The TNUP range comprises many standard sizes of enclosures manufactured in glass bre reinforced polyester to give the best environmental protection. Product range with standard sizes. Ingress protection to meet harsh environment with IP66 as standard. Suitable for demanding environments. Temperature range (-20C to +40C). Cover screws in SS316. Many cable entry options. May be used as a connection box for intrinsically safe circuits. High operational reliability and cost efciency, reduced lifetime maintenance costs. ATEX approved.
Technor as, Dusavikv. 39, P.O. Box 658, NO-4003 Stavanger, Norway Phone: +47 51844100, Fax: +47 51844101, E-mail: mail@technor.no. www.technor.no
General Specications
Material Glass bre reinforced polyester (GRP) IP Rating IP66 according to IEC 529 Temperature -20C +40C (T6) Approvals Standards Ex-Code DNV-2003-OSL-ATEX-0207X Cenelec EN50014, EN50019, EN50020, IEC 60529 EEx e II T6 EEx e[ia] IIC T6 EEx ia IIC T6 II 2 G Black Max. 750V PE bar and/or earth terminals Earth continuity plate/earth tag upon request Plastic or metal, quantities according to table According to table Upon request
Number of terminals
An ignition temperature is the temperature at which a hot surface will cause an ignition to occur in a given atmosphere. Dependent on the type of gas or dust, the maximum temperature that the surface of the terminal box can reach without a spontaneous ignition is known as the T Class. The maximum surface temperature must always be lower than the ignition temperature of the atmosphere in which the junction box is used. The terminal boxes within the TNUP range have been assigned a maximum heat dissipation relating to the ambient temperature and T Class. The TNUP range offers T6 protection: T6 = Maximum 85C (Internal wiring must have a temperature rating of at least 85C) For some applications it may be necessary to have several terminal sizes. The power heat dissipation determines the maximum number of terminals permissible for any size of terminal box, based on a 100% load. The following tables and examples demonstrate how this is solved in the same junction box. Example (TNUP 161609) Terminal/ conductor size (mm2) 1,5 2,5 4
Current (Amps) 10 16 20
Number of terminals 10 (of max 25) 6 (of max 16) 4 (of max 18) Total load
Current (A)
16 7 14 3 8 16 3 9 12 2 6 1
10 48 16 16 32 125 20 25 35 50 63 80 7 19 36 9 20 39 6 15 38 2 12 32 4 14 6
TNUP 404117
1,5 2,5 4
10 16 25 35
10 37 16 12 24 96 20 5 14 28 25 7 15 30 35 4 12 29 50 1 9 24 63 3 11 40 80 4 12 19 100 10 12 125 4
1,5 2,5 4
10 16 25 35
38 13 25 98 5 14 28 7 16 31 4 12 30 1 9 25 3 11 41 4 22 46 5 12 4
Current (A)
Entry Table
Depth 09 Side Width 12 16 36 12 16 25 40 40 A/B M20 4 6 18 17 27 40 A/B M25 3 4 11 11 17 27 A/B M32 2 2 7 7 13 20 A/B M40 1 2 5 4 6 16
The table is guidance for the maximum quantity of glands for installation in 1 face (the Width column in the table) on TNUP junction boxes. The quantity is based upon use of Polyamide glands. Note! Recommended quantity is 2/3 of guided quantity.
Width (cm) Height (cm) Depth (cm) 123 120 91 160 160 92 255 250 120 360 160 92 400 250 120 400 405 165
Applicable EX protection
EEx e Protection for electrical components that do not spark under normal working conditions but where measures are applied to prevent high temperatures and the occurence of arcs and sparks internally. EEx ia Protection for equipment containing intrinsically safe circuits, which are incapable of causing an explosion in the surrounding atmosphere, that is where current and voltage in normal operation would not produce enough spark energy or heat to ignite any potentially explosive gases.
Features
Zone 2 (Category 3)