FireFinder-XLS Wiring Compatibility Guide

INTRODUCTION This wiring guide contains information concerning circuits that leave the FireFinder XLS system enclosure. Table 6 contains specific ratings for each circuit and other data that is useful when planning field wiring. The Wiring Compatibility Matrix covers the requirements when multiple circuits share the same conduit or raceway. In all cases the wiring must comply with all local and national codes. Table 1 shows the allowable resistance to ensure no more than a 1.5dB loss in the wire for speaker circuits. While a 1.5dB loss does not represent a significant loss in sound pressure level, it cannot be used to guarantee acceptable sound pressure in all cases. Table 2 lists the typical resistance for copper wire at 75 degrees Celsius per NFPA 70 Table 8. The stated values are for a single conductor. If a more precise value is desired, contact the manufacturer of your cable and obtain the value for the specific cable being used.
Use of existing wire is allowed (provided it complies with the requirements of this guide) - pending approval of local AHJ. The use of multiple circuits, even of the same type, within the same jacketed cable is not allowed. When existing wire is to be used, it is recommended to conduct a wiring survey to determine the quality of the existing wire - prior to committing to use the wire.

TABLE 1: MAXIMUM SPEAKER ZONE WIRE RESISTANCE FOR -1.5dB LOSS 10W 25V 70.7V 12 94 20W 5.9 47 30W 3.9 32 40W 2.9 23 50W 2.4 19 75W 1.6 13 96W 1.2 9.8 125W 0.9 7.5 150W 0.8 6.3 180W 0.7 5.2

NOTES: 1. All resistances include both wires for Class B or all four wires for Class A. 2. For Bulk amplified zones, subtract the riser resistance from the value in the table. Multiply the remainder by the number of connected zones. This is the maximum resistance for each connected zone. This calculation assumes that each zone supports the same wattage.

TABLE 2: TYPICAL WIRE RESISTANCE AT 75C (167F) FOR 1000 FEET (1 WIRE) 22AWG Ohms 19.6 20AWG 12.3 18AWG 7.77 16AWG 4.89 14AWG 3.07 12AWG 1.93

P/N 315-034786-3

Siemen s Industry , Inc. Siemens Industry, Building Tec hnologies Di vision echnologies Division

Tables 3 through 5 are to be used when designing speaker and NAC circuits with the HCP . When designing speaker circuits use Table 1 to calculate maximum riser loss and Table 4 or 5 to calculate speaker zone loss.

TABLE 3: MAXIMUM ALLOWABLE HCP OUTPUT CIRCUIT LINE RESISTANCE FOR SPECIFIED DC RISER CURRENT AND LINE RESISTANCE MAXIMUM DC RISER C U R R EN T (in Amps) 4 3 2 1 .5 DC RISER RESISTANCE (in Ohms) 0.1 Ohm 2.73 2.80 2.86 2.93 2.96 0.25 Ohm 2.33 2.50 2.67 2.83 2.92 0.5 Ohm 1.67 2.00 2.33 2.67 2.83 0.75 Ohm 1.00 1.50 2.00 2.50 2.75 1 Ohm .33 1.00 1.67 2.33 2.67 1.5 Ohms 1.00 2.00 2.50

MAXIMUM LOOP RESISTANCE FOR EACH HCP ON RISER NOTES: 1. Resistances specified are for all wires. 2. If the total current requirement exceeds 4A, local auxiliary 24 VDC supplies that are UL listed for fire protection signaling use, such as Siemens PAD-3, may be used.

TABLE 4: HCP USED FOR 70.7V RMS OPTION


0
APPROXIMATE SPEAKER ZONE WIRE LOSS IN DECIBELS FOR VARIOUS GAUGE WIRES VERSUS TOTAL SPEAKER ZONE WIRE LENGTH (FEET), WHICH IS TWICE THE WIRE RUN LENGTH.

TABLE 5: HCP USED FOR 25V RMS OPTION


0
APPROXIMATE SPEAKER ZONE WIRE LOSS IN DECIBELS FOR VARIOUS GAUGE WIRES VERSUS TOTAL SPEAKER ZONE WIRE LENGTH (FEET), WHICH IS TWICE THE WIRE RUN LENGTH.

-0.05

-.5
14 A WG

-0.10

-1.0
dB LOSS

dB LOSS

16

AW G

16

AW G

-0.15
SPEAKER LOAD: 25 WATTS AT 70.7V RMS LOCATED AT END OF RUN DOES NOT INCLUDE ANY LOSS IN RISER RUN

18

-1.5
AW G
SPEAKER LOAD: 25 WATTS AT 25V RMS LOCATED AT END OF RUN DOES NOT INCLUDE ANY LOSS IN RISER RUN

18

AW G

-0.20

-2.0

-0.25

-2.5

100

200

700 300 400 500 600 TOTAL SPEAKER ZONE WIRE LENGTH (FEET)

800

900

1000

100

200

700 300 400 500 600 TOTAL SPEAKER ZONE WIRE LENGTH (FEET)

800

900

1000

The following cable was tested during the creation of this wiring guide. This information is provided for reference only. The use of #24 AWG cable is not allowed due to restrictions associated with Power Limited Circuits. Substitute an equivalent #22 AWG cable as needed.

CAT 5e #24awg (4 pair Shielded) CAT 5e #24awg (4 pair Unshielded) THHN #12awg (stranded) Twisted #14awg (FPLR) Twisted #18awg (FPLR) Twisted/Shielded #14awg (FPLR) Twisted/Shielded #18awg (FPLR) THHN #14awg (twisted pair)
Siemens Industry, Inc. Building Technologies Division

Olympic Wire P/N 3378M5-9 Olympic Wire P/N 3078M5U Olympic Wire P/N 12 THHN Olympic Wire P/N 2342L Olympic Wire P/N 2202L Olympic Wire P/N 2893L Olympic Wire P/N 2886L Olympic Wire P/N 14STR THHN-0&2

P/N 315-034786-3

Figures 1 through 3 illustrate how to calculate the total wire resistance that is specified in the MAX. LINE RESISTANCE column of Table 6. These figures apply to all circuits that are classified as Class A, Class B or Class X. For the DLC ONLY, Class B circuits may be T-Tapped.
WIRE 1

DEVICE

DEVICE

EOLR

WIRE 2

TYPICAL CLASS B CIRCUIT


MAXIMUM LINE RESISTANCE SPECIFIED IN TABLE 6 IS THE SUM OF THE LENGTH OF WIRE 1 + WIRE 2.

Figure 1
WIRE 1

WIRE 2

EOLR

DEVICE

DEVICE

WIRE 3

WIRE 4

TYPICAL CLASS A CIRCUIT


MAXIMUM LINE RESISTANCE SPECIFIED IN TABLE 6 IS THE SUM OF THE LENGTH OF WIRE 1 + WIRE 2 + WIRE 3 + WIRE 4.

Figure 2
DEVICE

WIRE 1

WIRE 2

DEVICE

WIRE 1

WIRE 1

WIRE 1

WIRE 1

WIRE 2

WIRE 1

DEVICE

DEVICE

DEVICE

DEVICE

WIRE 2 WIRE 1

WIRE 2 WIRE 2 DEVICE

WIRE 2

WIRE 2

CLASS B DLC LOOP WITH T-TAPS


NOT ALLOWED FOR CLASS A LOOPS. MAXIMUM LINE RESISTANCE SPECIFIED IN TABLE 6 IS THE SUM OF THE LENGTH OF ALL WIRE 1 SEGMENTS + ALL WIRE 2 SEGMENTS.

Figure 3
Siemens Industry, Inc. Building Technologies Division

P/N 315-034786-3

TABLE 6: SPECIFICATIONS AND LIMITATIONS

MODULE

CIRCUIT / BUS NAME

CIRCUIT TYPE

WIRING CLASSES SUPPORTED

TYPE OF WIRE ALLOWED

ACCEPTABLE WIRE GAUGE

FIBER OPTIC CABLE

MAX. CIRCUIT CURRENT DRAW

POWER LIMITED

MAX. LINE RESISTANCE (All Wires)

ALCC

Global Paging Riser

Notification Appliance Circuit/Zone

Class B or Class A

Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

.57A (40W @ 70.7V)

YES

80 Ohms

CDC-4

Conventional Detector Initiating Device Circuit Zone

Class B or Class A

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

175mA / zone

YES

70 Ohms (No Accessories) 40 Ohms (With Accessories)

DNET (Digital Audio) DAC-NET

Signaling Line Circuit

Class B (Style 4) or Class X (Style 7)

Twisted Pair, 12AWG to 22AWG CAT-3 (22AWG) or (FPL/FPLR/FPLP) CAT-5 (22AWG) Shielded wire is allowed CAT-3/CAT-5 with CAT-3 or CAT-5, (22AWG) but the distance is cut in half.

Yes - use DFM/DFM-BRK

NA

YES

22 AWG, 75 Ohms 20 AWG, 47 Ohms 18AWG, 30 Ohms 16AWG, 19 Ohms 14AWG, 12 Ohms 12AWG, 7 Ohms CAT3 (0.6mm), 38 Ohms CAT3 (0.8mm), 21 Ohms CAT5 (0.51mm), 157 Ohms

CAN (Local Network)

Signaling Line Circuit

Class B (Style 4)

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Not supported

NA

YES

15 Ohms

DLC

P2 Detector Loop

Signaling Line Circuit

Class B (Style 4) or Class A (Style 6)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Not supported

375mA

YES

252 Devices, 50 Ohms 200 Devices, 62 Ohms 100 Devices,126 Ohms 0-50 Devices, 250 Ohms

FMT

Telephone Riser

Telephone Riser

Class B or Class A (with FMT-AADPT)

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Not supported

NA

YES

100 Ohms

Steady NAC

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

1.5A

YES

See TABLE 3

HCP (Output)

Telephone Zone

Telephone Zone

Class B

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

35mA

YES

24 Ohms

Speaker Zone 25V, 70V

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

25W(25V) =1A

YES

See TABLES 4 & 5

HTRI -S/-D/-R/-M INPUT

Addressable Control Point

Initiating Device Circuit

Class B or Class A

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

14AWG to 18AWG

Not supported

6mA

YES

NA

HZM

Conventional Detector Initiating Device Circuit Zone

Class B or Class A

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

34mA

YES

35 Ohms

LVM

Remote Microphone / Speaker Circuit

Remote Microphone & Monitor Speaker

Class B

Twisted Shielded Pair

12AWG to 22AWG

Not supported

NA

YES

15 Ohms

HNET (Local Network)

Signaling Line Circuit

Class B (Style 4) or Class X (Style 7)

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Yes - use D2300CPS or D2325CPS

NA

YES

78.4 Ohms (22 AWG)

NIC-C

CAN (Local Network)

Signaling Line Circuit

Class B (Style 4)

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Not supported

NA

YES

15 Ohms

XNET (Peer to Peer Network)

Signaling Line Circuit

Class B (Style 4) or Class X (Style 7)

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Yes - use D2300CPS or D2325CPS

NA

YES

78.4 Ohms (22 AWG)

Siemens Industry, Inc. Building Technologies Division

P/N 315-034786-3

TABLE 6: SPECIFICATIONS AND LIMITATIONS


RATINGS IN THIS GUIDE SUPERSEDE INSTALLATION INSTRUCTION REVISION

MAX. CAPACITANCE LINE TO LINE

END OF LINE DEVICE

MAXIMUM WIRING DISTANCES ( @ 50pF/ft. line to line )

SPECIAL FEATURES

WIRING OUTSIDE THE BUILDING

MODULE

.33uF Line to Line .66uF Line to Earth

12AWG, 6600 feet (Class A, ZAC-40 Feed to Return) (Class B, ZAC-40 to last ALCC) (limited by capacitance) 68K Ohm 18AWG, 5100 feet (Class A, ZAC-40 Feed to Return) (Class B, ZAC-40 to last ALCC) (limited by resistance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

ALCC

NA

50uF @ 50V or 4.7K Ohms

18,000 feet (Feed to Return, 12AWG,Class A, no accessories) (limited by resistance) 2500 feet (18AWG,ClassB,with accessories) (limited by resistance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

5 or lower

CDC-4

.1uF (reference only, see MAXIMUM WIRING DISTANCE column)

Not required

980 feet CAT3 unshielded 490 feet CAT3 shielded 2900 feet CAT5 unshielded 1450 feet CAT5 shielded 1900 feet 12-22AWG Twisted Pair (between DACNET modules) (Class A or B)

Class B requires (2 pairs/4 wires) Class A requires (4 pairs/8 wires)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

8 or lower DAC-NET

.1uF TP .05uF TSP

120 Ohm at each end

2000 feet max. (12AWG) (Class B) (limited by capacitance) SureWire - polarity insensitive loop wiring. T-Tapping allowed (Class B ONLY) PCB Rev 3 and Firmware Rev 05.03.0006 or higher is required to achieve the ratings in this guide.

Not allowed

.5uF line to line, 1uF line to chassis

Not required

10,000 feet (12 AWG) (Class B) 252 Devices installed (limited by capacitance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

10 or lower

DLC

.5uF

10 K Ohms

10,000 feet (12 AWG) (Class B) (limited by capacitance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted. Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

7 or lower

FMT

NA

24K Ohm

See TABLE 3

.125uF

75K Ohm

2500 feet (12AWG)(Class B) (limited by capacitance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

9 or lower

HCP (Output)

NA

24K Ohm

See TABLES 4 & 5

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

.02uF Line to Line .04uF Line to Earth

470 Ohms

200 Feet All AWG (regardless of resistance or capacitance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

HTRI-M 3 or lower HTRI-S/D/R 5 or lower

HTRI -S/-D/-R/-M INPUT

NA

4.7K Ohm

12AWG, 9000 feet (Class A) 18AWG, 2250 feet (Class B) Panel Feed to Panel Return (Class A) Panel to Last Device (Class B) (all limited by resistance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

4 or lower

HZM

.1uF

3.3K Internal to the LVM

2000 feet max. (12AWG) (Class B) (limited by capacitance)

Up to 5 LVMs per LPB

Not Allowed

7 or lower

LVM

.25uF TP .15uF TSP

Not required

2000 feet (regardless of AWG) between nodes (Class A or B)

Short circuit isolation between Nodes. Network repeater built-in

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

.1uF TP .05uF TSP

120 Ohm at each end

2000 feet max. (12AWG) (Class B) (limited by capacitance)

Not allowed

8 or lower

NIC-C

.25uF TP .15uF TSP

Not required

2000 feet (regardless of AWG) between nodes (Class A or B)

Short circuit isolation between Nodes. Network repeater built-in

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

Siemens Industry, Inc. Building Technologies Division

P/N 315-034786-3

TABLE 6: SPECIFICATIONS AND LIMITATIONS CONTINUED

MODULE

CIRCUIT / BUS NAME

CIRCUIT TYPE

WIRING CLASSES SUPPORTED

TYPE OF WIRE ALLOWED

ACCEPTABLE WIRE GAUGE

FIBER OPTIC CABLE

MAX. CIRCUIT CURRENT DRAW

POWER LIMITED

MAX. LINE RESISTANCE (All Wires)

TZC-8B

Telephone Zone

Telephone Zone

Class B

Twisted Pair or Twisted Shielded Pair

12AWG to 22AWG

Not supported

35mA per Zone

YES

100 Ohms

Speaker Zone

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z) Zone can be wired Split/Interleaved/ A/B (2 Class B zones)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

40W(25V) load = 1.6A 20W(25V0 load = 0.8A 10W(25V) load = 0.4A

YES

See TABLE 1

ZAC-40 UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair 40W(25V) load = 1.6A 20W(25V0 load = 0.8A 10W(25V) load = 0.4A

Bulk Amplifier/ Audio Source

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

12AWG to 18AWG

Not supported

YES

See TABLE 1

Speaker Zone

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z) Zone can be wired Split/Interleaved/ A/B (2 Class B zones)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

180W(25V) load = 7.2A 90W(25V) load = 3.6A 45W(25V) load = 1.8A

NO

See TABLE 1

ZAM-180 UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair 180W(25V) load = 7.2A 90W(25V) load = 3.6A 45W(25V) load = 1.8A

Bulk Amplifier/ Audio Source

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

12AWG to 18AWG

Not supported

NO

See TABLE 1

NAC Steady

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

3A per zone

YES

.5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm .5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm .5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm

NAC Coded

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

3A per zone

YES

ZIC-4A UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

Sync Strobe

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

12AWG to 18AWG

Not supported

3A per zone

YES

Speaker Zone 25V, 70V

Notification Appliance Circuit/Zone

Class B (Style Y) or Class A (Style Z)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

96W(25V) = 3.84A

YES

See TABLE 1

NAC Steady

Notification Appliance Circuit/Zone

Class B (Style Y)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

2A per zone

YES

.5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm

NAC Coded

Notification Appliance Circuit/Zone

Class B (Style Y)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

2A per zone

YES

.5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm

ZIC-8B UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair .5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm

Sync Strobe

Notification Appliance Circuit/Zone

Class B (Style Y)

12AWG to 18AWG

Not supported

2A per zone

YES

Speaker Zone 25V, 70V

Notification Appliance Circuit/Zone

Class B (Style Y)

UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair

12AWG to 18AWG

Not supported

25W(25V) = 1A 30W(70V) = 0.43A

YES

See TABLE 1

Siemens Industry, Inc. Building Technologies Division

P/N 315-034786-3

TABLE 6: SPECIFICATIONS AND LIMITATIONS CONTINUED


MAX. CAPACITANCE LINE TO LINE RATINGS IN THIS GUIDE SUPERSEDE INSTALLATION INSTRUCTION REVISION

END OF LINE DEVICE

MAXIMUM WIRING DISTANCES ( @ 50pF/ft. line to line )

SPECIAL FEATURES

WIRING OUTSIDE THE BUILDING

MODULE

.5uF

10K Ohm

10,000 feet (12 AWG) (Class B) (limited by capacitance)

Provides dial and busy tones

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

5 or lower

TZC-8B

NA

68K Ohm

See TABLE 1

Zone is supervised when active can be used for non-emergency use (Convenience page or background music)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted. Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

5 or lower ZAC-40

NA

68K Ohm

See TABLE 1

NA

68K Ohm

See TABLE 1

Zone is supervised when active can be used for non-emergency use (Convenience page or background music)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

6 or lower ZAM-180

NA

68K Ohm

See TABLE 1

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B) (all limited by resistance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B) (all limited by resistance)

Single circuit can sound (3) unique codes- based on logic

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

7 or lower ZIC-4A

NA

24K Ohm

3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B) (all limited by resistance)

All strobe circuits on a given ZIC-4A are synchronized.

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

See TABLE 1

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B) (all limited by resistance)

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B) (all limited by resistance)

Single circuit can sound (3) unique codes- based on logic

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

6 or lower ZIC-8B

NA

24K Ohm

2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B) (all limited by resistance)

All strobe circuits on a given ZIC-8B are synchronized.

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

NA

24K Ohm

See TABLE 1

Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.

Siemens Industry, Inc. Building Technologies Division

P/N 315-034786-3

WIRING COMPATIBILITY MATRIX


KEY A = SINGLE CONDUCTOR THHN or B or C B = TWISTED UNSHIELDED C = TWISTED SHIELDED D = B or C X = DO NOT MIX LVM REMOTE MICROPHONE HCP ZAC-40 25V,70V AUDIO HZM INITIATING CIRCUIT FMT TELEPHONE RISER HCP TELEPHONE ZONE HTRIs INPUT CIRCUIT DLC P2 ( See Note 1 ) HCP SYNC STROBE HCP NAC STEADY DAC-NET DNET DAC-NET CAN R\C (ROW RATING \ COLUMN RATING) CDC-4 ALCC ALCC CDC-4 DAC-NET CAN DAC-NET DNET DLC P2 ( See Note 1 ) FMT TELEPHONE RISER HCP NAC STEADY HCP SYNC STROBE HCP TELEPHONE ZONE HCP ZAC-40 25V,70V AUDIO HTRIs INPUT CIRCUIT HZM INITIATING CIRCUIT LVM REMOTE MICROPHONE LVM REMOTE MONITOR SPEAKER NIC-C CAN NIC-C HNET NIC-C XNET NRC TZC-8B TELEPHONE ZONE ZAC-40 25V,70V AUDIO ZAM-180 25V,70V AUDIO NON POWER LIMITED ZIC-4A/-8B 25V,70V AUDIO ZIC-4A/-8B NAC CODED ZIC-4A/-8B NAC STEADY ( See Note 2 ) ZIC-4A/-8B SYNC STROBE D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D C\D C\A D\A D\A D\A D\A D\A A\A X A\A A\A A\A A\A C\D C\A A\D A\A A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\D D\A D\D D\B A\B C\B C\B D\B D\B D\B D\B D\B A\B X A\B A\B A\B A\B A\D A\A A\D A\B D\D D\A A\A C\A C\A D\A D\A D\A D\A D\A D\D X A\A A\A A\A A\A D\D D\A D\D D\B D\A D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D A\D A\A A\D A\B A\A A\D A\A D\A A\A D\A A\A C\A C\A D\A D\A D\A D\A D\A A\A X A\A A\A A\A A\A A\D A\A A\D A\B A\A A\D A\A D\D D\A D\D D\B D\A D\D D\A D\A A\A A\A D\A A\A D\A A\A C\A C\A D\A D\A D\A D\A D\A A\A X A\A A\A A\A A\A A\D A\A A\D A\B A\A A\D A\A A\A A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D B\D B\A B\D B\B B\A B\D B\A B\A B\D D\D D\A D\D D\B D\A D\D D\A D\A D\D D\A B\A D\D D\C A\A A\A D\A A\A D\A A\A C\C C\C D\A D\A D\A D\A D\C A\A X A\A A\A A\A A\A A\D A\A A\D A\B A\A A\D A\A A\A A\D A\A D\D D\A D\D D\B D\A D\D D\A D\A D\D D\A D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\A A\A D\A B\A A\A D\A A\A A\A D\A A\A D\A A\A C\A C\A D\A D\A D\A D\A D\A A\A X A\A A\A A\A A\A NIC-C CAN LVM REMOTE MONITOR SPEAKER

ZIC-4A/8B NAC STEADY ( See Note 2 ) TZC-8B TELEPHONE ZONE D\C A\C D\C B\C A\C D\C A\C A\C D\C A\C D\C A\C C\C C\C D\C D\C D\C D\C D\C A\C X A\C A\C A\C A\C D\C A\C D\C B\C A\C D\C A\C A\C D\C A\C D\C A\C C\C C\C D\C D\C D\C D\C D\C A\C X A\C A\C A\C A\C D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\D A\D D\D B\D A\D D\D A\D A\D D\D A\D D\D A\D C\D C\D D\D D\D D\D D\D D\D A\D X A\D A\D A\D A\D D\A A\A D\A B\A D\D D\A A\A A\A D\A A\A D\A A\A C\A C\A D\A D\A D\A D\A D\A A\A X A\A A\A A\A A\A ZAC-40 25V,70V AUDIO NIC-C HNET NIC-C XNET NRC

ZIC-4A/8B 25V,70V AUDIO

D\A

D\A

D\A

D\A

A\A

A\A

A\A

A\A

D\A

D\A

D\A

D\A

B\A

B\A

B\A

B\A

A\A

A\A

A\A

A\A

D\A

D\A

D\A

D\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

A\A

A\A

A\A

A\A

C\A

C\A

C\A

C\A

C\A

C\A

C\A

C\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

D\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

A\A

Note 1: DLC PCB Rev 3 & Firmware Revision 05.03.0006 or higher required. Note 2: Use these specifications for 24VDC circuits.

P/N 315-034786-3

A\A

A\A

A\A

A\A

ZIC-4A/8B SYNC STROBE

ZAM-180 25V,70V AUDIO NON POWER LIMITED

ZIC-4A/8B NAC CODED

Das könnte Ihnen auch gefallen