Sie sind auf Seite 1von 1

SEE DETAILS 1, 3 & 5

12 12

FLOAT FINISH

CUT MESH AROUND SKIRT OPENINGS

50mm x 50mm x 14 GA (2" x 2" x 14 GA) WIRE MESH FURRED OUT 12mm( 1/2 ") FROM SKIRT. SEE DETAIL 4 FIREPROOF TO TOP OF LUGS AND TO BASE RING BETWEEN LUGS NO FIREPROOFING INSIDE LUGS

TYPICAL FIREPROOFING OF COLUMN OR VESSEL SKIRT


1/4 " IN. HEX. NUTS TACK WELD TO SKIRT 300mm ( 1/2 ")C. TO C. BOTHWAYS

PLANT NO.

990
SEE DETAIL 2 14 GAGE STEEL FLASHING CONTINOUS SEAL WELD TO COLUMN 93^C(200^F)PREHEAT BEVEL TOP EDGE OF FIREPROOFING 12( 1/2 ") A CLEARANCE OFF 30mm IS REQUIRED PER SAES-B-006.

INDEX

AC-036915 001 07
DRAWING NUMBER SHT. NO. REV. NO.

NOTES:
1. 2. 3. 4. 5. 6. CONCRETE PER SECTION 7, SAES-B-006. CONCRETE SHALL EITHER BE CAST IN PLACE OR APPLIED BY GUNNITING TO A TOTAL FINISHED TH. OF 50mm(2"). CONCRETE SHALL BE DAMP CURED FOR AT LEAST 7 DAYS. STEEL MEMBERS TO BE FIREPROOFED, SHALL BE PAINTED IN ACCORDANCE WITH SAES-H-101 AND SAES-B-006. ALL DIMENSIONS IN MILLIMETERS UNLESS NOTED OTHERWISE. METRIC DIMENSIONS OF STOCK ITEMS ARE A DIRECT CONVERSION OF CONVENTIONAL UNITS TO METRIC UNITS.

DETAIL 2
AMS NUMBER 10-259-005 -

MATERIAL LEGEND
DESCRIPTION 1/4 " QTY. PER 1SSUE UNIT SQ. FT.-2" THK. 1 PER SQ. FT. -

DETAIL 1
NO VESSEL INSULATION

EA STEEL HEX. NUTS -

50mm x 50mm x 14 GA (2" x 2" x 14 GA) GALV. STL. REINF. MESH. 1.5m x 45.7m ( 5 FT x 150 FT)/ROLL

RO SM

12-157-679

14 GA CARBON STEEL SHEET

DETAIL 3
COLD VESSEL (INSULATED)

DRAWING RESPONSIBILITY:

LOSS PREVENTION STANDARDS COMMITTEE

07

FEB99

EDSD WED ESSD EPE BY JO/EWO

REVISED DETAIL 1 DRAWING DIGITIZED INTO CADD ORIGINAL ORIGINAL ORIGINAL DATABASE WITHOUT CHANGES SIGNED SIGNED SIGNED DESCRIPTION CHKD. CERT. APPD.

BEVEL TOP EDGE OF FIREPROOFING

06

MAY92

REV. DATE NO.

SAUDI ARABIAN OIL COMPANY


DRAWN BY DATE STARTED OPRG. DEPT. APPD FOR CONSTR. JH CHECKED BY DATE COMPLETED ENG. DEPT. SCALE NONE 08-10-60 ORIGINAL SIGNED

16 GA GALV. TIRE WIRES

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

CERTIFIED BY DATE

WIRE MESH

DETAIL 4

DETAIL 5
HOT VESSEL (INSULATED)

DETAILS FIREPROOFING FOR COLUMN AND VESSEL SKIRTS


STD. DWG
PLANT NO. INDEX DRAWING NUMBER

METRIC
SHT. NO. REV. NO.

990
CopyrightSaudi Aramco 2009. All rights reserved.

AC-036915 001 07
Saudi Aramco 2635 ENG. (3/91)

CADD-02

Das könnte Ihnen auch gefallen