CONTENT EMISSION STANDARD FUEL : COAL WATER MIXTURE TYPE OF BOILER RETROFIT OF BOILER AIR EMISSION CONTROL SYSTEM CONCLUSION
EMISSION STANDARD
Total Suspended Particulate mg/N.m Sulfur Dioxide (SO2) ppm Oxides of Nitrogen: NOX (as No2) ppm Carbon Monoxide (CO) ppm
Remark:
1. Reference Condition at 1 Atm or 760 mm.Hg at 25C (Dry Basis) with Excess Air at 50% or Excess Oxygen 7% 2. Reference under notification of the Minister of Industry 3. Reference the air emission standards from distribution facilities on February 4, B.E. 2548 (2005)
The Air Emission Standard from Electricity Generation Transmission New Power Plant After January 31, B.E. 2539 (1996)
No. Pollutants Unit Coal 640 450 320 350 120 Type of Fuel Oil Natural Gas 640 450 320 180 120 20 20 20 120 60 Biomass 60 60 60 200 120
1 Sulfur Dioxide (SO2) ppm Power Plant Size < 300 MWe 300-500 MWe > 500 MWe 2 Oxides of Nitrogen: NOX (as No2) ppm 3 Particulates mg/N.m
Remark:
1. Reference Condition at 1 Atm or 760 mm.Hg at 25C (Dry Basis) with Excess Air at 50% or Excess Oxygen 7% 2. Reference under notification of the Minister of Industry 3. Reference the air emission standards from electricity generation transmission or distribution facilities on September 28, B.E 2547 (2004)
Units Standard Values 5.5-9.0 < 2,000 m/cm mg/l < 1,300 mg/l < 20 mg/l < 120 mg/l < 50 mg/l < 100
CWM TECHNOLOGY
Technical Reliability CWM, a new and clean fuel, good fluidity and stability. It can be used an alternative fuel in steam boilers for industrial boilers, such as traveling grate boiler to increase combustion efficiency.
CWM TECHNOLOGY
Specification of Coal Total Moisture Inherent Moisture Ash Volatile Matter Fixed Carbon Gross Calorific Value Total Sulfur Hardgrove Grindability Index Ash Fusion Temperature Deformation Hemispherical Flow 10 2~3 5 39.9 44.1 6,400 0.7 46 1,235 1,305 1,360 %
kcal/kg
C C C
CWM Characteristics Concentration Particle Size Distribution Average Particle Diameter < 75 m < 150 m Viscosity Ash Low Calorific Value
% m m % % mPa.s % kcal/kg
Source : SKG-CONDORKESSEL
PARTIAL RETROFIT
Proposed Retrofit General layout still intact: Heating Surface Area almost same, varies a little Arrangement of Burners: at the original Oil Burners, Capacity of Burners, Heating Surface Area and Force Draught Blast Distribution: complete Combustion, primary & secondary Force Draught Fan Steam Generation: effective Utilizing and Operation After Retrofit: Tear and Wear at Heating Surface Area must be carefully thought over, especially at the Corners, Headers in hot Gas and also wear plate must be improved
1 2 3 4 5 6 7
CWM Preparation: Storage Tank & CWM supply System CWM Burners & Accessories Hearth Cool Ash Bucket, deslaging & dedusting Equipment Precipitator: ESP, Bag Filter, etc. Induced Draught Fan ( IDF ) Electricity & Control System Structure & auxiliary Facilities
Parameter
Remark Load Screw Pump, Unload Screw Pumps, Pull-out Screw Pump, Supply Screw Pumps, Magnetic Flowmeter, CWM Burners, Mechanical Soot Blower, Air Compressor, Dedusting & Deslaging System, Precipitator, IDF Unload Slot Tank, Storage Tank, Stirring Buckets, Slurry Filters, Steel Frame, Platform, Staircase, Exterior Cover Sheet
2 3 4 5
Local Fabrication & Erection Work Material & Labour Cost to Modify Combustion Chamber of Boiler Electricity & Control System Civil & Construction Work
by other
FULL RETROFIT
Proposed Retrofit CWM Preparation: Storage Tank & CWM supply System Arrangement of CWM Burners & Accessories Combustion Chamber Modification: Furnace Volume ( Height or Width ), Convection Surface Area, Analyze Structure of original of Boiler Hearth Cool Ash Bucket, deslaging & dedusting Equipment Precipitator : ESP, Bag Filter, etc. Induced Draught Fan ( IDF ) Electricity & Control System Structure & auxiliary Facilities
Blower & Induced Draught Fan System Dedusting & Deslaging System, Precipitator Flue Gas, Ducting System & Insulation Monitoring & Control System Stack Water Treatment Plant Softener, RO, Demineralization, etc. Deaerator & Feed Water Tank, Feed Water Pumps & Control Valves 10 Electricity System 11 Civil Work by other
3 4 5 6 7 8 9
ELECTROSTATIC PRECIPITATOR
Bag Filter
Source : EEC
Source : EEC
CONCLUSION
Boiler Retrofit concerned with the regulation as follow: Environmental Regulation:SO2,NO2,CO,Particulate,etc. The air emission standard from distribution facilities utilizing coal shall be considered this notification. Ambient Air Standard (1995) Pollution Control Department (PCD) Ministry of Natural Resources and Environment
The air emission standard from distribution facilities on February 4, B.E. 2548 (2005 ) The air emission standard from electricity generation transmission or distribution facilities on September 28, B.E. 2547 ( 2004 ) Department of Industrial Work Ministry of Industry Safety Repair and Modification Hydrostatic Test Safety Technology Bureau Ministry of Industry