Fig.3 Te relationshi between desulphuriztion tower entrance
temperature of the gas and desulphuriztion rate
P
.0
m
c
b.
b.0
c
.
=
. .0
= 4.
L
L
4.0
o. o0
10 1Z 14 1b
l1ne (h)
FigA Te relationshi between desulphuriztion tower exit
temperature of the gas and desulphuriztion rate
Figure 4 shows the relationship between the
desulphuriztion tower exit temerature of the gas and the
desulphuriztion rate. From the fgure we ca see smoke
from the desulphuriztion towe exit temerature is
invrsely proportional relationship with the
desulphuriztion rate. When the desulphuriztion tower
exit fue gas temerature reahes to 74.1 'c ,the
desulphuriztion rate can reah to 92.9%; exit Flue Gas
Temperature 76.8 'c when the desulphuriztion rate was
only 84.3%. This is due to adiabatic saturation
temerature. I order to ensure the end product of
desulphuriztion as "dry" , exit fue gas temerature
should be higher than its adiabatic saturation temerature,
difference between the two as the adiabatic saturation
temerature. Exit fue gas temerature higer, the geater
the adiabatic saturation temerature is. The fue gas
moisture content is smler, the more difcult to cary out
chemica reactions in the desulphuriztion. Exit fue gas
temerature is lower, the smler the adiabatic saturation
temerature is, the more beneft the desulphuriztion
reaction, but is easy to dip wall corosion.l41. A analysis
of the experimental reord, the best exit fue gas
temerature should be controlled at about 74-75 c. At
this point the desulphuri:tion rate will reach 90%. I ca
also ensure that the premise of desulphuri:tion efciency,
will reduce corosion on the desulphuri:tion tower wall.
2.2 Water spray on the desulphuriztion rate
Z
0
L
L
oo
L
ob
m
o4
t1re (h)
10 1Z 14 1b
1o
m
c
d
L
d
1Z w
=
b0
=
L
=
`
0
4
=
L
40
.J
L
1Z :. =
:. o 11
10 1Z 14 1b
l+re (h)
Fig.6 Te relationshi between desulphuriztion tower exit
temperature of the gas and injected water
We can see from the chart, spray volume 1.13 m3/h
when the exit temerature of the smoke desulphuri:tion
tower was 76.7C; spray volume 1.34 m3/h when the exit
temerature of the smoke desulphuri:tion tower was 74
C According to the foregoing anaysis, the
desulphuri:tion towe exit fue gas temerature rage of
optimum temerature 74-75 C, can be consideed in this
temerature rage, the appropriate amount of water spray
for the 1.17-1.25 m3/h, desulphuri:tion rate ca reah
90% or more, to meet the reuirements of industrial
desulphuri:tion.
2.3 Desulhuriztion tower inlet S02 concentration on the
desulphurition rate
m
L
>
1b00
=
v
100
`7 L
L
1400 d
C
0
C
O 1o00 -
c
P
I2OO
g
o
1100
o !
9
d
=
1000
;
L
m
00 ~05dIuIC8O00w6l 6BID6 bQ00B5l05 t/d:
]
65u I28Onl86 \
L o00 o0
10 1Z 14 1b
m
l1re (h)
Fig.? Te relationshi between desulphuriztion tower entrance
S02 densities and the desulphuriztion rate
Desulphuriztion tower inlet S02 concentration has
geat infuece on the desulphuriztion rate, as shown in
Figure 7. Desulphuriztion tower entrance S02
concentration is 901. 7mg/m3, the desulphuriztion rate
reach to 92.7%; when the entrance of S02 concetration is
1591.4mg/m3, the desulphuriztion rate was 83.2%.
Shows that the higher absortion towe inlet S02
concentration, the difcult to achieve a high
desulphuriztion rate. Te reason is: the higher
concentrations of S02 into the air, the more
desulphuriztion agent addition. Spray volume in the
same situation; have increased the concentration of lime
slur. Slur droplets in the case of the same siz, drying
time is reduced, liquid reaction time is reduced, thus
reducing the efciency of desulphuriztion.
2.4 Te boiler load on the desulphurition rate
1.40
1.35
1.30
U
%
_ 1.25
1.20
C
1.15
1.10
-90% raled |Oad
-80% raled |Oad
-70% raled |Oad
B B B B B 9O
deSu|phur1zal1 On rale(%)
Fig.S Te relationshi between the injected water under diferent
boiler load and the desulphuriztion rate
We can see fom the chart amount of water spray
1.20m3 / h, when 90% of the rated load coresponding to
the desulphuriztion rate was 86.6%;80% of the rated load
coresponding to the desulphuriztion rate was 88.6%;
70% of the rate load coresponding to the
desulphuriztion rate was 89.5%. When the
desulphuriztion rate was 89%, the boiler load is 90% of
spray volume used 1.3m3 / h; boiler loads of 80% of the
water spray was used 1.2m3 / h; boiler loads of 70% of the
water spray was used 115 m3 / h.
With the changes in boiler load, sulfr dioxide
content in fue gas desulphuriztion tower, inlet gas
temerature, water spray and othe factors also changed.
Desulphuriztion tower in the entrance area of the same
circumstances, the boiler load the geater the
concentration of sulfr dioxide in fue gas the more the
coresponding inputs to increase the amount of sorbent. I
the amount of water injected into the same, will result in
solid particles in the towe too many, cut down the drying
time, and not even a good flm fored at the particle
surface is not conducive to desulphuriztion to reduce the
desulphuriztion rate. Desulphuriztion tower inlet gas
197
temerature with the boiler load increases. I the injected
water remains unchanged, will lead to increased boiler
load inlet gas desulphuriztion tower higher temerature,
accelerated the speed of the particle surface evaporation
of water flm, makes the liquid-solid two-phase reaction
time is reduced, resulting in a large number of particulars
that reacted incomletely and reduce the desulphuriztion
rate. To sum up, when sprayed water is unchanged, the
boiler load the bigger the geater the sulfr dioxide in fue
gas, the reuired amount of sorbent to enter the geater,
the highe the desulphuriztion tower inlet gas
temerature, leading to increase the amount of solid
particles, cut the liquid reaction time, reduced
desulphuriztion rate. I you want to maintain a hig
desulphuriztion rate, then as the boiler load increases, the
water spray also will increase.
3. Conclusion
(1) When the boiler load chages, the operating
parameters have taken place, and subsequently affect the
desulphuriztion rate of change. Among them, the
desulphuriztion rate of inlet gas desulphuriztion tower
with the rise of temerature increae, the best rage of
desulphuriztion towe inlet gas temerature is 117 124
'C, the desulphuriztion rate at this temerature ca reach
90%; desulphuriztion rate increased with temerature
desulphuriztion tower rising exports of cigarettes
deceased, the best exit fue gas temerature
desulphuriztion towe range is 74-75 'C g in this
temerature, the appropriate amount of water spray for the
1.17-1.25m / h, the desulphuriztion rate can reach 90%.
(2) When injected water steady, the geater the
boiler load, the more sulfr dioxide in fue gas, the
required amount of sorbent to enter is geater, the highe
inlet gas temerature, the desulphuriztion rate is lower. I
you want to maintain a high desulphuriztion rate of
chage along with the boiler loa, water spray should also
chage with.
References
[1] Gao li-hui,Wu Shao-hua,Ma Chun-yuan,Qin Yu-kun. 3000m3/h
CFB fue desulfrization Pilot Study. Chemical Engineering, 2002,
30 (3) .
[2] Yang Xiao-yuan. The study of CFB-FGD Factor. Environmental
Prtect Science,2001, 12.
[3] Fan Li-ting,Li Hong-ru,Wang Fu-li,He Da-kuo. CFB fue gas
desulfrization system mathematical model. Chinese Society for
Electrical Engneering, 2008,28 (32) : 12-17.
[4] Teng Bin,Gao Xiang,Luo Zhong-yang. Semi-grde water on the
efciency of fue gas desulfrization. Power Prtection ,
2006,22 (3) : 22-25.
[5] Wei En-zong, Cheng Shi-qing,Wang Nz-hua. Semi-dry fue gas
desulfrization experiment and mechanism analysis. Power System
Engineering, 2003, 19 (1) : 49-52.
[6] Zhao Xu-ong, Xiang Guang-ming,Yao Qiang,Ma Chun-yuan,Chen
Chang-he. Dry fue gas desulfrization cycle characteristics of solid
particles and microscopic mecha nism. Chinese Society for Electrical
Engineering, 2006, 01.
[7] He Hong-zhou, Shen Liang-kun,Su Ya-xin. Circulating Fluidized
Bed Combustion Boiler in Fujian desulfrization two-step reaction
model. Chinese Society for Electrical Engineering, 2008, 28 (11) :
6-10.