Beruflich Dokumente
Kultur Dokumente
12 12
FLOAT FINISH
50mm x 50mm x 14 GA (2" x 2" x 14 GA) WIRE MESH FURRED OUT 12mm( 1/2 ") FROM SKIRT. SEE DETAIL 4 FIREPROOF TO TOP OF LUGS AND TO BASE RING BETWEEN LUGS NO FIREPROOFING INSIDE LUGS
PLANT NO.
990
SEE DETAIL 2 14 GAGE STEEL FLASHING CONTINOUS SEAL WELD TO COLUMN 93^C(200^F)PREHEAT BEVEL TOP EDGE OF FIREPROOFING 12( 1/2 ") A CLEARANCE OFF 30mm IS REQUIRED PER SAES-B-006.
INDEX
AC-036915 001 07
DRAWING NUMBER SHT. NO. REV. NO.
NOTES:
1. 2. 3. 4. 5. 6. CONCRETE PER SECTION 7, SAES-B-006. CONCRETE SHALL EITHER BE CAST IN PLACE OR APPLIED BY GUNNITING TO A TOTAL FINISHED TH. OF 50mm(2"). CONCRETE SHALL BE DAMP CURED FOR AT LEAST 7 DAYS. STEEL MEMBERS TO BE FIREPROOFED, SHALL BE PAINTED IN ACCORDANCE WITH SAES-H-101 AND SAES-B-006. ALL DIMENSIONS IN MILLIMETERS UNLESS NOTED OTHERWISE. METRIC DIMENSIONS OF STOCK ITEMS ARE A DIRECT CONVERSION OF CONVENTIONAL UNITS TO METRIC UNITS.
DETAIL 2
AMS NUMBER 10-259-005 -
MATERIAL LEGEND
DESCRIPTION 1/4 " QTY. PER 1SSUE UNIT SQ. FT.-2" THK. 1 PER SQ. FT. -
DETAIL 1
NO VESSEL INSULATION
50mm x 50mm x 14 GA (2" x 2" x 14 GA) GALV. STL. REINF. MESH. 1.5m x 45.7m ( 5 FT x 150 FT)/ROLL
RO SM
12-157-679
DETAIL 3
COLD VESSEL (INSULATED)
DRAWING RESPONSIBILITY:
07
FEB99
REVISED DETAIL 1 DRAWING DIGITIZED INTO CADD ORIGINAL ORIGINAL ORIGINAL DATABASE WITHOUT CHANGES SIGNED SIGNED SIGNED DESCRIPTION CHKD. CERT. APPD.
06
MAY92
THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED
CERTIFIED BY DATE
WIRE MESH
DETAIL 4
DETAIL 5
HOT VESSEL (INSULATED)
METRIC
SHT. NO. REV. NO.
990
CopyrightSaudi Aramco 2009. All rights reserved.
AC-036915 001 07
Saudi Aramco 2635 ENG. (3/91)
CADD-02