformer a) N/A b) N/A c) N/A 7. a) i) Hydraulic ii) Hydraulic b) W W i) 100 ii) 265 7.1 a) N/A b) i) N/A ii) N/A c) i) N/A ii) N/A
3
7.
Normal power consumption (w) at rated voltage of i) ii) Trip coil Closing coil
7.1
Pneumatic operating mechanism a) b) Rated operating pressure (kg/sq.cm) Rated of pressure for (kg/sq.cm) i) ii) c) Closing Opening
Air Consumption at rated pressure for i) ii) iii) Closing (m ) Opening (m ) Close -Open (m )
3 3
d) e)
Pressure drop/metre length of piping Number and Capacity (m ) of breaker local air storage receivers
3
Page 11
of 34
f)
No. of close operations for which sufficient air as available in local receiver
f) N/A
g)
g) N/A
h)
h) N/A
i)
Time to fill i) Air receiver after one C-O operation (Minutes) ii) For making up of losses occuring in 4 hours (Minutes)
i) i) N/A
ii) N/A
j)
k) l) m)
Material of compressed air piping Inner & outer dia of piping (mm) Whether time totaliser for the compressor provided
n) o)
Safety valve blow off at (kg/cm ) Alarm switch closes (kg/cm ) i) ii) iii) Closing Opening Auto reclose
2
7.2
Hydraulic operating mechanism a) Rated pressure of oil in operating cylinder (kg/cm ) b) c) d) Limits of pressure (kg/cm ) Quantity of oil (litre) Details of monitoring arrangement for hydraulic pressure
2 2
a) 320
kg/cm
L/phase
e)
e) 2 CO
Page 12
f) Pressure drop starting from lowest pressure at which motor starts for i) ii) iii) iv) v) g) C-operation O-operation CO-operation O-CO-operation 2CO-operation kg/cm kg/cm kg/cm kg/cm kg/cm
2 2 2 2 2
of 34
f)
Time required to make up pressure upto loss of nitrogen pressure after i) ii) iii) iv) v) C-operation O-operation CO-operation O-CO-operation 2CO-operation sec sec sec sec sec year & %/year
h)
7.3
Spring charged mechanism a) Number of close open operations possible after failure of AC supply to motor b) Time required for motor to charge the closing spring (minutes) c) Whether indication of spring charged condition provided in central control cabinet
7.3 a) N/A
b) N/A
c) N/A
8.
Motor Data a) b) c) d) Type Rating at site conditions (kW) Rated voltage (V) Full load current (A) kW V A
9.
SF6 gas system Normal operating pressure Normal operating density Weight of gas per breaker Lockout pressure bar g/cc kg bar 6 0.0462 (46.2Kg/m3) 65 5.5
Page 13
of 34
bar
Type of SF6 gas flow (axial or radial) Type of nozzles (single flow or double flow) Compression ratio for puffer action Quantity of compressed gas for puffer action Total volume of SF6 gas required per circuit breaker at operating pressure. kg m
3
10.
Control power requirement Tripping (3poles) current at rated supply voltage (220V DC) Closing (3 poles) current at rated supply voltage (220V DC) Tripping voltage range percent Closing voltage range percent % % A A
10. 19.8
6.3
11.
1.7 1.7 12. i) 100 ii) 70 iii) 50 iv) 40 13. Multi finger type
12.
Noise level in (dB) at distance of (m) i) ii) iii) iv) 0 50 100 150
13.
Interrupters Type of main contacts, arcing contacts & Aux. contacts. Material of main contacts/arcing contacts, silver coated or not Contact pressure kg/sq mm Number of interrupters per pole Breaker length of an interrupter Length of contact travel mm mm kg/sq mm
Page 14
of 34
m/sec m/sec
Whether fixed trip or trip free Details of anti pumping device Maximum line charging breaking current with temporary over voltage up to 1.4 p.u. (kA) kA A
15. Hydraulic operating mechanism has structurally anti-pumping capability 16. 600
17. 18.
Rated small capacitive breaking current Rated small inductive breaking current Generator transformer, Line & Bus coupler breakers
A A
17.
600
18. 50 as per requirement (To be submitted the calculation/ Test report separately) 19. Refer to the Annex I
19. 20.
Rated characteristics for short line fault a) Rated transient recovery voltage for terminal faults kV
20. a) 624
b)
parameters
21. 22.
Rated value of phase making current Max. interrupting capacity under phase opposition conditions
kA(rms) kA
21. 22.
50 12.5
23.
Maximum breaking Capacity under Kilimeteric faults and rated TRV characteristic (kA peak)
kA
23.
50
24.
Maximum period between closing of first contact & last contact in a pole (ms)
ms
24.
3.3
Maximum pole discrepancy (ms) Capacity for interrupting in-rush current of transformer Max. over voltage factor of the circuit breaker when switching off a) b) c) d) Unloaded transformer Loaded transformer Open circuited lines Synchronous system
ms A
28.
Page 15
counter
of 34
29.
a)
Number of auxiliary contacts per pole provided i) ii) iii) NO NC Adjustable Vdc
29. a) i) 20 ii) 20 iii) N/A b) 220 c) A A pC microvolt kg i) 20 ii) 10 30. 31. 32. 5 Below 1000
b) c)
Rated voltage of auxiliary contacts (V) Current capacity of Aux. contacts i) ii) Continuous (Amps) DC breaking with 20 ms time constant (A)
Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV (rms) Maximum impact loading on foundation during breaker operations under fault conditions. i) ii) Closed conditions Open conditions
ton ton
33.
34.
Tests to be conducted by the supplier at works (whether enclosed) a) b) c) Type tests Routine tests Tests to be conducted at site Yes/No Yes/No Yes/No m kg
a) To be submitted separately b) To be submitted separately through ITP for factory test c) To be submitted separately through ITP for site test 35. 3.4X1.7X4.5 (CB 3phase) 36.
35. 36.
Overall dimensions (LxBxH) Weight of breaker complete with operating mechanism, bushing, frame work, a) b) with SF6 gas without SF6 gas
ton ton
37.
Descriptive bulletins and drawings of the circuit breakers giving general details of construction.
38. 39.
Out of phase switching capability of the circuit breaker Comments regarding the suitability of the circuit breaker transformer carrying
kA
38. 39.
Page 16
40. Guaranteed time difference between the first pole and last pole operation timing. 41. Data on operating Coils (a) (b) 42. No. of trip coils/pole (No.) No. of close coils/pole (No.) 41. (a) 2 (b) 1 ms 40. 3.3
of 34
43.
No. of the enclosed drg. showing the control scheme of circuit breaker
44.
Details of the provision to be made on GIS to reduce H.V. transients to acceptable values.
44. N/A
45.
Guaranteed degraded values of B.I.L. switching surges and 50 Hz rated values during the life of equipment (Test data to support this guarantee to be enclosed by the bidder).
45. 80% of BIL voltage and the rated power Frequency for 30 years life time. 46. Yes/No Yes/No a) Yes b) To be submitted separately (0260-573-PVE-X-237)
46.
Whether the following are enclosed a) b) Type test reports Operation manual for breaker
c)
Yes/No
Page 17
of 34
B) Disconnectors / Grounding Switches B-I 1. 2. 3. 4. 5. 6. Disconnector Switches Manufacturers name & address Type & designation Standard applicable and duty M1/M2 Rated Frequency Whether all the 3 poles are gang operated Rated voltage i) ii) 7. Rated Max. permissible kV Hz 1. Hyosung, Korea 2. 420 SDSV, 420 SDSH 3. IEC 62271-102 4. 50 5. 3 poles grouped 6. i) 420 ii) 420 7.
Dielectric with-stand capacity of Completely assembled DS and earth switch a) One minute power frequency withstand test voltage (kV) rms i) against ground (kV peak) b) dry (kV rms) kV rms
a)
i) 650
1.2/50 micro second impulse withstand test voltage i) ii) against ground (kV peak) across open contacts (kV peak) kVp kVp
c)
250/2500 micro second switching surge withstand test voltage (dry) i) ii) against ground (kV peak) across open contacts (kV peak) kVp kVp
d)
Radio interference level at 1.1 x Um/ 3 (in micro volts) for frequency between 0.5 MHz to 2.0 MHz
8.
Rated normal current Generator Transformer module Line module Bus coupler module A A A kA A/V
9. 10.
Page 18
of 34
11.
a)
Rated short time current of DS i) ii) iii) for 1 sec. (kA rms) for 3 sec. (kA rms) Dynamic current kA rms kA rms kA
11. a) i) 50 ii) N/A iii) 130 b) i) <5 ii) <5 c) i) <5 ii) <5 d) <85
b)
c)
d)
Rated peak withstand current Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Maximum temperature rise above ambient at rated current Contacts, Hottest part
kA (peak) A kV A kV
Deg. C Deg. C
85 68 (enclosure) 18.
18.
Operating Mechanism a) b) c) d) Rated torque of the mechanism Type and rating (kW) of motor Rated voltage of motor Full load current (A) Vdc A kgf.m
19.
Interlockings a) Whether mechanical / constructional interlock between DS and Earth switch provided b) Details of electrical interlock enclosed for i) ii) DS Earth Switch Yes/No
a) No
b) Refer to the schematic provided by L&T i) CB: Open, ES: Open ii) DS: Open
Page 19
of 34
c)
Arrangement provided to prevent electrical or manual operation unless interlock conditions are satisfied
c) Provision for padlocking both open & close position / Isolating control circuit using device for preventing manual handle from inserting
d) e) f) 20.
Whether interlock coil is continuously rated Rated D.C. control voltage and variation allowed Power consumption (watts) V and %
d) No e) 220 and 80~110 f) Almost zero 20. Vdc Vdc W a) 220 b) 176~242 c) <650 21. Yes/No a) Yes, under supervision
Controls a) b) c) Rated D.C. control voltage (Volts) Limits of voltage Power consumption of control coils (W)
21.
Constructional Features a) Whether position of earth switch can be interchanged at site to either side of pole b) Main contacts i) ii) iii) iv) v) Type of contacts Contact area (cm ) Material of contacts Contact pressure (kg/cm ) Maximum current density under normal current carrying capacity (Amp/cm ) vi) c) Thickness of silver plating microns
2 2 2
b) i) Multi finger cm
2
kg A/cm
2
iv) 1.2 / segment v) 1.1 Aluminum 2.0 Copper vi) 30 c) i) 36 ii) 18 iii)18 iv) N/A v) N/A
Auxiliary contacts on Disconnecting switch i) ii) iii) iv) v) vi) vii) viii) Total number NO NC Adjustable Make before break Rated voltage (volts) Rated continuous current (Amps) Rated DC breaking current with 20 ms time constant (A) Vdc A A
Page 20
of 34
d)
Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) vii) Total number NO NC Adjustable Rated voltage (volts) Rated continuous current (Amps) Rated DC breaking current with 20 ms time constant (A) Vdc A A
e)
Whether counter balance spring provided for isolator and earth swtich
e) N/A
22.
Design data Type of contacts Contact area Contact pressure Surface treatment and thickness of surface coating / silver electrolytic plating. Overtravel distance after making of contacts Distance between the contacts in the fully open position Current density at the minimum cross section of switch blade Speed of break m/s pC secs. A/mm
2
mm mm
12 160
23. 24.
Partial discharge level at 1.1 Un / 3 a) Total operating time of disconnector along with its operating mechanism b) Total operating time of disconnector after the command is given
24. a)
secs.
b)
<5
25.
No. of operations the switch can withstand without any need for inspection
25.
26. 27.
26. 27.
Vertical type 1
Page 21
of 34
28.
28.
1.2
29. 30.
Type and material used for arcing contacts, if provided Weight of 3 pole isolating switch with earthing blades without earthing blades kg kg
29. 30.
Tungsten
31.
32.
Details of the type test reports enclosed and the standards as per which these tests have been carried out
Rated maximum time duration of short circuit Rated mechanical terminal load. Rated supply voltage of operating devices and auxiliary circuits.
ms kg Vdc
1000 30 220
36. 37.
Rated pressure of SF6 gas Minimum distance between poles with regard to insulation and forces caused by short circuit currents.
bar MPa.G mm
36. 37.
0.5 160
38.
Tests to be conducted at site Whether the following are enclosed: a) b) Type test reports OGA drawing for disconnecting switches with & without earth switches c) d) e) Operation manual Details of motor operating mechanism Leaflets & literature bringing out salient features of equipment offered f) Whether details of constructional interlock enclosed Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
38.
a) To be submitted separately b) Refer to the Doc. No. 0260-573-PVE-B-214 c) To be submitted separately (0260-573-PVE-X-237) b) To be submitted separately (0260-573-PVE-X-237) e) Already submitted during tender stage f) No (N/A for constructional interlock)
Page 22
of 34
B-II Safety Grounding Switches 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Manufacturers name & address Type / designation Standard applicable Maximum permissible operating voltage Maximum make and carry current for one sec. Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Operating Mechanism a) b) c) d) 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Rated torque of the mechanism Type and rating (KW) of motor Rated voltage of motor Full load current (A) Vdc A Vdc kV kg.f.m kV kA (peak) A kV A kV 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. a) 1.5 b) DC Motor / 260W c) 220 d) <5 11. 12. 13. mm mm 14. 15. 16. m/s pC microvolt 17. 18. 19. 176~242 / 220 6.6 Multi finger 12 160 6t x 100w 0.1 5 Below 1000 Hyosung, Korea 420 SESM IEC 62271-102 420 50 N/A N/A N/A N/A
Operating voltage range & rated voltage Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV (rms) Details of type test reports enclosed and the standards as per which these tests have been carried out
21.
Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) Total number NO NC Adjustable Rated voltage (volts) Rated continues current (Amps) Vdc A
Page 23
of 34
22.
Whether the following are enclosed: a) b) Type test reports OGA drawing for disconnecting switches with & without earth switches
Page 24
of 34
B-III High Speed Fault Making Grounding Switch 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Manufacturers name & address Type/ designation Standard applicable Maximum permissible operating voltage Maximum make and carry current for 1 sec. Rated inductive breaking current TRV caused by breaking/making inductive current Rated capacitive breaking current TRV caused by breaking/making capacitive current Operating Mechanism a) b) c) d) 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. Rated torque of the mechanism Type and rating (kW) of motor Rated voltage of motor Full load current (A) Vdc A kA A kA s kA s Vdc kV kgfm kV kA(peak) A kV A kV 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. a) 1.5 b) DC Motor / 260W c) 220 d) <5 11. 12. 13. 130 160 130 Hyosung, Korea 420 SESA IEC 62271-102 420 50 160 10 18 20
Making current Induced current switching capability Closing current Closing time Opening current Opening time Operating voltage range, rated voltage Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 kV Has equipment been type tested and to which standards?
14. <7 with actual contact making time of <200ms 15. 16. 17. 18. 19. 160 <8 176~242 / 220 6.6 Multi finger 12 160 6t x 100w 2.1 5 Below 1000 Yes
mm mm
m/s pC microvolt
Page 25
of 34
27.
Auxiliary contacts on earth switch i) ii) iii) iv) v) vi) Total number NO NC Adjustable Rated voltage (volts) Rated continues current (Amps) s Vdc
28.
29. 30.
Total operating time of switch after the command is given. Operating Mechanism a) b) c) d) Rated torque of the mechanism Type and rating (KW) of motor Rated voltage of motor Full load current (A)
29. 30.
<5
kgfm
Vdc A
c) 220 d) <5
Page 26
of 34
C) CURRENT TRANSFORMERS (Bidder to fill up date separately for each type of CT) 1. 2. 3. 4. 5. 6. Name of manufacturer Type Manufacturers type / designation Standard applicable Mounted inside/outside SF6 Gas enclosure Rated frequency Rated continuous normal current (A) 7. 8. 9. 10. 11. 12. 13. Short time current withstand for 1 sec. (kA) Dynamic current withstand (kA peak) Transformation Ratio Rated primary current Rated secondary current Numbers of cores. Number of secondary turns A A kA kAp 7. 8. 1. Hyosung, Korea 2. Ring type 3. 420 HGS 50 GIS type 4. IEC 60044-1 5. Inside 6. 2000 / 3000 50 130
Page 27
of 34
14.
Particulars of for each type of C.T. Refer to the Annex V 1 CORE 2 Rated output (VA) 3 Class of accuracy 4 Accuracy limit 5 Current error at rated primary current (%) 6 CORE Phase displacement at rated primary current (minutes) 7 Composite errors at cement rated accuracy limited it primary current. 10 CORE Secondary winding resistance (ohm) 11 Magnetising current (mA) at knee point voltage Refer to the next page Refer to the next page Refer to the next page 12 Instrument security factor As per IEC standard Refer to the next page Refer to the next page Refer to the next page 8 Knee point voltage (V) (Volts) 9 Secondary limiting voltage Refer to the next page Refer to the next page Refer to the next page As per IEC standard
Page 28
of 34
Page 29
of 34
15.
kA
15.
50
16. 17.
Rated dynamic current (peak value) in amps. Rated continuous thermal current temperature rise over ambient.
kA K
16. 17.
130 <60
18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28.
Partial discharge level at 1.1 Un/ 3 Radio Interference voltage at 266 kV (rms) Total weight Magnetisation curves of CT cores Mounting details Overall dimensions Temperature rise over an ambient temp. of 50 () Whether CT characteristic curves enclosed Type Test Reports enclosed OGA drawing enclosed Tests proposed to be conducted at site.
pC micro-volt kg
18. 19.
20. As per design 21. To be submitted separately in test report 22. Refer to the Doc. No. 0260-573-PVE-B-216 23. Refer to the Doc. No. 0260-573-PVE-B-216
24.
<85
25. To be submitted separately in test report 26. To be submitted separately 27. Refer to the Doc. No. 0260-573-PVE-B-216 28. To be submitted separately through ITP for site test
Page 30
of 34
D) VOLTAGE TRANSFORMERS 1. Name of manufacturer 1. Nissin Japan, Trench Germany or equivalent 2. 3. Type designation Standard applicable 2. 3. IEC 60044-2 Wdg Wdg Wdg 4. 5. 6. 7. 8. 9. Rated primary voltage Rated secondary voltage Rated output per phase Rated burden Rated frequency Standard values of rated voltage factor kV V VA VA Hz 4. 5. 6. 7. 8. 9. 400/ 3 110/ 3 50 50 50 1.5Un-30sec. 1.2Un-continuous 10. 11. Limits of temperature rise One-minute power frequency withstand voltage K kV(rms) 10. 11. <60 <60 <60 110/ 3 50 50 110/ 3 50 50
12. 13.
1.2/50 microsecond lightning impulse withstand voltage 250/2500 micro second impulse switching surge withstand test voltage of capacitor (dry wet) (kV peak)
kV(peak)
12. 13.
1425 1050
Total weight and dimensions Limits of voltage error and phase displacement in % Phase angle error Voltage error Accuracy class at rated burden Voltage factor and rated time Total weight Details of the tests to be conducted by the manufacturer at works i) ii) Type tests Routine tests
kg
3P / 3P / 0.2
As per IEC60044-2 900
kg
20. 21.
i) ii) 22.
22.
As per IEC Standard & Technical Specification As per Technical Specification As per Technical Specification
Page 31
of 34
E) SURGE ARRESTORS 1. 2. 3. 4. 5. 6. Manufacturer Type designation Arrestor Class & Type Rated Voltage of Arrestor Normal Maximum continuous operating voltage (MCOV) i) Minimum discharge capability (kj/kV) reffered to rated voltage at minimum of discharge characteristics ii) 7. 8. 9. Line Discharge class, as per IEC kA kVp 9. ii) Class 4 7. 8. Maximum 0.5 microsecond discharge voltage Maximum residual voltage for 8/20 micro sec current wave i) ii) iii) 10. 11. at 50% nominal discharge current (kVp) at 100% nominal discharge current (kVp) at 200% nominal discharge current (kVp) kVp kVp kVp kV(peak) kVrms i) N/A ii) 898 at 10kA iii) 960 at 20kA 10. 790 at 2kA 20 1055 at 20kA Front steepness : 1 micro sec kV kV 1. Toshiba, Japan 2. RVLRF-390KY 3. Gapless (Metal oxide) 4. 5. 390 315
6. i) 8
Maximum switching surge protective voltage a) One minute power frequency (dry) withstand voltage of arrester (kVrms) b) Impulse withstand test voltage of arrester housing with 1.2/50 micro sec wave, (kVp) c) Impulse current withstand i) High current short duration (4/10 micro sec. wave ) kAp ii) Low current short duration (A peak)
11. a) 630
kVp
b) 1425
c) kAp i) 100
Ap pC Microvolts kA
ii) 1200 12. 13. 14. 15. 5 N/A N/A 50kA / Class A
Partial discharge level at 1.1 Un/ 3 Radio interference level at 266 KV (rms) High current short duration test value Short circuit capability & class of pressure relief device
Page 32
of 34
16.
I)
Maximum internal ionization at 50 Hz voltage equal to i) ii) 1.05 COV 1.0 COV
16.
17.
a)
b)
Maximum internal leakage current at (mA) i) ii) iii) iv) COV 1.1 COV COV at 150 deg. C Reference voltage
b) i) Approx. 1.0mAp at 420kV / 3 X 2 ii) Approx. 1.1mAp at 420kV / 3 X 2 iii) To be submitted separately iv) 592 at 3mA c) Class A 18. kJ/kV 19. A 8
Protective level provided by surge arrestor Energy level Details of the type test reports enclosed and the standards as per these tests have been carried out
21.
Yes/No
21. Yes
Page 33
of 34
F) SUPPORT & BARRIER INSULATORS (Details for each type of insulator used to be indicated separately) Support 1. 2. 3. 4. 5. 6. Manufacturer & address Type of insulators used One-minute power frequency dry withstand test voltage Dry flashover value Wet flashover value 1.2/50 microsecond lightning impulse withstand test voltage 7. 8. 9. Creepage distance Puncture value of insulator in SF6 gas Weight of insulators in the SF6 GIS enclosure. mm kV(rms) kg 7. 8. 9. N/A >650 10 N/A >650 50 kV(rms) kV(rms) kV(rms) kV(peak) 1. 2. 3. 4. 5. 6. Barrier
Hyosung, Korea Epoxy Resin 650 >715 N/A 1425 650 >715 N/A 1425
Page 34
of 34
G) GROUNDING CONNECTION a. b. c. Type of conductor Arrangement for connecting conductor to ground Type of painting, if any required to be carried out at end points of ground riser a. Tinned Copper band b. Refer to the Dwg. No. 0260-573-PVE-F-204 /205 c. Paint with black color
H) DESIGN CLEARANCE Minimum insulating clearances at nominal rated SF6 gas pressure and rated voltage/BIL voltage for the following : a) b) Main bus to ground Circuit breaker c) Contact to ground Across the contacts mm mm c) mm mm d) mm mm 120 160 120 160 mm a) 200 b) 100 190
d)
I) TOLERANCES 1. Tolerance (vertical & horizontal) and at interface of SF6 to Transformer oil bushing 2. Tolerance (vertical & horizontal) and at interface of SF6 to GIS bus Reactor bushing 2. N/A mm 1. 10
TECHNICAL CLARIFICATION
CUSTOMER : NTPC TAMIL NADU ENERGY COMPANY LIMITED PROJECT : NTECL Power Project (3X500MW) (VALLUR Thermal Power Project-3X500MW) Drawing No. : 0260-573-PVE-Y-233 (GUARANTEED TECHNICAL PARTICULARS) Spec. No.& Sl. Specification Requirement Hyosung Clarification No Clause
1 0260-573-PVE-Y- Page 16 of 34 233 41. No. of closing coils/pole(No.) We would like to clarify that No. of closing coil is 1 instead of 2. In revision 2, 2(No. of coil) is typographical errors.
Remark
: 2